IS 10322: 1987 (Part 5 / Sec 3)

Download as pdf or txt
Download as pdf or txt
You are on page 1of 11

IS : 10322 ( Part !

i/Sec 3 ) - 1987
( Superseding
IS

: 2149.1970 )

Indian Standard
PART Section 3 5 PARTICULAR REQUIREIVIENTS

( Reaffirmed 1995 )

SPECIFICATION FOR LUMINAIRES


Luminaires for Road and Street Lighting

UDC

628 94 : 628-971.6

@JCofiyright 1988

BUREAU
MANAK

OF
BHAVAN,

INDIAN

STANDARDS

9 BAHADUR SHAH ZAFAR MARG NEW DELHI 110002


May 1988

Gr 4

IS : 10322 ( Part 5/&c 3 ) - 1987 ( Superseding IS :2149-1970)

Indian Standard

SPECIFICATION FOR LUMIJYAIRES


PART Section 3 5 PARTICULAR REQUIREMENTS Lighting Lumirtaires for Road and Street

0.
0.1 This Indian

FOR

EWORD
naires and which can be called up as required by the detailed specifications under Part 5. Part 1, 2, 3 and 4 are thus not to be regarded as a specification by itself for any type of luminaires and their provisions apply only to particular types of luminaires to the extent determined by the appropriate section of Part 5. 0.5 The sections of Part 5, in making reference to any other parts of the standard, specify the extent to which that section is applicable and the order in which the tests are to be performed they also include additional requirements as necessary. The order in which the clauses in Part 1: 2, 3 and 4 are numbered, therefore, has no particular significance as the order in which their provisions apply is determined for each type of luminaire or group of luminaires by the appropriate section of Part 5. All sections of Part 5 are self-contained and, therefore, do not contain references to other sections of Part 5. 0.6 In the preparation of this standerd, assistance has been derived from IEC Publication 598-2-3 (1979) Luminaires, Part 2 Particular requirements, Section 3 Luminaires for road and street lighting, published by the International Electrotechnical Commission (IEC), 0.7 For the purpose of deciding whether a particular requirement of the standard is complied with, the final value, observed or calculated , expressing the result of a test or analysis shall be rounded off in accordance with IS : 2-1960*. The number of significant places retained in the rounded off value should be the same as that of specified value in this standard. *Rules for rounding off numerical values ( revised ).

Standard ( Part 51%:~ 3 ) was adopted by the Bureau of Indian Standards on 28 October 1987, after the draft finalized by the Illuminating Engineering and Luminaires Sectional Committee had been approved by the Electrotechnical Division Council. 0.2 IS : 2149* was first published in 1962 and subsequently revised in 1970 to include photoand photometric test requirements metric procedures. In order to take account of the developments in the field of illumination engineering, this standard has now been prepared as a part of a new series of Indian standards on luminaires. This standard, therefore, supersedes IS : 2149-1970 published earlier on this subject. 0.3 This standard (Part 5/Set 3) is one among a series of Indian Standards which deal with luminaires. This series consists of the. following parts: Part 1 General requirements, requirements, terminals,

Part 2 Constructional Part 3 Screw

and screwless

Part 4 Methods Part 5 Particular

of tests, and requirements.

0.4 In general, Part 1, 2, 3 and 4 of this standard cover safety requirements for luminaires. The object of these parts is to provide a set of requirements and tests which are considered to be generally applicable to most types of lumirevision ) .

*Specification for luminaires for street lighting (Jirst

1. SCOPE
standard ( Part 5/Set 3 ) specifies requirements for luminaires for road and street lighting, for use with tungsten filament, tubular fluorescent and other discharge lamps on supply voltages not exceeding 1 OOOV. It is to be read in conjunction with Part 1 to 4 of this standard to which reference is made.

2. DEFINITIONS 2.0 For the purpose of this section, the deiinitions given in Part 1 of this standard shall apply together with the following definitions. 2.1 Span Wire - A wire between main supports which carries the weigh of the complete installation.
NOTE - This may include supply cables and stay wire. several luminaires,

1.1 This

fS I 10322 (. Part 2.2 Suspension

5/Set 3 )-1987
6. CONSTRUCTION

Wire - The wire attached to the span wire and carrying the weight of the luminaire.
2.3 Stay Wire - A tensioned wire between main supports to limit lateral and rotary movement of the suspended luminaires. 3.

6.0 The

provisions of Part 2 of this standard shall apply together with the requirements of 6.1 to 6.4. 6.1 Road and have protection least 1P X3. street lighting luminaires against ingress of moisture shall of at

GENERAL

T-EST REQUIREMENTS

3.1 The provisions

of 3 of Part 1 of this standard shall apply. The tests shall be carried out in the order listed in 13.

4. CLASSIFICATION

OF LUMINAIRES

4.1 Luminaires
with the standard.

shall be classified in accordance provisions of 5 of Part 1 of this

6.2 Luminaires for suspension on span wires shall be fitted with clamping devices for this purpose and the range of span wires sizes for which the clamping devices are suitable shall be stated ih the instruction leaflet supplied with the luminaire. The device shall clamp the span wire to prevent movement of the luminaire with respect to the span wire. The suspension devices shall the span wire during installa.tion normal use of the luminaire. not damage and during

NOTE - Luminaires for road and street lighting are normally suitable for one or more of the following modes of installation: a) On a pipe ( bracket b) On a mast ) or the like, arm,

( column)

c) On a post top, d) On span or suspension wires, and e) On a wall.

Compliance shall be checked by inspection after fitting the luminaire to the smallest and largest span wires in the range stated by the luminaire manufacturer.
NOTE -Care should be taken to avoid electrolytic corrosion between the clamping device and span wire.

5.

MARKING

5.1 The provisions

of 6 of Part 1 of this standard apply. In addition, the following information shall be provided in the instructton leaflet supplied with the luminaire:

a) Design

attitude

( normal

operating

posi-

tion );

6.3 The means for attaching the luminaire to its support shall be appropriate to the weight of the luminaire. The connection shall be designed to withstand wind speeds of 150 km/h on the projected surface of the assembly without undue deflection. Fixings which carry the weight of the luminaire and internal accessories shall be provided with means to prevent the dislodgement of any part of the luminaire by vibration, either in service or during maintenance. Parts of luminaires which are fixed other than with at least two devices, for example, screws or equivalent meansof sufficient strength shall have such extra protection as to prevent those parts falling and endangering persons, animals and surroundings, should a fixing device fail under normal conditions. Compliance shall be checked by inspection and, for mast arm or post top mounted luminaires, by the test of 6.3.1.
NOTEIn considering the possible effects of vibration, the luminiare should be studied in conjunction with the lamp and the column with which it may be used.

b) Weight including controlgear, if any; Cl Overall dimensions; d) If intended for mounting more than 8 m
above ground level, the jected area subjected ( see 6.3.1 ); and maximum proto wind force

e)

The range of cross-sectional suspension wires suitable for naire, if applicable. may

areas of the lumi-

5.1.1 The luminaires with Standard Mark.

also be marked

NOTE - The use of the Standard Mark is governed by the provisions of the Bureau of Indian Standards Act, 1986 and the Rules and Regulations made thereunder. The Standard Mark on products covered by an Indian Standard conveys the assurance that they have been produced to comply with the requirements of that standard under a welldefined system of inspection, testing and quality control which is devised and supervised by BIS and operated by the producer. Standard marked products are also continuously checked by BIS for conformity to that standard as a further safeguard. Details of conditions, under which a licence for the use,of the Standard Mark may be granted to manufacturers or producers may be obtained from the Bureau of Indian Standards.

6.3.1 Wind Force Te-st for Top Mounted Luminaires

Mast

Arm or Post

6.3.1.1 The luminaire is mounted with its largest projected area as viewed in elevation lying in the horizontal plane, and with the means of attachment secured in accordance with the manufacturers recommendations.

--IS : 10322 ( Part 5/Set 3 ) - 1987 -6.3.1.2 The constant evenly distributed load is applied for 10 min on the luminaire using sand bags providing 1.5 kN/ms ~oflantern projected area for mounting heights up to 8 m, 2.0 kN/mZ for mounting heights of 8 m to less than 15 m and 2.4 kN/n@ for mounting heights of 15 m and over. The luminaire is then turned 180, in the vertical plane, about the point of -attachment, and the test is repeated. 6.3.1.3 During the test, there shall be no failure or movement about the point of attachment and after either part of this test, there shall be no permanent set exceeding 1. 6.4 If the use of a single lampholder does not ensure the correct position of the lamp an adequate supporting device shall be provided. For adjustable lampholders or optical parts, suitable reference marks shall be provided. Compliance shall be checked by inspection. 7. CREEPAGE DISTANCES CLEARANCES AND The values for the pull and the torque to be applied depend on the weight of the supply cables. In general, the specified values are adequate, but for luminaires intended to be mounted higher than 20 m and where the weight of the supply cables affecting the cord anchorage exceeds 4 kg, a pull of 100N and the torque of O-35 Nm are applied, 11. PROTECTION SHOCK AGAINST ELECTRIC

11.1 The provisions given this standard shall apply. 12. PHOTOMETRIC

in 21 of Part 2 of

REQUIREMENTS

12.1 The photometric data of a luminaire shall consist of a set of luminous intensity values in different directions, derived from measurement on a distribution photometer (gonophotometer). The coordinate system to be used and the directions in which luminous intensity values are required are specified in 12.2 to 12.4. 12.2 The coordinate system used for defining the space around the road lighting luminaire is known as the C-gamma system and is shown in Fig. 1. The centre of the coordinate system coincides with the centre of the optical system of the luminaire. The vertical axis of the system is formed by the perpendicular line -dropped from the centre of the luminaire to the horizontal plane to be illuminated, independent of any luminaire tilt. Vertical half planes rotate around this axis. The half-planes parallel to the longitudinal roadway axis are defined by the angles C= 0 and C = 180. The halfplanes perpendicular to the road axis are defined by the angles C = 90 on the road side andC= 270 on the kerbside. The elevation angles in these planes are indicated by y, increasing from vertically downwards y = 0 to vertically upwards y = 180. Every direction is clearly defined b,y values of C and y.
AXIS OF OF ROTATION

7.1 The provisions given in 4 of Part 4 of this standard shall apply. 8. PROVISION FOR EARTHING

8.1 The provisions given in 20 of Part 2 of this standard shall apply. 9. TERMINALS 9.1 The provisions given in Part 3 ofthis standard shall apply. Terminals for supply connection shall allow the connection of conductors having nominal cross-sectional areas according to Table 1 of Part 3 of this standard, excluding provision of supply cables with cross-sectional areas smaller than 1 mm2. Compliance shall be checked by fitting conductors of smallest and largest cross-sectional areas specified. 16. EXTERNAL AND INTERNAL WIRING

C-PLANES

10.1 The provisions given this standard shall apply.

in 19 of Part 2 of

10.2 A luminaire for road and street lighting shall be provided with a cord anchorage such that the conductors for supply cables are relieved from strain where they are connected to the terminals, if without the cord anchorage, the weight of the supply cables would exert a strain on the connection. Compliance shall be checked by the relevant test given in Part 3 of this standard, but with a pull of 60 N and a torque of 0 25 Nm. 3

FIN. 1

C-GAMMA SYSTEM

12.3 Performance Manufacturer

Data to be Provided by

12.3.1 The manufacturer or supplier shall provide the following data relating to the performance ~of the luminaire:

a)

Light distribution roadway vertical c = 180 ).

in the longitudinal plane ( C = 0 and


The figure shows the beam axis making an angle ~max with the downward vertical, located midway between two directions of 90 percent Zmax. The angle Ymax defines the throw of the luminaire (seealso Figure 3 ).

b) 4

Light distribution in the transverse vertical plane on roadside ( C = 90 ) and on kerb side ( C = 270 ). Light distribution in the plane containing the maximum intensity the principal vertical plane. The C-angle of this plane shall be stated. Light distribution in the principal conical surface through the direction of maximum intensity. The value of the constant angle y to be stated by the supplier. Light output output ratio. ratio and downward light

FIG, 2

LUMINOUS INTENSITY DISTRIBUTION OF A ROAD LIGHTING .LUMINAIRE THE PLANE IN OF MAXIMUMINTENSITY ( I,,, )

e)

12.3.3.2 Spread - Spread is defined by the most distant longtudinal roadway line parallel to the road axis that just touches the far side of the 90 percent Zmsx contour on the road surface ( Fig. 3). Spread is the y angle of this tangent in the C = 90 plane (y 90).

12.3.2 If requested by the purchaser or responsible agent, the following data shall also be provided:
a) Built in angle of tilt, b) Isolux diagram, diagram, intensity Zss/Zss in the plane viewed O, and c) Isocandela d) Ratio of c = 00,

e) Flashed area F of the luminaire from 7 = 76 in the plane C = f) Specific 13.84


-

luminaire 3.31
430 r,,

index

given 1.3

in

SLZ Zss

log Zss +
+

log&L 4

i
U
/ /

0.08 log

1.29 log

I
the angle y 90 in the plane at

12.3.3 Luminaire Classijication - %o indicate the suitability or otherwise for a given application, a)

a 3-way classification
the extent to which

system based on:


the light

Cuts the far side of the 90 percent

right angles to the road axis between the downward vertical and the line parallel to the road axis that just
Zmax contour. The value of y 90 determines the spread of the luminaire and the angle yma,x its throw.

The figure indicates

up and down a road,

is thrown

b) the degree of sideways spread of light across a road, and c) the amount of control excercised over light emitted at high angles, shall be recommended.

FIG. 3

ISOCANDELA DIAGRAMPROJECTED ON THE ROAD

12.3.3.1 Throw-Throw is defined by the angle (ymax) that the beam axis makes with the downward vertical. The beam axis is defined
by the direction midway between the two directions of 90 percent ZmBx ( Fig. -2 and 3 ). 4

12.3.3.3 Control- It is defined by SLI, the specific luminaire index which consists of those parameters in the glare control mark of an installation which are characteristics of the luminaire used*

SLZ is determined

by using the formula:

SLZ= 13.84 - 3.31 log z*s+1~3(logZso/Z*,)~ - 0.08 log ZsO/Zss 1.29 log F +

IS : 10322 ( Part Three degrees each of throw, spread and control shall be recognized for classifying the photometric properties of the luminaires as given in Table 1.
TABLE 1 CLASSIFICATION SYSTEM PHOTOMETRIC PROPERTIES LUMlNAIRES SPREAD ymax<60 60<ymax narrow G70~average 45<y90 FOR THE OF

S/Set 3 ) - 19811

pared for the particular design temperature which shall be stated specifically in each set of data or charts.
NOTE - A separate Indian standard on methods of photometry of luminaires for street lighting is under preparation.

THROW Short Intermedtate Long

CONTROL y90<45 <55 limited

SLI <2
moderate 2< SLZ 44

ymnx~lOO broad

y90> 55 tight SL1>4

The throw and spread of a luminaire shall be determined from an isocandela diagram in which isocandela contours are projected on the plane illuminated by the lummaire. They can also be determined from isocandela diagram in zenithal projection ( Fig. 4 ).

12.4 Light-ControlLg Components -The attachment of refractors, rgflectors or any other light-controlling component shall be such that they can only be fitted or replaced in the correct relationship to their light source. Top entry, post top and similar luminaires which produce an asymmetric li-ght distribution shall bear a clear indication of the correct orientation of the luminaire and/or refractor(s) or reflector(s) with respect to the carriageway. 12.4.1 Prismatic refractors shall preferably have a smooth exterior surface. Where the optical design of a refractor requires prisms on its outer ( or light-emerging ) surface, the prisms shall either be provided with a sealed cover or be -of a type which does not hold water droplets or dirt and which is not difficult to clean. 13. TESTS 13.1 Classification 13.1.1 Type Tests constitute type tests: of Tests
-

12.3.4 The above data shall be stated for clean luminaires mounted in the designed attitude and equipped with lamps each with its light centre in the correct nominal position. The data shall also include the nominal average lumens through the life of the lamp (or lamps) for which the luminaire is designed. 12.3.5 For luminaires employing tubular fluorescent lamps, the above data shall be prepared on the basis of the luminaires operating in an ambient temperature of 25C with no wind. If the luminaire is specially designed for nominal operation in a higher or lower ambient temperature, the photometric data may be pre-

The

following

shall

a) Visual examination b) Protection against ( see 11.1 ),

( see 13.2 ), electric shock

LONG

\_

THROW

SPREan

In the abcve example,

Throw ymax = 59

and Spread y 90 = 36

FIG. 4

DEFINITION OF THROW AND SPREAD

IS,: 10322 ( Part 5/Sot 3 ) - 1987 c) Mechanical d) Endurance ( see 13.4 ), ), and electric fire and strength tracking strength test to test ( see 13.3 ), and dust thermal and test the purchaser recommended Appendix A. and the plan of supplier. sampling However, a is given in

e) Resistance ( see 13.5

moisture

13.1.3 Routine ~Tests - The constitute the routine tests: a) Visual examination

following ), and

shall

f ) Insulation

resistance ( see 13.6 ), heat,

( see 13.2

g) Resistance to ( see 1367 ), h) Photometric j) 13.1.1.1 which should specified in therein. Cord anchorage

b) Insulation resistance ( see 13.6 ).

and electric strength

tests ( see 13.8 ), and test (under consideration).

Number of samples shall be one be subjected to the type tests 13.1.1, in the order specified

13.2 Visual Examination - The luminaires shall be examined visually for external finish, workmanship and electric connections. 13.3 Mechanical visions of 5 of PPlY * 13.4 Endurance Test and Thermal The provisions of 6 of Part 4 of this shall apply. Test standard Strength Test - The proPart 4 of this standard shall

13.1.1.2 Criteria for a~jroval--The sample shall pass all the type tests, for proving conformity with the requirements of this standard. If one or more failures occur, the testing authority may call for two more samples and subject them to those tests in which the failure occurred. No single failure shall be permitted in the repeat test. 13.1.2 constitute Accepznce Tests -The the acceptance tests: examination to dust following shall

13.5 Resistance to Dust and Moisture The provisions of 2 of Part 4 of this standard shall apply. 1366 Insulation Strength Test of this standard Resistance and Electric -The provisions of 3 of Part 4 shall apply.

a) Visual

( see 13.2 ), and moisture strength

b) Resistance ( see 13.5 ), c)

13.7 Resistance to Heat, Fire and Tracking - The provisions of 7 of Part 4 of this standard shall apply. 13.8 Photometric Requirements The photometric tests shall be carried out to check the photometric requirements mentioned in 12.
NOTE - A separate Indian standard on methods. of photometry of luminaires for street lighting is under preparation.

Insulation resistance ( see 13.6, ), and

and electric

d) Photometric

tests ( see 13.8 ). samples for to between

13.1.2.1 The number of acceptance tests shall be agreed

APPENDIX ( Clause 13.1.2.1 )


SAMPLING A-l. LOT PLAN FOR

ACCEPTANCE

TESTS

A-l.1 In any consignment all the luminaires of same size and manufactured from the same material under similar conditions of production shall be grouped together to constitute a lot. A-2< SCALE OF SAMPLING

A-2.2 These luminaires shall be selected at random from the lot. In order to ensure the randomness of selection, procedures given in IS : 4905-1968* may be followed. A-3. NUMBER OF TESTS FOR CONFORMITY AND CRlTERIA

A-2.1 For judging the conformity of a lot to the requirements of the acceptance tests, sampling shall be done for each lot separately. For this purpose, the number of luminaires to be selected at random from each lot shall depend upod the size of the lot and shall be in accordance with Table 2.
6

A-3.1 The luminaires selected in accordance with co1 1 and 2 of Table 2 shall be subjected to visual examination, insulation resistance test and electric strength test. A luminaire fail-. ing to satisfy any of these acceptance test shall
*Methods for random sampling.

IS : 10322 ( Part S/Set 3 ) - 1987 be termed as defective. The lot shall be considered as conforming to the requirements of these acceptance tests if the number of defectives is less than or equal to the corresponding acceptance number given in co1 3 of Table 2, otherwise not. A-3.2 A lot which is found as conforming to the above requirements shall then be tested for the remaining acceptance tests, namely, resistance to dust and moisture and photometric tests. For this purpose, the sample size shall be selected in accordance with co1 4 of Table 2. The lot shall be considered as conforming to the requirements of these acceptance tests if there are no failures. The lot shall be considered as conforming to the requirements of acceptance tests if A-3.1 and A-3.2 are satisfied. A-3.3

~
TABLE 2 SAMPL:;WXZfEiND

~~-

ACCEPTANCE

( Clauses A-2.1, A-3.1 and A-3.2 )


LOT

SIZE

FORVISUALEXAMIFOROTHER NATION,~NSULATICN ACCEPTANCE RESHJTANOE AND TESTS ELECTRIC STRENQTH C-_-_h-_-_y Sample Acceptance Sample Size Number Size (2) (3) 0 0 1 2 3 5 (4) 2 2 3 5 8 8 8 13 20 32 50 80!

(1) up to 151 to 301 to 150 300 500

501 to 1000 1 001 to 3 000 3 001 and above

BU-REAU OF INDIAN
Headquarters: Manak Bhavan, Telephones: 9 Bahadur Shah Zafar

STANDARDS J .\:
-. :.

% Marg, NEW DELHI 110002

3310131, 3311375

Telegrams: Manaksanstha (Common to all offices) Telephone

Regional

Offices: 9 Bahadur Shah Zafar Marg,

Central: Manak Bhavan, NEW DELHI 110002 *Eastern: l/l4 CALCUTTA Northern: Southern:

3310131~, 3311375 362499 21843, 31641 412442, 412519, 412916

C I.T. Scheme VII M, V.I.P. Road, ~Maniktola, 700054 160036

SC0 445-446, Sector 35-C, CHANDIGARH C.I.T. Campus, MADRAS 600113 Marol, Andheri

twestern: Manakalaya, BOMBAY 400093 Branch Pushpak Offices: Nurmohamed

E9 MIDC,

( East )

6329295

Sheikh

Marg,

Khanpur,

AHMADABAD Road, Nagar,

380001

26348, 26349 384955, 384956 66716 53627

Peenya industrial BANGALORE

Area, 1st Stage, Bangalore-Tumkur 560058 Road, T.T.

Gangotri Complex, 5th Floor, Bhadbhada BHOPAL 462003 Plot No. 82/83, Lewis 53/5 Ward

Road, BHUBANESHWAR

751002 GUWAHATI 781003

No. 29, R.G. Barua Road, 5th By-lane, Station

231083 63471, 69832 216876, 218292 62305

5-856C L. N. Gupta Marg ( Nampally HYDERABAD 500001 RI4 Yudhister Marg, C Scheme, Nagar, 117/418 B Sarvodaya Patliputra Industrial KANPUR

Road ),

JAIPUR

302005

208005 800013 TRIVANDRUM 695035

Estate, PATNA

T.C. No. 14/1421, University Inspection Offices ( With

P.O., Palayam, Sale Point ):

76637

Pushpanjali, First Floor, 205A West High Court Road, Shankar Square, NAGPUR 440010~ Institution of Engineers Pune 411005 ( India) Building, 1332 Shivaji

Nagar Nagar,

25171 52435

*Sales Office in Calcutta Calcutta 700072 tSales Office in Bombay

is at 5 Chowringhee is at Novelty

Approach, Grant

P. 0. Princep Road, Bombay

Street, 400097

2i6800 896528

Chambers,

Printed at New India Printing Press. Khurja, India

NO. 1 JANUARY 1995 TO IS 10322( Part 5/See 3 ) :1987 SPECIFICATION LUMINAIRES


PART Section 3 5 PARTICULAR REQUIREMENTS

AMENDMENT

FOR

Luminaires

for Road and Street Lighting

(Page 6, clause 13.8) Substitute the following for the existing clause: 13.8 Photometric Tests The photometric performance shall be determined by the test method given in IS 13383 (Part 2): 1992 Photometry of lutninaires Method of measurement: Part 2 Luminaires for road and street lighting. The photometric requirements shall be as given in 12.

(Page 6, clause 13.8, Note) Delete. ( ETD 24 )


Reprography Uoit, BIS, New Delhi, India

NO. 2 MARCH 2002 TO IS 10322( PART 5/SEC 3 ) :1987 SPECIFICATION LUMINAIRES


PART Section 3 5 PARTICULAR REQUIREMENTS

AMENDMENT

FOR

Luminaires

for Road and Street Lighting No. 1 ) Substitute by a suitable photometric the test

( Page 6, clause 13.8 ( see also Amendment following for the existing matter:

The photometric performance shall be determined as agreed between the purchaser and the supplier: ( Page 6, Appendix A ) Delete. (ET24)

Reprography Unit, BIS, New Delhi, India

You might also like