100% found this document useful (1 vote)
388 views2 pages

Panel Test Cirtificate

The electrical panel passed all routine tests including dimensional checks, visual inspection, bill of material check, operational test, and insulation resistance tests. High voltage testing was also conducted at 2.5kV for 1 minute between all phase and earth combinations and the panel passed without issues. Insulation resistance values before and after high voltage testing were found to be within acceptable limits.

Uploaded by

Rohit Mukherjee
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
388 views2 pages

Panel Test Cirtificate

The electrical panel passed all routine tests including dimensional checks, visual inspection, bill of material check, operational test, and insulation resistance tests. High voltage testing was also conducted at 2.5kV for 1 minute between all phase and earth combinations and the panel passed without issues. Insulation resistance values before and after high voltage testing were found to be within acceptable limits.

Uploaded by

Rohit Mukherjee
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 2

JSW BENGAL STEEL LTD

ELECTRICAL PANEL TEST FORMAT


SL.NO. ITEM CUSTOMER PROJECT DRG.NO M/S M/S REV. 1 DATE OF TESTING JOB NO.

ROUTINE TEST RESULTS All dimensions are found within acceptable limits. Visual DIMENSIONAL, VISUAL & BOM CHECK inspection and bill of material checked, as per relevant drawing and found to be in order 3 Phase, 4 wire supply was given to the panel and operational test OPERATIONAL TEST carried out as per scheme, and same found to be OK. I.R TEST BEFORE H.V TEST BETWEEN R Y B R Y B R Y B Y B R N N N E E E VALUE M M M M M M M M M R Y R Y B R Y B AFTER H.V TEST BETWEEN Y B R N N N E E E VALUE M M M M M M M M M

B -

N - E M N - E M I.R VALUES BEFORE AND AFTER H.V TEST ARE FOUNDWITHIN ACCEPTABLE LIMITS H.V TEST : Test conducted 2.5 KV for 1 min. between phase to phase, phase to neutral, phase to earth and neutral to earth. TESTED BY CHECKED BY BLUESTAR APPROVED BY DESCON LIMITED LTD JSW