User's and Installation Guide UPS 40-160 kVA, 400V 50/60 HZ Output
User's and Installation Guide UPS 40-160 kVA, 400V 50/60 HZ Output
Control Panel
The control panel, located on the front door of the UPS, contains LCD screen and pushbutton switches to control the operation of the UPS, and to display the status of the UPS system.
The Control Panel consists of the following: A Liquid Crystal Display (LCD) screen (1) A horizontal row of pushbutton switches (2) A vertical column of status indicators (3)
When the unit powers up, the screen displays the Powerware logo. To advance to the Main menu and Mimic screen, press any Control Panel pushbutton once. After approximately 30 minutes on inactivity, the display screen darkens. To restore the screen, press any pushbutton once.
You can use the LCD screen and the pushbuttons to: Look at a log of UPS events (alarms, notices, and commands) Monitor UPS operation Set UPS parameters Control UPS operation
1023294 Revision A1
UPS 40 160 kVA, 400V 50/60 Hz output Users and Installation Guide
33
The UPS status area automatically scrolls between the Powerware model number, current date and time, active alarms, active notices, and load percent and battery run time for the UPS. Shown is a typical alarm message. The information area contains data about UPS status and operations. Select a menu option to display the desired information. The menu bar lists the titles of the available screens. To select a screen, press the pushbutton underneath the desired screen. Navigation pushbutton switches. Function changes depending on the screen displayed. Use to select menu screens or scroll through available screens. Designated function is indicated on the LCD screen above the respective pushbutton.
B C D
LOAD OFF
34
UPS 40-160 kVA, 400 V 50/60 Hz output Users and Installation Guide
1023294 Revision A1
Press the HISTORY pushbutton on the Active Events Menu bar to display the History Log. The History Log lists up to the 500 system events in chronological order, with the most recent event listed last. The History Log lists the events in the following groups: User and service status User instruction User alarm Check UPS Schedule service UPS shutdown Service alarm
The end of the log, i.e the most recent events, appears when you display the screen, and you must scroll upward to view older event listings. To scroll through the events, press the UP or DOWN pushbuttons on the menu bar. To return to the Active Events screen, press the EVENTS pushbutton on the menu bar.
The Output screen shows output voltage (phase-to-neutral), output current (each phase), and frequency, being supplied by the UPS, followed by the kVA, kW, and power factor measurements.
1023294 Revision A1
UPS 40 160 kVA, 400V 50/60 Hz output Users and Installation Guide
35
The Output Current Screen displays a real-time bar graph of the output current of the UPS. The graph shows the current for each phase.
The CHGR pushbutton switch, on the System Controls screen, toggles the charger function On and Off. The PM pushbutton switch toggles the Power Module function On and Off.
Figure 27. System Setup Level 0, enter password, and System Setup Level 1 screens.
36
UPS 40-160 kVA, 400 V 50/60 Hz output Users and Installation Guide
1023294 Revision A1
The System Setup Level 1 screen can be used to set the UPS date and time, the serial ports, change the Level 1 password, and logout of Level 1. In addition, the Level 0 functions are available. Use the UP or DOWN pushbuttons to highlight the setup function screen desired, then press the SELECT pushbutton to display the function screen. For example, select COM PORT SETUP from the System Setup Level 1 menu to display the Serial Port Setup screen. This screen allows selection of the serial COM port to set up. Use the UP or DOWN pushbuttons to highlight the COM port to be set up, then press the SELECT pushbutton. To return to the System Setup screen, press the RETURN pushbutton. The COM Setup screen is used to change and save the settings for the serial communication ports. The COM port number selected from the Serial Port Setup screen will be displayed. If the changes are not wanted, the ABORT pushbutton may be used to return to the Serial Port Setup screen. Use the UP or DOWN pushbuttons to highlight the setting to be changed. Use the SELECT pushbutton to toggle through the values for the setting to make the change. Press SAVE or ABORT. Once the action is completed, the Serial Port Setup screen appears.
The Level 1 screen will timeout after 60 minutes, or can be logged out at any time by selecting the LOG OUT function from the menu screen.
1023294 Revision A1
UPS 40 160 kVA, 400V 50/60 Hz output Users and Installation Guide
37
Bypass
Alarm
38
UPS 40-160 kVA, 400 V 50/60 Hz output Users and Installation Guide
1023294 Revision A1
7
7.1
1. 2. 3. 4. 5. 6.
Operating instructions
Starting the UPS in Normal Mode
Close the UPS input feeder circuit breaker. Close UPS Bypass input feeder circuit breaker. Observe UPS Control Panel display screen becoming active as an indication of logic power. Press the CONTROLS pushbutton on the Main menu bar. The System Controls screen appears. On the System Controls screen, the Power Module (PM) status should indicate SHUTDOWN. Press the NORMAL pushbutton on the System Controls menu bar. If Auto Bypass is enabled, the critical load is immediately supplied by the bypass source, in Bypass mode, until the inverter turns on and the UPS transfers to Normal mode. The status indicator on the UPS Control Panel indicates the UPS is in Bypass mode. If Auto Bypass is not enabled, the UPS output remains off until the UPS transfers to Normal mode.
The following procedures provide instructions for operating the UPS system.
7.
Observe the following messages appear sequentially on the Power Module (PM) status line: DC STARTING INVERTER STARTING READY ONLINE The rectier and inverter turn on. When the inverter reaches full voltage, UPS output contactor K3 closes and the static switch turns off supplying power to the critical load in Normal mode. It takes approximately 1 minute for the UPS to achieve Normal mode.
8. 9.
Close battery breaker any time after INVERTER SYNCING or CLOSE BATTERY appears on the display screen. The UPS is now operating in the Normal mode and the NORMAL status indicator is illuminated.
7.2
If the Inverter Output of the UPS is not available and the critical load needs to be energised, perform the following procedure: 1. Close the UPS input feeder circuit breaker.
1023294 Revision A1
UPS 40 160 kVA, 400V 50/60 Hz output Users and Installation Guide
39
2. 3. 4. 5. 6. 7.
Close UPS Bypass input feeder circuit breaker. Observe UPS Control Panel display screen becoming active as an indication of logic power. Press the CONTROLS pushbutton on the Main menu bar. The System Controls screen appears. On the System Controls screen, the Power Module (PM) status should indicate SHUTDOWN. Press the BYPASS pushbutton on the System Controls menu bar. The critical load is immediately supplied by the bypass source, in Bypass mode. The UPS is now operating in the bypass mode and the BYPASS status indicator is illuminated.
7.3
To start the Power Module without transferring the critical load to normal, perform the following procedure: 1. 2. 3. 4. 5. 6. 7. 8. Close the UPS input feeder circuit breaker. Close UPS Bypass input feeder circuit breaker. Observe UPS Control Panel display screen becoming active as an indication of logic power. Press the CONTROLS pushbutton on the Main menu bar. The System Controls screen appears. On the System Controls screen, the Power Module (PM) status should indicate SHUTDOWN. Press the pushbutton to display System Controls Screen 2. Press the PM ON pushbutton on the System Controls menu bar. Observe the following messages appear sequentially on the Power Module (PM) status line: DC STARTING INVERTER STARTING INVERTER SYNCING READY The rectier and inverter turn on. When the inverter reaches full voltage, the UPS is ready to transfer to the Normal mode and supply the critical load.
40
UPS 40-160 kVA, 400 V 50/60 Hz output Users and Installation Guide
1023294 Revision A1
7.4
In Bypass Mode, the critical load is not protected from commercial power interruptions and abnormalities. To transfer the critical load to bypass mode, perform the following procedure: 1. 2. Press the CONTROLS pushbutton on the Main menu bar. The System Control screen appears. Press the BYPASS pushbutton on the System Controls menu bar. The UPS switches to Bypass mode and the critical load is immediately supplied by the bypass source. If the bypass source is not available, the power processor remains on and an alarm sounds. The UPS is now operating in the bypass mode and the BYPASS status indicator is illuminated. The Power Module (PM) status indicates READY. System is now on bypass and UPS power processor remains on.
3.
Warning!
Power is present inside the UPS cabinets.
7.5
1. 2.
To transfer the critical load to normal mode, perform the following procedure:
3.
1023294 Revision A1
UPS 40 160 kVA, 400V 50/60 Hz output Users and Installation Guide
41
Warning!
Power is present inside the UPS cabinets.
7.7
To perform maintenance or service on the critical load, shut down power to the load by performing the following procedure: 1. 2. Turn off all equipment that is being powered by the UPS. Perform LOAD OFF procedure contained in paragraph 7.9. The input, output, and bypass backfeed contactors open, the battery breaker or disconnect is tripped, and the Power Module is turned off.
Warning!
Power is present inside the UPS cabinets, until the upstream input feeder circuit breaker is opened. 3. Open the UPS input and bypass (if dual feed) feeder circuit breakers.
7.8
1. 2. 3.
Charger Control
Press the CONTROLS pushbutton on the Main menu bar. The System Control screen appears. Press the pushbutton to display System Controls Screen 2. Press the CHARGER ON or CHARGER OFF pushbutton on the System Controls menu bar to toggle the charger on or off.
42
UPS 40-160 kVA, 400 V 50/60 Hz output Users and Installation Guide
1023294 Revision A1
7.9
The LOAD OFF pushbutton from the Main menu bar or the System Controls screen menu bar initiates an UPS Load Off. This pushbutton can be pressed to control the UPS output. The UPS LOAD OFF pushbutton de-energizes the critical load and powers down the UPS. The UPS (including Bypass) remains off until restarted. To Use the LOAD OFF Pushbutton: 1. Press the LOAD OFF pushbutton. The Load Off screen appears, providing a choice to proceed with the shutdown or to abort the shutdown.
Note!
All power to the critical load is lost when the LOAD OFF is selected in the following step. You should use this feature only when you want to de-energise the critical load. 2. To shut down the UPS, press LOAD OFF from the Load Off screen menu bar, and hold for three seconds. To abort the shutdown, press CANCEL. When LOAD OFF is selected and held for three seconds, the input, output, and bypass backfeed contactors open, the battery breaker or disconnect is tripped, and the Power Module is turned off.
Note!
Do not attempt to restart the system after Load Off until the cause of the shutdown has been identied and cleared. 3. To restart the UPS after pressing the LOAD OFF pushbutton, follow the procedure, in paragraphs 7.1 or 7.2.
Note!
All power to the critical load is lost when the REPO switch is activated in the following step. You should use this feature only when you want to de-energise the critical load. The following instructions are for the Powerware supplied REPO switch. If a customer supplied REPO switch is used it may not activate in the same manner. If this is the case, refer to the operating instructions provided with the switch.
1023294 Revision A1
UPS 40 160 kVA, 400V 50/60 Hz output Users and Installation Guide
43
1.
Press the REPO pushbutton switch. The input, output, and bypass backfeed contactors open, the battery breaker or disconnect is tripped, and the Power Module is turned off immediately, without asking for verication.
Note!
Do not attempt to restart the system after Load Off until the cause of the shutdown has been identied and cleared. 2. To restart the UPS after using the REPO pushbutton, reset the REPO switch and then follow the procedure, in paragraphs 7.1 or 7.2.
Note!
The integral MBS consist of four switches (S1, S2, S3, S4) and failure to understand the correct sequence may drop the critical load.
44
UPS 40-160 kVA, 400 V 50/60 Hz output Users and Installation Guide
1023294 Revision A1
2. 3. 4. 5. 6. 7. 8.
Perform transfer from normal mode to bypass mode as described in paragraph 7.4. Remember to verify the transfer before proceeding the next step. Turn ON the S3 switch to bypass UPS. Turn OFF the S4 switch to disconnect UPS output: Perform LOAD OFF procedure contained in paragraph 7.9. Turn OFF the S1 switch to disconnect UPS rectier input. Turn OFF the S2 switch to disconnect UPS bypass input: UPS is now in the mechanical bypass mode, see below:
1023294 Revision A1
UPS 40 160 kVA, 400V 50/60 Hz output Users and Installation Guide
45
2. 3. 4. 5. 6. 7. 8.
Turn ON S1 switch to connect rectier input to UPS. Turn ON S2 switch to connect bypass input to UPS: Perform UPS start-up procedure (bypass mode) contained in paragraph 7.2. Turn ON S4 switch to connect UPS output to load. Turn OFF S3 switch to disconnect bypass output. Perform transfer from bypass to normal mode as described in paragraph 7.5. Remember to verify the transfer before proceeding the next step. UPS is now in Normal mode, see below:
46
UPS 40-160 kVA, 400 V 50/60 Hz output Users and Installation Guide
1023294 Revision A1
8.1 General
The components inside the UPS cabinet are secured to a sturdy metal frame. All repairable parts and assemblies are located for easy removal, with very little disassembly. This design allows authorised service personnel to perform routine maintenance and servicing quickly. You must schedule periodic performance checks of your UPS system to keep it running properly. Regular routine checks of operation and system parameters will enable your system to function efciently for many trouble-free years.
Warning!
Qualied service personnel should perform servicing and maintenance only. LETHAL VOLTAGE PRESENT. This unit should not be operated with the cabinet doors open or protective panels removed. Do not make any assumptions about the electrical state of any cabinet in the UPS system. Since each battery string is an energy source in itself, opening the Battery Circuit Breaker does not de-energise the voltage within the battery string. DO NOT ATTEMPT TO ACCESS ANY INTERNAL AREA OF THE BATTERY STRING YOURSELF. VOLTAGES ARE ALWAYS PRESENT IN THE BATTERY STRINGS. If you suspect that a battery string needs service, you should contact your service representative. If the string requires service, refer to the battery manufacturers operating manual for instructions on battery maintenance, or contact your service representative. Observe these precautions when working on or around batteries: Remove watches, rings, or other metal objects. Use tools with insulated handles. Wear rubber gloves and boots. Do not lay tools or metal parts on top of batteries or battery cabinets. Disconnect the charging source prior to connecting or disconnecting terminals. Determine if the battery is inadvertently grounded. If it is, remove the source of the ground. Contact with any part of a grounded battery can result in electrical shock. The likelihood of such shock will be reduced if such grounds are removed during installation and maintenance. When replacing batteries, use the same number of sealed, lead-acid batteries. Proper disposal of batteries is required. Refer to your local codes for disposal requirements.
1023294 Revision A1
UPS 40 160 kVA, 400V 50/60 Hz output Users and Installation Guide
47
3.
48
UPS 40-160 kVA, 400 V 50/60 Hz output Users and Installation Guide
1023294 Revision A1
Note!
The brackets ([ ]) in the following bullets indicate standard keyboard characters. To use a key combination, hold down the Escape key and press the indicated letter key.
1023294 Revision A1
UPS 40 160 kVA, 400V 50/60 Hz output Users and Installation Guide
49
In this mode, system events are continually logged through the serial port to the device connected to the port. The printed log entries contain a time and date stamp and the alarm text message. Terminal mode uses this format for printing alarm entries: MM DD YYYY HH:MM:SS.hh KYWD MESSAGE **** <CR> <LF> Where: Equals: MM Month (2 digits) YYYY Year (4 digits) DD Day (2 digits) HH Hour (2 digits) MM Minute (2 digits) SS Second (2 digits) hh Hundredths of Second (2 digits) KYWD Keyword (ALARM, NOTICE, COMMAND, or STATUS) **** System Diagnostic Information <CR> Carriage Return Character (ASCII 13) <LF> Line Feed (ASCII 10) An alarm message is prexed by the word CLEAR whenever an alarm is entered into the Event History Log with a cleared status. If a port is operating in Terminal mode and is connected to a computer, you can press [Esc] [H] to print the entire log with a rmware version header. Here is a sample Event History Log printout: 03/11/2004 14:13:12.954 NOTICE: Battery Voltage Low
50
UPS 40-160 kVA, 400 V 50/60 Hz output Users and Installation Guide
1023294 Revision A1