Variable
Variable
Variable
Application Notes
Application principle
Chilled water supply temperatures typically range from 5 - 10C and the return water temperature is 5 - 10C higher. This temperature increase - resulting from the air conditioning load - is the key parameter for the variable flow system, also called delta T. Once the delta T is selected, all equipment must be designed to operate within that range. This means the chillers, air handling unit coils, and the control valves. Chilled water plants are generally one of two types: variable flow or constant flow. To reduce installation and operation costs, it is best to vary the chilled water flow throughout the building. Doing this allows the delta T to remain constant also during partial load conditions. The main circulating pump must be a variable flow pump. Multiple pumps can be staged on, but variable speed AC drives are more commonly used.
Detailed description
This system for the space cooling of several rooms has chilled water circulating through an air terminal device (6.) and thermostat controlled valve (5.) in each room. The return water is circulated by a chiller water pump (1.) through the chiller evaporator (3.). The water temperature is reduced by 5 to 10C in the evaporator and it is then supplied back to the rooms. The variable water circulation is achieved by the AC drive (2.), and the control parameter is the differential water pressure in the most distant room in order to keep the pressure high enough for the thermostat valves. The differential pressure is measured by the transmitter (4.).
ABB Oy Drives PO Box 184 FIN-00381 Helsinki, Finland Tel: +358 10 2211 Fax: +358 10 222 2287 www.abb.com/motors&drives e-mail: [email protected]