Power to rely on
Bridges short voltage interruptions Continuous Power Conditioning Up to 30 seconds Ride Through time Power Stabilization Battery Free solution Beneficial life cycle costs
People to rely on
Hitec Power Protection has a proven track record of delivering high quality power solutions in demanding industries such as: Data centres Finance Aviation Process Healthcare Telecommunication Semiconductor
A Hitec Ride Through system acts as a filter for all sorts of utility disturbances
Q3
1 3 6
Q1
Q2
4 2 5
1 2 3 4
5 6 7
Power to rely on
People to rely on
mission-critical
processes
Main Characteristics
In case of power outages the Ride Through system provides 15 - 30 seconds of Ride Through power. In utility and gen-set operation, the Ride Through system functions as an active harmonic filter, cleaning and regulating the output voltage to ensure that a smooth and constant sine wave is presented to the load. In addition it provides all the reactive power demand required by the load and so greatly improves the power factor requirement from the supply. In case of a short circuit of the utility or gen-set supply, the Ride Through system output voltage will be maintained regardless. Variations in the mains voltage will not influence the Ride Through output voltage. Whenever a short circuit occurs within the load distribution network,
Customer Support
The Hitec Power Protection name is synonymous with reliability, quality and excellent service. We believe that the best technology is only as good as the service that supports it. We have therefore established a worldwide network of subsidiaries and qualified service partners. Our service can offer you: Customized maintenance solutions, in line with your needs and additional to your internal capacity Help Desk Services - available 24x7- for operational questions, remote monitoring, support, troubleshooting, etc. Remote monitoring and diagnostic support. Our service department can access your Ride Through system through the Internet or a modem connection and assist with operational issues, offer maintenance advice, provide troubleshooting, etc. Training programs at various skill levels for the operation and maintenance of your system.
RT 400
System power (load) [kVA] Active power (load) [kW] Power factor (load) Rated voltage [V] 400 320
RT 750
750 600
RT 1250
1250 1000 400/480 up to 24KV
RT Parallel
System power x units Active power x units
Input Data
Voltage Power factor Frequency Starting current 400V / 480V 10% 3 phase 4 wire 0,98 50/60 Hz 1,5 - 4 % (adjustable) 10% x I nom
1250
Power (kVA)
750
500
400 kVA
250
Time (sec)
0 0 5 10 15 20 25 30 35
Output Data
Ride through time Voltage (static) Voltage (dynamic) Recovery time Voltage THD Frequency Overload capacity Voltage symmetry Fault clearing capacity 15 sec. 100% load 30 sec. half load (longer time on request) 1% 5% 250 ms (50% load step) 1000 ms (100% load step) 3,5% (phase-phase with linear load) according to mains input frequency 1hr 110% ,10 min. 125%, 1 min. 150% (at mains operation) 120 1% > 10 x I nom
Dimensions
Weight (kg) Length (mm) Width (mm) Height (mm)
RT 400
8000 5230 1250 1460
RT 750
11000 5770 1250 1590
RT 1250
15000 6380 1580 1780
General Data
Flywheel speed all types Efficiency Cable entry Ambient temperature Altitude Degree of protection Classification max 2900 rpm up to 96% bottom entry (optional top entry) 0C 40 C max 3000 m without power de-rating IP21 G3 acc. to IEC 88528-11
Data for the containerised Ride Through systems or specific requirements at request.
All data in this brochure is for information and is subject to change without prior notice. No rights can be obtained form the contents of this brochure. Data provided in our offerings prevail at all times.
Taiwan Hitec Power Protection Taiwan Ltd. 5F-1, No. 27, Puding Rd., Hsinchu 300 Taiwan Phone: +886 (03) 56 36 781 Fax: +886 (03) 56 37 135 e-mail: [email protected] web: www.hitec-ups.com The Netherlands Head office Hitec Power Protection bv Bedrijvenpark Twente 40 7602 KB Almelo The Netherlands Phone: +31 546 589 589 Fax: +31 546 589 489 e-mail: [email protected] web: www.hitec-ups.com United Kingdom Hitec Power Protection Ltd. Unit B21a Holly Farm Business Park Honiley, Kenilworth Warwickshire, CV8 1NP UK Phone: +44 1926 48 45 35 Fax: +44 1926 48 43 36 e-mail: [email protected] web: www.hitec-ups.com United States of America Hitec Power Protection Inc. 12502 Exchange Drive, Suite 404 Stafford, Texas 77477 USA Phone: +1 (281) 240 - 5335 Fax: +1 (281) 240 - 4774 e-mail: [email protected] web: www.hitecusa.com Spain Hitec Power Protection Ibrica S.L Pol. Ind. Moli den Serra C/Alt Penedes nave 4 43710 Santa Oliva (Tarragona) Spain Phone: +34 977 668 902 Fax: +34 977 157 334 e-mail: [email protected] web: www.hitec-ups.com China Hitec Power Protection Beijing Co. Ltd. D-1016 C, Building Top Box, No. 69 Bei Chen West Street Chaoyang District, Beijing 100029 China Phone: +86 10 58 77 20 36 Fax: +86 10 58 77 20 37 e-mail: [email protected] web: www.hitec-ups.com Singapore Hitec Power Protection BV Blk 3 Ang Mo Kio Industrial Park 2A #02-06 AMK Tech I Singapore 568050 Phone: +65 67 37 68 69 Fax: +65 67 37 68 70 e-mail: [email protected] web: www.hitec-ups.com Middle East & India Hitec Power Protection bv P.O. Box 50048 Dubai U.A.E. Phone: +971 434 737 00 Fax: +971 434 732 32 e-mail: [email protected] web: www.hitec-ups.com Malaysia Hitec Power Protection (Malaysia) SDN BHD TKT 3 Komplex MITC Jalan Konvensyen Ayer Keroh 75450 Melaka Malaysia Phone: +60 655 28 553 Fax: +60 655 28 563 e-mail: [email protected] web: www.hitec-ups.com