Direct Analysis Method Tips
Direct Analysis Method Tips
5. Combine first-order modal results (item 3) as speci-
fied in ASCE 7 Section 12.9.3. Apply B
2
multipliers
to the combined results (member forces and moments
caused by lateral loading). Then scale the combined
results as specified in ASCE 7 Section 12.9.4. Alge-
braic signs will typically be lost in modal combina-
tions; the member forces and moments due to seismic
effects should, therefore, be considered reversible
(i.e., use absolute values of forces and moments in the
modal combinations and then consider the resulting
overall forces and moments due to seismic effects to
be fully reversible).
6. Combine the member forces and moment due to seis-
mic effects (item 5) with the member forces and mo-
ments due to gravity load (item 2), with load factors as
specified in ASCE 7.
7. Apply B
1
multipliers to the moments in beam-
columns. The B
1
multiplier should be based on the full
LRFD-level axial force in the member, including axial
forces due to lateral loading, but need be applied only
to that part of the moment in the beam-column that
is caused by gravity loading. (Designers may use the
conservative approximation of applying B
1
to the full
moment to avoid the obvious bookkeeping difficulties
involved in this calculation.)
8. Perform strength checks in accordance with the AISC
Specification, using an effective length factor, K, of
unity for members subject to compression (unless a
lower value is justified by rational analysis).
This is an approximation. If the B
2
calculations for all stories are based
on story shears and drifts due to lateral load applied at the roof alone, the
resulting B
2
values should be reasonably accurate or conservative (high)
for all modes.
It should also be possible (as an alternative to the B
2
multiplier procedure
used herein) to adapt the modified geometric stiffness approach for use
with design by Modal Response Spectrum Analysis.
199_204_EJ3Q_2011_2010_07R.indd 203 9/13/11 2:38 PM
204 / ENGINEERING JOURNAL / THIRD QUARTER / 2011
9. As in the Equivalent Lateral Force procedure, confor-
mance to ASCE 7 seismic drift limits may be checked
using either the same analysis used for strength checks
(convenient, but potentially very conservative) or an
analysis using the full unreduced stiffness of the struc-
ture, with second-order effects (B
1
and B
2
multipliers)
determined at the lower loads specified by ASCE 7 for
calculation of the stability coefficient, .
SUMMARY AND CONCLUSIONS
Provisions related to seismic design and stability in ASCE/
SEI 7, Minimum Design Loads for Buildings and Other
Structures (ASCE, 2005), and features of the Direct Analy-
sis Method of design for stability in ANSI/AISC 360, Speci-
fication for Structural Steel Buildings (AISC, 2005a; AISC,
2010), have been explored and compared. While there are
inconsistencies between the two sets of provisions, they are
not fundamentally incompatible. Recommendations are of-
fered for the design of steel buildings for seismic effects and
stability in general conformance with both the AISC Speci-
fication and the ASCE 7 standard.
REFERENCES
AISC (2005a), Specification for Structural Steel Buildings,
ANSI/AISC 360, American Institute of Steel Construc-
tion, Chicago, IL.
AISC (2005b), Seismic Provisions for Structural Steel
Buildings, ANSI/AISC 341, American Institute of Steel
Construction, Chicago, IL.
AISC (2010), Specification for Structural Steel Buildings,
ANSI/AISC 360, American Institute of Steel Construc-
tion, Chicago, IL.
AISC-SSRC (2003), Background and Illustrative Examples
on Proposed Direct Analysis Method for Stability Design
of Moment Frames, Technical White Paper, AISC Tech-
nical Committee 10, AISC-SSRC Ad Hoc Committee on
Frame Stability, American Institute of Steel Construction,
Chicago, IL.
ASCE (2005), Minimum Design Loads for Buildings and
Other Structures, ASCE/SEI 7-05, American Society of
Civil Engineers, Washington, DC.
FEMA (2009), NEHRP Recommended Seismic Provisions
for New Buildings and Other Structures, FEMA P-750,
Federal Emergency Management Agency, Washington,
DC.
Nair, R.S. (2009a), Simple and Direct, Modern Steel Con-
struction, AISC, January.
Nair, R.S. (2009b), A Model Specification for Stability
Design by Direct Analysis, Engineering Journal, AISC,
Vol. 46, No. 1, pp. 2937.
199_204_EJ3Q_2011_2010_07R.indd 204 9/13/11 2:38 PM
,:..
"'-- L -
., -
j
~
bl
~
of
July 13, 2003
Background and Illustrati ve Examples on Proposed
Direct Analysis Method for Stability Design of Moment Frames
Report 011 behalf of AISC TC 10
Prepared by: Gregory Deierleill
PREFACE
Summarized herein is background infonnation and illustrative examples for new frame stability design
provisions proposed by AISC TC 10 for the 2005 AISC Standard. In the latest AlSC ballot (July 2003),
most of the new provisions appear in a new Appendix 6, entitled "Direct Analysis Method for Moment
Frames", which provides an alternative to the frame stability provisions in Section B6 of the Standard.
The frame stability provisions of Section B6 are essentially identical to those in the 1999 (3"' edition) of
the LRFD Specification for Structural Steel Buildings, except for the addition of a minimum moment
requirement. The background and fundamental features of the standard (Section B6) and alternative
(Appendix 6) provisions are described herein. Several illustrative example problems are presented to
demonstrate and contrast the two stability design approaches.
ACKNOW LEDGM ENTS
The developments summarized in this report are the result of contributions by many individuals over the
course of deliberations by AISC TC 10 and the AlSCSSRC Ad Hoc Comrnittee on frame stabi lity. The
AlSCSSRC Ad Hoc Committee cochairs (J. Yura and G. Deierlein) and members (W. Baker, J. Haliar,
T. Galambos, R. Heinge, L. Lutz, K. Mueller, S. air, C. Rex, R. Tremblay, D. White and R. Zieman)
developed the first draft of the provisions. Other noteworthy contributions include those of D. White, A.
Maleck, and R. Ziemian for their analysis of numerous benchmark validation studies and L. Lutz for
suggestions of illustrative example problems. Portions of this report are excerpts from an earlier paper
presented at the 2002 SSRC Annual Meeting, which introduced a preliminary (now superseded) draft of
the proposed provisions (Deierlein, Hajjar, Yura, White, Baker, "Proposed new provi sions for frame
stability using secoodorder analysis", SSRC 2002 Annual Meeting, Seattle, WA).
INTRODUCTION
The proposed new provisions for frame stability represent the culmination of work by task committees in
AlSC and SSRC over the past four years, which incorporate concepts of secondorder analysis and design
whose origins date back over twenty years. Concerted work on this began late in 1999, with the fonnation
of a joint AISCSSRC Adhoc Committee whose charge was to develop improved specification provisions
for member and frame stability. The committee's goals were to develop design methods for stability that
made more effective use of modem computer analysis methods, while reducing the over reliance on
effective buckling length procedures in the current AlSC Specifications. This adhoc committee was
combined with AI SC TC lOin 200 I , and the combined group developed provisions, which are proposed
for adoption in the 2005 AISC Standard. The new provisions were first balloted in March 2003 and have
since been revised to address comments raised by the AISC Specification Committee. This report reflects
the latest version of the proposed provisions for frame stability.
The July 2003 AlSC ballot outlines proposed provisions for the 2005 Standard, which will pernllt two
alternative methods to design for stability effects in moment frames . For discussion purposes, the two
approaches will be referred to as the "Effective Lellgth " and "Direct Allalysis" methods. Both approaches
"
,;0
,z,
~
."
""
require evaluation of second-order effects and member force interaction equations. The methods differ in
their specific requirements for calculating second-order effects and the axial strength tcrm, p., in the
member interaction equation. Requirements for the Effective Length method are contained in the proposed
Section B6 of the 2005 Standard. This method is essentially the same method as the approach used in
Chapter C of the 1999 AISC-LRFD Specification. Requirements for the Direct Analysis method are
specified in a newly proposed Appendix 6 to the 2005 Standard.
This report begins with a brief review of key behavioral effects and second-order analysis considerations,
which are relevant to stability design. Next, the two proposed approaches to framc stabi lit y are
summarized and contrasted through a design example of simplc cantilever column. This IS followed by
highlights of validation studies to evaluate the accuracy of the two proposed methods. The report
concludes with three design examples to illustrate practical application of the methods.
BEHAVIORAL EFFECTS
There are potentially many parameters and behavioral effects that influence stability of steel-framed
structures. The extent to which these factors are modeled in analysis will affect the criteria that one
applies in design of the (rame, its members and connecllons. Without repeating more complete
presentations given elsewhere (Birnstiel and Imand, 1980; McGuire, 1992; White and Chen. 1993; ASCE,
1997; Deierlein & White 1998), it is helpful to review three basic aspects of behavior: geometric
nonlinearities, inelastic spread-of-plasticity, and member limit states. These ultimately govern frame
deformations under applied loads and the resulting internal load effects.
Geometric Nonlinearities and Imperfections: Modern stability design provIsions are based on the
premise that the member forces are calculated by second-order elastic analyses, where equilibrium is
satisfied on the defonned structure. When stability effects are significant, consideration must be given to
initial geometric imperfections in the structure due to fabrication and erection tolerances. For the purpose
of calibrating the stability requirements described later, initial geometric imperfection are conservatively
assumed as equal to the maximum fabrication and erection tolerances pennitted by the AI Code oj
Stalldard Practice (2000). For columns and frames, this implies a member out-of-straightness equal to
UIOOO, where L is the member length between brace or framing points, and a frame out-of-plumb equal to
H/500, where H is the story height. The out-of-plumb is also limited by the absolute bounds as speCified
in the Code oj St{/l/{/ard Practice.
Inelastic Spread of Plasticity: The proposed analysis/design approaches are calibrated against inelastic
distributed-plasticity analyses that account for spread of plasticity through the member cross-section and
along the member length. Thermal residual stresses in W-shape members are assumed to have maximum
values of 0.3Fy and are distributed according to the so-called Lehigh pattern - linearly varying across the
flanges and unifornl tension in the web (Deierlein & White 1998).
Member Limit States: Member strength may be controlled by one or more of the following limit states:
cross section yielding, local bUCkling, flexural buckling, and torsional -flexural buckling. For structural
analyses envisioned for routine frame design, it is assumed that the analysis does not model local
flange/web buckling or torsional-flexural buckling. Therefore, these limits must be considered in separate
member design checks. For inelastic analyses, the member yield limit is incorporated directly in the
analysis; and for elastic analyses, this limit can be checked by an interaction equation that approximates
the P-M yield surface. Whether or not the analysis captures in-plane flexural buckling depends on the
extent to which the maximum moments are affected by distributed plasticity and member str3lghtness.
Concerns as to whether the analysis captures this effect suggest the need to apply a member check for lO-
plane flexural buckling, even when an accurate second-order analysis is used. As will be addressed later,
Page2oJI7
a key consideration for the in-plane flexural buckling check relates to the assumed buckling length used in
calculating the design compression strength, P".
SECOND-ORDER ELASTIC ANALYSIS
The AISC stability design provisions are developed for use with second-order elastic analysis. In practice,
there are alternative approaches one can employ for conducting second-order analyses, some of which are
more rigorous than others. For the purpose of this discussion, second-order clastic analyses will be
categorized as "rigorous" or "approximate". The difference between these two depends on the extent to
which P-O effects are modeled and whether the problem is "linearized" to expedite the solution.
Rigorous second-order analyses are those that accurately model all significant second-order effects.
Rigorous analyses include solution of the governing differential equation, either through stability
functions or computer frame analysis programs that model these effects (McGuire 1992; Deierlein &
White 1998). Many (but not all) modern commercial computer programs are capable of rigorous analyses,
though users should verify this. Methods that modify first-order analysis results through second-order
amplifiers (e.g. , B, and B: factors) are in some cases accurate enough to constitute a rigorous analysis, but
this depends on the magnitude of second-order effects and other characteristics of the problem.
Approximate second-order analyses are any methods that do not meet the requirements of rigorous
analyses. A common type of approximate analyses are those which only capture P-tJ due to member end
translations (e.g., interstory drift) but fail to capture P- oeffects due to curvature of the member relative to
its chord. Where P-O effects are significant, errors arise in approximate methods that do not accurately
account for the effect of P-o moments on amplification of both local member moments and the calculated
global (tJ)displacements. These errors can arise both with second-order computer analysis programs and
with the B, and B, amplifiers. White and Maleck (2002) propose the following criteria to rule out cases
where P-O effects can be safely ignored:
P, < 0. 15 P,L = 0.15(,(IIL') (I)
where P, is the required column strength and P<L is the elastic buckling load in the plane of bending. The
alternative to this equation is to verify the accuracy of the second-order analysis by comparisons to known
solutions for conditions similar to those in the structure. Examples of the errors one may encounter are
discussed by LeMessurier (1977) and Deierlein & White (1998).
BEAM-COLUM INTERACTION EQUATIONS
(SECTION HI OF THE 200S STANDARD)
80th the Effective Length (Section 86) and Direct Analysis (Appendix 6) stability procedures utilize the
beam-column interaction equations of Chapter H, albeit with differences in how the required strengths (P,
and M,) and the nominal compressive strength (p") are calculated. For reference in the later discussion, the
interaction equations for members under combined axial compression and bending are briefly reviewed.
For bi-symmetric beam-columns under combined axial compression and uniaxial bending, the 2005
Standard introduces a new interaction equation for checking out-of-plane (lateral-torsional) II1stability,
which is separate from the check for in-plane (flexural buckling) instability. These separate equations are
introduced since they provide more accurate predictions of in-plane and out-of-plane limit states, which
tests and theory show are independent phenomena. The separate equations reduce the conservatism in the
Page J oj17
;:1
.::>
'::J
,-
.:0
-..J
current (I999 A1SC-LRFD) provisions, which combine the two limit state checks into one equation, by
combining the most severe combinations of in-plane or out-of-plane limits for P ./;p" and M,/,pM".
Shown here for illustration are the interaction equations in LRFD fornlat for bi-symmetric beam-columns
subjected to axial compression and uniaxial bending. For members subjected to compression and minor
axis bending. only the in-plane check applies; whereas for columns under compression and major axis
bending, both checks apply.
The limit state of in-plane flexural buckling is checked using the following equations, which have the
same format as those in the 1999 A1SC-LRFD Specification:
p
for -"- ;, 0.2
,p, p"
(2a)
(2b)
where p" and M. are the required strengths, calculated from second-order analysis under the design loads;
and p" and M" are Ole nominal compression and bending strengths, calculated in the plane of the frame.
For the Effective Length method, p" is detemlined using the effective buckling length KL in the plane of
bending, whereas in the proposed Direct Analysis method, p" is calculated using K=/ (KL=L) in the plane
of bending. For compact member sections, M" for the in-plane check is equal to M".
The out-of-plane lateral-torsional limit state is checked by the following equation:
(3)
Here the required strengths p. and M" are the same as for Eq. 2a and 2b, and p" and M" are calculated
using the unbraced length in the out-of-plane direction. These out-of-plane nominal strengths would
typically be evaluated on the same basis for the Effective Length and Direct Analysis methods.
EFFECTIVE LE GTH METHOD
(SECTION 86 OF 2005 STANDARD)
The Effective Length (or critical load) approach for assessing member axial compressive strength has
been used in various forms in the A1SC Specification since 1961. The provisions proposed for Section 86
of the 2005 Standard are essentially the same as those from the 3'd edition (1999) of the AISC-LRFD
Specification, with the exception of a new minimum moment requirement. The approach is based on
calculating effective column buckling lengths, KL, which have their basis in elastic (or inelastic) stability
theory. The effective buckling length KL, or aiternatively the equivalent elastic column buckling load, P,
= 1iEII(KL/, is used to calculate an axial compressive strength, p", through an empirical column curve
that accounts for member geometric imperfections, yielding, and residual stresses. This column strength
is then combined with the design moment strength, ,pM", and second-order member forces, p. and M., in
the beam-column interaction equations.
Differences between the Effective Length and Direct Analysis approaches lie mainly in the in-plane
check. Figure la shows a plot of the in-plane interaction equation for the Effective Length approach,
Page 4 of 17
where the anchor point on the vertical axis, p.
KL
, is determined using an effective buckling length factor.
Also shown in this plot is the same interaction equation with the first term is based on the squash load. P,.
The load-deformation response of a typical member, obtained from second-order spread-of-plasticity
analysis and labeled "actual response," indicates the maximum axial force, p., that the member can
sustain prior to the onset of instability. The load-deflection response of a second-order elastic analysIs, as
would be done in design practice, is also shown. The "actual response" curve reveals larger moments than
the second-order elastic curve due to the combined effects of partial yielding and geometric imperfections,
which are not included in the second-order elastic analysis. The intersection of the second-order elastic
curve with the p.
KL
interaction curve represents the design strength. The plots in Fig. 2a show how the
effective length procedure has been calibrated to give a resultant axial strength, P" consistent with the
actual response. For slender columns, accurate assessment of the effective length (and p.
KL
) is critical to
achieving an accurate solution.
While the effective length approach is calibrated to accurately predict the resultant member strength, one
consequence of the procedure is that it under-estimates the actual internal moments under the factored
loads (see Fig. I a). This is inconsequential for the beam-column (since the p.
KL
reduces the effective
strength in the correct proportion), but the reduced moment can affect design of the beams and
connections, which provide rotational restraint to the column. This is of greatest concern when the
calculated moments are small and axial loads are large, where P-Ll moments induced by column out-of-
plumb can be significant. As a safeguard for these cases, the Effective Length procedure in Section B6
includes a new minimum required moment strength for beams and connections, which restrain the column
ends. This requirement is specified through the following equation (Eq. B6-3 in the July 2003 Ballot),
'fM. > O.OI'f.P.L (4)
where EMu is the minimum required strength, P
u
is the required strength (axial compression force) in the
columns being restrained, and L is the column length.
P
P,
p ..
Pu
Pi
P
-'"R
jWl
P,
0 .. ': jWl
elastic 2
nd
..order
p.
elastic 2
nd
-order (D.A.)
actual response
actual response
(a)
Mp M
(b)
Mp M
Fig. I - Comparison of beam-column interaction checks for (a) the
effective length approach and (b) direct analysis approach
DIRECT ANALYSIS METHOD
(APPENDIX 6 TO 2005 STANDARD)
The Direct Analysis approach has been developed with the goal to more accurately model frame stability
effects in analysis, and thereby. eliminate the need for calculating effective buckling length factors for
Page 5 of 17
columns. As summarized below, the new provIsions in Appendix 6 of the 2005 Standard Involve
reducing the nominal elastic stiffness and applying a notional load to the frame. Some aspects of the
proposed provisions are similar to so-called "notional load' methods found in steel standards in olher
countries, e.g., Canadian and Australian Standards and the Eurocode, however, many aspects of the
proposed provisions are unique 10 the AISC Standard and address known shoncomings of conventional
notional load approaches in other standards.
Like the Effective Length procedure, the Direct Analysis melhod begins with a basic requirement to
calculale internal member forces using a second-order elaslic analysis. As will be shown later in the
examples, the Direct Analysis method places a greater reliance on the second-order analysis (primarily in
the accurate calculation of second-order moments, M.), and for this reason, the method stipulales
requirements to ensure accuracy of the second order analysis. Analysis rigor is most important where
second-order amplifications are large, one measure of which is given by the ratio of member aXial
compression forces to their elastic buckling strengths (see Eq. I). Two additional requirements for Direct
Analysis are as follows:
A notional load of N, = 0.002 Y, is to be applied in combInalion with other factored loads. where
N, is the notional lateral load applied at floor i and Y, IS the gravity load (from strength load
combinations) acting at floor i . The notional load is applied to represent the destabilizing effect of
a geometric imperfections and olher effects (yielding. non-ideal boundary and loading condItIons,
elc.). The notional load magnitude of 0.002 corresponds to a frame out-of-plumb equal to HlSOO
(where H is the story height).
The nominal elastic flexural stiffness assumed in the second-order elastic analysis is equal 10
0.8tEI , where t is calculated as follows:
For members where p. S O.SPy: r = I
For members where p. > O.SP, : r = 4[P/ P, (J -P/ P,)}
Alternatively, where p. > 0.5P, for any members in the frame. r = I provided that an additional
notional load of N, = 0.001 Y, is applied to the frame.
There are two reasons for imposing the reduced stiffness for analysi s. For frames with slender members,
where the limit state is governed by elastic stability, the 0.8 factor on stiffness results in a system deSign
strength equal to 0.8 times the elastic stability limit. This is roughly equivalent to the margin of safety
implied by design of slender columns by the effective length procedure where the design strength ;p.
0.9(0.877)P, = 0.79P. where P, is the elastic critical load, 0.9 is the specified resistance factor, and 0.877
is a reduction factor in the column curve equation. For frames with inlermediate or stocky columns, the
0.8t factor reduces the stiffness to account for inelastic softening prior to the members reaching their
design strength. The t is similar to the inelastic stiffness reduction factor implied in the column curve 10
account for loss of stiffness under high compression loads (P. > 0.5P,). and the 0.8 factor accounts for
additional softening under combined axial compression and bending. It is a fonuitous coincidence that the
reductions coefficients for the slender and stocky columns are close enough, such that the single reductIOn
faclor ofO.8t works over the full range of slenderness.
The reduced stiffness and notional load requirements only penain 10 analysis of the strength lImit stale.
and they do not apply to analysis of other serviceability conditions for excessive deflections, vibration,
etc. For ease of application in design practice, the reduction on EI can be applied by modifying E In Ihe
analysis; however, in doing so, one should consider whether the possible side-effects of reducing EA.
Moreover, for computer programs that do semi-automated design, one should be sure that the reduced E IS
Page 6 of 17
'.
,;:p
,;:p
only applied for the second-order analysis, The elastic modulus should not be reduced in design
equations, which involve E to evaluate the design strength (e.g., M, for laterally unbraced beams).
As shown in Fig. Ib, the net effect of modifying the analysis in the manner just described is to amplify the
second-order moments to be closer to the actual internal moments in the member. It is for this reason that
the beam-column interaction for in-plane flexural buckling is checked using an ax.ial strength P,
calculated from the column curve using the actual unbraced member length L, i.e., with K I . In fact ,
arguments have been made to use p). in the interaction equation. but this would require recalibration
of the analysis adjustments, including additional adjustments to account for member out-of-straightness
(sweep). After considering alternative strategies, TC 10 decided to use the proposed method (with p.
based on L) as a pragmatic and conservative approach for practical design.
CANTILEVER EXAMPLE
To illustrate an application of the two stability design methods, consider the design of the cantilever beam-
column shown in Fig. 2. The cantilever is subjected to the vertical and proportional hori zontal load
shown, such that the design is controlled by the combined p. and M. at the base of the column.
Maximum strengths are calculated for three different column lengths, with slenderness ratios of Ur 20,
40 and 60 (equivalent to KUr 40, 80, and (20). Bending is about the major axis, and the column has
full out-of-plane (lateral) restraint. The design checks are based on the in-plane interaction check (Eq. 2a-
b). ate that the checks were made using a resistance factor of
in compression (consistent with the 1999 AJSC-LRFD Specification),
so the results would be slightly different if made with the revised value
of as proposed for Chapter E of the 2005 Standard.
Shown Fig. 3a-c are plots of the axial load versus moment at the column
base for the three column lengths, deternlined according to the Direct
Analysis (DA) and Effective Length (EL) methods. Notice that the
internal moments Mil increase much faster with P
II
for the Direct
Analysis method, due to the reduced stiffness (0.8tEI) and added
notional loads. Most of the stiffness adjustment is due to the 0.8 factor,
since t only affects the column with Ur 20 (Fig. 4a,) where the
maximum load p. > 0.5P, 440 kips. Overlaid on these force-point
traces are the beam-column strength interaction diagrams, where the P
n
anchor point for the Effective Length method P,,KL is based on
oJ
0
It)
.:
Cl
r:i
<0
)(
0
.....
and for the Direct Analysis method P,L is based on L. Fig. 2 - Canti lever Example
The calculated strengths, as determined by the two methods, are sununarized in Table I in tenns of the
max.imum vertical load p. (shown in bold). Net strengths for the two methods are within 10%, even
though the interim results are quite different. For example, as shown in Figs. 3a-c and summarized in
Table 1, the maximum internal moments at the strength limit point are much larger for the Direct Analysis
method; whereas the P ,/P" ratios, which indicated the relative significance of the axial load and moment
terms in the governing interaction equation, are consistently larger for the Effective Length method.
Moreover, the P ,/>P, ratios for the Effective Length procedure do not change much with increasingly
slenderness, because this procedure relies to a much greater degree on capturing stability effects in the P,
term. Conversely, in the Direct Analysis procedure the P '/P, contribution decreases and the moment
term dominates the solution for cases with increasing slenderness.
Page 7 of 17
800
700
600
_ 500
a.
~ 400
"
D.
300
200
100
0
0
700
600
500
E: 400
~
"
300
D.
200
100
0
0
700
600
500 J
E: 400
~
"
300
D.
200
100
0
0
1000
1000
(e)
1000
DALIr=20
.....-ELLIr20
Interaction PnKL
~ Interaction PnL
2000
Mu (k-in)
3000
DALir='O
EL Lir='O
Interaction PnKl
_Interaction PnL
2000
Mu (k-in)
3000
DALir = 60
-M- EL Lir = 60
Interaction PnKL
Interaction PnL
2000
!tIu (k-in)
300D
Fig. 3 - Comparison of P-M interaction curves for cantilever column example
(a) short Ur = 20, (b) medium Ur = 40, (c) long Ur = 60
Page 8 of 17
. .0
'.J
a e
- T bl I R esu ts or anti ever ~ C ' 1 CI o umn E x a m ~ l e
[frecti n Len th Method Direct Analys is "Iethod
Ur P.(kips) M.(k-ill) MI M, P/ (I',
P.(kips) M,lk-iII) MI M, P / (1',
20 562 580 1.17 0.85 578 777 1.27 0.80
40 345 988 1.63 0.74 371 1680 2.16 0.56
60 193 1007 1.98 0.74 213 2376 3.53 0.37
This comparison highlighlS Ihe pros and cons of each method. Compared to Direct Analysis procedure,
the Effective Length method has the advantage of being less sensitive to the accuracy of the second-order
analysis. On the other hand, the method requires calculation of effective column buckling lengths (KL),
which can be difficult for complicated structures. Direct Analysis eliminates the need to calculate
effective buckling lengths and provides more accurate measures of the true second-order moments. This
latter point is important for the design of members and connections, which restrain the beam-column. For
example, in the cantilever column example, the base moments from the Direct Analysis procedure take
into account initial out-or-plumb and inelastic second-order effects, which are not captured in the
Effective Length procedure. Referring to the second-order moments reported in Table I, the difference in
moments between the two methods can be quite large. Subject to the assumed geometric imperfections
(out-of-plumb) and residual stresses, validation studies have shown that the momenlS calculated by the
Direct Analysis procedure are generally conservative and closer to the true values. Observations of the
type described here about the underestimation of design moments the Effective Length method, led to the
new minimum moment requirement (Eq. 4) for the Effective Length method. One should recognize,
however, that this minimum does not address cases such as shown in this cantilever example, where the
calculated moments in the Effective Length procedure are above the minimum of O.O/PL, but still less
than the actual values, which are calculated more accurately by the Direct Analysis procedure.
VALIDATI ON STUDI ES
Over the course of developing the proposed stability provisions, hundreds of validation analyses have
been investigated by members of the SSRC-AISC Ad Hoc Committee. Some of the early investigations
(e.g., Maleck 200 I, Maleck and White 2003) he lped guide development of the provisions, and two recent
papers by Maleck and White (2002) and Martinez-Garcia (2002) provide selected case studies to validate
the final version of the proposed design methods. These two studies investigated twenty-five frame
configurations under multiple load cases, representing several hundred analyses with about 150
comparison points between the two design approaches and refined nonlinear analyses. These studies focus
on the limit state of combined axial load and bending in the beam-colunms and do not specifically address
design checks in restraining beams and connections.
Examples of the frame configurations considered in the benchmark srudies by Maleck and White (2002)
are shown in Fig. 4. These two-colunm portal frames and individual colunm structures provide rigorous
test cases of non-redundant systems of varying slenderness, levels of axial compression, and leaning
column effects. Other multi-story and multi-bay frames investigated by Martinez-Garcia (2002) embody
attributes of realistic structures that pose particular challenges in evaluating stability, three of which are
presented in the next session of JIIustrative Examples. The problems investigated for the benchmark
studies are ones where second-order effects are large and where errors between the stabi lity design
methods and more exact methods are accentuated. In this sense, these benchmark studies represent
extreme cases, which tend to exaggerate the differences one would typically encounter in design practice.
Page 9 of 17
;0
.... .)
Symmetric Frame
Leaned-Column
Frame
P
w_+
6
0
B.
E
b
Ib ,Lb
Eel Ie ,Le
,
,
,
Lb Lc
Pinned-Pinned
Beam-Column
it
~
,
B.
\
2W
-
;t
2P
+
f
2L,
(EI /L), = 0 and 3
(EI/L)b
(Llr), = 40
601L,= 0.002
BoiL, = 0 and 0.001
f" = 0 and 0.3F,
(EIIL),
---= 0 and 1
(EI/L)b
(Llr), = 40
601L, = 0.002
BoiL, = 0 and 0.001
f" = 0 and 0.3F,
(2L1r), = 80
BoI2L, = 0 and 0.001
f" = 0 and 0.3F,
straight line and sine curve
Fig. 4 - Test structures used for validation study (Maleck 2001)
Detailed analysis solutions based on second-order spread-of-plasticity analyses are used as benchmarks
against which the proposed design methods were validated. These benchmark solutions incorporate the
effects of gradual yielding, initial geometric imperfections, and residual stresses, as outlined previously in
the section of this report on Behavioral Effects. Thus, they represent the state-of-art in simulating inelastic
stability of beam-columns and frames. Material properties (E and Fy) in the spread-of-plasticity analyses
were reduced using a resistance factor of 0.9, such that the maximum strength calculated in these anal yses
corresponds to the structural "design strength" - as opposed to a "nominal strength".
Overall, the two studies (Maleck and White 2002 and Martinez-Garcia 2002) confirm that both the
Effective Length and Direct Analysis methods are sufficiently accurate (relative to current methods) for
design and that the errors (relative to the spread-of-plasticity solutions) are comparable for the two
methods. Maleck and White report that on average the two approaches give strengths within 2% to 7% of
those obtained by refined analyses. The maximum discrepancies they observed for the Direct Analysi s
approach, relative to the refined analyses, range from - 6% (unconservative) to +13% (conservative) for
members subjected to strong-axis bending and - 13% to + 15% for members subjected to weak-axi s
bending. For the Effective Length approach, the maximum discrepancies range from - 8% to + 18% for
strong-axis bending and - 17% to + 17% for weak-axis bending. These errors are based on design checks
made with rigorous second-order elastic analyses. Maleck and White caution that the Direct Analysis
design checks based on approximate P-6 analyses can be up to -23% (unconservative) for members
subjected to weak axis bending. This is an example of why the Direct Analysis provisions specifY the
need for a rigrous analysis when second-order effects are large. Maleck and White further note that for
frames where Pu < 0. 15 (71' ElfL' ), the maximum unconservative errors associated with approximate P-
Page 100JI7
'.0
J>.
analyses for the Direct Analysis approach are limited to the maximum errors present in existing Effective
Length procedures.
ILLUSTRATIVE EXAMPLES
Three example problems are presented next to illustrate practical application of the proposed stability
design methods. The first two examples are [rames with heavy gravity loads and large second-order
amplification factors. The third example is a stiffer six-story frame, which is more representative of
multi-story building frames. Each example includes a comparison of results from the Effective Length
and Direct Analysis approaches and more rigorous spread-of-plasticity solutions. The spread-of-plasticity
solutions have been independentl y reported by Maleck (2001) and Martinez-Garcia (2002), and the design
solutions have been prepared by multiple members of A1SC TC 10 and the A1SC-SSRC Ad Hoc
Committee. All design checks are based on the LRFD approach and load combinations. Resistance
factors used in the design checks are .=0.9 for bending and ,=0.85 for compression, the latter of whi ch
is slightly smaller than the proposed change to ,=0.9 in Chapter E of the 2005 Standard.
Low-Rise Industrial Example
The first example, see Figure 5, is a framing bent from a large floor plan single story industrial building,
such as an automobile plant. With heavy material handling equipment hung from the roof and a small
wind exposure, such structures are dominated by gravity loads wilh large second-order effects
(Springfield, 199 1). Loading shown in Figure 5 represents an eleven bay configuration with ten leaning
columns (only two of which are shown) and two lateral-load resi sting columns. The concentrated load P
has a tributary roof area of 35 ft x 35 ft , and the wind load W = 5.12 kips.
The member sizes sati sfy a drift limit of Hl400 for the service load wind of 0.7W, and the design strength
of the frame exceeds the minimum requirement of the LRFD strength load combinations. Based on
refined spread-of-plasticiry analyses, the frame has a desi gn strength ratio 17% larger than the required
strength for gravity (A.UQ. /.6L=1.I 7, where ~ = 0 . 9 ) and 20% larger than required under gravity plus wind
(A/m.o.5L /.6,.,=1. 20). Using the equation B5-5 (from the July 2002 ballot of Chapter B for the 2005
Standard), the second-order amplification factor under design gravity loads is B,= 2.41. Under the design
gravity plus wind loading combination, B,= 1.74.
4P 4P
Frame spadng = 35'0"
W-)
W27 x 84 W27 x 84
Fy = 50 ksi
'"
9
..,.
x E = 29,000 ksi
00
0 ~
~
~
J
\.
,
l
3 @ 35'-0" = 105'-0"
DL 80 psI Load Combinations:
'1
LL 40 psI 1.2DL + 1.6LL
Wind 16.25 psI 1.2DL + 0.5LL + 1.6WL
Figure 5 - Single-Story Industrial Building
Page II ofl7
..'
' . .,
---------------------
Axial column forces and maximum moments under the factored load combinations are summarized in
Table 2. The Effective Length results are from a second-order analysis of a model based on the ideal
geometry of the frame under the factored load combinations (no geometric imperfections or notional loads
are introduced). The Direct Analysis results incorporate initial geometric imperfections through the
notional load of 0.2% times the factored gravity loads (1.20 + 1.6L for the first combination and 1.20 +
0.5L for the second combination); and stiffness degradation is incorporated by reducing the flexural
stiffness of all framing members by to 0.8EI. Since the axial load ratio PIP, <0.5, no additional t-factor
stiffness adjustments are required. The "spread of plasticity" results are from a second-order inelastic
analysis, which models gradual yielding through the member cross sections and along their length due to
the combined effects of thermal residual stresses and the applied loads.
Table 2: Member Effects Under Factored Load Combinations
L R' I d . I E I or ow- Ise n ustna -xample
Analysis/Design l\ l elhod
Load Case
Check
SI)read of Effecti ve Direct
Plasticitv Allah'sis
p,. (kip) 215 216 218
1.2D+1.6L
M"" (k-in) 930 407 1220
Mbm (k-in) 8660 8410 8690
P"" (kip) 154 158 160
1.2D+0.5L+1.6W
M" (k-in) 1310 1040 1550
Mbm (k-in) 6490 6360 6630
Referring to Table 2, the Effective Length and Direct Analysis methods both predict the maximum beam
moments and axial column forces within about 4% of those from the spread-of-plasticity analysis. On the
other hand, there are significant differences in the column moments, particularly for the gravity load case
(1.2D + 1.6L). The Direct Analysis method predicts the column moments on average about 25% higher
than the spread-of-plasticity solution, and the Effective Length method predicts column moments on
average about 40% smaller than the spread-of-plasticity solution. These differences are also reflected in
the calculated displacements. This small moments calculated according to the Effective Length method
illustrate the need for the newly proposed minimum connection moment requirement (Eq. 4, 'f.M. >
0.0I''i.P"L). Without this minimum requirement, the comlection would be under-designed for the second-
order moment induced by the combined effects of gravity load and column out-of-plumb.
Using the member forces from Table 2, the columns are checked using the interaction formula for in-plane
or out-of-plane (torsional flexural) failure, and the resulting interaction ratios are summarized in Table 3.
For the Effective Length method, the in-plane checks are based on a column strength of P = 236 kips,
obtained with an effective length factor of K = 2.3 using Eq. C-C2-6 of A1SC (1999). In-plane checks for
the modified stiffness and notional load methods are based on p ...
t
= 511 kips, and out-of-plane checks
Table 3: Interaction Values for Low-Rise Industrial Example
Analysis/ Design 1\ l ethod
Load Case
Member
Check Effeclive Direcl
Length Analvsis
1.2D+1.6L
In-plane 1.05 0.83
Out-of-plane 0.62 0.81
1.2D+0.5L+I.3W
In-plane 1.0 I 0.82
Out-of-pJanc 0.58 0.77
Page 120[17
are all based on ;p ..
L
361 kips. The column design moment is ;Mp 2718 k-in. In-plane interaction is
checked using Eqs. 2a & 2b, and the out-of-plane check is made using Eq. 3.
Referring to Table 3, both the Effective Length and Direct Analysis checks are governed by the in-plane
strength (shown shaded). The Effective Length method is more conservative, as evidenced by a larger
interaction value as compared to the direct analysis method. The in-plane checks can be compared to
inelastic limit load ratios of ;),."0 and ;),."D.0.J/. >1.61V obtained from the spread-of-
plasticity analyses. The inverse of these limits (0.85 and 0.84 for gravity and gravity+wind, respectively)
help to gauge the conservatism in the methods, where larger interaction checks would be conservative and
smaller checks unconservative. Compared to these values (0.85 and 0.84) the in-plane checks for the
Effective Length method about 15% conservative, whereas the Direct Analysis results appear slightly
unconservative (e.g., 0.83 < 0.85 and 0.82 < 0.84). However, since the member forces vary nonlinearly
with load (due to second order effects), this simple comparison is approximate and a more accurate
comparison would be obtained by scaling up the loads in the Direct Analysis to the point that the in-plane
interaction check is equal to 1.0. Scaling the loads in this way results in a limit load for
the Direct Analysis which is about 6% smaller (conservative) as compared to the in-plane limit from the
spread-of-plasticity solution. Thus, this case demonstrates that the Direct Analysis is conservative (safe)
and provides the potential for a more efficient design as compared to the Effective Length method.
Exa mple Connection Design for Effective Length Method:
For the gravity load case, the minimum beam-column
connection strength provision of the Effective Length
procedure (Eq. 4) provides for a minimum required connection
strength of 1:M, > 2330 k-in. This is calculated using the
vertical load in one lateral load resisting column and one of the
leaning columns (a total of EP, 1078 kips). Comparing thi s
to the more exact required column moment from the spread-of-
plasticity solution (M, 930 k-in) indicates that the minimum
required by the Effective Length method is quite conservative
in this case. The required strength using the Direct Analysis
method would be 1220 k-in. To help gauge the impact of these
provisions, a connection designed for the Effective Length
method moment of 2330 k-in is shown in Fig. 6. This
connection would require eight - I inch diameter bolts, which
is not excessive for the connected members.
Grain Storage Bin
_.
Figure 6: Example Connection Design
(8-1" dia. bolts)
The second example is the support rack for a grain storage bin with the dimensions and loading shown in
Figure 7. This is a case where calculation of the column effective lengths is not obvious, and where the
Direct Analysis method offers a clear benefit. Colunms are assumed to be braced out-of-plane and the
cross-beams and bracing are pin-connected to the colunms. For the diagonal bracing, one-inch diameter
round bars are assumed. Using an elastic critical load analysis, the second-order amplification factors are
B, 2.75 and B, 2.20 for the gravity and wind load combinations, respectively. The spread-of-plasticity
analyses predict inelastic limit load ratios of 1.13 and ;),. I1G- 16W 1.07.
As in the previous example, results for the Effective Length method are calculated for the ideal geometry
and stiffness; whereas the Direct Analysis method is based on a reduced stiffness (0.8EI) and with
notional loads applied in combination with the design loads. Like the previous example, no additional t
adjustment of stiffness properties is required for Direct Analysis since the axial load ratio PIP, < 0.5.
Page 13 oj 17
'.0
--J
w
M
X
WI2x26
"' iI"----""
H
12'-0"
H
Loading:
IV - \.75 kops (10 psQ
G - 360 kips
Load Combinations:
1;>
1.4G
1.2G + 1.6W
Materials:
1;> Fy - SOksi
'"
E - 29.000 ksi
Figure 7 - Grain Bin Support Frame
Maximum column forces and moments (required strengths) are summarized in Table 4 and the interaction
checks are summarized in Table 5. As in the previous examples, there is not much difference in axial
loads between the methods, but there are large variations in the calculated moments. This is particularly
prevalent for the gravity load case, where the calculated column moments for the Effective Length method
are essentially zero, and the moments for the Direct Analysis method are about 36% larger than those in
the spread-of-plasticity analysis. Under the lateral load case, the differences are less, with moments for
the Effective Length method about 24% less (unconservative) than the spread-of-plasticity results and
those for Direct Analysis about 38% larger (conservative).
a e em er eets T bl 4 M b G or ram S torage III xample
Member
AnalYsis/ Desig n Met hod
Load Case
Check
Spread of Effecti ve Direct
Pl astici ty Analysis
P,.,,,,,Jkip) 233 247 249
lAG
P,.""dk-in) 255 252 257
M (k-in) 161 2 220
P , (kip) 203 217 220
1.2G+\.6W
P. "
k-in) 224 225 230
M, (k-in) 380 288 526
T bl a e 5: Interactton Va ues or ram
G . S
torage B' E 10
Member
Analysis/Design Method
Load Case
Check
Effecti ve Direcl
Length Anal\'sis
\.4GL
Top Column 1.07 0.84
Bot. Column 1.04 0.85
1.2GL+1.6W
Top Column 1.12 0.96
Bol. Column 1.11 0.99
Page 14 of 17
.:,
.::>
.:::>
.....
. ..:>
The interaction checks, shown in Table 5, are based on the following in-plane column strengths: critical
load method ;p.KL .. op = 232 kips (K = 2.4), .... = 243 kips (K = 2.9); and the direct analysis method,
;p.
L
. "" = 355 kips, = 366 kips. The K factors for the Effective Length procedure are based on an
elastic critical load analysis of the structure under gravity loads. The results in Table 5 show that strength
interaction checks based on the Effective Length method are roughly 20% more conservative than the
Direct Analysis method. Using the spread-of-plasticity analysis as a benchmark of the actual behavior,
interaction values larger than 0.89 (for lAG) and 0.93 (for 1.2G+I.6W) are conservative. The Effective
Length interaction values (1.07 and 1.12) exceed these and are about 20% conservative. The Direct
Analysis method is sli ghtly conservative for the gravity plus wind case (0.99 > 0.89) and appears slightly
unconservative for the gravity load case (0.85 < 0.93). However, as mentioned in the industrial frame
example these linear comparisons are only approximations. When the gravity loads are scaled in the
direct analysis to provide an interaction value of 1.0 for the bottom column, the limit load ratio was ;)., ' Ii
= 0.99, which exceeds the value of ;)."G= 1.07 from the spread-of-plasticity solution. This indicates that
the Direct Analysis is, in fact , 9% lower (conservative) as compared to the spread of plasticity solution.
Multi-story Frame Example
The final example is the multi -story frame shown in Figure 8. One load case is investigated (J .OG +
I .OW, where the specified loads are already factored), and member forces and interaction checks are
presented for the three columns in the first story. Unlike the previous examples , this frame is fairly stiff
with B1 = 1.10 for the first story. The second-order spread-of-plasticity analysis predicts an inelastic
design strength ratio of ;)., ' Ii = 1.06 for this frame, which combined with the low B 1 indicates that it is
dominated more by yielding than second-order effects. The center columns of the first two stories have
high axial forces and are subject to the t - factor adjustment in the Direct Analysis method. As di scussed
earlier, when PIP, > 0.5 for any column, the t - factor adjustments can be used or an additional notional
load of 0.001 Y, can be used. In thi s example, both approaches are presented and compared.
ell
IPf2"O
w
x
IPOOO
1ii
ffi
x
JPEJOO
N
ffi
x
IPf330
ffi
x
IPOW
m
w
x
IPf400
(il
:;:
CI2
w
x
2 0 6.Om - 12m
CJ3
l.IwIl
Gravity: "9. 1 kN/ m (11oor)
31.7 kN/ m (root)
Wind: 20 ..... kN (store 1 5)
10.23 kN (root)
F, _ 235 N/ mml'
E 205 kN/mml
Figure 8 - Multistory frame
Page 150[1 7
The first floor column forces, summarized in Table 6, reveal that differences between the three methods
are much smaller than in the previous examples. This follows from the fact that the second-order
amplification is small er in this example, which is more typical of most multi-story frames than the prior
examples.
T bl 6 M b a e em er eelS or F u t, story rame
E xample
Location and
Anal"sis/Desie" Method
[(ferr
Spread of EffeClivt
Direct Direct
Analysis "ilh Analysis with t
(t.OG+ t.OW)
Plasticity Length
Notional Load
Reduction
P,,, (kN) 683 672 659 662
P " (kN)
1720 1770 t770 1770
P,,, (kN) 92t 884 897 894
M ,(kN-ml 67 48 58 59
M,,(kN-m) t t5 11 8 143 135
Mu (kNrn) 99 87 96 96
Results of the beam-column interaction checks (Table 7) show that the Effective Length method is sli ghtly
less conservative than the Direct Analysis method, which is in contrast to the previous two examples
where the opposite was true. Based on the AlSC (1999) alignment charts, the effective buckling length
factors for the first story columns are K = 1.35, assuming the AlSC suggested value of G = 1.0 for the
foundation support . Accordingly, the in-plane interaction checks for the Effective Length procedure are
based on design compression strengths of $P,KL" = $P,KL IJ = 1580 kN and $P,KL" - 2140 kN. The in-
plane Direct Analysis checks (with K = J) are based design strengths of " - IJ - 1680 kN and
,P,L 12 = 2230 kN. All out-of-plane checks are based on K = I, with = IJ = 1460 kN and $P'L
12 = 2010 kN; and moment strengths of = = 175 kN-m and - 275 kN-m are used
throughout. As summarized in Table 7, the resulting interaction checks were all close, with the Direct
Analysis solutions about 2% to 3% conservative, relative to the Effective Length method. With reciprocal
of the inelastic limit load factor equal to 0.94, the average interaction values ranging from 0.94 to 0.99
indicate that all of the stability design methods are conservative in this ca e.
Ta bl e 7: Interachon VI a ues MI ' F or u ttstory ' rame E xampte
Location
Anahsis/Design Method
(t.OGL+t.OW)
Eerective Direct Analysis Direct Anll)sis
Length with Notional Load with t Reduction
Ctl molane 0.67 0.69 0.69
CII - oUI-of-pt'ne 0.54 0.56 0.57
Ct2 In-plane I.2t 1.25 1.23
Ct2 1.06 t.t5 1.12
cn - In-ptane 1.00 1.02 1.02
Cl3 out-of-olanc 0.85 0.92 0.9t
A VCT3SlC in-olanc 0.96 0.99 0.98
Page 16 of 17
REFERENCES
A1SC (1999), Load alld Resistallce Factor Specificatioll for Structural Steel Buildillgs, Arner. Insl. of
Steel Constr., Chicago, IL.
ASCE (1997), "Effective Length and Notional Load Approaches for Assessing Frame Stability", ASCE,
New York, NY.
A1SC (2000), Code ofStalldard Practicefor Steel Bllildillgs alld Bridges, American Institute of Steel
Construction, Chicago, IL.
Bimstiel, C., Imaod, 1. S. B. ( 1980), "Factors Influencing Frame Stability," JI. of the Struct. Div .. ASCE,
I 06(ST2), 491-504.
Deieriein, G.G., White, D. W. (1988), "Chapter 16 - Frame Stability," Gllide to Stability Desigll Criteria
for Metal Structures, Ed. T.V. Galambos, Fifth ed., Wiley, 1998.
Deierlein, Hajjar, Yura, White, Baker, "Proposed new provisions for frame stability using second-order
analysis", Proceedillgs 0fSSRC 2002 Allllllal Meetillg, Seattle, WA
LeMessurier, W. 1., (1977), "A Practical Method of Second-Order Analysis - Part 2 Rigid Frames," Ellgr.
JI., A1SC, 14(2), 49-67.
Maleck, A. E. & White, D. W. (2002), "Direct Analysis Approach for the Assessment of Frame Stability:
Verification Studies," SSRC Annual Technical Meeting, Baltimore, MD, SSRC, 17 pgs.
Maleck, A. E. & White, D. W. (2003), "Alternative Approaches for Elastic Analysis and Design of Steel
Frames: Part I Overview, PartH Verification Studies, " JI. ofStruct. Ellgrg., ASCE, submitted for
review.
Martinez-Garcia, J.M. (2002), "Benchmark Studies to Evaluate New Provisions for Frame Stability Using
Second-Order Analysis," M.S. Tllesis, supervised by R.D. Ziemian, Bucknel1 University, 241 pgs.
McGuire, W. (1992), "Computer-aided analysis," COllst.1 Steel Desigll- Allillti. Gllide, Dowling, et al.
(eds.), Elsevier, NY 915-932.
Springfield, J. (1991), "Limits on Second-Order Elastic Analysis," Proc. SSRC Annu. Tech. Sess., SSRC,
Bethlehem, PA, 89-99.
White, D. W., Chen. W.-F. (eds.) (1993), Plastic Hillge Based Methodsfor Adv. Allalysis alld Desigll of
Steel Frames, SSRC.
Page 170JI7