Manual Icm 450
Manual Icm 450
Manual Icm 450
ICM 450
Specification
Input Line Voltage: Universal, 190-630 VAC Frequency: 50-60 Hz Load Side Monitoring: Optional Control Voltage: 18-240 VAC Frequency: 50-60 Hz Output Type: Relay, SPDT Voltage Range: 240VAC @ 10A maximum Frequency: 50-60 Hz Control Operating Temperature Operating Temperature: -40F to +167F (-40C to +75C) Storage Temperature: -40F to +185F (-40C to +80C) LCD Operating Temperature Operating Temperature: -4F to +167F (-20C to +75C) Mechanical Mounting: Surface mount using (2) #8 screws Terminations: Screw terminals Weight: 12 ounces (341 grams) Dimensions 6 1/2 L, 4 1/4 W, 1 3/8 H (16.5 cm. L, 10.8 cm. W, 3.5 cm. H)
Parameters
Phase Unbalance Protection Voltage Unbalance: 2-20% adjustable Over/Under Voltage Protection Under Voltage: 2-25% adjustable Over Voltage: 2-25% adjustable Phase Loss Protection Phase Loss Condition: Equals 25% of nominal for any given phase; system will shut down and a fault will be recorded should this occur Delay on Break Timer Control Voltage: 18-240 VAC Time Delay: 0 to 10 minutes adjustable Fault Interrogation Delay Time Delay: 0 to 15 seconds adjustable Provides a delay between fault detection and system shutdown - helps to eliminate nuisance trips or unnecessary shutdowns
Caution
Installation of the ICM450 shall be performed by trained technicians only. Adhere to all local and national electric codes. Disconnect all power to the system before making any connections.
Installation
1. Using (2) #8 screws, mount the ICM450 in a cool, dry, easily accessible location in the control panel. 2. Connect voltage as shown in Figure 1 (below). Leave existing line and load side connections intact on the contactor. 3. Load side monitoring is optional (unit may be used to monitor line side only). Wire the contactor and optional control voltage monitoring as in Figures 2 and 3 (below). Note: Load/line wire must be rated for 3-phase voltage rating, 20ga minimum. 4. Upon application of power, the ICM450 will be on line and will begin to monitor the system.
Figure 1
Incoming 3-phase voltage from load or back side of contactor (optional)
Incoming 3-phase voltage from line or front side of contactor The incoming 3-phase voltage is used to power up the ICM450 as well (190-600)
Terminals 1 and 3 are the control signal input terminals Control Mode is turned ON or OFF in setup 6 5 4 With Control Mode set to ON, there must be a 3 voltage present on terminals 1 and 3 for the relay output terminals 4 and 6 to close; this voltage can be supplied from a thermostat, pressure switch, etc. When the voltage on these terminals is re-applied, * Switch can be the unit will not re-energize until the delay on break a thermostat, pressure (0-10 minutes) time has elapsed switch, etc. Use of terminals 1 and 3 is optional; they will be Control Voltage (18-240 VAC) ignored if the Control Mode is set to OFF
Figure 2
1
Figure 3
6 5 4 3 1
Terminals 4 and 6 are dry, normally open contacts Terminals 4 and 6 are closed when power is within specifications Terminals 4 and 6 open when there is a fault condition or loss of control signal
3-Pole Contactor
LI2 LI3 LOAD LOAD LOAD 3 2 1
Button Functions
Press arrows to scroll through and select user parameter settings in Setup mode. HOLD down for fast edit.
Press to read faults. Hold for 5 seconds to clear faults and reset memory.
Parameters
Parameter Line Voltage Delay On Break
Fault Interrogation
Description
Average phase to phase line voltage
Range
190-600
Default 208
.1 minute 15 seconds 20%
Amount of time between 0-10 the load de-energizing and minutes re-energizing Amount of time before 0-15 the load de-energizes due seconds to a non-critical fault* 2-25%
7-8 seconds**
% Maximum/minimum phase Over/Under to phase average voltage, Voltage respectively % Phase Unbalance Reset Mode Amount of allowable voltage unbalance AUTO or number of times the load can be re-energized after a load side fault before a manual reset is necessary Note: When monitoring line side only, the reset mode will always be AUTO With control mode set to OFF, the load will energize if no 3- phase fault conditions exist; with control mode ON, the load will energize if no fault conditions exist and control voltage is present at terminals 1 and 3 of the ICM450
12-15%**
20% AUTO
4-5%** AUTO
Control Mode
ON or OFF
ON
Based on wiring
* Non-critical faults are faults such as High/Low Voltage and Phase Unbalance. Critical faults, such as Phase Loss and Phase Reversal, have a fault interrogation of under 2 seconds and it is not user adjustable. ** For best recommendations, consult manufacturer of equipment.
Fault Conditions
Press and release fault button to scroll through all saved faults. Note: For initial setup, press and hold FAULT for 5 seconds to remove any previously stored faults. Fault
Back Phase Loss
Problem
Corrective Action
Not all three of the 1. Re-energize the contactor. phases on the load side 2. If the fault reappears after the load energizes: are present a. Turn all power OFF b. Check all load side connections c. Check the contacts of the contactor for debris or excess carbon. Loads 1, 2, or 3 are not 1. Turn OFF all power. in sequence (not 120 2. Swap any 2 phases on the load side of the phase shifted) ICM450 only (example: swap load 1 and load 2) * 3. Re-apply power. A voltage unbalance 1. Press the READ button to observe the present between the three load load voltages. Check system for unbalance cause. phases exceeds the 2. Increase the fault interrogation time if necessary. unbalance setpoint 3. Increase the percent unbalance setting if necessary. Average phase-phase voltage exceeds the maximum percentage Not all three of the phases on the line side are present 1. Check system for over-voltage cause. 2. Increase the percent over-voltage setting if necessary. 3. Increase the fault interrogation time if necessary. 1. Press and hold the READ button on the phase monitor or use an AC voltmeter to carefully measure all three phase-phase line voltages (example: Line 1 Line 2, Line 2 Line 3, Line 3 Line 1). 2. Repair the missing phase. 1. Turn OFF all power. 2. Swap any 2 phases on the line side of the ICM450 (example: swap load 1 and load 2)* 3. Re-apply power. 1. Press the READ button to observe the present load voltages. Check system for unbalance cause. 2. Increase the fault interrogation time if necessary. 3. Increase the percent unbalance setting if necessary. 1. Check system for under-voltage cause. 2. Increase the percent under-voltage setting if necessary. 3. Increase the fault interrogation time if necessary.
Lines 1, 2, or 3 are not in sequence (not 120 phase shifted) A voltage unbalance between the three line phases exceeds the unbalance setpoint Average phase-phase voltage is below the minimum percentage
* Only swap phases during initial setup, not after the ICM450 has been in operation without errors.
Troubleshooting
Problem
Load will not energize
LCD Readout
Phase Avg.
LED Status
All LEDs Off
Corrective Action
Confirm that the control input (terminals 1 & 3) is properly connected and configured (see Pages 1 and 3) Press FAULT to observe the current fault; correct the condition of the first fault that appears (see Fault Conditions, Page 4 for a list of corrective actions) Indicates there are faults saved in the memory, press FAULT rapidly to scroll through saved faults; to clear the faults, press and hold FAULT for more than 5 seconds The control mode setting is OFF; press SETUP to get to the control mode. Press to set the control mode ON To exit the setup mode, press either READ or FAULT
Phase Avg.
Fault LED blinks repeatedly while load is energized Load will not de-energize when control voltage is OFF Setup LED is on while load is being energized Load will not energize
Phase Avg.
Phase Avg.
Unit in lockout; maximum number of retries in manual reset mode has been reached; to reset unit, press FAULT and hold for more than 5 seconds Fix load side fault; press FAULT to observe condition; the delay on break period may be too short; press SETUP to enter the delay on break mode; press to lengthen the delay
Readout is Irrelevant
7 William Barry Blvd., North Syracuse, NY (Toll Free) 800-365-5525 (Phone) 315-233-5266 (Fax) 315-233-5276 www.icmcontrols.com