Peps Lectures
Peps Lectures
Peps Lectures
1/454
Course Outline
Introduction Load Compensation Shunt Compensation Series Compensation HVDC Transmission
Application of Power Electronics in Power Systems B. G. Fernandes
2/454
Hingorani N. G Understanding FACTS Concepts & Technology of FACTS Systems, IEEE PRESS, 2000.
Application of Power Electronics in Power Systems B. G. Fernandes
3/454
Introduction
Power Electronics has grown as a major & extremely important discipline in Electrical Engg. What are major applications of Power Electronics ? Major role in Power Transmission & Distribution
Application of Power Electronics in Power Systems B. G. Fernandes
4/454
Consumption of Electricity are Demanding Customers Loss of Power for single cycle can make computer screen go blank Can interrupt sensitive Electronic equipment
5/454
Consumption of Electricity is also Transmission lines are being operated close to their limits Power is being transmitted through long overhead transmission lines & they are interconnected
6/454
P
THERMAL LIMIT
Distance
7/454
Thermal limit
Voltage limitations For typical 400 kV line Zc = 300 SIL = 540 MW For cable SIL is large
8/454
Voltage profile along the line is flat if P = SIL If VS = VR = 1, V as we move towards the midpoint, if Ps > SIL
P < SIL P = SIL
VS
P > SIL
VR
9/454
Line absorbs reactive power V if PS < SIL Voltage swell, line generates Q
P, Q P, Q
is
iR Transmission Line
Vs
VR
10/454
To control VR & power transfer capacity of the line, Q generation is required at the receiving end
Application of Power Electronics in Power Systems B. G. Fernandes
11/454
V2 Q= XC
As VR
Q requirement as VR Other limitations L required during over voltage Separate L & C are required
Application of Power Electronics in Power Systems B. G. Fernandes
12/454
Requires only P
Application of Power Electronics in Power Systems B. G. Fernandes
13/454
O/P V => PWM 2- level inverter Harmonic spectrum depends on switching frequency (FS) PWM Constant FS Variable FS => Not suitable
14/454
What sort of PWM technique to use ? With low switching frequency how to improve the harmonic spectrum Do we need to change the power circuit configuration ?
15/454
VSVR = Sin X
To have sufficient stability margin max. length of line = 450 km Provide shunt reactive power compensation, there by P & maintain V profile. Use a mid point compensator
Application of Power Electronics in Power Systems B. G. Fernandes
16/454
Vm = VS = VR = V
It can be shown, for loss- less line
2V 2 P= Sin = 2 PUncompensated X 2
Application of Power Electronics in Power Systems B. G. Fernandes
17/454
If shunt compensation is applied at sufficient close interval, it may be possible to transmit power up to thermal limit of line P transmitted over long lines is limited by series reactance X
18/454
19/454
VS = VR = 1 pu
V P= Sin (1 K )X
K = Degree of compensation =
XC X
2
C is not permanently connected in series During fault condition, Xeff should be increased May require L also
Application of Power Electronics in Power Systems B. G. Fernandes
20/454
Is it possible to change the phase angle difference between two ends of the line and there by control the power flow Phase angle regulator ? Inject a voltage in series with the line & proportional to the current flow (voltage should lag the I )
21/454
22/454
Injecting V in series with line and with any phase angle with respect to VS
Both magnitude & phase angle of I has changed Both P & Q flow has changed
Application of Power Electronics in Power Systems B. G. Fernandes
23/454
Consider an AC network
Power flow in Line-1 & 2 depends on circuit conditions Lower X line may be over loaded Not possible to set the amount of power that should flow through a particular line!
Application of Power Electronics in Power Systems B. G. Fernandes
24/454
Definite amount of power that should flow through HVDC line can be set If power transfer over long distances Two near by areas having different frequencies ( Back to Back connection)
Application of Power Electronics in Power Systems B. G. Fernandes
25/454
Review
Power flow control through AC lines is not FLEXIBLE Depending upon the loading, there could be voltage swell or sag as we go towards the mid point
R+jX
V1
Application of Power Electronics in Power Systems B. G. Fernandes
V2
26/454
To control the power flow & to maintain voltage profile, provide Passive elements with Shunt compensation P.E switches or Series compensation
Inverter
Introduction ( contd)
Load compensation Loads are unbalanced P.F is lagging
No compensation of harmonics
Source should supply only active power & see a balanced load
28/454
Most of the loads are Non-linear Harmonics are generated Voltage at P.C.C is non sinusoidal P.F is lagging Circuit to filter the harmonics (on-line) + compensate the loads
Application of Power Electronics in Power Systems B. G. Fernandes
29/454
P.C.C
30/454
Current drawn by the load fed from P.E. equipment flows through system impedance. Voltage at P.C.C is non-sinusoidal (We had assumed that 'V' is sinusoidal).
31/454
1 1 ia = I0 sin t- sin 5 t + sin 7 t-............. 5 7 = 6N 1 , Harmonics Line Commutated converter causes notches in the source voltage waveform. Source current has harmonics.
2 3
32/454
Effe c t o f ha rm o nic s: A . In the Ro ta ting m a c hine Inc re a se s he a ting . The y p ro d uc e no ise . To rq ue p ulsa tio ns. C u lo sse s . A ud ib le no ise & he a ting . A d d itio na l he a ting . The rm a l vo lta g e stre ss. A ffe c ts c o ntro l syste m . M a lo p e ra tio n o f re la ys.
33/454
B. In Tra nsfo rm e rs
C . In C a b le s D . P.F c o rre c tio n c a p a c ito rs. E. Ele c tro nic Eq uip m e nts
Load compensation + Active filter Depending upon the voltage & power level, circuit configuration & control should change
34/454
Conclusions
Load compensator + Active filter to compensate non-linear loads Power flow in AC network is determined by circuit conditions Power transfer capability can be increased through shunt & series compensation HVDC can be used for bulk power transmission & to inter connect the systems of different frequencies
Application of Power Electronics in Power Systems B. G. Fernandes
35/454
Load compensation
In ideal power system V & F should be constant V should be sinusoidal P.F = 1 The above should be independent of size & characteristics of load No interference between different loads
Application of Power Electronics in Power Systems B. G. Fernandes
36/454
37/454
What are the characteristics of power system & loads which can deteriorate the quality of supply ? How to compensate ?
Ideal compensator
Correct the power factor to unity Reduce the voltage regulation to an acceptable value Balance the load current => not expected to compensate harmonics in V & I, also will not generate harmonics Should consume zero avg. power Response time = 0
39/454
PL
= QL = S L sin L = S L 1 cos2 L
SL
QL
40/454
Voltage regulation
Which is the most important parameter of the load & supply system affects regulation ?
IS RS+jXS
IL Sl = PL +jQL YL = GL +jBL
41/454
Vreg =
E V V
E V V
E V
IS R
No compensator IL= IS
V = Z S I L
IS X
V
S
VX
VI = PL + jQL
* L
IL= IS
42/454
VR
PL jQ L IL = V
PL jQL V = (RS + jX S ) V
RS PL + QL X S X S PL RS QL = +j V V
= VR + jVX
Change depends on both active & reactive power of the load
Application of Power Electronics in Power Systems B. G. Fernandes
43/454
IS RS+jXS
QS = QL + QC
Such that
2 2
V IL
2
2
IC
E = (V + VR ) + (VX )
2
RS PL + QS X S X S PL RS QS = V + + ( A) V V
Application of Power Electronics in Power Systems B. G. Fernandes
44/454
IS
IC
RS IS
IL
Application of Power Electronics in Power Systems B. G. Fernandes
45/454
RS PL + jX S PL V = V
Independent of QL Not under the control of compensator Passive reactive compensator can not maintain constant V & unity P.F at the same time
Application of Power Electronics in Power Systems B. G. Fernandes
46/454
PL = (RS + jX S ) V
Approximate relationship for voltage regulation Short circuit at the load bus
* S SC = PSC + jQ SC = EI SC
E2 = * Z SC
E2 = cos SC S SC
E2 = sin SC S SC
47/454
E VX V VR
Assume
E 1 V
V QL = V S SC
E V QL = V S SC
V
Slope = -E/SSC V
QL E = V 1 + S SC
QL V = E 1 + S SC
1
QL E 1 S SC
Application of Power Electronics in Power Systems B. G. Fernandes
QL
49/454
Load balancing
Assume all loads are fully compensated for reactive VA
V ab = V L 0 , V bc = V L 120 , V ca = V L 120
I a = I ab I ca I b = I bc I ab I c = I ca I bc
Vca Vab Vbc
50/454
Vab Vca Ia = R jX
VL 0 V120 VL 0 V30 = = R jX R X
1 1 = VL (cos 30 + j sin 30 ) R X 1 3 j = VL R 2X 2X
Application of Power Electronics in Power Systems B. G. Fernandes
51/454
I b = I c 120
3 1 3 j j 1 = + j 2X R 2X X 2 2
3 1 3 = 2X R 2X
X = 3R
Application of Power Electronics in Power Systems B. G. Fernandes
53/454
Review
Using passive reactive element, it is possible to achieve V = 0 VX has negligible effect on V Determined by VR ( iSRS)
E
VX
V
R
E V
IS
IS X
VX
VR
IL= IS
54/454
VR
Contd..
Using passive reactive element it is not possible to have V=0 & P.F =1 Load balancing All three line currents are balanced if
X = 3R
55/454
Comments
Branch currents of are unbalanced Reactive power is balanced within Reactive power generated by C connected between line b & c = Q is absorbed by L connected between c & a If the load is
ab L
= G + jB
ab L
ab C
ab L
ab L
Compensating susceptance
B = B
57/454
58/454
59/454
Observations
Any linear unbalanced 3- load can be transformed into a equal 3- balanced load Net real power is the same Corresponding elements are purely reactive
R X= 3
May not be possible Most of the loads are non-linear => Harmonics + lagging P.F
P.F cos I V
61/454
VC1VS P= sin X
If = 0 If
IC1
jLIC1 VS VC1
VC1 > VS
IC1 is leading VS
Application of Power Electronics in Power Systems B. G. Fernandes
62/454
VC 1 < V S
Ic1 is lagging
VS VC1 Q = VS I C1 VS L
VC1mVdc
Application of Power Electronics in Power Systems B. G. Fernandes
63/454
IC1
VS
j L IC
VS
jLIC
1
64/454
M => Magnitude of sine wave (not very popular) Magnitude of space vector T1 & T2 are to be determined
sin(60 ) .Tc T1 = m sin 60 sin T2 = TC m sin 60
65/454
Vary Vdc Var supplied Vdc Var generated is controlled by varying VC1 & iC1 O/P voltage of inverter Indirect current controller Synchronous link converter Var compensator (SLCVC) or STATCOM
Application of Power Electronics in Power Systems B. G. Fernandes
66/454
Review
Linear lagging load can be balanced using passive elements Difficult to realize in real life Use V.S.I to supply Q
YLbc
bc BC ca BC
YLca
ab BC
YLab
67/454
Contd..
Similar to over-excited Syn. motor on No-load Draws only small P is very small In V.S.I =
VC1 VS E V
Contd..
If space vector PWM is used at the Z.C instant of supply voltage, VS* should lag by angle In sinusoidal PWM technique, fundamental component of VC1 is in phase with modulating wave
Application of Power Electronics in Power Systems B. G. Fernandes
69/454
70/454
(n-1) harmonics are eliminated & magnitude of fundamental can be controlled 4 switchings /(1/4) cycle
3 significant harmonics = 0 Fundamental can be controlled Square wave has quarter wave odd symmetry Coefficient of the fundamental & harmonic components are given by
4 bn = n
m k 1 + 2 ( 1) cos(n k ) k =1
72/454
Assume that there are 5 switchings / (1/4) cycle 4 harmonics can be made zero In 3 phase, 3 wire system, triple harmonics can be ignored So harmonics to be eliminated are 5th, 7th, 11th and 13th
b1 =
4 b5 = {1-2cos51+2cos5 2 -2cos5 3 +2cos5 4 5 -2cos5 5 } = 0 4 b7 = {1-2cos71+2cos7 2 -2cos7 3 7 +2cos7 4 -2cos7 5 } = 0 4 b11 = {1-2cos111+2cos11 2 ........................ 11 -2cos11 5 } = 0 4 b13 = {1-2cos131+2cos13 2 ........................ 13 -2cos13 5 } = 0
Application of Power Electronics in Power Systems B. G. Fernandes
74/454
Non-linear transcendental equations Solve numerically Choose required value for b1 Fundamental component
1 = 10.514, 2 = 23.228, 3 = 29.289, 4 = 46.421, 5 = 50.157 b1 = 0.986 p.u.
Var supplied Vdc Var generated is controlled by varying VC1 or iC1 O/P voltage of inverter Indirect current controller Synchronous link converter Var compensator (SLCVC) or STATCOM
Application of Power Electronics in Power Systems B. G. Fernandes
76/454
= I P cos t + I q sin t
Multiply by cost
Iq IP = (1 cos 2t ) + sin 2t 2 2
Application of Power Electronics in Power Systems B. G. Fernandes
77/454
Use a low pass filter IP/2 average Remaining Reactive power Limitations: Response time is poor min. one cycle
78/454
79/454
iC = iPC + iqL
iqL obtained from Var calculator iPC Accounts for loss
Control strategy -I
81/454
To iC close S4 & S3 , To iC open S4 & S3 Response is fast Switching frequency varies Var calculator is required
Application of Power Electronics in Power Systems B. G. Fernandes
82/454
Review
In harmonic elimination technique, if there are n switchings / () cycle, (n-1) harmonics can be eliminated & fundamental can be controlled
If F of pre-dominant harmonic is > 2kHz at 50Hz, up to 40th harmonic should be absent 5, 7, 11, 13, 17, 19, 23, 25, 29, 31, 35, 37 12 harmonics should be eliminated
Application of Power Electronics in Power Systems B. G. Fernandes
83/454
Contd..
13 switchings / ( ) cycle 13 non linear transdential equations to be solved H. S. Patel & R. G. Hoft Generalized technique of harmonic elimination and voltage control in thyristor inverters, Part-1 harmonic elimination., IEEE Trans. Ind. Applicat., vol. IA-9, pp 310-317, May 1973.
Application of Power Electronics in Power Systems B. G. Fernandes
84/454
Contd..
Controlled current SLCVC
Compensator current iC = iPC + iqL sinusoidal if load is linear If iqL has the information about the non-linear, iC is non - sinusoidal
Application of Power Electronics in Power Systems B. G. Fernandes
85/454
86/454
iS* is in phase with vS iS is also in phase with vS VdC is held constant All the active power is supplied by the source Rest (Q + Harmonic I) supplied by inverter
iS = iL + iC
To iS, iC To iS, iC
If Inverter iS* is changed in between the cycle Source I will have a DC component Smaller size C may be sufficient
89/454
Current control is suitable for low power For high power loads switching F Inverter Voltage control Harmonic spectrum is inferior Load current has harmonics In addition inverter with voltage control also generates harmonics
Application of Power Electronics in Power Systems B. G. Fernandes
90/454
Use two compensators & connect them in parallel Var generator High power inverter High V & high I Harmonic filter Low power inverter Switching frequency is high Since low power, use current controlled PWM technique
Application of Power Electronics in Power Systems B. G. Fernandes
91/454
92/454
Main compensator Voltage control mode Aux. compensator controlled current mode Generate iref ref. I of suitable magnitude & in phase with source V Force iS = iCm + iCx + iL to follow the reference within a hysterisis band Error decides the switching instant of aux. compensator devices
Application of Power Electronics in Power Systems B. G. Fernandes
93/454
To iS, iCx close S4 & S3 To iS, iCx open S4 & S3 Now iref = iL(p) + iCm(p)
Where iL(p) = Real component of load I iCm(p) = Real component of the main compensator current
Application of Power Electronics in Power Systems B. G. Fernandes
94/454
VS VCm1 iCm1 = Z
95/454
96/454
97/454
Review
For low power
Var generator + Active filter
98/454
Contd..
For high power application
Use high power inverter for Var generation To compensate harmonics use active filter
Used Var calculator to determine Q required by the load Linear load is assumed
Application of Power Electronics in Power Systems B. G. Fernandes
99/454
[v] = [z] [i] [v'] = [z'] [i'] [v] = [A] [v'] [i] = [A] [i'] [v] = [z] [i]
Application of Power Electronics in Power Systems B. G. Fernandes
100/454
[A] [v'] = [z] [A] [i'] [v'] = [A]-1 [z] [A] [i] Z' Inverse should exist p = i1v1 + i2v2 + i3v3 = [i]t [v] p' = i1'v1' + i2'v2' + i3'v3' = [i']t [v']
Application of Power Electronics in Power Systems B. G. Fernandes
101/454
p = p' [it][v] = { [A] [i'] }t [A] [v'] = [i']t [A]t [A] [v']
[U] Unit matrix
102/454
ib
i
ia iC
103/454
i K d i = 0 i0 K 0
( 1 2) K d ( 3 2) K q K0
(1 2) K d ia i ( 3 2) K q b ic K0
[C]
2 3 Kd 1 [C ] = 1 3K d 1 3K d 0 1 1 3K q 3K q 1 3 K0 1 3 K0 1 3 K0
104/454
Kd [C ]t = (1 2) K d (1 2) K d
0 ( 3 2) K q ( 3 2) K q
K0 K0 K0
105/454
1 2 1 2 ia 1 i i i = 2 0 3 2 3 2 b 3 1 2 1 2 1 2 ic i0
Similarly 3-ph AC voltages two phase voltages
1 2 1 2 va e 1 e = 2 0 v 3 2 3 2 b 3 e0 1 2 1 2 1 2 vc
Application of Power Electronics in Power Systems B. G. Fernandes
106/454
0 1 va 1 v = 1 2 3 2 1 b vc 1 2 3 2 1
p = vaia+ vbib + vcic
2 e 2 e 2 0
p = ei+{ (-1/2 e+3/2 e) (-1/2 i+ 3/2 i) } + { (-1/2 e-3/2e) (-1/2i-3/2i) } p = 3/2 (ei+ei) = 3 2 e .i + e .i
Application of Power Electronics in Power Systems B. G. Fernandes
)
107/454
108/454
e = VS cos e = VS sin
i e
iS i
VS e
i = iS cos ( + ) i = iS sin ( + )
Can be concluded that 3/2 iS sin component of current iS can be eliminated without effecting P
Reactive power
q = 3 2 VS iS sin
= 3 2 VS iS sin ( + ) = 3 2 VS iS {sin ( + ) cos cos ( + ) sin } = 3 2 {VS cos .iS sin ( + ) VS sin .iS cos ( + )} = 3 2 {e i e i } = 3 2 e i + e i
110/454
In matrix form
p 3 e e i q = 2 e e i 2 e e 1 p i i = e e q 3
2 1 e = * 2 2 3 e + e e
e p e q
111/454
i C 2 1 e i = . 2 2 3 e + e e C
e 0 e q
112/454
i C =
*
3 2 e + e
2
e .q
2
i C
e .q = 2 2 3 2 e + e
3 Where q = [e i e i ] 2
Application of Power Electronics in Power Systems B. G. Fernandes
113/454
114/454
Frequency of e, i, e & i is same as supply frequency p & q are calculated based on instantaneous values Assume supply voltages & currents are nonsinusoidal and have few common harmonic components
Application of Power Electronics in Power Systems B. G. Fernandes
115/454
Avg. power due to these common harmonic components is finite We can not eliminate these frequency components from source i ! Source i is non-sinusoidal
116/454
Review
Instantaneous real power
i e iS VS
Contd..
q = 3 2 VS iS sin
= 3 2 e i + e i
If v is sinusoidal, iL is non-sinusoidal
If q=0, then iS will be sinusoidal and in phase with Vs ( since average of the product of fundamental & higher term = 0)
pn = v sin t in sin nt
n=2
Avg. of pn = 0
Application of Power Electronics in Power Systems B. G. Fernandes
118/454
Contd..
119/454
Contd..
If v is non-sinusoidal & iL is also non-sinusoidal iS will have component corresponding to common frequency term of voltage & current
H. Akagi, Y. Kanzawa, and A. Nabae Instantaneous Reactive Power Compensators Comprising Switching Devices without Energy Storage Components, Part-1 harmonic elimination., IEEE Trans. Ind. Applicat., vol. IA-20, No. 3,pp 625630, May 1984.
Application of Power Electronics in Power Systems B. G. Fernandes
120/454
121/454
d r cos S q = 2 sin S r 3 0 1 2
122/454
Let us assume that vS is along dr- axis in the syn. Rotating frame & iS is making an angle
3 P = VS I S cos 2 qr
qS iS
S
= 3 2 VS r I d r
3 and q = VS r I qr 2
vS
S dr dS
123/454
Transform all the variables to Syn. rotating frame (rotating at S) Fundamental component of v & i will become dc Other components will pulsates Use a filter to eliminate these pulsating component (Could have used a filter to eliminate harmonics from input signal)
124/454
126/454
Information about system frequency is required Frequency varies over a narrow range Should be insensitive to harmonics or multiple zero crossings
127/454
Harmonic Oscillator
. x 0 x Has Eigen values at S = j = . - 0 y If x(0) = 0 and y(0) =1 y
x(t ) = sint
& x = y
y (t ) = cos t
& y = x
128/454
x(t )
x n +1 x n = y t
y n +1 y n = x t
xn +1 = xn + yt
y (t )
y n +1 = y n x t
Application of Power Electronics in Power Systems B. G. Fernandes
129/454
x = sin t
va = Cost = y
y = cos t
3 x 2 3 x 2
1 1 3 e = ea eb ec = ea 2 2 2
3 3 e = eb ec 2 2
es = e + je
Space vector representation of va, vb and vc
2 j 3 2 j 3
vs = va + vb e
+ vc e
131/454
3 3 = cost + j sint = v + jv 2 2
132/454
ed = es cos( t )
= es {cos cost + sinsint}
ed = e cos t + e sin t
eq = es sin( t )
= es {sin cost cos sint}
eq = e cos t e sin t
Application of Power Electronics in Power Systems B. G. Fernandes
133/454
Objective
To make the phase and frequency of va, vb ,vc and ea, eb ,ec same vs and es are in phase eq=0
va = y
1 3 vb = y + x 2 2
1 3 vc = y x 2 2
134/454
Review
In synchronous rotating frame (speed of the frame = s ), supply frequency terms will become DC If input v are unbalanced
+ve sequence terms DC
Contd..
Other higher frequency terms in the synchronous reference frame can be filtered out They can also be filtered out in the input side Phase shift is introduced not an issue Active filter control
136/454
Frequency information is required. C. Schauder and H. Mehta, Vector analysis and control advanced static Var compensators IEE proc, vol.140, pp. 299-306, 1993
Application of Power Electronics in Power Systems B. G. Fernandes
137/454
Through Hardware
Digitize the sine wave and store in EPROM (1024 part) Address the EPROM using 10 bit counter 210 = 1024 ) ( Use a PLL as a multiplier
Application of Power Electronics in Power Systems B. G. Fernandes
138/454
139/454
Software approach
Harmonic oscillator
. x = 0 x . - 0 y y
Instantaneous frequency
140/454
3 sinusoids which are in phase with supply fundamental component of the supply voltage are required Input voltage may have harmonics ea, eb ,ec input system voltages may have harmonics + may be unbalanced
es = e + je
Application of Power Electronics in Power Systems B. G. Fernandes
141/454
eS
St
vS
va = y
1 3 vb = y + x 2 2
1 3 vc = y x 2 2
142/454
This voltage waveform can be used as reference current waveform in hystersis current control PWM technique Source current follows this reference i Source current is in phase with fundamental component of input voltage
143/454
Basic Analysis : Switching frequency is much higher than supply frequency Let x(t) be an input to a switch operating at variable ON and OFF times
Application of Power Electronics in Power Systems B. G. Fernandes
144/454
TON
1 y (t ) = Ts
T ON
x ( t ) dt
= x(t) D(t)
D= duty cycle
Application of Power Electronics in Power Systems B. G. Fernandes
145/454
Duty ratio has to be generated as control input based on some reference signal Vref(t) If the duty ratio is controlled so that
TON
x (t )dt = V
0 0
TS
ref
( t ) dt
Average output
1 y (t ) = Vref (t )dt Ts 0
146/454
Ts
Assume that over one cycle Vref(t) is roughly constant y(t)=Vref(t) Works for constant switching frequency Vref could be a variable feedback signal Can be implemented using a simple integrator with reset
Application of Power Electronics in Power Systems B. G. Fernandes
147/454
Generate reset pulse at required frequency At the start of every cycle switch is turned ON by the reset pulse Integrate the input When the output of the integrator just exceeds Vref turn OFF the switch Start the cycle again after Ts when integrator resets
Application of Power Electronics in Power Systems B. G. Fernandes
148/454
Rule to be followed
A term in the control equation which is being multiplied with duty cycle of the switch has to be passed through a reset integrator and compared with the appropriate reference
149/454
150/454
di L = V s + V DC dt
S1, S2 ON for (1-D)TS:
di L = V s V DC dt
151/454
Vs VDC = 1 2D
Application of Power Electronics in Power Systems B. G. Fernandes
152/454
Aim
is and Vs should be in phase Vs= isRe (Re = Emulated resistance) ..(a) (1-2D)Vdc = isRe
is = (1-2D)Vdc/Re (b)
In each switching cycle if the duty ratio D is controlled in such a way that equation (b) is satisfied , equation (a) also gets satisfied
Review
One cycle control
No PLL No ZCD
Rule to be followed:
A term in the control equation which is being multiplied with duty cycle of the switch has to be passed through a reset integrator and compared with the appropriate reference
Application of Power Electronics in Power Systems B. G. Fernandes
154/454
Contd..
Generate reset pulse at required frequency At the start of every cycle switch is turned ON by the reset pulse Integrate the input When the output of the integrator just exceeds Vref turn OFF the switch
Application of Power Electronics in Power Systems B. G. Fernandes
155/454
Start the cycle again after Ts when integrator resets K. M. Smedley & C. Qiao, Unified constantfrequency integration control of active power filters steady state and dynamics IEEE Transaction on power electronics, vol. 16, No. 3, May 2001
156/454
1 AC-DC
Control technique
(1 2 D)Vm = is
Vm Vc = Re
Emulated resistance
157/454
1 Vm Vmdt = is Ti 0 Vm DTs = is Vm Ti
Ti = Integrator time constant Fs = 1/TS = Switching frequency
DTs
(1 2 D )Vm = is
158/454
= Vc (1 2 D)
159/454
Buck Converter
L is small
V c + i L = V s
Information regarding Vs should be known Assume that Vs and is are in phase (required) Instead of varying D as function of Vs Vary D as a function of is If Vs and is are not in phase chosen values of D may not give the desired Vo If Vo is regulated, our assumption that Vs and is are in phase is valid
Application of Power Electronics in Power Systems B. G. Fernandes
161/454
162/454
163/454
DC link voltage has to be regulated Generate fixed frequency clock At the rising edge reset the integrator and turn ON the switches S4 and S3 is As t X When is = X ; R = 1 Turn OFF the S4, S3 and Turn ON S1, S2
Application of Power Electronics in Power Systems B. G. Fernandes
164/454
165/454
2 converters
166/454
Number of pulse should be high for superior harmonic spectrum Instead modify the Inverter structure More than two levels Multi-level inverter
167/454
3 Level Inverter:
VAX Vdc
Vdc 2
170/454
171/454
4 level Inverter
Number of switches ON = 3 = (n-1) Number of switches/leg = 6 = 2(n-1) Number of capacitors = 3 = (n-1) Voltage across each capacitor = Vdc/3 = Vdc/(n-1)
Application of Power Electronics in Power Systems B. G. Fernandes
172/454
Review
In one cycle control iS is compared with (1-2D)Vm Vm is passed through reset integrator & compared with Vm - RSiS
RS is sensing resistor
Contd..
For high power Use multi-level inverter For 3-level VAX = VdC, VdC, 0
Application of Power Electronics in Power Systems B. G. Fernandes
174/454
Contd..
At any time 2-devices (n-1) devices are ON No. of Switches = 2(n-1) V across each C = VdC / 2 = VdC /(n-1) V rating of switch = VdC /2 = VdC /(n-1) V rating of diode = VdC /2 No. of diodes = 2 = (m-1)*(m-2)
Application of Power Electronics in Power Systems B. G. Fernandes
175/454
References
Bum-Seok Suh and Dong-Seok Hyun A New NLevel High Voltage Inversion System, IEEE Trans. Ind. Electron., vol. 44, No. 1,pp 107-115, Feb 1997. Nam S. Choi, Jung G. Cho and Gyu H. Cho A General Circuit Topology of Multilevel Inverter, in Proc. IEEE Power electron specialist conf. Rec., pp 96103, 1991.
176/454
4-level inverter
Observations:
Duty cycle of switch is not the same Lower switches are ON for longer time Switch utilization is poor
Application of Power Electronics in Power Systems B. G. Fernandes
180/454
181/454
182/454
Vds 1 V = qs 0
184/454
VdC 0
VdC
VdC / 3
CBA
OPP POP PPO
CBA
OOP OPO POO
186/454
CBA
OON ONO NOO
CBA
ONN NON NNO
187/454
CBAOPP
VAO = VBO = VdC/2, VCO = 0 Van = VdC /6, Vbn = VdC /6, Vcn = - VdC /3
VdC VS = / 3 2
VdC POO VS = 4 / 3 2
POO
189/454
VdC ONN VS = 4 / 3 2
190/454
OOP :
VAO = VdC /2, Van = VdC /3, VBO = VCO = 0 Vbn = Vcn = -VdC /6
VdC , Vds = 2
VdC VS = 0 2
Vqs = 0
PPO OON
OOP NNO
VdC PPO VS = 2
191/454
NNO :
VAO = 0, VBO = VCO = -VdC / 2
Van = 1/3[0 +Vdc /2 + Vdc /2] = VdC /3, Vbn = Vcn = 1/3[-2VdC / 2 + VdC / 2] = - VdC/6
VdC OON VS = 2
192/454
OPO :
VAO = VCO = 0, VBO = VdC /2
VdC POP VS = 5 / 3 2
193/454
NON :
VAO = VCO = -VdC /2, VBO = 0 Van = Vcn = -VdC /6, Vbn = VdC/3
OPO NON
POP ONO
VdC ONO VS = 5 / 3 2
194/454
NOP : VAO = VdC /2, Van = VdC /2, VBO = 0 , VCO = -VdC /2 Vbn = 0 , Vcn = -1/2 VdC
NPO : VAO = 0, Van = 0, VBO = VdC /2 , VCO = -VdC /2 Vbn = VdC /2 , Vcn = -VdC /2
PNO : VAO = 0, Van = 0, VBO = -VdC /2 , VCO = VdC /2 Vbn = -VdC /2 , Vcn = VdC /2
Vds = 0,
3 Vqs = VdC 2
3 VS = VdC 3 / 2 2
Application of Power Electronics in Power Systems B. G. Fernandes
198/454
199/454
Review
3-Level Inverter
No. of large voltage vectors = 6 VS = VdC No. of small voltage vectors = 6 VS = 1/2VdC 12 possible combinations
+ ve or ve bus & mid point
200/454
Contd..
No. of medium voltage vectors = 6
+ ve, - ve & mid-point bus VS = 3 2 VdC
201/454
202/454
Voltage control
Space vector PWM Depending upon the position of space
vector, switch the corresponding switch
NPP
OPP NOO
NOP
OOP NNO
NNP
203/454
204/454
205/454
C1 supplies the power C2 does not supply the power V across C2 For remaining 2 configuration, V across C1
Application of Power Electronics in Power Systems B. G. Fernandes
206/454
Load compensation
Passive elements Inverter
Current control Voltage control Main compensator Aux. compensator
Instantaneous reactive power theory One cycle controlled inverter Multi level inverter
Application of Power Electronics in Power Systems B. G. Fernandes
207/454
VS
P > SIL
VR
208/454
Shunt Compensation :
Inject current in to the system If injected I is in phase quadrature with the V Only reactive power transfer Else, it has to handle real P as well
Series Compensation :
Inject voltage in series with the line
Application of Power Electronics in Power Systems B. G. Fernandes
209/454
If Vs = Vr = V
Pmax V2 = X
211/454
System is loss-less
Application of Power Electronics in Power Systems B. G. Fernandes
212/454
213/454
Let Vsm & Vmr are fictitious voltages in phase with Ism & Imr respectively
Vsm = Vmr = V .Cos ( / 4 )
I sm = I mr 2V .Sin ( / 4 ) 4V = = Sin ( / 4 ) X 2 X
Pr = P = Vsm .I sm
4V 2 = Sin ( / 4 ).Cos ( / 4 ) X
2V 2 = Sin( / 2 ) X
214/454
= 2.V .I sm Sin( / 4 )
8V 2 = Sin 2 ( / 4 ) X
4V 2 (1 Cos( / 2)) = X
215/454
216/454
Can have multiple compensators located at the equal distances Theoretically P would double for each doubling of the segments
217/454
Expensive
Application of Power Electronics in Power Systems B. G. Fernandes
218/454
Review
Mid-point shunt compensation
If Vs = Vr = V
2V 2 P= Sin( / 2 ) X
4V 2 (1 Cos( / 2)) Q= X
Contd..
For each doubling of the segments, transmittable P also doubles V profile is almost flat Large no. of shunt compensators expensive
220/454
Summary
Compensator must remain in synchronism with the ac system under all operating conditions including major disturbances Must regulate the bus voltage For the inter connecting two systems, best location is in middle For radial feed to a load, best location is at the load end
Application of Power Electronics in Power Systems B. G. Fernandes
221/454
223/454
i flows from to
di L = Vm Sint dt i (t ) = Vm (Cos Cost ) L
i(t) =0 at t =
Cos = Cos
= 2
= extinction angle
224/454
i is continuous when = /2 i is sinusoidal No control L is fixed & it is minimum As , all odd harmonics are introduced
225/454
As , L
I LF ( ) =
BL ( ) =
V 2 1 1 sin 2 L
1 2 1 1 sin 2 L
VL(MAX) Voltage limit IL(MAX) current limit BL(MAX) Max. admittance of TCR
Application of Power Electronics in Power Systems B. G. Fernandes
226/454
228/454
iL = iL(max) when = /2
In FC-TCR, for any value of iL, net effect of C C also provides a low impedance path for harmonics generated by TCR
Application of Power Electronics in Power Systems B. G. Fernandes
229/454
230/454
231/454
STATCOM
VSI can supply Q Also known as static synchronous condenser Similar to syn. motor
V E I= X
V E Q= .V X
Control
Q is controlled by M.I & accounts for losses Assumed that inverter is capable of injecting Q demand of the line
233/454
If Q demand >Var rating of inverter It may fail due to over load Have a inner I loop
234/454
235/454
Review
T.C.R
If = /2 i = imax As , Leff Harmonics
236/454
Contd..
T.S.C
Thyristors are triggered when vc = v
F.C.T.C.R
T.S.C T.C.R scheme is also possible
Application of Power Electronics in Power Systems B. G. Fernandes
237/454
Contd..
Above schemes are variable impedance types
STATCOM
Variable source type
V E I= X
V E Q= .V X
Application of Power Electronics in Power Systems B. G. Fernandes
238/454
Advantages
Since voltage profile is maintained (in radial system) Voltage instability is prevented Improves transient stability Damping of power oscillations Able to maintain V profile
Application of Power Electronics in Power Systems B. G. Fernandes
239/454
Series compensation
Reciprocal of shunt compensation Shunt compensator : Controlled reactive I source connected in parallel with the Tr. Line to control V Series compensator : Controlled reactive V source connected in series with the Tr. Line to control I
Application of Power Electronics in Power Systems B. G. Fernandes
240/454
Series compensation
Injects voltage in series with the line Could be variable Z (such as C or L) Voltage source Effective in controlling the power flow
241/454
X = (X L X C )
242/454
X eff = ( X L X C )
= (1 K )X L
K = X C X L Degree of series
compensation 0<K<1
Application of Power Electronics in Power Systems B. G. Fernandes
243/454
If VS = VR =V
V .Sin 2 2V .Sin 2 I= = (1 K )X L 2 (1 K )X L
2V .Sin 2 P = Vm I = (VCos 2 ). (1 K )X L
V 2 .Sin = (1 K )X L
max maximum angular difference between the two ends of the line
Application of Power Electronics in Power Systems B. G. Fernandes
245/454
If max 30 - 40o Qse = 7- 13% of QSL Cost of series capacitor ? Location of series capacitor is not very critical
Application of Power Electronics in Power Systems B. G. Fernandes
246/454
GTO is closed when vc = 0 Open when i charges C Duality between TCR & GCSC
Application of Power Electronics in Power Systems B. G. Fernandes
247/454
i (t ) = I .Cost
v (t ).Sint.d (t )
c 0
0
2 Sin 2 = IX c 1
249/454
Controlling modes
(a). Voltage compensation mode:
GCSC Should maintain rated compensation voltage when Imin < I < Imax
Vcomp = Vrated = Imin Xc As I, So that Vcomp is maintained constant
Application of Power Electronics in Power Systems B. G. Fernandes
250/454
Vc (max) I max
= Xc
Protection issues:
Required to have higher short time rating During S.C, I could be much higher than Irated Ifault > IGTO(rating)
Application of Power Electronics in Power Systems B. G. Fernandes
251/454
Limitations:
Harmonics are generated
252/454
Review
GTO controlled series capacitor (GCSC)
is measured w.r.t peak of i
1 2 1 X C ( ) = 1 Sin 2 C
extinction angle
VC has harmonics
Application of Power Electronics in Power Systems B. G. Fernandes
253/454
Contd..
TCR GCSC
Switch is series with L Switch is parallel with C Supplied from a V source Supplied from a i source
(turn-ON delay) is (turn-OFF delay) is measured w.r.t peak of v measured w.r.t peak of i
Application of Power Electronics in Power Systems B. G. Fernandes
254/454
Contd..
Control v across C Control i in L . developed by i source Parallel with the source representing variable representing variable admittance to the source reactance to the source
V 2 Sin 2 I LF ( ) = 1 L
BL ( ) = 1 2 1 1 sin 2 L
I 2 Sin 2 VCF ( ) = 1 C
1 2 Sin2 X C ( ) = 1 C
255/454
Capacitors are disconnected by turning ON the thyristors They turn OFF naturally (at Z.C of I )
Application of Power Electronics in Power Systems B. G. Fernandes
256/454
By-pass C
257/454
at rated I
258/454
259/454
If V is the applied voltage across the TCR Fundamental component of I for (measured w.r.t peak of voltage) is
Application of Power Electronics in Power Systems B. G. Fernandes
260/454
I1 ( ) =
V XL
1 2 1 Sin 2
X L ( ) = X L 2 Sin 2
X L < X L ( ) <
Combined Z of TCR & fixed C
X TCSC
X C . X L ( ) = X ( ) X C L
261/454
At XL() = XL X TCSC
262/454
263/454
L < X L ( ) <
When X L ( ) < , X TCSC = X C = 1 C
At XL() = XC parallel resonance, X TCSC
= 1 LC
C (lim) 2
Capacitive, i leads VC
In TCSC, the V is voltage across C Switch is open TCR is O.C, i flows through C Turn-on TCR at (w.r.t peak of v) i is +ve & vc is -ve
266/454
iTCR
jX C I = .I = (1 X TCR X C ) j ( X TCR X C )
268/454
I TCR 1 = = 2 I 1 1.5
X TCR = 0.75 X C
Application of Power Electronics in Power Systems B. G. Fernandes
269/454
X TCSC 1 = = 3 1 1 0.75 XC
I TCR 1 = =4 I 1 0.75
270/454
Modes of operation
By pass mode :
iL is continuous & sinusoidal Each thyristor conducts for 180o XTCSC inductive Most of the line I flow through L not C Used to protect C against over voltage
Application of Power Electronics in Power Systems B. G. Fernandes
271/454
Vernier control
Thyristors are gated and they conducts for part of cycle XTCSC as conduction angle from zero to C(lim)
Application of Power Electronics in Power Systems B. G. Fernandes
272/454
VSVR Sin P= (X L X C )
Application of Power Electronics in Power Systems B. G. Fernandes
273/454
Vq = j.Vq ( )
Application of Power Electronics in Power Systems B. G. Fernandes
274/454
P = VCos( 2).(2VSin( 2) + Vq )
V .Vq V2 = Sin + Cos ( 2 ) X X
Review
T.C.S.C :
Used for vernier control of C. GCSC also provides this feature Cost of GTO > that of thyristor Effective capacitive compensation increases as from /2 to C(lim)
Application of Power Electronics in Power Systems B. G. Fernandes
276/454
Contd..
For both region XL < XC (inductive & capacitive) In inductive zone, ITCR > ILine and are in phase In capacitive zone, ILine is out of phase with ITCR V across C gets distorted
277/454
Contd..
Static Synchronous Series Compensation:
Control range:
Voltage compensation mode : SSSC can maintain the rated capacitive or inductive compensating V for I till Iq(max) Ideal condition (I line can not be zero) P is required for SSSC
Application of Power Electronics in Power Systems B. G. Fernandes
279/454
Compensation for both reactive and resistive compensation of series line impedance to keep X/R ratio high (3-10 is desirable)
281/454
X/R ratio in case1 > X/R ratio in case2 Reactive component of I q = I .Sin( 2 + 1 ) Real component of I = I a = I .Cos( 2 + 1 ) transmitted to the receiving end decreases corresponding to R=0
282/454
If VS = VR =V
Per phase power received by the receiving end
P = V .I .Cos (90 + 2 )
= V .I .Sin( 2 )
2VSin / 2 =V. .Sin( 2 ) Z
2V 2 = .Sin / 2{Cos / 2.Sin Cos .Sin / 2} Z
Application of Power Electronics in Power Systems B. G. Fernandes
283/454
Q = VI .Sin(90 + / 2 )
2V 2 Sin / 2 = Cos ( / 2 ) Z
V2 {R.Sin + X (1 Cos )} = 2 2 R +X
285/454
Occur when ?
Power between two buses is transmitted over parallel lines of different length, use phase angle regulator (PAR)
Application of Power Electronics in Power Systems B. G. Fernandes
289/454
PAR : A sinusoidal synchronous ac voltage source with controllable amplitude and phase angle
VSeff = VS + Vr and VS = VSeff
Application of Power Electronics in Power Systems B. G. Fernandes
290/454
Basic idea is to keep the transmittable power at the desirable level independent of prevailing
also
Vr > 90o VS
angle to be controlled is (- )
V2 P= Sin( ) X
Application of Power Electronics in Power Systems B. G. Fernandes
291/454
Multi functional FACTS controller : based on back-back VSI with a common DC-link One converter in series (SSSC) and other is in shunt (SVC) unified power flow controller (UPFC) Both converters are connected in series but in two different lines (Inter line Power Flow Controller-IPFC)
Application of Power Electronics in Power Systems B. G. Fernandes
292/454
UPFC :
Able to control simultaneously or selectively all the parameters affecting the power flow in Tr. line
293/454
296/454
Control capabilities
Case1 : Voltage regulator
= 0, V pq = V
Similar to tap changing transformer with large no. of steps
compensator
V pq = V
at any angular relationship w.r.t VS so that desired phase shift is achieved
V pq = V + Vq + V
Application of Power Electronics in Power Systems B. G. Fernandes
298/454
Review
U.P.F.C :
Two VSI connected back to back with common DC-link One connected in series with line and other is connected across the line DC-link V is maintained constant by converter-1
Application of Power Electronics in Power Systems B. G. Fernandes
299/454
Contd..
Active power required by the system is drawn by converter-1
Can function as
Voltage regulator V+V SSSC injects V in quadrature with I Phase angle regulator injects V in quadrature with V
Application of Power Electronics in Power Systems B. G. Fernandes
300/454
Using UPFC
Active power flow and Reactive power flow can be set In SSSC : Quadrature injected V results in increase in power flow
Magnitude of injected V determines P Circuit conditions determines Q
Application of Power Electronics in Power Systems B. G. Fernandes
301/454
Main function : Control the flow of P & Q by injecting a voltage in series with the Tr. line Both magnitude & phase angle are varied Control of P & Q allows power flow in prescribed routes
2 port representation
Application of Power Electronics in Power Systems B. G. Fernandes
302/454
Re V I + Vu 2 I Ploss = 0
* u1 1
* 2
In addition to maintain real power balance, shunt branch can independently exchange reactive power with the system
Application of Power Electronics in Power Systems B. G. Fernandes
303/454
VS = Ve
j 2
Vr = Ve
j ( 2 + )
j 2
V pq = V pq e
304/454
= Ve
j 2
2+ )
= Ve
j 2
2VSin 2 V pq j ( e X jX
305/454
V .V pq V2 Pr = Sin Sin( + ) X X
V .V pq 2V 2 2 Qr = Cos ( + ) Sin 2 X X
Application of Power Electronics in Power Systems B. G. Fernandes
306/454
to
P ( ) +
V .V pq X
V .V pq (max ) V2 Sin = X X
307/454
Control strategy:
There are 3 degrees of freedom Magnitude and angle of series V Shunt reactive current
Reactive V injection similar to series connection of reactance except that injected V is independent of Tr. Line I
Magnitude of real component DC link V Magnitude of reactive component Bus V magnitude regulator
Application of Power Electronics in Power Systems B. G. Fernandes
310/454
TCSC
420 kV 79.87 MVar 16.6 kV 4.4 mH
312/454
HVDC
Long distance transmission ( Competing technology : AC with FACTS)
Cable transmission (> 40 Km) HVDC Asynchronous link HVDC
HVDC lines are cheaper than AC lines Terminal equipment costs are higher
Application of Power Electronics in Power Systems B. G. Fernandes
313/454
In India :
Long distance HVDC Rihand Dadri : 1500 MW, 500 kV Chandrapur Padghe : 1500MW, 500 kV Talcher Kolar : 2000MW, 500 kV Barsur Lower Sileru : 200MW, 200 kV
Application of Power Electronics in Power Systems B. G. Fernandes
314/454
Back to Back :
Chandrapur Ramagundam : 1000 MW (Asynchronous link) Jeypore Gajuwaka : 500 MW (Asynchronous link) Vindhyachal
: 500 MW
Sasaram : 500 MW
Application of Power Electronics in Power Systems B. G. Fernandes
315/454
P through DC link can be regulated. Power control through firing angle control
Application of Power Electronics in Power Systems B. G. Fernandes
316/454
317/454
P1 + P2 can be regulated
If alternator-2 generates 1000 MW & load 900 MW P1 +P2 has to be -100 MW (frequency of alternator-1 &2 are same)
P1 + P2 can be set
Application of Power Electronics in Power Systems B. G. Fernandes
319/454
Back to Back :
Two terminals with no DC line used for asynchronous link
321/454
Types of links :
Mono-polar Bi-polar
322/454
323/454
+ve -ve
324/454
Each terminal has two converters of equal rating V connected in series on the DC side Junction is grounded I in two phases are equal No ground I Two poles can operate independently If one is faulty, then other can operate with ground as the return
Application of Power Electronics in Power Systems B. G. Fernandes
325/454
Review HVDC
Asynchronous link Back to back
326/454
Bi-polar HVDC
327/454
Converter :
Perform
AC DC conversion DC AC conversion
12 pulse converter
328/454
Purpose :
harmonic voltage & current in DC line Prevents I from being discontinuous on light load Limit the I during S. C in the DC line
Application of Power Electronics in Power Systems B. G. Fernandes
329/454
Harmonic filter :
Converter generates harmonic currents Because of source L, V gets distorted Affects the other loads & interference with communication network
Application of Power Electronics in Power Systems B. G. Fernandes
330/454
Vcn = V 240
Vab = 3V 6 , Vbc =
3V 2 , Vca = 3V 210
332/454
2 = 1
Application of Power Electronics in Power Systems B. G. Fernandes
333/454
334/454
335/454
Va = Sin180 = 0,
Vb = Sin60 = 3 2
Vab = 3 2
336/454
At t = 210o
Va = Sin 210 = 1 2
Vb = Sin90 = 1
At t = 240o
Vab = 1.5
Va = 3 2 , Vb = 3 2
Vab = 3
Application of Power Electronics in Power Systems B. G. Fernandes
337/454
At t = 270o
Va = 1,Vb = 1 2
At t = 300o -
Vab = 1.5
Va = 3 2 , Vb = 0
Vab = 3 2
Va = 3 2 , Vc = 3 2
Vac = 3
338/454
At t = 330o
Va = 1 2 , Vc = 1
At t = 360o
Vac = 1.5
Va = 0, Vc = 3 2
At t = 30o
Vac = 3 2
Vac = 0
339/454
Va = 1 2 , Vc = 1 2
At t = 60o -
Va = 3 2 , Vc = 0
Vac = 3 2
340/454
At t = 300o
Va = 3 2 , Vb = 0 Vab = 3 2
At t = 330o
Va = 1 2 , Vb = 1 2
At t = 360o
Vab = 0
Va = 0, Vb = 3 2
Vab = 3 2 = + ve
341/454
= 1.35VLL .Cos
For = 30o
343/454
Review HVDC
Two six pulse converters connected in series
2 = 1
344/454
Contd..
As 1 (AC-DC converter), Q requirement also As 2 , duration for which the devices is reverse biased When = 150o, duration for which the devices
is reverse biased = 30o
Application of Power Electronics in Power Systems B. G. Fernandes
345/454
2 I Ln =
I Cosn .d
0 3
I Ln
2 n = .I 0 2 Sin 3 2n
I L1 =
I L5
.I 0 ,
I L3 = 0
I L7 I L1 = 7
346/454
I L1 , = 5
Cos = Cos =
Application of Power Electronics in Power Systems B. G. Fernandes
347/454
6 V0 = 2
+ 60
ab
.dt
6 = 2
= 3 3
+ 60
VmCos = VdcoCos
3 3
2Vrms Cos
As :
Vdc Displacement angle & P.F
Effect of source L :
i1 + i3 = I 0
di3 di1 = dt dt
di3 Vba = 2 Lc dt
Boundary conditions :
At t = , i1 = I 0 , i2 = I 0 , i3 = 0 = +, i1 = 0, i2 = I 0 , i3 = I 0
3Vm (Cos Cost ) i3 = 2Lc
At t = +, i3 = I 0
3Vm (Cos Cos ( + )) I0 = 2Lc
Application of Power Electronics in Power Systems B. G. Fernandes
351/454
352/454
V0 = V pn Vmn
= Vcn Vcn = 1.5Vcn 2
Reduction in V0 = (V0) :
V0 = 6 2
+
(V
bc
+ 1.5Vcn ).dt
6 = 2
353/454
3Lc
I0
3Lc
V0 = Vdc 0Cos
I0
354/454
Vd = Vdco cos Rc I d
Application of Power Electronics in Power Systems B. G. Fernandes
355/454
Vd = Vdco cos + Rc I d
= Vdco cos( ) + Rc I d
= Vdco cos + Rc I d
delay angle
Angle of advance
356/454
Converter
delay angle overlap angle
Inverter
= - advance angle overlap angle = - extinction angle = -(+)
357/454
Vd = Vdco Vo
Vdco = [cos + cos( + )] 2
Also
Vdco [cos + cos( + )] Vd = 2
= [cos( ) + cos( )]
Application of Power Electronics in Power Systems B. G. Fernandes
358/454
Eq. A+B
2Vd 2Lc 2 cos = + Id Vdco 3Vm
Vd = Vdco cos 3 3
Vm
Lc
3Vm
= Vdco cos
3Lc
Id
= Vdco cos Rc I d
Application of Power Electronics in Power Systems B. G. Fernandes
360/454
12-pulse converter
Series connection of two 6-pulse converters
3- voltages supplied to one bridge is displaced by 30o from those applied to 2nd bridge
361/454
362/454
363/454
Relation between Ac and DC quantity : With multi phase bridge If no. of bridges in series
Id 3
XC
bridge
3 Vd = VdoCos I d .B. X C
3 = VdoCos I d .B. X C
365/454
4*200 MVar
12th harmonic filter 2*120 MVar
Application of Power Electronics in Power Systems B. G. Fernandes
366/454
Power :
Nominal Power 2*750 MW
2*75 MW 2*825 MW 2*1000 MW
367/454
Direct voltage :
Nominal line voltage 500 kV Maximum line voltage 512 kV Minimum line voltage 488 kV
368/454
Direct current :
Nominal I 1500 A Maximum I at nominal load 1542 A Max. I at 2 hour over load Max. I at 5 sec. over load 1695 A 2140 A
Basic control :
DC voltage or I (or power) can be controlled by controlling the internal voltage (Vdcor Cos) and Vdcoi Cos
Gate control or using tap changing of converter transformer Gate control is fast
Application of Power Electronics in Power Systems B. G. Fernandes
371/454
Tap changing : Slow ( 5-6 sec/step) Gate control is used for initial rapid control action
Followed by tap changing to restore the converter quantities ( of rectifier & for inverter) to their normal ranges
372/454
Denominator is very small A small change in Vdcor or Vdcoi cause a large change in Id 25% change either in Vdcor or Vdcoi changes id by 100% If & are kept constant, Idc can vary over a wide range for small change in i/p AC voltage at either end
Application of Power Electronics in Power Systems B. G. Fernandes
375/454
Not acceptable Rapid converter control prevents fluctuation of Idc For a given power transmitted Vdc profile along the line should be close to rated values It minimizes Id & therefore line loss
Application of Power Electronics in Power Systems B. G. Fernandes
376/454
P.F should be as high as possible Minimize losses and current rating of equipment in the AC system Reduce the voltage drop at the AC terminal as load the cost of reactive power supply to line
377/454
So keep the rated power of the converter as high as possible for a given V & I rating of transformer P.F depends on &
min = 5o (a +ve V should appear across the device)
necessary to maintain a certain minimum extinction angle to avoid commutation failure Device should attain forward voltage blocking capability
=
= 15o at 50 Hz depends on Id & i/p V
Application of Power Electronics in Power Systems B. G. Fernandes
379/454
380/454
Power at rectifier terminal, Pdr = Vdc .Id Power at inverter terminal = Vdi .Id = Pdr-id2 RL
381/454
Control characteristics
Ideal characteristics :
Voltage regulation & current regulation
Kept distinct & are assigned to separate terminals
Maintains adequate commutation margin Vdc measured at the rectifier terminals Inverter characteristics includes Id.RL drop
383/454
Rectifier characteristics can be shifted horizontally by adjusting reference current or current command or current order If measured current < current command, controller Inverter characteristics can be raised or lowered by means of transformer taps
Application of Power Electronics in Power Systems B. G. Fernandes
384/454
As taps are changed, CEA regulator quickly restores desired Id changes Current regulator of rectifier changes and control i Tap changer of rectifier acts to bring in the desired range (10-20o)
Application of Power Electronics in Power Systems B. G. Fernandes
385/454
Review
Rectifier firing angle :
Minimum 5o Mini. during normal operation 12.5o Max. during normal operation
17.5o
Basic control :
DC voltage or I (or power) can be controlled by controlling the internal voltage (VdcoCos) and VdcoCos
Gate control or using tap changing of converter transformer Gate control is fast
Application of Power Electronics in Power Systems B. G. Fernandes
387/454
Tap changing : Slow ( 5-6 sec/step) Gate control is used for initial rapid control action
Followed by tap changing to restore the converter quantities ( of rectifier & for inverter) to their normal ranges
388/454
R 10 and L =250 mH Back to back L =1H for long line =20 m.sec roughly
Application of Power Electronics in Power Systems B. G. Fernandes
389/454
390/454
necessary to maintain a certain minimum extinction angle to avoid commutation failure Device should attain forward voltage blocking capability
=
= 15o at 50 Hz depends on Id & i/p V
Application of Power Electronics in Power Systems B. G. Fernandes
392/454
393/454
Control characteristics
Ideal characteristics :
Voltage regulation & current regulation
Kept distinct & are assigned to separate terminals
Quantities forming the co-ordinates are measured at some common point in the DC line Converter terminal can be one such possibility
396/454
Rectifier characteristics can be shifted horizontally by adjusting reference current or current command or current order If measured current < current command, controller Inverter characteristics can be raised or lowered by means of transformer taps
Application of Power Electronics in Power Systems B. G. Fernandes
397/454
As taps are changed, CEA regulator quickly restores desired Id changes Current regulator of rectifier changes and control i Tap changer of rectifier acts to bring in the desired range (10-20o)
Application of Power Electronics in Power Systems B. G. Fernandes
398/454
Constant current characteristics could be a line parallel to y-axis If proportional controller slope could be -ve Generally current control is given to both the converters Ref. current for rectifier > Ref. current for inverter
Application of Power Electronics in Power Systems B. G. Fernandes
399/454
Iref(conv) Iref(inv) = Imargin = +ve Assume that power flows in the line to be conv takes the value of min Incase Id approaches Iref(conv), then
rectifier is working under constant ignition control Inverter is working under constant extinction control
400/454
401/454
Actual characteristics :
Rectifier maintains constant I by changing can not be < min Once min is reached, no further V is possible Rectifier will operate constant ignition angle (CIA)
Application of Power Electronics in Power Systems B. G. Fernandes
402/454
Therefore rectifier characteristics has two segments (AB & FA) Constant current characteristics may not be truly vertical Depends on the current regulator With proportional control C.C characteristics has ve slope
Application of Power Electronics in Power Systems B. G. Fernandes
403/454
VdcoCos = K [I order I d ]
= Vd + Rcr I d
Vd = KI order (K + Rcr )I d
Vd = (K + Rcr )I d
Vd = (K + Rcr ) I d
(with PI it is vertical)
404/454
At reduced V, it does not intersect F1A1B A big reduction in rectifier V would cause Id & P System could shut down
406/454
In order to avoid the problem, inverter is provided with current control Inverter Iord < rectifier Iord
407/454
Under normal condition Rectifier C. C Inverter CEA When i/p V rectifier V Operating point E1 Changes from one mode to another is known as mode shift
Application of Power Electronics in Power Systems B. G. Fernandes
408/454
K (I ord I d ) = Vd RL I d + Rcr I d
409/454
K >1
Vd = (RL Rci + K )I d
Vd = (RL Rci + K )I d I d
Vdor to id Vdoi to id
410/454
Slope is +ve
411/454
Review
Rectifier characteristics
Constant current by control Constant ignition angle control
C.C
Contd..
Current control is given to both converters
But Iref(R) > Iref(I) Iref(R) - Iref(I) = Imargin 0.1Irated
414/454
415/454
416/454
Due to line fault or during low i/p AC voltage condition Vdco(R) will drop Assume Vdco(R)Cosmin < Vdco(I)Cos
If there is no current control by the inverter , id will and eventually becomes zero
Application of Power Electronics in Power Systems B. G. Fernandes
417/454
In order to avoid this situation inverter is also provided with current control Operate at E' till tap changer changes the tap
Inverter side :
Id can be by As , Id, but rectifier controller tries to the current (Iref(R) < Iref(I) ) Since Id is due to increase in , rectifier controller to reduce Id
towards 90o towards 90o
Application of Power Electronics in Power Systems B. G. Fernandes
419/454
New operating point could be D' Correct sign to Imar is very important Imar should not be too small because there could be measurement error
420/454
Mode stabilization :
Intersection of min characteristics of converter and inverter CEA may not be well defined There could be multiple crossings Instead change the slope of the inverter characteristics near the crossing
421/454
423/454
Constant control :
= +
function of id & Vac
Choose for worst case At low loads additional security against commutation failure As id , minimum may be encountered
Application of Power Electronics in Power Systems B. G. Fernandes
424/454
425/454
426/454
Current limit
Maximum current limit : Max. short term current = (1.2 -1.3) Irated Minimum current limit : if id below a certain limit due to finite ripple in I, current will become discontinuous
12-pulse converter 12 times in one cycle current become zero (current interruption)
Application of Power Electronics in Power Systems B. G. Fernandes
427/454
There could be lightly damped oscillations (smoothing L & line C) Over voltage across the device Simulation study is required Ensure Imin in DC link
428/454
VdcoCos
Application of Power Electronics in Power Systems B. G. Fernandes
429/454
To maintain the current, voltage at the other end of the line is adjusted Either or Reactive power demand Vac has , Q supplied by C or filter also Above problems can be addressed using voltage dependent current order limit
Application of Power Electronics in Power Systems B. G. Fernandes
430/454
431/454
Review
Rectifier characteristics
Constant current by control Constant ignition angle control
Inverter Constant extinction angle control Current control is given to both converters
Application of Power Electronics in Power Systems B. G. Fernandes
432/454
Contd..
But Iref(R) > Iref(I) Iref(R) - Iref(I) = Imargin 0.1Irated
433/454
Contd..
Imar should +ve :
If Imar is ve, reversal of power takes place (only academic interest)
434/454
Contd..
Mode stabilization :
Intersection is not well defined Change the slope
Constant Vdc Constant
435/454
Contd..
Current limit :
Imax = (1.2 -1.3) Irated Imin Should not be allowed to go into discontinuous
436/454
VdcoCos
Application of Power Electronics in Power Systems B. G. Fernandes
437/454
To maintain the current, voltage at the other end of the line is adjusted Either or Reactive power demand Vac has , Q supplied by C or filter also Above problems can be addressed using voltage dependent current order limit
Application of Power Electronics in Power Systems B. G. Fernandes
438/454
439/454
441/454
442/454
In current control mode closed loop regulator controls the firing angle to regulate Id at Iord Tap changer control of the converter brings within 10-20o
Application of Power Electronics in Power Systems B. G. Fernandes
443/454
Inverter is functioned with CEA control and a current control In CEA mode, is regulated at around 15o Inverter control could have constant control Under normal operation rectifier is in current control & inverter is on CEA control mode
Application of Power Electronics in Power Systems B. G. Fernandes
444/454
If there is a in AC voltage, of rectifier min (CIA mode) If current falls to a certain limit, inverter will assume C.C
Inject AC voltage in the link There could be V & I oscillations due to lightly damped circuit Transformer feeding the bridge is also subjected to DC magnetization By pass the bridge when the devices (valves) are blocked
Application of Power Electronics in Power Systems B. G. Fernandes
446/454
Commutation for T2 to T4 is in usual manner But incoming device T5 is prevented by not triggering T5. When T1 get F.B (VAB +ve ) trigger T1 Current by pass pair is shunted by closing S1 & open S
448/454
For energization of blocked bridge Current is first diverted from S1 to bypass pair S1 will generate arc voltage Trigger bypass pair
449/454
Modern techniques
HVDC using line commutated converters Requires AC voltage for commutation Requires reactive power DC link is equivalent to a current source V can reverse but I can not reverse Devices should be able to block ve voltage Not suitable for weak grid
Application of Power Electronics in Power Systems B. G. Fernandes
450/454
V can not reverse, but I can reverse Devices should be able to carry I in both directions
453/454
Thank you
454/454