1794-FLEX IO High-Density Analog Modules
1794-FLEX IO High-Density Analog Modules
1794-FLEX IO High-Density Analog Modules
Allen-Bradley, Rockwell Automation, FLEX I/O, DeviceNet, and TechConnect are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies.
ii
Table of Contents
Preface
Who Should Use this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . v Purpose of this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . v About the Vocabulary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . v Related Documentation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . vi Common Techniques Used in this Manual. . . . . . . . . . . . . . . . . . . . . . vii
Chapter 1 Overview of FLEX I/O and Your Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 The FLEX I/O System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Analog Module
Types of FLEX I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 How FLEX I/O Analog Modules Communicate with Programmable Controllers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Physical Features of Your Modules. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Summary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Chapter 3 Write Configuration to and Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Read Status from Your Module Configure Your Analog Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Range Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 Safe State Value Selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 Data Format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 Read Data From Your Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 Map Data for the Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29 Chapter Summary. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
iv
Table of Contents
Appendix A Specifications
Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 Input Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 Output Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36 General Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 Environmental Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 Certification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Appendix C
Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43 Block Transfer Read and Write. . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Index
Publication 1794-UM062A-EN-P -
ber 2012
Preface
Read this preface to familiarize yourself with the rest of the manual. It provides information concerning: who should use this manual the purpose of this manual related documentation conventions used in this manual
You must be able to program and operate an Allen-Bradley programmable controller to make efficient use of your FLEX I/O modules. In particular, you must know how to program block transfers. We assume that you know how to do this in this manual. If you do not, refer to the appropriate programming and operations manual before you attempt to program your modules.
This manual shows you how to use your FLEX I/O Analog modules with Allen-Bradley programmable controllers. The manual helps you install, program and troubleshoot your modules.
For Information About Overview of FLEX I/O and Your Analog Module Install Your FLEX I/O Module Write Configuration to and Read Status from Your Module Communicate With Your Module Specifications Differences Between Series Data Tables Module Programming See Chapter 1 Chapter 2 Chapter 3 Chapter 4 Appendix A Appendix B Appendix C Appendix D
In this manual, we refer to: the analog input or analog output module as the "input module" or "output module" the Programmable Controller as the controller
vi
Related Documentation
The following documents contain additional information concerning Rockwell Automation products. To obtain a copy, contact your local Rockwell Automation office or distributor
Resource 1794 FLEX I/O Product Data, publication 1794-PP019. FLEX I/O ControlNet Redundant Media Adapter, publication 17945.18. FLEX I/O EtherNet/IP Adapter Module Installation Instructions, publication 1794-IN082. ControlNet Adapter Module Installation Instructions, publication 1794-IN101. FLEX I/O DeviceNet Adapter Module Installation Instructions, publication 1794-IN099. Remote I/O Adapter Module User Manual, publication 1794UM009. FLEX I/O PROFIBUS Adapter Module Installation Instructions, publication 1794-IN087. FLEX I/O PROFIBUS Adapter Module User Manual, publication 1794-UM057. FLEX I/O Terminal Base Units Installation Instructions, publication 1794-IN092. Description Information on FLEX I/O general product specifications, certifications, and list of catalogs and descriptions. Information on how to install the FLEX I/O ControlNet Redundant Media Adapter Catalog No. 1794-ACNR. Information on how to install the FLEX I/O EtherNet/IP Adapter Module Catalog No. 1794-AENT. Information on how to install the ControlNet Adapter Modules Catalog No. 1794-ACN15, 1794-ACNR15. Information on how to install the FLEX I/O DeviceNet Adapter Modules Catalog No. 1794-ADN, 1794-ADNK. Information on how to use the Remote I/O Adapter Module Catalog No. 1794-ASB. Information on how to install the FLEX I/O PROFIBUS Adapter Catalog No. 1794-APB. Information on how to use the FLEX I/O PROFIBUS Adapter Module Catalog No. 1794-APB. Information on how to install the FLEX I/O Terminal Base Units Catalog No. 1794-TB2, 1794-TB3, 1794-TB3K, 1794-TB3S, 1794-TB32, 1794-TB3G, 1794-TB3GK, 1794-TB3GS, 1794-TB3T, 1794-TB3TS, 1794-TBN, 1794-TBNK, 1794-TBNF. Information on how to install the FLEX I/O Digital Modules Catalog No. 1794-IB8, 1794-IB16, 1794-IB16K, 1794-IB32. Information on how to install the FLEX I/O Digital DC Sourcing Output Modules Catalog No. 1794-OB8, 1794-OB8EP, 1794-OB16, 1794-OB16P, 1794-OB32P. Information on how to install the FLEX I/O Input and Output Combo Modules Catalog No. 1794-IB16XOB16P, 1794-IB10XOB6. Information on how to install FLEX I/O Analog Modules Catalog No. 1794-IE8/B, 1794-IE4XOE2/B, 1794-OE4/B, 1794-IE8K/B, 1794-OE4K/B. Information on how to install the Thermocouple/Millivolt Input Modules Catalog No. 1794-IRT8, 1794-IRT8K, 1794-IRT8XT. Information on how to use the FLEX I/O 8 Input RTD Module Catalog No. 1794-IR8. Information on how to use the Thermocouple and Millivolt Input Module Catalog No. 1794-IT8. Information on how to install the FLEX I/O AC Input Modules Catalog No. 1794-IA8, 1794-IA8I, 1794-IA16.
FLEX I/O Digital Input Modules Installation Instructions, publication 1794-IN093. FLEX I/O Digital DC Sourcing Output Modules Installation Instructions, publication 1794-IN094. FLEX I/O Input/ Output Module Installation Instructions, publication 1794-IN083. FLEX I/O Input and Output Module Installation Instructions, publication 1794-IN100. Thermocouple/Millivolt Input Module Installation Instructions, publication 1794-IN050. FLEX I/O 8 Input RTD Module User Manual, publication 1794-6.5.4. FLEX I/O Thermocouple/Millivolt Input Module User Manual, publication 1794-6.5.7. FLEX I/O AC Input Modules Installation Instructions, publication 1794-IN102.
vii
Resource FLEX I/O Digital AC Output Modules Installation Instructions, publication 1794-IN103 Interconnect Cable Installation Instructions, publication 1794-5.12 FLEX I/O DC Power Supply Installation Instructions, publication 1794-IN069 Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1 Allen-Bradley Industrial Automation Glossary, AG-7.1
Description Information on how to install the FLEX I/O Digital AC Output Modules Catalog No. 1794-OA8, 1794-OA8K, 1794-OA8I, 1794-OA16. Information on how to install the Interconnect Cable Catalog No. 1794-CE1, 1794-CE3. Information on how to install the FLEX I/O DC Power Supply Catalog No. 1794-PS13, 1794-PS3. In-depth information on grounding and wiring Allen-Bradley programmable controllers. A glossary of industrial automation terms and abbreviations.
The following conventions are used throughout this manual: Bulleted lists such as this one provide information, not procedural steps. Numbered lists provide sequential steps or hierarchical information. Italic type is used for emphasis.
viii
Notes:
Chapter
Overview
Read this chapter to familiarize yourself with configurable features on the FLEX I/O High Density modules. The following table lists where to find specific information in this chapter.
Topic The FLEX I/O System Types of FLEX I/O Modules How FLEX I/O Analog Modules Communicate with Programmable Controllers Physical Features of Your Modules Page 1 2 3 4
FLEX I/O is a small, modular I/O system for distributed applications that performs all of the functions of rack-based I/O. The FLEX I/O system contains the following components shown below:
Terminal base I/O module
20125
adapter/power supply powers the internal logic for as many as eight I/O modules terminal base contains a terminal strip to terminate wiring for two- or three-wire devices I/O module contains the bus interface and circuitry needed to perform specific functions related to your application
The following FLEX I/O analog modules are described in this user manual:
FLEX I/0 Analog Modules Catalog Number 1794-IE8 1794-IE8XT(1) 1794-IE12 1794-OE4 1794-OE4XT(1) 1794-OE12 1794-IE4XOE2 1794-IE4XOE2XT(1) 1794-IE8XOE4 24V DC 8 4 24V DC 24V DC 4 12 2 24V DC 24V DC 12 4 Voltage 24V DC Inputs Outputs 8 Description analog 8 input, single-ended, non-isolated analog 12 input, single-ended, non-isolated analog 4 output, single-ended, non-isolated analog 12 output, single-ended, non-isolated analog 4 input, single-ended, non-isolated and 2 output, single-ended, non-isolated analog 8 input, single-ended, non-isolated and 4 output, single-ended, non-isolated
(1)
Modules with "XT" indicated in the catalog number signify extended temperature modules.
FLEX I/O analog input, output and combination modules are block transfer modules that interface analog signals with any Allen-Bradley programmable controllers that have block transfer capability. Block transfer programming moves input from the modules memory to a designated area in the processor data table, and output data words from a designated area in the processor data table to the modules memory. Block transfer programming also moves configuration words from the processor data table to module memory. The analog modules have selectable ranges as shown in the table below:
Analog Module Selectable Ranges Voltage 010V DC +/- 10V DC Current 020 mA 420 mA
The adapter/power supply transfers data to the module (block transfer write) and from the module (block transfer read) using BTW and BTR instructions in your ladder diagram program. These instructions let the adapter obtain input values and status from the module, and let you send output values and establish the modules mode of operation. The Typical Communication Between the Adapter and a Module figure describes the communication process.
Typical Communication Between the Adapter and a Module
1794-ACN15 1794-ACNR15 1794-ADN 1794-AENT 1794-AENTR MicroLogix 1794-ASB 1794-APB Adapter 1794-AENT shown
FlexBus
TC RTD INPUT 8 CHANNEL
1794-IRT8
LOCAL FAULT
4 The adapter receives data from the modules and stores it in the data table.
3
IN 0 F IN 1 F IN 2 F IN 3 F IN 4 F IN 5 F IN 6 F IN 7 F PWR
5 The adapter module determine that the transfer was made without error and input values are within specified range. 6 Your ladder program can use and/or move the data (if valid) before it is written over by the transfer of new data in a subsequent transfer. 7 New configuration data can be sent to the module any time during operation.
3 The module converts analog signals into binary format and stores these values until the adapter requests their transfer.
45316
The module label identifies the keyswitch position, wiring and module type. A removable label provides space for writing individual designations per your application. Indicators are provided to identify input fault conditions, and to show when power is applied to the module.
Module Labels and Indicators
1794-IE8 (1794-IE8XT)
Module type Removable label
1794-IE12
Module type
Power on indicator
1794-OE12
Module type Removable label Keyswitch position indicator (#4)
OK
Power on indicator
46060
1794-OE4 (1794-OE4XT)
Module type Removable label
1794-IE4XOE2 (1794-IE4XOE2XT)
Module type Removable label
Power on indicator
1794-IE8XOE4
Module type
Power on indicator
46061
Summary
In this chapter you learned about the FLEX I/O system and the types of analog modules and how they communicate with programmable controllers.
Notes:
Chapter
Overview
This chapter provides you with pre-installation requirements and instructions on how to install your FLEX I/O analog module.
Topic Before You Install Your Module Power Requirements Install the Module Wire the Terminal Base Unit Connect Wiring to the FLEX I/O Module Page 7 7 9 15 16
Before installing your FLEX I/O analog module, you need to: Calculate the power requirements of all modules in each chassis, verify that a suitable enclosure is available for installation of the module, and position the keyswitch on the terminal base.
Power Requirements
The wiring of the terminal base unit is determined by the current draw through the terminal base. Make certain that the current draw does not exceed 10 A.
ATTENTION: Total current draw through the terminal base unit is limited to 10 A. Separate power connections may be necessary.
ATTENTION: Do not daisy chain power or ground from the terminal base unit to any AC or DC digital module terminal base unit.
Methods of wiring the terminal base units are shown in the illustration below.
Daisychain
TC/RTD/mV Module TC/RTD/mV Module TC/RTD/mV Module Analog Module
24V DC
Individual
TC/RTD/mV Module
24V DC 24V DC 24V DC Wiring when total current draw is less than 10A
Analog Module
Analog Module
TC/RTD/mV Module
Analog Module
Combination 24V DC 24V DC Total current draw through any base unit must not be greater than 10A
45318
ATTENTION: Note the following rules for each type of wiring configuration: Daisychain AIl modules must be analog or TC/RTD/mV modules for this configuration. Individual Use this type of configuration for any noisy DC digital I/O modules in your system. Combination All modules powered by the same power supply must be analog modules for the combination type of configuration.
Installation of the analog module consists of: mounting the terminal base unit installing the analog module into the terminal base unit installing the connecting wiring to the terminal base unit If you are installing your module into a terminal base unit that is already installed, proceed to the section, Mount the Analog Module on the Terminal Base Unit, on page 13.
9 8 7 6
1 2 3 4
45319
Make certain that the female FlexBus connector is fully retracted into the base unit.
10
3. Position the terminal base at a slight angle and hooked over the top of the 35 x 7.5 mm DIN rail A (Allen Bradley part number 199-DR1; 46277-3).
9 8 7 6
1 2 3 4
45320
4. Slide the terminal base over tight against the adapter (or proceeding terminal base). Make sure the hook on the terminal base slides under the edge of the adapter (or proceeding terminal base) and the FlexBus connector is fully retracted. 5. Rotate the terminal base onto the DIN rail with the top of the rail hooked under the lip on the rear of the terminal base. Use caution to make sure that the female FlexBus connector does not strike any of the pins in the mating male connector. 6. Press down on the terminal base unit to lock the terminal base on the DIN rail. If the terminal base does not lock into place, use a screwdriver or similar device to open the locking tab, press down on the terminal base until flush with the DIN rail and release the locking tab to lock the base in place.
45321
11
Gently push the FlexBus connector into the side of the adapter (or proceeding terminal base) to complete the backplane connection.
9 8 7 6
0 1 2 3 4
45322
For specific wiring information, refer to the installation instructions for the module you are installing in this terminal base unit. 7. Repeat the above steps to install the next terminal base unit. Ensure that the cover of the FlexBus connector on the last terminal base unit is in place.
If you are installing your module into a terminal base unit that is already installed, proceed to the section, Mount the Analog Module on the Terminal Base Unit, on page 13.
12
Use the mounting kit Cat. No. 1794-NM1 for panel/wall mounting.
1.4 (35.5)
millimeter (inch)
2
9 8 7 0 1 2 3 6 4 7
3
45323
Description Terminal base unit (not included) Adapter module (not included)
To install the mounting plate on a wall or panel: 1. Lay out the required points on the wall/panel as shown in the drilling dimension drawing.
Drilling Dimensions for Panel or Wall Mounting of FLEX I/O
Millimeters (Inches) 35.5 (1.4) 58.5 (2.3) 35.5 (1.4) 58.5 (2.3) 35.5 (1.4)
21 (0.83)
45327
13
3. Mount the mounting plate for the adapter module using two #6 self-tapping screws (18 included for mounting up to 8 modules and the adapter).
IMPORTANT Make certain that the mounting plate is properly grounded to the panel. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
4. Hold the adapter at a slight angle and engage the top of the mounting plate in the indention on the rear of the adapter module. 5. Press the adapter down flush with the panel until the locking lever locks. 6. Position the terminal base unit up against the adapter and push the female bus connector into the adapter. 7. Secure to the wall with two #6 self-tapping screws. 8. Repeat for each remaining terminal base unit.
14
2 1 3 4 5
40231
2. Make certain the FlexBus connector (1) is pushed all the way to the left to connect with the neighboring terminal base or adapter. You cannot install the module unless the connector is fully extended. 3. Make sure the pins on the bottom of the module are straight so they will align properly with the connector in the terminal base unit.
ATTENTION: If you remove or insert the module while the backplane power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
4. Position the module (8) with its alignment bar (7) aligned with the groove (6) on the terminal base. 5. Press firmly and evenly to seat the module in the terminal base unit. The module is seated when the latching mechanism is locked into the module.
15
6. Remove cap plug and attach another terminal base unit to the right of this terminal base unit if required. Make sure the last terminal base has the cap plug in place.
IMPORTANT The adapter is capable of addressing eight modules. Do not exceed a maximum of eight terminal base units in your system.
Wiring to the analog modules is made through the terminal base unit on which the module mounts.
1794-TB2 and 1794-TB3 Wiring
1794-TB3
A B C
0...15 16...33 34, 51
A B C
34 and 50 = 24V DC 35 and 51 = common 16, 33, 38 = chassis ground 4045, 47 = chassis ground
45328
34 and 50 = 24V DC 35 and 51 = common 16 and 33 = chassis ground 4045 = chassis ground
35 and 51 = common 34 and 50 = 24V DC 16 and 33 = chassis ground 4045 = chassis ground
45328
ATTENTION: Total current draw through the terminal base unit is limited to 10A. Separate power connections to the terminal base unit may be necessary.
16
Wiring to the analog module is made through the terminal base unit on which the module mounts. Verify which terminal base units your module is compatible with in table Module and Terminal Base Unit Compatibility on page 16.
Module and Terminal Base Unit Compatibility Module 1794-IE8 1794-IE8XT 1794-IE12 1794-OE12 1794-OE4 1794-OE4XT 1794-IE4XOE2 1794-IE4XOE2XT 1794-IE8XOE4 1794-TB2 1794-TB3 1794-TB3S 1794-TB3G 1794-TB3GS 1794-TB3T Yes Yes No No Yes Yes Yes Yes No Yes Yes No No Yes Yes Yes Yes No No Yes No No No Yes No Yes No No No Yes Yes No No No No Yes No No Yes Yes No No No No Yes No Yes No No No Yes No Yes No 1794-TB3TS No Yes No No No Yes No Yes No TBN No No No No No Yes No No No
2. Connect each channel signal return to: 1794-IE8 the associated terminal on row (B). 1794-OE4 the corresponding terminal on the same row (A). 1794-IE4XOE2 inputs: the associated terminal on row (B); outputs: the corresponding terminal on the same row (A). 3. Connect +24V DC to designated terminals on the 3451 row (C), and 24V common to designated terminals on the 1633 row (B).
ATTENTION: To reduce susceptibility to noise, power analog modules and discrete modules from separate power supplies. Do not exceed a length of 10 m (33 ft) for power cabling.
If daisy chaining the +24V DC power to the next base unit, connect a jumper from terminal 51 on this base unit to terminal 34 on the next base unit. Connect
17
the 24V DC common/return from terminal 33 on this base unit to terminal 16 on the next base unit.
Wire Connections for 1794-TB2, and 1794-TB3 using the 1794-IE8 Module Channel Input 0 Input 1 Input 2 Input 3 Input 4 Input 5 Input 6 Input 7 Signal Type Current Voltage Current Voltage Current Voltage Current Voltage Current Voltage Current Voltage Current Voltage Current Voltage 24V DC common +24V DC power
(1)
1794-TB2 and 1794-TB3 Input A-0 A-1 A-2 A-3 A-4 A-5 A-6 A-7 A-8 A-9 A-10 A-11 A-12 A-13 A-14 A-15 Common Terminal B-17 B-18 B-19 B-20 B-21 B-22 B-23 B-24 B-25 B-26 B-27 B-28 B-29 B-30 B-31 B-32
Wire Connections for 1794-TB2, and 1794-TB3 using the 1794-OE8 Module Channel Output 1 Signal Type Current signal Current common Voltage signal Voltage common Current signal Current common Voltage signal Voltage common Label Markings I RET V RET I RET V RET 1794-TB2 and 1794-TB3 Output A-0 A-1(1) A-2 A-3(1) A-4 A-5(1) A-6 A-7(1)
18
Wire Connections for 1794-TB2, and 1794-TB3 using the 1794-OE8 Module Channel Signal Type Current signal Current common Voltage signal Voltage common Current signal Current common Voltage signal Voltage common 24V DC common +24V
(1) (2)
1794-TB2 and 1794-TB3 Output A-8 A-9(1) A-10 A-11(1) A-12 A-13(1) A-14 A-15(1) B-1633(2)
Terminals 1, 3, 5, 7, 9, 11, 13 and 15 are connected in the terminal base unit. Terminals 1633 are internally connected in the terminal base unit.
19
Wire Connections for 1794-TB2, and 1794-TB3 using the 1794-IE4XOE2 Module Channel Input 0 Input 1 Input 2 Input 3 Output 0 Signal Type Current Voltage Current Voltage Current Voltage Current Voltage Current signal Current common Voltage signal Voltage common Output 1 Current signal Current common Voltage signal Voltage common 24V DC Common +24V DC Power
(1) (2)
1794-TB2 and 1794-TB3 Signal 0 1 2 3 4 5 6 7 8 9(2) 10 11(2) 12 13(2) 14 15(2) Common Terminal 17 18 19 20 21 22 23 24
Terminals 1633 are internally connected in the terminal base unit. Terminals 9, 11, 13, and 15 are internally connected in the module to 24V DC common.
20
4. If daisy chaining +V power to the next terminal base unit, connect a jumper from terminal 50 (+VDC power) on this base unit to the +VDC terminal on the next terminal base unit, and connect a jumper from terminal 51 (-VDC common) on this base unit to the common terminal on the next terminal base unit. 5. If continuing -V common to the next terminal base unit, connect a jumper from terminal 51 (-VDC common) on this base unit to the to the common terminal on the next terminal base unit.
Wire Connections for 1794-TB3G, and 1794-TB3GS using the 1794-IE12 Module Channel Input 0 Input 1 Input 2 Input 3 Input 4 Input 5 Input 6 Input 7 Input 8 Input 9 Input 10 Input 11 Signal Type Current Voltage Current Voltage Current Voltage Current Voltage Current Voltage Current Voltage Current Voltage Current Voltage Current Voltage Current Voltage Current Voltage Current Voltage Label Markings I V I V I V I V I V I V I V I V I V I V I V I V 1794-TB3G and 1794-TB3GS Input A-0 A-1 A-2 A-3 A-4 A-5 A-6 A-7 A-8 A-9 A-10 A-11 A-12 A-13 A-14 A-15 B-19 B-20 B-21 B-22 B-27 B-28 B-29 B-30 C-48 C-46 C39 C-37 B-32 B-31 B-26 B-25 B-24 B-23 B-18 Common Terminal B-17
21
Wire Connections for 1794-TB3G, and 1794-TB3GS using the 1794-IE12 Module Channel Signal Type 24V DC common +24V DC power Chassis ground (Shield)
(1) (2) (3)
Label Markings
1794-TB3G C-35, C-51(1) 1794-TB3GS C-35, C-51 1794-TB3G C-34, C-50(2) 1794-TB3GS C-34, C-50 1794-TB3G B-16, B-33, C-38, C-4045, C-47(3) 1794-TB3GS B-16, B-33, C-38, C-4045, C-47
Terminals C-35 and C-51 are internally connected in the terminal base unit. Terminals C-34 and C-50 are internally connected in the terminal base unit. Terminals B-16, B-33, C-38, C-40 through C- 45, and C-47 are internally connected to chassis ground
Wire Connections for 1794-TB3G, and 1794-TB3GS using the 1794-OE12 Module Channel Output 0 Output 1 Output 2 Output 3 Output 4 Output 5 Output 6 Output 7 Output 8 Output 9 Output 10 Signal Type Current Voltage Current Voltage Current Voltage Current Voltage Current Voltage Current Voltage Current Voltage Current Voltage Current Voltage Current Voltage Current Voltage Label Markings I V I V I V I V I V I V I V I V I V I V I V 1794-TB3G and 1794-TB3GS Output A-0 A-1 A-2 A-3 A-4 A-5 A-6 A-7 A-8 A-9 A-10 A-11 A-12 A-13 A-14 A-15 B-19 B-20 B-21 B-22 B-27 B-28 C-46 C39 C-37 B-32 B-31 B-26 B-25 B-24 B-23 B-18 Common Terminal B-17
22
Wire Connections for 1794-TB3G, and 1794-TB3GS using the 1794-OE12 Module Channel Output 11 Signal Type Current Voltage 24V DC common +24V DC power Chassis ground (Shield)
(1) (2) (3)
Label Markings I V
1794-TB3G C-35, C-51(1) 1794-TB3GS C-35, C-51 1794-TB3G C-34, C-50(2) 1794-TB3GS C-34, C-50 1794-TB3G B-16, B-33, C-38, C-4045, C-47(3) 1794-TB3GS B-16, B-33, C-38, C-4045, C-47
Terminals C-35 and C-51 are internally connected in the terminal base unit. Terminals C-34 and C-50 are internally connected in the terminal base unit. Terminals B-16, B-33, C-38, C-40 through C- 45, and C-47 are internally connected to chassis ground
Wire Connections for 1794-TB2, and 1794-TB3 using the 1794-IE8XOE4 Module Channel Input 0 Input 1 Input 2 Input 3 Input 4 Input 5 Input 6 Input 7 Output 0 Signal Type Current Voltage Current Voltage Current Voltage Current Voltage Current Voltage Current Voltage Current Voltage Current Voltage Current signal Current common Voltage signal Voltage common Label Markings I V I V I V I V I V I V I V I V I RET V RET 1794-TB3G and 1794-TB3GS Input/Output A-0 A-1 A-2 A-3 A-4 A-5 A-6 A-7 A-8 A-9 A-10 A-11 A-12 A-13 A-14 A-15 B-19 B-20 B-21 B-22 C-39 C-37 B-32 B-31 B-26 B-25 B24 B-23 B-18 Common Terminal B-17
23
Wire Connections for 1794-TB2, and 1794-TB3 using the 1794-IE8XOE4 Module Channel Output 1 Signal Type Current signal Current common Voltage signal Voltage common 24V DC common +24V DC power Chassis ground (Shield)
(1) (2) (3)
Label Markings I V I V
1794-TB3G C-35, C-51(1) 1794-TB3GS C-35, C-51 1794-TB3G C-34, C-50(2) 1794-TB3GS C-34, C-50 1794-TB3G B-16, B-33, C-38, C-4045, C-47(3) 1794-TB3GS B-16, B-33, C-38, C-4045, C-47
Terminals C-35 and C-51 are internally connected in the terminal base unit. Terminals C-34 and C-50 are internally connected in the terminal base unit. Terminals B-16, B-33, C-38, C-40 through C- 45, and C-47 are internally connected to chassis ground
Connect Wiring Using a 1794-TB3S, 1794-TB3T, 1794-TB3TS, or 1794-TBN Terminal Base Unit
1. Connect individual input/output wiring to numbered terminals on the 015 row (A) for 1794-TB3S, 1794-TB3T and 1794-TB3TS, or on row (B) for the 1794-TBN as indicated in the following tables. 2. Connect channel common/return to the associated terminal on row (A) or row (B) for the 1794-TB3S, 1794-TB3T and 1794-TB3TS, or on row (C) for the 1794-TBN. For input devices requiring terminal base power, connect the channel power wiring to the associated terminal on row (C). 3. Connect any signal wiring shields to functional ground as near as possible to the module. 1794-TB3T or -TB3TS only: Connect to earth ground terminals C-39C-46. 4. Connect the +V DC power to terminal 34 on the 3451 row (C) and -V common/return to terminal 16 on the (B) row. 5. If daisychaining +V power to the next terminal base, connect a jumper from terminal 51 (+V DC) on this base unit to terminal 34 on the next base unit.
24
6. If continuing DC common (-V) to the next base unit, connect a jumper from terminal 33 (common) on this base unit to terminal 16 on the next base unit.
Wire Connections for 1794-TB3S, 1794-TB3T and 1794-TB3TS using the 1794-IE8XT Module Channel Signal Type Label Markings 1794-TB3S 1794 -TB3S, -TB3T, -TB3TS Input Input 0 Input 1 Input 2 Input 3 Input 4 Input 5 Input 6 Input 7 24V DC common +24V DC power Chassis ground (Shield)
(1)
1794-TB3S
1794 -TB3T -TB3TS Shield C-39 C-40 C-41 C-42 C-43 C-44 C-45 C-46
Power(1) C-35 C-36 C-37 C-38 C-39 C-40 C-41 C-42 C-43 C-44 C-45 C-46 C-47 C-48 C-49 C-50
Common Terminal B-17 B-18 B-19 B-20 B-21 B-22 B-23 B-24 B-25 B-26 B-27 B-28 B-29 B-30 B-31 B-32 B-31 B-29 B-27 B-25 B-23 B-21 B-18 B-17
Current Voltage Current Voltage Current Voltage Current Voltage Current Voltage Current Voltage Current Voltage Current Voltage
I V I V I V I V I V I V I V I V
A-0 A-1 A-2 A-3 A-4 A-5 A-6 A-7 A-8 A-9 A-10 A-11 A-12 A-13 A-14 A-15
1794-TB3S Terminals 1633 are internally connected in the terminal base unit. 1794-TB3T, 1794TB3TS- Terminals 16, 17, 19, 21, 23, 25, 27, 29, 31 and 33 are internally connected in the terminal base unit. 1794-TB3S Terminals 3451 are internally connected in the terminal base unit. 1794-TB3T, 1794-TB3TS Terminals 34, 35, 50 and 51 are internally connected in the terminal base unit. 1794-TB3T, 1794-TB3TS Terminals 3946 are internally connected to chassis ground.
25
Wire Connections for 1794-TB3S, 1794-TB3T and 1794-TB3TS using the 1794-OE8XT Module Channel Signal Type Label Markings 1794-TB3S, 1794-TB3T, 1794-TB3TS Output Terminal(1) Output 0 Current Current Voltage Voltage Output 1 Current Current Voltage Voltage Output 2 Current Current Voltage Voltage Output 3 Current Current Voltage Voltage 24V DC common I I RET V V RET I I RET V V RET I I RET V V RET I I RET V V RET A-0 A-1 A-2 A-3 A-4 A-5 A-6 A-7 A-8 A-9 A-10 A-11 A-12 A-13 A-14 A-15 C-46 C-45 C-44 C-43 C-42 C-41 C-40 Shield 1794-TB3T, 1794-TB3TS C-39 1794-TBN Output Terminal(2) B-0 C-1 B-2 C-3 B-4 C-5 B-6 C-7 B-8 C-9 B-10 C-11 B-12 C-13 B-14 C-15
1794-TB3S Terminals 1633 are internally connected in the terminal base unit. 1794-TB3T, 1794TB3TS- Terminals 16, 17, 19, 21, 23, 25, 27, 29, 31 and 33 are internally connected in the terminal base unit. 1794-TB3S Terminals 3451 are internally connected in the terminal base unit. 1794-TB3T, 1794-TB3TS Terminals 34, 35, 50 and 51 are internally connected in the terminal base unit. 1794-TB3T, 1794-TB3TS Terminals 3946 are internally connected to chassis ground.
+24V DC power
1A-1, 3, 5, 7, 9, 11, 13 and 15 are internally connected in the module to 24V DC common. 2C-1, 3, 5, 7, 9, 11, 13 and 15 are internally connected in the module to 24V DC common
26
Wire Connections for 1794-TB3S, 1794-TB3T and 1794-TB3TS using the 1794-IE4XOE2XT Module Channel Signal Type Label 1794 Markings -TB3S, -TB3T, -TB3TS 1794-TB3S 1794-TB3S 1794-TB3T, 1794-TB3TS
Common Terminal Input/Output Power Terminal(2) Terminal(1) Input 0 Input 1 Input 2 Input 3 Output 0 Current Voltage Current Voltage Current Voltage Current Voltage Current Voltage I V I V I V I V I RET V RET Output 1 Current Voltage I RET V RET 24V DC common +24V DC power Chassis ground (Shield)
(1) (2)
A-0 A-1 A-2 A-3 A-4 A-5 A-6 A-7 A-8 A-9 A-10 A-11 A-12 A-13 A-14 A-15
1794-TB3S Terminals 1633 are internally connected in the terminal base unit. 1794-TB3T, 1794TB3TS- Terminals 16, 17, 19, 21, 23, 25, 27, 29, 31 and 33 are internally connected in the terminal base unit. 1794-TB3S Terminals 3451 are internally connected in the terminal base unit. 1794-TB3T, 1794-TB3TS Terminals 34, 35, 50 and 51 are internally connected in the terminal base unit. 1794-TB3T, 1794-TB3TS Terminals 3946 are internally connected to chassis ground.
A-9, 11, 13 and 15 are internally connected in the module to 24V DC common. Use when transmitter requires terminal base power.
Chapter Summary
In this chapter you learned how to install the FLEX I/O analog module in an existing programmable controller system and how to wire to a terminal base unit.
Chapter
Overview
This chapter describes how to configure, read data from, and map data to your FLEX I/O analog module.
Topic Configure Your Analog Module Range Selection Safe State Value Selection Data Format Read Data From Your Module Map Data for the Module Page 27 28 28 28 28 29
Because of the many analog devices available and the wide variety of possible configurations, you must configure your module to conform to the analog device and specific application that you have chosen. The module is configured using a group of data table words that are transferred to the module using a block transfer write instruction. The software configurable features available are: input/output range selection safe state operating value (customer selected analog values the module will maintain in the event of a network communication error)
ATTENTION: PLC-5 family programmable controllers that use 6200 software programming tools can take advantage of the IOCONFIG utility to configure these modules. IOCONFIG uses menu-based screens for configuration without having to set individual bits in particular locations. Refer to your 6200 software literature for details.
28
Range Selection
Individual input channels are configurable to operate with the following voltage or current ranges.
Voltage and Current Ranges Ranges 010V DC / 020 mA 420 mA -10+10V DC Off(1) Bit Settings Configure Select Full Range 0 1 1 0 1 0 1 0
(1)
ATTENTION: If using Series A modules, do not use configure select and full range bit settings of 0. Individual channels revert to 420 mA with bit selections of all zeroes. This could result in unwanted or incorrect action.
You can select individual channel ranges using the designated words of the write block transfer instruction. See the Word/Bit Descriptions for your particular module for word and bit numbers.
You can select the analog values that your output module maintains in the event of a network communication error. When the multiplex control bits (M) are cleared simultaneously by a communication error, (or by the user), the analog outputs automatically switch to the values set in the safe state analog words. This allows you to define a safe operating state for controlled devices which depend on the analog output from the module.
Data Format
The data returned from the analog-to-digital converter in the module is 12-bit resolute. This value is left-justified into a 16-bit field, reserving the most significant bit for a sign bit. The 420 mA mode scales in the module and uses all 16 bits. For more information on values for various current and voltage modes, and an example of scaling to engineering terms, see Module Programming on page 67.
Read programming transmits status and data from the analog module to the processor data table in one I/O scan. The processor user program initiates the request to the transfer data from the analog module to the processor.
29
Read and write words and bit/word descriptions describe the information written to and read from the analog modules. Each word is composed of 16 bits. For a complete list of data for your specific module, see Data Tables on page 43.
Chapter Summary
In this chapter you learned about data and instructions to configure and map your FLEX I/O High-Density Analog Modules.
30
Notes:
Chapter
Overview
Read this chapter to familiarize yourself with configurable features on the input and output analog modules
For Information About About DeviceNet Manager Communication Over the I/O Backplane Polled I/O Structure Defaults See Page 31 31 32 33
DeviceNet Manager is a software tool used to configure your FLEX I/O DeviceNet adapter and its related modules. This software tool can be connected to the adapter via the DeviceNet network. You must know and understand how DeviceNet Manager works in order to add a device to the network. Refer to the DeviceNet Manager software online help for more information on using DeviceNet Manager software.
A FLEX I/O adapter communicates to other network system components over the network. The adapter communicates with its I/O modules over the backplane. The I/O map for a module is divided into read words and write words. Read words consist of input and status words, and write words consist of output and configuration words. The number of read words or write words can be 0 or more. The length of each I/O modules read words and write words vary in size depending on module complexity. Each I/O module will support at least 1 input word or 1 output word. Status and configuration are optional, depending on the module. For example, a 16 point discrete input module will have up to 2 read words and 1 write word.
16-point Discrete Input Module
Delay Time Delay Time
1123
Check the I/O map for each module for the exact mapping.
32
Output data is received by the adapter in the order of the installed I/O modules. The Output data for Slot 0 is received first, followed by the Output data for Slot 1, and so on up to slot 7. The first word of input data sent by the adapter is the Adapter Status Word. This is followed by the input data from each slot, in the order of installed I/O modules. The Input data from Slot 0 is first after the status word, followed by Input data from Slot 2, and so on to slot 7.
FLEX I/O adapter
Read data
Adapter status Slot 0 input data
Network READ
...
Network WRITE
Write data
...
Read Write I/O module slot 0 I/O module slot 1
...
Slot 1
Slot 0
...
...
1 0
46063
33
The adapter input status word bit descriptions are shown in table Word Bit Description on page 33.
Word Bit Description Bit Description I/O module fault Bit 0 1 2 3 4 5 6 7 Node address changed I/O state 8 9 Explanation This bit is set (1) when an error is detected in slot position 0. This bit is set (1) when an error is detected in slot position 1. This bit is set (1) when an error is detected in slot position 2. This bit is set (1) when an error is detected in slot position 3. This bit is set (1) when an error is detected in slot position 4. This bit is set (1) when an error is detected in slot position 5. This bit is set (1) when an error is detected in slot position 6. This bit is set (1) when an error is detected in slot position 7. This bit is set (1) when the node address switch setting has been changed since power up. Bit = 0 idle Bit = 1 run
Possible causes for an I/O module fault are: transmission errors on the FLEX I/O backplane a failed module a module removed from its terminal base incorrect module inserted in a slot position the slot is empty
The node address changed bit is set when the node address switch setting has been changed since power up. The new node address does not take effect until the adapter has been powered down and then powered back up. Until this power cycling occurs, the node address switches will not match the actual node address.
Defaults
Each I/O module has default values associated with it. At default, each module generates inputs/status and expects outputs/configuration.
Module Default Values Module Defaults for: Catalog Number 1794-IE8/B 1794-IE8XT 1794-IE12 1794-OE4/B Description 8-pt Analog Input 8-pt Analog Input 12-pt Analog Input 4-pt Analog Output Factory Defaults Real Time Size Input Output Input Output Default Default Default Default 9 9 13 1 6 6 2 14 8 8 12 0 0 0 1 4
34
Module Default Values Module Defaults for: Catalog Number 1794-OE4XT 1794-OE12 1794-IE4XOE2 1794-IE8XOE4 Description 4-pt Analog Output 12-pt Analog Output 4 in/2 out Analog Combo 8 in/4 out Analog Combo Factory Defaults Real Time Size Input Output Input Output Default Default Default Default 1 1 5 5 9 14 14 10 10 6 0 0 4 4 8 4 13 2 2 5
Factory defaults are the values assigned by the adapter when you: first power up the system, and no previous stored settings have been applied. For analog modules, the defaults reflect the actual number of input words/output words. For example, for the 8 input analog module, you have 9 input words, and 6 output words. You can change the I/O data size for a module by reducing the number of words mapped into the adapter module, as shown in real time size. Real time size is the setting that provides optimal real time data to the adapter module. Analog modules have 15 words assigned to them. This is divided into inputs words and output words. You can reduce the I/O data size to fewer words to increase data transfer over the backplane. For example, an 8 input analog module has 9 words input and 6 words output with factory default. You can reduce the input words to 8 by not using the underrange settings set in Word 9. Likewise, you can reduce the write words to 0, thus eliminating the configuration setting and unused words. For information on using DeviceNet Manager software, refer to the DeviceNet Manager Software help.
Chapter Summary
Appendix A
Specifications
Overview
This Appendix lists all input, output, general and environment specifications, as well as certifications for the following FLEX I/O Analog Modules: 1794-IE8, 1794-IE8XT, 1794-IE12, 1794-OE4, 1794-OE4XT, 1794-OE12, 1794-IE4XOE2, 1794-IE4XOE2XT, 1794-IE8XOE4.
Input Specifications
The following are input specifications for the FLEX I/O analog input and combination modules.
Input Specifications 1794-IE8, 1794-IE8XT, 1794-IE12, 1794-IE4XOE2, 1794-IE4XOE2XT, 1794-IE8XOE4 Analog Input Modules Specification Number of inputs Resolution Voltage Current Conversion type Conversion rate, all channels Input current terminal (user configurable) Input voltage terminal (user configurable) Normal mode rejection ratio voltage terminal current terminal Step response to 63% voltage terminal current terminal 1794-IE12 12 single-ended, non-isolated 320 V/cnt 0.641 A/cnt Successive approximation 8.0 ms 420 mA 020 mA 10V 010V 256 s 1794-IE8XOE4 1794-IE8, 1794-IE8XT 1794-IE4XOE2, 1794-IE4XOE2XT 4 single-ended, non-isolated
8 single-ended, non-isolated
-3 db @ 0.05 Hz; -20 db/decade -52 db @ 50 Hz: -54 db @ 60 Hz -3 db @ 1.5 Hz: -20 db/decade -29 db @ 50 H 1.3 s 0.09 s
-3 db @ 17 Hz; -20 db/decade -10.0 dB @ 50 Hz, -11.4 dB @ 60 Hz -3 db @ 9 Hz; -20 db/decade -15.3 dB @ 50 Hz, -16.8 dB @ 60 Hz 9.4 ms 18.2 ms
35
36
Specifications
Input Specifications 1794-IE8, 1794-IE8XT, 1794-IE12, 1794-IE4XOE2, 1794-IE4XOE2XT, 1794-IE8XOE4 Analog Input Modules Specification Input Impedance Voltage Terminal Current Terminal Absolute accuracy Voltage Terminal Current Terminal Accuracy Drift with Temperature Voltage Terminal Current Terminal Max overload
(1)
1794-IE12
1794-IE8XOE4
1794-IE8, 1794-IE8XT
1794-IE4XOE2, 1794-IE4XOE2XT
> 1 M < 100 (1) 0.1% Full scale @ 25 C 0.1% Full scale @ 25 C
0.00428% Full scale/ C 0.00407% Full scale/ C 30V continuous or 32 mA continuous, one channel at a time
resistance is >1 M.
If 24V DC is removed from the module, input resistance is <100 . This is also true at 0 mA current input, even if there is 24V DC. If there is an input current applied, input
Output Specifications
The following are output specifications for the FLEX I/O analog output and combination modules.
Output Specifications 1794-OE4, 1794-OE4XT, 1794-OE12, 1794-IE4XOE2, 1794-IE4XOE2XT, 1794-IE8XOE4 Specification Number of outputs 1794-OE12 12 single-ended, non-isolated 020 mA 3 mA 320 V/cnt 0.641 A/cnt 0.1% Full scale @ 25% 0.1% Full scale @ 25% 2.56 V/cnt 5.13 A/cnt 0.133% Full scale @ 25% 0.425% Full scale @ 25% 1794-IE8XOE4 1794-OE4, 1794-OE4XT 1794-IE4XOE2, 1794-IE4XOE2XT 2 single-ended, non-isolated
4 single-ended, non-isolated
Output voltage range, nom 10V Output current, max Voltage output current load, max Voltage resolution Current resolution Absolute accuracy Voltage Terminal Current Terminal Accuracy Drift with Temperature Voltage Terminal Current Terminal Resistive load, mA output
Specifications
37
General Specifications
The following are general specifications common to all the FLEX I/O analog modules in this publication.
Output Specifications 1794-OE4, 1794-OE4XT, 1794-OE12, 1794-IE4XOE2, 1794-IE4XOE2XT, 1794-IE8XOE4 Specification Module location 1794-IE12, 1794-OE12, 1794-IE8XOE4 1794-TB3G 1794-TB3GS 1794-IE8, 1794-IE8XT, 1794-OE4, 1794-OE4XT,1794-IE4XOE2, 1794-IE4XOE2XT 1794-TB2 1794-TB3 1794 -TB3S 1794-TB3T 1794-TB3TS For 1794-OE4, 1794-OE4XT only 1794-TBN 1794-IE8, 1794-IE8XT 3 1794-OE4, 1794-OE4XT 4 1794-IE4XOE2, 1794-IE4XOE2XT 5 45.7 x 94.0 x 53.3 mm (1.8 x 3.7 x 2.1 in.) 1 green power indicator
Keyswitch position
1794-IE12 3 1794-OE12 4 1794-IE8XOE4 5 94.0 x 94.0 x 53.3 mm (3.7 x 3.7 x 2.1 in.) None required 1 green/red power/status indicator 16 bit 2s complement, left justified 24V DC 10.031.2V DC (includes 5% AC ripple) 1794-IE12 30 mA @ 24V DC; 45 mA @ 10V DC 1794-OE12 320 mA @ 24V DC; 720 mA @ 10V DC 1794-IE8XOE4 140 mA @ 24V DC; 280 mA @ 10V DC 80 mA 50V continuous Tested at 850V DC for 60 s between user power to system No isolation between individual channels
Dimensions, approx. (HxWxD) Calibration Indicators Data format External DC power supply, nom External DC power supply, voltage range External DC power supply, current
70 mA 60 mA For 1794-IE8, 1794-IE8XT only 50V continuous Tested @ 850V DC for 1 s between user power to system No isolation between individual channels
38
Specifications
Output Specifications 1794-OE4, 1794-OE4XT, 1794-OE12, 1794-IE4XOE2, 1794-IE4XOE2XT, 1794-IE8XOE4 Specification Power dissipation, max. 1794-IE12, 1794-OE12, 1794-IE8XOE4 1794-IE12 1.2 W @ 31.2V DC 1.1 W @ 24V DC 0.9 W @ 10.0V DC 1794-OE12 4.0 W @ 31.2V DC 4.3 W @ 24V DC 4.0 W @ 10.0V DC 1794-IE8XOE4 3.0 W @ 31.2V DC 2.3 W @ 24V DC 2.0 W @ 10.0V DC 1794-IE12 4.1 BTU/hr @ 31.2V DC 1794-OE12 4.7 BTU/hr @ 24V DC 1794-IE8XOE4 10.3 BTU/hr @ 31.2V DC 1794-IE8, 1794-IE8XT, 1794-OE4, 1794-OE4XT,1794-IE4XOE2, 1794-IE4XOE2XT 1794-IE8 3.0 W @ 31.2V DC 1794-OE8 4.5 W @ 31.2V DC 4.0 W @ 31.2V DC
0.342.5 mm2 (2212 AWG) stranded copper wire rated at 75 C 167 F) or higher 4 mm2 (12 gauge) stranded, max For 1794-IE8 and 1794-IE8XT only 1.2 mm (3/64 in.) insulation, max. 2 on signal port 2 on power ports 1794-TB3G and 1794-TB3GS 03791.02 Nm (79 lb-in.) None (open-style) 0.8 Nm (7 lb-in.) 1794-TBN 1.0 Nm (9 lb-in.)
Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring and Grounding Guidelines, publication 1770-4.1.
Specifications
39
Environmental Specifications
The following are the environmental specifications common to all the FLEX I/O analog modules in this publication.
Environmental Specifications Specification Temperature, operating Description IEC 60068-2-1 (Test Ad, Operating Cold), IEC 60068-2-2 (Test Bd, Operating Dry Heat), IEC 60068-2-14 (Test Nb, Operating Thermal Shock): 055 C (32131 F) -2060 C (-40185 F) For 1794-IE12, 1794-OE12 and 1794-IE8XOE4 only IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold), IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat), IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock): 4085 C (40185 F) IEC 60068-2-30 (Test Db, Unpackaged Damp Heat): 595% noncondensing IEC 60068-2-6 (Test Fc, Operating): 5 g @ 10500 H IEC60068-2-27 (Test Ea, Unpackaged shock): Operating 30 g IEC60068-2-27 (Test Ea, Unpackaged shock): Nonoperating 50 g CISPR 11: Group 1, Class A IEC 61000-4-2: 6 kV contact discharges 4 kV contact discharges For 1794-IE8, 1794-OE4, 1794-IE4XOE2 and 1794-IE4XOE2XT only 8 kV air discharges 1794-IE12, 1794-OE12, 1794-IE8XOE4 IEC 61000-4-3: 10 V/m with 1 kHz sine-wave 80% AM from 302000 MHz 10 V/m with 200 Hz 50% pulse 100% AM at 900 MHz 10 V/m with 200 Hz 50% pulse 100% AM at 1890 MHz 3 V/m with 1 kHz sine-wave 80% AM from 22.7 GHz 1794-IE8, 1794-OE4, 1794-IE4XOE2 and 1794-IE4XOE2XT 10V/m with 1kHz sine-wave 80%AM from 30MHz to 1000MHz EFT/B immunity IEC 61000-4-4: 2 kV at 5 kHz on power ports For 1794-IE12, 1794-OE12, 1794-IE8XOE4 only 2 kV at 5 kHz on signal ports
Temperature, nonoperating
Relative humidity Vibration Shock, operating Shock, nonoperating Emissions ESD immunity
Radiated RF immunity
40
Specifications
Environmental Specifications Specification Conducted RF immunity Description 1794-IE12, 1794-OE12, 1794-IE8XOE4 IEC 61000-4-6: 10V/m with 1kHz sine-wave 80%AM from 150 kHz80 MHz 1794-IE8, 1794-OE4, 1794-IE4XOE2 and 1794-IE4XOE2XT IEC 61000-4-6: 10V/m with 1kHz sine-wave 80%AM from 150 kHz30 MHz Surge transient immunity IEC 6100-4-5: 2 kV line-earth (CM) on shielded ports For 1794-IE8, 1794-OE4, 1794-IE4XOE2 and 1794-IE4XOE2XT only
Certification
The following are the certifications common to all the FLEX I/O analog modules in this publication.
Certifications Certifications (when Value product is marked)(1) c-UL-us UL Listed Industrial Control Equipment, certified for US and Canada. See UL File E65584 UL Listed for Class I, Division 2 Group A,B,C,D Hazardous Locations, certified for U.S. and Canada. See UL File E194810. CSA CSA certified Process Control Equipment CSA certified for Class 1, Division 2, Groups A, B, C and D Hazardous locations CE European Union 2004/108/EC EMC Directive, compliant with: EN 61326; Meas./Control/Lab., Industrial Requirements EN 61000-6-2; Industrial Immunity EN 61000-6-4; Industrial Emissions EN 50082-2; Industrial Immunity Australian Radiocommunications Act, compliant with: AS/NZS CISPR 11; Industrial Emissions European Union 94/9/EC ATEX Directive, compliant with: EN 60079-15; Potentially Explosive Atmospheres, Protection "n" (Zone 2)
1) See the Product Certification link at www.ab.com for Declarations of Conformity, Certificates, and other certification details.
C-Tick Ex
(1)
Appendix B
Overview
The following lists major differences between series A and series B of your FLEX I/O analog modules. .
Differences Between Series A and Series B Catalog Number 1794-IE8 1794-OE4 1794-IE4XOE2 Description Power Up bit in Read Word Series A None Series B This bit is set when all bits in the configuration register are 0 unconfigured state). Off position now produces 0V or 0 mA depending on the range selected, until module is configured.
Change to range selection No off position available. Module tables produces either 2V or 4 mA, depending on the range selected, until module is configured. Specifications 1794-OE4 Output current terminal 4 mA output until module is configured 420 mA user configurable 020 mA user configurable 2V output until module is configured 10V user configurable 010V user configurable 4 mA output until module is configured 420 mA user configurable 020 mA user configurable 2V output until module is configured 10V user configurable 010V user configurable CSA certified CSA Class I, Division 2, Groups A, B, C, D certified UL listed
0 mA output until module is configured 420 mA user configurable 020 mA user configurable 0 V output until module is configured 10V user configurable 010V user configurable 0 mA output until module is configured 420 mA user configurable 020 mA user configurable 0 V output until module is configured 10V user configurable 010V user configurable CSA certified CSA Class I, Division 2, Groups A, B, C, D certified UL listed CE marked for all applicable directives
1794-IE4XOE2
41
42
Notes:
Appendix C
Data Tables
Overview
I/O messages are sent to (consumed) and received from (produced) the FLEX I/O modules. These messages are mapped into the processor memory. This appendix lists the default data maps for 1794 FLEX I/O analog modules.
For the default data map of 1794-IE8 Series B and 1794-IE8XT 8 Input Analog Module Image Table Mapping 1794-IE12 12 Input Analog Module Image Table Mapping 1794-OE4 Series B and 1794-OE4XT 4 Output Analog Module Image Table Mapping 1794-OE12 12 Output Analog Module Image Table Mapping 1794-IE4XOE2 Series B and 1794-IE4XOE2XT 4 Input 2 Output Analog Combo Module Image Table Mapping See page 44 47 51 54 57
43
44
Data Tables
1794-IE8 Series B and 1794-IE8XT 8 Input Analog Module Image Table Mapping
Module Image
Input Data Channel 0 I/O Image Input Size 1 to 9 W ords Input Data Channel 1 Input Data Channel 2 Input Data Channel 3 Input Data Channel 4 Input Data Channel 5 Input Data Channel 6 PU Input Data Channel 7 Underrange Configure select Output Size 0 or 1 W o r d Not used Not used Not used Not used Not used
46064
Memory Map 1794-IE8/B and 1794-IE8XT Analog Input Module Decimal Bit Octal Bit 15 17 S S S S S S S S PU C7 Where: 14 16 13 15 12 14 11 13 10 12 09 11 08 10 07 07 06 06 05 05 04 04 03 03 02 02 01 01 00 00 Size Read/Write Words Read Word 0 Read Word 1 Read Word 2 Read Word 3 Read Word 4 Read Word 5 Read Word 6 Read Word 7 U7 C2 C1 C0 F7 U6 F6 U5 F5 U4 F4 U3 F3 U2 F2 U1 F1 U0 F0 Read Word 8 Write Word 0 Write Word 15
Analog Value Channel 0 Analog Value Channel 1 Analog Value Channel 2 Analog Value Channel 3 Analog Value Channel 4 Analog Value Channel 5 Analog Value Channel 6 Analog Value Channel 7 Not used set to zero C6 C5 C4 C3
Not used PU = Power up bit included in series B modules only. U = Underrange bits for 420 mA inputs C = Configure select bit F = Full range bit S = sign bit (in 2s complement)
Data Tables
45
Range Selection Bits 1794-IE8/B and 1794-IE8XT Analog Input Module Channel No. Bit 010V DC /020 mA 420 mA -10+10V DC Off(1) Where:
(1)
Ch 00 F0 00 1 0 1 0 C0 08 (10) 0 1 1 0
Ch 01 F1 01 1 0 1 0 C1 09 (11) 0 1 1 0
Ch 02 F2 02 1 0 1 0 C2 10 (12) 0 1 1 0
Ch 03 F3 03 1 0 1 0 C3 11 (13) 0 1 1 0
Ch 04 F4 04 1 0 1 0 C4 12 (14) 0 1 1 0
Ch 05 F5 05 1 0 1 0 C5 13 (15) 0 1 1 0
Ch 06 F6 06 1 0 1 0 C6 14 (16) 0 1 1 0
Ch 07 F7 07 1 0 1 0 C7 15 (17) 0 1 1 0
When configured to OFF, individual channels will return 000H on Series B modules, and 420 mA on Series A modules.
Word/Bit Descriptions 1794-IE8/B and 1794-IE8XT Analog Input Module Word Read Word 0 Decimal Bit (Octal Bit) Bits 0014 (0016) Bit 15 (17) Read word 1 Bits 0014 (0016) Bit 15 (17) Read word 2 Bits 0014 (0016) Bit 15 (17) Read word 3 Bits 0014 (0016) Bit 15 (17) Read word 4 Bits 0014 (0016) Bit 15 (17) Read word 5 Bits 0014 (0016) Bit 15 (17) Definition Channel 0 analog data 12-bit left justified two's complement number; unused lower bits are zero; 420 mA uses all 16 bits. Channel 0 analog data sign bit. Channel 1 analog data 12-bit left justified two's complement number; unused lower bits are zero; 420 mA uses all 16 bits. Channel 1 analog data sign bit. Channel 2 analog data 12-bit left justified two's complement number; unused lower bits are zero; 420 mA uses all 16 bits. Channel 2 analog data sign bit. Channel 3 analog data 12-bit left justified two's complement number; unused lower bits are zero; 420 mA uses all 16 bits. Channel 3 analog data sign bit. Channel 4 analog data 12-bit left justified two's complement number; unused lower bits are zero; 420 mA uses all 16 bits. Channel 4 analog data sign bit. Channel 5 analog data 12-bit left justified two's complement number; unused lower bits are zero; 420 mA uses all 16 bits. Channel 5 analog data sign bit.
46
Data Tables
Word/Bit Descriptions 1794-IE8/B and 1794-IE8XT Analog Input Module Word Read word 6 Decimal Bit (Octal Bit) Bits 0014 (0016) Bit 15 (17) Read word 7 Bits 0014 (0016) Bit 15 (17) Read word 8 Bits 0007 Definition Channel 6 analog data 12-bit left justified two's complement number; unused lower bits are zero; 420 mA uses all 16 bits. Channel 6 analog data sign bit. Channel 7 analog data 12-bit left justified two's complement number; unused lower bits are zero; 420 mA uses all 16 bits. Channel 7 analog data sign bit. Underrange bits (U) for individual channels (420 mA current input only) Bit 00 corresponds to input channel 0, bit 01 corresponds to input channel 1, and so on. When set (1), indicates either a broken or open input wire, or input current at or below 4 mA. Not used set to 0. Power Up bit included in series B modules only. This bit is always 0 in series A modules. This bit is set to 1 when all bits in the configuration register (write word 0) are 0 (unconfigured state). The configuration register can be cleared by either a reset, or by the user writing all zeroes to it. Full range bits (F) for individual channels Bit 00 corresponds to input channel 0, bit 01 corresponds to input channel 1 and so on. Configure select bits (C) for individual channels Bit 08 corresponds to input channel 0, bit 09 corresponds to input channel 1 and so on. Not used set to 0.
Write word 0
Bits 0007
Data Tables
47
3 4 5 6 7 8 9 10 11 PU FP GF NU Out of Range
EN QS
Reserved Set to 0
Memory Map 1794-IE12 Analog Input Module Decimal Bit Octal Bit 15 17 S S S S S S S S S S S S PU 14 16 13 15 12 14 11 13 10 12 09 11 08 10 07 07 06 06 05 05 04 04 03 03 02 02 01 01 00 00 Size Read/Write Words Read word 0 Read word 1 Read word 2 Read word 3 Read word 4 Read word 5 Read word 6 Read word 7 Read word 8 Read word 9 Read word 10 Read word 11 R8 R7 R6 R5 R4 R3 R2 R1 R0 Read word 12
Analog Value Channel 0 Analog Value Channel 1 Analog Value Channel 2 Analog Value Channel 3 Analog Value Channel 4 Analog Value Channel 5 Analog Value Channel 6 Analog Value Channel 7 Analog Value Channel 8 Analog Value Channel 9 Analog Value Channel 10 Analog Value Channel 11 FP GF NU R11 R10 R9
48
Data Tables
Memory Map 1794-IE12 Analog Input Module Decimal Bit Octal Bit 15 17 EN QS Where: 14 16 0 0 13 15 0 0 12 14 0 0 11 13 0 CAB 10 12 0 09 11 0 C89 08 10 0 07 07 0 C67 06 06 0 05 05 0 C45 04 04 0 03 03 0 C23 02 02 0 01 01 0 C01 00 00 0 Size Read/Write Words Write word 0 Write word 1
PU = Power up bit S = sign bit (in 2s complement) FP = Field power off GF = General fault NU = Not used Rx = Out of range (x = associated channel) EN = Enable QS = Quick step bit allows input filter to be reduced during rapid signal changes Cxx = Configuration Range Selection Bits 1794-IE12 Analog Input Module Range -10+10V DC 420 mA Out of Range < -10.0V or > 10.0V < 4.0 mA or > 20.0 mA Range Setting Set bits for each channel pair 00 = off 01 = 020 mA 10 = 420 mA 11 = 10V Cxx Channel Configuration C01 for channels 0 and 1 C23 for channels 2 and 3 C45 for channels 4 and 5 C67 for channels 6 and 7 C89 for channels 8 and 9 CAB for channels 10 and 11
020 mA Where:
Word/Bit Descriptions 1794-IE12 Analog Input Module Word Read Word 0 Decimal Bit (Octal Bit) Bits 0014 (0016) Bit 15 (17) Read word 1 Bits 0014 (0016) Bit 15 (17) Read word 2 Bits 0014 (0016) Bit 15 (17) Read word 3 Bits 0014 (0016) Bit 15 (17) Definition Channel 0 analog data 12-bit left justified two's complement number; unused lower bits are zero; 420 mA uses all 16 bits. Channel 0 analog data sign bit. Channel 1 analog data 12-bit left justified two's complement number; unused lower bits are zero; 420 mA uses all 16 bits. Channel 1 analog data sign bit. Channel 2 analog data 12-bit left justified two's complement number; unused lower bits are zero; 420 mA uses all 16 bits. Channel 2 analog data sign bit. Channel 3 analog data 12-bit left justified two's complement number; unused lower bits are zero; 420 mA uses all 16 bits. Channel 3 analog data sign bit.
Data Tables
49
Word/Bit Descriptions 1794-IE12 Analog Input Module Word Read word 4 Decimal Bit (Octal Bit) Bits 0014 (0016) Bit 15 (17) Read word 5 Bits 0014 (0016) Bit 15 (17) Read word 6 Bits 0014 (0016) Bit 15 (17) Read word 7 Bits 0014 (0016) Bit 15 (17) Read word 8 Bits 0014 (0016) Bit 15 (17) Read word 9 Bits 0014 (0016) Bit 15 (17) Read word 10 Bits 0014 (0016) Bit 15 (17) Read word 11 Bits 0014 (0016) Bit 15 (17) Definition Channel 4 analog data 12-bit left justified two's complement number; unused lower bits are zero; 420 mA uses all 16 bits. Channel 4 analog data sign bit. Channel 5 analog data 12-bit left justified two's complement number; unused lower bits are zero; 420 mA uses all 16 bits. Channel 5 analog data sign bit. Channel 6 analog data 12-bit left justified two's complement number; unused lower bits are zero; 420 mA uses all 16 bits. Channel 6 analog data sign bit. Channel 7 analog data 12-bit left justified two's complement number; unused lower bits are zero; 420 mA uses all 16 bits. Channel 7 analog data sign bit. Channel 8 analog data 12-bit left justified two's complement number; unused lower bits are zero; 420 mA uses all 16 bits. Channel 8 analog data sign bit. Channel 9 analog data 12-bit left justified two's complement number; unused lower bits are zero; 420 mA uses all 16 bits. Channel 9 analog data sign bit. Channel 10 analog data 12-bit left justified two's complement number; unused lower bits are zero; 420 mA uses all 16 bits. Channel 10 analog data sign bit. Channel 11 analog data 12-bit left justified two's complement number; unused lower bits are zero; 420 mA uses all 16 bits. Channel 11 analog data sign bit.
50
Data Tables
Word/Bit Descriptions 1794-IE12 Analog Input Module Word Read word 12 Decimal Bit (Octal Bit) Bits 0011 (0013) Definition Out of range bits (R) for individual channels Bit 00 corresponds to input channel 0, bit 01 corresponds to input channel 1, and so on. When set (1), indicates out of range. For more details on out of range, see Table Range Selection Bits 1794-IE12 Analog Input Module on page 48. Not used set to 0. General Fault Bit set to 1 if a fault has occurred including: RAM test failure, ROM test failure, reserved bits asserted (bits 120 of the Reserved word and 1512 of the Config word) and EEPROM failure. Field Power Off Bit is set to 1 if the field power is off. This is not an indication of field power that is out of tolerance. Power Up bit This bit is set to 1 when all bits in the configuration register (write word 1) are 0 (unconfigured state). Reserved set to 0. Module Enable bit Set the bit to 1 to enable the module. This will turn the OK LED solid green. Configuration Set the 2 bit pattern that configures a pair of channels for Off, 020 mA, 420 mA, and 10V. For more information, see Table Range Selection Bits 1794-IE12 Analog Input Module on page 48. Set to 0. Quick Step bit Set to 1 to allow input filter to be reduced during rapid signal changes. Ince the signal change is within 1% of FS (that is, 327 counts), filtering is returned to normal.
Bit 14 (16)
Bit 15 (17)
Write word 0
Write word 1
Data Tables
51
1794-OE4 Series B and 1794-OE4XT 4 Output Analog Module Image Table Mapping
46066
Memory Map 1794-OE4/B and 1794-OE4XT Analog Output Module Decimal Bit Octal Bit 15 17 PU S S S S 14 16 13 15 12 14 11 13 10 12 09 11 08 10 07 07 06 06 05 05 04 04 03 03 W3 02 02 W2 01 01 W1 00 00 W0 Size Read/Write Words Read word 0 Write word 0 Write word 1 Write word 2 Write word 3 M3 C3 C2 C1 C0 Not used set to 0 F3 M2 F2 M1 F1 M0 F0 Write word 4 Write word 5 Write words 69 Write word 10 Write word 11 Write word 12 Write word 13
Not used set to 0 Analog Value Channel 0 Analog Value Channel 1 Analog Value Channel 2 Analog Value Channel 3
Not used set to 0 Not used set to 0 Not used set to 0 S S S S Where: Safe State Value Channel 0 Safe State Value Channel 1 Safe State Value Channel 2 Safe State Value Channel 3
PU = Power up bit W = Diagnostic bits for current output wire broken or load resistance high. Not used on voltage outputs. S = Sign bit (in 2s complement) M = Multiplex control C = Configure select bit F = Full range bit
Publication 1794-UM062A-EN-P - September 2012
52
Data Tables
Range Selection Bits 1794-OE4/B and 1794-OE4XT Analog Output Module Channel No. Ch 00 F0 00 420 mA 010V DC /020 mA -10+10V DC Off(1) Where:
(1)
Ch 01 C0 08 (10) 1 0 1 0 F1 01 0 1 1 0 C1 09 (11) 1 0 1 0
Ch 02 F2 02 0 1 1 0 C2 10 (12) 1 0 1 0
Ch 03 F3 03 0 1 1 0 C3 11 (13) 1 0 1 0
0 1 1 0
When configured to OFF, individual channels will return 0V or 0 mA on Series B modules, and 2V or 4 mA on Series A modules.
Word/Bit Descriptions 1794-OE4/B and 1794-OE4XT Analog Output Module Word Read word 0 Decimal Bit (Octal Bit) Bits 0003 Definition Current outputs only When set (1), the wire on the output is broken or the load resistance is too high. Bit 00 corresponds to channel 0, bit 01 corresponds to channel 2, and so on. Not used set to 0. Power Up bit included in series B modules only. This bit is always 0 in series A modules. This bit is set to 1 when all bits in the configuration register (write word 0) are 0 (unconfigured state). The configuration register can be cleared by either a reset, or by the user writing all zeroes to it. Channel 0 analog data 12-bit left justified two's complement number; unused lower bits are zero; 420 mA uses all 16 bits. Channel 0 analog data sign bit. Channel 1 analog data 12-bit left justified two's complement number; unused lower bits are zero; 420 mA uses all 16 bits. Channel 1 analog data sign bit. Channel 2 analog data 12-bit left justified two's complement number; unused lower bits are zero; 420 mA uses all 16 bits. Channel 2 analog data sign bit. Channel 3 analog data 12-bit left justified two's complement number; unused lower bits are zero; 420 mA uses all 16 bits. Channel 3 analog data sign bit.
Write Word 0
Write Word 1
Write Word 2
Write Word 3
Data Tables
53
Word/Bit Descriptions 1794-OE4/B and 1794-OE4XT Analog Output Module Word Write Word 4 Decimal Bit (Octal Bit) Bits 0003 Definition Multiplex control bits for individual channels. These bits control the safe state analog outputs. Bit 00 corresponds to output channel 0, bit 01 corresponds to output channel 1, and so on. 1 = use words 0, 1, 2 or 3 as directed by channel number n 0 = use words 10, 11, 12 or 13 as directed by channel number n When bits 0003 are all cleared (0) simultaneously by a communication error or user choice through the programmable controller program, word 5 full range and configure select bits are preserved at their last setting. Not used set to 0. Full range bits (F) for individual channels Bit 00 corresponds to output channel 0, bit 01 corresponds to output channel 1, and so on. See Range Selection Bits 1794-OE4/B and 1794-OE4XT Analog Output Module on page 52. Not used set to 0. Configure select bits (C) for individual channels Bit 08 corresponds to output channel 0, bit 09 corresponds to output channel 1, and so on. See Range Selection Bits 1794-OE4/B and 1794-OE4XT Analog Output Module on page 52. Not used set to 0. Not used set to 0.
54
Data Tables
PU EN
FP Sn
GF
NU WR
3 4 5 6 7 8 9 10 11 Set to 0 Configuration
46067
Memory Map 1794-OE12 Analog Output Module Decimal Bit Octal Bit 15 17 PU EN S S S S S S S S S S S 14 16 FP S1 13 15 GF S0 12 14 NU 11 13 W1 1 10 12 W1 0 0 09 11 08 10 07 07 06 06 05 05 04 04 03 03 02 02 W2 0 01 01 W1 0 00 00 W0 0 Size Read/Write Words Read word 0 (Reserved) Write word 0 Write word 1 Write word 2 Write word 3 Write word 4 Write word 5 Write word 6 Write word 7 Write word 8 Write word 9 Write word 10 Write word 11
W9 W8 W7 W6 W5 W4 W3 0 0 0 0 0 0 0
WR 0
Analog Value Channel 0 Analog Value Channel 1 Analog Value Channel 2 Analog Value Channel 3 Analog Value Channel 4 Analog Value Channel 5 Analog Value Channel 6 Analog Value Channel 7 Analog Value Channel 8 Analog Value Channel 9 Analog Value Channel 10
Data Tables
55
Memory Map 1794-OE12 Analog Output Module Decimal Bit Octal Bit 15 17 S 0 Where: 14 16 0 13 15 0 12 14 0 11 13 CAB 10 12 09 11 C89 08 10 07 07 C67 06 06 05 05 C45 04 04 03 03 C23 02 02 01 01 C01 00 00 Size Read/Write Words Write word 12 Write words 13
PU = Power up bit FP = Field power bit GF = General fault NU = Not used Wx = Wire off (x = associated channel) EN = Enable outputs S1/S0 = Safe state source - When EN = 0, these bits indicate source of safe state output. WR = Wire-off reset Cxx = Configuration Range Selection Bits 1794-OE12 Analog Output Module Range -10+10V DC 420 mA 020 mA Out of Range 1 <-10.0V or >10.0V Range Setting Cxx(1) Channel Configuration C01 for channels 0 and 1 C23 for channels 2 and 3 C45 for channels 4 and 5 C67 for channels 6 and 7 C89 for channels 8 and 9 CAB for channels 10 and 11
Set bits for each channel pair <4.0mA or >20.0 mA 00 = off <0.0 mA or >20.0 mA 01 = 020 mA 10 = 420 mA 11 = 10V
(1)
Safe State Selection Bits 1794-OE12 Analog Output Module S1/S0 Safe State Select Source S1 0 0 1 S0 0 1 0 Safe State value is in the output words Reserved (Safe State value is in the output words) Clear/Reset the outputs, based on range selected Hold output at its present level Outputs use Safe State value Reserved (Outputs use Safe State value) +10V range Output set to 0V 420 mA range Output set to 4 mA 020 mA range Output set to 0 mA Outputs Hold Last State Safe State Mode Safe State Output Behavior
56
Data Tables
Word/Bit Descriptions 1794-OE12 Analog Output Module Word Read Word 0 Decimal Bit (Octal Bit) Bits 0011 (0013) Bit 12 (14) Bit 13 (15) Bit 14 (16) Bit 15 (17) Definition Wire Off Indicates the wire, for the associated output channel configured for current, has become disconnected or that the load resistance is too high. Not Used. General Fault Bit is set to 1 if there is a fault to the module. Field Power Off Bit is set to 1 if the field power is off. Power Up bit This bit is set to 1 when all bits in the configuration register (write word 1) are 0 (unconfigured state). The configuration register can be cleared by either a reset, or by the user writing all zeroes to it. Not Used. Wire Off Reset when asserted allowes the latched wire-off bits to be cleared. Safe State Source When EN = 0, these bits indicate source of safe state output, see Table Safe State Selection Bits 1794-OE12 Analog Output Module on page 55. Enable Outputs instructs the outputs to go to their commanded level. When EN = 0, the outputs go to the level as directed by S1/S0. Channel 0 analog data 12-bit left justified two's complement number; unused lower bits are zero; 420 mA uses all 16 bits. Channel 0 analog data sign bit. Channel 1 analog data 12-bit left justified two's complement number; unused lower bits are zero; 420 mA uses all 16 bits. Channel 1 analog data sign bit. Channel 2 analog data 12-bit left justified two's complement number; unused lower bits are zero; 420 mA uses all 16 bits. Channel 2 analog data sign bit. Channel 3 analog data 12-bit left justified two's complement number; unused lower bits are zero; 420 mA uses all 16 bits. Channel 3 analog data sign bit. Channel 4 analog data 12-bit left justified two's complement number; unused lower bits are zero; 420 mA uses all 16 bits. Channel 4 analog data sign bit.
Write word 0
Bit 15 (17)
Write word 1
Write word 2
Write word 3
Write word 4
Write word 5
Data Tables
57
Word/Bit Descriptions 1794-OE12 Analog Output Module Word Write word 6 Decimal Bit (Octal Bit) Bits 0014 (0016) Bit 15 (17) Write word 7 Bits 0014 (0016) Bit 15 (17) Write word 8 Bits 0014 (0016) Bit 15 (17) Write word 9 Bits 0007 Definition Channel 5 analog data 12-bit left justified two's complement number; unused lower bits are zero; 420 mA uses all 16 bits. Channel 5 analog data sign bit. Channel 6 analog data 12-bit left justified two's complement number; unused lower bits are zero; 420 mA uses all 16 bits. Channel 6 analog data sign bit. Channel 7 analog data 12-bit left justified two's complement number; unused lower bits are zero; 420 mA uses all 16 bits. Channel 7 analog data sign bit. Channel 8 analog data 12-bit left justified two's complement number; unused lower bits are zero; 420 mA uses all 16 bits. Channel 8 analog data sign bit. Channel 9 analog data 12-bit left justified two's complement number; unused lower bits are zero; 420 mA uses all 16 bits. Channel 9 analog data sign bit. Channel 10 analog data 12-bit left justified two's complement number; unused lower bits are zero; 420 mA uses all 16 bits. Channel 10 analog data sign bit. Channel 11 analog data 12-bit left justified two's complement number; unused lower bits are zero; 420 mA uses all 16 bits. Channel 11 analog data sign bit. Configuration Set range for each channel pair. For more information on range selection bits, see Table Range Selection Bits 1794-OE12 Analog Output Module on page 55. Not Used.
1794-IE4XOE2 Series B and 1794-IE4XOE2XT 4 Input 2 Output Analog Combo Module Image Table Mapping
58
Data Tables
Module Image
I/O Image Input Size Read 0 to 5 Words Input Data Channel 0 Input Data Channel 1 Input Data Channel 2 Input Data Channel 3 PU Output Data Channel 0 Output Data Channel 1 Not used Output Size Write 0 to 4 Words Not used Full Range and Configure Select Not used Not used Not used Not used Not used Not used
46068
OE
Memory Map 1794-IE4XOE2/B and 1794-IE4XOE2XT Analog Combo Module Decimal Bit 15 Octal Bit 17 S S S S PU S S 14 16 13 15 12 14 11 13 10 12 09 11 08 10 07 07 06 06 05 05 04 04 03 03 02 02 01 01 00 00 Size Read/Write Words Read word 1 Read word 2 Read word 3 Read word 4 W1 W0 U3 U2 U1 U0 Read word 5 Write word 1 Write word 2 OE1 OE0 Write word 3 C4 C3 C2 C1 C0 0 0 F5 F4 F3 F2 F1 F0 Write word 4 Write word 510
Analog Value Channel 0 Analog Value Channel 1 Analog Value Channel 2 Analog Value Channel 3 Not used set to 0 Analog Data Output Channel 0 Analog Data Output Channel 1 C5
PU = Power up bit included in series B modules only. W = Diagnostic bits for current output wire broken or load resistance high. (Not used on voltage outputs.) U = Underrange bits for 420 mA inputs S = Sign bit (in 2s complement) OE = Output enable bits (bit 00 corresponds to output 0, bit 01 corresponds to output 1, and so on. C = Configure select bit F = Full range bit
Data Tables
59
Range Selection Bits 1794-IE4XOE2/B and 1794-IE4XOE2XT Analog Combo Module Channel No. Input Channel 0 F0 Decimal Bits (Octal Bits) 420 mA 010V DC/020 mA -1010V DC Off Where: 00 1 0 1 0 C0 08 (10) 0 1 1 0 Input Channel 1 F1 01 1 0 1 0 C1 09 (11) 0 1 1 0 Input Channel 2 F2 02 1 0 1 0 C2 10 (12) 0 1 1 0 Input Channel 3 F3 03 1 0 1 0 C3 11 (13) 0 1 1 0 Output Channel 0 F4 04 1 0 1 0 C4 12 (14) 0 1 1 0 Output Channel 1 F5 05 1 0 1 0 C5 13 (15) 0 1 1 0
C = Configure select bit F = Full range bit Off = When configured to off, individual channels will return 0V. Word/Bit Descriptions 1794-IE4XOE2/B and 1794-IE4XOE2XT Analog Combo Module Word Read word 1 Decimal Bit Bits 0014 (0016) Bit 15 (17) Read word 2 Bits 0014 (0016) Bit 15 (17) Read word 3 Bits 0014 (0016) Bit 15 (17) Read word 4 Bits 0014 (0016) Bit 15 (17) Read word 5 Bit 0003 Definition Channel 0 analog data 12-bit left justified twos complement number; unused lower bits are zero; 420 mA uses all 16 bits. Channel 0 analog date sign bit. Channel 1 analog data 12-bit left justified twos complement number; unused lower bits are zero; 4...20 mA uses all 16 bits. Channel 1 analog date sign bit. Channel 2 analog data 12-bit left justified twos complement number; unused lower bits are zero; 420 mA uses all 16 bits. Channel 2 analog data sign bit. Channel 3 analog data 12-bit left justified twos complement number; unused lower bits are zero; 420 mA used all 16 bits. Channel 3 analog data sign bit. Underrange bits (U)- for individual channels (4...20mA current inputs only) -Bit 00 corresponds to input channel 0, bit 01 corresponds to input channel 1, and so on. When set (1), indicates either a broken or open input wire, or input current is at or below 4 mA. Wire Off bits (W) Current outputs only When set (1), the wire on the current output is broken or the load resistance is too high. Bit 00 corresponds to input channel 0, bit 01 corresponds to input channel 1, and so on. Not used set to 0. Power Up bit included in series B modules only. This bit is always 0 in series A modules. This bit is set to 1 when all bits in the configuration register (write word 3) are 0 (unconfigured state). The configuration register can be cleared by either a reset, or by the user writing all zeroes to it.
Bits 0405
60
Data Tables
Word/Bit Descriptions 1794-IE4XOE2/B and 1794-IE4XOE2XT Analog Combo Module Word Write word 1 Decimal Bit Bits 0014 (0016) Bit15 (17) Write word 2 Bits 0014 (0016) Bit15 (17) Write word 3 Bits 0001 Bits 0215 (0217) Write word 4 Bits 0005 Bits 0607 Bit 0813 (1015) Definition Channel 0 analog data 12-bit left justified twos complement number; unused lower bits are zero; 4...20mA uses all 16 bits. Channel 0 analog date sign bit. Channel 1 analog data 12-bit left justified twos complement number; unused lower bits are zero; 4...20mA uses all 16 bits. Channel 1 analog date sign bit. Output Enable bits Bit 00 corresponds to output 0, bit 01 corresponds to output 1, and so on. These bits must be set to 1. Not used set to 0. Full range bits (F) for individual channels Bit 00 corresponds to input channel 0, bit 01 corresponds to output channel 1, and so on. Not used set to 0. Configure select bits (C) for individual channels Bit 08 corresponds to input channel 0, bit 09 (11) corresponds to input channel 1, bit 10 (12) corresponds to input channel 2, bit 11 (13) correspoinds to input channel 3, bit 12 (14) corresponds to output channel 0, and bit 13 (15) corresponds to output channel 1. Refer to Range Bit Selections. Not used set to 0. Not used set to 0.
Data Tables
61
EN
3 QS Set to 0 Configuration
46069
Memory Map 1794-IE8XOE4 Analog Combo Module Decimal Bit 15 Octal Bit 17 S S S S S S S S PU EN S S S 14 16 13 15 12 14 11 13 10 12 09 11 08 10 07 07 06 06 05 05 04 04 03 03 02 02 01 01 00 00 Size Read/Write Words Read word 0 Read word 1 Read word 2 Read word 3 Read word 4 Read word 5 Read word 6 Read word 7 W2 0 W1 W0 R7 0 0 0 R6 0 R5 0 R4 0 R3 0 R2 0 R1 0 R0 0 Read word 8 Write word 0 (Reserved) Write word 1 Write word 2 Write word 3
Analog Value Channel 0 Analog Value Channel 1 Analog Value Channel 2 Analog Value Channel 3 Analog Value Channel 4 Analog Value Channel 5 Analog Value Channel 6 Analog Value Channel 7 FP S1 GF S0 NU WR W3 0
Analog Data Output Channel 0 Analog Data Output Channel 1 Analog Data Output Channel 2
62
Data Tables
Memory Map 1794-IE8XOE4 Analog Combo Module Decimal Bit 15 Octal Bit 17 S QS Where: 14 16 0 13 15 0 12 14 0 11 13 CAB 10 12 09 11 C89 08 10 07 07 C67 06 06 05 05 C45 04 04 03 03 C23 02 02 01 01 C01 00 00 Size Read/Write Words Write word 4 Write word 5
PU = Power up bit FP = Field power fault GF = General fault NU = Not used Wx = Wire off (x = associated channel) Rx = Out of range (x = associated channel) EN = Enable outputs S1/S0 = Safe state source - When EN = 0, these bits indicate source of safe state output. WR = Wire-off reset QS = Quick step bit - allows input filter to be reduced during rapid signal changes. Cxx = Channel Configuration (xx = associated channel pair) Range Selection Bits 1794-IE8XOE4 Analog Combo Module Range -10+10V DC 420 mA 020 mA Out of Range 1< -10.0V or > 10.0V Range Setting Cxx Channel Configuration C01 for channels 0 and 1 C23 for channels 2 and 3 C45 for channels 4 and 5 C67 for channels 6 and 7 C89 for channels 8 and 9 CAB for channels 10 and 11
Set bits for each channel pair <4.0 mA or >20.0 mA 00 = off <0.0 mA or >20.0 mA 01 = 020 mA 10 = 420 mA 11 = 10V Cxx = associated channel pair.
Where:
Safe State Selection Bits 1794-IE8XOE4 Analog Combo Module S1/S0 Safe State Select Source S1 0 0 1 S0 0 1 0 Safe State value is in the output words Reserved (Safe State value is in the output words) Clear/Reset the outputs, based on range selected Hold output at its present level Outputs use Safe State value Reserved (Outputs use Safe State value) +10V range Output set to 0V 420 mA range Output set to 4 mA 020 mA range Output set to 0 mA Outputs Hold Last State Safe State Mode Safe State Output Behavior
Data Tables
63
Word/Bit Descriptions 1794-IE8XOE4 Analog Combo Module Word Read Word 0 Decimal Bit (Octal Bit) Bits 0014 (0016) Bit 15 (17) Read word 1 Bits 0014 (0016) Bit 15 (17) Read word 2 Bits 0014 (0016) Bit 15 (17) Read word 3 Bits 0014 (0016) Bit 15 (17) Read word 4 Bits 0014 (0016) Bit 15 (17) Read word 5 Bits 0014 (0016) Bit 15 (17) Read word 6 Bits 0014 (0016) Bit 15 (17) Read word 7 Bits 0014 (0016) Bit 15 (17) Definition Channel 0 analog data 12-bit left justified two's complement number; unused lower bits are zero; 420 mA uses all 16 bits. Channel 0 analog data sign bit. Channel 1 analog data 12-bit left justified two's complement number; unused lower bits are zero; 420 mA uses all 16 bits. Channel 1 analog data sign bit. Channel 2 analog data 12-bit left justified two's complement number; unused lower bits are zero; 420 mA uses all 16 bits. Channel 2 analog data sign bit. Channel 3 analog data 12-bit left justified two's complement number; unused lower bits are zero; 420 mA uses all 16 bits. Channel 3 analog data sign bit. Channel 4 analog data 12-bit left justified two's complement number; unused lower bits are zero; 420 mA uses all 16 bits. Channel 4 analog data sign bit. Channel 5 analog data 12-bit left justified two's complement number; unused lower bits are zero; 420 mA uses all 16 bits. Channel 5 analog data sign bit. Channel 6 analog data 12-bit left justified two's complement number; unused lower bits are zero; 420 mA uses all 16 bits. Channel 6 analog data sign bit. Channel 7 analog data 12-bit left justified two's complement number; unused lower bits are zero; 420 mA uses all 16 bits. Channel 7 analog data sign bit.
64
Data Tables
Word/Bit Descriptions 1794-IE8XOE4 Analog Combo Module Word Read word 8 Decimal Bit (Octal Bit) Bits 0007 Definition Out of range bits (R) for individual channels Bit 00 corresponds to input channel 0, bit 01 corresponds to input channel 1, and so on. When set (1), indicates out of range. For more details on out of range, see Table Range Selection Bits 1794-IE12 Analog Input Module on page 48. Wire Off Indicates the wire, for the associated output channel configured for current, has become disconnected or that the load resistance is too high. Not used set to 0. General Fault Bit set to 1 if a fault has occurred including: RAM test failure, ROM test failure, reserved bits asserted (bits 120 of the Reserved word and 1512 of the Config word) and EEPROM failure. Field Power Off Bit is set to 1 if the field power is off. This is not an indication of field power that is out of tolerance. Power Up bit This bit is set to 1 when all bits in the configuration register (write word 1) are 0 (unconfigured state). Not Used. Wire Off Reset when asserted allowes the latched wire-off bits to be cleared. Safe State Source When EN = 0, these bits indicate source of safe state output, see Table Safe State Selection Bits 1794-IE8XOE4 Analog Combo Module on page 62. Enable Outputs instructs the outputs to go to their commanded level. When EN = 0, the outputs go to the level as directed by S1/S0. Channel 0 analog data 12-bit left justified two's complement number; unused lower bits are zero; 420 mA uses all 16 bits. Channel 0 analog data sign bit. Channel 1 analog data 12-bit left justified two's complement number; unused lower bits are zero; 420 mA uses all 16 bits. Channel 1 analog data sign bit. Channel 2 analog data 12-bit left justified two's complement number; unused lower bits are zero; 420 mA uses all 16 bits. Channel 2 analog data sign bit.
Bit 14 (16)
Bit 15 (17)
Write word 0
Bit 15 (17)
Write word 1
Write word 2
Write word 3
Data Tables
65
Word/Bit Descriptions 1794-IE8XOE4 Analog Combo Module Word Write word 4 Decimal Bit (Octal Bit) Bits 0014 (0016) Bit 15 (17) Write word 5 Bits 0011 (0013) Definition Channel 3 analog data 12-bit left justified two's complement number; unused lower bits are zero; 420 mA uses all 16 bits. Channel 3 analog data sign bit. Configuration Set the 2 bit pattern that configures a pair of channels for Off, 020 mA, 420 mA, and 10V. For more information, see Table Range Selection Bits 1794-IE8XOE4 Analog Combo Module on page 62. Set to 0. Quick Step bit Set to 1 to allow input filter to be reduced during rapid signal changes. Ince the signal change is within 1% of FS (that is, 327 counts), filtering is returned to normal.
66
Data Tables
Notes:
Appendix D
Module Programming
Overview
This Appendix serves as a reference to users of the PLC Processors to program their modules. To initiate communication between the analog input and output modules and your PLC processor, you must enter block transfer instructions into your ladder logic program. Use this chapter to enter the necessary block transfer instructions into your ladder logic program.
Your module communicates with the processor through bidirectional block transfers. This is the sequential operation of both read and write block transfer instructions. A configuration block transfer write (BTW) is initiated when the analog module is first powered up, and subsequently only when the programmer wants to enable or disable features of the module. The configuration BTW sets the bits which enable the programmable features of the module, such as scaling, alarms, ranges, etc. Block transfer reads are performed to retrieve information from the module. Block transfer read (BTR) programming moves status and data from the module to the processors data table. The processor user program initiates the request to transfer data from the module to the processor. The transferred words contain module status, channel status and input data from the module.
ATTENTION: If the analog module is not powered up before the remote I/O adapter, the adapter will not recognize the module. Make certain that the analog module is installed and powered before or simultaneously with the remote I/O adapter. If the adapter does not establish communication with the module, cycle power to the adapter.
The following sample programs are minimum programs; all rungs and conditioning must be included in your application program. You can disable BTRs, or add interlocks to prevent writes if desired. Do not eliminate any storage bits or interlocks included in the sample programs. If interlocks are removed, the program may not work properly. Your program should monitor status bits, block transfer read and block transfer write activity.
The following sample programs show you how to use your analog module efficiently when operating with a programmable controller. These programs show you how to:
Publication 1794-UM062A-EN-P - September 2012
68
Module Programming
configure the module read data from the module update the module output channels (if used) These programs illustrate the minimum programming required for communication to take place.
PLC-2 Programming
The 1794 analog I/O modules are not recommended for use with PLC-2 family programmable controllers due to the number of digits needed for high resolution. In addition, the data returned from the analog-to-digital converter in the module is 12-bit resolute. This value is left-justified into a 16-bit field, reserving the most significant bit for a sign bit.
PLC-3 Programming
Block transfer instructions with the PLC-3 processor use one binary file in a data table section for module location and other related data. This is the block transfer control file. The block transfer data file stores data that you want transferred to your module (when programming a block transfer write) or from your module (when programming a block transfer read). The address of the block transfer data files are stored in the block transfer control file. The same block transfer control file is used for both the read and write instructions for your module. A different block transfer control file is required for every module. A sample program segment with block transfer instructions is shown in FigurePLC-3 Family Sample Program Structure for a 1794-IE8 Module.
Module Programming
69
Pushbutton 2
BTR BLOCK TRANSFER WRITE RACK: 7 GROUP: 0 SLOT: 0 CONTROL: B3:0 DATA FILE: B5:0 LENGTH: 1
Program Action
At power-up in RUN mode, or when the processor is switched from PROG to RUN, the user program enables a block transfer read. Then it initiates a block transfer write to configure the module if the power-up bit is set. Thereafter, the program continuously performs read block transfers.
TIP
You must create the data file for the block transfers before you enter the block transfer instructions.
The pushbutton allows the user to manually request a block transfer write to configure the module.
70
Module Programming
BTR BLOCK TRANSFER WRITE RACK: 7 GROUP: 1 SLOT: 0 CONTROL: B6:0 DATA FILE: B8:0 LENGTH: 14
Program Action
At power-up in RUN mode, or when the processor is switched from PROG to RUN, the user program enables a block transfer read. Then it initiates a block transfer write to configure the module and send data values. Thereafter, the program continuously performs read block transfers and write block transfers.
TIP You must create the data file for the block transfers before you enter the block transfer instructions
ER
BTR BLOCK TRANSFER WRITE RACK: 7 GROUP: 2 SLOT: 0 CONTROL: B9:0 DATA FILE: B11:0 LENGTH: 8 EN DN
ER
Module Programming
71
Program Action
At power-up in RUN mode, or when the processor is switched from PROG to RUN, the user program enables a block transfer read. Then it initiates a block transfer write to configure the module and send data values. Thereafter, the program continuously performs read block transfers and write block transfers.
TIP You must create the data file for the block transfers before you enter the block transfer instructions
PLC-5 Programming
The PLC-5 program is very similar to the PLC-3 program with the following exceptions: block transfer enable bits are used instead of done bits as the conditions on each rung. separate block transfer control files are used for the block transfer instructions.
PLC-5 Family Sample Program Structure for a 1794-IE8 Module
BTR BLOCK TRANSFER READ RACK: 2 GROUP: 1 SLOT: 0 CONTROL: N12:0 DATA FILE: N13:0 LENGTH: 9 CONTINUOUS: N BTW Pushbutton 2 15 Power-up Bit1 B13:8 15
1
EN DN
ER
BLOCK TRANSFER WRITE RACK: 2 GROUP: 1 SLOT: 0 CONTROL: N12:5 DATA FILE: N13:20 LENGTH: 1 CONTINUOUS: N
EN DN
ER
Program Action
At power-up in RUN mode, or when the processor is switched from PROG to RUN, the user program enables a block transfer read. Then it initiates a block transfer write to configure the module if the power-up bit is set.
72
Module Programming
Thereafter, the program continuously performs read block transfers to configure the module. The pushbutton allows the user to manually request a block transfer write.
PLC-5 Family Sample Program Structure for a 1794-OE4 Module
BTR BTR Enable Bit N14:0 1 15 15 BTW Enable Bit N14:5 BLOCK TRANSFER READ RACK: 2 GROUP: 2 SLOT: 0 CONTROL: N14:0 DATA FILE: N15:0 LENGTH: 1 CONTINUOUS: N BTW BTW Enable Bit N14:5 2 15 15 BTR Enable Bit N14:0 BLOCK TRANSFER WRITE RACK: 2 GROUP: 2 SLOT: 0 CONTROL: N14:5 DATA FILE: N15:5 LENGTH: 14 CONTINUOUS: N EN DN EN DN
ER
ER
Program Action
At power-up in RUN mode, or when the processor is switched from PROG to RUN, the user program enables a block transfer read. Then it initiates a block transfer write to configure the module and send data values. Thereafter, the program continuously performs read block transfers and write block transfers.
PLC-5 Family Sample Program Structure for a 1794-IE4XOE2 Module
BTR Block Transfer Read Done Bit B9:0 1 15 BLOCK TRANSFER READ RACK: 7 GROUP: 2 SLOT: 0 CONTROL: B9:0 DATA FILE: B10:0 LENGTH: 5 EN DN
ER
BTR BLOCK TRANSFER WRITE RACK: 7 GROUP: 2 SLOT: 0 CONTROL: B9:0 DATA FILE: B11:0 LENGTH: 8 EN DN
ER
Module Programming
73
Program Action
At power-up in RUN mode, or when the processor is switched from PROG to RUN, the user program enables a block transfer read. Then it initiates a block transfer write to configure the module and send data values. Thereafter, the program continuously performs read block transfers and write block transfers.
TIP You must create the data file for the block transfers before you enter the block transfer instructions
Twos complement binary is used when performing mathematical calculations internal to the processor. To complement a number means to change it to a negative number. For example, the following binary number is equal to decimal 22. 0 101102 = 2210 First, the twos complement method places an extra bit (sign bit) in the leftmost position, and lets this bit determine whether the number is positive or negative. The number is positive if the sign bit is 0 and negative if the sign bit is 1. Using the complement method: 0 10110 = 22 To get the negative using the twos complement method, you must invert each bit from right to left after the first 1 is detected. In the above example: 0 10110 = +22
Its twos complement would be: 1 01010 = 22 Note that in the above representation for +22, starting from the right, the first digit is a 0 so it is not inverted; the second digit is a 1 so it is not inverted. All digits after this one are inverted. If a negative number is given in twos complement, its complement (a positive number) is found in the same way: 1 10010 = 14 0 01110 = +14 All bits from right to left are inverted after the first 1 is detected.
Publication 1794-UM062A-EN-P - September 2012
74
Module Programming
The twos complement of 0 is not found, since no first 1 is ever encountered in the number. The twos complement of 0 then is still 0.
The data returned from the analog-to-digital converter in the module is 12-bit resolute. This value is left-justified into a 16-bit field, reserving the most significant bit for a sign bit.
A/D unipolar data 11 10 09 08 07 06 05 04 03 02 01 00
A n a l o g v a l u e 0* 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
Input
A/D bipolar data S 10 09 08 07 06 05 04 03 02 01 00 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00 11 10 09 08 07 06 05 04 03 02 01 00 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
xxxxx
Output
Analog value S
* = Always positive
Current and Voltage Mode Values Current (mA) 420 mA Mode 020 mA Mode Voltage (V) -10.50 0.00 1.00 2.00 3.00 4.00 5.00 6.00 7.00 8.00 9.00 10.00 11.00 12.00 13.00 14.00 15.00 0000 0787 0F0F 1696 1E1E 25A5 2D2D 34B4 3C3C 43C3 4B4B 52D2 0000 0618 0C30 1248 1860 1E78 2490 2AA8 30C0 36D8 3CF0 4310 4928 4F40 5558 5B70 -10.00 -9.00 -8.00 -7.00 -6.00 -5.00 -4.00 -3.00 -2.00 -1.00 0.00 1.00 2.00 3.00 4.00 5.00 10V Mode Input 8000 8620 9250 9E80 AAB0 B6E0 C310 CF40 DB70 E7A0 F3D0 0000 0C30 1860 2490 30C0 3CF0 Output 8000 8618 9248 9E78 AAA8 B6D8 C310 CF40 DB70 E7A0 F3D0 0000 0C30 1860 2490 30C0 3CF0 0000 0C30 1860 2490 30C0 3CF0 010V Mode
Module Programming
75
Current and Voltage Mode Values Current (mA) 420 mA Mode 020 mA Mode Voltage (V) 16.00 17.00 18.00 19.00 20.00 21.00 5A5A 61E1 6969 70F0 7878 7FFF 6188 67A0 6DB8 73D0 79E8 7FF8 6.00 7.00 8.00 9.00 10.00 10.50 10V Mode Input 4920 5550 6180 6DB0 79E0 7FF0 Output 4928 5558 6188 6DB8 79E8 7FF8 4928 5558 6188 6DB8 79E8 7FF8 010V Mode
Scaling Example
To scale your data to a different range: SLC 500 use the scaling instruction. PLC-5 determine a constant (slope) by dividing the desired prange by the actual range. Multiply the result by your data, and add or subtract any offset.
EXAMPLE
A 420 mA input places data at N13:0 (see figure PLC-5 Family Sample Program Structure for a 1794-OE4 Module on page 72), with a range of 030,840. (30,840 = 7878 hex see table Current and Voltage Mode Values on page 74). You want the 420 mA (030,840) to be 0537.7 C (321000 F) in the PLC-5. Use the following formula:
Scaled Data (degrees) @ N30:0 = {[(Desired Range)/Actual Range] X Analog Input Data} + O ffset = {[(1000 - 32)/30,840] X N13:0} + 32 F8:0 = F8:0 + 32 Scaled Data (degrees) @ N30:0 = F8:0 + 32 (See ladder logic below)
76
Module Programming
instead of a floating point in the first compute instruction. The second compute instruction has a final destination of an integer location.
Index
Numerics
1794-IE12 2 compatibility 16 defaults 33 keyswitch 13 mapping 47 memory map 47 wire connections 20 1794-TB2 22 1794-TB3 22 1794-TB3G 20, 21 1794-TB3GS 20, 21 FlexBus 9, 10, 11, 14 male 9 conventions vii current draw 15 drawn 7 current mode 28
D
daisy chain 7 daisy chaining 16 daisychain wiring 8 data 29 output 32 real time 34 DC common 19 DC power 20, 23 defaults 1794-IE12 33 DeviceNet Manager 31
A
adapter status word 32 address node 33 alignment bar 14 groove 14 analog values 28
B
backplane 31 connection 11 power 14 base unit 14 bidirectional block transfer 67 block transfer bidirectional 67 read 67, 69 write 67, 69
F
fault conditions 4 fault conditions input 4 female connector 9 mating 9 FLEX I/O adapter 31 FLEX I/O system 11 FlexBus 3, 9 connector 9, 10, 11, 14
C
cap plug 14 channel range 28 combination wiring 8 common DC 19 configure select bit 44 connection backplane 11 connector female 9
I
I/O map 31 I/O messages 43 I/O modules 31 Indicators 4 individual wiring 8 input fault conditions 4 status 32 input status word 32 input word 31
Publication 1794-UM062A-EN-P - September 2012
78
Index
K
keyswitch 14 1794-IE12 13 position 4, 13
P
plate mounting 13 PLC processor 67 PLC-2 processor 68 PLC-3 processor 68 PLC-5 processor 71, 75 power DC 20, 23 processor PLC 67 PLC-2 68 PLC-3 68 PLC-5 71, 75 PROG mode 69, 71, 73 purpose of this manual v
L
Labels 4 Latching mechanism 14 locking tab release 10
M
male connector 9 mapping 1794-IE12 47 mating female connector 9 memory map 58 1794-IE12 47 messages I/O 43 mode PROG 69, 71, 73 RUN 69, 71, 73 voltage current 28 Module Labels 4 module input output 31 Modules Indicators 4 mounting plate 13 screw 12 mounting kit 12 mounting plate 12
R
read word 31 real time data 34 related documentation vi release locking tab 10 requirements 7 RUN mode 69, 71, 73
S
screw mounting 12 select bit configure 44 signal type 21 signal wiring 19 status word adapter 32 system FLEX I/O 11
N
node address 33
T
terminal base 9, 13, 33 wiring 7 twos complement 73
Index
79
V
values analog 28 voltage mode 28
W
Wiring module 15 wiring combination 8
daisychain 8 individual 8 input/output 23 terminal base 7 word input 31 output 31 read 31 write 31 write word 31
80
Index
Notes:
Installation Assistance
If you experience a problem within the first 24 hours of installation, review the information that is contained in this manual. You can contact Customer Support for initial help in getting your product up and running.
United States or Canada Outside United States or Canada 1.440.646.3434 Use the Worldwide Locator at http://www.rockwellautomation.com/support/americas/phone_en.html, or contact your local Rockwell Automation representative.
Documentation Feedback
Your comments will help us serve your documentation needs better. If you have any suggestions on how to improve this document, complete this form, publication RA-DU002, available at http://www.rockwellautomation.com/literature/.
Rockwell Otomasyon Ticaret A.., Kar Plaza Merkezi E Blok Kat:6 34752 erenky, stanbul, Tel: +90 (216) 5698400