Application areas
Static Excitation Systems (SES) for 50 Hz, 60 Hz or 16 2/3 Hz power supply with field currents from 1000 ADC to more than 10,000 ADC Automatic Voltage Regulating Systems (AVR) for exciter machines with special functions, supply frequencies from 16 2/3 Hz to 400 Hz.
Additional inputs and outputs Easy to extend to the required number with ARCnet devices Digital and analog Event and error log With real-time stamp Remote interrogation possible.
Power converter redundancy Up to a maximum of eight parallel power converters are possible Power converter redundancy is completely independent of the regulator configuration Intelligent power converter electronics Active equalization of the current between the power converters 4-quadrant operation (negative excitation current is possible) Thyristor current monitoring Fan control and monitoring Monitoring of fuses, power converter temperature and cooling-air flow Bridge current display.
Voltage regulator
AC field breaker
Page 2
ABB
S5_ D5_
AVR AVR
BFCR
__E
__T
AVR1
A5_
AVR2
AVR1
Q5_
BFCR
__S
AVR2
BFCR
AVR: Voltage regulator (AUTO) with field current regulator (MAN) BFCR: Backup-field current regulator Fig 2: The standard configurations of the voltage regulator section and power converter units can be combined at will, e.g. S5T, D5E, A5S, Q5T
ABB
Page 3
Monitoring and protection functions are classified in three different action levels: Fault display only Switch-over to the second channel or to the backup regulator (if provided) or use of the available power converter redundancy Instantaneous excitation trip for protection purposes. Control functions All standard excitation sequences and interlocks are software-based with fixed pre-programmed function blocks. They can be extended with freely programmable function blocks by the user.
Data recording
The UNITROL 5000 software has an event recorder (fault logger), that can record up to 100 events and alarms with real-time stamp. The logs are read and analyzed with the control panel or the CMT software. Up to six measurement signals can be recorded in real-time with the data recorder (data logger). These can be displayed graphically in the CMT software trend window for diagnostic purposes.
Page 4
ABB
Instead of a single lead/lag filter the MBPSS has three individually adjustable working bands, in order to ensure effective working over the complete frequency range of typically 0.05 4.0 Hz. The three bands are designed to damp the electromechanical oscillations at low, medium and high frequencies.
For the stabilizer in accordance with IEEE - PSS2A, fixed parameters take care of optimum damping with adjustable lead/lag filters. To determine these parameters ABB has calculation software that takes account of the generator and excitation system data, as well as the transformer and network reactances.
Adaptive power system stabilizer (APSS)
t t
The adaptive power system stabilizer works with variable parameters that are set by continuous calculation of the working point and the current state of the power system. For the UNITROL 5000 no additional hardware is necessary contrary to the UNITROL P system.
1
R S T
}
n
ABB
Page 5
Communication with the system Integration in higher hierarchical control systems The service panel SPA is connected to
the system via an RS485 interface. The four-line display shows system functions, system parameters, measured values, alarms etc. in clear text form. The excitation system can be controlled with the push-buttons. The control panel LCP (optional for smaller excitation systems) can be used for local or remote control is connected via the ARCnet bus. The LCP is for the control of the system, the display of actual values and events. Communication with higher hierarchical control systems is possible with the appropriate bus coupler that is connected to the DDCS interface (via an optical link). The following standard protocols are supported for control and data transfer: MODBUS MODBUS+ Profibus.
Remote Diagnostics
Fig. 4: Communication levels for the user friendly control and monitoring of the UNITROL 5000 system
AVRview
Firewall
LAN
Internet
Power plant
LCP
Excitation system
Nxxx
LCP
DDCS
Digital/analog inputs/outputs
ARCnet Ethernet
TCP/IP
LAN
ACT
PAR
FUNC
COM SEL
RS485
ENTER
LOC REM
RESET
REF
Voltage regulator
I
UNITROL
R
I/O
internal
CIN
...
CIN
CH2
SPA
Page 6
ABB
Parameter and signal display window Display and changing of parameters or signals in table form Each parameter or signal can be assigned to a parameter or signal group that can then be selected and processed as a group. Other display windows Event log display, shows the last 100 events and alarms in chronological order (Faults) Display of the data recorded (DLog), six channels, each with up to 1000 data points).
Fig. 6 (below): Display of application programs and parameter values with CMT
ABB
Page 7
Fig. 8: In the selection window (above), any signals can be selected for a general overview; the data logger window represents stored signals graphically
ABB Switzerland Ltd Static Excitation Systems, Voltage Regulators and Synchronizing Equipment CH-5300 Turgi / Switzerland Telephone: +41 (0) 58 589 24 86 Fax: +41 (0) 58 589 23 33 Email: [email protected] www.abb.com / unitrol Internet:
For more information about UNITROL please visit our website www.abb.com / unitrol