Angus Model S1: Standard Response Sprinkler

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

ANGUS MODEL S1

CONVENTIONAL UPRIGHT / PENDENT SPRAY (CU/P) STANDARD RESPONSE SPRINKLER


The Angus "S" range of miniature automatic sprinklers offers the very latest in design and performance, being both highly compact and durable. In addition, every S sprinkler is fitted with the unique Angus double grooved seal. The Angus "S" range is manufactured at the company's purpose built European factory which is assessed to ISO 9001:2000 The range is CE marked EN 12259-1 and approved by LPC and other leading national and international approval authorities*. "S" sprinklers are manufactured in brass, stainless steel, and titanium. 28
TECHNICAL SPECIFICATION Nominal Bore: 15mm K Factor: RTI-Value: Weight: Thread: Maximum Working Pressure: System Test Pressure: Factory Test Pressure: Bulb temperatures: 804 (metric) ~ 100 (metric) (Standard A) 69g (Brass) " BSPT (NPT optional) 12.5 Bar 20 Bar 35 Bar 57C/68C/79C/93C/141C/182C

53

Finishes available include chrome plated, electro nickel plated, white painted (to RAL 9010). Custom coloured paint finishes are also available to order. The Angus "S" range is complemented by a unique range of installation efficient colour matching single and recessed two piece rosettes (escutcheons) and by other accessories such as guards, watershields and spanners.
2 BAR RUNNING PRESSURE CEILING UPRIGHT UPRIGHT 2.50 2.00 PENDENT PENDENT 1.50 1.00 0.50 FLOOR 4 3 2 0 1 0 1 2 3 4 METRES RADIUS UNIFORM COVERAGE 0.5 BAR RUNNING PRESSURE 3.08 3.00

INSTALLATION: Install in the upright or pendent position. ANGUS spanners must always be used when fitting sprinklers into pipework. Sprinklers that have been dropped or damaged in any way must not be installed. Sprinklers removed from pipework for any reason must not be re-used and must be destroyed. Brass framed sprinklers should only be installed in non corrosive environments and environments free of ammonia, chloride vapours and cleaning solutions. * for a full, and up to date, list of approvals refer to Angus
The right is reserved to vary or modify any specifications without prior notice

ANGUS FIRE - SPRINKLER DIVISION Thame Park Road, Thame, Oxfordshire, OX9 3RT. UK TEL: 44 (0) 1844 265000 FAX: +44 (0) 1844 265159 Email: [email protected]
DATA SHEET No:

Data Sheet:

S1 CUP 15mm Std Rsp K80

SH005 1001 A

Page: Date:

1 of 1 7th February 2006