TRANSMITTERS TO DETECT CARBON DIOXIDE (CO 2 )
Measure carbon dioxide (CO2), carbon monoxide (CO) and temperature (T) Infrared measurement technology (NDIR) Automatic calibration eliminates maintenance requirements CO2 Measurement ranges from 040,000 ppm (04 %vol) Suitable for Commercial and Industrial applications where good indoor air quality is critical Analog output signals Available with relays, display and alarms Power supply 24 VDC/AC Range of application 050 C (30...120 F) / 095 %RH
T R A N S M I T T E R S F O R C O 2 , C O A N D T E M P E R AT U R E
Features Measurement range CO2: 03,000 ppm / temperature: 050 C / 30...120 F Measurement technique: infrared (NDIR) with automatic calibration Accuracy: 30 ppm Power supply: 16...29 VDC/AC Output 1 (0...2,000 ppm): 0/210 VDC or 0/420 mA Output 2 (0...50 C): 0/210 VDC or 0/420 mA Range of application: 050 C (30...120 F) / 095 %RH Maintenance: not necessary Lifetime: >15 years
CF5-W-Disp
Description Installed in the environment to be monitored Dimensions: 120 x 82 x 30 mm Enclosure protection: IP30 Duct mount design for insertion into ducts and vents Dimensions: 142 x 84 x 46 mm / Probe 245 x 22 x 15 mm Enclosure protection: IP65
CF5-D CF5-D-Disp*
CF5-D-Disp
T R A N S M I T T E R S F O R C O 2 , C O A N D T E M P E R AT U R E
CF3, CO 2 TRANSMITTERS
Applications For ventilation control in residential properties, offices, classrooms, cinemas, public rooms, etc.
Features Measurement range: 02,000 ppm Measurement technique: infrared (NDIR) with automatic calibration Accuracy: 30 ppm Power supply: 16...29 VDC/AC Output 1 (0...2,000 ppm): 010 VDC Output 2 (0...2,000 ppm): 420 mA (no output 2 in CF3-W-EU(US)-Disp-FLI) Range of application: 050 C (30...120 F) / 095 %RH Maintenance: not necessary Lifetime: >15 years Order code CF3-W-EU CF3-W-EU-Disp* Dimensions: 100 x 80 x 28 mm Enclosure protection: IP30 CF3-W-US CF3-W-US-Disp* Installed in the enthronement to be monitored and fits directly onstandard US surface-mounted boxes Dimensions: 130 x 85 x 30 mm Enclosure protection: IP30 CF3-D CF3-D-Disp* Duct mount design for insertion into ducts and vents Dimensions: 142 x 84 x 46 mm / Probe 245 x 22 x 15 mm Enclosure protection: IP65 CF3-W-EU-Disp-FLI* Measures the CO2 concentration in rooms and emits an audible and visual alarm (fresh air indicator) when a value of 1,400 ppm is exceeded. Mute button on the side of the housing. Fits directly on standard EU surface-mounted boxes. Dimensions: 100 x 80 x 28 mm Enclosure protection: IP30 Measures the CO2 concentration in rooms and emits an audible and visual alarm (fresh air indicator) when a value of 1,400 ppm is exceeded. Red mute button on the front of the housing. Fits directly on standard US surface-mounted boxes. Dimensions: 130 x 85 x 30 mm Enclosure protection: IP30
CF3-W-US-Disp-FLI CF3-D-Disp CF3-W-US-Disp
Description Installed in the enthronement to be monitored and fits directly on standard EU surface-mounted boxes
CF3-W-EU-Disp
CF3-W-EU-Disp-FLI
CF3-W-US-Disp-FLI*
T R A N S M I T T E R S F O R C O 2 , C O A N D T E M P E R AT U R E
Applications
Ventilation control in underground garages, Ventilation control in greenhouses and harsh transport/storage, vehicle terminals, tunnels, etc. environments
Model Measurement range CO2 Accuracy Temperature measurement range Power supply Output 1 (0...4 %vol) Output 2 (0...4 %vol) Output 2 (0...50 C) Output 3 (CO2) Output 4 (CO2) Dimensions Enclosure protection Range of application Communication Maintenance Lifetime Order code
AL (Alarm)
0/210 VDC or 0/420 mA Relay 1: open <1.4 %, closed >1.5 % Relay 2: open <2.9 %, closed >3.0 %
0/210 VDC or 0/420 mA Relay 1: open <1.9 %, closed >2.0 % 142 x 84 x 46 mm IP54 050 C (30...120 F) / 095 %RH MODBUS
Is not necessary for normal indoor applications. Certain industrial applications require annual calibration. >15 years CF8-W-Disp-AL CF8-W-Disp-GH
T R A N S M I T T E R S F O R C O 2 , C O A N D T E M P E R AT U R E
Applications
Monitoring of carbon monoxide and carbon dioxide in underground garages, tunnels, mines, latrge halls, with relays for CO2 and CO alarm systems.
Model Measurement range CO2 Measurement range CO Accuracy CO2 Accuracy CO Power supply Output 1 (0...100 ppm CO) Output 1 (0...3 %vol CO2) Output 2 (0...2 %vol CO2) Output 3, relay Dimensions Enclosure protection Range of application Communication Maintenance Lifetime Order code
CO (Carbon Monoxide) 03,000 ppm 0100 ppm 30 ppm 10 ppm 0/210 VDC or 0/420 mA open >35 ppm (CO) and >1'500 ppm (CO2) closed <30 ppm (CO) and <1'400 ppm (CO2) 142 x 84 x 46 mm IP54
IN (Incubator) 03 %vol (030,000 ppm) 200 ppm 16...29 VDC/AC 2...10 VDC or 4...20 mA 0...5 VDC or 0...10 mA 40 x 102 mm 050 C (30...120 F) / 095 %RH
MODBUS, RS-485 (optional) Is not necessary for indoor applications. Industrial applications may require annual calibration. >5 years (limited by the CO probe) CF8-W-Disp-CO
T R A N S M I T T E R S F O R C O 2 , C O A N D T E M P E R AT U R E
THE FUNDAMENTALS OF CO 2
Carbon dioxide (CO2) is a colorless and orderless gas that exists in the earths atmosphere and which is dangerous in high concentrations. The proportion of CO2 in natural ambient air is about 0.04 % or 400 ppm. When humans and animals exhale this gas, it is quickly mixed with the ambient air, as well as in rooms that are well ventilated. A high CO2 content becomes apparent in humans through rapid fatigue and loss of concentration. The negative effects become noticeable more quickly in small rooms in which there are many people or that are not well ventilated. Modern climate control systems measure not only parameters such as relative humidity and temperature, but also CO2 content. The concentration of CO2 is regarded as an important indicator for the quality of room air.
Guidelines
350 - 450 ppm 400 - 1,200 ppm > 1,000 ppm 5,000 ppm (0.5 %vol) Fresh air outdoors Room air Fatigue and loss of concentration become apparent Maximum permissible value at the workplace during an 8-hour workday 38,000 ppm (3.8 %vol) Breathing air (direct exhalation) > 100,000 ppm (10 %vol) Nausea, vomiting, loss of consciousness and death
Measurement technique
The measurement technique is based on non-dispersive infrared (NDIR) technology.
Calibration
All sensors are calibrated they have a lifetime of more than 15 years in normal indoor applications. The automatic baseline correction means the sensors require no further calibration.
ROTRONIC AG, Grindelstrasse 6, CH - 8303 Bassersdorf, Tel. +41 44 838 11 11, Fax +41 44 836 44 24, www.rotronic.ch ROTRONIC Instruments (UK) Ltd, Crompton Fields, Crompton Way, Crawley, West Sussex, RH10 9EE, UK, Phone +44 (0)1293 571000, Fax +44 (0)1293 571008, www.rotronic.co.uk ROTRONIC Instrument Corp, 135 Engineers Road, Hauppauge, NY 11788, USA , Phone, +1 631 427-3898, Fax, +1 631 427-3902, www.rotronic-usa.com