Pump Sizing

This document summarizes the sizing of a pump for moving water between an elevation of 99.5 feet and 86.6 feet. It identifies the pump model as a Goulds WS15D3 pump with a discharge pipe that is 130 feet long with a 3 inch diameter. Based on the pump and system curves, the operating point of the pump is determined to be 25.0 GPM of flow at a head of 160 feet, resulting in a velocity of 0.36 feet/sec and an operating pressure of 7.3 psi. Power requirements are also calculated.

Uploaded by

Nikunj
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
100% found this document useful (5 votes)
4K views4 pages

Pump Sizing

This document summarizes the sizing of a pump for moving water between an elevation of 99.5 feet and 86.6 feet. It identifies the pump model as a Goulds WS15D3 pump with a discharge pipe that is 130 feet long with a 3 inch diameter. Based on the pump and system curves, the operating point of the pump is determined to be 25.0 GPM of flow at a head of 160 feet, resulting in a velocity of 0.36 feet/sec and an operating pressure of 7.3 psi. Power requirements are also calculated.

Uploaded by

Nikunj
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 4

Size a Pump

CLIENT: DSN BY: COMMENTS: COUNTY: CHK BY: ___________ DATE: DATE:__________

Elevation at Highest Point Elevation at Low Point

99.5 86.6

ft ft

CLEAR CELLS

DISCHARGE PIPE Discharge Pipe Length Equivalent Length of Pipe Fittings Discharge Pipe Inside Diameter Hazen-Williams Roughness, C Other Losses

130.0 35.0 3.00 130 0.0

Static Head Total Discharge Pipe Length

12.9 165.0

Pump Manufacturer Pump Model #

Goulds WS15D3

ft ft (see tables) =============================> in ==========================> Hazen-Williams Material ft Brass Cast Iron Concrete Copper ft Fiberglass ft (includes equivalent length of fittings) PE, no joints PVC Steel, Smooth Steel, Spiral Steel, CMP

Pump Curve Flow GPM 0 50 100 150 200 250 300

Pump Head, ft 38 34 30 26 22 16 10

System Curve Flow GPM 0 50 100 150 200 250 300

System Head, ft 12.9 14.3 17.9 23.6 31.0 40.3 51.3 25.0 160 0.36 7.3 10.8 ft (Intersection of curves from graph below) gpm (Intersection of curves from graph below) cfs feet/sec psi

Head at Operating Point Flow at Operating Point Operating Velocity Operating Pressure

Note: Velocity will increase as static head pressure (acting against the pump) decreases

Pump & System Curves


60
Pump System

50

40 38

40.3 34

Head, feet

30

30 26 23.6

31.0

22 16

20 17.9 12.9 10 14.3

0 0 50 100 150 200 250 300

Flow, gallons per minute


POWER REQUIREMENTS Hydraulic Power 1.0 0.8 74.0 1.4 1.0 70.0 2.0 1.5 WHP WkW % bHP bkW % HP kW (net energy transferred to the fluid) (net energy transferred to the fluid) (see manufacturer's efficiency curves) (power delivered by the motor to the pump) (power delivered by the motor to the pump)

Installed Pump Efficiency Brake Power

Motor Efficiency Motor Input Power

COST OF ELECTRICITY Cost per kW-hr Hours used Total Cost

$0.100 1.0 $0.15

Dollars Hours Dollars

Size a Pump
8/10/12 DATE:__________

CLEAR CELLS

Hazen-Williams C 130 100 100 130 150 150 130 100 90 60

51.3

10

300

(power delivered by the motor to the pump) (power delivered by the motor to the pump)