ATV312 Installation Manual 090306
ATV312 Installation Manual 090306
ATV312 Installation Manual 090306
Installation manual
FT RA _06 D 03 9_ 0
Contents
Important Information __________________________________________________________________________________________ 4 Before you begin______________________________________________________________________________________________ 5 Documentation structure________________________________________________________________________________________ 7 Steps for setting up____________________________________________________________________________________________ 8 Setup - Preliminary recommendations _____________________________________________________________________________ 9 Drive ratings ________________________________________________________________________________________________ 10 Single phase supply voltage: 200240 V 50/60 Hz____________________________________________________________ 10 Three phase supply voltage: 200240 V 50/60 Hz ____________________________________________________________ 10 Three phase supply voltage: 380500 V 50/60 Hz ____________________________________________________________ 11 Three phase supply voltage: 525600 V 50/60 Hz ____________________________________________________________ 11 Dimensions and weights_______________________________________________________________________________________ 12 Mounting ___________________________________________________________________________________________________ 14 Mounting and temperature conditions ______________________________________________________________________ 14 Removing the vent cover ________________________________________________________________________________ 14 Mounting types ________________________________________________________________________________________ 14 Derating curves________________________________________________________________________________________ 15 Flow of air ____________________________________________________________________________________________ 15 Installing the EMC plates ________________________________________________________________________________ 16 Bus voltage measurement procedure_______________________________________________________________________ 16 Wiring _____________________________________________________________________________________________________ 17 Recommendations _____________________________________________________________________________________ 17 General wiring diagram__________________________________________________________________________________ 18 Logic input switch ______________________________________________________________________________________ 19 Power terminals _______________________________________________________________________________________ 20 Control terminals_______________________________________________________________________________________ 24 Electromagnetic compatibility (EMC) _______________________________________________________________________ 26 Operation on an IT system _______________________________________________________________________________ 28 Check list __________________________________________________________________________________________________ 29 Maintenance ________________________________________________________________________________________________ 30 Recommended fuse ratings ____________________________________________________________________________________ 31
Important Information
NOTICE
Read these instructions carefully, and look at the equipment to become familiar with the device before trying to install, operate, or maintain it. The following special messages may appear throughout this documentation or on the equipment to warn of potential hazards or to call attention to information that clarifies or simplifies a procedure.
The addition of this symbol to a Danger or Warning safety label indicates that an electrical hazard exists, which will result in personal injury if the instructions are not followed.
This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death.
DANGER
DANGER indicates an imminently hazardous situation, which, if not avoided, will result in death or serious injury.
WARNING
WARNING indicates a potentially hazardous situation, which, if not avoided, can result in death, serious injury or equipment damage.
CAUTION
CAUTION indicates a potentially hazardous situation, which, if not avoided, can result in injury or equipment damage.
CAUTION
CAUTION, used without the safety alert symbol, indicates a potentially hazardous situation which, if not avoided, can result in equipment damage.
PLEASE NOTE
The word "drive" as used in this manual refers to the controller portion of the adjustable speed drive as defined by NEC. Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this product. 2009 Schneider Electric. All Rights Reserved
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Read and understand this manual before installing or operating the Altivar 312 drive. Installation, adjustment, repair, and maintenance must be performed by qualified personnel. The user is responsible for compliance with all international and national electrical code requirements with respect to grounding of all equipment. Many parts of this drive, including the printed circuit boards, operate at the line voltage. DO NOT TOUCH. Use only electrically insulated tools. DO NOT touch unshielded components or terminal strip screw connections with voltage present. DO NOT short across terminals PA/+ and PC/ or across the DC bus capacitors. Before servicing the drive: Disconnect all power, including external control power that may be present. Place a DO NOT TURN ON label on all power disconnects. Lock all power disconnects in the open position. WAIT 15 MINUTES to allow the DC bus capacitors to discharge. Then follow the Bus Voltage Measurement Procedure page 16 to verify that the DC voltage is less than 42 V. The drive LEDs are not indicators of the absence of DC bus voltage.
Install and close all covers before applying power or starting and stopping the drive. Failure to follow these instructions will result in death or serious injury.
DANGER
UNINTENDED EQUIPMENT OPERATION
Read and understand this manual before installing or operating the Altivar 312 drive. Any changes made to the parameter settings must be performed by qualified personnel. Failure to follow these instructions will result in death or serious injury.
WARNING
DAMAGED DRIVE EQUIPMENT
Do not operate or install any drive or drive accessory that appears damaged. Failure to follow these instructions can result in death, serious injury, or equipment damage.
WARNING
LOSS OF CONTROL
The designer of any control scheme must consider the potential failure modes of control paths and, for certain critical control functions, provide a means to achieve a safe state during and after a path failure. Examples of critical control functions are emergency stop and overtravel stop. Separate or redundant control paths must be provided for critical control functions. System control paths may include communication links. Consideration must be given to the implications of unanticipated transmission delays or failures of the link.a Failure to follow these instructions can result in death, serious injury, or equipment damage.
a. For additional information, refer to NEMA ICS 1.1 (latest edition), Safety Guidelines for the Application, Installation, and Maintenance of Solid State Control and to NEMA ICS 7.1 (latest edition), Safety Standards for Construction and Guide for Selection, Installation and Operation of Adjustable-Speed Drive Systems.
CAUTION
INCOMPATIBLE LINE VOLTAGE
Before turning on and configuring the drive, ensure that the line voltage is compatible with the supply voltage range shown on the drive nameplate. The drive may be damaged if the line voltage is not compatible. Failure to follow these instructions can result in injury or equipment damage.
CAUTION
RISK OF DAMAGE TO THE MOTOR
The use of external overload protection is required under the following conditions: Repowering up the product since there is no motor thermal state memory. Running multiple motors. Running motors rated at less than 0.2 times the nominal drive current. Using motor switching. Failure to follow these instructions can result in equipment damage
Documentation structure
The following Altivar 312 technical documents are available on the Schneider Electric website (www.schneider-electric.com) as well as on DVD-ROM (reference VW3A8200).
Installation manual
This manual describes how to install and wire the drive.
Programming manual
This manual describes the functions, parameters and use of the drive terminal (integrated display terminal, optional graphic display terminal and optional remote terminal).
Simplified manual
This manual is an extract from programming and installation manual. This manual is delivered with the drive.
Quick Start
The Quick Start describes how to wire and configure the drive to start motor quickly and simply for simple applications. This document is delivered with the drive.
INSTALLATION
1. Receive and inspect the drive
the purchase order. damaged in transit.
v Check that the catalog number printed on the label is the same as that on v Remove the Altivar from its packaging and check that it has not been
v Mount the drive in accordance with the v Install any options required (see option
documentation). instructions in this document (see page 14).
PROGRAMMING
5. Please refer to the programming manual.
DANGER
UNINTENDED EQUIPMENT OPERATION
Ensure that all logic inputs are inactive to help prevent an accidental startup. Failure to follow these instructions will result in death or serious injury.
DANGER
UNINTENDED EQUIPMENT OPERATION
Read and understand this manual before installing or operating the Altivar 312 drive. Any changes made to the parameter settings must be performed by qualified personnel. Ensure that all logic inputs are inactive to help prevent an accidental startup when modifying parameters. Failure to follow these instructions will result in death or serious injury.
Line contactor
CAUTION
RISK OF DAMAGE TO THE DRIVE
Avoid operating the contactor frequently to avoid premature aging of the filter capacitors. Power cycling must be more than 60 seconds. Failure to follow these instructions can result in equipment damage.
Drive ratings
A 1.5 3.3 3.7 4.8 6.9 8.0 11.0 13.7 17.5 27.5 33.0 54.0 66.0
(1) These power ratings and currents are for a maximum ambient temperature of 50C and a switching frequency of 4 kHz in continuous operation.The switching frequency is adjustable from 2 to 16 kHz. Above 4 kHz, the drive will reduce the switching frequency in the event of excessive temperature rise. The temperature rise is controlled by a sensor in the power module. Nonetheless, the nominal drive current should be derated if operation above 4 kHz needs to be continuous. Derating curves are shown on page 15 as a function of switching frequency, ambient temperature and mounting conditions. (2) Current on a line supply with the "Max. prospective line Isc" indicated. (3) Peak current on power-up, for the max. voltage (240 V + 10%). (4) For 60 seconds. (5) These references can be ordered without terminal board in order to integrate an optionnal communication board. Add a B at the end of the reference. For example, ATV312HU11M2 becomes ATV312HU11M2B.
10
A 1.5 1.9 2.3 3.0 4.1 5.5 7.1 9.5 14.3 17.0 27.7 33.0
HP 1 2 3 5 7.5 10 15 20
(1) These power ratings and currents are for a maximum ambient temperature of 50C and a switching frequency of 4 kHz in continuous operation. The switching frequency is adjustable from 2 to 16 kHz. Above 4 kHz, the drive will reduce the switching frequency in the event of excessive temperature rise. The temperature rise is controlled by a sensor in the power module. Nonetheless, the nominal drive current should be derated if operation above 4 kHz needs to be continuous. Derating curves are shown on page 15 as a function of switching frequency, ambient temperature and mounting conditions. (2) Current on a line supply with the "Max. prospective line Isc" indicated. (3) Peak current on power-up, for the max. voltage (500 V + 10%, 600 V + 10%). (4) For 60 seconds. (5) These references can be ordered without terminal board in order to integrate an optionnal communication board. Add a B at the end of the reference. For example, ATV312H037N4 becomes ATV312H037N4B. (6) The use of an AC choke, which must be ordered separately (please refer to the catalog), is mandatory on these drives
11
ATV312H
U1pM3 U1pM2, U22M3, 037N4 to U15N4 075S6, U15S6p U22M2, Up0M3, U22N4 to U40N4, U22S6, U40S6
12
D mm (in.) 6 (0.24)
J mm (in.) 5 (0.2)
K mm (in.) 17 (0.67)
D mm (in.) 6 (0.24)
J mm (in.) 7 (0.28)
13
Mounting
50 mm
When IP20 protection is adequate, we recommend that the vent cover on the top of the drive be removed, as shown below.
Example ATV312HU11M3
Mounting types
3 types of mounting are possible:
Type A mounting:
u 50 mm 2 in. u 50 mm 2 in.
Free space u 50 mm (2 in.) on each side, with vent cover fitted. Mounting type A is suitable for drive operation at surrounding air temperature less or equal to 50C (122F).
Type B mounting:
Drives mounted side-by-side, vent cover should be removed (the degree of protection becomes IP20).
Type C mounting:
u 50 mm 2 in.
u 50 mm 2 in.
Free space u 50 mm (2 in.) on each side. Vent cover should be removed for operation at surrounding air temperature above 50C (122F). The degree of protection becomes IP20
Note: For switching frequencies above 4 kHz and derating conditions, please refer to the derating curves for guidelines.
14
Mounting (continued)
Derating curves
Derating curves for the drive current In as a function of the temperature, switching frequency and type of mounting. I/In
In = 100 % -5% 90 % 80 % - 25 % 70 % - 35 % 60 % 50 % 40 % - 65 % 30 %
60C mounting types A and B
- 10 % - 15 %
- 10 % - 20 %
40C mounting types A, B and C
- 25 % - 30 %
50C mounting type C
- 35 % - 40 %
50C mounting types A and B
- 45 % - 50 %
60C mounting type C
- 55 %
Switching frequency
4 kHz
8 kHz
12 kHz
16 kHz
Flow of air
If you are installing the drives in enclosures, make provision for a flow of air at least equal to the value given in the table below for each drive. ATV312H
3
018M2, 037M2, 055M2, 018M3, 037M3, 055M3, 037N4, 055N4, 075N4, U11N4 075S6, U15S6 075M2, U11M2, U15M2 075M3, U11M3, U15M3 U15N4, U22N4 U22S6, U40S6 U22M2, U22M3, U30M3, U40M3 U30N4, U40N4 U55S6, U75S6 U55M3 U55N4, U75N4 D11S6 U75M3, D11M3, D11N4, D15N4 D15S6 D15M3
18
11
33
19
93
55
102
60
168 216
99 127
15
Mounting (continued)
2 screws
2 screws
2 screws
2 screws
Screws supplied: 4 x M4 screws for fixing the EMC clamps (clamps not supplied) 1 x M5 screw for ground
ATV312H 018M3, 037M3 055M3, 075M3 018M2, 037M2 055M2, 075M2 U11M3, U15M3 U11M2, U15M2, U22M3, 037N4, 055N4, 075N4, U11N4, U15N4, 075S6, U15S6
Size 1 2 3 4 5 6
ATV312H U22M2, U30M3, U40M3, U22N4, U30N4, U40N4, U22S6, U40S6 U55M3, U75M3, U55N4, U75N4, U55S6, U75S6 D11M3, D15M3, D11N4, D15N4, D11S6, D15S6
Size 7
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Read and understand the precautions in Before you begin page 5 before performing this procedure. Failure to follow these instructions will result in death or serious injury. The DC bus voltage can exceed 933 Vdc. Use a properly rated voltage-sensing device when performing this procedure. To measure the DC bus voltage: 1. Disconnect all power. 2. Wait 15 minutes to allow the DC bus to discharge. 3. Measure the voltage of the DC bus between the PA/+ and PC/ terminals to ensure that the voltage is less than 42 Vdc. 4. If the DC bus capacitors do not discharge completely, contact your local Schneider Electric representative. Do not repair or operate the drive.
16
Wiring
Recommendations
Power and circuit protection
The drive must be grounded to conform with the regulations concerning high leakage currents (over 3.5 mA). Where local and national codes require upstream protection by means of a residual current device, use a type A device for single-phase drives and a type B device for three-phase drives as defined in the IEC Standard 60755. Choose a suitable model integrating: High frequency current filtering, A time delay that helps to prevent tripping caused by the load from stray capacitance on power-up. The time delay is not possible for 30 mA devices; in this case, choose devices with immunity against nuisance tripping. If the installation includes several drives, provide one "residual current device" per drive. Keep the power cables separate from circuits in the installation with low-level signals (detectors, PLCs, measuring apparatus, video, telephone). If you are using cables longer than 50 m (164 ft) between the drive and the motor, add output filters (please refer to the catalogue).
Control
Keep the control circuits away from the power cables. For control and speed reference circuits, we recommend using shielded twisted cables with a pitch of between 25 and 50 mm (1 and 2 in.), connecting the shielding to ground at each end.
Equipment Grounding
Ground the drive according to local and national code requirements. A minimum wire size of 10 mm (6 AWG) may be required to meet standards limiting leakage current.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
The drive panel must be properly grounded before power is applied. Use the provided ground connecting point as shown in the figure below. Failure to follow these instructions will result in death or serious injury. Ensure that the resistance of the ground is one ohm or less. When grounding several drives, you must connect each one directly, as shown in the figure to the left. Do not loop the ground cables or connect them in series.
WARNING
IMPROPER WIRING PRACTICES
The ATV312 drive will be damaged if input line voltage is applied to the output terminals (U/T1,V/T2,W/T3). Check the power connections before energizing the ATV312 drive. If replacing another drive, verify that all wiring connections to the ATV312 drive comply with wiring instructions in this manual page 29. Failure to follow these instructions can result in death, serious injury, or equipment damage.
WARNING
INADEQUATE OVERCURRENT PROTECTION
Overcurrent protective devices must be properly coordinated. The Canadian Electrical Code and the National Electrical Code require branch circuit protection. Use the fuses recommended in the installation manual. Do not connect the drive to a power feeder whose short-circuit capacity exceeds the drive short-circuit current rating listed in this manual page 29. Failure to follow these instructions can result in death, serious injury, or equipment damage.
17
Wiring (continued)
R / L1
S / L2
R / L1
S / L2
T / L3 W / T3
R1A
PA / +
U / T1
V / T2
PC / -
COM
COM
AOC
AOV
A0C
+10
AI1
AI3
PB
AI2
P0
M 3a
(3)
X - Y mA 0 - 10 V
W1
U1
V1
Reference potentiometer
(1) Line choke, if used (single phase or 3-phase) (2) Fault relay contacts, for remote indication of the drive status (3) If a braking resistor is connected, set [Dec ramp adapt.] (brA) parameter to yes (refer to the progamming manual). Note 1: Use interference suppressors on all inductive circuits near the drive or coupled to the same circuit (relays, contactors, solenoid valves, etc). Note 2: This diagram is for the standard ATV312 products. Optional communication cards may change the control wiring of the product. Please see the associated documentation for the option cards for details. Choice of associated components: Please refer to the catalogue.
18
Wiring (continued)
LI1
24V
SOURCE
COM
CLI
LI1
24V
ATV312pppp
24V
Switch position
LI1 COM
in
Sink
0V
CLI SINK
ATV312pppp
COM
CLI
LI1
0V
PLC
24V
DANGER
UNINTENDED EQUIPMENT OPERATION
Prevent accidental grounding of logic inputs configured for sink logic. Accidental grounding can result in unintended activation of drive functions. Protect the signal conductors against damage that could result in unintentional conductor grounding. Follow NFPA 79 and EN 60204 guidelines for proper control circuit grounding practices. Failure to follow these instructions will result in death or serious injury.
19
Wiring (continued)
Power terminals
Access to the power terminals
To access the terminals, open the cover as shown in the example below.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH.
Replace the cover plate on the terminals and close the door before applying power. Failure to follow these instructions will result in death or serious injury.
20
Wiring (continued)
CAUTION
RISK OF DAMAGE TO THE DRIVE
Never remove the link between PO and PA/+. The PO and PA/+ terminal screws must always be fully tightened as a high current flows through the link. Failure to follow these instructions can result in equipment damage
(1) The value in bold corresponds to the minimum wire gauge to permit secureness. (2) 75C (167 F) copper cable (minimum wire size for rated use).
21
Wiring (continued)
ATV312H U11M3 ...U40M3 ATV312H 037N4 ... U40N4 ATV312H 075S6 ... U40S6
ATV312H
U11M3, U15M3 037N4, 055N4, 075N4, U11N4, U15N4 075S6, U15S6 U22M3
R/L1 S/L2 T/L3 P0 PA/+ PB PC/- U/T1 V/T2 W/T3
2.5 (14)
0.8 (7.1)
2.5 to 6 (12 to 10) 2.5 to 6 (14 to 10) 2.5 to 6 (14 to 10) 4 to 6 (12 to 10)
ATV312H
Tightening torque Nm (lb.in) 2.5 (22.3) 2.5 (22.3) 2.5 (22.3) 2.5 (22.3)
10 to 16 (8 to 6) 10 to 16 (8 to 6) 4 to 6 (12 to 10) 10 to 16 (8 to 6)
(1) The value in bold corresponds to the minimum wire gauge to permit secureness. (2) 75C (167 F) copper cable (minimum wire size for rated use).
22
Wiring (continued)
ATV312H
10 to 25 (8 to 4) 10 to 25 (8 to 4) 10 to 25 (8 to 4)
(1) The value in bold corresponds to the minimum wire gauge to permit secureness. (2) 75C (167 F) copper cable (minimum wire size for rated use).
23
Wiring (continued)
Control terminals
Access to the control terminals
COM
AOC
AOV
R1C
COM
10V
R2C
R1A
R1B
R2A
AI3
Control terminals
AI2 CLI LI4 LI5 LI6
RJ45 connector
RJ45
I/O terminal card can be removed to install in place optional communication boards. Please refer to installation and wiring details supplied with each board.
24V
LI1
LI2
DANGER
UNINTENDED EQUIPMENT OPERATION
Do not plug or unplug the terminal board while drive is powered. Check the tightening of the fixing screw after any manipulation on the terminal board. Failure to follow these instructions will result in death or serious injury.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
Do not touch the terminal board before : removing power on the drive, removing any voltage on input and output terminals. Failure to follow these instructions will result in death or serious injury.
(1) The value in bold corresponds to the minimum wire gauge to permit secureness. (2) Recommended to maximum value.
24
LI3
Wiring (continued)
COM AI1
10 V AI2
AI3
Analog I/O common Analog output voltage AOV or Analog output current AOC or Logic output voltage AOC AOV or AOC can be assigned (either, but not both)
25
Wiring (continued)
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
Do not expose cable shielding except where connected to ground at the metal cable glands and underneath the grounding clamps. Ensure that there is no risk of the shielding coming into contact with live components. Failure to follow these instructions will result in death or serious injury.
26
Wiring (continued)
Sizes 1 to 4
Size 5 to 7
Size 8
Size 9
1. 2. 3. 4. 5.
EMC plate supplied with the drive, to be installed as indicated on the diagram. Altivar 312 Non-shielded power supply wires or cable Non-shielded wires for relay contacts Attach and ground the shielding of cables 6, 7 and 8 as close as possible to the drive: - Strip the shielding. - Use stainless steel cable clamps of an appropriate size on the parts from which the shielding has been stripped, to attach them to the plate 1. The shielding must be clamped tightly to the metal plate to improve electrical contact. 6. Shielded cable for motor connection with shielding connected to ground at both ends. The shielding must be continuous and intermediate terminals must be in EMC shielded metal boxes. For 0.18 to 1.5 kW drives, if the switching frequency is higher than 12 kHz, use cables with low linear capacitance: max. 130 pF (picoFarads) per meter. 7. Shielded cable for connecting the control/signalling wiring. For applications requiring several conductors, use cables with a small cross-section (0.5 mm2, 20 AWG). The shielding must be connected to ground at both ends. The shielding must be continuous and intermediate terminals must be in EMC shielded metal boxes. 8. Shielded cable for connecting braking resistor (if used). The shielding must be continuous and intermediate terminals must be in EMC shielded metal boxes. Note: If using an additional input filter, it should be mounted under the drive and connected directly to the line supply via an unshielded cable. Link 3 on the drive is then via the filter output cable. The HF equipotential ground connection between the drive, motor and cable shielding does not remove the need to connect the PE ground conductors (green-yellow) to the appropriate terminals on each unit.
27
Wiring (continued)
Operation on an IT system
IT system: Isolated or impedance earthed neutral. ATV312ppppM2 and ATV312ppppN4 drives have a built-in EMC filter. As a result they exhibit leakage current to ground. If the leakage current creates compatibility problems with your installation (residual current device or other), then you can reduce the leakage current by opening the IT jumper. In this configuration EMC compliance is not guaranteed. Use a permanent insulation monitor compatible with non-linear loads (for example Merlin Gerin type XM200).
ATV312H 018M2 to U22M2 and ATV312H 037N4 to U40N4: Pull out the jumper on the left of the ground terminal as illustrated below.
ATV312H U55N4 to D15N4: Move the cable tag on the top left of the power terminals as illustrated below (example: ATV312HU55N4): IT system (filter disconnected)
28
Check list
Read carefully the safety information in programming, installation, simplified manuals and the catalogue. Before starting up the drive, please check the following points regarding mechanical and electrical installations, then use and run the drive. For complete documentation, refer to www.schneider-electric.com.
1. Mechanical installation
For drive mounting types and recommendations on the ambient temperature (see the Mounting instructions on page 14). Mount the drive vertically as specified (see the Mounting instructions on page 14). The use of the drive must be in agreement with the environments defined by the standard 60721-3-3 and according to the levels defined in the catalogue. Mount the options required for your application (see catalogue).
2. Electrical installation
Connect the drive to the ground (see Equipment Grounding on page 17). Ensure that the input power voltage corresponds to the drive nominal voltage and connect the line supply as shown on the drawing on page 18. Ensure to use appropriate input power fuses and circuit breaker. Wire the control terminals as required (see Control terminals on page 24). Separate the power cable and the control cable according to EMC compatibility rules. The range ATV312ppppM2 and ATV312ppppN4 integrates EMC filter. The leakage current can be reduced using the IT jumper as explained in the paragraph Operating on an IT system on page 28. Ensure that motor connections correspond to the voltage (star, delta).
29
Maintenance
Servicing
The Altivar 312 does not require any preventive maintenance. However, it is advisable to perform the following checks regularly: The condition and tightness of connections. Ensure that the temperature around the unit remains at an acceptable level and that ventilation is effective. Average service life of fans: 10 years. Remove any dust from the drive. Ensure proper fan operation. Physical damage to covers.
Display menu
Use the display menu to show the status of the drive and it's current values as an aid for finding the causes of detected faults.
WARNING
RISK OF EXPLOSION AT THE POWER UP
The capacitors after a long time storage can have issues. Following a storage time between 2 and 3 years: Use one AC supply variable connected between L1, L2 and L3 Increase AC supply voltage to have: - 25% of rated voltage during 30mn - 50% of rated voltage during 30mn - 75% of rated voltage during 30mn - 100% of rated voltage during 30mn Failure to follow these instructions can result in death, serious injury, or equipment damage.
30
Reference
Power rating
kW ATV312H018M2 ATV312H037M2 ATV312H055M2 ATV312H075M2 ATV312HU11M2 ATV312HU15M2 ATV312HU22M2 ATV312H018M3 ATV312H037M3 ATV312H055M3 ATV312H075M3 ATV312HU11M3 ATV312HU15M3 ATV312HU22M3 ATV312HU30M3 ATV312HU40M3 ATV312HU55M3 ATV312HU75M3 ATV312HD11M3 ATV312HD15M3 ATV312H037N4 ATV312H055N4 ATV312H075N4 ATV312HU11N4 ATV312HU15N4 ATV312HU22N4 ATV312HU30N4 ATV312HU40N4 ATV312HU55N4 ATV312HU75N4 ATV312HD11N4 ATV312HD15N4 0.18 0.37 0.55 0.75 1.1 1.5 2.2 0.18 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 11 15 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 11 15
HP 0.25 0.5 0.75 1 1.5 2 3 0.25 0.5 0.75 1 1.5 2 3 3 5 7.5 10 15 20 0.5 0.75 1 1.5 2 3 3 5 7.5 10 15 20
Fuse Class J and CC SC (3) 6 10 10 15 20 20 30 3 6 10 10 15 15 20 25 35 50 60 80 110 3 6 6 10 10 15 15 20 30 35 50 70 not tested not tested not tested not tested not tested not tested not tested 22 22 22 22 22 22 22 22 22 22 22 22 22 100 100 100 100 100 100 100 100 100 100 100 100
(1) Product design level (2) Output short circuit tested (3) If line Isc is greater than the values in the table, add line chokes
31
Reference
Power rating
kW ATV312H075S6 ATV312HU15S6 ATV312HU22S6 ATV312HU40S6 ATV312HU55S6 ATV312HU75S6 ATV312HD11S6 ATV312HD15S6 0.75 1.5 2.2 4 5.5 7.5 11 15
HP 1 2 3 5 7.5 10 15 20
(1) Product design level (2) Output short circuit tested (3) If line Isc is greater than the values in the table, add line chokes
32