Assignment 1

The document describes modeling a 10 bus power system in PowerWorld and PSAT software. It first models the system without compensation. Analysis shows voltage levels fall below 0.95 p.u. at several buses due to transmission losses over long distances from generators to loads. When shunt compensation is added, voltage profiles improve but one bus remains below standard. Reactive power support is needed to maintain acceptable voltages throughout the network.

Uploaded by

Ayub Machiri
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
300 views21 pages

Assignment 1

The document describes modeling a 10 bus power system in PowerWorld and PSAT software. It first models the system without compensation. Analysis shows voltage levels fall below 0.95 p.u. at several buses due to transmission losses over long distances from generators to loads. When shunt compensation is added, voltage profiles improve but one bus remains below standard. Reactive power support is needed to maintain acceptable voltages throughout the network.

Uploaded by

Ayub Machiri
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 21

Tshwane University of Technology

Department of Electrical Engineering

Student name: Ayub Machiri Wanjala Student no.: 212 492 884

Power Systems V

Assignment 1
i

Table of Contents
1. 2. INTRODUCTION............................................................................................................ 1 SYSTEM MODELLING USING POWERWORLD SIMULATOR AND PSAT ..... 2 2.1. About PowerWorld simulator and PSAT .................................................................... 2 PowerWorld ..................................................................................................... 2 PSAT ................................................................................................................ 2

2.1.1. 2.1.2. 2.2. 2.3. 2.4. 3.

Line Modelling ............................................................................................................ 2 Load Modelling ........................................................................................................... 3 Generator Modelling ................................................................................................... 4

SYSTEM MODELLING WITHOUT COMPENSATION .......................................... 6 3.1. 3.2. Analysis of System ...................................................................................................... 6 Observation and Results .............................................................................................. 7

4.

SYSTEM MODELLING WITH COMPENSATION ................................................ 10 4.1. Choice of Compensation ........................................................................................... 10 Shunt Compensator ............................................................................................ 10 Synchronous Condenser..................................................................................... 11 Static Var Compensators.................................................................................... 12

4.1.1. 4.1.2. 4.1.3. 4.2.

Analysis of system .................................................................................................... 14 Point of Installation ........................................................................................ 14

4.2.1. 4.3. 5. 6.

Observation and Results ............................................................................................ 16

CONCLUSION .............................................................................................................. 18 References ....................................................................................................................... 19

ii

1. INTRODUCTION
Power flow studies are performed to determine the voltages, active and reactive power etc. at various points in the network for different operating conditions subject to the constraints on generator capacities and specified net interchange between operating systems and several other restraints. Power flow or load flow solution is essential for the continuous evaluation of the performance of the power systems so that suitable control measures can be taken in case of necessity. In practice it will be required to carry out numerous power flow solutions under a variety of conditions. With the advent of the modern digital computers possessing large storage and high speed the mode of power flow studies have changed from analog to digital simulation. A large number of algorithms are developed for digital power flow solutions. These methods basically distinguish between themselves in the rate of convergence, storage requirement and time of computation. Loads are generally represented by constant power [P, Q]. Network equations can be solved in a variety of ways in a systematic manner. The most popular method is node voltage method. When nodal or bus admittances are used complex linear algebraic simultaneous equations will be obtained in terms of nodal or bus currents. However, as in a power system since the nodal currents are not known, but powers are known at almost all the buses, the resulting mathematical equations become non-linear and are required to be solved by iterative methods. The bus admittance matrix is invariably utilized in power flow solutions This report describes a 10 bus system which is composed of 10 buses and 17 lines implemented in the power system simulation tool PowerWorld (Version 16) and PSAT Matlab toolbox. The system consists of 3 generator buses and 7 load buses. The total real and reactive power demand of the system are 1350 MW and 670 MVAR, respectively. The main objective of this study is to carry out the load flow study on the system and compensate it accordingly to ensure that the required voltage levels are maintained within the permissible level of for all the buses

within the given network. This is done using shunt compensation devices since the capability of using FACT devices on PowerWorld is not available. I have explained briefly on the usage of FACT devices as well as their respective advantages in this report.

2. SYSTEM MODELLING USING POWERWORLD SIMULATOR AND PSAT


2.1. About PowerWorld simulator and PSAT

2.1.1. PowerWorld PowerWorld is simulation software designed by PowerWorld Corporation in USA, which is used to carry out the analysis of a network using a visual interface. It is used to show the various states of the network when carrying out load flow studies on the network. The software works by using the Single Line Diagram to define the parameters of the given network and the state of the network at a given instance. The main figures used in this report are generated using this software. 2.1.2. PSAT PSAT is a Matlab toolbox developed by Federico Milano and uses the computational power of the Matlab software. It is used to carry out various network studies such as load flow analysis. In this case, I used PSAT to be able to generate a complete outlook of the network parameters which I was unable to do using PowerWorld. I also used it to carry out the verification of the parameters I got using PowerWorld software. The main reports used in this report are generated using this toolbox.

2.2.

Line Modelling

To be able to carry out the load flow studies, it is paramount that the given data is standardised to suit the given software interface. This data usually consists of the base value of the voltages as well as the base value for the power. In this case the values specified for the base are as follows:

Table 1: Basic formulaes used

From the data given, we can specify the line data as follows:

Where: is a complex of resistive [R] and reactive [Q] components as shown below:

Line 1-2 Given that

From Bus 1 1 1 2 3 3 5 6 7 7 7 10

To Bus 2 4 5 10 8 9 8 7 5 4 9 6

R [p.u.] 0.00477 0.00569 0.00272 0.00676 0.00297 0.00145 0.00388 0.0004 0.0043 0.00589 0.00289 0.00546

X [p.u.] 0.05103 0.06008 0.02872 0.09429 0.03706 0.01802 0.4834 0.004 0.0477 0.05995 0.03603 0.06794

R [ ] 7.632 9.104 4.352 10.816 4.752 2.32 6.208 0.64 6.88 9.424 4.624 8.736

X [ ] 81.648 96.128 45.952 150.864 59.296 28.832 773.44 6.4 76.32 95.92 57.648 108.704

Table 2: Line parameters

2.3.

Load Modelling

From the data given, we can specify the load data as follows:

Where: is a complex of real [P] and reactive [Q] power as shown below

Load 9 Given that

Load Bus 9 7 6 10 4 8 5 Total

P 3 2.5 1.8 0.5 1 3.2 1.5 13.5

Q [ 2 1 0.5 0.2 0.6 2 0.4 6.7


Table 3: load parameters

P ] 300 250 180 50 100 320 150 13500 [

Q ] 200 100 50 20 60 200 40 670

2.4.

Generator Modelling

From the data given, we can specify the generator data as follows:

Where: is a complex of real [P] and reactive [Q] power as shown below

Generator 1 Given that

PV bus Generator Bus 1 2

Table 4: PV parameters

Slack bus Generator Bus 3


Table 5: Slack generator parameters

Using the data obtained in the above tables (1 5), it is now possible to enter the data into the PowerWorld softwares to perform the load flow analysis as shown in the following sections.

3. SYSTEM MODELLING WITHOUT COMPENSATION


Consider the given 10 bus system with 2 PV buses, 7 PQ buses and 1 slack bus. The system is modelled using PowerWorld simulator to obtain the initial state of the respective voltage nodes without any compensation coupled to the network. The figure below shows the Single Line Diagram (SLD) obtained:

Fig 1: single line diagram for uncompensated 10 bus network using PowerWorld

3.1.

Analysis of System

The given system shows a typical traditional power system. The main generators (bus 1 and 2) are centralised and coupled by a tie line (line 1-2). These provide the main power supply for the loads (bus 4 - 10) through a transmission grid comprising of 12 lines. The slack generator (bus 3) is used as the reference for modelling the load flow analysis. 6

The network configuration is such that the loads can be characterised by the distance from the main generators. It can be seen that the 1st tier loads are the ones closest to the generators, which are buses 10, 4 and 5 with respect to generator 1 and 2; buses 8 and 9 are the ones closest to the slack generator 3. The 2nd tier loads are further away from the generating source and these are buses 6 and 7. It can be noted that the major loads are found on the 2nd tier level from the main generators (1 and 2) compared to the 1st tier level. This means that the electrical distance from the generator to the loads is high and as a result the system will incur transmission losses due to the inductive reactance of the transmission lines. It is assumed that the lined do not have any line charging and as a result it is mainly an inductive (lagging) transmission network.

3.2.

Observation and Results

From the simulation of the load flow using PowerWorld, it is noted that the voltage levels at the respective buses fall far below the recommended limit; 0.95 p.u. A complete report is generated using PSAT to show the respective voltage levels [p.u.] and the total line flows as well as the losses in the lines.

POWER FLOW REPORT P S A T 2.1.6 Author: Federico Milano, (c) 2002-2010 e-mail: [email protected] website: http://www.uclm.es/area/gsee/Web/Federico File: C:\MATLABR61\psat\model.mdl Date: 20-Oct-2012 19:17:36 NETWORK STATISTICS Buses: Lines: Generators: Loads: 10 12 3 7

SOLUTION STATISTICS Number of Iterations: Maximum P mismatch [p.u.] Maximum Q mismatch [p.u.] Power rate [MVA] 4 0 0 100

POWER FLOW RESULTS Bus Bus1 Bus10 Bus2 Bus3 Bus4 Bus5 Bus6 Bus7 Bus8 Bus9

V [p.u.]
1 0.93961 1 1 0.94894 0.9476 0.91808 0.9196 0.92605 0.94281

phase

[rad]
0.03483

P gen [p.u.]
4.848 0

Q gen [p.u.]
2.4335 0

P load [p.u.]
0

Q load [p.u.]
0

-0.07789 0.03445
0 -0.05704 -0.06112 -0.12829 -0.12356 -0.09275 -0.07557

0.48912
0 0 0.49888 1.4925 1.6811 2.3426 3.0407 2.9548

0.19565
0 0 0.19955 0.39799 0.46696 0.93702 1.9004 1.9698

1.154
6.6575 0

0.62069
4.891 0

0 0 0 0 0

0 0 0 0 0

Minimum voltage limit violation at bus <Bus10> [V_min = 0.95] Minimum voltage limit violation at bus <Bus4> [V_min = 0.95] Minimum voltage limit violation at bus <Bus5> [V_min = 0.95] Minimum voltage limit violation at bus <Bus6> [V_min = 0.95] Minimum voltage limit violation at bus <Bus7> [V_min = 0.95] Minimum voltage limit violation at bus <Bus8> [V_min = 0.95] Minimum voltage limit violation at bus <Bus9> [V_min = 0.95] LINE FLOWS From Bus Bus10 Bus10 Bus8 Bus9 Bus2 Bus1 Bus4 Bus3 Bus7 Bus5 Bus5 Bus5 To Bus Bus2 Bus6 Bus3 Bus7 Bus1 Bus4 Bus7 Bus9 Bus6 Bus1 Bus7 Bus8 Line P Flow Q Flow P Loss Q Loss

[p.u.] 1 2 3 4 5 6 7 8 9 10 11 12
-1.1498 0.66066 -2.4381 1.1974 -0.0075 1.5221 1.0067 4.1905 1.024 -3.2809 1.1837 0.60483

[p.u.]
-0.45654 0.26089 -1.545 0.53899 0.0007 0.77232 0.39773 2.9859 0.25015 -1.2663 0.48527 0.38302

[p.u.]
0.01172 0.00312 0.02885 0.00561 0 0.01658 0.00766 0.03839 0.00053 0.03746 0.00784 0.00221

[p.u.]
0.16345 0.03883 0.36004 0.06989 0 0.17503 0.078 0.47711 0.00526 0.39557 0.08693 0.02759

GLOBAL SUMMARY REPORT TOTAL GENERATION REAL POWER [p.u.] REACTIVE POWER [p.u.] TOTAL LOAD REAL POWER [p.u.] REACTIVE POWER [p.u.] 12.4995 6.0674 8 12.6595 7.9451

TOTAL LOSSES REAL POWER [p.u.] REACTIVE POWER [p.u.] 0.15997 1.8777

LIMIT VIOLATION STATISTICS No of voltage limit violations: 7 All reactive power within limits. All current flows within limits. All real power flows within limits. All apparent power flows within limits.

4. SYSTEM MODELLING WITH COMPENSATION


4.1. Choice of Compensation

The choice of compensation to be used depends mainly on the instantaneous characteristic of the network at any given point. This is usually done by analysing the voltage levels at the given nodes (buses) which give us a general idea as to how the condition of the network is. When the voltages at a given node are higher than the recommended value, it indicates that the line capacitance is great and therefore injecting reactive power into the network. Similarly, when the voltage at the node is lower than the recommended value, it indicates that the line reactance is high and as a result the reactive power is absorbed by the line which lowers the voltages. It is therefore important to know that the compensation devices are usually inductive or capacitive in nature. A brief look at the types of compensators and there use is discussed below. 4.1.1. Shunt Compensator The shunt compensator is the connection of a reactive power component in a power network. These reactive power components are either an inductor or capacitor. The types of shunt compensation used at a given voltage node is directly dependant on the voltage profile at the point. 4.1.1.1. Shunt capacitor bank

The shunt capacitor bank is used to inject reactive power into the network at the given node. It consists of a bank of capacitors connected to the network and operated individually at a time. The amount of reactance to be injected into the given node is determined by the voltage at the node itself. The capacitors are used in an inductive (leading) network. In such a transmission network the voltage profile at the node is usually below the recommended level of 0.9p.u, and this is to be improved. 4.1.1.2. Shunt reactor

The shunt reactor is used to absorb excess reactive power in the network at a given node. It is an inductive reactor made of air or iron core. Traditionally, the shunt reactor has a fixed 10

rating and is either connected to the power line all the time or switched in and out depending on the load. Recently Variable Shunt Reactors (VSR) have been developed and introduced on the market. The rating of a VSR can be changed in steps ranging from 100-200MVars. The variability brings several benefits compared to the traditional fixed shunt reactors. The VSR can continuously compensate reactive power as the load varies and thereby securing voltage stability. Variable Shunt Reactors are used in high voltage energy transmission systems to stabilize the voltage during load variations. They are used in capacitive (lagging) networks which usually experience voltages above the recommended 1.1p.u voltage level. 4.1.2. Synchronous Condenser In the initial power networks, the control of reactive power flow in the system to ensure unity power factor was done by the use of synchronous condensers. A synchronous condenser is a device which is identical to the synchronous motor, whose shaft is not connected to a load, but is let to spin freely. The main purpose for this synchronous condenser is to adjust the conditions in a power transmission grid. The field is controlled by a voltage regulate to either generate or absorb reactive power in the network as needed to improve the power factor. Principle of operation: When the devices field excitation is increased it resulted in the injection of reactive power into the system operating as a capacitor bank. When the excitation on the field reduced, the motor absorbs the reactive power from the network effectively working as an inductor. It is through this principle that it was implemented to help in stabilizing the power system during short circuits or rapidly fluctuating loads. The installation and operation of this synchronous condenser is largely identical to large electrical motors. When compared to the capacitor banks, the value of reactive power from a synchronous condenser can be continuously adjusted depending on the network conditions which was difficult to do when suing the capacitor banks. In addition, reactive power from a capacitor

11

bank decreases with voltage decrease, while a synchronous condenser can increase current as voltage decreases. Even though it does offer some advantages compared to the static capacitor banks, it does have higher losses, which makes them to be uneconomical. Most synchronous condensers connected to electrical grids are rated between 20 Mvar and 200 Mvar and many are hydrogen cooled. 4.1.3. Static Var Compensators SVCs are part of the Flexible AC transmission system device family which is used for regulating voltage and stabilizing the power system. It is an electrical device used to provide fast acting reactive power on high voltage transmission networks. It encompasses both the capacitive and inductive elements which are controlled by the switching action of the thyristors and the voltage at the given point of installation in the network. The SVCs have no significant moving parts. Prior to the invention of the SVC, power factor compensation and voltage regulation was done using synchronous condensers or switched capacitor banks as explained in the above section. Principle of operation: The SVC is designed to automatically inject or absorb the required reactive power at a given bus depending on the instantaneous load present in a system. It is designed to bring the system closer to a unity power factor. In the transmission network, it is used to regulate the transmission voltage levels. The SVC may also be used near large industrial loads to improve the power quality. The components of the SVC comprise of the following elements:Thyristor switched capacitor (TSC) Considering a power network, which is under inductive (lagging) conditions, the SVC uses Thyristor switched capacitors (TSC) which are automatically switched on hence injecting reactive power into the network. This results in an increase in the voltage profile at the given node.

12

Thyristor controlled reactor (TCR), When the network is under capacitive (leading) conditions, The SVC will use Thyristor controlled reactors (TCR) which are turned on hence absorb reactive power in the system which results in the decrease of the voltage profile at the given. Harmonic filter(s) This device is used to filter out the harmonic frequencies which are generated by the switching action of the Thyristor. Mechanically switched capacitors or reactors (switched by a circuit breaker) In case of an emergency or failure of the thyristors, a mechanical switch may be provided to control the reactive power injected or absorbed by use of a circuit breaker which is mechanically operated. Advantages 1. The main advantage of SVCs over simple mechanically-switched compensation schemes is their near-instantaneous response to changes in the system voltage. For this reason they are often operated at close to their zero-point in order to maximize the reactive power correction they can rapidly provide when required. 2. They are, in general, cheaper, higher-capacity, faster and more reliable than dynamic compensation schemes such as synchronous condensers. However, static var compensators are more expensive than mechanically switched capacitors, so many system operators use a combination of the two technologies (sometimes in the same installation), using the static var compensator to provide support for fast changes and the mechanically switched capacitors to provide steady-state Vars.

13

Fig 2: Single Line Diagram representing the SVCs

4.2.

Analysis of system

Considering the 10 bus network given above, we are able to characterise the network as a lagging network due to the low voltage levels at the respective nodes. The network has to be compensated by using shunt capacitor banks or SVCs so as to inject reactive power into the network. This is done to improve the voltage profile to the recommended levels. 4.2.1. Point of Installation Now that we know we are supposed to inject reactive power into the network, we are supposed to establish the nodes in the network which will offer the optimal performance for the network. On observing the network, we can note that the network is radial in nature. The system can be identified by using three main radial configurations. These radial configurations are 1. Bus < 2 10 6 7 4 1 2 > 2. Bus < 2 10 6 7 5 1 2 > 3. Bus < 3 9 7 5 8 3>

14

From the initial results in the uncompensated system, it was noted that the voltage deviation from the recommended value occurred in buses 4, 5, 6, 7, 8, 9 & 10 with the maximum deviation occurring on bus 6. According to the radial networks assumed observed above, radial 1 has bus 6 with the maximum voltage deviation at 0.91808 and radial 2 also has bus 6 with the maximum voltage deviation and in radial 3, the bus with the most voltage deviation is bus 7 with 0.9196. Radial network 1 & 2 share a total of 4 lines. This basically means that the placement of the capacitor bank is able to inject reactive power into both networks if placed correctly. It can be noted that Bus 6 is part of the 1st and 2nd radial networks. It is also noted that the distance from the generating source is high as it forms part of the 2nd tier loads. From this observation, we can say that the best place to install the shunt capacitor banks is at bus 6. When we consider the 3rd radial network, the main load is installed at bus no 8, which also has a relatively low voltage profile and the distance from the generator 1 and 2 are great. Since the bus is independent of both the 1st and 2nd radial network, it was noted that for the regulation of voltage at this node, it was important to add a shunt capacitor bank at this node too. The system was compensated as shown in the SLD below by injecting reactive energy at bus 6 and bus 8 respectively.

15

Fig 3: single line diagram for compensated 10 bus network using PowerWorld

4.3.

Observation and Results

POWER FLOW REPORT P S A T 2.1.6 Author: Federico Milano, (c) 2002-2010 e-mail: [email protected] website: http://www.uclm.es/area/gsee/Web/Federico File: C:\MATLABR61\psat\model.mdl Date: 20-Oct-2012 19:14:23 NETWORK STATISTICS Buses: 10 Lines: 12 Generators: 3 Loads: 7 SOLUTION STATISTICS Number of Iterations: Maximum P mismatch [p.u.] Maximum Q mismatch [p.u.] Power rate [MVA]

4 0 0 100

16

POWER FLOW RESULTS Bus V Bus1 Bus10 Bus2 Bus3 Bus4 Bus5 Bus6 Bus7 Bus8 Bus9

phase

[p.u.] 1 0.99091 1 1 0.98757 0.98929 1.0058 0.99623 1.0012 0.96829

[rad] 0.02092 -0.09301 0.01937 0 -0.0716 -0.07405 -0.14041 -0.1349 -0.10054 -0.08018

P gen [p.u.] 4.848 0 1.154 7.1331 0 0 0 0 0 0

Q gen [p.u.] 0.34605 0 0.08065 1.4636 0 0 0 0 0 0

P load [p.u.] 0 0.5 0 0 0.5 1.5 1.8 2.5 3.2 3

Q load [p.u.] 0 0.2 0 0 0.2 0.4 -2.8151 1 -0.67833 2

LINE FLOWS From Bus To Bus Bus10 Bus10 Bus8 Bus9 Bus2 Bus1 Bus4 Bus3 Bus7 Bus5 Bus5 Bus5 Bus2 Bus6 Bus3 Bus7 Bus1 Bus4 Bus7 Bus9 Bus6 Bus1 Bus7 Bus8

Line

P Flow

Q Flow

P Loss

Q Loss

1 2 3 4 5 6 7 8 9 10 11 12 GLOBAL SUMMARY REPORT TOTAL GENERATION REAL POWER [p.u.] REACTIVE POWER [p.u.] TOTAL LOAD REAL POWER [p.u.] REACTIVE POWER [p.u.] TOTAL LOSSES REAL POWER [p.u.] REACTIVE POWER [p.u.]

[p.u.] -1.1746 0.67458 -2.6809 1.3984 -0.0301 1.531 1.0176 4.4305 1.1313 -3.2574 1.2369 0.52045

[p.u.] 0.05496 -0.25496 0.38325 -0.82281 0.00284 0.13217 -0.20971 1.5756 -2.494 0.09495 -0.21706 -0.27789

[p.u.] 0.00952 0.00289 0.02173 0.00811 0 0.01344 0.00652 0.03206 0.00302 0.02951 0.00693 0.00138

[p.u.] 0.13278 0.03598 0.27117 0.10116 5e-005 0.14188 0.06635 0.39845 0.03023 0.31162 0.07686 0.01719

13.1351 1.8903

13 0.30653

0.13512 1.5837

LIMIT VIOLATION STATISTICS All voltages within limits. All reactive power within limits. All current flows within limits. All real power flows within limits. All apparent power flows within limits. 17

5. CONCLUSION
In this report the 10 bus test system was initially analysed and compensated for voltage instability. It was observed that generators have the capability of providing reactive power but are limited to a certain extent. The reactive power produced by the generators cannot be effectively utilized since the demand for the reactive power is far from its location. A Shunt capacitor bank was used for compensation to provide local reactive power support at the buses 6 and 8.