ANSI C12.11 Final
ANSI C12.11 Final
ANSI C12.11 Final
11-2007
Revision of
ANSI C12.11-2006
Secretariat:
ANSI C12.11-2007
AMERICAN
NATIONAL
STANDARD
Published by
ANSI C12.11-2007
ii
ANSI C12.11-2007
Contents
Page
1
2
3
Scope...................................................................................................................................................... 1
References ............................................................................................................................................. 1
Definitions ............................................................................................................................................... 1
3.1 Accuracy Class............................................................................................................................... 1
3.2 Indoor Applications of Instrument Transformers ............................................................................ 1
General Requirements ........................................................................................................................... 1
4.1 ANSI / IEEE C57.13 Provisions...................................................................................................... 1
4.2 Metric Conversion........................................................................................................................... 2
4.3 Space for User Identification .......................................................................................................... 2
4.4 Serial Numbers ............................................................................................................................... 2
Current Transformers ............................................................................................................................. 2
5.1 Nameplates..................................................................................................................................... 2
5.1.1 Ratio Marking Syntax ................................................................................................................ 2
5.1.2 Ratio Marking ............................................................................................................................ 2
5.1.3 Tapped-secondary Current Transformer Secondary Terminal Indication................................. 2
5.1.4 Indoor Application Rating Factor ............................................................................................... 2
5.1.5 Bar Code.................................................................................................................................... 2
5.2 Primary Rating Marking on Body of Current Transformers ............................................................ 2
5.3 Terminals ........................................................................................................................................ 3
5.3.1 Primary Terminals ..................................................................................................................... 3
5.3.2 Secondary Terminals and Voltage Terminals ........................................................................... 3
5.4 Polarity Marking .............................................................................................................................. 3
5.4.1 Polarity Marking Permanence ................................................................................................... 3
5.4.2 Polarity Marking Contrast .......................................................................................................... 3
5.4.3 Polarity Marking Relief............................................................................................................... 3
5.4.4 Primary and Secondary Polarity Marks ..................................................................................... 3
5.4.5 Direct Burial Polarity Marking .................................................................................................... 3
5.5 Test Card ........................................................................................................................................ 3
5.6 Effect of Cooling Air Temperature on Permissible Temperature Rise for 55 C Rise
Transformers .................................................................................................................................. 4
5.7 Indoor and Outdoor Current Transformers, 10 kV BIL (0.6 kV NSV)............................................. 4
5.7.1 Electrical Characteristics and Dimensions ................................................................................ 4
5.7.2 Current Ratings ......................................................................................................................... 4
5.8 Indoor Current Transformers, 60 kV BIL through 110 kV BIL (4.8 kV NSV through 14.4 kV
NSV) ............................................................................................................................................. 12
5.8.1 Electrical Characteristics and Dimensions .............................................................................. 12
5.8.2 Current Ratings ....................................................................................................................... 14
5.9 Outdoor Current Transformers, 60 kV BIL through 110 kV BIL (4.8 kV NSV through 14.4 kV
NSV) ............................................................................................................................................. 14
5.9.1 Electrical Characteristics and Dimensions .............................................................................. 14
5.9.2 Current Ratings ....................................................................................................................... 14
5.10 Small-Size Outdoor Current Transformers, 125 kV BIL through 200kV BIL (25 kV NSV
through 34.5 kV NSV)................................................................................................................... 14
5.10.1 Electrical Characteristics and Dimensions .............................................................................. 14
5.10.2 Current Ratings ....................................................................................................................... 14
5.11 Large-Size Outdoor Current Transformers, 150 kV BIL through 350 kV BIL (25 kV NSV
through 69 kV NSV)...................................................................................................................... 15
5.11.1 Electrical Characteristics and Dimensions .............................................................................. 15
5.11.2 Current Ratings ....................................................................................................................... 15
Voltage Transformers ........................................................................................................................... 20
6.1 Terminals ...................................................................................................................................... 20
6.1.1 Primary Terminals ................................................................................................................... 20
iii
ANSI C12.11-2007
iv
Current Ratings in Amperes for Small-Size Outdoor Current Transformers, 125 kV BIL
through 200 kV BIL (25 kV NSV through 345 kV NSV) ................................................................14
Current Ratings in Amperes for Large-Size, Outdoor Current Transformers, 150 kV BIL
through 350 kV BIL (25 kV NSV through 69 kV NSV) .................................................................15
Electrical ratings for Indoor or Outdoor Voltage Transformers, 10 kV and 110 kV BIL ................21
Electrical Ratings for Small-Size Outdoor Voltage Transformers, with One Bushing, 125 kV
through 200 kV BIL........................................................................................................................27
ANSI C12.11-2007
5
6
7
Electrical Ratings for Small-Size Outdoor Voltage Transformers, with Two Bushings, 125 kV
through 200 kV BIL........................................................................................................................27
Electrical Ratings for Large-Size Outdoor Voltage Transformers, with One Bushing, 150 kV
through 350 kV BIL........................................................................................................................28
Electrical Ratings for Large-Size Outdoor Voltage Transformers, with Two Bushings, 150 kV
through 350 kV BIL........................................................................................................................28
Figures
1
2
3
4
5
6
7
8
9
10
11
12a
12b
13
14
15
16
17
18
ANSI C12.11-2007
vi
ANSI C12.11-2007
Name of Representative
Austin Energy
Center for Neighborhood Technology
City of L.A. Water & Power
Cooper B-Line
Duke Power Company
Elster Electricity
Florida Power & Light
Future DOS R&D
General Electric
Itron, Inc.
Landis+Gyr
Measurement Canada
National Institute of Standards and Technology
Oncor Group
PacifiCorp
Pacific Gas & Electric
Public Service Electric & Gas
Schweitzer Engineering Labs
Tucker Engineering
Underwriters Laboratory
H. Millican
L. Kotewa
C. Gomez
F. Marta
T. Morgan
S. Weikel
J. McEvoy
A. Moise
C. Crittenden
A. Snyder
M. Anderson
V. Nguyen
T. Nelson
J. Mining
L. Pananen
D. Y. Nguyen
D. Ellis
B. Hughes
R. Tucker
R. Breschini
vii
ANSI C12.11-2007
At the time this Standard was completed, Subcommittee 15 of ANSI Committee C12, which developed
and revised this Standard, had the following membership:
Shawn Glasgow, Chairman
Paul Orr, Secretary
Organization Represented
Name of Representative
J. McEvoy
J. DeMars
C. Crittenden
J. Darnell
J. Gagnon
Milbank Manufacturing
S. Glasgow
NIST
T. Nelson
Oncor
G. Hendley
D. Y. Nguyen
PacifiCorp
L. Pananen
D. Ellis
Austin Energy
H. Millican
L. Kotewa
R. Lokys
Cooper B-Line
F. Marta
Duke Energy
W. Ray
Malemezian Consulting
E. Malemezian
Ekstrom
M. Lewis
Elster Electricity
S. Weikel
ERCOT
D. Tandon
Itron, Inc.
A. Snyder
J. Young
W. Rose
M. Shoemaker
In addition, the following comprised the Editorial Committee for the current revision of C12.11:
M. Shoemaker, Chair
D. Ellis
D. Makinson
C. Partridge
C. Smith
A. Snyder
B. Sonnenberg
K. Wade
viii
ANSI C12.11-2007
2 References
IEEE Std C57.13-1993 (R2003), IEEE Standard Requirements for Instrument Transformers
IEEE Std C57.13.6-2005, IEEE Standard for High-Accuracy Instrument Transformers
3 Definitions
All definitions, except as specifically covered in this Standard, shall be in accord with the latest version of
ANSI / IEEE C57.13.
3.1 Accuracy Class
The limits of transformer correction factor, in terms of percent error, that have been established to cover
specific performance ranges for line power factors between 1.0 and 0.6 lag.
3.2 Indoor Applications of Instrument Transformers
Installations where two conditions are met:
(1)
(2)
Note that these conditions may be met when instrument transformers are mounted in enclosures that are
outside of buildings.
4 General Requirements
4.1 ANSI / IEEE C57.13 Provisions
Instrument transformers shall meet the applicable provisions of the latest version of ANSI / IEEE C57.13
or IEEE C57.13.6, in addition to the provisions in this Standard.
Accuracy performance is shown in Figures 1 thru 18 as secondary burdens for which performance will
meet 0.3 accuracy class. IEEE Std C57.13.6-2005 defines 0.15 and 0.15S accuracy classes and E0.04 and E-0.2 burdens for current transformers. It may be acceptable for a current transformer design
that meets either 0.15 or 0.15S accuracy class for some burdens to not meet the 0.3 accuracy class for
the highest burden shown in Figures 1-12.
To meet specific applications, it is acceptable, upon agreement between the user and manufacturer, to
provide instrument transformers with electrical characteristics that are less than the minimum electrical
characteristics published in Figures 1-18.