15/2
Introduction 3WL Air Circuit Breakers 3WL Air Circuit Breakers/ Non-Automatic Air Circuit Breakers up to 6300 A (AC) General data - Design - Function - Configuration - Technical specifications Project planning aids - Characteristic curves - Dimensional drawings - Schematics - More information 3WL Non-Automatic Air Circuit Breakers up to 4000 A (DC) General data - Technical specifications Project planning aids - Characteristic curves - Dimensional drawings - Schematics - More information
Siemens LV 1 T 2008
15
Siemens AG 2008
Overview
Size I
Size II
Size III
3WL non-automatic air circuit breakers up to 4000 A (DC) II 1000, 2000, 4000
Number of poles Rated operational voltage Ue Rated ultimate short-circuit breaking capacity at 500 V AC Endurance Mounting position
3-pole, 4-pole -Up to 1000 Size III 100/150 (3-pole), 130 (4-pole) 10000 30/25/20 (at 300/600/1000 V DC) 15000
3 0 3 0 3 0 3 0
15
N S E 0 _ 0 0 0 6 1 a
N S E 0 _ 0 0 0 6 2 a
N S E 0 _ 0 0 0 6 1 a
N S E 0 _ 0 0 0 6 2 a
Degree of protection With cover Without cover (with door sealing frame) Dimensions 3-/4-pole
B H T
IP55 IP41
IP55 IP41
W mm Fixedmounted H mm D mm Withdrawable H mm D mm
NSS0_00535
Rating Plug
NSE0_01106a
NSE0_01107a
NSE0_01108a
NSE0_01109a
NSE0_01110b
Rating Plug
OFF :
cs
cw
Type Overload protection Short-time delayed short-circuit protection Instantaneous short-circuit protection Neutral conductor protection Ground-fault protection Zone Selective Interlocking LCD, 4-line LCD, graphic Communication through PROFIBUS DP Measurement function Plus Selectable parameter sets Parameters freely programmable CubicleBUS Standard -- Not available Optional
ETU15B - ----------
ETU25B -----------
ETU27B ---------
ETU45B - --
ETU55B --
ETU76B -
ECO switching capacity N Standard switching capacity S High switching capacity H Very high switching capacity C DC switching capacity
3WL air circuit breakers/non-automatic air circuit breakers according to UL 489 up to 5000 A, see Catalog LV 16.
15/2
Siemens LV 1 T 2008
NSE0_01111a
Siemens AG 2008
19
interface
6 Browser-capable input
7 8 9 10 11 12 13 14 15 16 17 18 19
Features Coordinated communication concept using the PROFIBUS DP or MODBUS, ranging from 16 A to 6300 A with SENTRON 3VL and SENTRON 3WL The high level of modularity of circuit breakers and accessories allows easy retrofitting of all communication components Significant additional benefits for the switchboard due to the possibility of linking up external input and output modules to the circuit breaker-internal CubicleBUS of the SENTRON 3WL
Innovative software products for parameterization, operation, monitoring, and diagnostics of SENTRON circuit breakers, both locally or via PROFIBUS DP, MODBUS or Ethernet/Intranet/Internet Complete integration of the SENTRON circuit breakers into the Totally Integrated Power and Totally Integrated Automation solutions
NSE0_01105f
and output device (e.g. notebook) SENTRON 3WL COM15 PROFIBUS module or COM16 MODBUS module Breaker Status Sensor (BSS) Electronic release ETU Metering function Plus ZSI module Digital output module as relay Digital output module as relay, configurable Analog output module Digital input module Switch ES Power on PC 1) PLC e.g. SIMATIC S7 SIMATIC powercontrol
17
18
12
13
14
15
16
4 8 9 1 10 11 7
Siemens LV 1 T 2008
15/3
15
Siemens AG 2008
6 2 7
3 4 5
9 1 25
15
21 19 22
10
11
23 12
24
18
13
17 14 20 16 15
$ % & ( ) * + , . / 0 1
Guide frame Main circuit connection, front, flange, horizontal, vertical Position indicator switch Grounding contact, leading Shutter COM15 PROFIBUS modules or COM16 MODBUS modules External CubicleBUS modules Closing solenoid, auxiliary trip unit Auxiliary conductor plug-in system Auxiliary switch block Door sealing frame Interlocking set for base plate Transparent panel, function insert
2 3 4 5 6 7 8 9 : ; < =
EMERGENCY-STOP pushbutton, key operated Motorized operating mechanism Operating cycles counter Breaker Status Sensor (BSS) Electronic trip unit (ETU) Reset solenoid Breaker Data Adapter (BDA) 4-line LCD module Ground-fault protection module Rated current module Measuring function module Circuit breaker
15/4
Siemens LV 1 T 2008
NSE0_01887
Siemens AG 2008
Design
Circuit breaker rated current n max (A) Breaking capacity cu at 500 V AC (kA) or cc at 300 V DC (kA)
6300
Dimensions
Fixed-mounted, 3- /4-pole Withdrawable 3- /4-pole
Size III
5000 4000
H 100
460 / 590
460 / 590
Width
Size II
DC 30
N 66
S 80
H 100
434 / 434
460 / 460
Height
291 / 291
385 / 385
Depth
1600 1250
320 / 410
320 / 410
Width
Size I
N 55
S 66
434 / 434
460 / 460
Height
291 / 291
385 / 385
Depth
NSE0_00887 n
The dimension for the depth of the circuit breaker is from the circuit breaker rear to the inner surface of the closed switchgear door.
Versions Rated currents: 630 A to 6300 A 3 sizes for different rated current ranges (see illustration "Overview of SENTRON 3WL Circuit Breakers/Non-Automatic Circuit Breakers") 3 and 4-pole versions Rated operational voltage up to 690 V AC and 1000 V DC. Special versions up to 1000 V AC available 4 different switching capacity classes in the range from 55 kA to 150 kA for AC applications and one switching capacity class for DC applications. The SENTRON 3WL circuit breakers are supplied complete with operating mechanism (manual operating mechanism with mechanical closing), electronic trip unit and auxiliary switches (2 NO contacts + 2 NC contacts in the standard version), and can be equipped with auxiliary trip units. Installation types Fixed-mounted or withdrawable version Ambient temperatures The SENTRON 3WL circuit breakers are climate-proof according to IEC 60068-2-30. They are intended for use in enclosed areas where no severe operating conditions (e.g. dust, corrosive vapors, damaging gases) are present. When installed in dusty and damp areas, suitable enclosures must be provided.
Coordinated dimensions The dimensions of SENTRON 3WL circuit breakers only differ in terms of the width of the device which depends on the number of poles and the size. Due to the nature of the design, the dimensions of devices with a withdrawable version are determined by the dimensions of the guide frames, which are slightly larger. Non-automatic air circuit breakers A special version of circuit breaker is utilized as a non-automatic air circuit breaker. The non-automatic air circuit breakers are designed without an electronic trip unit system and do not perform any protection duties for the system. One potential application is the use as a bus coupler in systems with parallel feed-ins. The versions and features can be selected according to those of the circuit breakers. Operating mechanisms The circuit breakers are available with various optional operating mechanisms: Manual operating mechanism with mechanical closing (standard design) Manual operating mechanism with mechanical and electrical closing Motorized operating mechanism with mechanical and electrical closing The operating mechanisms with electrical closing can be used for synchronization tasks.
Siemens LV 1 T 2008
15/5
15
Siemens AG 2008
Horizontal connection
Vertical connection
N S E 0 _ 0 0 9 7 0 b
N S E 0 _ 0 0 9 7 1 b
N S E 0 _ 0 0 9 6 7 b
N S E 0 _ 0 0 9 7 2 b
N S E 0 _ 0 0 9 7 3 b
Other safety features include: Infeed from above or below, as required Locking of the guide frame with the circuit breaker removed, as standard Locking of the withdrawable circuit breaker against movement, as standard High degree of protection with cover IP55 Mechanical closing lockout after overload or short-circuit tripping as standard The circuit breaker is always equipped with the required number of auxiliary supply connectors Standard design SENTRON 3WL circuit breakers are equipped with the following features as standard: Mechanical ON and OFF pushbutton Manual operating mechanism with mechanical closing Switch position indicator Ready-to-close indicator Memory status indicator Auxiliary switch 2 NO + 2 NC Rear horizontal main circuit connections for fixed-mounted and withdrawable versions up to 5000 A, and rear vertical main circuit connections for 6300 A applications and size II with 4000 A For 4-pole circuit breakers, the fourth pole (N) is installed on the left and is 100 % loadable with the rated current Contact erosion indicator for the main contacts Auxiliary circuit plug system with SIGUT screw terminals Delivery inclusive of all auxiliary circuit connectors to internal features including coding device for the prevention of incorrect installation of auxiliary supply connectors for fixed-mounted circuit breakers Mechanical "tripped" indicator for electronic trip unit system Mechanical closing lockout after tripping operation Operator panel cannot be taken off with the circuit breaker in the ON position Additional features of the withdrawable version: Main contacts: Laminated receptacles in the guide frame, penetration blades on the withdrawable circuit breaker Position indicator in the operator panel of the withdrawable circuit breaker Captive manual crank handle for moving the withdrawable circuit breaker Guide frame with guide rails for easy moving of the withdrawable circuit breaker The withdrawable circuit breaker can be locked to prevent it being pushed out of position The withdrawable circuit breaker cannot be moved when it is in the ON position Coding of the rated current between the guide frame and the withdrawable circuit breaker Standards SENTRON 3WL circuit breakers comply with: IEC 60947-2 DIN VDE 0660 Part 101 Climate-proof to DIN IEC 68 Part 30-2 Versions according to UL 489 also available, see Catalog LV 16. For further specifications, see Appendix.
Horizontal connection
N S E 0 _ 0 0 9 6 7 b
Vertical connection
N S E 0 _ 0 0 9 7 9 a
Flange connection
Main circuit connections All circuit breakers are equipped with horizontal main circuit connections on the rear for up to 5000 A as standard (horizontal connection to busbars). Exception: Circuit breakers of size II with max. rated current 4000 A. Circuit breakers with a max. rated current of 6300 A and circuit breakers of the size II with a max. rated current of 4000 A are equipped with vertical main connections (for upright busbars). The following options are available, with all combinations of top and bottom connections possible: Accessible from the front, one hole (for vertically installed busbars) Accessible from the front, double hole (holes according to DIN 43673) (for vertically installed busbars) At the rear, vertical (for vertically installed busbars) Connecting flange (for direct connection to guide frame up to 4000 A).
N S E 0 _ 0 0 9 7 5 b
15
Auxiliary supply connections The type of connection for the auxiliary switches depends on the type of installation: Withdrawable version: The internal auxiliary switches are connected to the male connector on the switch side. When fully inserted, the connector makes a connection with the sliding contact module (see "Design", graphic "Guide Frame") in the guide frame. Various adapters can then be used to complete the wiring (see the graphic "Connection Options for Auxiliary Circuit Connections"). Fixed mounting: In this case the auxiliary supply connectors are engaged directly onto the circuit breaker. The connectors are equipped with coding pins that prevent them being mistakenly interchanged. Operator panel The operator panel is designed to protrude from a cut-out in the door providing access to all control elements and displays with the control cabinet door closed. The operator panels for all circuit breakers (fixed-mounted/ withdrawable versions, 3-/4-pole) are identical. The operator panel ensures degree of protection IP41.
15/6
Siemens LV 1 T 2008
N S E 0 _ 0 0 9 7 6 b
Siemens AG 2008
An energy storage device for shunt trip units allows the circuit breaker to be opened even if the control voltage is no longer available. Undervoltage trip unit The undervoltage trip unit causes the circuit breaker to be opened if the operational voltage falls below a certain value or is not applied. The circuit breaker cannot be closed manually or by means of an electrical ON command if the undervoltage trip unit is not connected to the operational voltage. The undervoltage trip unit has no delay as standard. A delay can be set by the customer in the range between td < 80 ms and td < 200 ms. In addition, an undervoltage trip unit with a delay in the range from 0.2 to 3.2 s is available. Closing solenoid The closing solenoid is used to close the circuit breaker electrically by means of a local electrical ON command or by a remote unit. Motorized operating mechanisms The operating mechanism is used to load the storage spring automatically. The operating mechanism is activated if the storage spring has been unloaded and the control voltage is available. It is switched off automatically after loading. This does not affect manual operation of the storage spring. Indicators, signals, and control elements Motor shutdown switch Control switch for switching off the motorized operating mechanism (automatic loading). Operating cycles counter The motorized operating mechanism can be supplied with a 5-digit operating cycles counter. The display is incremented by "1" as soon as the storage spring is fully loaded. Resetting the manual "tripped" signal When the circuit breaker has tripped, this is indicated by the protruding red mechanical tripped indicator on the ETU. When the mechanical tripped indicator is activated, the tripping solenoid and tripped signal are reset. If this display is to be reset remotely, the reset button can be equipped with a reset solenoid. This option allows the circuit breaker to be reset both manually and electrically. Automatic resetting of closing lockout When the ETU is activated, reclosing of the circuit breaker is prevented until the trip unit is either electrically or manually reset. If the "Automatic resetting of closing lockout" option is used, the pre-tensioned circuit breaker is ready to close immediately after tripping. Resetting the manual "tripped" indicator is not included in this option. Tripped signal switch If the circuit breaker has tripped due to an overload, short-circuit, ground fault or extended protection function, the tripped signal switch can indicate this. This signal switch is available as an option. If the circuit breaker is used for communication, this option is supplied as standard. Ready-to-close indicator switch The SENTRON 3WL circuit breakers are equipped with an optical ready-to-close indicator as standard. In addition, the ready-toclose status can be transmitted by means of a signal switch as an option. If the switch is used for communication, the signal switch is supplied as standard.
All withdrawable terminals are short-circuited and grounded on delivery. Qualified electricians can easily convert it to a withdrawable bridging unit by following the enclosed instructions. In addition, the withdrawable unit can be adapted to various rated currents of a size. Withdrawable short-circuit and grounding unit The withdrawable short-circuit and grounding unit consists of a breaker enclosure with penetration blades which are connected with the short-circuiting link. Depending on the version, the short-circuiting links are arranged at the top or bottom. The grounding and short-circuit connections are established when the device is inserted. It must be ensured that the side to be short-circuited and grounded is not live. For this reason it is recommended that the withdrawable unit is only wound in when the door is closed. Withdrawable bridging unit The withdrawable bridging unit consists of a breaker enclosure in which all disconnection components and the operating mechanism have been replaced with simple connections between the upper and lower contacts. Auxiliary trip units Up to two auxiliary trip units can be installed at the same time. The following are available: 1 shunt trip unit or 1 undervoltage trip unit or 2 shunt trip units or 1 shunt trip unit + 1 undervoltage trip unit. Alarm switch for auxiliary trip units One signaling contact is used for each auxiliary trip unit to determine the positions of the auxiliary trip units. Shunt trip unit When the operational voltage is connected to the shunt trip unit, the circuit breaker is opened immediately. The shunt trip unit is available in the variants 5 % ON period for overexcitation and 100% ON period for permanent excitation. This means that it is also possible to block the circuit breaker against being jogged into closing.
Siemens LV 1 T 2008
15/7
15
Siemens AG 2008
(2 6 ) (2 5 )
(3 ) (4 ) (5 )
) Name plate for circuit breaker * Spring charge indicator + "Mechanical ON" button , Rated current indication - Positioning pictogram . Operating cycles counter (option) / Hand-operated lever 0 Crank handle 1 Withdrawable unit drive shaft 2 Equipment plate 3 Ground terminal
(2 4 ) (6 ) (2 3 ) (2 2 ) (2 1 ) (8 ) (2 0 ) (9 ) (7 )
4 Position indicator 5 Table for ground-fault protection 6 Safety lock for crank handle (option) 7 Mechanical unlocking of crank handle (option) 8 Electronic trip unit 9 Rated current module : "Mechanical OFF" button or "EMERGENCY-STOP" mushroom pushbutton (option) ; Ready-to-close indicator < Switch position indicator = "Tripped" indicator (reset button) > "Secure OFF" locking device (option) ? Operator panel @ Male connector for auxiliary circuit connections
(1 9 ) (1 8 )
(1 0 ) (1 1 )
15
(1 7 ) (1 6 )
N S E 0 _ 0 0 9 6 5 b
(1 2 ) (1 3 ) (1 4 ) (1 5 )
Guide frames
$ Arc chute cover (option)
(1 ) (2 )
% Blow-out openings & Opening for crane hook ( Shutter (option) ) Locking device (shutter) (option) * Name plate for guide frame + Isolating contacts , Ground terminal 14 mm - Locking device for racking rail . Locking device against movement when control cabinet door is open (option) / Door interlocking for guide frame (option) 0 Racking rail 1 Factory-set rated current coding 2 Sliding contact for breaker grounding (option) 3 Equipment-dependent coding (option) 4 Shutter actuator (option) 5 Position indicator switch (option) 6 Sliding contact module for auxiliary conductors (number depends on equipment)
(1 8 )
(3 )
(1 7 )
(4 ) (5 ) (6 )
(1 6 ) (7 ) (1 5 ) (1 4 ) (1 3 ) (1 2 ) (9 ) (1 1 ) (1 0 )
N S E 0 _ 0 0 9 6 6 b
(8 )
15/8
Siemens LV 1 T 2008
Siemens AG 2008
Siemens LV 1 T 2008
15/9
15
Siemens AG 2008
(1 )
The guide frame can be equipped with position indicator switches. These can be used to determine the position of the circuit breaker in the guide frame.
(4 )
Two versions are available: Option 1 Connected position 1 changeover contact Test position 1 changeover contact Disconnected position1 changeover contact Option 2 Connected position 3 changeover contacts Test position 2 changeover contacts Disconnected position1 changeover contact
(2 ) (3 ) (5 )
(1) Guide frame, interior of l/h side; interior of r/h side similar (2) Coding pin on racking rail in guide frame (3) Racking rail (4) Withdrawable circuit breaker, r/h side; l/h side similar (5) Coding pin on guide frame
Rated current coding unit between circuit breaker and guide frame
15
Positions of the withdrawable circuit breaker in the guide frame
Display Maintenance position
(1 )
TEST
Position indicator
(2 )
CONNECT
(4 )
N S E 0 _ 0 1 0 3 3 a
DISCON
NSE01037
Disconnected position
(3 )
CONNECT
disconnected
disconnected
closed
closed
TEST
DISCON
N S E 0 _ 0 1 0 3 4 a NSE01038
Test position
CONNECT
disconnected
connected
closed
closed
TEST
DISCON
N S E 0 _ 0 1 0 3 5 a NSE01039
Connected position
CONNECT
connected
connected
closed
open
TEST
DISCON
N S E 0 _ 0 1 0 3 6 a
NSE01040
(4) Shutter
Phase barriers The plant engineering company can manufacture phase barriers made of insulating material for the arcing fault barriers. The rear panel of the fixed-mounted circuit breakers or guide frames are equipped with guide grooves. Arc chute cover The arc chute cover is available as optional equipment for the guide frame. It protects switchgear components which are located directly above the circuit breaker.
Door sealing frame and cover SENTRON 3WL circuit breakers have degree of protection IP20 as standard. However, if the switchgear is to be equipped with a higher degree of protection, a door sealing frame with IP41 and a cover with IP55 are available.
15/10
Siemens LV 1 T 2008
Siemens AG 2008
PC with Switch ES Power SENTRON 3WL/3VL configuration and visualization tool using PROFIBUS DP
ZSI module
Measurement function
MODBUS Output device e.g. notebook with browser ZSI module Digital output module Relay Digital output module, configurable Analog output module COM16 BSS ETU Measurement function Plus Digital input module
The requirements for power distribution in terms of communication capability, data transparency, flexibility and integration are constantly increasing. An integrated and modular communication architecture was designed for the SENTRON 3WL to ensure that it can satisfy these requirements. The core component of this architecture is the CubicleBUS, which links together all of the intelligent components within the SENTRON 3WL and enables the easy and safe connection of other additional external components to the circuit breaker. The CubicleBUS is already incorporated and pre-connected in all complete circuit breakers with ETU45B, ETU55B and ETU76B trip units.
The high level of modularity of the system allows communication functions to be retrofitted at any time (e.g. the measurement function). Similarly, the upgrade of a non-communication-capable SENTRON 3WL (e.g. changeover from ETU25B to ETU45B with CubicleBUS) can be carried out easily on site in the plant. All modules connected to the CubicleBUS can directly access the existing source data of the circuit breaker, which guarantees the quickest possible access to information and response to events. Furthermore, additional external modules (including digital inputs/ outputs, analog outputs) can be connected to the CubicleBUS to provide cost-effective solutions for the automation of further devices in the switchgear.
NSE0_01894
Siemens LV 1 T 2008
15/11
15
PC with Win PM. Net SENTRON 3WL configuration and indication software
Siemens AG 2008
Function
NSE0_00880b
NSE0_00881b
R
R
s d
s d s d g
t t
g
s d
N S E 0 _ 0 0 9 5 0 c
N S E 0 _ 0 0 9 5 1 b
N S E 0 _ 0 0 9 5 2 b
ETU15B
ETU25B
ETU27B
15
Basic protection functions Overload protection Short-time delayed short-circuit protection Instantaneous short-circuit protection Neutral conductor protection Ground-fault protection L S I N G - -- --
Additional functions
N-conductor protection can be switched on/off N-conductor protection adjustable Instantaneous short-circuit protection can be switched on/off Non-delayed short-circuit protection can be switched on/off Thermal image can be switched on/off Load monitoring Short-time delayed short-circuit protection switchable to I2t Instantaneous short-circuit protection adjustable Overload protection switchable to I4t Overload protection can be switched on/off Selectable parameter sets ------- -------------- -----------
Measurement function
Measurement function Plus ----
Communication
CubicleBUS Communication through PROFIBUS DP Communication through MODBUS Communication through Ethernet Standard -- Not available Optional Detailed information about the functions of the electronic trip units is given in the following. -------------
15/12
Siemens LV 1 T 2008
NSE0_00882b
Siemens AG 2008
ETU76B
Rating Plug
=
12
NSE0_00883b
NSE0_00884c
IR tR Isd t sd Ii
IR tR Isd t sd Ii
IR tR Isd t sd Ii
Ig tg
NSE0 00953a
Ig tg
NSE0 00953a
Ig tg
NSE0 00953a
ETU45B
ETU55B
ETU76B
NSE0_00886c
---
-- --
- - ---
- -
Siemens LV 1 T 2008
15/13
15
Siemens AG 2008
LCD alphanumeric with 15 inclination and rotatable through 180 Sliding-dolly for switchable overload characteristic curve
15
I2t and I4t characteristic curve for overload protection The best protection for the whole switchgear is achieved by setting the tripping characteristic curve to an optimum value. In order to achieve optimal discrimination for upstream fuses or medium voltage protection systems, the inclination of the characteristic curve can be selected for the overload range. The overload protection L (long time protection) for the electronic trip units ETU45B, ETU55B, and ETU76B allows the characteristic curve to be switched between I2t and I4t. The I4t characteristic improves discrimination for downstream circuit breakers and fuses. Electronic trip units ETU Modularity has also been strictly emphasized during the development of the electronic trip units. These are some of the modules which can be easily retrofitted at any time: Ground-fault protection module Communication Measurement function Display Rated current module (Rating Plug) This allows quick adaptation to new local mains specifications. In addition, innovative functions have been included in the ETUs. Rated current module/Rating Plug The rated current module is an exchangeable module which allows the user to reduce the rated device current so as to adapt it optimally to the plant; e.g. if a new plant section is taken into operation. The rated current module must be selected to fit the rated current of the plant.
Example of configuration for ETU45B
Selectable parameters In the case of quick changes of power supply conditions, e.g. for switchovers from transformer to generator operation or if a section of the supply is disconnected when the shift changes, SENTRON 3WL allows the relevant protection parameters to be quickly adapted to the new conditions. The ETUs contain two independent tripping characteristic curves (parameter sets). The switchover is completed within 200 ms and is performed with the help of an external signal.
15/14
Siemens LV 1 T 2008
Siemens AG 2008
Application: Simple building and system protection without time-selective coordination up to 3200 A Features: Adjustable overload protection with I2t characteristic curve with preset delay time tR = 10 seconds at 6 IR Instantaneous short-circuit protection adjustable in the range 2 ... 8 In Overload display Protection function is set by means of the rotary coding switch For technical details see the table "Functional Overview of the Electronic Trip Unit System" under "Technical Specifications".
Indicator: overcurrent release activated Indicator: overload alarm Indicator: fault in overcurrent release
Sealing ring
NSE0_00954b
Test socket
Application: Classical building, motor and system protection with time-selective coordination for up to 6300 A Features: Adjustable overload protection with I2t characteristic curve Delay time tR = 10 seconds at 6 IR Short-time delayed short-circuit protection adjustable in the range 1.25 ... 12 In and Instantaneous short-circuit protection preset to 20 In, max. 50 kA Can be adapted at any time to the required plant currents through retrofittable rated current module, thus ensuring overload protection in the range from 100 A to 6300 A. Overload display Indicates the reason for tripping by means of an LED Test facility for the release Protection functions are set by means of the rotary coding switch For technical details see the table "Functional Overview of the Electronic Trip Unit System" under "Technical Specifications".
ETU25B
Indicator: fault in overcurrent release Indicator: cause of release Rotary switch for delay, short-circuit release
Rated current module Rotary switch for setting value, overload release Rotary switch for setting value, instantaneous short-circuit release Short-circuit protection fixed setting
NSE0_00955b
Sealing ring
Siemens LV 1 T 2008
15/15
15
Siemens AG 2008
Classical building, motor and system protection with time-selective coordination for up to 6300 A Features: The same as ETU25B but also Reversible neutral conductor protection Permanently integrated ground-fault protection. Calculation of the ground-fault current through vectorial summation current formation For technical details see the table "Functional Overview of the Electronic Trip Unit System" under "Technical Specifications".
ETU27B
OFF ON
Rated current module Rotary switch for setting value, overload release Rotary switch for setting value, instantaneous short-circuit release Short-circuit protection fixed setting Rotary switch for setting value, earth-fault protection Query pushbutton Test pushbutton
N
Indicator: cause of release Rotary switch for delay, short-circuit release Sealing ring
OFF
15
Option: safety lock prevents pressing of reset button after overcurrent release Option: alphanumeric display Scroll down Indicator: fault in overcurrent release
Application: Low-cost all-round system for intelligent buildings and all types of industrial applications "CubicleBUS integrated" Features: The same as ETU25B but also Adjustable time-lag class for overload protection Selectable characteristic for overload and short-delayed short-circuit range (current discrimination) for more accurate discrimination adaptation to upstream fuses and protective devices Thermal image as restart protection for tripped motor outgoing feeders Reversible and adjustable neutral conductor protection Modular ground-fault protection module with alarm and tripping functions which can be adjusted separately Communication interface, measurement function Plus, optional connection of external modules or for retrofitting Storage of events and causes for tripping for detailed fault analysis Extended protection function possible with measurement function Optional high-contrast display with viewing angle adjustment option The protection functions can be set by means of a rotary coding switch or slide switch For technical details see the table "Functional Overview of the Electronic Trip Unit System" under "Technical Specifications".
ETU45B
OFF ON
Rotary switch for setting value, overload release Rotary switch for setting value, instantaneous short-circuit release Rotary switch for setting value, short-circuit protection Selector for earth-fault protection Rotary switch for setting value, earth-fault protection Rotary switch for setting value, earth-fault alarm Test pushbutton Query pushbutton
NSE0_00957b
1 1 1 1 1
Thermal memory on/off N-conductor protection on/off Setting value N-conductor overload Transfer of overload characteristic 2 t / 4t Rotary switch for delay, overload release Rotary switch for delay, short-circuit release Indicator: cause of release Sealing ring Option: earth-fault module
SI
g
12
Indicator: earth-fault alarm Indicator: earth-fault tripped Rotary switch for delay, earth-fault protection t g / Clear pushbutton Test socket
2
tg
15/16
Siemens LV 1 T 2008
Siemens AG 2008
Option: safety lock prevents pressing of reset button after overcurrent release
Application: The trip unit for special safety requirements which can be adjusted via exclusive external parameter access for generator and motor protection as well as industrial applications "CubicleBUS integrated" Features: The same as ETU45B but also including Two protection parameter sets which can be stored separately in the release (switchover is performed by means of external signal) With overload protection which can be deactivated for operation in modern drive technology Adjustable delay of delayed shortcircuit protection up to 4000 ms Neutral conductor protection adjustable up to IN = 200 % In Setting of protection functions by means of Breaker Data Adapter (BDA) or via communications interface For technical details see the table "Functional Overview of the Electronic Trip Unit System" under "Technical Specifications".
ETU55B
Indicator: fault in overcurrent release Fields for noting setting values
Option: earth-fault module Fields for noting setting values Test pushbutton Query pushbutton
NSE0_00958c
Indicators: Earth-fault alarm Earth-fault tripped Fields for noting setting values Clear pushbutton Test socket
ETU76B
The multi-talent with graphical display for system analysis "CubicleBUS integrated" Features: The same as ETU55B but also including Graphical display of all parameters and events/ curve trends Graphics display with high contrast, backlit display, and sleep mode. For technical details see the table "Functional Overview of the Electronic Trip Unit System" under "Technical Specifications".
Graphical display
Control keys for setting he release parameters Rated current module Option: earth-fault module Fields for noting setting values Test pushbutton Query pushbutton
NSE0_00960b
Indicators: Earth-fault alarm Earth-fault tripped Fields for noting setting values Clear pushbutton Test socket
Siemens LV 1 T 2008
15/17
15
Siemens AG 2008
Indicators:
GFM AT 45B ALARM ALARM t TRIP
g (s)
g TRIP
I 2t g
.1 .2 .3 .4 .5
OFF
Rotary switch for setting value ground-fault alarm
A B C D E
.5 .4 .3 .2 .1
NSE0_00962a
I g=
TRIP
A
TRIP
I 2t t g= ms
Fields for noting setting values
I g=
NSE0_00964a
15
15/18
Siemens LV 1 T 2008
Siemens AG 2008
This setting can be implemented for the electronic trip unit versions ETU55B and ETU76B with Menu/Comm. Ground-fault protection with I2t characteristic curve With the exception of the ETU27B electronic trip unit, all versions of the ground-fault modules are supplied with an I2t characteristic curve which can be activated. Selection criteria for SENTRON 3WL circuit breakers Basic criteria for selecting circuit breakers are: Max. short-circuit current at place of installation of circuit breaker I k max . This value determines the short-circuit breaking capacity or short-circuit current carrying capacity of the circuit breaker. It is compared with the value Icu, Ics, Icw of the circuit breaker and essentially determines the size of the circuit breaker. See illustration "Overview of SENTRON 3WL Circuit Breakers/Non-Automatic Air Circuit Breakers". Rated current In which is to flow through the branch circuit. This value must not be larger than the maximum rated current for the circuit breaker. The rated current for the SENTRON 3WL is set with the rated current module. See "Design", illustration "Overview of SENTRON 3WL Circuit Breakers/Non-Automatic Air Circuit Breakers". Ambient temperature for the circuit breaker. This is usually the control cabinet internal temperature. Design of the circuit breaker Minimum short-circuit current which flows through the switching device. The trip unit must still detect this value as a short-circuit and must respond by tripping. Protection functions of the circuit breaker. These are determined by the selection of the corresponding electronic trip unit, see the table "Functions of the Electronic Trip Units" under "Functions".
SENTRON WL
L1 L2 L3 N PE
NSE 00946
T5
SENTRON WL
NSE 00947
3-pole circuit breakers, current transformers in the grounded neutral point of the transformer
L1 L2 L3 N T6 PE
SENTRON WL
NSE 00948
4-pole circuit breakers, current transformers in the grounded neutral point of the transformer
P E
N S E 0 _ 0 1 2 5 1
Siemens LV 1 T 2008
15/19
15
Siemens AG 2008
Short-circuit protection: Setting range Ii = 1.25 IR up to max. 4 In If the set value is exceeded, tripping occurs in less than 50 ms. In IR tR Ii = = = = Rated current of the circuit breaker Set current value of the adjustable overload release Assigned tripping time of the overload trip Instantaneous tripping current of the adjustable short-circuit releases
The components are available only from the company mat Maschinen- und Anlagentechnik.
15
Configuration
Mutual mechanical circuit breaker interlocking The module for mutual mechanical interlocking can be used for one or two SENTRON 3WL circuit breakers and can be adapted easily to the corresponding versions. The fixed-mounted and withdrawable circuit breaker versions are fully compatible and can therefore be used in a mixed configuration in an installation. This also applies to 3WN6 circuit breakers. The circuit breakers can be mounted alongside each other or one above the other, whereby the distance of the circuit breakers is determined solely by the length of the Bowden cable (lengths: 2 m/3 m/4.5 m). Interlock signals are looped through using the Bowden cables. Interlocking is only effective in the connected position in the case of withdrawable circuit breakers. The mechanical endurance of the Bowden cables is 10000 operating cycles. Minimum requirements must be fulfilled in the switchgear for the interlocking to function: Bowden cables must be installed as far as possible in a straight line with minimum bending. Mutual mechanical interlocking of circuit breakers examples
Mutual interlocking of two circuit breakers Interlocking between three circuit breakers Mutual interlocking of three circuit breakers Interlocking of three circuit breakers, two of them mutual
G
The bending radii of the Bowden wire must be greater than 500 mm. The sum of all bending angles along the Bowden cable must not exceed 640. In a vertical arrangement of circuit breakers to be interlocked, the interlocking mechanisms must be in line. Circuit breakers to be interlocked must be arranged so that Bowden cables can be optimally installed in compliance with the conditions mentioned in the above points. The installed Bowden cable must be fixed (with cable ties or the like) before the interlock is adjusted. Select the width of switchgear cubicle to allow enough freedom of movement for adjusting the interlock! Openings and cut-outs in system elements must be designed so that Bowden cables are not changed in direction or obstructed when they are passed through.
S1
S2
S1 S2
S3 S1
NSE01043
S1 S2 S3
S2
S3
S1 S2
S3
NSE01041
NSE01042
NSE01044
NSE01045
15/20
Siemens LV 1 T 2008
Siemens AG 2008
--
--
- - --
Not necessary for this function, optionally combinable -- Function not available
Siemens LV 1 T 2008
15/21
15
Siemens AG 2008
Potential applications
Transmission of circuit breaker data to PROFIBUS DP or MODBUS and integration into higher-level visualization systems are possible e.g. in PCS7, Power Management Systems, WinCC (including add-ons like the text message radio server) Transmission of circuit breaker data and software (i.e. HTML pages with data) to a local output device, or remotely through Ethernet/Intranet/Internet (without the possibility of integration into higher-level visualization systems) e.g. for monitoring, diagnostics, maintenance and parameterization of individual circuit breakers Utilization of the functionality of all CubicleBUS modules e.g. configuration of the configurable digital output module, status check of the digital input modules, diagnostics -
--
15
Measurement function Plus Order code F01+ ... or F02+ ... F05
Data only available in conjunction with the COM15 module (BUS connection not required). Only possible with ETU55B, ETU76B.
15/22
Siemens LV 1 T 2008
Siemens AG 2008
Digital input modules With the digital input module, up to 6 additional binary signals (24 V DC) in the circuit breaker environment can be connected to the system. It is thus possible to send messages concerning the state of a switch disconnector or a control cabinet door to the PROFIBUS DP/MODBUS. With the digital input module on the CubicleBUS it is also possible for the two different protection parameter sets held in the ETU55B and ETU76B electronic trip units to be switched over automatically in a few milliseconds. It is thus possible, for example, to automatically change the parameters of a coupling switch should the transformer infeed fail. One module each of this type can be used for holding the six items of digital information and for automatically switching over the parameters.
Digital output modules, configurable The configurable output module is available for higher-performance solutions. With this module, random events on the CubicleBUS can be switched directly to one of six available outputs or three of these outputs can be assigned with up to six events. In other words, up to six events can be placed on one physical output with OR operation. Either BDA/BDA Plus or Switch ES Power is used for configuring. A relay variant is also available here the same as for the output modules with rotary coding switch. Only one module of this type is possible per SENTRON 3WL.
ZSS modules (short-time grading control) The use of ZSS modules is recommended when Siemens circuit breakers are arranged in several staggered levels but full grading with the smallest possible delay is to be assured nevertheless. The circuit breakers are interconnected by these modules. In case of a short-circuit, each affected circuit breaker asks the circuit breakers directly downstream whether the short-circuit has also occurred in the next, lower level. The short-circuit is exactly localized as the result, and only the next upstream circuit breaker in the energy flow direction is switched off.
Analog output modules The analog output module can be used to output the following measured values to analog indicators in the control cabinet door: IL1, IL2, IL3, IN or UL12, UL23, UL31, UL1N or PL1, PL2, PL3, Stot or p.f.1, p.f.2, p.f.3, I% or favg, ULLavg, Ptot, p.f.avg Four 4-20-mA/0-10-V interfaces are available for this. The measured values to be output are selected with a rotary coding switch. By using the analog output module it is possible to do without additional converters and their conventional installation/ wiring in the main current path. Up to two modules of this type can be connected to one SENTRON 3WL.
ZSS modules (short-time grading control)
Siemens LV 1 T 2008
15/23
15
Siemens AG 2008
Technical specifications
Size Type Switching capacity class I 3WL11 N S II 3WL12 N S H III 3WL13 H C 3-pole C 4-pole
15
Icm
kA kA
50 42
66 50
66 50
80 75
100 85
100 85
100 100
100 100
Size II with In max 2500 A. Size II with In max = 3200 A and In max = 4000 A. At a rated voltage of 690 V the Icw value of the circuit breaker cannot be greater than the Icu or Ics value at 690 V. Rated operational voltage Ue = 1150 V.
15/24
Siemens LV 1 T 2008
Siemens AG 2008
and/ or
N S E 0 _ 0 0 0 6 1 a N S E 0 _ 0 0 0 6 2 a
h m a x . = 1 m m
3 0
3 0
3 0
3 0
N S E 0 _ 0 0 9 2 7 a
Unit(s) Copper bars, mm2 bare Unit(s) Copper bars, mm2 painted black Standard connection = strain-relief clamp Without end sleeve With end sleeve acc. to DIN 46228 Part 2 With twin end sleeve Optional connection = tension spring Without end sleeve With end sleeve acc. to DIN 46228 Part 2
IP20 without cabinet door, IP41 with door sealing frame, IP55 with cover 1 2 2 1 1 2 2 60 10 40 10 50 10 50 10 60 10 40 10 50 10 1 2 2 1 1 2 2 60 10 40 10 50 10 50 10 60 10 40 10 50 10 2 0.5 mm2 (AWG 20) ... 2 1.5 mm2 (AWG 16); 1 2.5 mm2 (AWG 14) 1 0.5 mm2 (AWG 20) ... 1 1.5 mm2 (AWG 16) 2 0.5 mm2 (AWG 20) ... 2 1.5 mm2 (AWG 16) 2 0.5 mm2 (AWG 20) ... 2 2.5 mm2 (AWG 14) 2 0.5 mm2 (AWG 20) ... 2 1.5 mm2 (AWG 16)
3 50 10 3 50 10
Position indicator switches Tension spring terminals Weights 3-pole Fixed-mounted circuit breakers Withdrawable circuit breakers 4-pole Guide frames Fixed-mounted circuit breakers Withdrawable circuit breakers Guide frames
1) 2)
56 60 31 67 72 37
56 60 31 67 72 37
56 60 31 67 72 37
50 54 30
50 54 30
67 72 37
67 72 37
Opening time on instantaneous short-circuit release with ETU15B = 85 ms. Make-time through closing solenoid for synchronization purposes (short-time excited) 50 ms.
Maintenance means: replace main contact elements and arc chutes (see Operator's Guide). Use of trip units from 20 C ETU76B with graphics display can be used up to max. 55 C.
Siemens LV 1 T 2008
15/25
15
Siemens AG 2008
B (except switching capacity class DC) C 25/+70 C 40/+70 A 2500 A 2500 A 2280 V 2000 25/+70 40/+70 3200 3020 2870 2000 25/+70 40/+70 3950 3810 3600 2000 25/+70 40/+70 4000 4000 4000 2000 25/+70 40/+70 5000 5000 5000 2000 25/+70 40/+70 5920 5810 5500 2000
CO 270 CO 520 ms ms 35 34
15
Electrical make-time (through closing solenoid)2) Electrical opening time (through shunt trip unit) Electrical opening time (instantaneous undervoltage trip unit) Opening time due to ETU, instantaneous short-circuit release Endurance Mechanical (without maintenance) Mechanical (with maintenance)3) Electrical (without maintenance) 1000 V version (without maintenance) Electrical (with maintenance)3) Switching frequency 690 V version 1000 V version Minimum interval between tripping operation by electronic trip unit and next making operation of the circuit breaker (only with automatical mechanical resetting of the lockout device) Mounting position
ms 100 ms 73 ms ms 73 501)
Operating cycles 10000 Operating cycles 15000 Operating cycles 7500 Operating cycles 1000 Operating cycles 15000 1/h 60 1/h 20 ms 80
3 0
3 0
and/ or
N S E 0 _ 0 0 0 6 1 a N S E 0 _ 0 0 0 6 2 a
h m a x . = 1 m m
3 0
3 0
N S E 0 _ 0 0 9 2 7 a
Degree of protection Main conductor Copper bars, Minimum cross-sections bare Copper bars, painted black Auxiliary conductors (Cu) Max. no. of auxiliary conductors cross-section (solid/stranded)
IP20 without cabinet door, IP41 with door sealing frame, IP55 with cover Unit(s) 2 mm2 100 10 Unit(s) 2 mm2 100 10 3 100 10 3 100 10 3 120 10 3 100 107) 4x 100 x 10 4 100 10 6x 100 x 10 6 100 10 6x 120 x 10 6 120 10
Standard connection = strain-relief clamp Without end sleeve With end sleeve acc. to DIN 46228 Part 2 With twin end sleeve Optional connection = tension spring Without end sleeve With end sleeve to DIN 46228 Part 2
2 0.5 mm2 (AWG 20) ... 2 1.5 mm2 (AWG 16); 1 2.5 mm2 (AWG 14) 1 0.5 mm2 (AWG 20) ... 1 1.5 mm2 (AWG 16) 2 0.5 mm2 (AWG 20) ... 2 1.5 mm2 (AWG 16) 2 0.5 mm2 (AWG 20) ... 2 2.5 mm2 (AWG 14) 2 0.5 mm2 (AWG 20) ... 2 1.5 mm2 (AWG 16) 1 0.5 mm2 (AWG 20) ... 1 2.5 mm2 (AWG 14) kg kg kg kg kg kg 59 63 39 71 76 47
4) 5) 6) 7)
Tension spring terminals Fixed-mounted circuit breakers Withdrawable circuit breakers Guide frames Fixed-mounted circuit breakers Withdrawable circuit breakers Guide frames
4-pole
1) 2)
64 68 45 77 82 54
82 88 60 99 106 84
82 88 60 99 106 84
Opening time on instantaneous short-circuit release with ETU15B = 85 ms. Make-time through closing solenoid for synchronization purposes (short-time excited) 50 ms. 3) Maintenance means: replace main contact elements and arc chutes (see Operator's Guide).
Use of trip units from 20 C. ETU76B with graphics display can be used up to max. 55 C. 4000 A, size II in fixed-mounted version, 3-pole. Minimum main conductor cross-sections for 4-pole withdrawable circuit breakers: 3 x 120 x 10 mm.
15/26
Siemens LV 1 T 2008
Siemens AG 2008
Power consumption Minimum command duration at Us for the closing solenoid Short-circuit protection Smallest permissible DIAZED fuse (gL operational class)/ miniature circuit breaker with C characteristic
Power consumption of motor Time required to charge the stored-energy mechanism at 1 Us Closing solenoid For motor and closing solenoid
Short-circuit protection Smallest permissible DIAZED fuse (gL operational class)/ miniature circuit breaker with C characteristic; Motor and closing solenoid for the same rated control supply voltages Smallest permissible DIAZED fuse (gL operational class)/ miniature circuit breaker with C characteristic (for different rated control supply voltages) At Us = 24 ... 30 V At Us = 48 ... 60 V At Us = 110 ... 125 V DC/ 110 ... 127 V AC At Us = 220 ... 250 V DC/ 208 ... 240 V AC
2A 2A 1A 1A
V 110 ... 127/208 ... 240/380 ... 415 V 24/30/48/60/110/220 ... 2501) V 110 ... 127; 208 ... 240; 380 ... 415 V 48; 110 ... 125; 220 ... 250 VA 50/5 CO 50/5 ms 200 ms 80 ms 200 s 0.2 ... 3.2 ms 100 1 A TDz (slow) 1 A
AC DC
Siemens LV 1 T 2008
15/27
15
Siemens AG 2008
V 110; 230 V 24; 30; 48; 60; 110; 220 VA/W 15/15 ms 60 ms 80 1 A TDz (slow)/1 A
- short-circuit protection Smallest permissible DIAZED fuse (gL operational class)/ miniature circuit breaker with C characteristic 5 % ON period - response value - operating range - extended operating range for battery operation - rated control supply voltage Us - power consumption At 24 V DC, 48 V DC 60 V DC, 110 V DC 220 V DC AC 50/60 Hz DC AC/DC AC/DC Pickup
> 0.7 Us (circuit breaker is tripped) 0.85 ... 1.1 Us 0.7 ... 1.26 Us
V 110 ... 127; 208 ... 240 V 24; 48; 110 ... 125; 220 ... 250 VA/W 15/15 ms 25 ms 50 1 A TDz (slow)/1 A
15
- short-circuit protection Smallest permissible DIAZED fuse (gL operational class)/ miniature circuit breaker with C characteristic With stored energy feature consisting of shunt trip unit and capacitor storage device - rated control supply voltage Us - operating range - power consumption - storage time at Us/ recharging time at Us - opening time of circuit breaker, short-circuit protection AC/DC AC 50/60 Hz DC
V 110; 230 V 110; 220 0.85 ... 1.1 Us VA/W 1/1 Max. 5 min/min. 5 s As with "for continuous command"
Contact position-driven auxiliary switches (S1, S2, S3, S4, S7, S8)
Rated insulation voltage Ui Rated operational voltage Ue Rated impulse withstand voltage Uimp Switching capacity Alternating current 50/60 Hz - rated operational voltage Ue - rated operational current Ie /AC-12 Ie/AC-15 - rated operational voltage Ue - rated operational current Ie/DC-12 Ie/DC-13 V AC/DC 500 V AC/DC 500 kV 4 V 24 ... 230 A 10 A 4 V 24 A 10 A 8 48 8 4 380/400 10 3 110 3.5 1.2 500 10 2 220 1 0.4
DC current
Short-circuit protection
Largest permissible DIAZED fuse (gL operational class) Largest permissible miniature circuit breaker with C characteristic Alternating current DC current - rated operational voltage Ue - rated operational current Ie - rated operational voltage Ue - rated operational current Ie
Short-circuit protection
Tripped signaling switch (S24) and alarm switch for auxiliary trip units (S22, S23) (according to DIN VDE 0630)
Switching capacity Alternating current DC current Short-circuit protection "Tripped" alarm switch - rated operational voltage Ue - rated operational current Ie/AC-12 - rated operational voltage Ue - rated operational current Ie/DC-12 V 250 A 8 V 24 A 6 6 A Dz (quick) Until manual or electrical remote-controlled reset (option) 125 0.4 250 0.2
Largest permissible DIAZED fuse (gL operational class) Signal duration after tripping
15/28
Siemens LV 1 T 2008
Siemens AG 2008
Rated insulation voltage Ui Rated operational voltage Ue Rated impulse withstand voltage Uimp Switching capacity Rated operational current Ie
Siemens LV 1 T 2008
15/29
15
Siemens AG 2008
ETU25B D -0.4-0.45-0.5-0.55-0.60.65-0.7-0.8-0.9-1 -10 s fixed --at tsd = 20 ms (M) --- -1.25-1.5-2-2.5-3-4-6-8-10-12 0-M-100-200-300-400 ms --- -fixed for Ii 20 In, max. 50 kA ------------------ -------------------
ETU27B D&S -0.4-0.45-0.5-0.55-0.60.65-0.7-0.8-0.9-1 -10 s fixed --at tsd = 20 ms (M) 1 -1.25-1.5-2-2.5-3-4-6-8-10-12 0-M-100-200-300-400 ms --- -fixed for Ii 20 In, max. 50 kA fixed mounted - - -A-B-C-D-E -100-200-300-400-500 ms --------- -----------------
Setting range for time-lag class tR at I2t 10 s fixed Setting range for time-lag class tR at I4t -R Thermal image can be switched on/off -Phase failure sensitivity -Neutral conductor protection -Function can be switched on/off -N conductor setting range IN = In ... -Short-time delayed short-circuit protection -Function can be switched on/off -Setting range Isd = In ... -s d Setting range for delay time tsd -Switchable short-time delayed short-circuit protection -s d (I2t-dependent function) Setting range for delay time tsd at I2t -Zone Selective Interlocking function -i Instantaneous short-circuit protection N S E 0 _ 0 0 8 8 8 b Function can be switched on/off -Setting range Ii = In ... 2-3-4-5-6-7-8 Ground-fault protection -Tripping and alarm function -Tripping function can be switched on/off -Alarm function can be switched on/off -Detection of the ground-fault current through summation -current formation with internal or external neutral g conductor transformer Detection of ground-fault current through external -transformer g Setting range of the operating current Ig for release -Setting range of the operating current Ig for alarm -N S E 0 _ 0 0 8 8 9 a Setting range of the delay time tg -Switchable ground-fault protection characteristic curve -(I2t-dependent function) Setting range for delay time tg at I2t -Zone Selective Interlocking ground-fault protect. function -Parameter set switchover Switchable between parameter set A and B -LCD Alphanumeric LCD (4-line) -Graphical LCD (24 V, external power supply required) -Communication CubicleBUS integrated -Communication-capable through PROFIBUS DP -Measurement function Measurement-function capable with measurement -function Plus LED display Electronic trip unit active Alarm ETU fault L-release -S-release -I-release -N-release -NSE00890 G-release -G-alarm -Release through extended protection function -Communication -Signals from signaling switches with external CubicleBUS modules (relays) Overload warning -Load shedding, load receiving -Leading signal overload trip 200 ms -Temperature alarm -Phase unbalance -Instantaneous short-circuit release -Short-time delayed short-circuit release -Overload trip -Neutral conductor release -NSE00891 Ground-fault protection release -Ground-fault alarm -Auxiliary relay -ETU fault --
N S I
15
Delay time figures given in ms. M = Motor protection, corresponds to 20 ms. D = Rotary coding switch D & S = Rotary coding and slide switch K = Communication M/K = Menu/communication
optional.
For the setting range of the operating current Ig see page 15/31.
15/30
Siemens LV 1 T 2008
Siemens AG 2008
Switchable overload protection (I2t- or I4t-dependent function) Setting range for time-lag class tR at I2t 2-3.5-5.5-8-10-14-17-21-25-30 s Setting range for time-lag class tR at I4t 1-2-3-4-5 s Thermal image can be switched on/off Phase failure sensitivity at tsd = 20 ms (M) Neutral conductor protection Function can be switched on/off N conductor setting range IN = In ... 0.5 ... 1 Short-time delayed short-circuit protection Function can be switched on/off Setting range Isd = In ... 1.25-1.5-2-2.5-3-4-6-8-10-12 Setting range for delay time tsd M-100-200-300-400 ms Switchable short-time delayed short-circuit protection (I2t-dependent function) 2 Setting range for delay time tsd at I t 100-200-300-400 ms Zone Selective Interlocking function by CubicleBUS-Modul Instantaneous short-circuit protection Function can be switched on/off Setting range Ii = In ... 1.5-2.2-3-4-6-8-10-12-0.8 x Ics Ground-fault protection Module can be retrofitted Tripping and alarm function Tripping function can be switched on/off Alarm function can be switched on/off -Detection of the ground-fault current through summation current formation with internal or external neutral conductor transformer Detection of ground-fault current through ext. transformer Setting range of the operating current Ig for release A-B-C-D-E A-B-C-D-E Setting range of the operating current Ig for alarm Setting range of the delay time tg 100-200-300-400-500 ms Switchable ground-fault protection characteristic curve (I2t-dependent function) Setting range for delay time tg at I2t 100-200-300-400-500 ms Zone Selective Interlocking ground-fault protect. function by CubicleBUS-Modul Parameter set switchover Switchable between parameter set A and B -LCD Alphanumeric LCD (4-line) Graphical LCD (24 V, external power supply required) -Communication CubicleBUS integrated Communication-capable through PROFIBUS DP Measurement function Measurement-function capable with measurement function Plus LED display Electronic trip unit active Alarm ETU fault L-release S-release I-release N-release (only with ground-fault protection module) G-release G-alarm (only with ground-fault protection module) Release through extended protection functions Communication Signals from signaling switches with external CubicleBUS modules (relays) Overload warning Load shedding, load receiving Leading signal overload trip 200 ms Temperature alarm Phase unbalance Instantaneous short-circuit release Short-time delayed short-circuit release Overload trip Neutral conductor release Ground-fault protection release (only with ground-fault protection module) Ground-fault alarm (only with ground-fault protection module) Auxiliary relay ETU fault Setting range of the operating current Ig Size I and size II Size III A 100 A 400 A B 300 A 600 A C 600 A 800 A D 900 A 1000 A E 1200 A 1200 A
Increment size for adjustment of M From ... to Increment size From ... to 0 ... 1 0.1 1000 ... 1600 1 ... 100 1 1600 ... 10000 100 ... 500 5 10000 ... max 500 ... 1000 10
Siemens LV 1 T 2008
15/31
15
Siemens AG 2008
Characteristic curves2)
Every electronic trip unit type and every setting has its own characteristic. Only a selection is shown in the following. The characteristic curves each show the largest and smallest setting range of SENTRON 3WL circuit breakers with 1000 A rated current at 500 V rated voltage with various trip units. In order to obtain a complete tripping characteristic, the relevant parts of the characteristics have to be combined. The characteristic curves show the behavior of the electronic trip unit when it is activated by a current that is already flowing before the tripping operation. If the overcurrent tripping occurs immediately after switch on and the electronic trip unit is therefore not yet enabled, the opening time is extended, depending on the level of the overcurrent by up to 15 ms. In order to determine the break-times of the circuit breakers, approximately 15 ms must be added to the opening times shown for the arcing time. Refer to the following legend for tolerances. The characteristic curves shown apply to ambient temperatures at the circuit breaker between -5 and +55 C. The trip unit can be operated at ambient temperatures of -20 to +70 C. An extended tolerance band can apply at these temperatures.
NSE0_01520
R min
R max
1000
Opening time
100
10
1 0,1
i min
i max
2 ... 8 x
0,01 0,1 1 10 /
n
100
R min
R max n
R min
R max n N
1000
1000
15
100
100
10
sd min sd max n
sd max sd min
10
sd min sd max
1 0,1
1,25 ... 12 x
1 0,1
1,25 ... 12 x
sd max
sd min
0 ... 0,4 s
i
0 ... 0,4 s
i
i > 20 x n max. 50 kA
i > 20 x n max. 50 kA
0,01 0,1 1 10 /
n
100
SENTRON 3WL circuit breaker with ETU25B electronic trip unit, LSI characteristic curve
NSE0_01521
SENTRON 3WL circuit breaker with ETU27B electronic trip unit, LSIN characteristic curve
NSE0_01523a
10000
Opening time [s]
1000
1000
sd
n sd =
100
g min g max
const
10
10
1 const 0,1
sd =
const
0,01 100
100
SENTRON 3WL circuit breaker with ETU27B electronic trip unit, G characteristic curve Tolerances for the set currents L : Tripping operations between 1.05 and 1.2 x IR S : 0 %, +20 % I : 0 %, +20 % G : 0 %, +20 % Tolerances for the tripping times L : 20 %, +0 % for I2t characteristic curve S : 0 %, +60 ms or 0 %, +10 % for characteristic curve with fixed delay time I : < 50 ms G : 0 ms, +60 ms or 0 %, +10 % for characteristic curve with fixed delay time
SENTRON 3WL circuit breaker with ETU45B electronic trip unit, S characteristic curve
1) 2)
Sizes I and II: 100 ... 1200 A Size III: 400 ... 1200 A. With single-pole loading in the lowest rated current range, the response times of the short-circuit release can be extended by approx. 10 % and the tripping times by approx. 15 % compared to the charactreristic curve.
15/32
Siemens LV 1 T 2008
NSE0_01519
10000
10000
NSE0_01527
10000
[s]
Siemens AG 2008
1000
100
g
= const
10
1
g
0,1
SENTRON 3WL circuit breaker with ETU45B, ETU55B and ETU76B electronic trip unit, G characteristic curve
NSE0_01526a
1000 1,25 x
= const
NSE0_01522a
sd n ... 0,8
100
cw
1000
n 2
= const
10
2 sd =
10
1 const 0,1
sd =
const
0,02 ... 4 s
0,01 0,1 1 10 /
n
100
SENTRON 3WL circuit breaker with ETU55B and ETU76B electronic trip unit, S characteristic curve
SENTRON 3WL circuit breaker with ETU45B, ETU55B and ETU76B electronic trip unit, L characteristic curve
NSE0_01524a
Further characteristic curves are shown in the manual and the planning and configuring tool SIMARIS deSign, or ask your Siemens contact person.
Tolerances for the set currents L : Tripping operations between 1.05 and 1.2 IR S : 0 %, +20 % I : 0 %, +20 % G : 0 %, +20 % Tolerances for the tripping times L : 20 %, +0 % for I2t characteristic curve S : 0 %, +60 ms or 0 %, +10 % for characteristic curve with fixed delay time I : < 50 ms G : 0 ms, +60 ms or 0 %, +10 % for characteristic curve with fixed delay time
1000
100
10
1
i
0,1
1,5 x
n ... 0,8
cs
0,01 0,1 1 10 / n 1 /
cs
SENTRON 3WL circuit breaker with ETU45B, ETU55B and ETU76B electronic trip unit, I characteristic curve
1)
Sizes I and II: 100 ... 1200 A Size III: 400 ... 1200 A.
Siemens LV 1 T 2008
15/33
15
100
Siemens AG 2008
Dimensional drawings
Voltage transformer for SENTRON 3WL
260
125
1 6 8 8 ,9 R 1 3 ,1 2 2 1 8
4 0
2 2 8 1 9 6 ,8
87
5 1
Current transformers for overload protection in the neutral conductor External transformers for neutral conductor with copper connection pieces
Size I, 3WL9 111-0AA31-0AA0
1 5 4 1
3 6 7 0 8 3
5 4 1 1 5 1 3 1
1 3 ,5
R 6 5 ,5
2 7
N S E 0 _ 0 1 3 7 6
4 4
2 4
8 8 9 5 1 1 3 3
1 3 0 6 8 5 1
N S E 0 _ 0 0 6 0 6 b
1 7 0
5 1
9 1
15
5 5 8 3
1 6 1 1 0 7 1 2 3
N S E 0 _ 0 1 3 7 7
3 0 1 3 ,5 4 4
3 0
3 1 0
3 1
5 0 ,5
4 5
R 1 5
N S E 0 _ 0 1 3 7 5
NSE0_01103b
1 6 0 1 8 4 2 4 1 7 0
5 1
1 3 0 6 8 5 1
N S E 0 _ 0 0 6 0 7 b
9 1
9 0 1 1 3
3 0
3 0
3 1 0
5 2
2 4 0
1 3 0 6 8 5 1
2 4
9 1
1 7 0
N S E 0 _ 0 0 1 6 4 c
Door cut-out for operator panel using the door sealing frame
N S E 0 _ 0 0 6 0 8 b
3 4 0
1 6 0 1 8 4
3 1 4 3 0 0 4 0 3 ) R 5 2 )
R 5
5 ,5
3 5 0
1 4 0
1 4 0
4 )
1 7 5
4 0 5 ,5
1 2 0
1) Mounting surface
1 1 ,5
2) Center SENTRON 3WL operator panel 3) 8 mounting holes for door sealing frame 4) 3 mounting holes for door interlocking
6 5
1 )
1 2 2 1 4 0
15/34
Siemens LV 1 T 2008
1 8 0
1 8 5
Siemens AG 2008
85
295-300
72
70
Switch mounting level 341 Mounting surface for switch or guide frame Circuit breaker mounting level
68
435
17
313
148
02) 02) 0 0 0
02) 02) 0 0 0
02) 02) 0 0 0
14 14
50 200
14 14
Value for plate; 0 mm for struts and grids. 40 mm (size II: 70 mm) for plates which cover the lateral openings in the guide frame.
All safety clearances above the circuit breaker refer to the upper edge of the auxiliary connector - not to the upper edge of the arc chute! See dimensional drawings on pages 15/36 to 15/42, parts 4) and 5).
Siemens LV 1 T 2008
15/35
15
Siemens AG 2008
13,5
55
55
55
55
275 439,5
434
NSE00613b
421
3)
35
11)
e
NSE00611
26
8 2
60 90
90
90
8 ) 3 3 ,5
N S E 0 _ 0 0 6 1 5 c
40
9 ) 6 0 ,5
13,5 4 7 55 55 55 55
5 4 1 ,5 4 6 1 ,5
NSE00616b
421
3)
80
11)
3 ) 2 7 5 5 ,5 2 0
3 2 7 ,5
1 5 0
15
7 6
N S E 0 _ 0 0 6 1 4 c
40 14
4 5 1 3 0 1 5 0 2 1 0 2 3 0
c 6 ) 1 0 6 1 2 7
8 2
60 90
90
90
Vertical connection
90 35 55 90 90 60 13,5
1 1 )
3 5
NSE00619
11) 7) 3) 7)
6 0
2 6 7 ,5
3 0
3)
N S E 0 _ 0 0 6 1 8 c
M8
NSE00617a
1 2 7 ,5
58
1 3 ,5
1 1 3 ,5 1 2 8 ,5
60
90
90
90
NSE00620
3)
60
90
90
90
4-pole version 1) Mounting space for removal of the arc chutes. 2) Space above arc chute, space for electrical auxiliary circuit connections. 3) Grooves (4 mm wide, 5 mm deep) for supporting phase barriers in the system. 4) Auxiliary connector with screw connections (SIGUT). 5) Auxiliary connector with screwless connection method (tension spring). 6) Dimension to inside surface of the closed cabinet door. 7) Fixing points for mounting the circuit breaker in the system. 8) "Secure OFF" locking device. 9) Key operation. 11) Terminal face. Rated a circuit breaker current A up to 1000 1250 ... 1600 10 15 10 15 10 15 11 6 451 461 34 39 541 551 b c d e f g
For safety clearances to grounded parts and to live parts see page 15/35.
15/36
Siemens LV 1 T 2008
80
35
15 10
123,5
Siemens AG 2008
320 270 5)
3 5 0 5 5 1 3 ,5
N S E 0 _ 0 0 6 2 3 b
4)
2 6 0 5 5
5 5
5 5 3 5 1 1 ) 2 8 7
275 465,5
403
3 7 3
3 )
123,5
10)
13 210 300
N S E 0 _ 0 0 6 2 4 b
30 55
11
169,5
7 )
8 ) 9 )
2 6
3 5 0 1 3 ,5
4 0
5 5
2 6 0 5 5
5 5
5 5
8 0
3 )
a
2 7 5
3 2 7 ,5
4 6 0
493
1 5 0 3 1
6
3 7 3
N S E 0 _ 0 0 6 2 6 b
1 0 ) 2 7 4 2 2 2 0 3 6 7 ,5 3 8 2 ,5 4 5 5 8 8 8 ,5 1 2 1 ,5 1 4 0 ,5
4 0
7 6
2 8 7
1 1 )
3 5
1 5
9 0
9 0
9 0
6 9
34
6 )
c 38
169,5
4 0
1 4
1 5
9 0 3 5 0 2 6 0 b
9 0
9 0
Vertical connection
11)
55
55
55
55
13,5 11)
NSE00627a
267,5 127,5
30
N S E 0 _ 0 0 6 2 9 a
13,5
38
60
3 )
68 25
NSE00628a
150 165
1 5
NSE00630
9 0
9 0 2 6 0 5 5
9 0 3 5 0
N S E 0 _ 0 0 6 3 2 a
Flange connection
14
NSE00631
5 5 M 1 2 3 3
5 5
5 5
3)
6 9
2 8 7
5 9
8 0
2 8 2 ,5
3 ) 1 4 2 ,5 5 9
10) 55
15 90
90
90
1 5
9 0
9 0
9 0
4-pole version 3) Grooves (4 mm wide, 5 mm deep) for supporting phase barriers in the system. 4) Auxiliary connector with screw connections (SIGUT). 5) Auxiliary connector with screwless connection method (tension spring). 6) Dimension to inside surface of the closed cabinet door. 7) SENTRON 3WL in connected position. 8) SENTRON 3WL in test position. 9) SENTRON 3WL in disconnected position. 10) Fixing holes 9 mm. 11) Terminal face. Rated circuit breaker current A up to 1000 1250 ... 1600 10 15 10 15 10 15 a b c
For safety clearances to grounded parts and to live parts see page 15/35.
Siemens LV 1 T 2008
6 9
10)
121
2 8 7
2 6
6 9
15/37
15
Siemens AG 2008
40
275 435,5
434
421
6 e
NSE00635c
4 7
90
90
90
90
123,5
3)
NSE00633
26
10 85 c 8 2 d
90
130
130
130
40
1 ) 2 )
90 40
90
90 40
90 80
5 4 1 ,5 4 6 1 ,5
N S E 0 _ 0 0 6 3 7 d
3 ) 2 7 5
6 g
1 5 0 a
7 6
15
40
N S E 0 _ 0 0 6 3 6 d
5 ,5 4 5 1 3 0 1 5 0 2 1 0 2 3 0
90 130
130
130
13,5
6 ) 1 0 6 1 2 7
8 2
3 5
7 )
1 3 ,5
3 )
1 1 ) 7 ) 290 98
30
3)
4 9
N S E 0 _ 0 0 6 3 9 d
134,5
1 3 9 4 6 0 5 9 0
1 2 8
NSE00640b
11)
NSE00642
1)
3)
2) 85 Nm
30
13,5
NSE0_01868
90
130
130
130
4-pole version 1) Mounting space for removal of the arc chutes. 2) Space above arc chute, space for electrical auxiliary circuit connections. 3) Grooves (4 mm wide, 5 mm deep) for supporting phase barriers in the system. 4) Auxiliary connector with SIGUT screw terminals. 5) Auxiliary connector with tension spring connection. 6) Dimension to inside surface of the closed cabinet door. 7) Fixing points for mounting the circuit breaker in the system. 11) Terminal face. c d e f g
10 20 20
11 6 6
80
2 0 f
14
NSE00638c
3 2 7 ,5
421
3)
34 39 39
35
For safety clearances to grounded parts and to live parts see page 15/35.
15/38
Siemens LV 1 T 2008
Siemens AG 2008
62,5
NSE00644b
9 0 4 0 1 3 ,5
4 0 0 9 0 4 0
9 0
9 0
N S E 0 _ 0 0 6 4 5 c
5 3 0
275 465,5
461
403
6 3 )
3 7 3 2 8 7 6 9
1 1 )
123,5
10) 480
270 350
40 55
10)
11
c 169,5
2 6
5 5
1 2 )
4 5 ,1 1 3 0
1 3 0
1 3 0
N S E 0 _ 0 0 6 4 6 d
7 )
8 ) 9 )
1 3 ,5
62,5
9 0 4 0
4 0 0 9 0 4 0
9 0
9 0
4 0 ,5
N S E 0 _ 0 0 6 4 8 c
5 3 0
4 0
3 2 7 ,5 5 1 7
4 6 0
493
3 )
2 7 5
3 7 3
1 5 0
3 1 4 0
6 )
2 7 4 2
5 5 4 5
1 3 0
1 3 0
1 3 0
4 0
30
30 38
11) 38 30 30
5 3 0 4 0 0 b
N S E 0 _ 0 0 6 5 1 a
13,5
11)
NSE00649a
3 ) 290 100 2 8 7
138 95
135
157 172
5 5 4 5
1 3 0
1 3 0
1 3 0
100
NSE0_01869
3)
315,5
109,5
30
30
90
90
90
90
10)
4,6 55 200 45
10 20 130 200
4-pole version 3) 4) 5) 6) 7) 8) 9) 10) 11) 12) Grooves (4 mm wide, 5 mm deep) for supporting phase barriers in the system. Auxiliary connector with SIGUT screw terminals. Auxiliary connector with tension spring connection. Dimension to inside surface of the closed cabinet door. SENTRON 3WL in connected position. SENTRON 3WL in test position. SENTRON 3WL in disconnected position. Fixing holes, diameter 9 mm. Terminal face. Top edge of circuit breaker only 1000 V AC version. Rated circuit breaker current A up to 2000 2500 3200/4000 10 15 30 10 15 30 10 20 20 a b c
For safety clearances to grounded parts and to live parts see page 15/35. Flat connectors (see following page)
6 9
Siemens LV 1 T 2008
15/39
15
3 6 7 ,5 3 8 2 ,5
c 169,5
1 4
2 2 0
4 5 5 8 8 8 ,5 1 2 1 ,5 1 4 0 ,5
7 6
1 0 )
34
8 0
6 9
2 8 7
1 1 )
8 0
3 5
3 5
Siemens AG 2008
5 3 0 4 0 0 M 1 2
3 3
9 0
4 0
2 6
2 8 2 ,5
1 4 2 ,5
5 9
121 4 5 1 3 0 1 3 0 1 3 0
4-pole version 3) Grooves (4 mm wide, 5 mm deep) for supporting phase barriers in the system.
For safety clearances to grounded parts and to live parts see LV 1T, page 15/35. For more connection options see previous page.
15
15/40
Siemens LV 1 T 2008
6 9
2 8 7
3 )
5 9
N S E 0 _ 0 0 6 5 4 a
Siemens AG 2008
50
451
421
NSE00657c
3)
434
35 11)
N S E 0 _ 0 0 6 6 0 c
47
160
160
160
160
123,5
890
11
270 680
20 82
130
210
210
210
4 7
1 3 ,5 4 0
1 6 0 5 0 5 0
1 6 0 5 0 5 0
1 6 0
1 6 0
3 0
5 4 1 ,5 4 6 1 ,5
3 ) 2 7 5 2 0
N S E 0 _ 0 0 6 5 9 d
3 2 7 ,5
5 4 1
4 2 1
3 )
8 0 1 1 ) 7 6 5 ,5 4 5 1 3 0 1 5 0 2 1 0 2 3 0
1 5 0 3 0
3 4
N S E 0 _ 0 0 6 5 8 d
1 4
8 0
35
205
12
26
6 ) 1 0 6 1 2 7
8 2
Vertical connection
3 0 1 6 0 1 5 1 3 0 15 30 2 1 0 2 1 0 2 1 0 3 5 107 20 10
NSE00663
7 )
1 3 ,5
N S E 0 _ 0 0 6 6 1 d
9 1 4
13,5
142 162
NSE00664a
3)
130
210
210
210
130
4-pole version 1) Mounting space for removal of the arc chutes. 2) Space above arc chute, space for electrical auxiliary circuit connections. 3) Grooves (4 mm wide, 5 mm deep) for supporting phase barriers in the system. 4) Auxiliary connector with SIGUT screw terminals. 5) Auxiliary connector with tension spring connection. 6) Dimension to inside surface of the closed cabinet door. 7) Fixing points for mounting the circuit breaker in the system. 11) Terminal face.
For safety clearances to grounded parts and to live parts see page 15/35.
NSE00662a
1 3 9 7 0 4
2 4 8
94,5 120
330,5
3 )
1 1 ) 7 )
11)
40
3)
4 0
2 0
1 3 0
2 1 0
2 1 0
2 1 0
40
85
210
210
210
Siemens LV 1 T 2008
15/41
15
Siemens AG 2008
62,5
NSE00666b
1 3 ,5
1 6 0 5 0
6 3 0 1 6 0 5 0
1 6 0
1 6 0
N S E 0 _ 0 0 6 6 7 c
8 4 0
275 466,5
461
123,5
403
6 3 7 3 2 8 7 6 9 2 8 7 6 9 20 169,5 1 1 )
10)
10) 800
270 590
160 57
10) 11
5 7 1 2 )
N S E 0 _ 0 0 6 6 8 b
5 9 0 8 0 0 8 4 0
62,5
1 3 ,5
7 )
4 0
8 ) 9 )
1 6 0 5 0
6 3 0 1 6 0
1 6 0 5 0
1 6 0
NSE00669b
3 0
N S E 0 _ 0 0 6 7 0 c
2 6
3 2 7 ,5 5 1 7
4 6 0
3 ) 3 0
493
2 7 5
1 5 0
7 6
1 0 ) 3 1 4 0 4 0 ,5 2 7 4 2 3 6 7 ,5 3 8 2 ,5 2 2 0 4 5 5 8 8 8 ,5 1 2 1 ,5 1 4 0 ,5 6 )
1 4
3 7 3
1 1 )
15
20 169,5
34
8 5 5 7
2 1 0
5 9 0
2 1 0 8 0 0
2 1 0
4 0
30
8 4 0 2 0 1 0 6 3 0 7 0 4
N S E 0 _ 0 0 6 7 3 b
11)
NSE00671a
914
13,5
5 7
a b
5 9 0
b 8 0 0 9 1 4
2 1 0
160
160
160
NSE00675
8 4 0 1 6 0 M 3 3 1 2 1 6 0 1 6 0
N S E 0 _ 0 0 6 7 6 a
6 3 0 7 0 4 1 6 0
6 9 5 9 2 8 2 ,5 1 4 2 ,5 2 6 5 7 8 5 3 0 2 1 0 2 1 0 5 9 0 8 0 0 9 1 4 2 1 0
260 217
24 177 197
2 8 7
57 85
210
210
210
121
4-pole version 3) Grooves (4 mm wide, 5 mm deep) for supporting phase barriers in the system. 4) Auxiliary connector with SIGUT screw terminals. 5) Auxiliary connector with tension spring connection. 6) Dimension to inside surface of the closed cabinet door. 7) SENTRON 3WL in connected position. 8) SENTRON 3WL in test position. 9) SENTRON 3WL in disconnected position. 10) Fixing holes, diameter 9 mm. 11) Terminal face. 12) Top edge of circuit breaker only 1000 V AC version.
a 40 40 5
For safety clearances to grounded parts and to live parts see page 15/35.
15/42
Siemens LV 1 T 2008
6 9
5 9
2 8 7
8 0
8 0
3 5
8 5
2 1 0
2 1 0
2 1 0
3 5
Siemens AG 2008
Schematics
Terminal assignment diagram
optional Zubehr / Accessories (Hilfsschalter S1, S2 = Standard) (Auxiliary switch S1, S2 = Standard) Interne Beschaltung Internal wiring Klemmen Terminals Externe Beschaltung External wiring L / L+ N / L 14 13 12 11 10 9 8 7 6 5 4 3 2 1 s/ c
Fern-Rcksetzmagnet / Remote reset bell alarm & tripped indicator F7 G-Wandler / G transformer S2 G-Wandler / G transformer S1 N-Wandler / N sensor S2 N-Wandler / N sensor S1 ext. Spannungswandler Stern / ext. voltage transformer Com ext. Spannungswandler / ext. voltage transformer L3 ext. Spannungswandler / ext. voltage transformer L2 ext. Spannungswandler / ext. voltage transformer L1 0 V DC 24 V DC
Nicht vorhanden bei Kommunikationsfunktion "F02" oder F12. Auf der Position von "-X7" befindet sich das Modul COM15/COM16.
z.B. Wandler im TransformatorSternpunkt oder Summenstromwandler 1200 A /1 A e.g. current transformer in the star point of power transformer or a summation current transformer 1200 A /1A Brcke, wenn kein N-Wandler Short terminals if no N-sensor L1 L2 L3 N 24 V DC input Abschlusswiderstand, wenn kein externes CB-modul! Termination resistor, if not external CB-module!
BUS + BUS
Not available with communication connection "F02" or F12. COM15/COM16 module is at position "-X7".
10 9 8 7 6
Close +
Speicherzustandsmeldung / "Spring charged" signal S21 Elektrisch "EIN" / Local electric close S10
11
External
4 3 2 1
Meldeschalter am zweiten Hilfsauslser / S23 Signaling contact at the 2nd auxiliary release
Internal
IN
Free +
L / L+
s/ c
Erster Hilfsauslser F1 "f" / 1st auxiliary release F1 "ST" S1 "S" / "NO" S1 "" / "NC" Einschaltmagnet / Closing solenoid
14 13 12 11 10 9 8 7 6 5 4 3 2 1
L / L+ N / L c
N / L L / L+ c
nur F4 "Schnell AUS" / F4 only "quick OFF" nur F4 "Schnell AUS" / F4 only "quick OFF" Zweiter Hilfsauslser: F2 "ST", F3 "UVR", F4 "UVR td" / 2nd auxiliary release: F2 "ST", F3 "UVR", F4 "UVR td" S3 "S" oder S7 "S" / S3 "NO" or S7 "NO" S3 "" oder S7 "S" / S3 "NC" or S7 "NO" S4 "S" oder S8 "S" / S4 "NO" or S8 "NO" S4 "" oder S8 "S" / S4 "NC" or S8 "NO"
NSE0_00605 o
14 13 12 11 10 9 8 7 6 5 4 (sw) M (br) 3 2 1
Motorantrieb / Charging motor opt.: Motorabstellschalter / opt. motor main switch S12
L / L+ N / L
Siemens LV 1 T 2008
15/43
15
Y1
12
1 2 3 4 5 6 7 8 9
Ausgelst-Meldeschalter (Stellung nach Auslsung) / trip signalling switch S24 (position after tripping)
14 13
/COM16
(Option F02/F12)
Siemens AG 2008
with "UVR" undervoltage trip unit (F3), with "ST" shunt trip unit (F1), with tripped signaling switch (option K07), with auxiliary switch 4 NO + 4 NC.
release contact
OFF
ON -X7.12 -X7.14 -X6.12 -X6.10 -X6.14 -X5.12 -X6.4 -X6.2 -X5.10 -X5.8 -S3 -S4 -X6.6 -X5.2 -X6.7 -X7.9 -X5.6 -X5.4 -X5.5 -X5.3
NSE0_01558b
-A1 -S10
version
L S I N N G
ETU
electr. ON
QS M mech. ON
15
mech. OFF
-X6.11
-X6.3 -X6.1
-X5.9
-X6.13
-X5.11
-X7.13
-X5.1
-X8.9
N (L-)
N (L-)
-X8.10
-X6.8
-X6.5
Electronic trip unit ETU 1st auxiliary switch block (2 NO + 2 NC) 2nd auxiliary switch block (2 NO + 2 NC) 2nd auxiliary switch block, S7 (2 NO) can be used if there is no S3 - S3 and S7 have the same terminal assignment/mounting space 2nd auxiliary switch block, S8 (2 NO) can be used if there is no S4 - S4 and S8 have the same terminal assignment/mounting space 3WL1. ..-.....-...2 3WL1. ..-.....-...4 3WL1. ..-.....-...7 3WL1. ..-.....-...8 (2 NO + 2 NC) S1+S2 (4 NO + 4 NC) S1+S2+S3+S4 (6 NO+ 2 NC) S1+S2+S7+S8 (5 NO + 3 NC) S1+S2+S3+S8
-S10 -S11 -S12 -S20 -S24 -F1 -F3 -F5 -M -P -QS -Q1 -T1/-T2/-T3 -X5/-X6/-X7/-X8 -Y1 -R -X8.9/-X8.10
Electrical ON button Internal motor shutdown switch (if spring is tensioned) Motor shutdown switch (no automatic tensioning of spring) Ready-to-close signaling switch Tripped signaling switch 1st auxiliary trip unit shunt trip unit 2nd auxiliary trip unit shunt trip unit Tripping solenoid Motor for "charging store" Stored-energy mechanism Actuator lever for "stored-energy feature" Main contacts Current transformers Terminals Closing solenoid Indicator and reset button for electronic trip unit Connection option: external neutral conductor transformer
NSE0_01559c
15/44
Siemens LV 1 T 2008
-X6.9
-X5.7
2 4
1 3
Siemens AG 2008
ZSI module
5 6 1 2 3 4
NSE0_01898
Connection diagram for a Zone Selective Interlocking functionality with multiple infeed and several outgoing units with SENTRON 3WL circuit breakers
SENTRON 3VL and SENTRON 3WL circuit breakers used in various staggered levels
SENTRON 3WL 3 4 5 6 ZSI module SENTRON 3WL 3 4 5 6 ZSI module
5 6 1 2 3 4
ZSI module
NSE0_01899
SENTRON 3WL
Zone Selective Interlocking functionality: Connection using a coupling switch, use of SENTRON 3WL circuit breakers
More information
Up-to-date information on the Internet at: http://www.siemens.com/sentron
Siemens LV 1 T 2008
15/45
15
Siemens AG 2008
Technical specifications
Size Type Rated current In at 40 C Main conductor Rated operational voltage Ue (1000 V version, see Catalog LV 1, order code "A05") Rated insulation voltage Ui Rated impulse withstand voltage Uimp Main current paths Auxiliary circuits Control circuits Isolating function to EN 60947-2 Permissible ambient temperature Operation Storage Permissible load At rear horizontal main circuit connections (Cu painted black) up to 40 C up to 55 C up to 60 C up to 70 C II 3WL12 10 A ... 1000 V DC ... 600/1000 V AC 1000 kV 12 kV 4 kV 2.5 Yes C 25/+75 C 40/+70 A A A A 1000 1000 1000 1000 3WL12 20 2000 ... 600/1000 1000 12 4 2.5 Yes 25/+75 40/+70 2000 2000 2000 1950 770 35 34 100 73 73 10000 15000 6000 1000 15000 60 20
3 0 3 0 3 0 3 0
3WL12 40 4000 ... 600/1000 1000 12 4 2.5 Yes 25/+75 40/+70 4000 3640 3500 3250 1640 35 34 100 73 73 10000 15000 4000 1000 15000 60 20
h m a x . = 1 m m
Power loss at In for symmetrical loads Withdrawable circuit breaker Operating times Make-time Opening time Electrical make-time (through activation solenoid)1) Electrical opening time (through shunt trip unit) Electrical opening time (instantaneous undervoltage trip unit) Endurance3) Mechanical (without maintenance) Mechanical (with maintenance)2) Electrical (without maintenance) 1000 V version Electrical (with maintenance)2) Switching frequency 600 V version 1000 V version Mounting position
W 280 ms ms 35 34
ms 100 ms 73 ms 73
15
Operating cycles 10000 Operating cycles 15000 Operating cycles 6000 Operating cycles 1000 Operating cycles 15000 1/h 60 1/h 20
and/ or
N S E 0 _ 0 0 0 6 1 a N S E 0 _ 0 0 0 6 2 a
N S E 0 _ 0 0 9 2 7 a
Degree of protection Auxiliary conductors (Cu) Max. number of auxiliary conductors cross-section (solid/stranded) Standard connection = strain-relief clamp Without end sleeve With end sleeve to DIN 46228 Part 2 With twin end sleeve Optional connection = tension spring Without end sleeve With end sleeve to DIN 46228 Part 2 Weights 3-pole Fixed-mounted circuit breakers Withdrawable circuit breakers Guide frames Fixed-mounted circuit breakers Withdrawable circuit breakers Guide frames
IP20 without cabinet door, IP41 with door sealing frame, IP55 with cover 2 0.5 mm2 (AWG 20) ... 2 1.5 mm2 (AWG 16); 1 2.5 mm2 (AWG 14) 1 0.5 mm2 (AWG 20) ... 1 1.5 mm2 (AWG 16) 2 0.5 mm2 (AWG 20) ... 2 1.5 mm2 (AWG 16) 2 0.5 mm2 (AWG 20) ... 2 2.5 mm2 (AWG 14) 2 0.5 mm2 (AWG 20) ... 2 1.5 mm2 (AWG 16) kg 56 kg 60 kg 31 kg 67 kg 72 kg 37
2) 3)
56 60 31 67 72 37
64 68 45 77 82 54
4-pole
1)
Make-time through activation solenoid for synchronization purposes (short-time excited) 50 ms.
Maintenance means: replace main contact elements and arc chutes (see Operator's Guide). Further technical specifications on request.
15/46
Siemens LV 1 T 2008
Siemens AG 2008
Characteristic curves
10000
R=
[s]
= 0.4
= 1.0
R=
R n
B A B A
10 s [B] 2 s [A]
10
n
Dimensional drawings
DIG S100
AUTO
NSE0_01578
I=
MIN 1.25
I=
1.5
I=
MAX 4 n
257 250
_ +
MENUE
3,5
136
ON R2 R1
NSE0_01576
122 115
NSE0_01575
AUTO MAN
PEAK
DIAG
MAIN
271
DIGmat S100
For dimensions of the "3WL Non-Automatic Circuit-Breakers (DC)" and the "3WL Air Circuit Breakers/Non-Automatic Air Circuit Breakers up to 6300 A (AC)", "1000 V Version", see pages 15/34 to 15/42.
Schematics
L1 N PE AC230 AC230 + DC24
X1.2 X1.1 X5.2 X5.1
DIGmat S100 Auxiliary power EMERGENCY-STOP + DC24 X4.i1+ X4.i1X4.i2+ X4.i2Automatic-RESET Digital output
X4.01 X4.01 X4.02 X4.02 X4.03 X4.03 X4.04 X4.04 + + + + -
+ -
Shunt (60mV)
14 -Q01 -X6.14 -X5.12 SENTRON 3WL -F1 -F3 -X6.13 -X5.11 -Q01 2 4 6 1 3 5
Schematics of the DIGmat S100 and the SENTRON 3WL non-automatic air circuit breaker Siemens LV 1 T 2008
NSE0_01577a
15/47
15
Siemens AG 2008
Up to 300 V + 10 %
1-pole, 2-pole 2 parallel conducting paths, only with grounded-neutral system Over 300 V + 10 % Up to 600 V + 10 %
2-pole, only with grounded-neutral system Over 600 V + 10 % Up to 1000 V + 10 % (version for 1000 V required, order with "-Z" and order code A05)
2-pole
15
The connection to the circuit breakers is not dependent on direction and polarity; the circuit diagrams can be adapted accordingly. If the parallel or series connections are made directly to the connecting bars, for thermal reasons the continuous load on the circuit breakers must only be 80 % of the permissible operational current. If the parallel or series connection is made at a distance
of 1 m from the connecting bars, the circuit breaker can be used at full operational current load.
Grounded-neutral system
@ Load
More information
Up-to-date information on the Internet at: http://www.siemens.com/sentron
15/48