Inspection Guidelines by Lincoln
Inspection Guidelines by Lincoln
Inspection Guidelines by Lincoln
1.0 2.0 3.0 4.0 5.0 6.0 6.1 6.2 6.3 6.4 6.5 6.6 6.6.1 6.6.2 6.6.3 6.6.4 6.6.5 6.6.6 6.6.7 7.0 8.0 9.0 10.0 10.1 10.2 11.0 11.1 11.2 11.3 11.4 11.5 11.6 12.0 12.1 13.0 13.1 13.2 13.3 13.4 13.5 14.0
Page
1 1 2 2 5 6 6 6 7 7 11 12 13 13 15 16 16 16 16 16 17 17 18 18 18 19 19 19 20 21 21 21 22 22 23 23 23 24 24 24 25
Figure
Figure 5-1 Figure 5-2 Figure 6-1 Figure 6-2 Figure 6-3 Figure 6-4 Figure 6-5 Figure 6-6 Figure 6-7 Figure 6-8 Figure 6-9 Figure 6-10 Figure 6-11 Figure 6-12 Figure 6-13 Figure 6-14 Figure 6-15 Figure 6-16 Figure 6-17 Figure 6-18 Figure 6-19 Figure 6-20 Figure 6-21 Figure 6-22 Figure 6-23 Figure 6-24 Figure 6-25 Figure 7-1 Figure 9-1 Figure 10-1 Figure 11-1 Figure 11-2 Figure 11-3 Figure 11-4 Figure 11-5 Figure 11-6 Figure 12-1 Figure 12-2 Figure 12-3 Figure 12-4 Figure 13-1 Figure 13-2 Figure 13-3 NGV Fuel Tank TUFFSHELL Tank Cut Away Typical Label Configuration Inspection Equipment Container/ Bracket Assembly Chin Strap Bracket Assembly Double Bracket Assembly Split Strap Bracket Assembly 180 Strap Bracket Assembly Knuckle Joints Touching Displaced Rubber Pad Bracket Mount Location Torque Values Rubber Set Example Pressure Relief Devices (PRD) Valves Pressure Relief Device (PRD) Hardware Tool List Inspection of Damage Depth Damage Levels Level 1 Cut or Scratch Damage Level 2a Loose Fiber Damage Level 2b Loose Fiber from Gouge Damage Level 3 Abrasion Damage Level 3 Impact Damage Fire Damage Discoloration and Resin Burnout Fiber Gaps Container Condemn Tool List Roof Pack Assembly Set Screw Location Hinge Pin Location for Punch Vent Line Removal Fuel Line Removal Clip to Frame Carriage Bolt Strap Bolt Removal Hardware Tool List Fitting Removal Line Clamps PRD Manifold Assembly Hardware Tool List Skirt Location Fairing Assembly
Page
5 5 6 7 8 8 8 8 8 9 10 10 10 10 11 11 12 12 12 13 14 14 14 14 14 14 16 16 17 18 19 19 19 20 20 20 22 22 22 23 23 24 25
Introduction Scope Pertinent Specifications/Documents Description of Terms General Design Information Inspection Procedures When Tanks Should Be Inspected Preparation for Inspection General Installation Inspection Mounting Bracket Inspection Valve, Solid Plug, and PRD Plug Inspection Composite Tank Inspection Damage Identification and Categorization Cut, Scratch and Abrasion Damage Impact Damage Fire and Excessive Heat Damage Gas Leakage Chemical Damage Weathering Damage Non Structural Anomalies Tank Disposition Tank Destruction Tank Pack Components Fitting Information Frame Inspection Tank Removal from and Installation in Standard Roof Packs Door Removal Outer Tank Removal Inner Tank Removal Tank Installation Door Cover Installation Tank Pack Assembly Leak Test PRD Manifold Assembly Repair PRD Manifold Assembly Replacement Procedures Covers, Skirts, and Fairing Inspection Door Cover and Fairing Inspection Rivet Removal and Installation Skirt Removal and Installation Fairing Removal and Installation Fairing Support Frame Removal and Installation Summary
Appendices
Appendix I Appendix II Appendix III TUFFSHELL Size Chart NGV Tank Inspection Record Notes 26 27 28
1.0
Introduction
In conjunction with other applicable standards and specifications, these guidelines include information regarding proper TUFFSHELL NGV fuel tank installation, which is not directly related to inspection of the composite fuel tank. This additional information is provided only as a reminder of critical installation issues and is not intended to supersede or replace other applicable specifications. In particular, any inspector of fuel tanks should be knowledgeable of the requirements of NFPA 52 and/or CAN/CGA-B109. See section 3.0. Please read and understand all aspects of these guidelines prior to performing any inspection or maintenance on a composite TUFFSHELL NGV fuel tank or tank pack assembly manufactured by Lincoln Composites. Inspectors should be registered through Lincoln Composites or certified through a nationally recognized training program. To be a Lincoln Composites registered inspector, an individual must attend the Lincoln Composites NGV Fuel Tank Training course and have successfully completed the Lincoln Composites Inspection Examination to verify his or her knowledge of the material covered within this manual. Note: It is the responsibility of the company seeking training from Lincoln Composites to assess the general level of ability of each trainee to perform fuel tank re-certification and to see that only qualified personnel attend Lincoln Composites training for registration. Lincoln Composites assumes no liability for improperly inspected tanks. A description of terms used in these guidelines is provided within. Any questions pertaining to training and registration of inspectors and interpretation or use of these guidelines should be directed to: Lincoln Composites Attn: Customer Service 6801 Cornhusker Highway Lincoln, Nebraska 68507 800 279 TANK 8265 or 402 464 6611 FAX 402 464 6777 Email: [email protected] Web Address: www.lincolncomposites.com
Composite reinforced pressure vessels have been used in commercial service since 1976. The technology for these vessels was originally developed by the aerospace industry for weight critical applications. This technology has evolved significantly and has been increasingly used in commercial applications as more efficient and cost effective materials and manufacturing methods have been developed. Lincoln Composites designs and manufactures many types of composite pressure vessels, including lightweight all-composite fuel tanks for vehicles powered by compressed natural gas (CNG) and compressed hydrogen (CH2). Natural Gas Vehicle (NGV) fuel tanks may be designed and qualified to a number of appropriate specifications. These include, but are not limited to, ANSI/CSA NGV2, CSA B51-Part 2, NFPA-52, the US Department of Transportation, (NHTSA), FMVSS 304,TC 301.2 , and ISO 11439. When referencing these documents please refer to the most current revision. Note: Applications that necessitate deviation from the guidelines listed in this manual must fall within the requirements of the applicable specifications listed above. The guidelines herein are for the inspection, installation, and service of TUFFSHELL NGV Type-4 fuel tanks and tank packs manufactured by Lincoln Composites.
2.0
Scope
The purpose of this publication is to provide sufficient information about TUFFSHELL NGV fuel tanks and tank packs manufactured by Lincoln Composites so that a trained inspector can effectively: Examine composite fuel tanks and assess their condition and determine if they are safe for continued service. Identify minor repair procedures which may be used to prolong the useful life of fuel tanks with minor surface damage. Install, maintain, and assess their condition and determine if the fuel tanks are safe for continued service. Replace a tank in the Lincoln Composites tank pack assembly.
3.0
Pertinent Specifications/Documents
The guidelines of this document should be used in conjunction with other applicable standards and specifications invoked by governing regulations in the area of use. The following documents may be useful in performing an inspection and servicing of TUFFSHELL fuel tanks manufactured by Lincoln Composites. a. Methods For Visual Inspection Of Natural Gas Vehicle (NGV) Fuel Tanks And Their Installations , CGA C-6.4, available from: Compressed Gas Association, Inc. 4221 Walney Road, 5th floor Chantilly, VA 20151-2928 Phone: 703 788 2700 www.cganet.com b. Recommendations for the Disposition of Unserviceable Tanks, CGA C-2, available from: Compressed Gas Association, Inc. 4221 Walney Road, 5th floor Chantilly, VA 20151-2928 Phone: 703 788 2700 www.cganet.com c. Compressed Natural Gas (CNG) Vehicular Fuel Systems, ANSI/NFPA 52, available from: National Fire Protection Association 1 Batterymarch Park, P.O. Box 9101 Quincy, MA 02269-9101 Phone: 800 344 3555 www.nfpa.org d. Basic Requirements For Compressed Natural Gas Vehicle (NGV) Fuel Tanks, ANSI/CSA NGV2, specification available from: CSA America, Inc. 8501 East Pleasant Valley Road Cleveland, OH 44131 Phone: 216 524 4990 www.csa-america.org e. High Pressure Tanks for the On-Board Storage of Natural Gas as a Fuel for Automotive Vehicles, CSA B51 Part 2, available from: Canadian Standards Association 178 Rexdale Boulevard Rexdale (Toronto), Ontario, Canada M9W 1R3 CANADA. Phone: 800 463 6727 www.csa.ca
f. Federal Motor Vehicle Safety Standards: Compressed Natural Gas Fuel Tanks, DOT FMVSS 304, available from: Department Of Transportation, National Highway Traffic Safety Administration 400 Seventh Street, SW, Washington D.C. 20590. Phone: 202 366 4000 www.dot.gov g. METI/KHK TECH. STD. #9 Technical Standard and Interpretation of Compressed Natural Gas Fuel Tanks. The High Pressure Gas Safety Law High Pressure Gas Safety Institute of Japan. Toranomon, Minato-ku, Tokyo Japan 105-8447 Phone: 81 3 3436 2201 www.khk.or.jp/e-khk.htm h. Service Bulletin 95-001 Painting NGV Fuel Tanks i. Service Bulletin 97-07-001 Pressure Relief Device Replacement For Superior (P/N 1120SX6SF) and GFI (P/N T1-100) Manual Valves With Circle Seal (P/N RV 99-245) and Mirada (P/N B-51715) PRDs j. Service Bulletin 97-08-001 Venting Procedures k. Service Bulletin 97-08-002 Fill Procedures l. Service Bulletin 00-02-001 Inspection for Water in the Vent Line and Pressure Relief Device m. Service Bulletin 96-12-001 Label Installation Procedures TUFFSHELL NGV Fuel Tanks n. Service Bulletin 00-11-001Honda Provided Superior/ GFI Solenoid Valve on Lincoln Composites CNG Fuel Containers o. Service Bulletin 03-06-001 Crush Washer Replacement Procedure p. TUFFSHELL all-composite NGV Fuel Tanks size and capacity chart q. NGV Tank Inspection Record
Fill Line Assembly. A high-pressure line used to conduct gas into the tank through the valve assembly or assemblies. Foam Insert. Impact absorbing material located under the fiberglass wrap designed to protect the tangent area from damage. Frame. General term that is used to describe the metal structure of the tank pack. The frame encloses and supports the tanks, brackets and pressure lines, fairings, and doors also attach to the frame. Glass Fiber. One type of reinforcement fibers used in the structural wrap. Also fiber used in the external sacrificial wrap. Glass fiber is also referred to as fiberglass. Hardware. General description of valves, PRDs and any other component that will attach to the tank or the tanks related systems. Impact Damage. Damage caused by dropping or by a blow from another object. Impact damage may be at the surface, internal to the structure, or both. Inspection Stamp. The stamp applied to the label by a registered inspector indicating acceptance of the three-year required inspection. The stamp shall identify the inspecting individual. Level 1 Damage. Minor damage that is considered inconsequential to the safe operation of the tank. Level 2 Damage. Damage which is more severe than level 1 damage. This level of damage is rejectable. Additional evaluation and/or rework may allow the tank to be returned to service. Level 3 Damage. Damage which is sufficiently severe that it is not repairable and renders a tank unfit for continued service. Tanks with level 3 damage must be condemned and destroyed. Liner. An internal component of the tank that serves as a permeation barrier, preventing leakage of gas through the composite tank structure. Manufacturers Label(s). The label(s) containing the official markings required by the U.S. DOT, FMVSS304, ANSI/CSA NGV2, ISO 11439, CSA B51Part 2 (Canada), and/ or other national standards as may apply. The label markings shall include a CNG Only designation, manufacturers symbol or trademark, manufacturers model number, type designation, serial number, month and year of manufacture, service pressure, the inspectors symbol or trademark and the date when the service life of the tank will expire. Maximum Fill Pressure. The fill pressure allowed to obtain the settled Service Pressure at 70 F (21 C). For all tanks, maximum fill pressure under ANSI/ CSA NGV2 is 125% of the rated Service Pressure.
by a valve or pressure relief device. Strap. The part of the bracket assembly that connects with the base or clips and wraps around the tank to hold the tank to the frame or base. Strap Bolt. The bolt that secures the straps to the tank. Tangent Area. The area of the tank where the cylinder section meets the dome section of the tank. Tank Pack. A general description to apply to all multiple tank systems contained within a frame that include the related pressure and vent lines assemblies. Tap Test. An inspection technique in which the surface of a Lincoln Composites tank is tapped with a small solid object, such as a Coin, to detect delaminations. A delaminated area will emit a different sound than an area that is not damaged. This inspection can only be performed on the cylinder region of a TUFFSHELL tank and not in the domes. Thermal Trigger. The thermal trigger is the portion of a thermally activated pressure relief device that is actuated by excessive heat input and activates the relief device. Transition Bracket. An attachment bracket used to interface between the tank pack and the vehicle frame. TUFFSHELL. Protective features that include foam inserts on the tank ends and a glass overwrap. These features absorb impact and abrasion damage. Valve, Manual. A device installed in one of the ports of the tank that is used to open or close off the gas flow into or out of the tank. The valve is turned on or off manually with a handle. Valve, Solenoid. A device installed in one of the tank ports that is used to open or close off gas flow into or out of the tank. The valve is turned on or off electrically. The valve can be closed manually, if necessary with special tools following a defined procedure. Vent Line. A high-pressure line used to conduct gas from a pressure relief device to a location outside of the vehicle where gas may be safely discharged. Vent lines are required where pressure-carrying components are installed in a closed compartment. Vent Enclosure. A low-pressure, gas-tight enclosure used to collect and conduct gas that may permeate through o-rings or leak from plumbing connections to a location where gas may be safely discharged outside the vehicle. The enclosure typically made of low-density polyethylene encloses the neck of the boss port on the valve, plug, and all CNG fittings. The vent enclosure must not interfere with heating or operation of the PRD. This vent system is required for installations where the tank is installed in a closed compartment.
Aluminum Boss
TUFFSHELL Foam Insert
HDPE Liner
6.
The initial inspection should include examination of the general fuel tank installation. This inspection should include: 1. A record of the inspection (by tank serial number) should be generated or up-dated if any inspection is performed on a tank or tank hardware. For an example of an inspection record, reference the inspection form in the back of this manual in Appendix II. 2. Determine that the installation is compliant with applicable regulations. 3. Verify that the fuel tank is being used only for the storage of compressed natural gas or hydrogen. 4. Verify that Lincoln Compsites manufactured the tank to be inspected (See note below for additional information on additional tanks that apply to these guidelines). The guidelines in this manual were formulated specifically for the Lincoln Composites Type 4 tank, and may not be appropriate for tanks from other manufacturers. Verify that the service pressure and tank serial number are clearly legible on the tank label. The tank must be destroyed if the identity (i.e. model/part number and serial number) cannot be clearly established. Contact Lincoln Composites Customer Service for label replacement if the label is damaged or not firmly attached. Note: This manual and instructions also apply to tanks manufactured by Brunswick and General Dynamics, Lincoln Operations. Note: For tanks manufactured after July of 1999: If the label is missing or damaged, the serial number of the tank is etched on one of the bosses, and a replacement label can be supplied. 5. Verify that the tank service life has not expired. The label will identify the service life as Do not use after xx-xxxx. The tank must be removed from service and destroyed when the service life expires.
Verify that the service pressure rating listed on the tank label is greater than or equal to vehicle markings for service pressure. 7. Determine potential for damage due to location in vehicle. Damage to a tank could result from shifts of cargo, proximity to the exhaust system, or road debris. 8. Verify that the surface of the tank is not in contact or close proximity to objects that could cut, gouge, or abrade the surface of the tank. This includes shields, cables, tubing, vehicle components, or mounting bracket components. A minimum of 1/2-inch (127 mm) clearance completely around the tank is recommended. Additional clearance may be required in areas where the vehicle can flex during operation. An 8 inch (20.32 cm) minimum ground clearance is recommended for under vehicle installations. 9. Verify that installations in which tanks are enclosed in a vehicle are vented externally to the vehicle. The vent line from the pressure relief device (PRD) should be a high-pressure line, which is adequately secured to the vehicle (every 12 inches [30.48 cm] for lengths of tube over 24 inches [60.96 cm] long) to prevent whipping in the event of PRD activation. The vent line exit should be free of debris and be oriented in such a manner that the vent line will not trap fluids. A lightweight cap that can easily be expelled by pressure in the vent line may be used to prevent accumulation of debris in the vent line. A vent line cap must not inhibit gas flow from escaping should the system vent. Verify the presence of a vent enclosure. 10. Verify that lines connected to the tank are installed in a manner to prevent damage to the plumbing when the vehicle flexes or the tank expands under pressurization.
If the strap bolts are loosened or removed and the rubber pads are not inspected or replaced, then the torque values listed in Figure 6-11 will not be correct to properly secure the tank. Do not install the tank pressurized, as the recommended torque in Figure 6-11 will not be sufficient to hold the tank in place when depressurized. The nuts used in the mounting hardware are equipped with a self-locking feature. This makes it necessary to replace them when the tank is removed. The tank must be mounted in a manner that adequately restrains it but does not induce damage. Because the tank expands and contracts as the internal pressure increases or decreases, the tanks diameter and length will vary. Note: A good rule to follow for tank expansion is 0.006 inches times the length dimension for linear growth or the diameter expansion at service pressure. A tank that is at 3600 psi and is 15.7 inch diameter will grow 0.094 inch diameter. If the tank is 120 inches long then this tank at service pressure will increase in length by 0.72 inches. The tank mounting system must be able to accommodate this movement without inducing excessive loads to the bracket or causing abrasion to the tank. Lincoln Composites offers mounting brackets specifically designed for use with Lincoln Composites tanks. Use of other brackets may result in bracket damage or improper restraint of the tank, either of which could result in a hazardous situation. Mounting Bracket Inspection Must Include: 1. Verification that the tank is firmly restrained. The centerline of the mounting straps should be located a minimum of two-thirds of the tank diameter inboard from the boss face and a maximum of one-third the total tank length inboard from the boss face (see Figure 6-10). All dimensions are to be relative to the boss closest to the tank end in question. The tank and mounting brackets should be firmly attached to the vehicle. The tank must not be allowed to rock, shift, or show any evidence of instability. If a tank is loose within the brackets, then the tank must be vented and removed from the vehicle, and a visual inspection of the tank and the brackets must be initiated and recorded. Rubber pad inspection must also be included (Figure 6-12).
NOTE: Do not verify the torque of the strap bolts. Verifying the torque of the strap bolts wil result in the knuckle joints touching as shown in Figure 6-8. The rubber pad located between the tank and the bracket is designed to compress during tank expansion. Proper torque of the strap bolts can only be accomplished during initial installation. After the rubber pads are in use, the rubber will take a set, which will reduce the torque value originally applied to the strap bolt. This change in the rubber pad will not affect the proper restraint of the tank.
3.
4.
Verification that the brackets are in good condition and suitable for continued service. Hardware bolts or vehicle attachment points exhibiting severe corrosion or cracking in the mounting region should be repaired or replaced. Note: Lincoln Composites Customer Service may be contacted for specific bracket kit mounting instructions. Lincoln Composites brackets may be mounted in any orientation. Tank expansion must be a consideration for proper bracket location. See note for tank expansion section 6.4, Mounting Bracket Inspection.
Tank Length
Tank
Figure 6-10 Bracket Mount Location Thread Size 1/8-27 NPTF 1/4-18 NPTF 2-3 Turns from finger tight 2-3 Turns from finger tight Torque Nm 20-27 94-108 54-68 27-41 53-57 47-61 122-149 136-163 149-176 271-298 Detail Adapter Port Manual Valve Outlet Detail Manual Valve Fuel Outlet Bracket Base Mounting Bolt Strap Bolt and Clip Carriage Nut Solenoid Valve Outlet, Female SAE Manual Valve Outlet, Male, PRD Solenoid Valve Outlet, Female SAE Green Boss Port, Female, SAE Black Boss Port, Female, SAE Special Blue Boss Port, Female, SAE Black Boss Port, Female, SAE Special
Thread Size Torque ft-lbs 7/16-20 UNF 15-20 1/2-13 UNC 70-80 1/2-13 UNC 40-50 9/16-18 UNF 20-30 0.650-19 UNS 39-42 3/4-16 UNF 35-45 1-1/16-12 UN 90-110 1-1/8-12 UN 100-120 1-3/16-12 UN 110-130 2.0-12 UN 200-220
11
4.
For PRDs equipped with external thermal triggers (see Figure 6-15), examine triggers for partial actuation. If the trigger has been partially actuated, there is an extrusion of the eutectic on the top of the trigger through the white marking. This may be evidence that the tank has been subjected to extreme temperatures.
4.
Factory Inspection- Tanks which are known or suspected to have been subjected to a potentially damaging incident, or which exhibit evidence of damage not specifically identified as acceptable by these guidelines, should be removed and may be sent to Lincoln Composites for more extensive evaluation. Arrangements for factory inspection/services may be made by contacting Lincoln Composites Customer Service (see section 2.0).
Note: Before any rework to the tank and/or related hardware, the tank must be vented of all pressure (see important note in section 6.1).
The depth of the area determines the damage level assigned to the composite fibers in question. Accurate depth measurement of damage requires removing all loose fibers associated with the damage. Once the loose fibers are removed, the damage level can be determined per Figure 6-18. See Figure 6-17 for an example of inspecting damage depth.
Damage Levels (Rework Types) Level 1 Level 2a (Rework in the Field) Level 2b (Factory Inspection) Level 3 (Condemn)
Damage Levels Scratch, Gouge, and Abrasion Depth Figure(s) Inches 6-19 0 < 0.010 6-20 6-21 6-22 6-23 0.011 < 0.035 0.036 < 0.050 Greater than 0.05
Millimeters 0 < 0.25 0.26 < 0.89 0.90 < 1.27 Greater than 1.27
Damage Level
Description of Damage
Disposition
Minor damage that is Remove loose fibers and paint considered inconse- area with polyurethane paint. Level 1 quential to the safe operation of the tank
Customer rework. Remove loose fibers or rough edges of a cut or gouge by hand filing or sanding. Paint area with polyurethane paint. Remove tank from service and contact Lincoln Composites Customer Service for factory inspection. Tank will be evaluated by engineering for possible rework procedures.
Gouge Damage
Gouges, impact Remove from service and Level 3 damage, fire damage/ condemn. exposure
Impact Damage
Fire Damage
15
Tanks exhibiting this condition have Level 3 damage and are to be condemned and destroyed. If damage to the tank is localized to the dome areas only, this damage or softness of the dome wall may be repairable. 3. Damage to tank bosses. Impact to the ends of the tank, including the valves, plumbing, and pressure relief devices, should be investigated to ensure composite damage has not been sustained. 4. Localized areas of surface crazing. Tanks which incur impact damage may exhibit circular, oval, or linear zones of crazing of the composite surface. These zones may also be accompanied by a change in coloration. Each area exhibiting these types of indications should be subjected to the tap test. Questionable areas should also be subjected to factory inspection. Note: Small random hairline cracks in the resin surface parallel to the reinforcing fibers are common in composite pressure tanks and are not a cause for concern. A group of cracks that are more closely spaced than generally observed on the tank and have a localized circular, oval, or linear pattern as described above are evidence of impact damage. 5. Differences in sound emitted by performance of a tap test in the potentially damaged area relative to the surrounding area. The tap test is a tool used to identify delaminations within the composite wall and should be performed only when the composite surface has been impacted. The tap test will not reveal delaminations from abrasion damage because abrasion damage will not delaminate underlying layers. The tap test is performed by tapping the surface of the composite with a quarter or similarly sized metal object grasped between the fingers. The tapping sound emitted by the surface should be compared in zones of potential damage relative to surrounding areas where damage is not suspected. The tap test must be confined to the cylinder portion of the tank. False indications may be heard if this is attempted in the dome (end) areas. Differences in sound are evidence of damage within the composite wall. Tanks exhibiting this type of damage must be removed from service. The tanks may be subjected to further field evaluation, factory inspection at Lincoln Composites, or be condemned and destroyed. Note: Only a registered or experienced inspector should perform the tap test. Any uncertainties that result from these inspections shall be resolved by removing the tank from service and performance of a factory inspection. Contact Lincoln Composites Customer Service regarding questions arising during the inspection and to make arrangements for factory inspection services and return authorization if necessary.
Figure 6-25 Level 3 Heat Damage Discoloration and Resin Burnout (Condemn) 6.6.5 Gas Leakage
Tanks that exhibit apparent gas leakage must be removed from service. Contact Lincoln Composites Customer Service to report the condition and obtain information regarding additional tank testing and disposition. Tanks with confirmed gas leaks are condemned and must be destroyed. Note: Bubbles are typically observed on the composite surface for several hours after pressurization, particularly after the initial pressurization following installation, or if the tank is empty or nearly empty. The bubbles are caused by air trapped between the liner and composite being forced through the composite when the tank is pressurized and the liner expands.
7.0
Non-Structural Anomalies
Frequently, tanks may exhibit superficial anomalies that have no effect on the structural quality of the tank. Non-structural anomalies include the following: 1. Fiber gaps on the surface of the dome area. Fiber gaps do not include loose fiber that has separated from the surface of the composite (see Figure 7-1). 2. Resin and paint runs, which may appear as a hard circle or spot on the tank surface. 3. Excessive resin on the composite surface. 4. Splices on the external TUFFSHELL wrap.
8.0
Tank Disposition
Tanks inspected in accordance with these guidelines will have one of four dispositions. These are: 1. The tank has no damage or Level 1 damage and is deemed acceptable. The tank may remain in service. 2. The tank has Level 2a damage that may be reworked in the field and the tank can be returned to service. 3. The tank has Level 2b damage that cannot be fully assessed in a field inspection and must be subjected to factory inspection. 4. The tank has Level 3 damage and is condemned, removed from service and destroyed.
9.0
Tank Destruction
Before condemning a tank, the owner of the tank must be notified. Tanks that are condemned must be clearly marked as CONDEMNED at the time of inspection. The marking shall be affixed to the manufacturers label and the duplicate manufacturers label, if used. To prevent unauthorized pressurization, the tank must be destroyed by drilling two or more holes one-half inch or greater in diameter completely through the tank wall and internal liner (see Figure 9-1). Caution: Residual natural gas and/or air can be trapped between the liner and the composite after venting. Allow the vented tank (open to atmosphere) to sit for 8 hours to allow the trapped gas to escape before drilling the condemned tank. Reference note in section 6.6.5. Note: The vessel will contain residual gas fumes after depressurization. Precautions should be taken to ensure that residual fumes are not ignited during destruction. Vent all pressure from the tank and displace residual fumes with compressed nitrogen. If compressed nitrogen is not available, flushing the tank with water will also displace residual fumes.
Tank Condemn Tool List Drill with 1/2 inch (13 mm) bit Compressed nitrogen (see 9.0 Note) supply to remove as much natural gas as possible. If nitrogen is not available then flush the tank with water.
17
Figure 10-1 Roof Pack Assembly 10.0 Tank Pack Components General Information
The following section applies to Lincoln Composites standard line of tank packs. While some of the procedures and descriptions may apply to non-standard, custom designed tank packs, this document does not specifically apply to them. Six main components to the Lincoln Composites tank pack are shown in Figure 10-1. These are: 1. Frame: Riveted steel construction with black powder coat finish and unitized mounting rail for vehicle integration 2. Tank Brackets: Steel construction with black powder coat finish. Mounting brackets, two (2) per tank. 3. Tanks: All-composite, NGV-2 Type 4 for 3000 psi (207 Bar) or 3600 psi (248 Bar) working pressure. 4. Valves: Manual or solenoid valves are available. One valve per cylinder. 5. Plumbing System: Type 300 stainless steel tubing supported with polyethylene bushings. Stainless steel compression fittings, flare fittings, SAE ports, and NPT fittings. The plumbing system includes a fill connection and vent lines. 6. Cover Set: Reinforced fiberglass doors with hardware, skirts, brackets, nose fairing, and support frame. Depending on the tank pack configuration, each door can have up to three (3) latches actuated with a single T handle. Important Note: Doors are held open with a single prop rod at the center of each door. The prop rod inserts into the middle door latch to hold the door open safely. To close the door, the T handle will have to be turned to release the prop rod. The prop rod will have to be properly stowed by inserting it into the prop rod storage clip located on the frame rail.
10.2
Frame Inspection
The metal frame is composed of many individual sections that are riveted or welded together. Inspection of the tank pack frame must include weld inspection, rivet inspection, and inspection for damage to metal frame sections. 1. Weld Inspection: Ensure that all welds (that are visually accessible) are not cracked or broken. 2. Rivet Inspection: Ensure that the rivet is holding the sections of the frame together and a loose condition does not exist. Frame Inspection: Ensure that the frame is in good condition and has not been damaged. Areas that had the powder coat finish removed should be cleaned and sanded thoroughly and repainted with high quality rust inhibiting epoxy paint. Questions of specific damage to the frame should be directed to Lincoln Composites Customer Service.
3.
18
11.0
5. 6.
Note: Insure tank pack assembly is vented of all fuel before loosening any fittings or brackets. See Important Note on venting in section 6.1.
11.1
1. 2.
Door Removal
3.
Remove door cover on the same side as the tank to be removed. Stand on the opposite side of door to be opened and pull the T handle out of the recess of the door (of door to be removed). Rotate the T handle to open the door. The door will swing away from where you are standing. With the door open remove the prop rod from its holder and engage the prop rod in the latch until the latch closes around the prop rod pin. With the door open, locate the set screws on the inside of the hinges. The setscrews can only be accessed with the door open. Loosen the set screws enough to be able to remove the door hinge pin shown in Figure 11-1. NOTE: Do not remove the hinge pins at this time.
7.
8.
Close the door cover and latch into place. With the door cover in the closed position, locate the door hinges at the bottom outside edge of the tank pack assembly. Remove the hinge pins by inserting a 0.1 inch (2.54 mm) punch into the hinge pin opening. With a 16 oz. hammer, pound the pin out the opposite side of the hinge. Repeat this step to remove all hinge pins for each door. Reference Figure 11-2 for the correct location to place the end of the center punch to remove (drive out) the hinge pin. Stand on the opposite side of the door to be opened and the pull T handle out of the recess of the door (of door to be removed) and rotate the T handle to the left to disengage the latches. The door cover is ready to be removed from frame.
Loosen fitting nuts A and B (reference Figure 11-3). After nuts are loose, slide the nuts away from the fitting on the vent line.
Container to be removed
4.
NOTE: If tank pack has skirts along the length of the tank pack, it may be necessary to remove the skirts to access the cover door hinges. To remove the skirt rivets, reference section 13.1 of this manual. Hinge pins can be accessed through the inside with the door covers open. If the hinge pins need to be removed with the cover doors open, then the door will have to be held in position while the pins are removed. With the door open, use 2 each 7/16 inch wrenches to remove both eyebolts that attach door cables. Ensure that the door is restrained in such a position to allow for the slack in the cables before removing the eyebolts.
Nut B
19
2.
3.
The connecting vent line may now be removed by pulling the tube assembly away from the center of the tank pack assembly. Once the tube assembly has been removed, place the assemblies on a clean surface for re-use during installation. On the valve end, loosen both nuts C (reference Figure 11-4). After the nuts are loose, slide the nuts away the from fittings.
Tank to be removed Nuts C
should be placed on a clean surface for re-use during installation. The 1/2" Nylok nuts should be replaced after removal.
Open Slot Rocker Pin (Loosen and tighten from this open slotted rocker pin)
Nuts D
5.
Note: Rotation of the tank within the straps may be necessary if it becomes necessary to remove and replace a valve from the tank. The new valve orientation to the fuel lines will probably not line up for re-assembly without rotating the tank within the straps. 8. While the tank is removed, perform a visual inspection of the entire surface of the tank per section 6.6 of this manual. Record inspection results on the vehicle log or the individual tank inspection log. 9. Inspect and re-paint the mounting brackets as required per section 6.4 of this manual. 10. Inspect and replace strap rubber as required per section 6.4 of this manual.
2.
Clip
3.
Carriage Bolt Frame
4.
5. 6.
7.
20
7.
Attach a lifting sling to the center of the tank to be removed and lift most of the weight of the tank so as to remove the carriage bolts (Figure 11-5) that attach the clips to the tank pack frame. Place the bolts on a clean surface for re-use during installation. The tank is ready to be removed from the tank pack by lifting the tank straight up and guiding the tank past the latch pins and prop rod assemblies. 8. Loosen and remove both strap bolts (Figure 11-6) if required. After removal, the straps, rubber, and bolts should be placed on a clean surface for re-use during installation. The 1/2 inch Nylok nuts should be replaced after removal. Note: Rotation of the tank within the straps may be necessary if it becomes necessary to remove and replace a valve from the tank. The new valve orientation to the fuel lines will probably not line up for re-assembly without rotating the tank within the straps. 9. While the tank is removed, perform a visual inspection of the entire surface of the tank per section 6.6 of this manual. Record inspection results on the vehicle log or the individual tank inspection log. 10. Inspect and re-paint the mounting brackets as required per section 6.4 of this manual. 11. Inspect and replace strap rubber as required per section 6.4 of this manual.
6.
While ensuring proper alignment; reinstall the vent line assembly removed in Step 4 of section 11.2 or Step 2 of section 11.3 of this manual. Tighten nuts A and B (Figure 11-3) per the fitting manufacturers specifications. Note: It may be necessary to adjust the position of the positional elbow that nut B attaches to. If this fitting does not line up to the vent tube assembly, adjust the position of the fitting per the fitting manufacturer's specifications.
11.4
Tank Installation
After repair or replacement of damaged components, reinstall the tank per the following steps: 1. If the strap assemblies were removed, install the strap assemblies onto the tank. Note the position of the valve fuel line fittings and match the position of the tank within the straps to fit the existing fuel line fitting orientation on the tank pack. 2. Install the tank on to the tank pack and line up the clips with the corresponding holes in the frame. With the clips aligned, insert the carriage bolts (4 ea. per tank) through the clips and frame holes with the carriage bolt head inserted in the carriage holding hole. 3. Install the 1/2 inch Nylok nuts on to the carriage bolts and torque to the correct specifications as listed in Figure 6-4. 4. Attach and tighten nut D while ensuring proper alignment and nut E if necessary per the fitting manufacturers specifications (see Figure 11-4). 5. Insert the fuel line section removed in step 4 of section 11.2 or step 4 of 11.3. Tighten nuts C per the fitting manufacturers specifications (see Figure 11-4).
Leak Procedures
1. Close the tank valves and pressurize the tank supply lines to 500 psig with CNG. Inspect for leaks at all fitting locations with emphasis on fittings that were loosened or replaced.
21
2.
3.
4.
5.
Repair leaks as needed. Raise the pressure to operating pressure and check for leaks. Repair leaks as needed. Rinse all fittings that have been sprayed with liquid leak detector with water to wash off all residues that could corrode brass surfaces. WARNING: IF BUBBLES ARE DETECTED DO NOT ATTEMPT TO TIGHTEN THE FITTING UNDER PRESSURE. If no leaks are detected in the lines, then open the valves and pressurize to 500 psig and check for leaks. Allow the system to set for approximately a minute at full pressure and then proceed with a bubble test of all fittings and tanks. WARNING: ANY ATTEMPT TO TIGHTEN OR LOOSEN A FITTING UNDER PRESSURE IS EXTREMELY DANGEROUS. DO NOT ROTATE A FITTING UNDER PRESSURE. If a leak is detected, release the pressure from the system by draining the tank pressure. Ensure the tank is properly grounded per Important Note in section 6.1 of this manual before draining or venting the assembly. Verify that the pressure in the system (lines and tanks) is fully vented before proceeding. After the tank is safely vented, re-tighten the leaking fitting per the manufacturers specifications, and repeat the leak test per 11.6 items 1 and 2. If the fitting has a persistent leak that will not quit after proper tightening techniques are applied, then replace the fitting and line as necessary. Pressurize the system to 500 psig again and check for leaks. If no leaks exist, pressurize to operating pressure and check for leaks. Continue the process until no leaks exist.
Figure 12-2 Fitting Removal 12.1 PRD Manifold Assembly Replacement Procedures
1. Before any repairs to the PRD assembly can be accomplished, the tank pack must be vented of all pressurized gas. See Important Note in section 6.1 on venting pressure. Remove the tank located on the same side as the PRD manifold line clamps per instructions in section 11 of this manual. Determine what parts need to be replaced. Remove all damaged parts. Be careful not to loosen other connections to components that dont need repair. It may be necessary to remove the entire PRD manifold from the tank pack assembly to repair the manifold. Follow steps 4a through 4d to remove the manifold. 4a. Loosen and remove the fittings (2ea.) at the end of the PRD manifold (Figure 12-2). 4b.Loosen and remove all of the line clamps located on the PRD vertical supports (Figure 12-3). 4c. Carefully remove PRD manifold. Avoid twisting lines when removing the manifold. 4d.Lay out the removed manifold on a clean, flat surface for replacement or repair.
2.
3. 4.
8.
Flow arrow located in this area of the PRD.
7d. Re-install both fittings (2ea.) at the end of the PRD manifold per section 10 this manual. 7e. Tighten the line clamps with 70 inch pounds of torque (8 N*m). Re-install the fuel tank per section 11.4 of this manual.
Rivet Removal
The following steps should be followed for rivet removal. 1. 2. 3. Identify what rivets are in need of replacement. To remove the rivets, the rivet stem must be drilled out using a 5/32 inch (3.84 mm) drill bit. With the stem removed drill out the rivet hole with a 1/4 inch (6.35 mm) drill bit.
23
Rivet Installation
1. 2. Install the rivet into the rivet gun and insert the rivet into the hole. Actuate the rivet gun while keeping pressure against the rivet.
Fairing Removal
The following steps should be followed for fairing removal: 1. Loosen attaching bolts at both sides of the fairing from the U bracket support that is attached to the frame assembly shown in Figure 13-3. The U bracket need not be removed unless damaged. If damaged, the U bracket can be removed from the header rail with 2 each 7/16 inches wrenches. Place the removed bolts and washers on a clean surface for re-assembly later. All 1/4 inch Nylok nuts should be replaced after removal. 2. Remove the skirt rivets attached to the L bracket that is attached to the fairing as required. 3. Remove the rivets at the top and face of the fairing per section 13.2 of this manual. These rivets attach the fairing to the support bracket. With rivets and attaching bolts removed the fiberglass portion of the fairing can be removed. The fairing is to be installed in the reverse order of removal.
Skirt Removal
Note: Some tank pack configurations do not have skirts. If there are no skirts on your application, skip this section. The following steps should be followed for skirt removal. The skirt is located at the outer edge of the tank pack, between the tank pack and roof of the vehicle. 1. Remove all rivets holding the skirt in place per section 13.2 of this manual. The skirt will have to be held in place while removing the rivets to keep from damaging the skirt and/or the vehicle. 2. Remove the skirt from tank pack assembly.
13.5 Fairing Support Frame Removal and Installation Support Frame Removal
The following steps should be followed for removal of the support frame: 1. Remove all rivets attaching the support frame to the tank pack assembly. The two bottom rivets will have to be drilled out from the back side of the rivet. 2. With all rivets removed, the frame assembly is ready to be removed from the tank pack.
Skirt Installation
1. 2. Align the skirt holes with existing holes in the skirt mounting frame of the tank pack assembly. Install the rivet into the rivet gun and insert the rivet into the hole in the skirt and through the skirt mounting frame hole. Actuate the rivet gun while keeping pressure against the rivet.
3.
25
Appendix I
Weight
Lbs. 27 37 42 68 47 65 74 84 102 153 69 78 95 118 119 147 235 139 156 232 157 235 303 350 195 258 352 380 Kg. 12.4 16.8 19.1 30.8 21.3 29.5 33.6 38.1 46.3 69.4 31.3 35.4 43.1 53.5 54.0 66.7 106.6 63.0 68.6 105.3 71.2 106.6 137.4 158.8 88.3 117.0 159.7 172.4
3600 PSI (248 BAR)* Water Volume Gas Capacity Gasoline Equivalent
Cu. In. 905 1425 1655 2810 3061 3345 3932 4515 5695 8920 4390 5175 6685 7108 8620 10030 17620 10883 12147 19222 9128 15230 19695 23944 15304 21153 29352 32937 Liters 14.8 23.4 27.1 46.0 50.2 54.8 64.4 74.0 93.3 146.2 71.9 84.8 109.5 116.5 141.3 164.4 290.0 178.3 199.1 315.0 149.6 249.6 322.7 392.4 250.8 346.6 481.0 539.7 SCF** 153 244 284 482 531 574 675 775 977 1530 753 888 1147 1219 1479 1721 3023 1867 2083 3295 1566 2613 3379 4108 2624 3629 5032 5651 SCM 4.3 6.9 8.0 13.7 15.1 16.3 19.1 21.9 27.7 43.3 21.3 25.1 32.5 34.5 41.9 48.7 86.0 52.9 59.0 93.4 44.3 74.0 96.0 116.3 74.3 102.8 142.5 160.0 Gallons 1.2 2.0 2.3 3.9 4.4 4.6 5.4 6.2 7.9 12.3 6.1 7.2 9.2 9.8 11.9 13.9 24.4 15.1 16.8 26.6 12.6 21.1 27.2 33.1 21.2 29.3 42.1 45.6 Liters 4.7 7.5 8.7 14.7 16.5 17.5 20.6 23.6 29.8 46.7 23.0 27.1 35.0 37.2 45.1 52.5 92.3 57.0 63.8 100.7 47.8 79.8 103.2 125.4 80.3 110.8 159.2 172.5
Diesel Equivalent
Gallons 1.1 1.8 2.0 3.5 3.9 4.1 4.9 5.6 7.0 11.0 5.4 6.4 8.3 8.8 10.6 12.4 21.7 13.4 15.1 23.7 11.3 18.8 24.3 29.6 19.0 26.1 37.7 40.7 Liters 4.2 6.7 7.7 13.1 14.7 15.6 18.4 21.1 26.6 41.7 20.5 24.2 31.2 33.2 40.3 46.9 82.3 50.8 57.1 89.8 42.6 71.2 92.0 111.9 71.9 98.8 142.6 153.9
* Pressure rating at 70 F (21 C) ** Standard Cubic Feet. Natural gas capacity is based on a tank at service pressure filled with gas at a specific gravity of 0.60 and a temperature of 70F
Port sizes: 1 1/16 -12 UNF, 1 1/8-12 UNF, 2-12 UNF Tanks are available in boss mount configurations. Contact us for other sizes and service pressures. Valves, end plugs, pressure relief devices, bracket kits and tank packs are available.
Lincoln Composites, Inc. 6801 Cornhusker Highway, Lincoln, NE 68507 USA Tel: 1-800-279-TANK or 402-464-6611 Fax: 402-464-6777 E-mail: [email protected] www.lincolncomposites.com
26
Appendix II
27
Appendix III
Notes:
28