GE Power Management
Modular Voltage Relays TOV Instructions GEK 98834B
GEK-98834B
7$%/( 2) &217(176
1. 2. DESCRIPTION.................................................................................................................. 3 MODEL LIST .................................................................................................................... 4
2.1. THREE PHASE MODEL LIST ....................................................................................................... 4 2.2. SINGLE PHASE MODEL LIST...................................................................................................... 4 2.3. SPECIAL MODELS .................................................................................................................... 5 3. 4. APPLICATION .................................................................................................................. 6 TECHNICAL CHARACTERISTICS .................................................................................... 7
4.1. TEMPERATURE RANGE ............................................................................................................. 7 4.2. INSULATION TEST ................................................................................................................... 7 4.3. OPERATING RANGE DEPENDING ON THE DIFFERENT MODELS ....................................................... 7 4.4. AUXILIARY POWER SUPPLY ...................................................................................................... 7 4.5. TRIP CONTACT CAPACITY ......................................................................................................... 7 4.6. AUXILIARY CONTACTS CAPACITY .............................................................................................. 8 4.7. ACCURACY ............................................................................................................................. 8 4.8. AMBIENT HUMIDITY ................................................................................................................. 8 4.9. FREQUENCY RANGE................................................................................................................. 8 4.10 BURDENS .............................................................................................................................. 8 4.11. MAXIMUM VOLTAGE ............................................................................................................. 8 4.12. TYPE TESTS .......................................................................................................................... 9 4.13. TIMING ................................................................................................................................ 9 5. OPERATING PRINCIPLES.............................................................................................. 10
5.1. THREE PHASE VERSIONS (TOV4000)...................................................................................... 11 5.2. SINGLE PHASE VERSIONS (TOV5000)..................................................................................... 11 6. CONSTRUCTION ........................................................................................................... 12
6.1. CASE ................................................................................................................................... 12 6.2. IDENTIFICATION ..................................................................................................................... 13 6.3. EXTERNAL CONNECTIONS ...................................................................................................... 14 6.4. PRINTED CIRCUITS BOARD MODULE ........................................................................................ 15 6.5. LOCATION OF CONTROLS AND TARGETS .................................................................................. 16 6.6. INTERNAL CONTROLS AND TEST POINTS .................................................................................. 17 7. 8. RECEPTION, HANDLING AND STORAGE .................................................................... 19 ACCEPTANCE TESTS.................................................................................................... 20
8.1. VISUAL INSPECTION ............................................................................................................... 20 8.2. ELECTRICAL TESTS ................................................................................................................ 20 9. INSTALLATION.............................................................................................................. 24
9.1. INTRODUCTION ..................................................................................................................... 24 9.2. INPUT SETTING ..................................................................................................................... 24 9.3. TESTS .................................................................................................................................. 25 10. TESTS AND PERIODIC MAINTENANCE....................................................................... 26
GEK-98834B
The information provided herein does not intend to cover all details of the variations of the described equipment nor does it take into account the circumstances that may be present in your installation, operating or maintenance activities. Should you wish to receive additional information, or for any particular problem which cannot be solved by referring to the information contained herein, please write to: GE Power Management, S.A. Av. Pinoa, 10 E-48170 ZAMUDIO
GEK-98834B
'(6&5,37,21
The TOV relays are over or undervoltage relays, single phase or three phase, instantaneous or fixed time adjustable from 0.1 to 25.5 s. The settings are adjusted using the switches located on the front side of the relay. The single phase type relays include a filter for the third harmonic. The three phase models do not include that filter. The TOV relays are modular solid state relays and are supplied to the customer in a 1/8 rack case, allowing it to be a part of a distribution system.
GEK-98834B
! UurrQuhrHqryGv
02'(/ /,67
4 0 * 1 2 I M F G H C S 3 * 0 3 0 * 00 * DESCRIPTION
Voltage range: 20/275 VAC Voltage range: 50/305 VAC Undervoltage Overvoltage Vaux= 24/48 VDC/VAC Vaux= 48/125 VDC/VAC Vaux= 110/240 VDC 110/220 VAC Individual housing As part of a MID system
TOV
!!TvtyrQuhrHqryGv
TOV
* 1 2 3
00
DESCRIPTION
20/275 VAC 50/305 VAC 3/66 VAC
1 2 F G H C S
50 Hz filter 60 Hz filter Vaux= 24/48 VDC/VAC Vaux= 48/125 VDC/VAC Vaux= 110/240 VDC 110/220 VAC Individual housing As part of a MID system
GEK-98834B
!"TrpvhyHqry
TOV TOV TOV TOV
- - - - - - - - - - - - - - - - - - - - - - - - -
9 9 9 9
- 0 - 0 - 0 - 0
1 2 3 4
Timing: t=0.19 + 0.75 * ( ) Timing: t=0.375 + 1.5 * ( ) Instantaneous = 20 ms Number or tripping contacts increased
All of the models include one n.o. trip contact, three form C type relays, one for power supply alarm, one for pickup and one auxiliary trip. The operating input voltage is as follows depending on the model: 20 to 275 VAC in 1 V steps 50 to 305 VAC in 1 V steps 3 to 66 VAC in 1 V steps The relay power supply range can be selected from the following choices: 24/48 VDC/VAC 20% 48/125 VDC/VAC 20% 110/240 VDC 20% 110/220 VAC 20%
GEK-98834B
$33/,&$7,21
Some of the most common applications of the TOV when operating as an undervoltage relay are: 1. Instantaneous detection of undervoltage in automatic transfer equipment. 2. Fault detection for line protection equipment with a communication channel. If the line has three terminals, and one of them does not contribute to the fault. Some of the most common applications of the TOV when operating as an overvoltage relay are: 1. Time delay devices, in which operation security depends on the voltage. 2. Protection against overvoltage in a three phase system, with the possibility of being delayed from 100 ms up to 25.5 s. 3. Protection against a phase to ground fault in three phase systems with an insulated ground and in ground fault protection of AC rotating machines.
GEK-98834B
# UrrhrShtr
7(&+1,&$/ &+$5$&7(5,67,&6
14 F to 131 F (-20 C to +55 C) -40 F to 149 F (-40 C to +65 C)
Operating: Storage:
#!DyhvUr
Between any terminal and ground: 2 kV, 50/60 Hz, 1 min duration. Between independent circuits: 2 kV, 50/60 Hz, 1 min duration.
#"PrhvtShtr9rrqvtur9vssrrHqry
20 to 275 VAC in 1V steps 50 to 305 VAC in 1V steps 3 to 66 VAC in 1V steps
##6vyvhQrTy
Rated Voltage VDC/VAC 24/48 48/125 110/240
Operating Range VDC/VAC 19/58 38/150 88/288
If the power supply falls below the values listed in the table, the relay disconnects automatically and activates a power supply alarm auxiliary contact. The power supply variation included in the ranges established by the table cause a variation in the operating margins not greater than 3%. The relay consumption is less that 3W for any power supply value.
#$Uv8hp8hhpv
Continuous: Make and carry: Break:
3A 30A 180 VA resistive at 125/250 VDC 60 VA inductive at 125/250 VDC.
GEK-98834B
#%6vyvh8hp8hhpv
Continuous: Make and carry: Break: Carry continuously:
#&6pphp
3A 5 A during 30 s. 25 W inductive at 125/250 VDC 20 W maximum of 250 VDC or 5 A.
Voltage: Time:
5% 5% or 30 ms (whichever is greater).
#'6ivrCvqv
Up to 95% without condensation.
#(ArrpShtr
Rated frequency Effective range Operative range
# 7qr
SINGLE PHASE 50 or 60 Hz 48/51 Hz or 57/63 Hz 46/53 Hz or 56/64 Hz
THREE PHASE 50/60 Hz 48/63 Hz 46/64 Hz
20-275 VAC and 50-305 VAC ranges Tap set to 50 VAC V (VAC) 30 120 210 300
#
3-66 VAC range Tap set to 5 VAC
VA 0.012 0.100 0.291 0.783
V(VAC) 5 25 45 65
VA 0.019 0.022 0.053 0.092
HhvWyhtr
Ranges 20-275 VAC and 50-305 VAC: Range 3-66 VAC
400 VAC continuously. 200 VAC Continuously.
GEK-98834B
#
!UrUr
Insulation test: Impulse test: 1 Mhz noise test: Electrostatic discharge: Radio interference: Fast Transient:
# "Uvvt
2kV, 50/60 Hz for 1 min (IEC 255-5) 5 kV peak, 1.2/50 s, 0.5J (IEC 255-5) 2.5 kV common mode, 1 kV differential mode, Class III (IEC 255-22-1) Class IV (IEC 255-22-2) Class III (IEC 255-22-3) Class IV (IEC 255-22-4)
Instantaneous: Definite time range:
30 to 50 ms. 130 ms to 25.5 s in 100 ms steps.
GEK-98834B
23(5$7,1* 35,1&,3/(6
The different TOV relay models operation principles are shown in figures 1 and 2:
VA
VB
VC
Figure 1. Three Phase version block diagram
Vo
Figure 2. Single phase version block diagram
10
GEK-98834B
$
UurrQuhrWrvUPW#
The input voltage transformers provide a secondary voltage adequate for the internal operation at low voltages as well as an electrical insulation with the internal electronic circuits. The measuring signals are rectified and are compared with the trip level setting in the level detectors. Once a fault is detected (overvoltage or undervoltage), the pickup indicator Vs lights up. When the fault has been detected, the trip can be instantaneous or time delayed. Selection of this option is performed by switches located on the front of the relay. If the fault situation remains once the set time has passed, the relay trips, and the trip indicator (TRIP) lights up. If the fault disappears, this indicator remains lighted until RESET button is pressed.
$!TvtyrQuhrWrvUPW$
The single phase versions, different from the three phase versions, may include a filter for the third harmonic in the stage prior to the rectifiers, as well as the possibility of selecting the operating mode as undervoltage or overvoltage. As in the three phase case, the rectifier output signal is compared to the trip level. Once the pickup has been produced, the operation is similar to the three phase model. Both versions, single phase and three phase, have a power supply supervision circuit. If the power supply reduces by 20% of the rated voltage, the relay automatically turns itself off to prevent incorrect operations.
11
GEK-98834B
% 8hr
&216758&7,21
The TOV case is made of steel. The general dimensions are provided in figure 3.
4 HOLES OF 7 FOR DRILLING
Figure 3. Case dimensions in mm (226B6086H1)
12
GEK-98834B
Figure 4. Rear view (226B3205H1) Vertically mounted, the module contains a connector on the rear side that provides a mechanical support and electrical connections. The case includes two plastic guides to ensure correct alignment.
%!Dqrvsvphv
The complete relay model is described on the nameplate. To ensure the correct identification, the model number should be checked so that it coincides with the number on the table in the description section.
13
GEK-98834B
%"@rhy8rpv
Figures 5 and 6 illustrate the TOV external connections for the three phase and single phase models respectively.
Figure 5. Three phase version external connections (226B6083H1)
Figure 6. Single phase version external connections (226B6083H2)
14
GEK-98834B
%#Qvrq8vpv7hqHqyr
The TOV relay consists of a single printed circuit board. The handles on the front allow the module to be removed from the case. The modules electrical connections are established through a male connector that is inserted inside a female connector located in the rear side of the case, allowing the module to be easily extracted.
15
GEK-98834B
%$Gphvs8yhqUhtr
Figure 7 shows the location of the TOVs controls and targets.
1 2
5 6
1. Power On (Green LED) 2. Pickup indicator (RED LED) 3. Operating Voltage selection 4. Time selection 5. Trip indicator (RED LED) 6. Trip memory RESET pushbutton
Figure 7. Location of controls and targets
16
GEK-98834B
The green indicator located on the top of the module (Vaux) indicates the relay power supply status. When the power supply is operating correctly the indicator stays on, whereas if the power supply is disabled the indicator light is turned off. The red LED below it (Vs) is the pickup indicator. This led remains lit as long as the relays detects a fault condition. The red indicator labeled TRIP is a trip indicator that remains lit after a trip and can be turned off by pressing the RESET button once the cause of the trip has disappeared. The microswitches on the front panel are divided into two groups, the upper group of microswitches is used to select the trip level while the lower group is used to select the timing.
%%Drhy8yhqUrQv
The relays are calibrated before leaving the factory, therefore it is not necessary for the user to calibrate them. Changing between overvoltage and undervoltage in the single phase models is performed through the use of jumpers as shown in figure 8:
SINGLE PHASE MODEL
JP5 JP7 JP6 JP5 JP7 JP6
OVERVOLTAG JP8
UNDERVOLTAG JP8
WITH LOW PASS
WITHOUT LOW PASS
Figure 8a. Under-overvoltage selection for equipments with PCB revision 4 or higher (for single phase models only)
17
GEK-98834B
TDIBG@QC6T@HP9@G
PW@SWPGU6B@
VI9@SWPGU6B@
XDUC GPXQ6TTAD GU@S
XDUCPVU GPXQ6TTADGU@S
Figure 8b. Under-overvoltage selection for equipments with PCB revision 3 or lower. (for single phase models only)
18
GEK-98834B
5(&(37,21 +$1'/,1* $1' 6725$*(
This relay is supplied to the customer in a special package, which adequately protects it during transportation, as long as this is performed under normal conditions. Immediately after receiving the relay, the customer should check whether it shows any signs of transportation damage. If injury or rough handling is evident, a damage claim should be filed at once with the Transportation Company and the nearest General Electric Sales Office should be notified promptly. When unpacking the relay, care should be taken not to lose the screws supplied in the box. If you do not intend to install the relay immediately, it is recommended that the relay is stored in its original package and kept in a dry, dust-free place. It is important to check that the data on the nameplate coincides with the data from the order.
19
GEK-98834B
$&&(37$1&( 7(676
Immediately after receiving the relay, the customer should perform a visual check and perform the acceptance tests in this chapter to ensure the relay has not suffered transportation damage and that the factory calibration has not been altered. These tests can be performed as installation or acceptance tests in accordance with user criteria. Given that the majority of users utilize different procedures for installation and acceptance tests, this section includes all of the necessary tests that may be performed with these relays.
' WvhyDrpv
Verify that the data on the nameplate coincides with the data from the order. Disassemble the relay and check that the parts have not been broken or damaged during transportation.
'!@yrpvphyUr
'! Brrhy8vqrhvhiurIrx
All devices that are powered by alternating current are affected by the frequency. Because a non-sine wave is the result of a fundamental wave and a series of harmonics belonging to this fundamental wave, the devices that are powered by alternating current are affected by the form of wave applied. To correctly test relays that operate on alternating current it is necessary to use a voltage and/or a current sine wave. The purity of a sinusoidal wave (absence of harmonics) cannot be expressed specifically for any given relay. However, in any relay that includes tuned circuits, circuits R-L and R-C are affected by the non-sine waves as in the case of the TOV relay. These relays respond to the voltage waveform differently from the majority of alternating current voltmeters. If the AC source used for the test contains many harmonics the voltmeter and the relay readings will be different. The relays are calibrated in the factory using a network of 50 or 60 Hz containing a minimum amount of harmonics. When testing the relay, you should use an AC source whose waveform does not contain harmonics. The voltmeters and chronometers used to perform trip tests and operating time must be calibrated and their precision should be better than that of the relay. The network power used in the tests must remain stable, mainly in the levels near the pickup voltage.
20
GEK-98834B
It is important to stress that the precision used in the tests depends on the network power and the instruments used. Operating tests performed with inadequate power and instruments are useful to test that the relay operates correctly and that its characteristics are verified approximately. However, if the relay is calibrated under these conditions, its operating characteristics may be outside the tolerance levels.
'!!UrvturG@9Uhtr
Perform the connections in accordance with figure 9 without connecting the X and Y terminals and apply a DC voltage to the relay. Press the RESET button and check that all three LEDs on the front panel light up.
CHRONOMETER
Vaux (+)
$ $ $ $ $ $ $ $
% % $ % % % % %
Vaux (-)
PHASE X Y
A A1 B1
B A2 B2
C A3 B3
=^cT: In the single phase version connect X and Y to A2 and B2.
Figure 9. Test connections.
21
GEK-98834B
'!"UvGrryUrvt
Once the connections indicated in figure 10 are performed, (for a single phase relay connect the measuring voltage to terminals A2 and B2) connect the auxiliary power supply and set the relay for instantaneous trip. Depending on the relay model (single phase, three phase, undervoltage or overvoltage) connect the X and Y terminals to the corresponding phases in accordance with figure 10. Vary the alternating voltage and check that the relay trips in accordance with the values in table 1. In the same way, check that when the relay trips the TRIP indicator is lit and remains lit once the cause for fault disappears. Press the RESET button and check that the TRIP LED is turned off.
TABLE 1 Range 20 to 275
SWITCHES TO RIGHT (SW1) 8 (top) 7 6 5 4 3 2 1 Umin (VAC) 19.95 20.9 22.8 26.6 34.2 49.4 79.8 140.6 Umax (VAC) 22.05 23.1 25.2 29.4 37.8 54.6 88.2 155.4
Range 50 to 305
SWITCHES TO RIGHT (SW1) 8 (top) 7 6 5 4 3 2 1 Umin (VAC) 48.45 49.4 51.3 55.1 62.7 77.9 108.3 169.1 Umax (VAC) 53.55 54.6 56.7 60.9 69.3 86.1 119.7 186.9
Range 3 to 66
SWITCHES TO RIGHT (SW1) 6 (top) 5 4 3 2 1 Umin (VAC) 3.8 4.75 6.65 10.45 18.05 33.25 Umax (VAC) 4.2 5.25 7.35 11.55 19.95 36.75
22
GEK-98834B
'!#DhhrVvUr
Set the trip level to the minimum range of the setting, and the timing to instantaneous mode (all switches to the left). Establish the connections as indicated in figure 10, including the chronometer. Apply the rated voltage to the relay. Apply to points X and Y a voltage higher that the trip level in the case of an overvoltage relay, and lower than the trip level in the case of an undervoltage relay. Check that the time indicated by the chronometer is less that 50 ms.
'!$UvvtUr
Apply a fault and check that the results are in accordance with the following table:
SWITCHES TO RIGHT (SW2) 1 (top) 2 4 8 None
Tmin (ms) 123 218 788 12158 30
Tmax (ms) 157 242 872 13441 40
23
GEK-98834B
( Dqpv
,167$//$7,21
The place where the relay is to be installed must be clean, dry, free of dust and excessive vibration, and well illuminated to facilitate inspection and tests. The relay must be mounted on a vertical surface. Figures 3 and 4 represent the dimensions and drilling diagram of the TOV relays.
(!DTrvt
(! UvGrryTrvt
The following example is for setting a relay with a range of 20/275 V. The setting procedures are the same for models with other ranges. This setting is performed through the upper switch block which has the following inscription below it: Vs = 20 + ( ) To set the selected trip voltage move the corresponding switches to the right (ON position). The input value range is in 1V steps. If, for example, we would like the relay to trip at 57 V, the switches would be situated as follows:
OFF ON === === === === === === === === SW 1
1 2 4 8 16 32 64 128
Vs = 57 = 20 + ( ) ( ) = 37 = 32+4+1
24
GEK-98834B
(!!UvvtTrvt
The following inscription appears on the nameplate: t = 0.03 + 0.1 * ( ) s The value indicated between parenthesis is formed by the lower block of microswitches on the front of the relay, by adding the value of the microswitches placed to the right. To select the instantaneous trip just place all switches to the left.
("Ur
Given that the majority of users use different procedures for installation tests, the section ACCEPTANCE TESTS includes all necessary tests to be performed as installation tests according to the users criteria.
25
GEK-98834B
7(676 $1' 3(5,2',& 0$,17(1$1&(
Given the primary role that protection relays have in any installation, it is recommended that a periodic test program is followed. Given that the intervals between these tests vary for different types of relays and installations as well as the experience of the user performing the tests, it is recommended that the points described in the section INSTALLATION are checked at intervals of 1 to 2 years.
26