Module 1
Module 1
2012
www.PDHcenter.com
www.PDHonline.org
Module 1 -
Page 1
www.PDHcenter.com
www.PDHonline.org
Overview
This module provides an introduction to power systems. It discusses a basic structure of power systems, the fundamentals of AC circuits, mathematical notations, balanced three-phase systems and per unit values.
This basic structure of a power system is shown in Figure 1-1. The generator converts nonelectrical energy to electrical energy. The devices connecting generators to transmission
Generation
G 13.8:115 kV
Transmission
Distribution
115:12 kV
Fig. 1-1. A basic structure of a simplified power system. system and from transmission system to distribution system are transformers. Their main functions are stepping up the lower generation voltage to the higher transmission voltage and stepping down the higher transmission voltage to the lower distribution voltage. The main advantage of having higher voltage in transmission system is to reduce the losses in the grid. Since transformers operate at constant power, when the voltage is higher, then the current has a lower value. Therefore, the losses, a function of the current square, will be lower at a higher voltage.
Module 1 -
Page 2
www.PDHcenter.com
www.PDHonline.org
DC vs. AC
The current of a direct current (DC) circuit, as shown in Figure 1-2, consisting of a battery and a pure resistive load can be calculated as
I DC = VDC , R
2 VDC = I2 R , DC R
PDC = VDC I DC =
where
IDC = DC current in Amperes (A), VDC = DC voltage in Volts (V), PDC = DC power in Watts (W), and R = the load resistance in Ohms (). The voltage and current waveforms are shown in Figure 1-3.
IDC
VDC + -
V, I VDC IDC t
Module 1 -
Page 3
www.PDHcenter.com
www.PDHonline.org
Example 1-1: A DC circuit, as shown in Figure 1-2, has a DC voltage of 12 volts and a resistor of 2 . What are the DC current in the circuit and the power consumed by the resistor? Solution:
I DC =
12 = 6 (A) 2
PDC = 12 6 = 72 (W) It is worth mentioning that these DC quantities are real numbers not complex numbers.
There is another category of circuits, the alternating current (AC) circuits. Since in power systems the sinusoidal voltages are generated, and consequently, most likely sinusoidal currents are flowed in the generation, transmission and distribution systems, sinusoidal quantities are assumed throughout this material, unless otherwise specified. In general, a set of typical steady-state voltage and current waveforms of an AC circuit can be drawn as shown in Figure 1-4, and their mathematical expressions can be written as follows:
v (t ) = Vm cos(t ) ,
and
i (t ) = I m cos(t + ),
where Vm, Im = the peak or the maximum values of the voltage and current waveforms, = angular frequency in radians/second, and
Vm
Period
Fig. 1-4. Typical voltage and current waveforms The period in Figure 1-4 can be 360 or 2. In some cases, the period can be in time, for instance, 0.016667 second for 60 Hz.
Module 1 -
Page 4
www.PDHcenter.com
www.PDHonline.org
There is an important quantity called root mean square value, or rms, and is defined as
Vrms = 1 T 2 v (t )dt . T 0
For a sinusoidal voltage, its rms value equals Vrms = 1 T [Vm cos(t )]2 dt = T 0
2 Vm T
1 + cos 2t d (t ) = 2
2 Vm t sin 2t Vm 2 + 4 = 2 . 2 0
For example, a typical household voltage of 120 volts is rms value, and its peak value is 120 2 = 170 volts. Since the frequency in U.S. is 60 Hertz (Hz), the angular frequency = 2 60 = 377 . Such a voltage can be expressed as
Phasor Representations
It may not be convenient to express the voltages and currents in instantaneous forms all the time. As utilized in AC circuits, phasor representations are used in power systems because of convenience. Recall Eulers identity
e j = cos + j sin .
Then, the current can be re-written as
Im 2
e j e jt ) = 2 Re(Ie jt ) ,
where I is defined as the phasor (or polar) representation of i(t), and is a complex number in general. It has two parts, the magnitude and phase angle, namely,
I = I I =
Im 2
= I ,
where I is the rms value of the current, and the subscript rms is commonly neglected. Figure 1-5 shows the graphical representation of I . The direction of the phase angle is defined as counterclockwise for a positive value, and clockwise for a negative value.
Module 1 -
Page 5
www.PDHcenter.com
www.PDHonline.org
Imaginary Axis
I = I
I sin
I cos
Real Axis
Fig. 1-5. A graphical representation of I . From Figure 1-5, it is obvious that a phasor can be expressed not only in a polar form but also in a rectangular form, namely, I = I = I cos + jI sin . One of the advantages of using phasor representations instead of instantaneous forms is that one can add sinusoidal functions of the same frequency by expressing them as phasors and then adding the phasors by the rules of vector algebra. More information on the phasor (or polar) representation can be found in the Appendix 1A. Example 1-2: What are the phasor representations of the following instantaneous quantities? v(t ) = 170 cos(377t ) volts, and i (t ) = 85 cos(377t + 30) amps Solution: V= 170 2 85 2 0 = 1200 volts
I=
30 = 60.130 amps
Unlike in DC circuits, the loads in AC circuits, as shown in Figure 1-6, can be expressed as its impedance, consisting of resistance R and reactance X, as follows
Z=
where
V 1 = R + (jL + ) = R + j(X L X C ) = R + jX = Z , I jC
Z = R 2 + X2 ,
and
= tan 1 ( ) .
X R
Module 1 -
Page 6
www.PDHcenter.com
www.PDHonline.org
+
V
L
Z
Fig. 1-6. RLC circuit. Example 1-3: A 60 Hz 120 volts AC voltage source is connected to a 10 resistor, a 31.83 mH inductor and 1326.26F capacitor, as shown in Figure 1-6. Find The total impedance Z . (1) (2) The current I in polar form. The voltage and current in instantaneous forms. (3) Solution: (1) Since the frequency is 60 Hz, the inductive and capacitive reactances can be obtained as
X L = L = 377 31.83 10 3 = 12
XC = 1 1 = = 2 C 377 1326.26 10 6
( 10
10 + 10 2 tan 1 = 10 245 10
(2) To calculate the current, the angle of the voltage is set to be the reference, namely, 0. Then,
I=
v(t ) = 120 2 cos(377t ) = 170 cos(377t ) volts i(t ) = 8.485 2 cos(377t 45) = 12 cos(377t 45) amps
When the imaginary part of the impedance is positive, the load is called an inductive load, and the current lags the voltage. On the other hand, if the imaginary part of the impedance is negative, the load is called a capacitive load, and the current leads the voltage.
Module 1 -
Page 7
www.PDHcenter.com
www.PDHonline.org
and
i (t ) = 2 I cos(t i ) .
i(t) + A v(t) B
Fig. 1-7. Power transfer between two systems. Then, the instantaneous power from A to B is the product of v(t) and i(t) as follows
p (t ) = v(t )i (t ) = 2VI[cos(2t v i ) + cos( v i )] .
The real power or the active power is defined as the average of the instantaneous power in one period
P=
where the angle = v i , and is defined as the phase angle of the current lags the voltage. The complex power S from A to B can be calculated as
(VA),
Module 1 -
Page 8
www.PDHcenter.com
www.PDHonline.org
Q = Im{ S } = VI sin , is the reactive power in voltamperes reactive (var). Furthermore, can be expressed in Polar form as follows
S=
(P
Q + Q 2 tan 1 = S . P
The magnitude of the complex power is defined as the apparent power S = S = VI = P 2 + Q 2 (VA).
A graphical presentation of complex power, active power and reactive power is called a power triangle (or P-Q triangle), as shown in Figure 1-8. It is worth mentioning that these power quantities are directional. For instance, when P is positive, the power flow is as defined, from A to B. If the P is negative, the power flow is actually from B to A.
S = S
jQ
Fig. 1-8. Power (P-Q) triangle. The power factor, pf, is defined as
pf =
P VI cos = = cos . S VI
Therefore, the phase angle is sometimes called the power factor angle. A lagging power factor indicates an inductive impedance and therefore a positive value for . Similarly, a leading power factor implies a capacitive impedance, and therefore a negative value for .
Module 1 -
Page 9
www.PDHcenter.com
www.PDHonline.org
In general, the phase voltages of a balanced three-phase voltage source with positive sequence can be expressed as
v an (t ) = 2V cos(t ) ,
Their waveforms are shown in Figure 1-9. discussed for single-phase systems
Period
Fig. 1-9. Waveforms of phase voltages of balanced three-phase systems. The above notation is obtained with the assumption that the symmetrical voltage source has a positive (or a-b-c) sequence. If a negative (or a-c-b) sequence is assumed, then Vbn leads
Module 1 - Page 10
www.PDHcenter.com
www.PDHonline.org
Therefore, for a wye connected balanced three-phase voltage source, the line-to-line voltages, or line voltages, are 3 times the phase voltages in magnitude and the line voltages are 30 ahead of their coresponding phase voltages. Figure 1-11 shows a graphical presentation of these relationships.
van (t )
ia(t) +
a vab (t )
vbn (t )
ib(t)
- b +
vbc (t )
vca (t )
vcn (t )
ic(t)
- c
Vca
Vcn
Vab = 3Van 30
30
Van
Vbn
Vbc Fig. 1-11. The relationships of phase voltages and line-to-line voltages in a three-phase system with wye configuration.
Module 1 - Page 11
www.PDHcenter.com
www.PDHonline.org
As one can see from the Figure 1-10, the phase currents are the same as the line currents for a wye connected voltage source. The other configuration of the three-phase voltage source is to connect them in a delta configuration, as shown in Figure 1-12. As one can see, the phase voltages are the same as their corresponding line voltages in such a delta configuration. However, the line currents and phase currents are different, and their relationships can be derived similar to the voltage relationships in a wye configuration, namely, at node a by Kichhoffs current law (KCL- the sum of all phasor currents into any nodes in a circuit equals zero)
I a = I ab I ca = I0 I120 = I[1 (0.5 + j0.866)] = 3I 30 = 3I ab 30 .
Similarly, at nodes b and c, the other two line currents can be obtained as follows
I b = 3I 150 = 3I bc 30 , I c = 3I90 = 3I ca 30 .
Therefore, for a delta connected balance three-phase voltage source, the line currents are 3 times the phase currents in magnitude and the line currents are 30 behind of their coresponding phase currents. Figure 1-13 shows a graphical presentation of these relationships. ia(t) a
+ iab(t) ib(t) ibc(t) ic(t) c b
vab (t )
+
vca (t )
+ ica(t) vbc (t )
Ica
- 30
Iab
Ib
I bc
Ia = 3Iab 30
Fig. 1-13. The relationships of phase currents and line currents in a three-phase system with delta configuration.
Module 1 - Page 12
www.PDHcenter.com
www.PDHonline.org
A balanced three-phase system has their phase/line voltages mutually shifted by 120, and their phase/line currents has the same property. Since it is balanced, the power for each phase is the same, for instance, the per phase complex power
San = Sbn = Scn = S1 ,
or
Sab = Sbc = Sca = S1 .
Therefore, the three-phase complex power equals three times of its per phase value, namely,
S3 = 3S1 = 3V I ,
where V and I are the phase voltage and the phase current, respectively. As discussed earlier, for a wye connected voltage source, the magnitude of the line voltage is 3 times of the phase voltage, while the line and phase current are the same. Therefore, the three-phase apparent power is equal to
S3 = 3V I = 3
VL 3
I L = 3VL I L ,
where VL and I L are the rms values of the line voltage and line current, respectively. This equation can be applied to a delta connected source as well. Then, the three-phase active power, reactive power and power factor can be obtained as follows P3 = 3V I cos = 3VL I L cos , Q 3 = 3V I sin = 3VL I L sin , and
pf 3 = P3 S3 = P1 S1 = cos .
Example 1-4: A balanced three-phase load of 50 kVA, pf = 0.85 lagging is supplied from a balanced three-phase wye connected voltage source of positive sequence such that VL = 4157 volts. Calculate: (1) I L , V and I . (2) S3 , P3 and Q 3 . Solution: (1) V =
VL 3
4157 3
= 2400 volts
Module 1 - Page 13
www.PDHcenter.com
www.PDHonline.org
I = I L =
S3 3VL
50 10 3 3 4157
= 6.94 amps
where X can be the power, voltage, current and/or impedance. However, usually the base voltage and base power (VA) are given quantities while the base current and base impedance are to be determined accordingly.
Example 1-5: A motor is rated 4.16 kV and can be operated +/- 10% of its rated voltage (1.1~0.9 pu). What is the range of the operational voltage in kV? Solution: The high limit voltage is 1.1 pu and its actual voltage can be calculated as VHi = 1.1 4.16 = 4.576 kV . Similarly, the low limit voltage is VLo = 0.9 4.16 = 3.744 kV . The motor can be operated in the range of 4.576~3.744 kV.
For single-phase systems: (1) Select S Base,1 = S1 , and VBase,1 = V . Then, I Base,1 =
S Base,1 VBase,1 = S1 V
(2)
, and Z Base,1 =
VBase,1 I Base,1
2 VBase,1
S Base,1
Module 1 - Page 14
www.PDHcenter.com
www.PDHonline.org
(3)
Therefore,
Spu =
Vpu =
I pu =
Z pu =
Once the per unit values are calculated, the actual values can be obtained by multiplying the per unit values with their corresponding base values. Example 1-6: A single-phase system, as shown in Figure 1-6, is given in actual values. Find: (1) IBase and ZBase with selecting SBase = 7.2 kVA and VBase = 120 volts. (2) Vpu , I pu , Z pu , R pu , and X pu . (3) The current in amperes. Solution: 7200 = 60 amps (1) I Base = 120 120 2 =2 Z Base = 7200 (2) Set the voltage as the reference, 0. Then 1200 = 10 pu Vpu = 120 10 + j10 Z pu = = 5 + j5 = R pu + jX pu pu 2 R pu = 5 pu
X pu = 5 pu
= 0.14142 45 pu 5 245 (3) I = I Base I pu = 60 (0.14142 45) = 8.485 45 amps
I pu =
10
Similarly, for three-phase systems: (1) Select S Base,3 = S3 = 3S1 , and VBase,3 = VBase,L = VL = 3V = 3VBase,1 .
Module 1 - Page 15
www.PDHcenter.com
www.PDHonline.org
(2)
Then, I Base,3 =
S Base,1 VBase,1
Z Base,3 =
2 VBase,1
S Base,1
(3)
Therefore,
Spu =
S Actual , S Base,3
VActual , VBase,3 I Actual , and I Base,3 Z Actual . Z Base,3
Vpu =
I pu = Z pu =
From time to time, it is necessary to change the per unit value of the impedance from one base to another. The following equation can be used for this conversion: Z pu(new) VBase(old) = Z pu(old) VBase(new)
2
S Base(new) . S Base(old)
Proof: (Hint: when changing the impedance per unit value from one base to another, its actual value does not change)
2 VBase(old) Z pu(old) 2 S Base(old) VBase(old) S Base(new) =Z = pu(old) 2 VBase(new) S Base(old) VBase(new)
Z pu(new) =
Z Actual Z Base(new)
S Base(new)
Z pu = 0.05 + j0.5
pu on
S Base,3 = 200MVA
and
VBase,L = 138kV . Calculate the new Z pu if new base values for S Base,3 and VBase,L are given as (a) 100MVA, 138 kV (b) 200MVA, 132 kV
Module 1 - Page 16
www.PDHcenter.com
www.PDHonline.org
(c) 100MVA, 132 kV, respectively. Solution: 100 (a) Z pu = (0.05 + j0.5) = 0.025 + j0.25 pu 200 (b) Z pu (c) Z pu
138 = (0.05 + j0.5) = 0.05465 + j0.5465 pu 132 138 100 = (0.05 + j0.5) = 0.02732 + j0.2732 pu 132 200
2
Example 1-8: A three-phase equipment is rated at 800 kVA, 12 kV and has an impedance of 0.005+j0.1 pu referred to its ratings. Calculate the impedance in ohms. Solution:
Z pu = Z Actual pu. Z Base,3
Therefore,
Z Actual = Z pu Z Base,3 = (0.005 + j0.1)
(12 10 )
3 2
800 10 3
Module 1 - Page 17
www.PDHcenter.com
www.PDHonline.org
4 = 553.13 . 3 The magnitude is the distance of the complex number to origin, and the angle (or argument) is the counterclockwise angle from the real-axis (0) of the complex number. 3 + j4 =
2 2
1
( 3 + 4 ) tan
ImaginaryAxis
5 4 3 2 1
3+j4
Real-Axis
5 4 3 2 1 1
4 3 2
5 553.13 53.13
Real-Axis
0 1 2 3 4 5 Fig. A2. Polar representation of 3 + j 4 in complex plane. Example A1: Convert 1.15 + j 0.9 into its Polar coordinate. Solution: 0.9 = 1.4603 38.05 1.15 + j0.9 = 1.15 2 + 0.9 2 tan 1 1.15
Module 1 - Page 18
www.PDHcenter.com
www.PDHonline.org
Example A2: Convert 1030 into its trigonometric form. Solution: 10 30 = 10 (cos30 + jsin30 ) = 10(0.866 + j0.5 ) = 8.66 + j5
Example A3: Adding 1030 and 1.15 + j 0.9 and express the sum in trigonometric form and polar form. Solution: The sum in trigonometric form:
Module 1 - Page 19