Operation and Maintenance of HVAC Water System
Operation and Maintenance of HVAC Water System
Operation and Maintenance of HVAC Water System
Topics: Introduction Types of Water-Distribution Systems Key Components of Water-Distribution Systems Safety Issues Best Practices for Efficient Operation Best Practices for Maintenance Maintenance Schedule for Water-Distribution Systems References
Introduction
Many large buildings and campuses have HVAC water-distribution systems, also called hydronic systems. Water is heated or cooled in a central plant, then pumped to air handlers, where ventilation air is conditioned as needed. Maintaining and optimizing the performance of pumps and valvesthe key mechanical components of water-distribution systemscan be challenging. These systems often have hidden performance problems that waste energy and cause excessive wear on equipment. As with other mechanical components of the HVAC system, a preventive and predictive maintenance plan is an excellent way to maintain an efficient system, save energy dollars, prevent costly breakdowns, and extend equipment life. Learn more about establishing a Best Practice Operation-and-Maintenance Program.
Produced by BetterBricks, the commercial initiative of the Northwest Energy Efficiency Alliance BOpEqSysWaterDistributionSystem.doc 1
Produced by BetterBricks, the commercial initiative of the Northwest Energy Efficiency Alliance BOpEqSysWaterDistributionSystem.doc 2
In cold weather, if the loop temperature drops below 65F, the water will be diverted through a boiler to increase the water temperature in the loop. Hydronic heat pumps are typically closed-loop systems. Ground-source water-loop heat pumps: This is a water-loop heat-pump system (as described above) with the addition of an extensive piping loop buried in the ground which acts as a heat sink. Heat is absorbed from the ground by the water in the piping loop in heating season, and rejected into the ground in cooling season.
Produced by BetterBricks, the commercial initiative of the Northwest Energy Efficiency Alliance BOpEqSysWaterDistributionSystem.doc 3
Schematic of primary-secondary loop system Primary-loop variable-flow systems: These are chilled-water or heating-water systems with a single variable-flow loop. A two-way bypass valve is typically used to maintain a minimum specified flow rate through the chiller or boiler. Primary-loop variable-flow systems are more efficient than primary-secondary variable-flow systems.
Centrifugal pump Valves: Manual or automatic valves regulate the flow of water throughout the piping system. Valves perform four basic functions: 1) starting, stopping, and directing flow; 2) regulating or throttling flow; 3) preventing backflow; and 4) relieving or regulating pressure.
Produced by BetterBricks, the commercial initiative of the Northwest Energy Efficiency Alliance BOpEqSysWaterDistributionSystem.doc 4
Balance valves, also called circuit setters, are a special type of regulating valve that limit flow at design conditions. This allows the system to be balanced so that every coil in the system has adequate flow. Excessive pressure drop across these valves can waste a considerable amount of energy. Valve bodies are available in many configurations according to type of service. Regardless of function, the basic valve components are the body, seat, stem, and packing or gasket. Valve actuators control water flow through automatic valves in response to electronic or pneumatic control signals. Either two-way or three-way valves control the flow of heating or cooling water. Two-way valves reduce flow and are commonly found in variable-flow systems. Three-way valves maintain a single flow rate by diverting the water around the coil (or other equipment such as a chiller or boiler) when necessary. Threeway valves are typically used in constant-flow systems.
Valve components Pipe and other system components: Pipes connect all components and, with the possible exception of hydronic-heat-pump loops, should be insulated per local codes. Other system components that need to be operated and maintained properly are expansion tanks, strainers, and gauges for pressure and temperature.
Safety Issues
Working near rotating pump shafts and couplings can be dangerous. Control panels for electrical motors and electrical connections on pump motors present a shock hazard. Heating-water systems are dangerous if not fully insulated, so be careful not to touch uninsulated piping without first checking its temperature. Always observe lock-out and tag-out procedures during maintenance.
Produced by BetterBricks, the commercial initiative of the Northwest Energy Efficiency Alliance BOpEqSysWaterDistributionSystem.doc 5
Produced by BetterBricks, the commercial initiative of the Northwest Energy Efficiency Alliance BOpEqSysWaterDistributionSystem.doc 6
Balance or recommission the system: If temperature-control problems are found in multiple air handlers and cant be otherwise resolved, or if the hydronic system has been expanded or modified, a test-and-balance specialist or commissioning engineer should test and recommission the system. The table below provides a checklist for maintenance tasks. Maintenance Schedule for Water-Distribution Systems Description Check pump use/sequencing Visually inspect pumps, valves, and all mechanical joints Test water Check lubrication Check packing Comments Turn off/sequence unnecessary pumps. Visually inspect components to ensure that all equipment is operating, safety systems are in place, and no unusual leaks exist. Test for proper concentrations of dissolved solids and chemistry. Adjust chemicals as necessary. Ensure that all bearings are lubricated according to manufacturers recommendations. Check packing for wear and repack as necessary. Consider replacing packing with mechanical seals. Check for leakage that exceeds the manufacturers specifications. Replace if necessary. Align the pump/motor coupling to ensure efficient torque transfer to the pump. Check and secure all pump mountings. Inspect bearings and drive belts for wear. Adjust, repair, or replace as necessary. Clean strainers. Inspect these tanks to make sure that the acceptance capacity is adequate and that they function properly. Maintenance Frequency Daily Weekly
Monthly
Annually Annually
Inspect heating and Temperature differences may indicate air binding, clogged Annually cooling heat exchangers. strainers, or excessive scale. Determine the cause and correct. Cycle valves Observe the valves moving through their full range from closed to 100% open. Back off one-half turn from 100% open to prevent the valve from freezing in the full open position. Check the condition of the motor through temperature or vibration analysis. Annually
Motor condition
Annually
Produced by BetterBricks, the commercial initiative of the Northwest Energy Efficiency Alliance BOpEqSysWaterDistributionSystem.doc 7
References
ASHRAE Handbook, HVAC Systems and Equipment, 2000 US Department of Energy, Improving Pumping System Performance, Second Edition, May 2006 www1.eere.energy.gov/industry/bestpractices/pdfs/pump.pdf Harold R. Colen, PE, HVAC Systems Evaluation, 1990 FEMP O&M Best Practices Guide 2.0, July 2004 For additional information on pumps, visit these sites sponsored by the Hydraulic Institute: www.pumplearning.org, www.pumps.org, and www.pumpsystemsmatter.org.
Produced by BetterBricks, the commercial initiative of the Northwest Energy Efficiency Alliance BOpEqSysWaterDistributionSystem.doc 8