Capacity regulator (hot gas bypass), type TUH/TCHE/TRHE

REFRIGERATION AND AIR CONDITIONING

Technical leaet

Technical leaet

Capacity regulator (hot gas bypass), type TUH/TCHE/TRHE

Contents

Page Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 Standard range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 Identication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 Ordering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 Capacity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 R134a - Replacement capacity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6 R134a - Mass ow rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7 R22 - Replacement capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8 R22 - Mass ow rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9 R404A/R507 - Replacement capacity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 R404A/R507 - Mass ow rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 R407C - Replacement capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 R407C - Mass ow rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 R410A - Replacement capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 R410A - Mass ow rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 Design/Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Dimensions and weight. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Application. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

RD4EG202 DKRCC.PD.HK0.A1.02 / 520H0483

Danfoss A/S (RC-CMS/MWA), 05 - 2005

Technical leaet

Capacity regulator (hot gas bypass), type TUH/TCHE/TRHE

Introduction

TUH/TCHE/TRHE capacity regulators adapt compressor capacity to actual evaporator load in applications operating at an evaporating temperature of around 0C. TUH/TCHE/TRHE valves are typically used in applications such as: Air driers Water chillers Fitted in a bypass between the high and lowpressure sides of the air-drier system, TUH/TCHE/ TRHE maintain compressor suction pressure by injecting hot gas/cool gas from the high-pressure side. TUH has internal pressure equalisation and opens when pressure drops at the valve outlet. TCHE/TRHE have external pressure equalisation and open directly when compressor suction pressure drops. For all types, the bulb only serves as a reservoir for the charge. However, it is recommended that the bulb be mounted in a location where temperature variation during operation is limited (see application drawings).

Features

Bimetal connections straightforward and fast soldering (no wet cloth or refrigeration pliers required) high connection strength Refrigerants R410A, R134a, R404A/R507, R407C, R22 and other refrigerants on request. Replacement capacities up to 70.3 kW (20.1 TR) for R410A Stable regulation Tight across the seat Compact design small dimensions and low weight Hermetically tight design

Stainless steel element high corrosion resistance capillary tube joints of high strength and vibration resistance Laser-welded, stainless steel diaphragm element optimum function long diaphragm life high pressure resistance Adjustable setting accurate setting ne tuning possible Low p-band Low hysteresis TUH & TCHE have an advanced lter/strainer design Connections TUH & TCHE Inlet: 10 mm / 3/8 in. Outlet: 12 mm / 1/2 in. TRHE10 & TRHE20 Inlet: 16 mm / 5/8 in. Outlet: 16 mm / 5/8 in. TRHE40 Inlet: Outlet: TRHE80 Inlet: Outlet:

Standard range
(Variants available on request)

Standard models: One standard range per refrigerant Refrigerants R134a, R404A/R507, R407C, R22, R410A Capillary tube length
TUH TCHE TRHE10 TRHE20 TRHE40 TRHE80 0.8 m / 2.6 ft. 0.9 m / 2.9 ft. 1.5 m / 5.0 ft. 1.5 m / 5.0 ft. 3.0 m / 10 ft. 3.0 m / 10 ft.

22 mm / 7/8 in. 22 mm / 7/8 in.

Orice sizes
TUH TCHE TRHE10 TRHE20 TRHE40 TRHE80 Orice 9 Orice 3 Orice 4 Orice 10 Orice 20 Orice 40 Orice 70

28 mm / 11/8 in. 28 mm / 11/8 in.

Danfoss A/S (RC-CMS/MWA), 05 - 2005

RD4EG202 DKRCC.PD.HK0.A1.02 / 520H0483

Technical leaet

Capacity regulator (hot gas bypass), type TUH/TCHE/TRHE

Identication - TUH & TCHE

Main valve data is given on the element (g. 1) and on the valve body (g. 2). Main valve data example, g. 1 TUH = Type 068U2954 R404A 5 +5C +23 +41F PS 34 bar/ MWP 500 psig 104B = Code number = Refrigerant = Adjusting range in C = Adjusting range in F = Max. working pressure = Date marking (week 10, year 2004, weekday B = Tuesday)
Fig. 1

Main valve data example, g. 2 = Normal ow direction inch ORIF 9 1.3 TR 4.5 kW = Connection in inches (MM = millimetres) = Orice number 9 = Replacement capacity in Tons of Refrigeration = Replacement capacity in kW
Fig. 2

Identication - TRHE

Main valve data example, g. 3 TRHE10 = Type 3.0 TR = Rated replacement capacity Qnom in Tons of Refrigeration = Rated replacement capacity Qnom in kW = Refrigerant = Adjusting range in C = Adjusting range in F = Code number = Max. working pressure
Fig. 3
PS

10.3 kW R410A 5 +5C +23 +41F 067Lxxxx PS 42 bar/ MWP 600 psig

Technical data

Max. valve body temperature: 120C / 248F Transient peak: 150C / 302F Permissible working pressure R134a, R22, R407C, R404A: PS = 34 bar / MWP = 500 psig R410A PS = 42.5 bar / MWP = 615 psig Max. test pressure R134a, R22, R407C, R404A: p = 37.5 bar / 540 psig R410A: p = 47 bar / 680 psig P-band max. 0.5 bar / 7.3 psig

Setting The valve is set to start opening at an evaporating temperature of +2C/+36F . The setting can be changed by turning the setting spindle. The temperature at which the valve starts opening is increased by turning the spindle anti-clockwise and decreased by turning the spindle clockwise. Specically designed for hot gas applications. All valves react only on to suction pressure variations.

RD4EG202 DKRCC.PD.HK0.A1.02 / 520H0483

Danfoss A/S (RC-CMS/MWA), 05 - 2005

Technical leaet

Capacity regulator (hot gas bypass), type TUH/TCHE/TRHE

Technical data (Continued) Adjustment range for start opening

Valve Type

Refrigerant

Adjustment range for start opening [C] [F] +20 +51F +25 +46F +27 +44F +29 +42F +22 +48F +26 +43F +28 +42F +22 +47F +22 +48F +22 +48F +24 +46F +25 +44F 7 +11C 4 +8C 3 +7C 2 +6C 6 +9C 3 +6C 3 +6C 5 +8C 6 +9C 6 +9C 5 +8C 4 +7C

Valve Type

Refrigerant

Adjustment range for start opening [C] [F] +19 +51F +21 +48F +22 +47F +21 +48F +24 +46F +24 +46F +26 +44F +27 +43F +25 +44F +23 +46F +25 +44F +28 +42F 7 +10C 6 +9C 5 +8C 6 +9C 5 +8C 5 +8C 4 +7C 3 +6C 4 +7C 5 +8C 4 +7C 3 +6C

R134a TUH R22 / R407C R404A R410A R134a TCHE R22 / R407C R404A R410A R134a TRHE10 R22 / R407C R404A R410A

R134a TRHE20 R22 / R407C R404A R410A R134a TRHE40 R22 / R407C R404A R410A R134a TRHE80 R22 / R407C R404A R410A

Ordering Supplied with bulb strap

Standard range
Refrigerant Type

R134a, R22, R404A/R507, R407C, R410A


Orice no. 9 3 4 10 20 40 70 9 3 4 10 20 40 70 9 3 4 10 20 40 70 9 3 4 10 20 40 70 9 3 4 10 20 40 70 Nominal replacement capacity 1) kW TR 0.5 0.8 1 0.8 1.9 3.2 5.9 1.3 1.7 2.2 1.5 3.2 5.7 11.8 0.8 1.2 1.5 1.2 2.6 4.7 8.2 0.9 1.2 1.5 1.6 3.4 5.9 10.7 2.1 2.9 3.7 3.0 6.4 10.0 20.1 int. ext. ext. ext. ext. ext. ext. int. ext. ext. ext. ext. ext. ext. int. ext. ext. ext. ext. ext. ext. int. ext. ext. ext. ext. ext. ext. int. ext. ext. ext. ext. ext. ext.
3 3 3 5 5 7

Pressure equalisation in. 2) /8 1/2 /8 1/2 /8 1/2 /8 5/8 /8 5/8 /8 7/8 /8 1/2 /8 1/2 /8 1/2 /8 5/8 /8 5/8 /8 7/8 /8 1/2 /8 1/2 /8 1/2 /8 5/8 /8 5/8 /8 7/8 /8 1/2 /8 1/2 /8 1/2 /8 5/8 /8 5/8 /8 7/8 /8 1/2 /8 1/2 /8 1/2 /8 5/8 /8 5/8 /8 7/8

Connection Inlet Outlet Code no. 068U2953 068U4540 068U4537 067L1500 067L1600 067L3500 067L3600 068U2954 068U4541 068U4538 067L1501 067L1601 067L3501 067L3601 068U2955 068U4542 068U4539 067L1502 067L1602 067L3502 067L3602 068U2959 068U4546 068U4547 067L1503 067L1603 067L3503 067L3603 068U2960 068U4548 068U4549 067L1504 067L1604 067L3504 067L3604 mm 3) 10 12 10 12 10 12 16 16 16 16 22 22 28 28 10 12 10 12 10 12 16 16 16 16 22 22 28 28 10 12 10 12 10 12 16 16 16 16 22 22 28 28 10 12 10 12 10 12 16 16 16 16 22 22 28 28 10 12 10 12 10 12 16 16 16 16 22 22 28 28 Code no. 068U2950 068U4530 068U4534 --------068U2951 068U4531 068U4535 --------068U2952 068U4532 068U4536 --------068U2957 068U4544 068U4545 --------068U2958 068U4528 068U4529 ---------

TUH

R134a

TUH TCHE TCHE TRHE10 TRHE20 TRHE40 TRHE80

1.8 2.6 3.4 2.9 6.5 11.3 20.8 4.5 5.9 7.6 5.1 11.3 20.0 41.3 2.8 4.1 5.3 4.1 9.1 16.6 28.8 3.0 4.1 5.3 5.4 11.9 20.8 37.5 7.3 10.0 12.9 10.3 22.6 34.9 70.3

11/8 11/8
3 3 3 5 5 7

R404A/R507

TUH TCHE TCHE TRHE10 TRHE20 TRHE40 TRHE80

TCHE

11/8 11/8
3 3 3 5 5 7

R407C

TUH TCHE TCHE

TRHE

TRHE10 TRHE20 TRHE40 TRHE80 R22 TUH TCHE TCHE TRHE10 TRHE20 TRHE40 TRHE80 R410A TUH TCHE TCHE TRHE10 TRHE20 TRHE40 TRHE80
1)

11/8 11/8
3 3 3 5 5 7

11/8 11/8
3 3 3 5 5 7

11/8 11/8

2) 3)

The nominal replacement capacity is the regulator capacity at evaporating temperature te = 2C / 28F, condensing temperature tc = +40C / 104F, reduction of suction temperature / suction pressure ts = 4 K / 7F. Valves with inch connections have 1/4 in. pressure-equalisation. Valves with mm connections have 6 mm pressure-equalisation.

Danfoss A/S (RC-CMS/MWA), 05 - 2005

RD4EG202 DKRCC.PD.HK0.A1.02 / 520H0483

Technical leaet

Capacity regulator (hot gas bypass), type TUH/TCHE/TRHE

Replacement capacity

R134a
6 5

TUH & TCHE


Conditions used in calculation: tcond = +40C tsubcooling = 4K tsuperheat = 4K etaisentrop =0.7 Start opening: tevap = 2C pevap = 0.2 bar

Replacement capacity [kW]

4 3 2 1 0 -6 -5 -4 -3 -2 -1 0 1 2 3

TCHE 3 TCHE 4 TUH 9

Evaporating temperature [C]

TRHE
35 30

Replacement capacity [kW]

25 20 15 10 5 0 -6 -5 -4 -3 -2 -1 0 1 2 3

Conditions used in calculation: tcond = +40C tsubcooling = 4K tsuperheat = 4K etaisentrop =0.7 Start opening: tevap = 2C pevap = 0.5 bar

TRHE 10 TRHE 20 TRHE 40 TRHE 80 Evaporating temperature [C]

Correction factor for condensing temperature

Condensing temperature R134a +30C 0.8 +40C 1.0 +50C 1.2

Above capacities have to be multiplied with the correction factor.

RD4EG202 DKRCC.PD.HK0.A1.02 / 520H0483

Danfoss A/S (RC-CMS/MWA), 05 - 2005

Technical leaet

Capacity regulator (hot gas bypass), type TUH/TCHE/TRHE

Mass ow rate

R134a
0.030 0.025 0.020 0.015 0.010 0.005 0.000 -6 -5 -4 -3 -2 -1 0 1 2 3

TUH & TCHE


Conditions used in calculation: tcond = +40C tsubcooling = 4K tsuperheat = 4K etaisentrop = 0.7 Start opening: tevap = 2C pevap = 0.2 bar

Mass ow [kg/s]

TCHE 3 TCHE 4 TUH 9

Evaporating temperature [C]

TRHE
0.18 0.16 0.14
Mass ow [kg/s] Conditions used in calculation: tcond = +40C tsubcooling = 4K tsuperheat = 4K etaisentrop = 0.7 Start opening: tevap = 2C pevap = 0.5 bar

0.12 0.10 0.08 0.06 0.04 0.02 0.00 -6 -5 -4 -3 -2 -1 0 1 2 3


Evaporating temperature [C]

TRHE 10 TRHE 20 TRHE 40 TRHE 80

Correction factor for condensing temperature

Condensing temperature R134a +30C 0.8 +40C 1.0 +50C 1.2

Above capacities have to be multiplied with the correction factor.

Danfoss A/S (RC-CMS/MWA), 05 - 2005

RD4EG202 DKRCC.PD.HK0.A1.02 / 520H0483

Technical leaet

Capacity regulator (hot gas bypass), type TUH/TCHE/TRHE

Replacement capacity

R22
8 7

TUH & TCHE


Conditions used in calculation: tcond = +40C tsubcooling = 4K tsuperheat = 4K etaisentrop = 0.7 Start opening: tevap = 18C pevap = 0.2 bar

Replacement capacity [kW]

6 5 4 3 2 1 0 -6 -5 -4 -3 -2 -1 0 1 2 3

TCHE 3 TCHE 4 TUH 9 Evaporating temperature [C]

TRHE
70 60

Replacement capacity [kW]

50 40 30 20 10 0 -6 -5 -4 -3 -2 -1 0 1 2 3

Conditions used in calculation: tcond = +40C tsubcooling = 4K tsuperheat = 4K etaisentrop = 0.7 Start opening: tevap = 2C pevap = 0.5 bar

TRHE 10 TRHE 20 TRHE 40 TRHE 80

Evaporating temperature [C]

Correction factor for condensing temperature

Condensing temperature R22 +30C 0.8 +40C 1.0 +50C 1.2

Above capacities have to be multiplied with the correction factor.

RD4EG202 DKRCC.PD.HK0.A1.02 / 520H0483

Danfoss A/S (RC-CMS/MWA), 05 - 2005

Technical leaet

Capacity regulator (hot gas bypass), type TUH/TCHE/TRHE

Mass ow rate

R22
0.04

TUH & TCHE


Conditions used in calculation: tcond = +40C tsubcooling = 4K tsuperheat = 4K etaisentrop = 0.7 Start opening: tevap = 18C pevap = 0.2 bar

0.03

Mass ow [kg/s]

0.02

0.01

0.00 -6 -5 -4 -3 -2 -1 0 1 2 3

TCHE 3 TCHE 4 TUH 9 Evaporating temperature [C]

TRHE
0.30 0.25

Mass ow [kg/s]

0.20 0.15 0.10 0.05 0.00

Conditions used in calculation: tcond = +40C tsubcooling = 4K tsuperheat = 4K etaisentrop = 0.7 Start opening: tevap = 2C pevap = 0.5 bar

TRHE 10 TRHE 20 TRHE 40 TRHE 80


-6 -5 -4 -3 -2 -1 0 1 2 3

Evaporating temperature [C]

Correction factor for condensing temperature

Condensing temperature R22 +30C 0.8 +40C 1.0 +50C 1.2

Above capacities have to be multiplied with the correction factor.

Danfoss A/S (RC-CMS/MWA), 05 - 2005

RD4EG202 DKRCC.PD.HK0.A1.02 / 520H0483

Technical leaet

Capacity regulator (hot gas bypass), type TUH/TCHE/TRHE

Replacement capacity

R404A/R507
12 10

TUH & TCHE


Conditions used in calculation: tcond = +40C tsubcooling = 4K tsuperheat = 4K etaisentrop = 0.7 Start opening: tevap = 2C pevap = 0.2 bar

Replacement capacity [kW]

8 6 4 2 0 -6 -5 -4 -3 -2 -1 0 1 2 3

TCHE 3 TCHE 4 TUH 9

Evaporating temperature [C]

TRHE
70 60
Replacement capacity [kW] Conditions used in calculation: tcond = +40C tsubcooling = 4K tsuperheat = 4K etaisentrop = 0.7 Start opening: tevap = 2C pevap = 0.5 bar

50 40 30 20 10 0 -6 -5 -4 -3 -2 -1 0 1 2 3
Evaporating temperature [C]

TRHE 10 TRHE 20 TRHE 40 TRHE 80

Correction factor for condensing temperature

Condensing temperature R404A/R507 +30C 0.8 +40C 1.0 +50C 1.2

Above capacities have to be multiplied with the correction factor.

10

RD4EG202 DKRCC.PD.HK0.A1.02 / 520H0483

Danfoss A/S (RC-CMS/MWA), 05 - 2005

Technical leaet

Capacity regulator (hot gas bypass), type TUH/TCHE/TRHE

Mass ow rate

R404A/R507
0.08 0.07 0.06

TUH & TCHE

Mass ow [kg/s]

0.05 0.04 0.03 0.02 0.01 0.00 -6 -5 -4 -3 -2 -1 0 1 2 3

Conditions used in calculation: tcond = +40C tsubcooling = 4K tsuperheat = 4K etaisentrop = 0.7 Start opening: tevap = 2C pevap = 0.2 bar

TCHE 3 TCHE 4 TUH 9

Evaporating temperature [C]

TRHE
0.4 5 0.4 0 0.3 5

Mass ow [kg/s]

0.3 0 0.2 5 0.2 0 0.1 5 0.1 0 0.0 5 0.0 0 -6 -5 -4 -3 -2 -1 0 1 2 3

Conditions used in calculation: tcond = +40C tsubcooling = 4K tsuperheat = 4K etaisentrop = 0.7 Start opening: tevap = 2C pevap = 0.5 bar

TRHE 10 TRHE 20 TRHE 40 TRHE 80

Evaporating temperature [C]

Correction factor for condensing temperature

Condensing temperature R404A/R507 +30C 0.8 +40C 1.0 +50C 1.2

Above capacities have to be multiplied with the correction factor.

Danfoss A/S (RC-CMS/MWA), 05 - 2005

RD4EG202 DKRCC.PD.HK0.A1.02 / 520H0483

11

Technical leaet

Capacity regulator (hot gas bypass), type TUH/TCHE/TRHE

Rplacement capacity

R407C
8 7

TUH & TCHE


Conditions used in calculation: tcond = +40C tsubcooling = 4K tsuperheat = 4K etaisentrop = 0.7 Start opening: tevap = 2C pevap = 0.2 bar

Replacement capacity [kW]

6 5 4 3 2 1 0 -6 -5 -4 -3 -2 -1 0 1 2 3

TCHE 3 TCHE 4 TUH 9

Evaporating temperature [C]

TRHE
50 45 40 35 30 25 20 15 10 5 0 -6 -5 -4 -3 -2 -1 0 1 2 3

Replacement capacity [kW]

Conditions used in calculation: tcond = +40C tsubcooling = 4K tsuperheat = 4K etaisentrop = 0.7 Start opening: tevap = 2C pevap = 0.5 bar

TRHE 10 TRHE 20 TRHE 40 TRHE 80

Evaporating temperature [C]

Correction factor for condensing temperature

Condensing temperature R407C +30C 0.7 +40C 1.0 +50C 1.4

Above capacities have to be multiplied with the correction factor.

12

RD4EG202 DKRCC.PD.HK0.A1.02 / 520H0483

Danfoss A/S (RC-CMS/MWA), 05 - 2005

Technical leaet

Capacity regulator (hot gas bypass), type TUH/TCHE/TRHE

Mass ow rate

R407C
0.05 0.04

TUH & TCHE


Conditions used in calculation: tcond = +40C tsubcooling = 4K tsuperheat = 4K etaisentrop = 0.7 Start opening: tevap = 2C pevap = 0.2 bar

Mass ow [kg/s]

0.03 0.02

0.01

0.00 -6 -5 -4 -3 -2 -1 0 1 2 3

TCHE 3 TCHE 4 TUH 9

Evaporating temperature [C]

TRHE
0.30 0.25 0.20 0.15 0.10 0.05 0.00 -6 -5 -4 -3 -2 -1 0 1 2 3

Mass ow [kg/s]

Conditions used in calculation: tcond = +40C tsubcooling = 4K tsuperheat = 4K etaisentrop = 0.7 Start opening: tevap = 2C pevap = 0.5 bar

TRHE 10 TRHE 20 TRHE 40 TRHE 80

Evaporating temperature [C]

Correction factor for condensing temperature

Condensing temperature R407C +30C 0.7 +40C 1.0 +50C 1.4

Above capacities have to be multiplied with the correction factor.

Danfoss A/S (RC-CMS/MWA), 05 - 2005

RD4EG202 DKRCC.PD.HK0.A1.02 / 520H0483

13

Technical leaet

Capacity regulator (hot gas bypass), type TUH/TCHE/TRHE

Replacement capacity

R410A
20 18 16 14 12 10 8 6 4 2 0 -6 -5 -4 -3 -2 -1 0 1 2 3

TUH & TCHE


Conditions used in calculation: tcond = +40C tsubcooling = 4K tsuperheat = 4K etaisentrop = 0.7 Start opening: tevap = 18C pevap = 0.2 bar

Replacement capacity [kW]

TCHE 3 TCHE 4 TUH 9

Evaporating temperature [C]

TRHE
120 100

Replacement capacity [kW]

80 60 40 20 0 -6 -5 -4 -3 -2 -1 0 1 2 3

Conditions used in calculation: tcond = +40C tsubcooling = 4K tsuperheat = 4K etaisentrop = 0.7 Start opening: tevap = 2C pevap = 0.5 bar

TRHE 10 TRHE 20 TRHE 40 TRHE 80

Evaporating temperature [C]

Correction factor for condensing temperature

Condensing temperature R410A +30C 0.8 +40C 1.0 +50C 1.2

Above replacement capacity has to be multiplied with the correction factor.

14

RD4EG202 DKRCC.PD.HK0.A1.02 / 520H0483

Danfoss A/S (RC-CMS/MWA), 05 - 2005

Technical leaet

Capacity regulator (hot gas bypass), type TUH/TCHE/TRHE

Mass ow rate

R410A
0.10 0.09 0.08 0.07

TUH & TCHE


Conditions used in calculation: tcond = +40C tsubcooling = 4K tsuperheat = 4K etaisentrop = 0.7 Start opening: tevap = 18C pevap = 0.2 bar

Mass ow [kg/s]

0.06 0.05 0.04 0.03 0.02 0.01 0.00 -6 -5 -4 -3 -2 -1 0 1 2 3

TCHE 3 TCHE 4 TUH 9

Evaporating temperature [C]

TRHE
0.60 0.50

Mass ow [kg/s]

0.40 0.30 0.20 0.10 0.00 -6 -5 -4 -3 -2 -1 0 1 2 3

Conditions used in calculation: tcond = +40C tsubcooling = 4K tsuperheat = 4K etaisentrop = 0.7 Start opening: tevap = 2C pevap = 0.5 bar

TRHE 10 TRHE 20 TRHE 40 TRHE 80

Evaporating temperature [C]

Correction factor for condensing temperature

Condensing temperature R410A +30C 0.8 +40C 1.0 +50C 1.2

Above replacement capacity has to be multiplied with the correction factor.

Danfoss A/S (RC-CMS/MWA), 05 - 2005

RD4EG202 DKRCC.PD.HK0.A1.02 / 520H0483

15

Technical leaet

Capacity regulator (hot gas bypass), type TUH/TCHE/TRHE

Design/Function

1. Bulb with capillary tube 2. Diaphragm element 3. Setting spindle for adjustment of opening point/minimum suction pressure 4. Fixed orice 5. Filter

TUH, Angleway

TCHE, Angleway

1. 2. 3. 4. 5.

Bulb with capillary tube Thermostatic element Pressure pin seal Two-way balanced port Setting spindle for adjustment of static superheat SS

TRHE, Straightway

16

RD4EG202 DKRCC.PD.HK0.A1.02 / 520H0483

Danfoss A/S (RC-CMS/MWA), 05 - 2005

Technical leaet

Capacity regulator (hot gas bypass), type TUH/TCHE/TRHE

Dimensions and weight TUH

Connection dimensions, see ordering table. TUH, Angleway - all dimensions in mm

Weight 0.13 kg

Dimensions and weight TCHE

Connection dimensions, see ordering table. TCHE, Angleway - all dimensions in mm

Weight 0.15 kg

Danfoss A/S (RC-CMS/MWA), 05 - 2005

RD4EG202 DKRCC.PD.HK0.A1.02 / 520H0483

17

Technical leaet

Capacity regulator (hot gas bypass), type TUH/TCHE/TRHE

Dimensions and weight TRHE

Connection dimensions, see ordering table. TRHE, Straightway


Type Connection, ODF solder Inlet outlet in. TRHE10 TRHE20 TRHE40 TRHE80
5 5 7

Inlet outlet mm 16 16 16 16 22 22 28 28

Capillary tube length m 1.5 1.5 3 3

H1 mm 32 37 42 47

H2 mm 7.5 9 13 17

H3 mm 5 8 11 13

H4 mm 104 122 145 165

L1 mm 45.5 48 57.5 67

L2 mm 45.5 48 57.5 67

L3 mm 34.5 38 41 44

L4 mm 70 119 111 148

D1 mm 45 53 60 72

D2 mm 15 16.5 20.3 20.3

Weight kg 0.39 0.60 0.79 1.34

/8 5/8 /8 5/8 /8 7/8

11/8 11/8

18

RD4EG202 DKRCC.PD.HK0.A1.02 / 520H0483

Danfoss A/S (RC-CMS/MWA), 05 - 2005

Technical leaet

Capacity regulator (hot gas bypass), type TUH/TCHE/TRHE

Application TUH and TCHE a

Note: The bulb serves only as a reservoir for the charge, however, it is recommended to mount it in a position where the temperature variation during running conditions is limited (see a and b in the application drawings). b
1. 2. 3. 4. 5. Evaporator Condenser Receiver Solenoid valve Discharge bypass valve with adjustable setting 6. Compressor

System with capillary tube expansion and internal pressure-equalised hot gas bypass valve type TUH

System with capillary tube expansion and external pressure-equalised hot gas bypass valve TCHE or TRHE

System with capillary tube expansion and external pressure-equalised hot gas bypass valve TCHE or TRHE

Danfoss A/S (RC-CMS/MWA), 05 - 2005

RD4EG202 DKRCC.PD.HK0.A1.02 / 520H0483

19

Technical leaet

Capacity regulator (hot gas bypass), type TUH/TCHE/TRHE

Application TRHE

1. 2. 3. 4. 5.

Evaporator Condenser Receiver Solenoid valve Discharge bypass valve with adjustable setting 6. Compressor

System with thermostatic expansion valve expansion and external pressure-equalised hot gas bypass valve TCHE or TRHE

20

RD4EG202 DKRCC.PD.HK0.A1.02 / 520H0483

Danfoss A/S (RC-CMS/MWA), 05 - 2005