3ez e (Bocr) .Manual

This document summarizes the features of the BOCR-3EZ digital overcurrent relay. It provides microcontroller-based protection for overcurrent, undercurrent, phase loss, reversal, and unbalance. It also protects against ground faults and locked rotor conditions. Current readings are displayed for each phase and ground fault. Settings include protection ranges from 0.5-960A, time delays from 0.05-30 seconds, and reset options. Specifications cover model details, setting ranges for current and time, and operation characteristics.

Uploaded by

Naveen Gupta
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
75% found this document useful (4 votes)
11K views4 pages

3ez e (Bocr) .Manual

This document summarizes the features of the BOCR-3EZ digital overcurrent relay. It provides microcontroller-based protection for overcurrent, undercurrent, phase loss, reversal, and unbalance. It also protects against ground faults and locked rotor conditions. Current readings are displayed for each phase and ground fault. Settings include protection ranges from 0.5-960A, time delays from 0.05-30 seconds, and reset options. Specifications cover model details, setting ranges for current and time, and operation characteristics.

Uploaded by

Naveen Gupta
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 4

BOCR-3EZ

Digital Over-current Relay with Ground Fault Protection and Ammeter

█ Introduction █ Relay Facia


► MCU(Micro Controller Unit) based
► Function feature

Protected Item Operation Delay


Overcurrent 0.5 / 1~30 sec(Definite time)
1~30 class(Inverse time)
Undercurrent 0.5 / 1~30 sec(Definite time)
Phase Loss Within 3 sec
Phase Reversal 0.1 sec
Unbalance Within 8 sec
Locked Rotor Trip after preset ‘dt’
Stall 0.5 / 1~10 sec(Definite time)
Ground Fault 0.05~10 sec(Definite time)
► Ampere meter function :
- Load current of 3 phases & GF are displayed in sequence
- Display time of each phase current is 5 sec
► Overcurrent protection range █ How to set
- 0.5~60A(wide range type) : displays line current under 100A Mode Search a mode to be adjusted by depressing UP/DN
- 11~960A with external CT mode switch.
► Undercurrent protection range Set Selected mode and setting value start flickering which
: 0.5A ~ less than oc setting value / OFF(- -) means to be ready to accept setting as depressing
► Ground Fault once a Set/store button
- Operated by zero sequence current. Adjust Select a required setting value and/or characters by
- A Type : 0.02~3A(Definite time type)/OFF(--) depressing continuously UP/DN mode switch until
B Type : 0.2~10A(Definite time type)/OFF(--) reaching what want to do.
► Time-Current characteristics Store Store a selected value and/or characters by
depressing once Set/store button. Instantaneously the
- 0.5~10A : Definite/Inverse, selectable
flickering is stopped.
- Equal or more than 11A Reset After completing above procedure, make a reset to be
: definite(if inverse required, use with external CT) ready to operate. If not made reset, it will be reset
► Easy troubleshooting by 7 segment LED. automatically after an elapse of 30 sec.
► Trip cause memory : Last 3 trip, stored regardless power Current rotation by Instead of automatic rotation, manual display
failure. Manual rotation is possible as depressing once SET/ Store
► Reset : manual(instantaneous)/electrical(remote) button during an operation. If manual is selected, the
► Fail safe(self-diagnostics) : The output relay of “OL” is information of phase current L1 is displayed firstly and
energized when control power applied. next information is displayed continuously like a
► Appicable to Inverter(20~400Hz) manner of L1→L2→L3→GF→L1→….
How to check trip • Enter into “trip” mode by depressing once Set/store
cause button, then last trip cause is showed.
█ Typical Application Diagram • Each phase current is displayed in order whenever
depress UP/DN button in every once
• The 2nd trip cause is showed after displaying
3 phase current of last trip
• The 3rd trip can be checked by same manner.
Table#1
Current Setting Number of External Setting of Remark
Range Conductors CT Ratio CT Ratio
(Amps) thru CT
windows
0.5∼60A 1 - OFF Wide Range
(Mode:--)
0.25∼3.0A 2 - 2t
0.1∼1.2A 5 - 5t
1∼12A 1 10:5 10
1.5∼18A 1 15:5 15
2.0∼24A 1 20:5 20
2.5∼30A 1 25:5 25
3.0∼36A 1 30:5 30
4.0∼48A 1 40:5 40
5∼60A 1 50:5 50
█ Relay Facia 6∼72A 1 60:5 60
7.5∼90A 1 75:5 75
10∼120A 1 100:5 100
12∼144A 1 120:5 120
15∼180A 1 150:5 150
20∼240A 1 200:5 200
25∼300A 1 250:5 250
30∼360A 1 300:5 300
40∼480A 1 400:5 400
50∼600A 1 500:5 500
60∼720A 1 600:5 600
75∼900A 1 750:5 750
80∼960A 1 800:5 800
█ Specification

Model BOCR-3EZ
Current SettingRange Over-current(oc) 0.5 ~ 60A
Under-current(uc) 0.5A ~ Less than “oc” setting value./ OFF
Ground Fault current(Ec) A Type : 0.02 ~ 3A(Definite time type) / OFF
B Type : 0.2 ~ 10A(Definite time type) / OFF
Time Setting Starting Delay Time(dt) 1 ~ 200 sec(Definite time type) / OFF
Over-current Trip Delay(ot) 0.5 / 1~30 sec(Definite time), 1~30 class(Inverse time)
Under-current Trip Delay(ut) 0.5 / 1~30 sec(Definite time)
Ground Fault Trip Delay(Et) 0.05 ~ 10 sec(Definite time)
Ground Fault Starting OFF / 1~10 sec(Definite time)
Delay Time (Ed)
Reset Manual Depressing Reset button or control voltage interruption
Operation Characteristic Definite/Inverse,selectable • Overcurrent
- 0.5~10A : definite / inverse, selectable
- more than 11A : definite(If inverse time required, use with external CT)
• Undercurrent : definite
Tolerance Current I < 1A : ±0.05A, I ≥ 1A : ±5%
Time t ≤ 3s : ±0.2s, t > 3s : ±5%
Ambient Temperature Storage -30~80°C
Operation -20~60°C
Ambient Humidity 30~85% RH without Condensation
Control Voltage • 220VAC : ±15%, 50/60Hz
• 110VAC : ±15%, 50/60Hz
• 24VAC/DC
Output Contacts Contacts • (OL/UL)1-SPST 3A/250VAC, Resistive
• (GR) 1-SPST 3A/250VAC, Resistive
Condition Normally Energized in FS:ON, 97─┤├─98 Closed.
Insulation Between Casing & Circuits Over 10MΩ(DC 500V Megger)
Dielectric Strength Between Casing & Circuits 2㎸ 60Hz 1min.
Between Contacts 1㎸ 60Hz 1min.
Between Circuits 2㎸ 60Hz 1min.
Mounting 35mm Din Rail or Panel
Power Consumption Less than 3W
Electrostatic Discharge IEC61000-4-2 Level 3: Air Discharge : ±8㎸, Contact Discharge: ±6㎸
Radiated Electromagnetic IEC61000-4-3 Level 3: 10V/m, 150MHz & 450MHz Portable transceiver
Field Disturbance
EFT / Burst IEC61000-4-4 Level 3: ±2㎸, 1min
Surge IEC61000-4-5 Level 3: 1.2×50㎲, ±2㎸(0˚, 90˚, 180˚, 270˚)
1MHz Burst disturbance IEC61000-4-12 Level 3: 2.5kV, 1MHz
Conducted Emission EN55011 Class B

█ Time-Current Characteristics █ how to setup


1) Current :
Definite Time – Set the rated motor current
in “OC” mode. For protection of connected
machinery with motor, it is recommended to
set the 110~115% of running current after
motor current is stabilized.
Inverse Time – 100% of rated motor current
or 110~125% actual motor current is
recommended.
2) D-Time : Set the expected run-up time of
motor in “dt” mode.
3) O-Time :
Definite Time – Set the desired trip delay time in
“ot” mode.
Inverse Time – Set the trip delay time
according to Time-Current characteristics.
4) Ground Fault :
Set the ground fault current in “Ec”, set Its
operating time “Et”, and then delay time in
“Ed” .

Table#2. <Definite time characteristics of OC>


Table#3. <Inverse time characteristics of OC>
0.5~10A / combined with external CT
█ Display Setting
Function Setting Range FND Display Description
1 Over-current 0.5A~60A ▪ 0.5~10A : 0.1A steps.
▪ 10~60A : 1A steps.
▪ Not possible to set a current value over 10A if inverse characteristics is
selected.
▪ Required to set a preset protected value(<6A) at first based on CT
secondary output before setting a CT ratio if needed to adopt external
CT instead of wide range[“CT”:OFF(--)].
2 Starting Delay Time 1~200sec / OFF(dt--) ▪ 1~100sec : 1 sec steps.
▪ 100~200sec : 10 sec steps.
3 Over-current ▪ Within 0.5sec / 1~30sec ▪ 0.5sec / 1~30sec : 1sec steps.
(definite time)
Trip Delay Time ▪ 1~30 class(Inverse) ▪ Operated after “Starting Delay Time”
4 Under-current 0.5A~less than “oc” setting ▪ Not possible to set over “over-current set-value(“oc”)”.
▪ 0.5, 1~10A : 0.1A steps.
value / OFF(uc--) ▪ 10A ~ : 1A steps.
5 Under-current Within 0.5sec / 1~30sec ▪ 0.5sec / 1~30sec : 1sec steps.
Trip Delay Time ▪ Operated after “Starting Delay Time”
6 Ground Fault A Type :0.02~3A /OFF(Ec--) • Operated by zero sequence current.
B Type :0.2~10 A /OFF(Ec--)
7 Ground Fault Trip • 0.05~10 sec(Definite time) • 0.05 / 0.1~1 sec : 0.1 sec steps.
• 1~10sec : 1 sec steps.
Delay Time
8 Ground Fault • 1~10 sec • OFF : Disable
Starting Delay Time • OFF(Ed--)
9 Locked Rotor ▪ 2~10 times of oc setting ▪ Definite
▪ OFF(Lc--) ▪ Tripped within 0.5 sec, After elapse of “dt”.
▪ The decreased proportional % of “Lc” is determined by follow
formular, [Max. value of “Lc”=100/”oc” setting value]
10 Stall ▪ 1.5~5times of oc setting ▪ Definite
▪ OFF(Sc--) ▪ Tripped after elapse of preset time(“St”)
▪ More than 11A: Set automatically by proper decreased %.
▪ The decreased proportional % of “Sc” is determined by follow
formular, [Max. value of “Sc”=100/”oc” setting value]
11 Operating Time of Within 0.5sec / 1~10sec ▪ In case of “Sc:OFF”, “St” mode becomes OFF automatically
Stall
12 Phase current 5~50% / OFF(Ub--) ▪ [ ( Max curr. – Min curr. ) / Max ] x 100[%] > Ub setting %
Unbalance
13 Fail Safe ON(FSon), OFF(FS--) ▪ Impossible to set during operation.

14 Phase Reversal ON(RPon), OFF(RP--) ▪ Tripped 0.1sec.

15 Phase Loss ON(PLon), OFF(PL--) ▪ Tripped within 3 sec.

16 Time characteristics ▪ Definite(tcdE) ▪ Definite: Followed by Table #2


for over-current ▪ Inverse(tcIn) ▪ Inverse: Followed by Table #3
▪ In case of “oc” setting value is more than 11A, applied for definite
characteristics automatically.
17 CT Ratio OFF-5t,2t, ▪ OFF(ct--) : wide range(0.5~60A).
10-15-20-25-30-40-50-60-75- ▪ 5t : Displayed the current more than 0.04A.
100-120-150-200-250-300-400- ▪ 2t : Displayed the current more than 0.1A
500-600-750-800 ▪ Required to set a current value under 6A based on CT secondary
output if need to adopt external CT instead of wide range
[“CT”:OFF(--)] Refer detail in “oc” mode.
▪ Not possible to adjust during the operation
18 Trip Cause Memory Memorized the last 3 trip ▪ Stored the trip causes, regardless power is off.
causes ▪ The stored information is displayed from last trip causes and able to
check each phase current when tripped.
19 Test Not permitted to test this
→(3sec) →(o-time)
function during the operation to
Not possible to test during the operation.
prevent the unnecessary trip.
█ Dimension

※ In case that time-current characteristics of BOCR is inverse


and overcurrent setting is more than 10A, use SRCT only.