Definition of Timing Functions
Definition of Timing Functions
INTERVAL ON Interval
Upon application of input voltage, the relay is energized and the preset time begins. At the end of the preset time, the relay is de-energized. Input voltage must be removed and reapplied to reset the time delay.
Upon application of input voltage, the time delay relay is ready to accept trigger signals. Upon application of the trigger signal, the relay is energized. Upon release of the trigger signal, the preset time begins. At the end of the preset time, the relay is de-energized. Any application of the trigger signal during the preset time will keep the relay energized & reset the time delay.
Upon application of input voltage, the time delay relay is ready to accept trigger signals. Upon application of the trigger signal, the relay is energized and the preset time begins. During the preset time, the trigger signal is ignored. The time delay relay is reset by applying the trigger signal when the relay is not energized.
1/09
52
FLASHER
REPEAT CYCLE Upon application of input voltage, a preset delay begins (OFF). At the end of the preset delay, the relay is Off/On Delay energized and remains in that condition for a second, independently adjustable preset time (ON). At the end of this time, the relay is de-energized and the sequence repeats until input voltage is removed. Upon application of input voltage, the relay is energized REPEAT CYCLE and a preset delay begins (ON). At the end of the preset delay, the relay is de-energized and remains in On/Off Delay that condition for a second, independently adjustable preset time (OFF). At the end of this time, the relay is energized and the sequence repeats until input voltage is removed. DELAYED INTERVAL Single Cycle Upon application of input voltage, a preset delay begins (OFF). At the end of the preset delay, the relay is energized and remains in that condition for a second, independently adjustable preset time (ON). At the end of the second preset time, the relay is de-energized. Input voltage must be removed and reapplied to reset the time delay relay. Upon application of input voltage, the time delay relay is ready to accept trigger signals. Upon application of the trigger signal, a preset delay begins (OFF). At the end of the preset delay, the relay is energized and remains in that condition for a second, independently adjustable preset time (ON). At the end of the second preset time, the relay is de-energized. During both the OFF time & the ON time, the trigger signal is ignored. Upon application of input voltage, the relay is energized. When the input voltage is removed, the preset time begins. At the end of the preset time, the relay is de-energized. Voltage must be applied for a minimum of 0.1 seconds to assure proper operation. Any application of the input voltage during the preset time will keep the relay energized & reset the time delay. No external trigger switch is required.
1/09
53