American National Standard


For Instrument Transformers for Revenue Metering
10kV BIL through 350 kV BIL
(0.6 kV NSV through 69 kV NSV)

Secretariat:

National Electrical Manufacturers Association


Approved November 6, 2007

American National Standards Institute, Inc.

NOTICE AND DISCLAIMER


The information in this publication was considered technically sound by the consensus of persons
engaged in the development and approval of the document at the time it was developed. Consensus
does not necessarily mean that there is unanimous agreement among every person participating in the
development of this document.
NEMA standards and guideline publications, of which the document contained herein is one, are
developed through a voluntary consensus standards development process. This process brings together
volunteers and/or seeks out the views of persons who have an interest in the topic covered by this
publication. While NEMA administers the process and establishes rules to promote fairness in the
development of consensus, it does not write the document and it does not independently test, evaluate,
or verify the accuracy or completeness of any information or the soundness of any judgments contained
in its standards and guideline publications.
NEMA disclaims liability for any personal injury, property, or other damages of any nature whatsoever,
whether special, indirect, consequential, or compensatory, directly or indirectly resulting from the
publication, use of, application, or reliance on this document. NEMA disclaims and makes no guaranty or
warranty, express or implied, as to the accuracy or completeness of any information published herein,
and disclaims and makes no warranty that the information in this document will fulfill any of your particular
purposes or needs. NEMA does not undertake to guarantee the performance of any individual
manufacturer or sellers products or services by virtue of this standard or guide.
In publishing and making this document available, NEMA is not undertaking to render professional or
other services for or on behalf of any person or entity, nor is NEMA undertaking to perform any duty owed
by any person or entity to someone else. Anyone using this document should rely on his or her own
independent judgment or, as appropriate, seek the advice of a competent professional in determining the
exercise of reasonable care in any given circumstances. Information and other standards on the topic
covered by this publication may be available from other sources, which the user may wish to consult for
additional views or information not covered by this publication.
NEMA has no power, nor does it undertake to police or enforce compliance with the contents of this
document. NEMA does not certify, test, or inspect products, designs, or installations for safety or health
purposes. Any certification or other statement of compliance with any health or safetyrelated
information in this document shall not be attributable to NEMA and is solely the responsibility of the
certifier or maker of the statement.

ANSI C12.11-2007

AMERICAN
NATIONAL
STANDARD

Approval of an American National Standard requires verification by


ANSI that the requirements for due process, consensus, and other
criteria for approval have been met by the standards developer.
Consensus is established when, in the judgment of the ANSI Board of
Standards Review, substantial agreement has been reached by directly
and materially affected interests. Substantial agreement means much
more than a simple majority, but not necessarily unanimity. Consensus
requires that all views and objections be considered, and that a
concerted effort be made toward their resolution.
The use of American National Standards is completely voluntary; their
existence does not in any respect preclude anyone, whether he has
approved the standards or not, from manufacturing, marketing,
purchasing, or using products, processes, or procedures not
conforming to the standards.
The American National Standards Institute does not develop standards
and will in no circumstances give an interpretation of any American
National Standard. Moreover, no person shall have the right or
authority to issue an interpretation of an American National Standard in
the name of the American National Standards Institute. Requests for
interpretations should be addressed to the secretariat or sponsor
whose name appears on the title page of this standard.
Caution Notice: This American National Standard may be revised or
withdrawn at any time. The procedures of the American National
Standards Institute require that action be taken periodically to reaffirm,
revise, or withdraw this standard. Purchasers of American National
Standards may receive current information on all standards by calling or
writing the American National Standards Institute.

Published by

National Electrical Manufacturers Association


1300 North 17th Street, Rosslyn, VA 22209
Copyright 2007 by National Electrical Manufacturers Association
All rights reserved including translation into other languages, reserved under the Universal Copyright
Convention, the Berne Convention for the Protection of Literary and Artistic Works, and the International
and Pan American Copyright Conventions.
No part of this publication may be reproduced in any form, in an electronic retrieval system or otherwise, without the
prior written permission of the publisher.

Printed in the United States of America

ANSI C12.11-2007

This page intentionally left blank.

ii

ANSI C12.11-2007

Contents
Page

1
2
3

Scope...................................................................................................................................................... 1
References ............................................................................................................................................. 1
Definitions ............................................................................................................................................... 1
3.1 Accuracy Class............................................................................................................................... 1
3.2 Indoor Applications of Instrument Transformers ............................................................................ 1
General Requirements ........................................................................................................................... 1
4.1 ANSI / IEEE C57.13 Provisions...................................................................................................... 1
4.2 Metric Conversion........................................................................................................................... 2
4.3 Space for User Identification .......................................................................................................... 2
4.4 Serial Numbers ............................................................................................................................... 2
Current Transformers ............................................................................................................................. 2
5.1 Nameplates..................................................................................................................................... 2
5.1.1 Ratio Marking Syntax ................................................................................................................ 2
5.1.2 Ratio Marking ............................................................................................................................ 2
5.1.3 Tapped-secondary Current Transformer Secondary Terminal Indication................................. 2
5.1.4 Indoor Application Rating Factor ............................................................................................... 2
5.1.5 Bar Code.................................................................................................................................... 2
5.2 Primary Rating Marking on Body of Current Transformers ............................................................ 2
5.3 Terminals ........................................................................................................................................ 3
5.3.1 Primary Terminals ..................................................................................................................... 3
5.3.2 Secondary Terminals and Voltage Terminals ........................................................................... 3
5.4 Polarity Marking .............................................................................................................................. 3
5.4.1 Polarity Marking Permanence ................................................................................................... 3
5.4.2 Polarity Marking Contrast .......................................................................................................... 3
5.4.3 Polarity Marking Relief............................................................................................................... 3
5.4.4 Primary and Secondary Polarity Marks ..................................................................................... 3
5.4.5 Direct Burial Polarity Marking .................................................................................................... 3
5.5 Test Card ........................................................................................................................................ 3
5.6 Effect of Cooling Air Temperature on Permissible Temperature Rise for 55 C Rise
Transformers .................................................................................................................................. 4
5.7 Indoor and Outdoor Current Transformers, 10 kV BIL (0.6 kV NSV)............................................. 4
5.7.1 Electrical Characteristics and Dimensions ................................................................................ 4
5.7.2 Current Ratings ......................................................................................................................... 4
5.8 Indoor Current Transformers, 60 kV BIL through 110 kV BIL (4.8 kV NSV through 14.4 kV
NSV) ............................................................................................................................................. 12
5.8.1 Electrical Characteristics and Dimensions .............................................................................. 12
5.8.2 Current Ratings ....................................................................................................................... 14
5.9 Outdoor Current Transformers, 60 kV BIL through 110 kV BIL (4.8 kV NSV through 14.4 kV
NSV) ............................................................................................................................................. 14
5.9.1 Electrical Characteristics and Dimensions .............................................................................. 14
5.9.2 Current Ratings ....................................................................................................................... 14
5.10 Small-Size Outdoor Current Transformers, 125 kV BIL through 200kV BIL (25 kV NSV
through 34.5 kV NSV)................................................................................................................... 14
5.10.1 Electrical Characteristics and Dimensions .............................................................................. 14
5.10.2 Current Ratings ....................................................................................................................... 14
5.11 Large-Size Outdoor Current Transformers, 150 kV BIL through 350 kV BIL (25 kV NSV
through 69 kV NSV)...................................................................................................................... 15
5.11.1 Electrical Characteristics and Dimensions .............................................................................. 15
5.11.2 Current Ratings ....................................................................................................................... 15
Voltage Transformers ........................................................................................................................... 20
6.1 Terminals ...................................................................................................................................... 20
6.1.1 Primary Terminals ................................................................................................................... 20

iii

ANSI C12.11-2007

6.1.2 Secondary Terminals............................................................................................................... 20


6.2 Identification.................................................................................................................................. 20
6.2.1 Terminal Identification ............................................................................................................. 20
6.2.2 Rated Voltage Identification .................................................................................................... 20
6.3 Test Card ...................................................................................................................................... 20
6.4 Construction.................................................................................................................................. 20
6.4.1 Nameplates ............................................................................................................................. 20
6.4.2 Bar Code.................................................................................................................................. 21
6.5 Effect of Cooling Air Temperature on Permissible Temperature Rise for 55 C Rise
Transformers ................................................................................................................................ 21
6.6 Indoor or Outdoor Voltage Transformers, 10 kV and 30 kV BIL, and Indoor Voltage
Transformers, 60 kV through 110 kV BIL ..................................................................................... 21
6.6.1 Electrical Characteristics and Dimensions .............................................................................. 21
6.6.2 Rated Voltages ........................................................................................................................ 21
6.7 Outdoor Voltage Transformers, 60 kV BIL through 110 kV BIL ................................................... 22
6.7.1 Electrical Characteristics and Dimensions .............................................................................. 22
6.7.2 Rated Voltages ........................................................................................................................ 22
6.8 Small-Size Outdoor Voltage Transformers, with One Bushing, 125 kV through 200 kV BIL....... 25
6.8.1 Electrical Characteristics and Dimensions .............................................................................. 25
6.8.2 Rated Voltages ........................................................................................................................ 27
6.9 Small-Size Outdoor Voltage Transformers, with Two Bushings, 125 kV through 200 kV BIL ..... 27
6.9.1 Electrical Characteristics and Dimensions .............................................................................. 27
6.9.2 Rated Voltages ........................................................................................................................ 27
6.10 Large-Size Outdoor Voltage Transformers, with One Bushing, 150 kV BIL through 350 kV
BIL................................................................................................................................................. 27
6.10.1 Electrical Characteristics and Dimensions .............................................................................. 27
6.10.2 Rated Voltages ........................................................................................................................ 27
6.11 Large-Size Outdoor Voltage Transformers, with Two Bushings, 150 kV BIL through 350 kV
BIL................................................................................................................................................. 28
6.11.1 Electrical Characteristics and Dimensions .............................................................................. 28
6.11.2 Rated Voltages ........................................................................................................................ 28
Annex A: Circle Method for Determination of Voltage Transformer Accuracy ........................................... 32
Annex B: Suggested Utility Practices on Field Application of Current Transformers ................................. 34
B.1 Determination of 55 C Rise Current Transformer Capacity........................................................ 34
B.2 Geographic Area .......................................................................................................................... 34
B.3 Determination of 55 C Rise Current Transformer Replacement Need ....................................... 34
B.4 Determination of 55 C Rise Current Transformer Sizes for Specific Loading Conditions .......... 35
B.4.1 Replacement of Existing CTs on Primary Service* (Primary Service is 2 kV or greater) ...... 35
B.4.2 Replacement of Existing CTs on Secondary Service (Secondary Service is 600 V or less) . 35
Annex C: Bar Code ..................................................................................................................................... 36
C.1 Bar Code Characters.................................................................................................................... 36
C.2 Bar Code Size and Format ........................................................................................................... 36
C.3 Bar Code Example ....................................................................................................................... 38
Annex D: Historical Background ................................................................................................................. 39
D.1 Foreword to ANSI C12.11-1987 ................................................................................................... 39
Tables
1
2
3
4

iv

Current Ratings in Amperes for Small-Size Outdoor Current Transformers, 125 kV BIL
through 200 kV BIL (25 kV NSV through 345 kV NSV) ................................................................14
Current Ratings in Amperes for Large-Size, Outdoor Current Transformers, 150 kV BIL
through 350 kV BIL (25 kV NSV through 69 kV NSV) .................................................................15
Electrical ratings for Indoor or Outdoor Voltage Transformers, 10 kV and 110 kV BIL ................21
Electrical Ratings for Small-Size Outdoor Voltage Transformers, with One Bushing, 125 kV
through 200 kV BIL........................................................................................................................27

ANSI C12.11-2007

5
6
7

Electrical Ratings for Small-Size Outdoor Voltage Transformers, with Two Bushings, 125 kV
through 200 kV BIL........................................................................................................................27
Electrical Ratings for Large-Size Outdoor Voltage Transformers, with One Bushing, 150 kV
through 350 kV BIL........................................................................................................................28
Electrical Ratings for Large-Size Outdoor Voltage Transformers, with Two Bushings, 150 kV
through 350 kV BIL........................................................................................................................28

Figures
1
2
3
4
5
6
7
8
9
10
11
12a
12b
13
14
15
16
17
18

Small-Size Window-Type Current Transformers, 10 kV BIL...........................................................5


Intermediate-Size Window-Type Current Transformers, 10 kV BIL ...............................................6
Large-Size Window-Type Current Transformers, 10 kV BIL ..........................................................7
Large-Size Window-Type Current Transformers, 10 kV BIL ..........................................................8
Small-Size Wound or Bar-Type Current Transformers, 10 kV BIL .................................................9
Intermediate-Size Wound or Bar-Type Current Transformers, 10 kV BIL ....................................10
Large-Size Bar-Type Current Transformers 10 kV BIL.................................................................11
Window-Type Current Transformers, 10 kV BIL for Application in Secondary Compartment
of Pad-Mounted Distribution Transformers ...................................................................................12
Indoor Current Transformers, 60 kV BIL through 110 kV BIL.......................................................13
Outdoor Current Transformers, 60 kV BIL through 110 kV BIL ....................................................16
Small-Size Outdoor Current Transformers, 125 kV BIL through 200 kV BIL................................17
Large-Size Outdoor Current Transformers, 150 kV BIL through 350 kV BIL ...............................18
Primary Terminal Dimensions for Large- Size Outdoor Current Transformers, 150 kV BIL through
350 kV BIL.....................................................................................................................................19
Indoor or Outdoor Voltage Transformers, 10 kV BIL through 30 kV BIL Indoor Voltage
Transformers, 60kV BIL through 110 kV BIL ................................................................................23
Outdoor Voltage Transformers, 60 kV BIL through 110 kV BIL....................................................24
Small-Size Outdoor Voltage Transformers, with One Bushing, 125 kV BIL through
200 kV BIL.....................................................................................................................................26
Small-Size Outdoor Voltage Transformers, with Two Bushings, 125 kV BIL through
200 kV BIL.....................................................................................................................................29
Large-Size Outdoor Voltage Transformers, with One Bushing, 150 kV BIL through
350 kV BIL.....................................................................................................................................30
Large-Size Outdoor Voltage Transformers, with Two Bushings, 150 kV BIL through
350 kV BIL.....................................................................................................................................31

ANSI C12.11-2007

This page intentionally left blank.

vi

ANSI C12.11-2007

Foreword (This Foreword is not part of American National Standard C12.11-2007.)


This Standard was developed by the Accredited Standards Committee on Electricity Metering, C12, for
full consensus approval as an American National Standard. This revised edition supersedes ANSI
C12.11-1987.
The new edition differs from the previous one in both technical and editorial content. Besides several
minor revisions, technical changes include: increased focus on Current Transformer Rating Factors
when ambient temperature is not 30 C, and revisions to Rating Factor and Burden & Accuracy
performance to fit established industry practice. Editorial revisions included the redrawing of all figures.
This Standard provides recommended minimum requirements for current and voltage transformers used
for electricity metering. It is to be used in conjunction with the latest revision of ANSI / IEEE C57.13 and
IEEE Std C57.13.6.
Comments on standards and requests for interpretations should be addressed to ANSI Committee C12
Secretary, National Electrical Manufacturers Association, 1300 North 17th Street, Rosslyn, Virginia,
22209.
This Standard was processed and approved for submittal to ANSI by Accredited Standards Committee on
Electricity Metering C12. Committee approval of the standard does not necessarily imply that all
committee members voted for its approval. At the time of its approval, the C12 Committee had the
following members:
Tom Nelson, Chairman
Paul Orr, Secretary
Organization Represented

Name of Representative

Austin Energy
Center for Neighborhood Technology
City of L.A. Water & Power
Cooper B-Line
Duke Power Company
Elster Electricity
Florida Power & Light
Future DOS R&D
General Electric
Itron, Inc.
Landis+Gyr
Measurement Canada
National Institute of Standards and Technology
Oncor Group
PacifiCorp
Pacific Gas & Electric
Public Service Electric & Gas
Schweitzer Engineering Labs
Tucker Engineering
Underwriters Laboratory

H. Millican
L. Kotewa
C. Gomez
F. Marta
T. Morgan
S. Weikel
J. McEvoy
A. Moise
C. Crittenden
A. Snyder
M. Anderson
V. Nguyen
T. Nelson
J. Mining
L. Pananen
D. Y. Nguyen
D. Ellis
B. Hughes
R. Tucker
R. Breschini

vii

ANSI C12.11-2007

At the time this Standard was completed, Subcommittee 15 of ANSI Committee C12, which developed
and revised this Standard, had the following membership:
Shawn Glasgow, Chairman
Paul Orr, Secretary
Organization Represented

Name of Representative

Florida Power & Light Company

J. McEvoy

Florida Power & Light Company

J. DeMars

GE Consumer & Industrial

C. Crittenden

Houston Lighting and Power

J. Darnell

Meter Devices Company

J. Gagnon

Milbank Manufacturing

S. Glasgow

NIST

T. Nelson

Oncor

G. Hendley

Pacific Gas & Electric

D. Y. Nguyen

PacifiCorp

L. Pananen

Public Service Electric & Gas

D. Ellis

Austin Energy

H. Millican

Center for Neighborhood Technology

L. Kotewa

Central Hudson Gas & Electric

R. Lokys

Cooper B-Line

F. Marta

Duke Energy

W. Ray

Malemezian Consulting

E. Malemezian

Ekstrom

M. Lewis

Elster Electricity

S. Weikel

ERCOT

D. Tandon

Itron, Inc.

A. Snyder

Siemens Energy and Automation

J. Young

Siemens Energy and Automation

W. Rose

The Durham Company

M. Shoemaker

In addition, the following comprised the Editorial Committee for the current revision of C12.11:
M. Shoemaker, Chair
D. Ellis
D. Makinson
C. Partridge
C. Smith
A. Snyder
B. Sonnenberg
K. Wade

viii

AMERICAN NATIONAL STANDARD

ANSI C12.11-2007

For Instrument Transformers For Revenue Metering 10 kV BIL through 350 kV


BIL (0.6 kV NSV through 69 kV NSV)
1 Scope
This Standard covers the general requirements, metering accuracy, thermal ratings, and dimensions
applicable to current transformers and inductively coupled voltage transformers for revenue metering, 10
kV basic lightning impulse insulation level (BIL) through 350 kV BIL for 0.6 kV nominal system voltage
(NSV) through 69 kV NSV.

2 References
IEEE Std C57.13-1993 (R2003), IEEE Standard Requirements for Instrument Transformers
IEEE Std C57.13.6-2005, IEEE Standard for High-Accuracy Instrument Transformers

3 Definitions
All definitions, except as specifically covered in this Standard, shall be in accord with the latest version of
ANSI / IEEE C57.13.
3.1 Accuracy Class
The limits of transformer correction factor, in terms of percent error, that have been established to cover
specific performance ranges for line power factors between 1.0 and 0.6 lag.
3.2 Indoor Applications of Instrument Transformers
Installations where two conditions are met:
(1)
(2)

Ambient temperatures may significantly exceed outdoor temperatures


Protection is provided from weather (precipitation).

Note that these conditions may be met when instrument transformers are mounted in enclosures that are
outside of buildings.

4 General Requirements
4.1 ANSI / IEEE C57.13 Provisions
Instrument transformers shall meet the applicable provisions of the latest version of ANSI / IEEE C57.13
or IEEE C57.13.6, in addition to the provisions in this Standard.
Accuracy performance is shown in Figures 1 thru 18 as secondary burdens for which performance will
meet 0.3 accuracy class. IEEE Std C57.13.6-2005 defines 0.15 and 0.15S accuracy classes and E0.04 and E-0.2 burdens for current transformers. It may be acceptable for a current transformer design
that meets either 0.15 or 0.15S accuracy class for some burdens to not meet the 0.3 accuracy class for
the highest burden shown in Figures 1-12.
To meet specific applications, it is acceptable, upon agreement between the user and manufacturer, to
provide instrument transformers with electrical characteristics that are less than the minimum electrical
characteristics published in Figures 1-18.