Protection Basics r2
Protection Basics r2
Multilin
Outline
Introductions Tools
Enervista Launchpad On Line Store Demo Relays at ISO / Levine
Discussion of future classes Protection Fundamentals ANSI number handout, Training CDs
2
GE Consumer & Industrial
Multilin
Introduction
Speakers:
Craig Wester GE Multilin Regional Manager John Levine GE Multilin Account Manager
3
GE Consumer & Industrial
Multilin
Objective
We are here to help make your job easier. This is very informal and designed around ISO Applications. Please ask question. We are not here to preach to you. The knowledge base on GE Multilin Relays varies greatly at ISO. If you have a question, there is a good chance there are 3 or 4 other people that have the same question. Please ask it.
4
GE Consumer & Industrial
Multilin
Tools
5
GE Consumer & Industrial
Multilin
6
GE Consumer & Industrial
Multilin
7
GE Consumer & Industrial
Multilin
Multilin
9
GE Consumer & Industrial
Multilin
Future Classes
GE Multilin Training will be the 2nd Friday of every month. We will cover:
March Basics, Enervista Launchpad, ANSI number and what they represent, Uploading, downloading, Training CDs, etc. April 489 Relay May MIF II relay June - 750 Relay July - UR relay basic including Enervista Engineer August UR F60 and F35 relays September G30 and G60 including Transformer and Generator in same zone October Communications and security November - Neutral Grounding Resistors December Cts and PTs
10
GE Consumer & Industrial
Multilin
Protection Fundamentals
11
GE Consumer & Industrial
Multilin
Selectivity: Trip the minimal amount to clear the fault or abnormal operating condition
Speed: Usually the faster the better in terms of minimizing equipment damage and maintaining system integrity Simplicity: KISS
Economics: Dont break the bank
12
GE Consumer & Industrial
Multilin
13
GE Consumer & Industrial
Multilin
14
Multilin
Multilin
Reactors - to limit fault current (series) or compensate for charge current (shunt)
VT and CT - to measure primary current and voltage and supply scaled down values to P&C, metering, SCADA, etc. Regulators - voltage, current, VAR, phase angle, etc.
16
GE Consumer & Industrial
Multilin
Types of Protection
Overcurrent Uses current to determine magnitude of fault
Simple May employ definite time or inverse time curves May be slow Selectivity at the cost of speed (coordination stacks) Inexpensive May use various polarizing voltages or ground current for directionality Communication aided schemes make more selective
17
GE Consumer & Industrial
Multilin
Distribution Substation 18
GE Consumer & Industrial
Multilin
(TOC) Coordination
Relay closest to fault operates first Relays closer to source operate slower Time between operating for same current is called CTI
Distribution Substation 19
GE Consumer & Industrial
Multilin
Operate region lies above selected curve, while no-operate region lies below it
Inverse curves can approximate fuse curve shapes
20
GE Consumer & Industrial
Multilin
Multiples of pick-up
21
GE Consumer & Industrial
Multilin
Types of Protection
Differential
current in = current out Simple Very fast Very defined clearing area Expensive Practical distance limitations
Line differential systems overcome this using digital communications
23
GE Consumer & Industrial
Multilin
Differential
Note CT polarity dots This is a through-current representation Perfect waveforms, no saturation
24
GE Consumer & Industrial
Multilin
Differential
Note CT polarity dots This is an internal fault representation Perfect waveforms, no saturation
25
GE Consumer & Industrial
Multilin
Types of Protection
Voltage Uses voltage to infer fault or abnormal condition May employ definite time or inverse time curves May also be used for undervoltage load shedding
Simple May be slow Selectivity at the cost of speed (coordination stacks) Inexpensive
26
GE Consumer & Industrial
Multilin
Types of Protection
Frequency Uses frequency of voltage to detect power balance condition May employ definite time or inverse time curves Used for load shedding & machinery under/overspeed protection
Simple May be slow Selectivity at the cost of speed can be expensive
27
GE Consumer & Industrial
Multilin
Types of Protection
Power Uses voltage and current to determine power flow magnitude and direction Typically definite time
Complex May be slow Accuracy important for many applications Can be expensive
28
GE Consumer & Industrial
Multilin
Types of Protection
Distance (Impedance)
Uses voltage and current to determine impedance of fault Set on impedance [R-X] plane Uses definite time Impedance related to distance from relay Complicated Fast Somewhat defined clearing area with reasonable accuracy Expensive Communication aided schemes make more selective
29
GE Consumer & Industrial
Multilin
ZL
Impedance
Relay in Zone 1 operates first Time between Zones is called CTI
R
T2 T1 ZA
ZB
21
21
A
Source
30
GE Consumer & Industrial
Multilin
Receives power from transmission system and transforms into subtransmission level
Subtransmission-typically at 69-161kV
Receives power from subtransmission system and transforms into primary feeder voltage
Distribution network-typically 2.4-69kV
Multilin
Protection Zones
1. Generator or Generator-Transformer Units 2. Transformers 3. Buses 4. Lines (transmission and distribution)
~
Generator XFMR Bus Line Bus XFMR Bus Motor
34
GE Consumer & Industrial
Multilin
Zone Overlap
1. Overlap is accomplished by the locations of CTs, the key source for protective relays.
2.
In some cases a fault might involve a CT or a circuit breaker itself, which means it can not be cleared until adjacent breakers (local or remote) are opened.
Relay Zone A
Relay Zone A
Zone A
Relay Zone B
Zone B
Zone A
Relay Zone B
Zone B
CTs are located at both sides of CBfault between CTs is cleared from both remote sides
CTs are located at one side of CBfault between CTs is sensed by both relays, remote right side operate only.
35
GE Consumer & Industrial
Multilin
Multilin
41
GE Consumer & Industrial
Multilin
Multilin
43
GE Consumer & Industrial
Multilin
44
GE Consumer & Industrial
Multilin
45
GE Consumer & Industrial
Multilin
46
GE Consumer & Industrial
Multilin
1-Line [1]
47
GE Consumer & Industrial
Multilin
1-Line [2]
3-Line
49
GE Consumer & Industrial
Multilin
52
GE Consumer & Industrial
Multilin
86b 86 TC 86b
86a
55
GE Consumer & Industrial
Multilin
56
GE Consumer & Industrial
Multilin
57
GE Consumer & Industrial
Multilin
Current Transformers
Current transformers are used to step primary system currents to values usable by relays, meters, SCADA, transducers, etc. CT ratios are expressed as primary to secondary; 2000:5, 1200:5, 600:5, 300:5 A 2000:5 CT has a CTR of 400
58
GE Consumer & Industrial
Multilin
Multilin
61
GE Consumer & Industrial
Multilin
Current into the Dot, Out of the Dot Current out of the dot, in to the dot
62
GE Consumer & Industrial
Multilin
Voltage Transformers
Voltage (potential) transformers are used to isolate and step down and accurately reproduce the scaled voltage for the protective device or relay VT ratios are typically expressed as primary to secondary; 14400:120, 7200:120 A 4160:120 VT has a VTR of 34.66
VP VS
Relay
63
GE Consumer & Industrial
Multilin
64
GE Consumer & Industrial
Multilin
Secondary Circuit
Case ground made at IT location Secondary circuit ground made at first point of use
65
Multilin
Equipment Grounding
Prevents shock exposure of personnel Provides current carrying capability for the ground-fault current Grounding includes design and construction of substation ground mat and CT and VT safety grounding
66
GE Consumer & Industrial
Multilin
System Grounding
Limits overvoltages Limits difference in electric potential through local area conducting objects Several methods
Ungrounded Reactance Coil Grounded High Z Grounded Low Z Grounded Solidly Grounded
67
GE Consumer & Industrial
Multilin
System Grounding
1. Ungrounded: There is no intentional ground applied to the systemhowever its grounded through natural capacitance. Found in 2.415kV systems.
2. Reactance Grounded: Total system capacitance is cancelled by equal inductance. This decreases the current at the fault and limits voltage across the arc at the fault to decrease damage.
X0 <= 10 * X1
68
GE Consumer & Industrial
Multilin
System Grounding
3. High Resistance Grounded: Limits ground fault current to 10A-20A. Used to limit transient overvoltages due to arcing ground faults. R0 <= X0C/3, X0C is capacitive zero sequence reactance
69
GE Consumer & Industrial
Multilin
System Grounding
5. Solidly Grounded: There is a connection of transformer or generator neutral directly to station ground.
Effectively Grounded: R0 <= X1, X0 <= 3X1, where R is the system fault resistance
70
GE Consumer & Industrial
Multilin
76
GE Consumer & Industrial
Multilin
Substation Types
Single Supply
Multiple Supply
Mobile Substations for emergencies
Multilin
78
GE Consumer & Industrial
Multilin
79
GE Consumer & Industrial
Multilin
Multilin
Bus 1
Bus 2
Breaker-and-a-half allows reduction of equipment cost by using 3 breakers for each 2 circuits. For load transfer and operation is simple, but relaying is complex as middle breaker is responsible to both circuits
Ring bus advantage that one breaker per circuit. Also each outgoing circuit (Tx) has 2 sources of supply. Any breaker can be taken from service without disrupting others.
81
GE Consumer & Industrial
Multilin
Transfer
Bus 1
Tie breaker
Bus 2
Double Bus: Upper Main and Transfer, bottom Double Main bus
Main-Reserved and Transfer Bus: Allows maintenance of any bus and any breaker
82
Multilin
Switchgear Defined
Assemblies containing electrical switching, protection, metering and management devices Used in three-phase, high-power industrial, commercial and utility applications Covers a variety of actual uses, including motor control, distribution panels and outdoor switchyards The term "switchgear" is plural, even when referring to a single switchgear assembly (never say, "switchgears") May be a described in terms of use:
"the generator switchgear" "the stamping line switchgear"
83
GE Consumer & Industrial
Multilin
Multilin
Multilin
93
GE Consumer & Industrial
Multilin
Contribution to Faults
94
GE Consumer & Industrial
Multilin
95
GE Consumer & Industrial
Multilin
99
GE Consumer & Industrial
Multilin
100
GE Consumer & Industrial
Multilin
Useful Conversions
102
GE Consumer & Industrial
Multilin
Standard practice is to define Base power 3 phase Base voltage line to line Other quantities derived with basic power equations
103
GE Consumer & Industrial
Multilin
104
GE Consumer & Industrial
Multilin
105
GE Consumer & Industrial
Multilin
106
GE Consumer & Industrial
Multilin
Zbase = kV
MVAbase
X 2 base2
2 base
kV
2 base1
Zactual
Zpu2 = MVAbase2
kV
Zactual
Zpu2 =Zpu1 x kV
2 base1 x kV 2base2
MVAbase2 MVAbase1
107
GE Consumer & Industrial
Multilin
A Study of a Fault.
120
GE Consumer & Industrial
Multilin
121
GE Consumer & Industrial
Multilin
122
GE Consumer & Industrial
Multilin
Multilin
Multilin
Current limiting fuses (provides partial protection only for a limited current range)
125
GE Consumer & Industrial
Multilin
FlexCurve for improved coordination opportunities Employ 51VC/VR on feeders fed from small generation to improve sensitivity and coordination Employ UV light detectors with current disturbance detectors for selective gear tripping
126
GE Consumer & Industrial
Multilin
128
GE Consumer & Industrial
Multilin
129
GE Consumer & Industrial
Multilin
133
GE Consumer & Industrial
Multilin
Protection Fundamentals
QUESTIONS?
134
GE Consumer & Industrial
Multilin