GT Trips List (Generic)
GT Trips List (Generic)
GT Trips List (Generic)
DWG. NO.
401B3661
REV
SH.
REV.
IssuedBy
13
12
11
10
REV SH
BOM ISSUED
UNLESS OTHERWISE SPECIFIED DIMENSIONS ARE IN INCHES TOLERANCES ON 2 PL DECIMALS 3 PL DECIMALS ANGLES FRACTIONS
SIGNATURES
DRAWN RAGHU GUDA. CHECKED DURGA NALLAMOTTU ENGRG DURGA NALLAMOTTU ISSUED KERRIE LOKENBERG
DATE
08-11-12 08-11-12 08-11-12 08-11-12
COPYRIGHT 2008
PROPRIETARY INFORMATION-THIS DOCUMENT CONTAINS PROPRIETARY INFORMATION OF GENERAL ELECTRIC COMPANY AND MAY NOT BE USED OR DISCLOSED TO OTHERS, EXCEPT WITH THE WRITTEN PERMISSION OF GENERAL ELECTRIC COMPANY.
0
APPLIED PRACTICES
SIM TO:
0476 401B3661
0
SHEET
B
SCALE
1 of 13
DT-1N
SIZE
DWG. NO.
401B3661
SH.
REV.
SIGNAL NAME
TYPE
DESIGN JUSTIFICATION
DETECTION METHOD
LOGIC DESCRIPTION
L39VT
PROTECTIVE STATUS 2
Trip when any detector measures vibration above trip level AND other detector in that pair is disabled or measures above alarm level for LK39TTD
See Control Spec: Trip Level LK39VTx = 1.0 inch/sec Alarm Level LK39VAx = 0.5 inch/sec LK39TTD= 0.5 sec
GT EXHAUST TEMPERATURE AND PRESSURE Trip when 96EP-1 pressure transmitter exceeds limit AND at 63ET-1,63ET-2 least one of the two 96EP-1 exhaust pressure trip switches 63ET-1 or 63ET-2 is picked up. Trip when exhaust temperature exceeds Exhaust Temperature TTKOT1 limit or when it TC's exceeds exhaust temp TT-XD-1 through 31 reference by TTKOT2 deg F. See Control Spec and Device Summary: 63ET-1:INCREASING: 24.0+-0.5 INH2O 63ET-2:INCREASING: 24.0+-0.5 INH2O KAFPEPHH=24 INH2O See Control Spec: TTKOT1 = 1240F TTKOT2 = 40F
L63ETH
PROTECTIVE STATUS
L86TXT
PROTECTIVE STATUS
L86TXT
See Control Spec: Over.temp trip isothermal settingTTKOT1 = 1240F Over.temp trip incremental setting.TTKOT2 = 40F diff Low range exhaust temp limit TTKOT5= 1215 F High range ex
L86TFB
PROTECTIVE STATUS
Trip when exhaust temperature signal drops below TTKXM4 deg F while in operation.
SIZE CAGE CODE
B
401B3661
SCALE CONT ON SHEET
0476
DISTR TO
DRAWN ISSUED
2 of 13
SIZE
DWG. NO.
401B3661
SH.
REV.
PROTECTIVE FUNCTION Compressor Discharge Pressure Low EXHAUST FRAME AND #2 BEARING High Load Tunnel Temperature Trip LUBE OIL AND HYDRAULIC OIL PROTECTION LOW LUBE OIL PRESSURE TRIP
SIGNAL NAME
TYPE
DETECTION METHOD
LOGIC DESCRIPTION Trip when compressor discharge pressure drops below CAKCPD psig when Gen breaker is closed.
L3TFLT
PROTECTIVE STATUS
96CD-1, 1B, 1C
L30LTT
PROTECTIVE STATUS
TT-IB-1,TT-IB-2,TT-IB3
Trip when Load Tunnel Inner Barrel Temp exceeds LTKTRIP deg F.
L63QTX
PROTECTIVE STATUS
96QT-1, 2, 3
15 psig QHTPK = customer specified DECREASING: 20.0+-2.0 PSIG OR 1.4061+-0.1406 KG/Cm2G (INCREASING: 22.0+-2.0 PSIG OR 1.5468+-0.1406 KG/Cm2G) NORM=(1) NO-CEC;
L63HGL
PROTECTIVE STATUS
63HG-1,2,3
COMBUSTION MONITOR AND GT FLAME DETECTION Trip occur (1) Spread See Control Spec: #1 > Allowable spread K30SPT= 2sec Allowable Spread limit Exhaust Temperature or (TTXSPL) = Calculated TC's Spread #1 (varies between TTKSPL7 TT-XD-1 through 31 >TTXSPL_Z1 and TTKSPL6 (30-125 AND Spread#2 is 0.8 degF) Compressor times greater rhan Steady state allowable Discharge TC's allowable spread when spread = function CT-DA-1, 2, 3 2nd and 3rd coldest (exhaust temperature, TC's are adjacent after compressor discharge K30SPT seconds temperature)
L30SPT
PROTECTIVE STATUS
SIZE
CAGE CODE
DWG NO
B
401B3661
SCALE SHEET
0476
DISTR TO
DRAWN ISSUED
3 of 13
SIZE
DWG. NO.
401B3661
SH.
REV.
LOGIC DESCRIPTION Trip when two of the four combustor flame detectors indicate loss of flame. Trip when 1) Turbine Speed falls below highest attained speed by more than the allowable limit (LK60BOG1) for LK60BOG2 seconds, OR (2) Static starter fails to start after getting start up permissiv e After run and Torque command is giv en to startic
L3SMT
PROTECTIVE STATUS
TNH, 52CR-1
See Control Spec: LK60BOG1 = 5 % LK60BOG2 = 1 sec LK14SSBOG = 1 % LK60SSBOGTRIP = 45 sec, KSS_CON_FAIL = 10 sec K60SSBOGTRIP=45 SECONDS
GT COMPRESSOR PROTECTION Trip when difference between IGV position feedback (CSGV) and IGV refrence angle (CSRGV) is greater than LK86GVT1 DGA for more than LK86GVT2 sec below L14HS (95% speed), or when IGV position feedback (CSGV) is less than LK4IGVTX DGA abov L14HS e (95% sp Trip when any bleed v alv is not full open e after a time delay of K20CBY sec while the gen circuit breaker is open or the turbine drops below L14HS (94% speed) Trip when compressor pressure ratio, offset by CPKERRO, exceeds the compressor operating limit line by CPKERRMX for CPKERRTD sec.
SIZE CAGE CODE
L4IGVT
PROTECTIVE STATUS
96TV-1, -2 90TV-1
See Control Spec: LK86GVT1 = 7.5 DGA LK86GVT2 = 5 sec LK4IGVTX = 38 DGA
L86CBT
PROTECTIVE STATUS
33CB-1, 2, 3, 4
LCPRERR
PROTECTIVE STATUS
96CD-1, 1B, 1C
DWG NO
B
401B3661
SCALE SHEET
0476
DISTR TO
DRAWN ISSUED
4 of 13
SIZE
DWG. NO.
401B3661
SH.
REV.
PROTECTIVE FUNCTION FUEL CONTROL Gas Aux Stop Position Fault PreIgnition Trip
SIGNAL NAME
TYPE
DESIGN JUSTIFICATION
DETECTION METHOD
LOGIC DESCRIPTION Trip if the aux stop valve is commanded open and does not open or open fully before flame is detected. Trip when SRV position feedback, fsgr, exceeds startup fuel stroke reference high setpoint, LK60FSGH, and the warmup is not complete and also leak test master should be enabled. If you are on Liquid fuel and if flow divider speed FQL1 is higher than constant LK60FFLH FOR K2SFTL time In liquid fuel , turbine trip is intiated whenever fuel flow is high after completion of warmup,accelerating stage and no liquid fuel recirculation Trips when the firing timer, K2F, expires and when flame is not detected from 2 of 4 flame detectors after giving startcommand K6TT2 times and on total gas.
L4VS4_PI
PRE IGNITION
33VS4-1, 2
NA
L2SFT
L94FIG L4FIGFLT
28FD-1, 2, 3, 4
L86FIGFLT
PRE IGNITION
28FD-1, 2, 3, 4
Successive Failures to K62TT2 = 2 unsuccessfull light off on gas fuel. start attempts
SIZE CAGE CODE DWG NO
B
401B3661
SCALE SHEET
0476
DISTR TO
DRAWN ISSUED
5 of 13
SIZE
DWG. NO.
401B3661
SH.
REV.
PROTECTIVE FUNCTION
SIGNAL NAME
TYPE
DESIGN JUSTIFICATION
DETECTION METHOD
LOGIC DESCRIPTION Trip when a gas speed ratio valve fault occurs: the error between position command and psoition feedback exceeds K3GRVTX %. Trips (1) When GCV feedback is less than K3GCVFB after time delay of K3GFTD (2) When GCV is failed to open in comparison (greater)with LK3GCVxO when valve is not enabled after time delay of K3GVFTD (3) or if the servo current is lesser than K3GCVSC after time delay of K3GVFTD Trip when difference between GCV position and reference is greater than LK3GCVx for for 10 seconds. Trip when P2 pressure exceeds KFPG2IH for K86FPG2IH seconds before firing permissive is reached. Trip when P2 Pressure exceeds FPG2WUH (post ignition high pressure trip set point) for K86FPG2HT seconds between firing permissive and warmup complete.
SIZE CAGE CODE
L3GRVT
PROTECTIVE STATUS
96SR-1, 2
L3ACS
96GC-x, 77FD
See Control Spec: LK3GCVxFB = -5% LK3GCVxO = 5% LK3GCVxSC = 37.5% K3GVFTD=3 sec (where x = GCV number: 1, 2, 3, Q)
L86GCVxT
96GC-n
L86FPG2IH
96FG-2A, 2B, 2C
L86FPG2H T
96FG-1, 2A, 2B
DWG NO
B
401B3661
SCALE SHEET
0476
DISTR TO
DRAWN ISSUED
6 of 13
SIZE
DWG. NO.
401B3661
SH.
REV.
PROTECTIVE FUNCTION
SIGNAL NAME
TYPE
DESIGN JUSTIFICATION
DETECTION METHOD
LOGIC DESCRIPTION Trip when P2 pressure falls below FPG2WUL (post ignition P2 low pressure trip setpoint) for K86FPG2LT seconds between firing permissive and warmup completeon fuel gas operation Trip when the leakage across the SRV is excessive and the P2 cavity pressure rises above K86GLTA psig in K86GLT1 seconds, or if the P2 pressure drops below K86GLTB psig in K86GLT3 sec during a bottle test both during startup and shutdown. Trip when any of the following conditions match: (1) when Aux gas purge trip OR (2) When Pilot premix mode or premix mode and K20PG3ONY sec. to G3 purge command off and purge G3 command close category 4 fault OR (3) Purge G1 Command Close Category Fault and TD G1 Purge command off in Prmix mode (4) TD G2 purge cmd off and purge command category fault
SIZE CAGE CODE
Gas Fuel Intervalve P2 Pressure Low PROTECTIVE L86FPG2LT During Ignition and STATUS TRIP 2 Warm Up
96FG-2A, 2B, 2C
L94GLTSU L94GLTSD
PRE IGNITION
96FG-2A, 2B, 2C
See Control Spec: K86GLTA = 100 psig K86GLT1 = 30 sec K86GLTB = 150 psig K86GLT3 = 30 sec
L4GPFT
TRIP
33PG-xx,63PGxx,20PG-x
K20PG3ONY = 8 Sec.
DWG NO
B
401B3661
SCALE SHEET
0476
DISTR TO
DRAWN ISSUED
7 of 13
SIZE
DWG. NO.
401B3661
SH.
REV.
PROTECTIVE FUNCTION
SIGNAL NAME
TYPE
DESIGN JUSTIFICATION
DETECTION METHOD
LOGIC DESCRIPTION Trip when either of following condition match (1) Purge G3 command open no faults and K20PG30NZ1 sec. TD G3 Purge commandm On Flame not Detected Minimum speed signal come (2)Purge G2 command open no faults and K20PG20NZ1 sec. TD G2 Purge commandm On Flame not Detected Minimum speed signal come (3) Purge G1 command open no faults and K20PG10NZ1 sec. TD G1 Purge commandm On Flame not Detected Minimum speed signal come
L4GPF_PI
33PG-xx,63PGxx,20PG-x
SPEED PROTECTION Turbine Primary Electrical Overspeed Trip L12H PROTECTIVE STATUS Overstress of rotating components 77NH-1, 2, 3 Trip when median selected speed is above Primary OS trip level
SIZE CAGE CODE
B
401B3661
SCALE SHEET
0476
DISTR TO
DRAWN ISSUED
8 of 13
SIZE
DWG. NO.
401B3661
SH.
REV.
LOGIC DESCRIPTION
Loss of Primary Control Speed L12HF Signal Loss of Emergency Control Speed L12H_FLT Signal
PROTECTIVE Loss of speed control and STATUS TRIP 3 Primary OS protection PROTECTIVE Loss of speed control and STATUS TRIP 2 Emergency OS protection
77NH-1, 2, 3
77HT-1, 2, 3
L12HFD_C L12HFD_P
PROTECTIVE STATUS
77NH-1, 2, 3 77HT-1, 2, 3
Loss of Emergency L12H_ACC Speed Signals TURBINE CONTROL PANEL Control System Fault Trip L3SFLT
PROTECTIVE STATUS
77HT-1, 2, 3
Trip when median See Control Spec: selected speed is Emergency Trip Level = above Emergency OS 110% trip level Trip when primary See Control Spec: speed signal is low Speed signal < 5% while in operation Trip when emergency See Control Spec and speed signal is low GEH 6421 Chapter 7: while in operation Speed signal < 2.16RPM Trip when difference between Emergency See Control Spec: speed signal and Trip Level = 5% of rated Primary speed signal is speed greater than the trip level. Trip when 2oo3 Emergency speed NA signals indicate sudden deceleration.
Trip when 2 of 3 controllers are not voting. Trip when 2 of 3 <P:> controllers are Trip
SIZE CAGE CODE DWG NO
NA NA
0476
DISTR TO
B
401B3661
SCALE SHEET
DRAWN ISSUED
9 of 13
SIZE
DWG. NO.
401B3661
SH.
10
REV.
SIGNAL NAME
TYPE
DESIGN JUSTIFICATION
DETECTION METHOD
LOGIC DESCRIPTION
ACTION SETPOINT (Nominal Setpoints) Trip when Customer Trip hardwired digital input drops out. NA
L4CT
Customer Crosstrip
Contact inputs from Customer controller Trip when Remote or Local E-Stop pushbutton is depressed.
L5E, R5E
Emergency Trip
PROTECTIVE STATUS
33CB-1, 2, 3, 4
2oo3 Compressor Bleed Valve Open Limit Switches indicate open when commanded closed AND IGVs have 2oo3 open limit switches op ened past the for each of 4 Bleed Valves minimum operating positionL33CSGV_CB. IGV is opened during operation
STEP TO FSNL Remote Breaker Open Detect L83RBO PROTECTIVE STATUS Initiate a Step to Full Speed No Load to avoid machine damage due to overspeed Initiate a Step to Full Speed No Load to avoid machine damage due to overspeed TNH, TNHA 77NH Overspeed and Acceleration Detected Load Rejection due to Generator Breaker opening
SIZE CAGE CODE DWG NO
External52G Trip
L52GX
PROTECTIVE STATUS
52GX
NA
B
401B3661
SCALE SHEET
0476
DISTR TO
DRAWN ISSUED
10 of 13
SIZE
DWG. NO.
401B3661
SH.
11
REV.
LOGIC DESCRIPTION Load Rejection due to DCS detecting highhigh HRSG temperatures Open Breaker when Maximum of dwatt1 and dwatt2 is less then LK32DWRP When DWATT is lesser than DWTLLIM and Gen Watt transducer is sensing fault after time delay of V32DWTDC Gen Bkr opens on reverse power Open Breaker when operator Issue Manual breaker open Trips before ignition if DC emergencey lube oil pump is determined to be in under voltage condition Trips before ignition if DC emergencey seal oil pump is determined to be in under voltage condition Trip Signal is generated by logic L45LEL_PRET. This protection generates TRIP command in either og the following operating condition (1) If Turbine compartment Haz Gas Level Hi (2) If Gas Compt Has gas Level Hi (3) If Turbine compt Local Haz Gas Level Hi (4) If either of this Haz Gas monotor Rack #1, Rack # 2, Rack#3 (5) If Haz Gas syatem analog signal trbl
SIZE CAGE CODE
L32DW
STEP TO FSNL
Maximum of MW sensors
Manual Breaker open Emegency Lube Oil Pump Undervoltage Relay SEAL OIL Emegency Seal Oil Pump Undervoltage Relay
L52GT_TRI P
STEP TO FSNL
Operator Action
Operator Initiated
L27QEL
27QE-1
NA
L27ESL
27ES-1
NA
l45LEL_PR ET
PROTECTIVE STATUS
45HA,HT,HG
NA
DWG NO
B
401B3661
SCALE SHEET
0476
DISTR TO
DRAWN ISSUED
11 of 13
SIZE
DWG. NO.
401B3661
SH.
12
REV.
LOGIC DESCRIPTION Trip signal generates If either fire found in Turbine/Acc compt or other any of 4 zones Gen trip lock out [l86g1a],Breaker failure lock out [l86bft], Gen& GSU Transformer lock out trip[l86v] ,GSU Transformer lock out trip [l86t] Unit trip Via 86G1B[l86g_1b], Trip command will triggered if Emergency push button pressed Turbine trips after time delay of BY K4BTFLT When low ventillation pressure still both oh of the ventillation fans running Trips when level gets high when compared with predetermined level Trips when level gets high when compared with predetermined level
L86GT
Emergecny stop
L5ESTOP1 _FBZ
[5E-1/PB] [R5E/PB]
L4BTFLT
63AT-1.2.3,4
L4PSTX 4_A
To prevent uncleaned/moistured fuel entering into the machine To prevent uncleaned/moistured fuel entering into the machine
71GS-1 ,2A,2B
L4PSTX 4_B
71GCF1A,1B,2A,2B,3A,3B
L63AG_TR P
63AG-1,2
Trip signal will generate 1)If load compt vent pressure comes low sensed by both Control spec Pressure pr.switches after a switch setting time delay of 30 sec GEAR/LOAD COMPT AIR K63AG_TRP2 still two PRESSURE SWITCH fans are running DECREASING: 0.4 2)Load compt vent fan INH2O OR 10.1600 control signal is mmH2O enabled , still pressure NORM=NO-CEC; from sensed by 63AG 1,2 is GR1072 low after time delay of 7 min K63AG_TRP2 trip signal will be generated
SIZE CAGE CODE DWG NO
B
401B3661
SCALE SHEET
0476
DISTR TO
DRAWN ISSUED
12 of 13
SIZE
DWG. NO.
401B3661
SH.
13
REV.
PROTECTIVE FUNCTION
SIGNAL NAME
TYPE
DESIGN JUSTIFICATION
DETECTION METHOD
LOGIC DESCRIPTION Trips when (1)IF After the firing timer delay of L2F ,no flame is detected in total liquid fuel mode (2) Any protective trip command triggers when Startup firing fuel command is enabled or under operation (3) If total mass flow of liquid fule is gr Trips When fuel feedback exceeds limit while L20FLXX _X timer is denergized ,when there is no recirculation and total liquid fuel
L94FIL
L3FFL_FLT
77FD
K33FFL_FLT=15 Sec
SIZE
CAGE CODE
DWG NO
B
401B3661
SCALE SHEET
0476
DISTR TO
DRAWN ISSUED
13 of 13