Padmount & Overhead Distribution Transformers

The document is a specification sheet for 12.47kV distribution transformers for padmount and polemount applications. It provides requirements for standards, evaluation criteria, information to be submitted with bids, technical requirements for polemount and padmount transformers, and testing and inspection details. Requirements include transformer ratings, bushings, terminals, tanks, insulation, and coating systems. Approved manufacturers are listed and losses will be evaluated based on a cost formula.

Uploaded by

mellymoyo
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
520 views18 pages

Padmount & Overhead Distribution Transformers

The document is a specification sheet for 12.47kV distribution transformers for padmount and polemount applications. It provides requirements for standards, evaluation criteria, information to be submitted with bids, technical requirements for polemount and padmount transformers, and testing and inspection details. Requirements include transformer ratings, bushings, terminals, tanks, insulation, and coating systems. Approved manufacturers are listed and losses will be evaluated based on a cost formula.

Uploaded by

mellymoyo
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 18

DISTRIBUTION TRANSFORMERS SPECIFICATION #1212.

01

12.47kV Grd Wye Padmount & Polemount


6/15/2012 Page 1 of 18

Material Specification 1212.01 Distribution Transformers Padmount & Polemount

TABLE OF CONTENTS
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 SCOPE ............................................................................................................................................. 3 STANDARDS .................................................................................................................................. 3 EVALUATION AND AWARD ..................................................................................................... 3 INFORMATION TO BE FURNISHED WITH BID ................................................................... 4 POLEMOUNT TRANSFORMERS .............................................................................................. 6 PAD MOUNT TRANSFORMER SINGLE PHASE ................................................................ 8 PAD-MOUNTED TRANSFORMERS THREE PHASE ....................................................... 10 TRANSFORMER OIL ................................................................................................................. 15 NOISE ............................................................................................................................................ 15 PAINT FINISH ............................................................................................................................. 15 INSPECTION................................................................................................................................ 16 TESTS ............................................................................................................................................ 17 WORKMANSHIP, MATERIAL, AND FINISH ....................................................................... 17 DELIVERY METHODS .............................................................................................................. 17 SPECIFICATIONS REVISIONS LOG...................................................................................... 18

6/15/2012

Page 2 of 18

Material Specification 1212.01 Distribution Transformers Padmount & Polemount


1 SCOPE

This specification is to cover minimum requirements for Polemount & Padmount type, outdoor, oil-immersed distribution transformers suitable for operation on the Districts 12470GrdY/7200 Volt Distribution System. 2 STANDARDS

All material and equipment furnished under these specifications shall conform to the latest applicable approved standards of IEEE, ANSI, NEMA and DOE except as otherwise specified herein
2.1 2.2 2.3 2.4 ANSI C37.47 Specifications For Distribution Fuse Disconnecting Switches, Fuse Supports, And Current Limiting Fuses. ANSI/IEEE C57.12.00 General Requirements for Liquid Immersed Distribution, Power and Regulatory Transformers. ANSI/IEEE C57.12.01 General Requirements for Dry Type Distribution and Power Transformers. ANSI C57.12.22 Requirements for Pad Mounted, Compartmental Type, Self Cooled, Three Phase Distribution Transformers with High Voltage Bushings: High Voltage, 34,500 Grdy/19,900 Volts and Below, 2500kva and Smaller. ANSI C57.12.26 Requirement for Pad Mounted, Compartmental Type, Self Cooled, Three Phase Distribution Transformers with High Voltage Bushings: High Voltage 24,940 Grdy/14,400 Volts and Below, 2500kva and Smaller. ANSI C57.12.28 - Switchgear and Transformers - Pad-Mounted Equipment - Enclosure Integrity. ANSI C57.12.70 Terminal Markings and Connections for Distribution and Power Transformers. ANSI/IEEE C57.12.80 Terminology for Power and Distribution Transformers. ANSI/IEEE C57.12.90 Test Code for Liquid Immersed Distribution Power, And Regulating Transformers.

2.5

2.6 2.7 2.8 2.9

2.10 ANSI/IEEE C57.12.91 Test Code for Dry Type Distribution and Power Transformers. 2.11 ANSI/IEEE 386 Separable Insulated Connector Systems for Power Distribution Systems Above 600v. 2.12 ASTM D877 Test Method for Dielectric Breakdown Voltage of Insulating Liquids Using Disk Electrodes. 2.13 ANSI Z535. 2.14 DOE 2010 Medium Voltage Transformer Efficiencies

EVALUATION AND AWARD

For the purpose of evaluating bids, consideration will be given to the following three items. Product Quality Loss Evaluation Adherence to Specifications

6/15/2012

Page 3 of 18

Material Specification 1212.01 Distribution Transformers Padmount & Polemount


3.1 Product Quality

Product quality will be determined by the placement of the manufacturer in the most recent Washington PUD Design Committee (WAPUD) transformer teardown. Quality will be ranked by the manufacturer placement on the teardown. Current approved manufacturers are listed below. Single Phase Pandmount 2007: ABB, Cooper, Ermco Three Phase Padmount 2005: ABB, Cooper, Ermco, Pauwels (CG Power) Pole Mount 2009: ABB, Cooper, Ermco, Central Maloney
3.2 Loss Evaluation 3.2.1 Losses furnished for evaluation shall be guaranteed maximum losses for each transformer bid. o 3.2.2 No load losses (NLL) shall be in watts, at 20 C in accordance with ANSI C57.12.00 and shall be evaluated at $4.07 per watt. o 3.2.3 Full-load losses (FLL) shall be in watts, measured at rated nameplate load at 85 C in accordance with ANSI C57.12.00 and shall be evaluated at $1.79 per watt 3.2.4 Evaluated Price Formula = [$4.07 x NLL] + [$1.79 x FLL] + Unit Price 3.2.5 The manufacturer shall furnish with each transformer a certified test report of the no-load and fullload losses. The test report shall be submitted with the Contractors invoice. 3.3 Adherence to Specifications. The District expects all bids to conform to these Specifications. Any exception is cause for rejection.

INFORMATION TO BE FURNISHED WITH BID OR QUOTE

Technical information shall be provided by Bidder with their Bid in a Microsoft Excel Spreadsheet on CD or paper copy of the same for all bid items. An electronic copy of the form is available on CD; a sample form is shown below.

6/15/2012

Page 4 of 18

Material Specification 1212.01 Distribution Transformers Padmount & Polemount Table 1 : Technical Information Sample Form
Technical Information The following data must be provided for each Bid Item in the following format in hard copy and electronically in an Excel spreadsheet. Only one spread sheet shall be submitted per contractor. Add columns as needed. BID ITEM:
Manufacturer Contract Number: Vendor KVA Size: High Voltage (ANSI Designation) (kV) Low Voltage (ANSI Designation) (volts) Impedance Voltage: (%) Maximum L.V. Short Circuit Current (kA) Maximum L.V. Short Circuit Current is at: L-L or L-N L.V. Windings (Interlaced or Non-interlaced): Short Circuit Impedance: (%) Total Weight: (lbs) Oil: (Gallons) H.V. Winding Metal: L.V. Winding Metal: Core Metal, Type: (Grain Oriented, Amorphous) Minimum Primer Thickness: (Mils) Minimum Paint Thickness: (Mils) Base Dimensions: Overall Width: (Inches) Overall Depth: (Inches) Overall Height: (Inches) Access Hole Width: (Inches) Access Hole Depth: (Inches) Core Loss: (Watts) Copper (Winding) Loss: (Watts) Describe the coating system on separate sheets. Include the corrosion resistant material used on the bottom and lowest 2" of the sides. 1 2 3 4

6/15/2012

Page 5 of 18

Material Specification 1212.01 Distribution Transformers Padmount & Polemount


5 POLEMOUNT TRANSFORMERS
5.1 Ratings 5.1.1 All ratings shall be for 60 hertz alternating current, oil immersed, self-cooled transformers capable of o continuous operation at rated KVA without exceeding either a 65 C average temperature rise or an o 80 C hot spot temperature rise. 5.1.2 The basic impulse level (BIL) shall be 95 kV. 5.2 Pressure Relief Device 5.2.1 All transformers shall be designed such that all excessive pressure build-ups are released without damage to the tank in accordance with ANSI C57.12.25. 5.2.2 All transformers shall be equipped with a pressure relief device (either Tomco Series 1776K or Qualitrol Model 202-032-1). 5.3 Transformer Taps 5.3.1 No transformer taps are required. 5.4 Transformer Oil 5.4.1 Transformers shall be insulated with new (unused) mineral oil. The oil shall meet the requirements of ANSI C57.12.00, Article 6.6.1 (1), ANSI C57.106 and ASTM 3487 Type II. The transformer nameplate shall indicate that the PCB content of said transformer is less than 1 PPM or at time of manufacture gas chromatographic analysis certified non-detectable PCB. The oil shall be inhibited mineral oil containing 0.2 % by weight DBPC. The nameplate shall show the gallons of oil and state the oil type as Mineral Oil. 5.5 High Voltage Bushings and Terminals 5.5.1 Transformers shall be equipped with cover-mounted, wet process porcelain high voltage bushings (two bushings) with clamp style terminals in accordance with ANSI C57.12.20, Table 7. The bushings shall be light gray in color. The clamp type terminal shall be capable of being tightened with a Fargo wrench (Fargo Manufacturing, Catalog No. GP-203). 5.6 Low Voltage Bushings and Terminals 5.6.1 Transformers shall be equipped with side wall-mounted, low voltage bushings. Units 100 KVA and smaller shall have clamp type terminals in accordance with ANSI C57.12.20, Figure 4a. Units 167 KVA and larger shall have 4-hole square spade type terminals in accordance with ANSI C57.12.20, Figure 4b, Spade H. 5.6.2 Number and arrangement of low-voltage terminals shall be in accordance with ANSI C57.12.20, Table 9. 5.6.3 Polymer secondary bushings shall be used for transformers. 5.7 Transformer Tanks 5.7.1 Transformer tanks shall be of welded steel construction. The tank shall be a conventional, oil-filled, pole-type with only one pole-mounting position. 5.7.2 The tank covers shall have a slope of 10-15 percent for moisture run-off and shall have an insulated coating on the cover capable of withstanding a minimum of 10kV at a 2000 volt/second rate of rise, tested per ASTM D149 using diameter electrodes. 5.7.3 The overall size of the transformer and the weight of the transformers, once filled with oil, shall not exceed the following: 5.7.4 Tanks shall have tank ground provisions and support lugs in accordance with ANSI Standard C57.12.20.

6/15/2012

Page 6 of 18

Material Specification 1212.01 Distribution Transformers Padmount & Polemount Table 2: Single Phase Pole Mount Transformers Max Dimensions
Size (KVA)
25 50 75 100 167

Weight (lbs.)
375 600 875 1000 1600

Height (in.)*
41 45 51 50 54 * Height shall be measured from bottom of tank to top of primary terminal at top of primary bushing.

Width (in.)**
23 25 25 32 38 ** Width shall be measured from lifting hook to lifting hook.

Depth (in.)***
25 27 27 30 38 *** Depth shall be measured from mounting bracket to outside of secondary terminal.

5.8 Grounding Lugs 5.8.1 Transformers shall be furnished with a ground lug installed in the transformer low-voltage ground provision. The ground lug shall be a Fargo (Catalog No. GC-207). 5.9 TIF and RIV Requirement 5.9.1 TIF - Transformers shall be designed to meet REA Telephone Influence Factor (TIF) requirements, as detailed in REA Specifications D-10. Transformer I-T tests shall be made in accordance with the method described in IEEE Standard No. 469-1977, except as noted in REA Specifications D-10. REA Specification D-10 requires that the average overall I-T of the secondary windings per transformer nameplate KVA shall not exceed the following limits:

I-T per KVA


120 Volts 22 132 Volts 66

5.9.2 RIV - The Radio Influence Voltage (RIV) shall not (per REA Specification D-10) exceed 100 V (average measurement) at 1 MHz measured at 110% of rated voltage in accordance with the methods outlined in ASA Publication C63.2, 1950, Appendix A, Figure 5. Dual voltage transformers shall be tested on the highest connection.

6/15/2012

Page 7 of 18

Material Specification 1212.01 Distribution Transformers Padmount & Polemount


6 PAD MOUNT TRANSFORMER SINGLE PHASE
6.1 Ratings 6.1.1 All ratings shall be for 60 Hertz alternating current, oil immersed, self-cooled transformers capable of o continuous operation at rated KVA without exceeding either a 65 C average temperature rise or an o 80 C hot spot temperature rise. 6.1.2 The electrical characteristics of the completely assembled high and low voltage terminals shall be in accordance with ANSI C57.12.25, Table 1 and Section 6.2.1. 6.1.3 The basic impulse level (BIL) shall be 95 kV. 6.2 Loop Feed 6.2.1 Transformers will be suitable for loop feed. 6.2.2 The minimum current-carrying capabilities of components for looped primary cable systems shall be 200 Amps (continuous) and 10,000 Amps rms symmetrical for 0.17 sec. (short-time current rating) for transformers with or without high-voltage switching. 6.3 Transformer Type 6.3.1 Transformers shall be Type 2 in accordance with Figure 2a of ANSI C57.12.25 6.4 Pressure Relief Device 6.4.1 All transformers shall be designed such that all excessive pressure build-ups are released without damage to the tank in accordance with ANSI C57.12.25. 6.4.2 All transformers shall be equipped with a pressure relief device (either Tomco Series 1776K or Qualitrol Model 202-032-1). 6.5 Transformer Taps 6.5.1 No transformer taps are required. 6.6 High Voltage Bushings 6.6.1 Transformers shall come equipped with two high voltage bushing wells and corresponding load break inserts for dead front application. The bushing wells shall be externally clamped, 200-amp rated, separable, and rated for primary switching per IEEE 386. 6.6.2 The bushings shall conform to ANSI C57.12.25, Type 2 arrangement. 6.6.3 The load-break bushing inserts shall be Cooper Power Systems LBI 215 or Elastimold (Catalog No. 1601A4). 6.6.4 Inserts shall be shipped with physically wired down & secured dust caps or use a dust cap equiped with a pressure relief hole to prevent pressure build up in the dust cap that would cause loss of the dust cap. 6.7 Low Voltage Bushings 6.7.1 Transformers shall be equipped with fully insulated, low voltage bushings with in-line NEMA standard stud terminals in accordance with Figure 4C of ANSI C57.12.25. 6.7.2 Transformers shall be furnished with the following terminals:

Table 3: Single Phase Padmount Terminal Size


KVA
25-75 100 167

Secondary Voltage
240/120 240/120

Terminal Size
Stud, 5/8 11 UNC-2A Stud, 1 14 UNC-2A

6/15/2012

Page 8 of 18

Material Specification 1212.01 Distribution Transformers Padmount & Polemount


6.8 Grounding Lugs 6.8.1 Transformers shall be furnished with a total of 3 grounding lugs: one ground lug installed in the transformer low-voltage ground provision and two ground lugs installed in the transformer highvoltage ground provision. 6.8.2 The ground lugs shall be Fargo (Catalog No. GC-207). 6.9 Compartmental Locking 6.9.1 The terminal compartment covers shall be secured with a captive nut and a captive recessed 9/16 stainless steel or silicon bronze Pentahead bolt, and provisions for padlocking. The Pentahead bolt shall be coordinated so that it must be engaged before a padlock can be inserted into or removed from the hasp. All transformers shall meet the requirements for tamper-resistance of NEMA TR-1 and Western Underground Guide No. 2.13. 6.10 Fusing 6.10.1 Transformers shall be provided with Cooper Power Systems Bay-O-Net fuse holders. They shall be of the sidewall mount type with flapper, Cat. No. 40003616C99FV. 6.10.2 Transformers shall be provided with Cooper Power Systems Bay-O-Net, dual sensing, load break, externally removable fuses, in series with under oil, internally mounted 8.3 kV partial range current limiting fuses (CLF). The partial range fuse shall be manufactured by Cooper Power Systems (Type ELSP). 6.10.3 The partial range current limiting fuses shall be placed in series with the Bay-O-Net fuse holder and be mounted internally under oil. Partial range current limiting fuses shall have a nominal voltage rating of 8.3kV. 6.10.4 Oil drip shields shall be provided designed to catch and hold oil. Oil drip shields that redirect oil rather than catch and hold it will not be allowed. 6.10.5 The Bay-O-Net Fuse size and type shall be painted on the inside of the primary side cabinet door utilizing yellow characters one (1) inch high. In addition, the bayonet and current limiting fuse part numbers will be displayed on the nameplate. Fuses shall meet the Districts current fusing specifications which are shown in the table below.

Table 4: 7.2 kV Single Phase Transformer Fusing


Stock # 88888 88801 88802 88803 88804 88805 KVA 15 25 50 75 100 167 Bay-O-Net Fuse (Dual Sensing) 4000358C03M 4000358C05M 4000358C08M 4000358C10M 4000358C10M 4000358C12M Continuous Rating (A) 3 8 15 25 25 50 Current Limiting (ELSP Backup) 3001861A01M (Isolation Link only) CBUC08040C100 CBUC08080C100 CBUC08125C100 CBUC08125C100 CBUC08165D100 ELSP Rating (A) na 40 80 125 125 165

6/15/2012

Page 9 of 18

Material Specification 1212.01 Distribution Transformers Padmount & Polemount

Table 4b: 2.4 kV Single Phase Transformer Fusing


Stock # 89188 89189 89190 89191 89192 89193 89194 KVA 15 25 37.5 50 75 100 167 Bay-O-Net Fuse (Dual Sensing) 4000358C08M 4000358C10M 4000358C12M 4000358C12M 4000358C14M 4038361C03CB 4038361C04CB Continuous Rating (A) 15 25 50 50 65 65 100 Current Limiting (ELSP Backup) CBUC08065C100 CBUC08100C100 CBUC08150D100 CBUC08165D100 CBUC08165D100* CBUC08165D100* CBUC08250D100*
* Two fuses in parallel 6.11 Transformer Tanks 6.11.1 Transformer tanks shall be constructed in accordance with ANSI C57.12.25. The primary and secondary bushing compartment shall have a hinged, vertical-swing cover. Both the cover and the tank shall be domed or sloped to prevent moisture collection. 6.11.2 The cover hinge pins and the threaded lifting inserts shall be stainless steel. 6.11.3 Grounding provisions shall consist of three grounding pads, two on the HV compartment and one on the LV compartment side of the transformer. The tapped holes shall be plugged during painting to prevent coating of the threads. 6.11.4 The overall maximum transformer size shall be within the following dimensional ranges:

ELSP Rating (A) 65 100 150 165 330 330 500

Table 5: Single Phase Transformers - Tank Sizes


Size (KVA)
25 167

Height (in.)*
36 max. * Height shall be measured from top of highest point to bottom of unit.

Width (in.)**
36 max. ** Width shall be measured from left to right, when facing the lid, across widest part of unit.

Depth (in.)***
40 max *** Depth shall be measured from lid to rear, across deepest part of unit.

Minimum Terminal Compartment Depth (in.)****


15 **** Depth shall be measured from lid to front of bushing well wall.

6/15/2012

Page 10 of 18

Material Specification 1212.01 Distribution Transformers Padmount & Polemount


7 PAD-MOUNTED TRANSFORMERS THREE PHASE
7.1 Ratings 7.1.1 All ratings shall be for 60 Hertz alternating current, oil immersed, self-cooled transformers capable of o continuous operation at rated KVA without exceeding either a 65 C average temperature rise or an o 80 C hot spot temperature rise. 7.1.2 The electrical characteristics of the completely assembled high and low voltage terminals shall be in accordance with IEEE C57.12.26, Table 3 and Table 4. 7.1.3 The basic impulse level (BIL) shall be 95 kV. 7.2 Transformer Type 7.2.1 Transformers shall be loop feed construction, in accordance with Figure 2 of IEEE C57.12.26. 7.3 Core Construction 7.3.1 The core shall be either triplex or five-legged construction. 7.4 Pressure Relief Device 7.4.1 All transformers shall be designed such that all excessive pressure build-ups are released without damage to the tank in accordance with IEEE C57.12.26. 7.4.2 All transformers shall be equipped with a pressure relief device (either Tomco Series 1776K or Qualitrol Model 202-032-1). 7.5 Transformer Taps 7.5.1 No transformer taps are required. 7.6 High Voltage Bushings 7.6.1 Transformers shall come equipped with high voltage bushing wells and corresponding load break inserts for dead front application. The bushing wells shall be externally clamped, 200-amp rated, separable, and rated for primary switching per IEEE 386. 7.6.2 The load-break bushing inserts shall be Cooper Power Systems (Catalog No. LBI 215 or Elastimold (Catalog No. 1601A4). 7.6.3 The primary neutral shall be insulated and no H0 bushing provided on Y- transformers. 7.6.4 Inserts shall be shipped with physically wired down & secured dust caps or use a dust cap equiped with a pressure relief hole to prevent pressure build up in the dust cap that would cause loss of the dust cap. 7.7 Low Voltage Bushings 7.7.1 Transformers shall be equipped with fully insulated, low voltage bushings, in accordance with Fig. 8(a) of IEEE C57.12.26. 7.7.2 Transformers shall be furnished with the following NEMA standard stud or spade terminals as per IEEE C57.12.26 Fig. 9.

6/15/2012

Page 11 of 18

Material Specification 1212.01 Distribution Transformers Padmount & Polemount Table 6: Three Phase Padmount Transformers Terminal Sizes
KVA 75-300 75-150 225-300 500 500 500 750 750-1500 750-1500 1000 Secondary Voltage Terminal Size 480Y/277 Stud, 5/8 11 UNC 2A (Fig. 9d) 240, 208Y/120 240, 208Y/120 480Y/277 240 208Y/120 240 480Y/277 208Y/120 240 Stud, 1 14 UNC 2A With 6 hole Spade (Fig. 9d)

Spade, 6 hole - (Fig. 9b)

Spade, 10 hole - (Fig. 9c)

2000-2500 480Y/277
7.7.3 Ten-hole spade pads shall be furnished with additional support, as designed by the manufacturer. The supports shall be attached to the pads at the farthest point from the tank wall and attached in a manner so as to not interfere with the use of any of the pads holes. 7.8 Grounding Lugs 7.8.1 Transformers shall be furnished with a total of 3 ground lugs: one ground lug installed in the transformer low-voltage ground provision and two ground lugs installed in the transformer highvoltage ground provision. 7.8.2 The ground lugs shall be Fargo (Catalog No. GC-207). 7.9 Compartmental Locking 7.9.1 All hinged or removable cabinet access lids or doors shall have a three point latch and be provided with a 9/16 stainless steel or silicon bronze Pentahead captive bolt locking device and provisions for padlocking. The Pentahead bolt shall be coordinated so that it must be engaged before a padlock can be inserted into or removed from the hasp. All transformers shall meet the requirements for tamper-resistance of NEMA TR-1 and Western Underground Guide No. 2.13. 7.10 Hand Holes 7.10.1 A bolted on tank hand hole shall be secured against tampering by some means accessible only from the inside of the compartment. 7.11 Fusing 7.11.1 Transformers shall be provided with Cooper Power Systems Bay-O-Net fuse holders. They shall be of the sidewall mount type with flapper, Cat. No. 40003616C99FV. 7.11.2 Transformers shall be provided with Cooper Power Systems Bay-O-Net, dual sensing, load break, externally removable fuses. They shall also be provided with internally mounted partial range current limiting fuses (CLF) manufactured by Cooper Power Systems. 7.11.3 The partial range current limiting fuses (type ELSP) shall be placed in series with the Bay-O-Net fuse holder and be mounted internally under oil. Partial range current limiting fuses shall have a nominal voltage rating of 8.3kV. 7.11.4 Oil drip shields shall be provided with the Bay-O-Net fuse holder and be designed to catch and hold oil. Oil drip shields that redirect oil rather than catch and hold it will not be allowed.

6/15/2012

Page 12 of 18

Material Specification 1212.01 Distribution Transformers Padmount & Polemount


7.11.5 The Bay-O-Net Fuse size and type shall be painted on the inside of the primary side cabinet door utilizing yellow characters one (1) inch high. In addition, the bayonet and current limiting fuse part numbers will be displayed on the nameplate. Fuses shall meet the Districts current fusing specifications which are shown in the table below.

Table 7: 12.47 kV Three Phase Transformer Fusing


Stock # 88843 88845 88848 88849 88853 88854 88857 88858 88859 88861 88862 88863 89007 Three Phase KVA 75 150 300 500 750 1000 1500 2000 2500 Bay-O-Net Fuse (Dual Sensing) 4000358C05M 4000358C08M 4000358C10M 4000358C12M 4000358C14M 4000358C14M 4038361C04CB 4038361C05CB 4038361C05CB Continuous Ampere Rating 8 15 25 50 65 65 100 125 125 Current Limiting (ELSP Backup) CBUC15030C100 CBUC15080C100 CBUC15100C100 CBUC15150D100 CBUC15125C100* CBUC15125C100* CBUC15125C100* CBUC15125C100* CBUC15125C100* ELSP Ampere Rating 30 80 100 150 250 250 250 250 250

Table 7b: 4.16 kV Three Phase PAD Transformer Fusing


Stock # KVA 45 89200 89201 89202 89203 89204 89205 89206 75 112.5 150 225 300 500 750 Bay-O-Net Fuse (Dual Sensing) 4000358C08M 4000358C10M 4000358C12M 4000358C12M 4000358C14M 4000358C14M 4038361C04CB 4038361C05CB Continuous Rating (A) 15 25 50 50 65 65 100 125 Current Limiting (ELSP Backup) CBUC15080C100 CBUC15125C100 CBUC15165D100 CBUC15165D100 CBUC15150D100* CBUC15150D100* CBUC15180D100* CBUC15180D100*
* Two fuses in parallel

ELSP Rating (A) 80 125 165 165 300 300 360 360

6/15/2012

Page 13 of 18

Material Specification 1212.01 Distribution Transformers Padmount & Polemount


7.12 Transformer Tanks 7.12.1 Transformer tanks shall be constructed in accordance with IEEE C57.12.26. 7.12.2 Grounding provisions shall consist of three grounding pads, two on the HV compartment and one on the LV compartment side of the transformer. The tapped holes shall be plugged during painting to prevent coating of the threads. 7.12.3 For transformers 300 kVA and larger, the front cabinet apparatus compartment shall have side panels that open, extend, and lock allowing side entry to termination compartments and less restricted space. 7.12.4 For transformers 300 kVA and larger, Roof sections shall be able to be raised to allow vertical cable pulling / support. 7.13 Oil Drain Valve 7.13.1 Transformers shall come equipped with an oil drain valve installed at the bottom edge in the transformer secondary compartment, minimum diameter, gate or ball activated. 7.14 Labeling 7.14.1 A danger label, complying with ANSI Z535, shall be located on the inside of the transformer and readily visible whenever the first equipment door is open. 7.15 Accessories 7.15.1 In addition to standard accessories, each transformer 1500 KVA and larger shall be properly equipped with the following gauges mounted in the low voltage compartment.

7.15.1.1 Oil Level Gauge. 7.15.1.2 Dial thermometer with maximum top oil temperature indicator and magnetic reset. 7.15.1.3 Tank Pressure Vacuum Gauge.
7.16 Tank Dimensions 7.16.1 The maximum dimensions of the 3 phase Padmount transformers shall be as shown below. These dimensions do not include cooling fins.

Table 8: Three Phase Transformers Maximum Dimensions


Height Width Depth
75 KVA Mini-Pad 42 max 44.5 max 42 max 150 to 500 KVA 70 max 72 max 62 max 750 to 2500 KVA 89 max 88 max 66 max

7.16.2 Depth of Apparatus Compartment - The minimum depth of the apparatus compartment (except 75KVA mini-pad) shall be 24 inches, as shown in Dimension F of Figure 7 of IEEE Standard C57.12.26 - 1992. 7.16.3 Cooling Fins - Cooling fins shall not extend further than 12 inches beyond the dimensions shown above.

6/15/2012

Page 14 of 18

Material Specification 1212.01 Distribution Transformers Padmount & Polemount


8
8.1

TRANSFORMER OIL
Transformers shall be insulated with new (unused) mineral oil. The oil shall meet the requirements of ANSI C57.12.00, Article 6.6.1 (1), ANSI C57.106 and ASTM 3487 Type II. The transformer nameplate shall indicate that the PCB content of said transformer is less than 1 PPM or at time of manufacture gas chromatographic analysis certified non-detectable PCB. The oil shall be inhibited mineral oil containing 0.2 % by weight DBPC. The nameplate shall show the gallons of oil.

9
9.1

NOISE
Transformer sound levels shall not exceed the values specified in the latest revision of NEMA Publication TR 10.11.

10 PAINT FINISH
10.1 The transformer shall have a corrosion resistant finish that shall be capable of meeting the functional specifications or exceed paint requirements of ANSI C57.12.28, latest revision. The outside shall be properly prepared, primed and painted with highly weather resistant finish coat. All transformers shall have the manufacturers premium paint system. 10.2 Transformers shall be given a phosphatizing bath, or sand blasted, grit blasted or shot blasted, then primed with epoxy or vinyl primer. Transformers shall have a corrosion resistant finish that shall be capable of meeting the functional specifications or exceed ANSI c57.12.28. The exterior finish coat shall meet or exceed the following: be semi-gloss polymer , free of runs and sags, primed with a primer, no less than 2.0 mils dry thickness and a coat of semi-gloss polymer type enamel paint no less than one (1) mil dry thickness (total measured thickness 3 mils). 10.3 Pole Mounted Transformers the finish coat shall be semi-gloss sky gray similar in color to ANSI Standard no. 70. The transformer top shall meet or exceed the following: have at least 10 mils of paint. The transformer sides and bottom shall have at least 3 mils of paint. The inside of the transformer shall have at least 3 mils of paint from a point 2 inches below the oil level up to and including the top. Complete painting of the inside is acceptable. 10.4 Pad Mounted Transformers - the finish coat shall be semi-gloss olive-green gray similar to Munsel no. 7GY3.29/1.5. The interior cabinet surfaces shall be primed and finished, with no less than 2.0 mils dry thickness 10.5 NAMEPLATES 10.5.1 Nameplates shall be made of stainless steel or anodized aluminum and permanently marked with essential operating data meeting ANSI standard c57.12.00 for nameplate b. 10.5.2 The transformer nameplate shall specifically state that the transformer is filled with Mineral Oil and the number of gallons of oil it contains. 10.5.3 The nameplate shall indicate that the PCB content of said transformer is less than 1 ppm or that at the time of manufacture gas chromatographic analysis certified non-detectable PCB. 10.5.4 Each nameplate shall contain a transformer bar code. The bar code label shall meet all requirements of IEEE standard c57.12.35 1996. 10.5.5 The bayonet and current limiting fuse part numbers will be displayed on the nameplate for all Padmount units 10.5.6 Nameplates shall be mechanically fastened with rivets, bolts, screws or corner tack welds.

6/15/2012

Page 15 of 18

Material Specification 1212.01 Distribution Transformers Padmount & Polemount


11 INSPECTION
11.1 The purchaser shall at any reasonable time be permitted to have a representative visit the Contractors factory for the purpose of witnessing manufacture of the transformers to ascertain if the material and process used in the manufacturing conform to the Specifications.

6/15/2012

Page 16 of 18

Material Specification 1212.01 Distribution Transformers Padmount & Polemount


12 TESTS
12.1 Each transformer shall receive complete tests at the factory in accordance with latest ANSI standards. At the option of the district, transformers may be tested for acceptance upon receipt. 12.2 All transformers manufactured under this specification shall be tested for core and winding (copper) losses at 85oC, percent impedance at 85oC, and exciting current (100% voltage and subjected to a full wave voltage impulse). Actual loss data shall be prepared in accordance with the bid form. 12.3 Vendor shall supply verification that the design has passed short circuit criteria per ANSI C57.12.00 and c57.12.90 latest revision. 12.4 Guaranteed losses: the losses submitted by the bidder for bid evaluation shall be considered as guaranteed losses by the district. DOE efficiencies will be calculated off of these quoted losses. 12.5 Certified test reports shall be furnished to the district at time of delivery or invoicing of transformers. Invoices must reference serial number of transformer, bid item and quoted losses. No payment will become due until proper serial numbers and the corresponding certified test reports are received by the district.

13 WORKMANSHIP, MATERIAL, AND FINISH


13.1 All workmanship and material used on the equipment shall be first class, the best of their respective kinds and shall be in full accordance with the most modern manufacturing practices for distribution transformers.

14 DELIVERY METHODS
14.1 Destination 14.1.1 The transformers shall be shipped f.o.b. destination to 1150 Hawley Street, Wenatchee, WA. 98801. The delivery will be accepted Monday through Friday between the hours of 9:00 am and 2:00 pm. No delivery of transformers will be accepted on holidays. Please call the Hawley Street Warehouse Forman at (509) 663-8121, ext. 4730, 24 hours prior to delivery. No transformers will be received on national holidays. 14.2 Methods 14.2.1 Polemount transformers shall be filled with the proper amount of transformer oil and shipped, completely assembled, in an enclosed van. 14.2.2 Padmount transformers rated up to 300 KVA shall be shipped on individual pallets made with 4 by 4 lumber minimum (one transformer per pallet) and securely attached to the pallets to facilitate handling with forklift and shipped, completely assembled, in an enclosed van. 14.2.3 Padmount transformer rated 500-2500 KVA shall be capable of being unloaded with an overhead crane (skids are not required on these sizes) and must be shipped on flatbed trailers and tarped or otherwise protected from the elements during shipping. 14.3 Rejection Of Shipment 14.3.1 Transformers exhibiting damaged parts, broken securing devices, or are dirty from lack of proper shipping, shall be cause for rejection of shipment.

6/15/2012

Page 17 of 18

Material Specification 1212.01 Distribution Transformers Padmount & Polemount


15 SPECIFICATIONS REVISIONS LOG # 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Date 9/14/05 9/26/05 9/30/04 10/05/05 10/05/05 11/04/05 Section 7.7.2 Description Added Specifications Revision Log Reformated Padmount Transformer Secondary Studs or Spade Terminals table Required polymer insulators on all pole mount KVA. Require 10-hole spade for 750-1500 480/277 volt padmount instead of 6 hole. Renumbered Spec from 2200.000 to 2212.0050 Addede Table Numbers Added ELSP Fuse Ratings (A)

6.6.3 7.7.2 all all Table 4 & 7 12/29/05 ALL 8/15/06 Table 7

Renumbered spec from 2211.0050 to 1212.01 Changed 3543 series of CLF to 3544 per Cooper Power memo dated July 8, 2004 1/23/07 Evaluation Eliminated reference to Contract Document Section B. Criteria 3/29/07 14.2 Reduce size of transformers than can be delivered in an enclosed van.DLS 12/10/10 2, 4, 10 Added provision for paper copy of technical data. Added DOE 2010, added meet or exceed to paint finishing. Formatted for readability. 5/5/11 3, 6, 7, 12 4kV fuse tables added, typos fixed, Latest WAPUD info added. 12/2/11 6.10, 7.11 ELSP fuse numbers updated to new part numbers 6/15/12 7.12 Side entry to secondary terminals.

6/15/2012

Page 18 of 18