Low Z Differential Relay Protection Settings
Low Z Differential Relay Protection Settings
Low Z Differential Relay Protection Settings
Low impedance differential protection systems typically have 3 to 5 settings required to properly define the restraint characteristic of the relay. See Fig. 4.2.1. The ensuing discussion will mainly focus on differential protection for power transformers. Generator and motor diff are included where applicable.
IREST, IDIFF(min)
Operating Region
S2
S1 IDmin
Restraint Region
ITP1 Fig. 4.2.1 IDmin ITP1 ITP2 S1 S2 ITOT IREST, IDIFF(min) IDIFF-HI
ITP2
ITOT
= minimum differential current (secondary) required to operate the relay = turning point 1 = turning point 2 = Slope 1 setting = Slope 2 setting = Total current through the differential system. Measure of system loading. = For a given value of ITOT, this is the restraint current applied by the relay or alternatively the minimum differential current required to operate the relay. = Should the differential current exceed this threshold, operation results irrespective of the restraint current applied
The settings to be considered are IDmin, ITP2, S1, S2 and IDIFF-HI. These are generic representations of the settings. They will differ from one manufacturer to the next.
Before proceeding to discuss the settings, some fundamental concepts first. Consider the equivalent circuit of a two-ended circulating current differential protection system as shown in Fig. 4.2.2 with a throughfault current flowing from End P to End Q.
Object to be protected
RLDP
RCTP
M1 IR
RLDQ
RCTQ
I21P
CT P XP
E2P VR
RRELAY
CT Q
IMP
I2P M2
IMQ
E 2P E 2Q
R CTP R CTQ
I2P I2 Q
(4.2.1) (4.2.2)
The limiting case for a low impedance relay (relay current prevails over relay impedance) is for the case when RRELAY = 0, i.e. a dead short from M1 to M2. Equations (4.2.1) and (4.2.2) now become,
E 2P E 2Q
R CTP R CTQ
(4.2.3) (4.2.4)
For the case when both ends see the same primary current, the turns ratios are identical and there is no saturation, then I21P = I21Q. Thus I2P + IMP = I2Q + IMQ. Relay current is thus IR = I2Q - I2P = IMP - IMQ. Let the relay operating current be IROC. Then to ensure stability must have IR = IMP - IMQ < IROC. What the above states is that for throughfault stability, the differential current is the difference between the magnetisation currents. These in turn depend on :
a) b)
Thus, non-zero IDIFF can still result if the CT s are identical but the sum of CT and lead resistances are substantially different. This is the case when the relay is not located at the electrical midpoint of the secondary system and/or the CT resistances are different.
On the other hand, non-zero IDIFF can also result if the CT mag curves are not identical. Different magnetisation currents are required to produce identical induced voltages, the difference between the mag currents now seen by the relay.
This translates into the requirement that the minimum current required to operate the relay should be > maximum difference between the mag currents at the two ends. Thus IROC. > max(IMP, IMQ ) or even more conservatively, IROC > IMP + IMQ. The minimum current required to operate the relay system assuming a single ended fault may be approximated as follows:
Object to be protected
RLDP
RCTP
M1 IROC
RLDQ
RCTQ
I21P
CT P XP
E2P VR
RRELAY
E2Q
XQ
CT Q
IMP
I2P M2
IMQ
END Q
IFOC
IFOC IMP, IMQ IROC settable) N
N IMP
IMQ
IROC
(4.2.5)
= minimum primary fault current required to operated the differential relay = respective CT magnetisation currents = minimum differential current required to operated the relay (usually
IFOC
N IROC
(4.2.6)
A) IDmin IDmin should satisfy the following criteria: 1. The minimum current required to operate the relay, IROC, should be at least > maximum difference between the mag currents at the two ends. Thus IROC. > max(IMP, IMQ ) or even more conservatively,
IROC
2.
IMP
IMQ
(4.2.7)
It must also be ensured that the relay remains stable under no-load conditions when only transformer magnetising current flows from the primary side. This is typically 1% of full load amps. Escalate this to 5% to allow a sufficient margin of safety.
(4.2.8)
IDmin
applications. Thus it is only necessary to ensure that the above two criteria are satisfied with IDmin = 200mA.
IMP
B) Slope 1, S1 When applied to motors and generators this setting is based on worst case unbalance that could result due to CT errors up to 120% of rated load. With high accuracy CT s (Class PL, PX, P, etc.) a setting of between 0 and 10% will suffice whilst for low accuracy CT s (Class P, PR) a setting of between 10 to 25% is recommended. When applied to power transformers this is based on the worst case IDIFF that could result due to the action of the tapchanger. It is assumed that the transformer impedance remains constant over the tapping range.
Transformers o Determine the tap which results in the largest unbalance. This is usually the maximum boosting tap.
Denote the turns ratio corresponding to this tap position by TRMIN (maximum boosting corresponds to the minimum turns ratio). TRMIN is calculated as follows:
TR MIN
(4.2.9)
where VHV-MAXTAP = HV voltage corresponding to the maximum tap (on nameplate) VHV-NOM TRNOM = nominal HV voltage corresponding to the nominal tap position (on nameplate). = nominal turns ratio of the transformer
ILV
CTR CFHV
(4.2.10)
CTRCFLV CTRCFHV
IDIFF
IHV
ITOT
IHV 2
IHV
ILV
(4.2.11)
Type B:
ITOT
ILV
(4.2.12)
IHV
ILV
(4.2.13)
For motor and generator applications, replace IHV with I1 and ILV with I2. o o In each case the Slope 1 setting is given by Allow for 5% relay and calculation errors.
S1
(4.2.14)
Tapchanger
IFLA
1.8.
LV
420MVA 3 23kV
TR MIN
19.587
ILV
CTR CFHV
3.28 1.177 A
Type A relay,
IDIFF
1.177 1
0.177 A , ITOT
IHV 2
ILV
1.177 1 1.0885 A 2
S1
0.177 100% 16.26% . Allowing for a 5% error, get a slope setting of 17.1%. Set 1.0885
to 20%.
Type B relay,
IDIFF
1.177 1
0.177 A , ITOT
IHV
ILV
1.177 1 2.177 A
S1
10%.
Type C relay,
IDIFF
1.177 1
0.177 A , ITOT
IHV
ILV
1.177
2.177
S1
10%.
C) Turning Point 2, ITP2 Slope 1 dictates the relay restraint characteristic over the load current range of the transformer. Thus it is meant to be effective up to the maximum possible loading of the transformer. For large transformers on the transmission system this could be up to 200% of rated current. For smaller transformers allowable maximum loading could be anything from 100% to 200% of rated load typically 150%. For most cases a turning point of 2 (corresponding to twice rated load) suffices.
Type A
ITOT
2 IFLA 2
2 IFLA 2 IFLA
2 IFLA
(4.2.15)
Type B
ITOT ITOT
2 IFLA 2 IFLA
(4.2.16)
Type C
(4.2.17)
Alternatively some texts advocates that slope 1 is effective over the linear operating range of the current transformer. ITP2 should thus be set at this limit. This approach leads to ITP2 typically being greater than ITP2 = 2 as advocated above. This implies improved sensitivity over the linear operating range but less stability. For this reason the approach of ITP2 is adopted in this text.
When it comes to generators and motors a turning point > 1.2 IRATED times rated current is generally considered sufficient as motors and generators are rarely loaded above this.
D) Slope 2, S2 The second bias slope is intended to ensure additional restraint with severe throughfault currents that could lead to CT saturation. Thus additional restraint is provided on top of the two other restraints already mentioned so far, viz. IDmin to cater for differences in CT magnetisation currents and transformer magnetisation currents and the slope 1 which caters for the action of the tapchanger.
Most manufacturers recommend a slope 2 setting of at least 80% (Type 1 relay). The limitation is that there should be a sufficient margin of safety between the restraint characteristic and the inzone fault characteristic to ensure relay operation for high current single ended faults.
IDIFF
IHV
ILV
IHV
Type A:
ITOT
IHV 2
ILV
IHV 2
, and so slope
IHV IHV 2
IHV IHV
100
200%
(4.2.18).
Type B:
ITOT
IHV
ILV
100 100%
(4.2.19)
Type C:
ITOT
IHV
IHV IHV
100 100%
(4.2.20)
IREST, IDIFF(min) A B C
IDmin
ITP1 A B C D = = = =
ITP2
ITOT
single-ended inzone fault characteristics for a Type 1 relay single-ended inzone fault characteristics for Type 2 and 3 relays typical restraint characteristic for a Type 1 relay typical restraint characteristic for Types 2 and 3 relays Inzone fault vs. restraint characteristic for Types 1, 2 and 3 relays
Fig. 4.2.4
E) IDIFF-HI This function allows operation of the differential protection whenever the differential current exceeds the IDIFF-HI setting. The objective is to ensure fast, yet selective protection operation for high current inzone faults.
The settings criteria is based on one set of CT s saturating under worst case throughfault conditions, i.e. considering maximum DC offset.
Object to be protected
RLDP
RCTP
M1 IR
RLDQ
RCTQ
I21P
CT P XP
E2P VR
RRELAY CT Q
IMP
I2P M2
END Q
In Fig. 4.2.5 have that the throughfault lead to CT Q being fully saturated. The differential current is thus IDIFF = I2P = IF/CTR. Thus,
IDIFF
Where IF CTR K1 K2
HI
IF K1 K 2 CTR
(4.2.21)
= maximum symmetrical throughfault current (no DC offset included). = current transformer ratio = allows for the CTR correction factor = safety factor
The choice of safety factor, K2, depends on several factors. For properly sized CT s full saturation is only a remote possibility especially if a close-up throughfault is cleared by a unit protection scheme such as buszone. Clearance times are then in the order of 100ms and with high X/R ratios full saturation may take up to 1s. A safety factor of 5% or at most 10% will suffice. This is generally applicable to large transformers as they have high X/R ratios. Their size also would imply large LV fault currents making buszone protection a near certainty.
20MVA, X/R
throughfault may not be cleared in 100ms. A higher degree of saturation is now possible and so a safety factor of 30% may be necessary.