Eaton Motor Control Basic Wiring
Eaton Motor Control Basic Wiring
Eaton Motor Control Basic Wiring
Technical Data
Table of Contents
Description
M OL OL OL T1 T2 T3
Page 2 3 4 6 6 8 9 10 11 11 11 12 13
L1 AC Lines M L2 M L3
Motor
Stop 1 2
Start A1 3 M
M A2 95
OL 96
Language of Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Circuitry of a Starter . . . . . . . . . . . . . . . . . . . . . . . . . . . . Two-Wire Control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . Three-Wire Control . . . . . . . . . . . . . . . . . . . . . . . . . . . Control Power Transformers . . . . . . . . . . . . . . . . . . . . . . Control Circuit Wiring of CPTs . . . . . . . . . . . . . . . . . . Reversing Starters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cover Control Circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . Start/Stop with Pilot . . . . . . . . . . . . . . . . . . . . . . . . . . Hand/Off/Auto . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Forward/Reverse with 2 Pilots . . . . . . . . . . . . . . . . . . Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Introduction
A Refresher Course for the Product Modier
This text is designed as a refresher course for personnel who will have the responsibility of modifying CutlerHammer products from Eatons electrical business to meet their customers needs. The scope of the material has been necessarily limited. It covers the most commonly used products and wiring schematics. Despite its brevity, you are cautioned not to skim lightly over the content.
TD03309004E
Technical Data
Page 2 Effective: April 2007
Language of Control
Circuit diagrams communicate information quickly and efciently. Every trade and profession has its method of communicating ideas and information quickly and efciently. In addition to the terminology shown in the glossary of this text, diagrams play a vital role of communication in electrical circuits. A knowledge of symbols, diagrams and terminology will aid in our understanding of electrical control. The basic language of control is the circuit diagram. Consisting of a series of symbols interconnected by lines to indicate the ow of current to the various components, it tells in remarkably short time a series of events that would take many words to explain. Circuit diagrams are available in two formats. Wiring diagrams show the connections to the controller. Wiring diagrams, sometimes called main or construction diagrams, show the actual connection points for the wires to the components and terminals of the controller. They show the relative location of the components. They can be used as a guide when wiring the controller. Figure 1 is a typical wiring diagram for a three-phase magnetic starter.
L3
Line diagrams show circuits of the operation of the controller. Line diagrams, also called schematic or elementary diagrams, show the circuits which form the basic operation of the controller. They do not indicate the physical relationships of the various components in the controller. They are an ideal means for troubleshooting a circuit. Figure 2 shows a typical line or schematic diagram.
M L1 AC Lines M L2 M
OL OL OL T1 T2 T3
Motor
Stop 1 2
Start A1 3 M
M A2 95
OL 96
L1 1
L2
L3
A1 M
A2
T1
T2
T3
3-Phase Motor
TD03309004E
Technical Data
Effective: April 2007 Page 3
Symbols
Standardized symbols make diagrams easier to read. Both line and wiring diagrams are a language of pictures. It is not difcult to learn the basic symbols. Once you do, you are able to read diagrams quickly, and can often understand a circuit at a glance. The more you work with both line and wiring diagrams, the better you will become in analyzing them. The American Standards Association (ASA) and the National Electrical Manufacturers Association (NEMA) are the agencies which are responsible for setting up and maintaining the symbol standards. Because of these standards, you will be able to read all diagrams that come across your workbench. Figure 3 shows many of the most commonly used symbols on Control diagrams.
Coils Single Voltage Magnet Coils Dual Voltage Magnet Coils Link 12 34 Time Delay W/Inst. Interlock T.C. T.C. T.O. Low Voltage Contacts Normally Open Limit Switch Normally Open Normally Closed Limit Switch Held Open Limit Switch Normally Closed T.O. Timed Closed T.C. Fuse Indicator Lights Standard Standard R A-Amber R-Red G-Green B-Blue T2 Limit Switch Held Closed Selector Switch Two-Position Jog Run Switches Pushbutton Normally Closed Pushbutton Normally Open TR T.O.
On Contacts and Switches or Pushbuttons, you will nd a designation of NO or NC (Normally Open or Normally Closed). This refers to the state of the contacts when power is not applied to them. In tracing circuits on line diagrams, you will need to visualize the opening or closing of the contacts when the circuit is energized or de-energized. The pushbutton symbols shown in Figure 3 represent Momentary pushbuttons. The contacts will change state from their normal position only for as long as your nger is on the button. Later in this text, we will be working with actual applications and line diagrams. So study these symbols carefully please.
Relays
Thermal Overload OL
98 97 96 Reset 95
Timed Open
Motors AC
Single-Phase
T1
Three-Phase
T1
T2
T3
Technical Data
Page 4 Effective: April 2007
Circuitry of a Starter
The two circuits of a motor starter are the power and control circuits. There are two circuits to a starter the Power Circuit and the Control Circuit. The electricity that passes through the contacts of the starter, through the overload relay, and out to the motor, is called the power circuit. The thick lines of Figure 4 represent this power circuit. It is the power circuit that passes electricity to the motor enabling it to run. For this reason, it is sometimes referred to as the motor circuit. Common Control power and control circuits at same voltage. Separate Control is at different voltages. The thin lines in Figure 4 represent the control circuit. The magnet coil of the starter is energized with this circuit, which creates the electro-magnetic eld that pulls the power circuit contacts closed. The control circuit is separate from the motor circuit. The control circuit may not be at the same voltage as the power circuit. When the voltage of the control and power circuits is the same, it is referred to as Common Control. If the voltages are different, it is called Separate Control. Separate voltages supplied by Control Power Transformers. Another method for supplying separate voltages for power and control circuits, is to use a Control Power Transformer. These are sometimes also referred to as Control Circuit Transformers. One voltage source is used to supply the motor. This same voltage is also supplied to the primary side of the transformer. The transformers secondary supplies the voltage to operate the magnet coil in the control circuit. A more detailed explanation of transformers can be found on Page 8. Common Control is when the power circuit and the control circuit are fed from the same voltage source. Common control is when the control circuit is tied back to lines 1 and 2 of of the starter. It is supplied with the same voltage as the power or motor circuit. The understanding of Common Control and Separate Control becomes signicant when changing magnet coils from one voltage to another. Changing magnet coils from 120V or to 120V involves adding or removing wire C. If you stock starters or contactors with different rated magnet coils, and need to convert the device to a 120V magnet coil for separate control, you must remove the connection to the power circuit that is provided. Figure 5 shows this connection. Wire C is connected to L2 and terminal 96 on the overload relay in all Cutler-Hammer starters supplied with magnet coils greater than 120V. You must remove the wire, and then connect the separate control voltage lines to the number 1 terminal on the remote pilot device and terminal 96 on the overload relay. On the other hand, if you are converting a starter that was factory supplied for 120V Separate Control to a Common Control device, you must put in this jumper. If you are swapping out a 480V magnet coil to supply one with 240V coil to meet a customers needs, you do not need to worry about wire C. Only when changing to 120V or less from any voltage greater than 120V or changing to any voltage greater than 120V from 120V or less, is this signicant.
L1 1
L2
L3
A1 M
A2
T1
T2
T3
3-Phase Motor
Figure 4. Typical Starter Wiring Diagram Three-Phase Separate voltages supplied by different voltage sources. How can you have two different voltages going into the same starter? One method is to run different wires from different electrical voltage sources. You might have a 480V supply that is attached to the line side of the starter, and that runs through to the motor. Another set of wires, from a different voltage source would bring 120V to the magnet coil. The coil is energized by the 120V, and the pushbuttons or other control devices operate at this same voltage. The motor operates at the power circuit voltage, in this case, 480V. The coil rating must match the control source voltage, and the starter is sized to match the horsepower and voltage ratings of the power circuit.
TD03309004E
Technical Data
Effective: April 2007 Page 5
Circuitry of a Starter
Common Control 1/ L1 1 A1 M 3 A2 2 C Remote Pilot Devices 2-Wire Control 3/ L2 5/ L3
98 97 96 4/ T2 6/ T3 Reset 95 Separate Control T1 T2 T3 Remove Wire C when it is supplied. Connect Separate Control Lines to the No. 1 Terminal on the Remote Pilot Device and the Terminal 96 on the Overload Relay.
OL 2/ T1
3-Phase Motor
1/ L1
3/ L2
5/ L3
CPT M
A1
A2
98 L1 X2 1 G 2/ T1 4/ T2 6/ T3 X1 L2 OL 97 96 Reset 95
T1
T2
T3
3-Phase Motor
Technical Data
Page 6 Effective: April 2007
Circuitry of a Starter
Two-Wire Control
Two-Wire Control circuits or Low Voltage Release One of the common control wiring circuits used is known as Two-Wire or Low Voltage Release (LVR). It utilizes a maintained contact type of pilot device such as a thermostat, oat switch or presence sensor. Figure 6 shows the line and wiring schematics for this circuit. When the maintained contacts on the pilot device are closed, it energizes the coil of the starter, which connects the load through the power circuit. When the contacts of the pilot device open, the coil is de-energized, and the starter drops the load off line. Automatically restarts when power is restored if pilot device is still closed. The circuit provides for an automatic operation of the load. If there is a power outage or loss, the starter will be de-energized. This is why the circuit is often called Low Voltage Release (LVR). If the maintained contacts of the pilot device remain closed during the power loss or outage the starter will be reenergized when the power to the control circuit is restored. Caution must be used in the application of this circuit there is no personnel safety protection when the power is restored.
1/ L1 1 A1 M 3 A2 2 3/ L2 5/ L3 1
98 OL 2/ T1 T1 4/ T2 T2 6/ T3 T3 97 96 Reset 95 2
L1 3-Phase Motor PD 1 3 A1 M A2 95 OL 96
L2
Three-Wire Control
Three-Wire Control circuits or Low Voltage Protection The other very common control wiring circuit used is known as Three-Wire or Low Voltage Protection (LVP). This circuitry does provide personnel safety protection in the event of power loss or outages. It utilizes momentary contact pilot devices and a holding circuit contact. This holding circuit, or seal-in circuit, is most commonly provided by an auxiliary contact on the contactor or starter. Figure 7 shows the typical line and wiring diagrams for Three-Wire control circuits. Circuit does NOT automatically restart when power is restored. This circuitry provides LVR, because if there is a power outage or loss, the starter will be de-energized. But, it provides Low Voltage Protection, because the circuit does not automatically restart. The only way to restart this circuit is to manually use the START button. Because this circuit is very popular in motor control systems, lets go through the operation of it step-by-step. The circuit consists of a Normally Closed (NC) STOP button wired in series with a Normally Open (NO) START button. A Normally Open (NO) Auxiliary contact on the starter will be used as the holding circuit.
OL L1 1 A1 M 3 98 97 96 Reset 95 Stop Start 3 2 1 A2 2 L2 L3
T1
T2
T3
3-Phase Motor
TD03309004E
Technical Data
Effective: April 2007 Page 7
Circuitry of a Starter
Three-Wire Control (Continued)
When the START button is depressed (Figure 8), it completes the circuit to energize the coil of the starter. When that occurs, the Normally Open (NO) Auxiliary contact closes. This auxiliary is shown as | | M on the line diagram. When power is restored, the circuit CANNOT automatically restart because the START button needs to be pushed to complete the circuit. Because someone must manually restart the circuit, this can provide a means of personnel safety. As we saw in the common vs. separate control wiring, the control circuit is connected through a contact on the overload relay. When an overload is detected, this contact opens the circuit and de-energizes the coil. If you are using a ThreeWire control circuit, then the starter cannot automatically restart the Start button with its NO contacts prevent the circuit from being completed.
L1 Stop Start OL
L2
M M
L1
L2 Stop Start M M OL
Figure 8. START Button Completes Circuit When you remove your nger from the START button, its contact returns to the Normally Open state. Even though this opens a path to the coil, the circuit now travels through the closed M contact to keep the starter energized. The electricity ows from L1, through the Stop (NC), through the path completed when contact M closed, to the coil, through the overload relay control circuit, to L2 ( Figure 9).
Figure 10. STOP Button Opens Circuit With 3-Wire control, automatic reset on an overload relay will NOT re-energize the circuit. There is sometimes confusion with overload relays that have an Automatic Reset capability. In a Three-Wire circuit, with the overload relay set for Manual Reset, both the RESET button on the overload, as well as the START button, must be used to re-energize the circuit. An overload relay in the Automatic mode would not automatically re-energize the circuit, because the START button is still open. An overload relay with Automatic Reset, used with a twowire circuit would provide automatic restart. This type of circuitry must be used only on applications where personnel safety is not an issue.
L1
L2
Stop
Start M M
OL
Figure 9. Electrical Path is through Contact M Pressing the STOP (Figure 10) button will cause the Normally Closed (NC) contact to open the circuit, de-energize the coil, and drop out contact M. Releasing the STOP button will return the circuit to its original (off) state. If there is a power outage or loss, the coil is de-energized, contact M opens, and the starter drops the load off line.
TD03309004E
Technical Data
Page 8 Effective: April 2007
Magnetic Field of Primary Winding Expands and Contracts as AC Current Flow Increases and Decreases.
AC Power Source
Load
Figure 12. AC Flow in Windings Voltages based on number of turns on both windings. The relationship of the voltage across the primary to the voltage across the secondary is in direct proportion to the number of turns on both windings. For example, 100 turns on the primary, and 10 turns on the secondary, is a 10 to 1 ratio. If the primary is 500 volts, we will get 50 volts at the secondary. This is referred to as a Step-Down transformer. They are most commonly used in control circuits where the motor voltage is 480V, 600V, or higher. The step-down control transformer would reduce the voltage to pushbuttons or PLCs to 120V or even 24V. A transformer with the reverse proportion of more turns on the secondary winding than on the primary is called a StepUp transformer. It will increase the voltage according to the ratio of turns.
Iron Core
TD03309004E
Technical Data
Effective: April 2007 Page 9
Stop 1
X1 X2 Start M A1 A2 OL 2 M 3 95 96 G
The primary winding of the transformer is connected to two phases of the power circuit. The secondary winding is connected to the control circuit.
The leads from the secondary of the transformer are connected to Terminal 1 of the remote pilot device, and terminal 96 on the Freedom Series overload relay (see Figure 14).
CPT
L1
X2
X1 L2 BLK
TD03309004E
Technical Data
Page 10 Effective: April 2007
Reversing Starters
To reverse a motor, you reverse the leads to the motor. To reverse a motor, you need to reverse the leads to the motor. When using a reversing magnetic starter, this task is accomplished using two contactors, one overload relay, and a mechanical interlock. The control circuit is designed to provide an electrical interlock as well. Both the mechanical and electrical interlocking prevent the simultaneous operation of the forward and reverse contactors. Figure 15 shows the wiring diagram for a full-voltage magnetic reversing starter. When the forward contacts (F) close, L1, L2, and L3 are connected to T1, T2, and T3, just as they would be on a nonreversing starter. When the reverse contacts (R) close, the motor is connected L1 to T3, L2 to T2, and L3 to T1. On a three-phase motor, it is necessary to change only two leads in order to reverse the rotation of the motor.
Pushbutton with FOR and REV Buttons Electrically 4 Interlocked. 1 For Rear 2 3 2 2 7 4 5 1 3 5 3 L1 A1 F L2 L3 A2 A1 A2 R B 4 5 6 L1 Lines L2 L3 Contactors F and R are Mechanically Interlocked F R F R F R OL OL T1 T2 T3 Motor OL
C For
Stop 1
REV 2 F
FLS R 3 6
A1 F A2
OL 95 96
Figure 16. Reversing Starter Line Diagram This circuit operates as follows: Depressing the FORWARD pushbutton energizes coil F, completing the circuit from L1 to L2. Coil F energizes NO auxiliary contact F, closing it for the holding circuit. Coil F also operates NC auxiliary contact F, opening it to insure that coil R cannot be energized. The mechanical interlock physically prevents the power contacts of contactor R from operating. When the STOP button is pushed, the entire circuit is deenergized. All of the contacts return to their normal state. The REVERSE pushbutton can then be depressed to operate the reverse contactor. Pressing the REVERSE button allows current to energize coil R to complete the circuit to the motor. Power can ow through NC contact F, since coil F is not energized. When coil R is energized, NO contact R acts as the seal-in contact. In this control circuit, the STOP button must be operated before the direction of the motor can be changed. The power circuit connections reverse the rotation of the motor. Refer back to the wiring diagram ( Figure 15). Trace the power circuit lines connected to Coil R. A connection at L1 is traced through the power contacts, and connected to T3, through the overload relay and to the motor. The connection at L3 is traced through to be connected at T1. L2 is connected to T2 as it would be in a non-reversing starter. It is these connections that reverse the rotation of the motor.
Rev
Stop
98 A Separate Control 97 OL 96 Remove Wire C 2/ 4/ 6/ Reset C when it is supplied. T1 T2 T3 95 Connect Separate Control Lines to the No. 1 Terminal FLS RLS on the remote 3 6 5 7 pilot device and Terminal T1 T2 T3 When Limit Switches are No. 96 on the used, omit Connectors A overload relay. and B and connect per Dotted Lines. Motor
Figure 15. Reversing Starter Wiring Diagram Mechanical Interlock prevents simultaneous operation. To keep the forward and reverse contacts from operating simultaneously, a mechanical device is used. This device mounts in between the two contactors and physically prevents the power contacts from operating at that same time. Control circuitry provides an electrical interlock to prevent operation at the same time. Additionally, the control circuits are wired in such a way as to prevent simultaneous operation. This is done with the use of Normally Closed (NC) auxiliary contacts. As the coil of one direction contactor is energized, its associated NC contact opens insuring an open electrical path to the coil of the opposite contactors coil. Figure 16 shows this circuitry.
TD03309004E
Technical Data
Effective: April 2007 Page 11
contact is closed, allowing power to pass from L1 to L2. When the motor is off, the light is on when the motor is on, the light is off. When wiring this circuit on enclosed controllers, remember that a NC auxiliary contact is needed in addition to the standard NO auxiliary contact.
L1
L2
L3
Stop T1 X2 T2 T3
Figure 18. START/STOP with Pilot Light OFF When Motor Running
1/ L1 1 A1 M 3 Pilot Light R 1/ L1 3/ L2 5/ L3 4 3 Hand 1 A1 A2 Start 3 2 Stop T1 T2 T3 OL L1 Stop 3-Phase Motor 1 2 M R Start 3 A1 M A2 95 Pilot Light OL 96 L2 2/ 4/ T1 T2 T1 T2 6/ T3 T3 1 98 97 96 Reset 95 Contact A B Position Hand Off Auto X X M 4 3 2 2 4 A Off Auto 1 B A2 2 3/ L2 5/ L3
Another very common control circuit is the HAND/OFF/ AUTO (HOA). It can be accomplished using either a threeposition selector switch, or three maintained pushbuttons. Figure 19 shows this circuit.
98 OL 2/ T1 4/ T2 6/ T3 97 96 Reset 95
X = Contact Closed
Figure 17. START/STOP with Pilot Light ON When Motor Running A variation to this circuit is to have a pilot light indicate that the motor is NOT running. Figure 18 shows this circuit. It operates as: There is a standard Three-Wire STOP/START circuit. An additional auxiliary contact on the starter is what operates the pilot light. Notice that it is an NC contact. When the coil is energized, this contact will open. At that point, the pilot light will turn off. When the starter is not energized, this
TD03309004E
4
L1 4 Auto 1
Pilot Device
L2
Off Hand 2 3 A1 M A2 OL 95 96
Technical Data
Page 12 Effective: April 2007
REV.
Rear
2/ T1 Motor 8
Figure 20. 2 Pilot/FORWARD/REVERSE Circuit Additional examples and explanations of control circuits can be found in Eatons Standard Motor Control Line & Wiring Diagrams, publication number TD03309001E. This publication is available to you at no charge from your local sales ofce.
TD03309004E
Technical Data
Effective: April 2007 Page 13
Glossary
Some of the Terminology of Motor Control
Across-the-Line: A method of motor starting that connects the motor directly to the supply line on starting or running. Also known as Full-Voltage. Auxiliary Contact: Contact of a switching device within the control circuit, and operated when the magnet coil is energized. Bimetal: Two different metals bonded together to provide fast heat transfer to trip contacts. Used in thermal overload relays. Common Control: Electricity to both Power circuit and Control circuit are supplied from the same voltage source. See Page 4. Contactor: A device to repeatedly establish or interrupt an electric power circuit. Control Circuit: A circuit that controls the magnet coil of a contactor or starter, and operates pilot devices connected to it. See Page 4. Control Circuit Transformer: See Control Power Transformer Control Power Transformer: A device that increases or decreases voltage to a desired level to operate the control circuit. See Page 8. De-energize: To disconnect a component or circuit from the power source. Energize: To apply voltage to an electrical device. Eutectic Alloy: A solder-like substance used in some thermal overload relays to provide heat transfer to trip the contacts. Converts from a solid to a liquid state at specic recurring points. Full Voltage Control: Connects the equipment directly to line supply on starting. Also known as Across-the-Line. Jogging (Inching): Momentary operation, small movement of driven machine or motor. Ladder Diagram: A schematic diagram where all the components are in a ladder form, up and down picture, to show function of circuit, regardless of physical location of devices. Also known as a Line Diagram. See Page 2. Line Voltage: The voltage being supplied to the equipment from the power supply. Load: Electrical devices that consume electricity to do useful work, such as motors, solenoids, lights, etc. The output of a motor circuit. Low Voltage Protection (LVP): Also known as three-wire control, providing non-automatic restart during power loss or failure. Circuit must be manually restarted upon restoration of power. See Page 6. Low Voltage Release (LVR): Also known as two-wire control. Provides a means to automatically restart a control circuit upon restoration of power from loss or failure mode. See Page 6. Normally Closed: The position of a set of contacts that are closed when the device has no electricity applied to it. Normally Open: The position of a set of contacts that are open (separated) when the device has no electricity applied to it. Open Circuit: A circuit without a complete path for the electricity to ow through. Overload Relay: A device designed to protect a motor by sensing the heat from excessive amperage draw of a jammed or overworked motor, and dropping the devices offline (open circuit) before damage occurs. Often uses either a bi-metal element or a eutectic alloy to sense the thermal changes in the power circuit. Parallel Circuit: An electrical circuit that has more than one path for current ow. (Connected rungs on a ladder diagram.) Plugging: Braking of a motor by reverse line voltage or phase sequence. Motor develops retarding force. Power Circuit: Also known as the Motor Circuit. The electrical path that passes electricity to the motor enabling it to run. See Page 4. Reduced Voltage Starter: Applies a reduced voltage or current supply to the motor during starting to avoid excessive inrush. Rotor: The rotating part of an electric motor. Schematic Diagram: A diagram that lays out the control system circuit by circuit, and is composed of symbols and lines representing the functions of devices regardless of their physical locations. Also known as Ladder or Line diagram. See Page 2. Separate Control: There is a different voltage source supplying the control circuit from that of the power/motor circuit. See Page 4. Series Circuit: an electrical circuit that has only one path for the ow of the electricity. May have several pilot devices through which the electricity must ow before the circuit is completed. Starter: A device to repeatedly establish or interrupt an electric power circuit to a motor, that also provides thermal protection to the motor. The two main components are a Contactor and an Overload Relay. Three-Wire Control: See Low Voltage Protection (LVP), Page 6. Two-Wire Control: See Low Voltage Release (LVR), Page 6. Wiring Diagram: Shows all the devices in a circuit and their physical relationship to each other. Terminal connections for all components are identied to wire a complete circuit. See Page 2.
TD03309004E
Eaton Corporation Electrical Group 1000 Cherrington Parkway Moon Township, PA 15108 United States 877-ETN CARE (877-386-2273) Eaton.com
2007 Eaton Corporation All Rights Reserved Printed in USA Publication No. TD03309004E/CPG April 2007