This document summarizes the air system sizing for the control room at the GAYATHI-3 project in Abu Dhabi, United Arab Emirates. The control room has a floor area of 2220 square feet and requires a central cooling coil with a capacity of 12.3 tons to handle a peak cooling load of 147.8 MBH. The required airflow is 6715 CFM based on a July design condition of 110.2°F dry bulb and 85°F wet bulb. Outdoor air ventilation for the space is designed at 50 CFM.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as RTF, PDF, TXT or read online on Scribd
0 ratings0% found this document useful (0 votes)
104 views1 page
Load Summary
This document summarizes the air system sizing for the control room at the GAYATHI-3 project in Abu Dhabi, United Arab Emirates. The control room has a floor area of 2220 square feet and requires a central cooling coil with a capacity of 12.3 tons to handle a peak cooling load of 147.8 MBH. The required airflow is 6715 CFM based on a July design condition of 110.2°F dry bulb and 85°F wet bulb. Outdoor air ventilation for the space is designed at 50 CFM.
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as RTF, PDF, TXT or read online on Scribd
You are on page 1/ 1
Air System Sizing Summary for Control Room
Project Name: GAYATHI-3
Prepared by: KHAIRALLA CENTRAL A/C
09/04/2011 10:34AM
Air System Information
Air System Name .................................. Control Room Equipment Class ........................................ PKG ROOF Air System Type ................................................ SZCAV
Number of zones ............................................................. 1
Floor Area ............................................................... 2220.0 ft Location .................... Abu Dhabi, United Arab Emirates
Sizing Calculation Information
Zone and Space Sizing Method: Zone CFM ....................... Sum of space airflow rates Space CFM ................... Individual peak space loads
Calculation Months ......................................... Jan to Dec
Sizing Data ...................................................... Calculated
Central Cooling Coil Sizing Data
Total coil load ......................................................... 12.3 Total coil load ....................................................... 147.8 Sensible coil load ................................................. 132.7 Coil CFM at Jul 1800 ............................................. 6715 Max block CFM ..................................................... 6715 Sum of peak zone CFM ........................................ 6715 Sensible heat ratio ............................................... 0.898 ft/Ton ................................................................... 180.2 BTU/(hr-ft) ............................................................. 66.6 Water flow @ 10.0 F rise ....................................... N/A
Tons MBH MBH CFM CFM CFM
Load occurs at ..................................................... Jul 1800
OA DB / WB ................................................... 110.2 / 85.0 Entering DB / WB ............................................. 76.7 / 64.5 Leaving DB / WB .............................................. 58.3 / 57.2 Coil ADP ..................................................................... 56.3 Bypass Factor .......................................................... 0.100 Resulting RH ................................................................. 52 Design supply temp. ................................................... 58.0 Zone T-stat Check ................................................... 1 of 1 Max zone temperature deviation .................................. 0.0
F F F F % F OK F
Central Heating Coil Sizing Data
Max coil load .......................................................... 51.4 MBH Coil CFM at Dec 0800 ........................................... 6715 CFM Max coil CFM ........................................................ 6715 CFM Water flow @ 20.0 F drop ..................................... N/A
Load occurs at ................................................... Dec 0800
BTU/(hr-ft) ................................................................. 23.1 Ent. DB / Lvg DB .............................................. 60.6 / 67.7 F
Supply Fan Sizing Data
Actual max CFM .................................................... 6715 CFM Standard CFM ....................................................... 6694 CFM Actual max CFM/ft ................................................ 3.02 CFM/ft
Fan motor BHP ........................................................... 0.00 BHP
Fan motor kW ............................................................. 0.00 kW Fan static .................................................................... 0.00 in wg CFM/person .............................................................. 10.00 CFM/person