CVS 4150 and 4160 Pressure Controllers: Instruction Manual
CVS 4150 and 4160 Pressure Controllers: Instruction Manual
CVS 4150 and 4160 Pressure Controllers: Instruction Manual
The valve should be positioned on the line so the flow direction indicator corresponds to the direction of the flow of the pipeline. If the body is flanged, the bolts should be tightened up evenly to reduce risk of damage to the valve body and the flange. A good quality thread lubricating compound should be used on all male connections if the body has screwed connections.
Controllers
Inspect the controllers for shipping damage and foreign debris when uncrating.
Valve
Ensure the pipeline is free of welding slag, chips and other debris by blowing out the line prior to installation. It is recommended that a strainer be installed up stream of the valve to protect the valve from foreign debris in the line. CVS recommends a standard three-valve maintenance bypass be installed. This allows isolation of the control valve without shutting down the pipeline system.
Head Office 3900 101 Street Edmonton, Alberta, Canada T6E 0A5 Office: (780) 437-3055 Fax: (780) 436-5461
Calgary Sales Office 205, 2323 32 Avenue NE Calgary, Alberta, Canada T2E 6Z3 Office: (403) 250-1416 Fax: (403) 291-9487
Website: www.cvs-controls.com
E-Mail: [email protected]
Control Line Connectors contd The control pressure line is run from the tapped hole in the side or the back of the case to the main pipeline. Install a lock shield needle valve in the control line to slow down the controlled pressure or to dampen out any pulsations. While the control valve is operational, the needle valve must never be entirely closed. An air vent is provided on all controllers and works well when air is used as the operating medium. When gas is used the vent can be removed, this allows for an additional 1/4 NPT connection for gas to be piped away.
Proportional-Reset Controllers 1. The reset dial should be set to maximum. 2. The air supply should be connected to Bellofram Type 50 filter regulator. 3. Zero the pressure setting dial and proportioned setting dial. 4. There should be no pressure sent to the measuring element. 5. For direct or reverse acting controllers the range and output should be as follows. Range 3-15 psi 6-30 psi Output 8-10 psi 16-20 psi
Operation
Although the output for these controllers are set prior to shipping, upon arrival the following items should be checked.
Start Up
Proportional Controllers 1. The air supply should be connected to Bellofram Type 50 filter regulator. 2. Connect the control pressure line and open the lock shield needle valve. 3. Ensure all piping and connections are free from leaks. 4. Set the pressure to the desired control point. 5. Proportional band should be set at 15% of the bandwidth. 6. Open the manual control valves that are upstream and downstream, at the same time close the by-pass valves. 7. Set the controller near the desired control point. When it reaches that point, begin to broaden the proportional band. Broaden the band as little as possible. The narrowest band that will not result in cycling provides the best control. This band adjustment will affect the zero. Re-zero the unit. 8. Test the bandwidth by changing the pressure setting adjustment for a moment. If this causes cycling, then broaden the proportional band and test again. This procedure is to be repeated until stability is reached. Proportional-Reset Controllers 1. The air supply should be connected to Bellofram Type 50 filter regulator. 2. Connect the control pressure line and open the lock shield needle valve. 3. Ensure all piping and connections are free from leaks. 4. Set pressure to the desired control point.
Proportional-Reset Controllers contd 5. Proportional band should be set at 100% of bandwidth. 6. Maximize the setting on the reset dial. 7. Open the manual control valves that are upstream and downstream, at the same time close by-pass valves. 8. Set the controller near the desired control point. When it reaches that point, begin to narrow the proportional band until a cycling condition exists. Broaden the band slightly until a stable condition is reached. There is no need to reset the zero in controllers that have reset. 9. Try to obtain the fastest reset time without introducing cycling control carefully by adjusting the reset rate. 10. Test the bandwidth and the reset rate by changing the pressure setting adjustment for a moment. If this causes cycling, then broaden the proportional band and test again. This procedure is to be repeated until stability is reached. The goal for the controller setting is to have the narrowest proportional band and the fastest reset rate that will not cause cycling.
Figure 1:
If there is a decrease in control pressure the above mentioned steps will proceed in reverse. The control pressure will bleed out through the exhaust vent (J). Please note that the changes in pressure are continuous in nature. The process has been explained in steps for ease of explanation. As seen in the figure 3, schematic illustration of Type 4150, the output pressure from relay chamber (H) goes to both the proportional band adjustment relay three-way valve (K) and the control valve diaphragm. The amount of feedback to the proportional bellows (I) can be adjusted by adjusting the orifice. If valve (K) is fully open, then the total of the diaphragm pressure is sent to the bellows chamber (I). This causes the beam (B) to move away from nozzle (C) allowing the pressure to be released from chamber (D). The result of this is 100% proportional band based on the rating of the Bourdon tube. Closing the three-way valve (K) will result in a lowering of proportional band response. The proportional band would be approximately 3% when fully closed.
2.
3.
4. 5.
6.
7.
8.
Figure 3:
CVS Series 4150/4160 Bourdon Tubes can be replaced. They may be replaced due to changes in pressure regulations or for maintenance.
Maintenance
Two steps should be carried out in regular scheduled maintenance. A cleaner button allows you to clean the passages in the relay orifice. This button should be pushed regularly. The second step is using the drain cock that is located on the underside of the drip well in the Type 50 filter. This drip well, should be allowed to bleed off to atmosphere to prevent moisture from contaminating the controller.
Replacing Bellows
(Refer to figure 6) 1. Detach sub-assembly from controller. 2. Remove the connecting link and bearing (Key 37) from the beam. 3. Remove the bellows unit from the frame (Key 16) 4. Install the bellows in the control assembly. Begin by ensuring that the beam is horizontal and with the pressure setting dial at zero. Then attach the connecting link and the bearing link to bellows and beam. Ensure that there is tension on the connecting link. Tension can be added by bending the cross springs (Key 28). 5. Adjust and calibrate for start up.
Troubleshooting
The following is a list of suggestions on where to start troubleshooting particularly immediately after installation. 1. The control valve continually cycling or hunting. 1.1. The constant cycling of a controller can occur if the reset rate is set too fast or the band setting is set too narrow. 1.2. Ensure that the controller valve plug is not sticking. 1.3. A control valve always operating near its seat will indicate an oversized control valve. 2. Incomplete Pressure Change on the Diaphragm. 2.1. Ensure an accurate reading is being displayed from the diaphragm pressure gauge. 2.2. Verify that lines and connections are free from leaks.
Calibration of Controllers
1. Move the calibration adjuster (Key 30, Figure 6) to the right or the left. 2. Repeat the nozzle adjustment and step 5 for proportional controller or step 6 for proportionalreset controller. 3. To release the calibration adjuster, loosen the two screws, above and below the beam, to the left of the nozzle.
Note 1 - These steps are to be used if the zero setting pressure or output range is not obtained when maximum pressure is applied to the measuring element. 1. Move the calibration adjuster (Key 30, Figure 6) to the right or the left. 2. Repeat the nozzle adjustment and Step 5 for proportional controller, or Step 6 for proportional-reset controller. 3. To release the calibration adjuster, loosen two screws, above and below the beam, to the left of the nozzle.
Output Range 3-15 psi 6-30 psi 15-3 psi 30-6 psi
Zero Setting 8-10 psi 16-20 psi 8-10 psi 16-20 psi
Dimensional Data
Dimensional Data
Figure 4:
CVS Type 4150 Proportional Pressure Controller with Bourdon Tube Measuring Element 7
Parts Reference
Figure 5:
Partial view of Type CVS 4160 Pressure Controller Showing the Reset Valve and the Arrangement of Tubing
5*
26
CVS4H2699 CVS1C8974 CVS1N8738 CVS1C9419 CVS1H2702 CVS1H2888 CVS1H3013 CVS1H4528 CVS1H3011 CVS1H4526 CVSML536X CVSML536XH CVS1A3321 CVS536X61 CVS536X15 CVS1H2755 CVS1H6870 CVS1H2757 CVS1H6870 CVS1H5271 CVS1H5270 CVS1A7675 CVS1A7675
Case Relay Gasket Relay Gasket, Hi-Temp Screw, 2 Reqd Instruction Plate Roll Pin, 2 Reqd Cont. Tubing Assy, 4150, 4160 Cont. Tubing Assy. Cont. Tubing Assy, 4150, 4160 Cont. Tubing Assy. Cont. Sub-Assy. 4150, 4160 Cont. Sub-Assy. Hi-Temp, 4150, 4160 Screw, 6 Reqd Reset Valve Reset Valve, Hi-Temp Compensator Tubing Assy. Compensator Tubing Assy. Conpensator Tubing Assy. Compensator Tubing Assy. Screw, 2 Reqd Screw, 4160 Pipe Plug Pipe Plug
Aluminum Neoprene Silicone Rubber Steel Cd. Pl Aluminum/SST Steel Cd. Pl Copper Copper 304 SST 304 SST Sub-Assy. Sub-Assy. Steel Cd Pl
6 7 8 9*
27* 28 29 30
10*
CVS1H2887 CVS1N8737
Neoprene Si Rubber
31*
CVS0T0191 CVS1A4658 CVS1A5120 CVS0T0192 CVS1C3762 CVS1C2256 CVS1C3333 CVS1H2698 CVS1H2895 CVS1H3435 CVS1H3436 CVS1H2759 CVS1H6861 CVS536X47 CVS536X84
Glass Gasket, 2 Reqd Retaining Ring, 2 Reqd Screw, 8 Reqd Gauge Glass, 2 Reqd O-Ring Lockwasher, 4 Reqd Screw, 4 Reqd Cont. Pres. Block Cont Pres. Block Supply Pres. Gauge 0-30 psi Supply Pres. Gauge 0-60 psi Relay Tubing Assy Relay Tubing Assy Pilot Relay Pilot Relay Hi-Temp
Neoprene Galv, Steel Cd. Pl. Steel Cd. Pl Acrylic Buna-N Steel Cd. Pl Steel Cd. Pl Steel 316 SST Sub-Assy Sub-Assy Copper 304 SST
32 33 34 35* 36* 37 38 39
Copper 304 SST Copper 304 SST Steel Cd. Pl Steel Cd. Pl Steel 316 SST
Parts Reference
Figure 6
Controller Sub-Assembly for Bourdon Tube Controllers CVS Type 4150 and 4160
Parts Reference
Pilot Relay Assembly
KEY NO. 1 2 PART NUMBER CVS1A3319 CVS1H2697 CVS1H2696 3* CVS1K7000 4 5* 6* 7 8 9* 10* 11* 12 13 14* 15* 16 CVS1K7002 17 CVS1P8261
* Recommended Spare Part
PART DESCRIPTION Screw, 4 Reqd Spring Plate Spring Plate Gasket, Temp. To 150F Spring Plate Gasket, Temp. To 150F-250F Valve Plug Spring Relay Spring Valve Plug Dia. Assy. Temp To 150F Dia. Assy. Temp 150-250F Top Dia., Temp 150F Screw Temp to 150F 6 Reqd Screw 150F-250F 6 Reqd O-Ring Restriction Plug Orifice Assy. Core & Wire Assy. Relay Body Spacer Ring Diaphragm Case Assy Bottom Gasket (Not Shown) Temp. 150F-250F Top Gasket, Temp 150-250F Washer, 6 Reqd (Not Shown)
Sil. Rubber Inconel Inconel 316 SS Brass Sub Assy. Buna-N Steel Syn. Rubber Sub Assy. Sub Assy. Zinc Zinc Sub Assy. Sil. Rubber Steel
CVS0X0836 CVS1C8961 CVS0Y0617 CVS0Y0617B CVS1C9370 CVS1K6996 CVS1L5556 CVS1C8969 CVS1A3294 CVS1D6875 CVS1H8266 CVS1E2303 CVS2H2693 CVS2K4404 CVS1C9369 CVS1K7001
Figure 7:
Exploded View of Pilot Relay used in CVS Type 4150 and 4160 Controllers
Psig Bar Psig Bar 3 to 15 or 0.2 to 1.0 or 20 1.4 50 0 & 20 (on-off) 0 & 20 (on-off) 6 to 30 or 0.4 to 2.0 or 35 2.4 50 0 & 30 (on-off) 0 & 2.4 (on-off) * Stability and control may be compromised if pressure is exceeded. A Proportional Band setting of 0-10 B Proportional Band setting of 5
10
Notes
11
Head Office 3900 101 Street Edmonton, Alberta, Canada T6E 0A5 Office: (780) 437-3055 Fax: (780) 436-5461 Calgary Sales Office 205, 2323 32 Avenue NE Calgary, Alberta, Canada T2E 6Z3 Office: (403) 250-1416 Fax: (403) 291-9487
Website: www.cvs-controls.com
E-Mail: [email protected]
12