9
9
9
Systems
By
J.ILANGUMARAN
REFRIGERATION SYSTEM
• Vapour compression refrigeration systems (VCR) and Vapour
absorption refrigeration systems (VAR) find wide usage in the
Indian industry.
• Although VCR's are dominating, over 1000 VAR's are in use in
India.
Condenser
Cooler
Work
• Reciprocating Compressor
• Centrifugal Compressors
• Screw Compressors and
• Scroll Compressors
Types
• Steam Based
• Double Effect Steam Fired Machines
• Single Effect Steam Fired
• Oil / Gas Based
• Hot Water Based
STEAM BASED VAM
Double Effect Steam Fired Machines
• Steam pressure : 3.5 kg / cm2 to 10 kg / cm2
• Capacity : 40 TR to 1400 TR
• Sp. Consumption : 4.5 kg / hr @ 8 kg / cm2 / TR
Conventional System
• Lower Shell of VAM
• Split into two sections
• One each for Evaporator & Absorber
Improved Design
• - Split into three sections
• - Evaporation section split into two
• - One each on side of the Absorber
SPLIT EVAPORATOR FOR IMPROVEMENT OUTPUT
How ?
• Improved Design
• Allows uniform flow of the evaporated vapours
• Optimal Absorption of refrigerant vapours by
LiBr in the Absorber
• Results in
• Improvement in Evaporation rate
• Enhanced Output
BENEFITS OF VAM
• Non-dependence on Electrical Power
Non-
• Environmentally Clean & friendly
• Lesser Down Time
• Lower Noise Level
• Availability
• Continuous and Step-
Step-less Modulation and
• 100 % Depreciation
LIMITATIONS OF VAM
• Minimum chilled water
• Temperature possible : + 4.5 °C
• Only water cooled condensers are available commercially.
• High initial investment
APPLICATIONS OF VAM IN INDUSTRIES
• Automobile
• Engineering
• Petrochemicals
• Pharmaceutical
• Cement
• Soft Drinks
• Chemicals
• Fertilizers
• Refinery
• Commercial Establishments and more
REFRIGERATION SYSTEM
ENERGYCONSERVATION OPPORTUNITIES
• Replace Chiller (Usually Smaller)
• Reduce Refrigeration Loads
• Minimize Chiller Operation
• Isolate Special Loads
• Lower Condenser Water Temperature
• Reasons to replace a chiller
• Future Refrigerant Cost / Availability
• Future Maintenance Repair Cost
• Efficiency Improvements
REDUCTION IN REFRIGERATION LOAD
LIMITATIONS
• Multistage compressors have the added complexity of
maintaining the appropriate inter stage pressure,
hence varying the speed will upset this balance and
this will penalise the performance of the compressor.
OTHER BENEFITS OF VSD
• Ideal soft starter (Inrush amp for VSD never
exceeds the 100 % FLA of the motor where
solid state starter of Star Delta starter have 300
- 400 % FLA).
• Addition of VSD enhances the unloading
capability of a Centrifugal chiller by varying the
speed prior to closing the guide vanes.
• Quite Operation
• VSD also come with automatic power factor
correction
VSD Vs CONSTANT SPEED OPERATING
COST COMPARISON
Load Annual kWh
ECWT Annual
Poin Tons
°F hours Alt 1 Alt 2 Savings
ts
1 200 78 100 12 758 10 172 2 586
2 250 80 300 45 806 37 065 8 741
3 300 82 500 89 861 76 767 13 124
4 350 84 2 150 4 50 487 4 05 091 45 396
5 400 86 1 800 4 38420 4 12 744 25 676
6 450 88 200 56 709 55 754 955
7 500 90 100 32 438 33 851 -1 413
Total 5 150 11 26 479 10 31 414 95 065
•Alt 1 is for the chiller with constant speed unit
•Alt 2 is for VSD chiller.
CASE STUDY ON HOT WATER FIRED
VAPOUR ABSORPTION MACHINE
• A continuous process industry in TN.
• DG set details
• Capacity : 2 Nos of 4 MW
• Fuel : LSHS
40°C
• Supply air @ 40°
25°C
• Design parameter is at 25°
• Average Units generation
• (per DG set) : 3400 kW / hr
RECOMMENDATIONS
• One number of Vapour Absorption Machine (VAM)
connected to one DG set hot water circuit with a
provision to link the second DG set, in case the first is
under maintenance.
• Capacity of VAM : 173 TR
• Chilled water flow : 104.6 m3 / hr
• 17°C
Chilled water inlet / outlet temp. : 12 / 17°
• Hot water flow : 144 m3 / hr
• Hot water inlet / outlet temp 85°C
: 91 / 85°
• Cooling Water Flow : 300 m3 / hr
• 36.5°C
Cooling water inlet / outlet temp : 32 / 36.5°
• Power consumption for VAHP : 3.7 kW
• Charge air cooling requirement : 73 TR
SAVINGS IN FUEL CONSUMPTION BY VAM
• Savings in specific fuel consumption / kW
6.5 gm / kW
• Savings in fuel cost / year : Rs. 39 lakhs
• Savings due to additional loading in DG :Rs. 50 lakhs.
• Total savings : Rs. 89 lakhs
• Other benefit : 100 TR of chilled water for plant use
(OR) 173 TR of Chilled Water
• Investment of Rs. 44 lakhs
AMMONIA VAPOUR ABSORPTION
REFRIGERATION (AVAR) - FEATURES
• Ability to operate at rates higher than
nameplate capacitors without negative
consequences. Inertial storage at low loads to
meet transient with sizable spikes.
• Putting up with interrupted heat supply while
maintaining cold supply on continuous mode.
Low pressure steam and available waste heat
sources can be utilized.
FACTORS IN FAVOUR OF AVAR
• Increase in cost of electricity and low cost steam
generation through various available resources.
• Improvement in COP (COP has gone up from 0.4 to
0.56, in latest machines)
Example
• COP : 0.56
• Evaporation temp : 30°°C
- 30
• Heating media temp : 172°C
172°
• Basis : 33°C
Cooling Water at 33°
BARRIERS IN AVAR
Energy Input
Flow Hours Hours Power Consumption kW
kWh
Run
% % 1 2 1 2
100 0 0 0 0.00 0 0