Varlogic NR6, NR12 Power Factor Controller: User Manual

Download as pdf or txt
Download as pdf or txt
You are on page 1of 32

Varlogic NR6, NR12 Power factor controller

User manual
DB121630

Power Factor Controller NR6 / NR12 User manual Table of Contents


1. General ..............................................................................................3
1.1 Safety .......................................................................................................... 3 1.2 Description ................................................................................................. 3

2. Installation ........................................................................................5 3. Display ..............................................................................................6 4. Start-up Procedure ...........................................................................6 5. Menu Operations ..............................................................................7
5.1 General ........................................................................................................ 7 5.2 Main Menu ................................................................................................... 9 5.3 Bank Pre-Conguration ........................................................................... 11 5.4 Commissioning ........................................................................................ 13 5.5 Auto Setup of Parameters ........................................................................ 14 5.6 Manual Setup of Parameters ................................................................... 15 5.7 Measurement Menu .................................................................................. 17 5.8 Parameter Update ..................................................................................... 18 5.9 Alarms Menu ............................................................................................. 19 5.10 Maintenance Menu ................................................................................. 21

6. Miscellaneous ................................................................................22
6.1 Stepping Programs .................................................................................. 22 6.2 Manual calculation of response value .................................................... 26 6.3 High Voltage use of NR6/NR12 ................................................................ 27

7. Glossary ..........................................................................................29 8. Technical specications ................................................................32

3653491EN_01.indd

Power Factor Controller NR6 / NR12 User manual 1. General


The following precautions must be taken into account when installing and operating the controller: @ The installation of the controller must be performed by a qualied electrician. @ Do not touch the connectors when the controller is energized, make sure that the operating voltage is disconnected before touching any parts located on the rear side of the controller. @ Do not open a live current circuit, this may cause dangerous overvoltages. Always short circuit the current transformer (CT) before replacing or removing the controller installed in a bank. @ Do not open the controller casing, there are no user serviceable parts inside. For better understanding of the terminology used, please refer to the Glossary (chapter 7) at the end of this manual.

1.1 Safety

1.2 Description
DB121632

Front view: Legend A B C D E F Display Keys Opening of door Door Alarm information Mounting bracket for panel mounting installation 3

3653491EN_01.indd

Power Factor Controller NR6 / NR12 User manual


DB121631

Rear view: Legend G H I J K L M


DB121633

Step output connectors Specication label Mounting bracket for panel mounting installation Fixing spring for DIN-rail mounting Current/voltage connection inputs Fan and alarm outputs DIN-rail mounting installation area

Side view: Legend


N

Screwdriver guide

See Chapter 8 for technical specications. 4


3653491EN_01.indd

Power Factor Controller NR6 / NR12 User manual 2. Installation

The controller is designed for either panel (cut-out 138 x 138 mm) or DIN-rail installation. It is locked to the rail by a screwdriver-operated xing spring and to a panel by a side tting spring. There are two ways of connecting the controller to the network: (CT on the same line phase) @ Voltage LN (Line Neutral) (CT on the third phase) @ Voltage LL (Line Line) Incorrect connections can be automatically corrected by the controller when Auto Setup is selected from the main menu. Caution: For use in HV network, look rst at chapter 6.3.
DB121673

Figure 1: Controller connections.

3653491EN_01.indd

Power Factor Controller NR6 / NR12 User manual 3. Display


DB121674

The controller is equipped with a backlighted LCD-display.

Figure 2: Display layout and symbols.

4. Start-up Procedure

Before connecting power, check the wiring of all controller terminals. Check carefully for correct operating voltage. Selection of wrong voltage input can permanently damage the controller. After the rst power switch-on, the controller will automatically ask for the language setting of the menu.

3653491EN_01.indd

Power Factor Controller NR6 / NR12 User manual


DB121675

Figure 3: Language setting dialog.

5. Menu Operations
5.1 General
Navigation between different menu levels. As a precaution against accidental use, the access of certain menus has been protected by a keylock, which is a special sequence of keystrokes enabling the use the particular menu item.

3653491EN_01.indd

Power Factor Controller NR6 / NR12 User manual


DB121676

Figure 4: General way of entering the menu with a keylock. Adjusting a value.
DB121677

Figure 5: Adjusting a value. Special case: The wiring editor.


DB121677

Figure 6: The wiring editor.

3653491EN_01.indd

Power Factor Controller NR6 / NR12 User manual


5.2 Main Menu

The main menu contains all basic submenus required to set up and operate the controller. Which menu to choose ?
DB121678

Figure 7: Required skills and menu selection. If bank preconguration is properly done, commissioning does not require any special skill.

3653491EN_01.indd

Power Factor Controller NR6 / NR12 User manual


(1) Bank pre-conguration When factory settings have not been changed, this menu provides the bank builder the means of pre-conguring the bank at the workshop. After pre-conguration, this menu topic is replaced by (2) Commissioning, by which the controller is taken into service. (3) Automatic setup of parameters In the event that the controller has not been pre-congured, an inexperienced user can automatically set up all the characteristics of the bank and bring it into service. (4) Manual setup of parameters In the event that the controller has not been pre-congured, an experienced user can manually set up all the characteristics of the bank and bring it into service. (5) Measurement The measurement menu contains the most common measurements taken from the network and provides some information about the bank. This is a read-only menu. (6) Parameter update At any time, an experienced user can access the most common operating parameters from this menu. Unlike the conguration and setup sequences, this is a menu allowing a free and unrestricted entry into all its items and should be used when an occasional parameter access is needed. (7) Alarm settings To adjust status and parameters of alarms. (8) Maintenance The maintenance menu provides some useful information about the usage of the bank, capacitors and contactors. Some auxiliary settings and action have also been provided. This menu is basically intended for use by the manufacturers maintenance team.
DB121679

Figure 8: Main menu.

10

3653491EN_01.indd

Power Factor Controller NR6 / NR12 User manual


5.3 Bank Pre-Conguration

This menu item is a forced sequence, meaning that all items must be accessed before the pre-conguration takes place. NOTE: Do not use of the Bank Pre-Conguration menu for HV network applications. key.

The sequence can be interrupted by pressing

See Glossary (chapter 7) for parameters denitions.

3653491EN_01.indd

11

Power Factor Controller NR6 / NR12 User manual


DB121680

Figure 9: Bank pre-conguration.

12

3653491EN_01.indd

Power Factor Controller NR6 / NR12 User manual


5.4 Commissioning

A pre-congured controller is put into service by this menu. The sequence contains an automatic parameter verication to check that the manually entered parameters agree with the network used. See Glossary (chapter 7) for parameter denitions. NOTE: Do not use of the Commissioning menu for HV network applications.
DB121681

Figure 10: Commissioning. What to do in case of error? Error codes can help you to identify a problem and make corrections.
3653491EN_01.indd

13

Power Factor Controller NR6 / NR12 User manual


Code Meaning Action to do Unstable network: The controller is @ Enter the parameter settings unable to operate due to excessive manually using Parameter Update load variations on the network. CT menu. @ Rerun the commissioning sequence. oversized. Step size too small: The effect of the @ Check wiring, CT, condition of 1st step cannot be measured. CT capacitor steps (1st step). oversized, wrong wiring, inoperative steps. Sequence not found: Step ratio does @ Check the condition and sizes of not match available step sequences. steps and contactors. @ Check the condition and sizes of Step size too large: The ratio of measured step compared with the 1st steps and contactors. step is too large. Step sequence cannot be resolved. Non-relevant autosetup process with @ Use manual setup to conrm or this bank conguration. correct the information obtained by autosetup. Reserved to Wiring verify error: Controller wiring @ Check the wiring of voltageand not correct. current inputs. @ Check the Wiring setting from Parameter Update menu. Step count error: The Number of @ Check the Number of Steps setting. @ Check the number of steps in the Steps setting is incorrect. bank and the condition of steps. Step sequence error: The step size @ Check Step Sequence setting @ Check step sizes used in the bank ratios differ from the selected step sequence. @ Check the response value used C/K value error. @ Check the size of 1st step in the bank

5.5 Auto Setup of Parameters


The auto setup sequence is intended for inexperienced users so they can commission the bank with minimal prior knowledge. The user need only input three of the most common parameters and then launch an automatic search for the other parameters. NOTE: The use of Auto Setup of Parameters menu is forbidden on HV network applications.

In the event of error, see the Commissioning Menu (chapter 5.4). 14


3653491EN_01.indd

Power Factor Controller NR6 / NR12 User manual


DB121682

Figure 11: Auto setup of parameters.

5.6 Manual Setup of Parameters


The manual setup sequence is intended for experienced users. There are nine important parameters to input before the controller can be taken into service. This sequence is completed by an automatic verication of the parameters entered earlier in this sequence. This menu item is a forced sequence, meaning that all items must be accessed before the validation of the setup takes place. key. The sequence can be interrupted by pressing See Glossary (chapter 7), for parameter denitions. In case of error, refer to the Commissioning Menu, chapter 5.4.
3653491EN_01.indd

15

Power Factor Controller NR6 / NR12 User manual


DB121683

Figure 12: Manual setup of parameters. 16


3653491EN_01.indd

Power Factor Controller NR6 / NR12 User manual


5.7 Measurement Menu

The measurement menu contains the most common measurements taken from the network. This is a read-only menu sequence.
DB121684

Figure 13: Measurement menu.

3653491EN_01.indd

17

Power Factor Controller NR6 / NR12 User manual


5.8 Parameter Update

The most common operating parameters can be accessed from this menu. Unlike the conguration and setup sequences presented earlier in this text, this is a menu allowing a free and unrestricted entry into all of its items and should be used when occasional parameter access is needed. See Glossary (chapter 7), for parameter denitions. In case of error, refer to the Commissioning Menu, chapter 5.4..
DB121533

Figure 14: Parameter update.

18

3653491EN_01.indd

Power Factor Controller NR6 / NR12 User manual


5.9 Alarms Menu

In Alarms menu, each individual alarm can be enabled or disabled. Once an alarm condition is detected, the corresponding alarm number is shown at the upper part of the display, and the alarm symbol is on. The alarm relay is also activated.
An alarm can be reset by an extended pressure of key, this clears all passive alarms. If alarm condition is still active, the alarm cannot be reset.

List of alarms: Alarm Alarm Possible cause No. 1 Low power factor @ Wiring or LL/LN denition error. @ Undersized bank. 2 Hunting @ Too small C/K value. @ Wrong program choice. @ Defective capacitors (optimal program). 3 Abnormal Cos Phi @ Wiring mistake. @ overcapacitive network (welded contactors). @ Too low current. 4 Low voltage 5 6 7 8 9 10 Overcapacitive @ Wiring or LL/LN denition error. @ Improper use of xed steps. Wrong frequency @ Wrong or unstable network frequency detected at startup. @ Undersized CT.

Controller action

Pauses regulation for 10 minutes.

Disconnection till voltage returns. Stop regulation. No automatic restart. Temporary disconnection of steps. Temporary disconnection of steps. Temporary disconnection of steps.

Overcurrent Overvoltage

Overtemperature @ Ambient temperature too high. @ Defective coolingsystem. Voltage distortion @ Harmonic pollution. @ Resonance.

3653491EN_01.indd

19

Power Factor Controller NR6 / NR12 User manual


Alarm contacts are @ closed when the controller is not energized. @ opened when the controller is energized without alarm. @ closed when the controller is energized with alarm. ALRM.SET @ informs on the status of each alarm: enabled or disabled. @ allows enabling or disabling of each individual alarm by setting it ON or OFF. If an alarm is set to OFF, it cannot cause an alarm under any condition. To allow a normal alarm response, the appropriate alarm must be enabled, i.e. set ON. Some alarm triggering levels can be adjusted @ Alarm No 9 (overtemperature ), with temperature limit setting. @ Alarm No 10 (voltage distortion ), with THD(U) limit setting.
DB121685

Figure 15: Alarms menu.

20

3653491EN_01.indd

Power Factor Controller NR6 / NR12 User manual


5.10 Maintenance menu

The maintenance menu provides useful information about the usage of the bank, capacitors and contactors. Also, some auxiliary settings have been provided.
CAUTION: This menu access is dedicated to specialists.

CAUTION: In case of installation in a HV bank (with VT), you must adjust the default factory settings. The reconnection delay must be changed to a larger value (e.g. 600 secs) to prevent destruction of capacitors.
DB121686

Figure 16/1: Maintenance menu.


3653491EN_01.indd

21

Power Factor Controller NR6 / NR12 User manual


DB121687

Figure 16/2: Maintenance menu.

6. Miscellaneous
The controller's algorithm will try to reach the target cos inside a tolerance area dependant upon the C/K value. It reaches the value by switching on or off available relevant steps. The regulation step program choice is as follows: a) Stack Program (linear): All capacitor steps are of equal size (ex: 1.1.1.1). The operation sequence obeys to a last-in-rst-out (LIFO) principle. The rst step connected will be the last one to be disconnected and vice versa. See Fig. 17 22
3653491EN_01.indd

6.1 Stepping programs

Power Factor Controller NR6 / NR12 User manual


b) Normal program (2+ linear) Normal program can be used on bank whose step ratio is 1.2.4.4.. The linear sequence starts with the 3rd step. The two rst steps are used as ne-tuning. The controller always start by switching the rst step then the second. Other steps are used successively. See Fig. 18. c) Circular A program All capacitor steps are of equal size (ex: 1.1.1.1). The operation sequence obeys the rst-in-rst-out (FIFO) principle. The rst step connected will be the rst one to be disconnected and vice versa. Then a circular sequence is followed. In order to operate correctly, the number of steps programmed into the controller must strictly comply with the number of physical steps. See Fig. 19. d) Circular B program (1+Circular) Circular B program can be used on a bank whose step ratio is 1.2.2.2.. The rst step is used as tuning after the activating limit is exceeded. The circular sequence starts with the 2nd step.

Step Step number demand 1 2 3 4


+ X + X X + X X X + X X X X + X X X X + X X X X X X X X X X X X X X X X X + X X X + X X X X + X X X X X X X X X X X X X X Figure 17: Stack program
Operation sequence 1:1:1:1

Step Step number demand 1 2 3 4


+ X + X X + X X X + X X X X X X X X X + X X X + X X X X + X X X X X X X X X X X X Figure 18: Normal program
Operation sequence 1:2:4:4

X X X

X X X

3653491EN_01.indd

23

Power Factor Controller NR6 / NR12 User manual


Step demand Step number 1 2 3 4

Step Step number demand 1 2 3 4 5


+ X + X X + X X X X X + X X X + X X X X X X X X X X + X X + X X X + X X X + X X X X X X X X X X Figure 20: Circular B program
Operation sequence 1:2:2

+ X + X X + X X X + X X X X X X X X X + X X X + X X X X X X + X X + X X X X X Figure 19: Circular A program


Operation sequence 1:1:1

X X X X X X

X X X X X

e) Optimal Program: The optimal program operates with many step congurations: 1.1.1.1.1 1.2.2.2.2 1.2.4.4.4 1.2.4.8.8 1.1.2.2.2 1.1.2.3.3 1.1.2.4.4 1.2.3.3.3 1.2.3.4.4 1.2.3.6.6 The target cos power is reached using the fewest number of steps in minimal time. Like the circular program, this algorithm equalises the usage of steps. This program uses optimally selected steps sizes when approaching the target power and at the same time the response delays are shortened, particularly if there is a large requirement for kvar or if the network suddenly becomes capacitive. Comparison between normal and optimal program: Normal program will reach the cos target value by successive connection/ disconnection of kvar corresponding to the smallest step value. Optimal program will reach the target cos value by successive connection/ disconnection of kvar corresponding to the highest relevant and available step value.

24

3653491EN_01.indd

Power Factor Controller NR6 / NR12 User manual


Optimal Stepping Program
DB121688

Uncompensated reactive power

Compensated reactive power

+4
Connection of steps

Step sizes : 1:2:4:4

+4 +4 Ind Cap
Steps on : 4

+1
Steps on : 4+4+4+1

t
Steps on : 4+1

-4 -4
Disconnection of steps

-4

Normal Stepping Program


DB121688

+1 +2 +4 +4

Step sizes : 1:2:4:4

Ind Cap
Steps on : 4

+4 -1 -2 -4
Steps on : 4+4+4+4 Steps on : 4

-4 -4

Figure 21: Regulation example - Optimal vs. Normal.


3653491EN_01.indd

25

Power Factor Controller NR6 / NR12 User manual


6.2 Manual calculation of response value

Normally the response value, more generally known as the C/K value, is set automatically as a part of the Auto Setup sequence, but there are cases when these values must be entered manually. The correct value can be calculated using an equation requiring the 1st step size (in vars), line-to-line voltage of the network used (in volts) and the CT ratio as follows:
C/K= Q1st I1 / 5A x ULL x 3

where

Q1st = = ULL I1/5A =

size of 1st step in vars line-to-line voltage in volts CT ratio

Alternatively, the C/K value can be taken from the table below (valid for 400 V networks) n1/n2 30 100/5 150/5 1.44 200/5 1.08 250/5 0.87 300/5 0.72 400/5 0.54 500/5 0.43 600/5 0.36 800/5 0.27 1000/5 1500/5 2000/5 2500/5 3000/5 Table 1: C/K-values for 400 V network. Smallest step (kvar) 12.5 20 25 0.91 1.44 0.80 0.96 1.20 0.45 0.72 0.90 0.36 0.58 0.72 0.30 0.48 0.60 0.36 0.45 0.29 0.36 0.30 40 1.44 1.16 0.96 0.72 0.58 0.40 0.36 0.29 50 60 100

1.44 1.16 0.90 0.72 0.60 0.45 0.36 0.24

1.44 1.08 0.87 0.72 0.54 0.43 0.29 0.22

1.44 1.20 0.90 0.72 0.48 0.36 0.29 0.24

26

3653491EN_01.indd

Power Factor Controller NR6 / NR12 User manual


By successive connections (or disconnections) of steps we adjust the reactive power between two symmetrical limits corresponding to response value.
DB121689

Figure 22: Compensation example and consequences.

6.3 High Voltage use of NR6/NR12

This controller is primarily intended for LV network, but may be used in HV networks under the commissioners full responsibility, if the following points are taken into account. Connections must employ VT and CT with respect to the following gure. In HV applications the power values displayed in Measurement Menu represent only the secondary side values of the VT. To avoid potential misunderstandings, set the CT ratio to percentage scale. Safety (or reconnection) delay must be adapted to the value of the discharge resistors of the capacitors, the most usual value is 10 minutes (600 seconds). The controllers default response delay is adapted for LV use. Using too short a response delay may damage the capacitors. Important: @ the whole commissioning process must be performed using the Manual setup menu and Parameter menu @ the commissioner should not use Bank Pre-Conguration and Commissioning menus @ the use of Auto Setup menu is strictly forbidden to prevent capacitor destruction.
3653491EN_01.indd

27

Power Factor Controller NR6 / NR12 User manual


DB121690

Figure 23: HV use of the controller.

28

3653491EN_01.indd

Power Factor Controller NR6 / NR12 User manual 7. Glossary


Alarms Menu. Alarm Setup (Enable/Disable). Automatic search of C/K response value. Automatic Setup Sequence. Bank Pre-conguration Sequence Menu. Bank Test: each step is automatically connected and disconnected in turn. This facilitates testing of the operation of each capacitor step contactor. See also Step Test. CIRC.A Circular A stepping program. CIRC.B Circular B stepping program. C/K Response value, normally set up automatically by the controller. CLR.STAT Clear Statistics. COMMISS Commissioning Sequence Menu. COS PHI Target cos value. 0.8ind 1.00 CT Current Transformer primary setting, xxx/5 A.25/5 % DELAY Safety Delay or reconnection delay. 10s 50s Response delay is xed 20% of reconnection delay. The default value corresponds to capacitors with internal discharge resistors 50V 1 min. ENGLISH Language names: English, for instance. ERR NN Error in parameter search or verify. NN= error number. FACTOR.S Restore Factory Settings. IGNORED The controller does not require the information about step sequence for any program outside Optimal. The controller denes it automatically. I HIGH Current too high. I LOW Current too low. <2.5% IN LANGUAG Language Selection for menus. LL Line to Line connection. LN Line to Neutral connection. LV Low Voltage. MAINTEN Maintenance Menu. MAN.SET Manual Setup Sequence Menu. Display information ALARMS ALRM.SET AUTO AUTO.SET BANK.PRE BANK.TST Long form text Min value Default Max value value

0.9cap 6000/5 600s

>115% IN

3653491EN_01.indd

29

Power Factor Controller NR6 / NR12 User manual


Display Long form text Min information value MANUAL Manual setting of C/K response value. See 0.01 further. MEASURE Measurements Menu. N.CONNEC Number of Connections. N.STEPS Number of used steps. 1 NORMAL Normal, Standard stepping program. OPTIM Optimal program. PARAMET Parameters Menu. PROGRAM Selection of suitable stepping program between (see 6.1 Stepping programs) The controlers algorithm will try to reach the target cos inside a tolerance area dependant upon the C/K value. It reaches the value by switching on or off available relevant steps. Stack Normal Circular A Circular B Optimal SEARCH Search (response value, step sizes, wiring...) SERIAL.N Serial Number of the product (for internal manufacturer use) STACK Linear stepping program. STEP.SEQ Setting of Step Size Sequence 1.1.1.1.1 - 1.1.2.2.2 - 1.1.2.3.3 - 1.1.2.4.4 1.2.2.2.2 1.2.4.4.4 - 1.2.4.8.8 -1.2.3.3.3 - 1.2.3.4.4 1.2.3.6.6 This concerns the Optimal program. Step sequence are predened with other programs and modication request are not then taken into account. STEP.TST Step Test: each step can be manually connected and disconnected. This facilitates testing of the operation of each capacitor step contactor. See also Bank Test. TEMP.LIM Temperature Limit (adjustable) Fan switch- 20C on limit is 15C lower than temperature limit. THD.U Total Harmonic Distortion of Voltage. Default Max value value 0.50 1.99

6/12

12

50C

60C

30

3653491EN_01.indd

Power Factor Controller NR6 / NR12 User manual


Display Long form text information THD.U.LIM Maximum Harmonic Distortion of Voltage (adjustable). U LOW Voltage too low. UPTIME Uptime (Power On Hours). VERIFY Automatic verication of parameters. VERSION Software version number (for internal manufacturer use). VOLTAGE Input Voltage reference value for voltage alarms. WIRING Connections of voltage and current inputs. Example: U.L2-L3 (Voltage connected between phase 2 and 3) Example: I.1.AUTO (Current connected to phase 1 with automatic polarity selection) Current polarity selections: DIR = direct connection INV = inverted connection AUTO = automatic polarity (dened by controller) Min value 5% <85%UN Default Max value value 7% 20%

80V

400V

460V

3653491EN_01.indd

31

Power Factor Controller NR6 / NR12 User manual 8. Technical specications


Number of steps Dimensions Frequency Measuring current Measuring and supply voltages Relay outputs Display Protection class Target cos -range Response limits, C/K Reconnection delay Response delay Displayed measurements Installation method Casing Operating temperature range Alarm log Step counters Fan control with dedicated relay Accuracy (of FS) 6 or 12 155 x 158 x 70 mm 48...52 Hz, 58...62 Hz 05 A 88...130 V 185265 V 320460 V 120 Vac/5A, 250 Vac/2A, 400 Vac/1A 110 Vdc/0.3A, 60 Vdc/0.6A, 24 Vdc/2A LCD glass with 160 symbols, backlighted IP41 front panel, IP20 rear part 0.85 ind 1.00 0.90 cap 0.01 1.99 symmetrical 10600 s 20 % of reconnection delay, min. 10 s cos , P, Q, S, THD(U), temperature Panel installation, DIN-rail installation Impact resistant PC/ABS, UL94V-0 060C List of 5 last alarms Yes Yes Is: 5% Iq: 5% U/I-samples: 5% Phase: 5 Distortion: 3 dB (up to 11th) Temperature: 3C 25/5 6000/5 Reaction time > 15 ms CEI 61010-1 CEI 61000-6-2 CEI 61000-6-4 CEI 61326

Schneider Electric Industries SAS


Rectiphase 399 rue de la Gare 74370 Pringy France Tel.: 33 (0)4 50 66 95 00 Fax: 33 (0)4 50 27 24 19 http://www.schneider-electric.com http://www.merlin-gerin.com

As standards, specications and designs change from time to time, please ask for conrmation of the information given in this publication. Printed on ecological paper. Layout: Schneider Electric - Sedoc Photos: Schneider Electric Printing: 04-2009

N 3653491EN_01

2009 - Schneider Electric - All rights reserved.

CT setting range Power outage detection Approvals

You might also like