Distance 2

Download as pptx, pdf, or txt
Download as pptx, pdf, or txt
You are on page 1of 23

Distance Protection Schemes

6/12/12

Zones Of Distance Protection


Zone 1:
Trips with no intentional time delay Underreaches to avoid unnecessary operation for faults beyond remote terminal Typical reach setting range 80-90% of ZL Zone 2: Set to protect remainder of line Overreaches into adjacent line/equipment Minimum reach setting 120% of ZL Typically time delayed Zone 3: Remote backup for relay/station failures at remote terminal 6/12/12Reaches beyond Z2, load encroachment a

Z3 (remote backup) Z2 (time delayed) Z1

BU S

6/12/12

BU S

Local Z1

Click to edit Master subtitle style


BU S BU S

Z1 Remot e 6/12/12

Local Z1 End Zone

BU S

End Zone 6/12/12

Remot e

BU S

Z1

Pilot Aided Schemes

Non-Pilot Aided Schemes (Step Distance)

Communication between Distance relays


6/12/12

No Communication between Distance Relays

Zone1 Extension Scheme

6/12/12

BU S

Local Relay Communication Channel

6/12/12

BU S

Remote Relay

Pilot Communications Channels


Typical communications media include: Power line carrier Microwave Radio Optic fiber (directly connected or multiplexed channels)

6/12/12

Pilot-Aided Distance-Based Schemes


DUTT Direct Under-reaching Transfer Trip

PUTT Permissive Under-reaching Transfer Trip

POTT Permissive Over-reaching Transfer Trip

DCB Directional Comparison Blocking Scheme

DCUB Directional Comparison Unblocking Scheme

6/12/12

DUTT Scheme
Local Z1 Breake r Trippe d

BU S

Breake r Closed

6/12/12

BU S

Z1

DUTT Scheme

6/12/12

Requires both under reach and overreach zones Identical to DUTT, with pilot tripping signal supervised by overreach

Permissive Underreaching Transfer Trip (PUTT)

6/12/12

PUTT Scheme

6/12/12

Current Reversal Condition

6/12/12

PUTT Scheme

6/12/12

Permissive Overreaching Transfer Trip (POTT)

6/12/12

Weak Infeed Feature

6/12/12

Substation A Will Not Pick up for fault If there is fault substation b send permissive signal To prevent incorrect tripping at end A in case of reverse fault reverse looking feature provided

Substation A Will Not Pick up for fault If there is fault substation b send permissive signal To prevent incorrect tripping at end A in case of reverse fault reverse looking feature provided

6/12/12

Logic Diagram

6/12/12

Blocking Over Reach Protection scheme

6/12/12

Directional Comparison Unblocking Scheme

6/12/12

6/12/12

You might also like