Ask a qualified installer or contractor to install this product. Do not try to install the product yourself.
Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.
PCG0558
Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or
contractor to install those parts and accessories. Use of unauthorized parts and accessories or
improper installation of parts and accessories can result in water or refrigerant leakage, electrical
shock, fire or explosion.
Read the User's Manual carefully before using this product. The User's Manual provides important
safety instructions and warnings. Be sure to follow these instructions and warnings.
For any inquiries, contact your local distributor.
Dealer
Head Office:
Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,
Kita-ku, Osaka, 530-8323 Japan
Tokyo Office:
JR Shinagawa East Bldg., 2-18-1, Konan,
Minato-ku, Tokyo, 108-0075 Japan
http://www.daikin.com/global/
c All rights reserved
Printed in Japan 10/05/003 Y.K.
The specifications, designs, and information in this brochure are subject to change without notice.
AIR CONDITIONERS
LINE UP
Split
SkyAir
VRV
Packaged Air Conditioners
Contents
Al Nokhba Tower
(Elite Residential Suites)
Kuwait
June 2003
11 VRV Plus
S P L I T T y pe A i r C o n di t i o n e r s
7
Sanabel Tower Hotel
Saudi Arabia
January 2001
75 VRV Plus
Air Cooled Split Type Air Conditioners
Awqaf Tower
Qatar
June 2004
8 VRV Plus
Production Site
Overseas Affiliate
Production Site
Sales Agent
Overseas Affiliate
21
The Intelligent Air Conditioning System
Sales Agent
28.....HRV
29.....Control Systems
ASIA/OCEANIA
CHINA
EUROPE
33
Daikin Industries
Czech Republic
Daikin Airconditioning
UK
Since it's foundation in 1924, Daikin Industries, Ltd. has constantly been
developing to become a global leader in an array of fields, such as air
conditioning systems, refrigerants, fluorochemicals, electronics and hydraulic
machineries. In particular, Daikin holds the largest market share of both
residential- and commercial-use air conditioning systems in Japan. It is
the world's sole manufacturer that combines research, development and
manufacturing of air conditioning systems, refrigerants and compressors.
Daikin Airconditioning
Singapore
PACKAGED
AIR CONDITIONERS
42.....Water Chillers
Daikin Australia
JAPAN
U.S.A.
Daikin Airconditioning
France
Daikin Airconditioning
Spain
Daikin Airconditioning
Germany
Daikin Airconditioning
Italy
Kanaoka Factory,
Sakai Plant
Shiga Plant
Yodogawa Plant
Rinkai Factory,
Sakai Plant
Kashima Factory
Line up
Type
The Split System is the ideal air conditioning solution for one room or
an area of your home. Daikin air conditioners lead the industry with
their energy savings. Each indoor unit features silent operation
function, bringing comfort in your living room or bedroom.
Daikin now has a new D series. The simple and stylish design softly
harmonizes with your living space.
RT
Btu
kcal
kW
Model Name
Wallmounted
type
FT-D
C/O 60 Hz
FT-GA
C/O 60 Hz
FT-GA
C/O 50 Hz
Capacity class
1.42
17,100
4,300
5.0
1.72
20,500
5,160
6.0
FTY-GA H/P 60 Hz
Function list
Function
Wall-mounted type
FT60D
FT50/60GA FTY50/60GA
W I DE
ANGLE
Wide-angle louvers
Vertical auto-swing
Horizontal auto-swing
AUT O
Comfort
control
operation
Lifestyle
convenience
N EW
Healthy &
clean
Timer
Night set mode
Auto-restart after power failure
Worry free
SELF
Wall-mounted type
FT-D Series
FT(Y)-GA Series
5.06.0 kW
5.06.0 kW
Comfortable
Energy-saving
Using your air conditioner for extended periods of time is now a completely
affordable luxury thanks to Daikins advanced energy-saving technology.
Heating
Cooling
Outdoor Unit
Indoor Unit
Wireless
remote controller
Wipe-Clean
Flat Panel
FT(Y)50/60GA
Outdoor Unit
Indoor Unit
Indoor unit
FT50GAVEA
Outdoor unit
R50GV1K
Cooling capacity
*1 (1)/(2)
FT60GAVEA
R60GV1K
R60D
FT60DVMK
Outdoor unit
R60DVLK
CDB
Cooling capacity
*1 (2)/(3)
1 phase, 220 V, 60 Hz
1.96/1.59
23,500/19,100
5,900/4,800
6.9/5.6
2.71/3.10
2.55
19.4 to 54
1.83/1.82
22,000/21,800
5,540/5,500
6.44/6.40
2.42/2.41-2.51/2.50
2.66-2.56
CDB
19.4 to 54
*1 (1)/(2)
1.52/1.51
18,200/18,100
4,590/4,560
5.34/5.30
2.01/2.00-2.19/2.18
2.65-2.43
RT
Btu/h
kcal/h
kW
kW
Indoor unit
FT50GAVAL
FT60GAVAL
FTY50GAVAL
FTY60GAVAL
Outdoor unit
R50GVAL
R60GVAL
RY50GVAL
RY60GVAL
Power Supply
RT
Btu/h
kcal/h
kW
kW
RY60G
1 phase, 220-240 V, 50 Hz
Power Supply
Cooling capacity
RY50G
Power Supply
R60G
Wireless
remote controller
FT50/60GA
Model
R50G
Heating capacity
*2(1)/(2)
Conversion rates
RT
Btu/h
kcal/h
kW
RT
Btu/h
kcal/h
kW
kW
kW
1.59/1.28
19,100/15,400
4,800/3,900
5.6/4.5
2.18/2.50
2.57
1 phase, 220 V, 60 Hz
1.93/1.59
23,200/19,100
5,850/4,800
6.8/5.6
2.68/3.06
2.54
1.65/1.42
19,800/17,100
4,990/4,300
5.8/5.0
1.79/1.71
21,500/20,500
5,420/5,200
6.3/6.0
2.00/2.30
1.87/1.85
2.90
3.37
Cooling*1 (2)/(3)
Heating*2 (1)/(2)
Cooling *1 (2)
COP
Heating *2 (2)
19.4 to 54
19.4 to 54
Operation range Cooling
CDB
(Outdoor unit)
-10 to 15
Heating
CWB
Notes: *1: Nominal cooling capacities are based on the following conditions:
(1) Return air temperature: 27CDB, 19.5CWB, Outdoor temperature: 35CDB. Equivalent ref. piping: 5 m (Horizontal)
(2) Return air temperature: 27CDB, 19.0CWB, Outdoor temperature: 35CDB. Equivalent ref. piping: 5 m (Horizontal)
(3) Return air temperature: 29CDB, 19.0CWB, Outdoor temperature: 46CDB, 24CWB. Equivalent ref. piping: 7.5 m (Horizontal) (SSA385/386)
*2:Nominal heating capacities are based on the following conditions:
(1) Return air temperature: 20CDB, Outdoor temperature: 7CDB, 6CWB. Equivalent ref. piping: 5 m (Horizontal)
(2) Return air temperature: 21CDB, Outdoor temperature: 7CDB, 6CWB. Equivalent ref. piping: 7.5 m (Horizontal) (SSA385/386)
Power comsumption
kcal/h = kW x 860
Btu/h = kW x 3412
RT = kW x 0.284
1 phase, 220 V, 60 Hz
1.85/1.59
22,200/19,100
5,590/4,800
6.5/5.6
2.04/2.02
24,500/24,200
6,180/6,100
7.19/7.10
2.61/2.97
2.44/2.46
2.49
2.95
Conversion rates
kcal/h = kW x 860
Btu/h = kW x 3412
RT = kW x 0.284
Type
Capacity
Line Up
Model Name
RT
1.6
1.9
2.3
3.2
4.1
4.5
6.8
8.3
13.6
16.6
Btu
19100
23200
27600
38900
48800
53900
81900
99600
163400
199300
kW
5.6
6.8
8.1
11.4
14.3
15.8
24.0
29.2
47.9
58.4
2.5
10
15
20
HP
FHC
Ceiling
mounted
cassette type
Indoor units.....................................10
60 Hz
FHYC
H/P
FH
C/O
FHY
H/P
60 Hz
FHK
C/O
50 Hz
Ceiling
mounted
built-in type
FHB
C/O
50 Hz
FHYB
H/P
60 Hz
Wall mounted
type
FA
C/O
FAY
H/P
FV
C/O
FVY
H/P
Ceiling
suspended type
Ceiling mounted
cassette corner
type
Floor standing
type
Stores often feature the latest in designed decor. This refined beauty attracts
people.
Meanwhile, offices have a functional beauty. This encourages those within to
work hard and apply intelligence and passion to their tasks.
In either situation, a certain elegance should fill the space because thinking
minds require high quality air conditioning. SkyAir by Daikin ensures a
comfortable indoor environment. All over the world, stores, offices, and homes
prefer the low operating noise, attractive design, complete comfort control,
and other benefits brought by SkyAir.
C/O
FH(Y)C
Specifications..................................11
Simultaneous operation system......16
50 Hz
FDBG
Duct
connection
low static
pressure
type
FDB
FDYB
60 Hz
50 Hz
60 Hz
50 Hz
60 Hz
60 Hz
50 Hz
60 Hz
60 Hz
50 Hz
C/O
60 Hz
H/P
60 Hz
50 Hz
FDMG
Duct
connection
middle static
pressure
type
50 Hz
C/O
60 Hz
FD(Y)M
50 Hz
H/P
Duct
connection
high static
pressure
type
FD
C/O
FDY
H/P
60 Hz
50 Hz
60 Hz
50 Hz
60 Hz
Operation system
Applicable Models
Capacity
4.5
6.3
7.6
Btu
53900
75700
90800
kW
15.8
22.2
26.6
10
HP
50 Hz
C/O
Indoor unit
Indoor unit
60 Hz
Twin
50 Hz
Outdoor
unit
H/P
50 Hz
Indoor unit
Triple
60 Hz
*1
C/O
60 Hz
Indoor unit
Indoor unit
Outdoor
unit
*2
50 Hz
H/P
60 Hz
*2
50 Hz
Indoor unit
Double
Twin
C/O
60 Hz
Indoor unit
Indoor unit
Indoor unit
Outdoor
unit
50 Hz
H/P
*1
60 Hz
Notes: Specifications for RT, Btu and kW are based on the following conditions; Power supply: 60 Hz; Cooling: Indoor temp. of 27CDB, 19.0CWB, and outdoor temp. of 35.0CDB.
The values given for 2 HP to 6 HP are for the FHY(C) model and 8 HP to 20 HP are for the FD model. The values given for simultaneous operation system are for the FHYC model.
*1:FDYB and FDYM model operate for 2025 (kW) class.
*2:FDYB and FDYM model operate for 20 (kW) class.
Indoor units
Ceiling Mounted Built-in Type
FH(Y)C
FA(Y)
FDMG
FDB(G)
FDYB
FD(Y)M
FD(Y)
For details, please refer to P33-P40.
Outdoor Unit
R emote C ontroller
LCD Wireless
LCD Wired
Remote Controller Remote Controller
10
Outdoor unit
60
71
100
125
FHC50KVE
FHC60KVE
FHC71KVE
FHC100KVE
FHC125KVE
R71FUV1
R100FUV1
R71FUY1
R100FUY1
R60GV1K
R50GV1
Power supply
R125FUY1
VE: 1 phase, 220-240 V/220 V, 50/60 Hz/V1: 1 phase, 220-240 V,50 Hz/Y1: 3 phase, 380-415 V,50 Hz
kW
RT
1.5/1.5
1.8/1.8
2.2/2.2
3.0/3.0
Cooling capacity
Btu/h
18,200/18,100
22,000/21,800
26,600/26,300
36,200/35,800
44,400/43,700
*1 (1)/(2)
kcal/h
4,590/4,560
5,540/5,500
6,700/6,600
9,100/9,000
11,200/11,000
7.80/7.7
10.6/10.5
2.55/2.53
10.6/10.5
13.0/12.8
3.69/3.65
4.39/4.35
2.87/2.88
2.96/2.94
COP *1 (1)/(2)
3.6/3.56
3.06/3.04
2.94/2.95
CDB
21 to 52
60
71
100
125
FH50BVE
FH60BVE
FH71BVE
FH100BVE
FH125BVE
R71FUV1
R100FUV1
R71FUY1
R100FUY1
R50GV1
R60GV1K
R125FUY1
RT
1.5/1.4
1.9/1.8
2.2/2.2
3.0/3.0
Btu/h
17,700/17,400
22,500/22,200
26,600/26,300
36,200/35,800
44,400/43,700
kcal/h
4,460/4,400
5,690/5,600
6,700/6,600
9,100/9,000
11,200/11,000
3.7/3.6
36,200/35,800
44,400/43,700
6,700/6,600
9,100/9,000
11,200/11,000
kW
7.8/7.7
10.6/10.5
13.0/12.8
2.58/2.56
3.79/3.75
4.67/4.63
3.02/3.01
2.80/2.80
2.78/2.76
COP *1
7.80/7.7
kW
10.6/10.5
2.67/2.65
13.0/12.8
3.76/3.74
2.92/2.91
(1)/(2)
4.49/4.45
2.82/2.81
CDB
2.9/2.88
21 to 52
45
60
Indoor unit
FHK45FV1
FHK60FV1
Outdoor unit
R50GV1
R60GV1K
Power supply
1 phase, 220-240 V, 50 Hz
RT
1.5/1.4
1.9/1.8
Cooling capacity
Btu/h
17,700/17,400
22,500/22,200
*1 (1)/(2)
kcal/h
4,460/4,400
5,690/5,600
kW
5.19/5.1
6.6/6.5
kW
2.25/2.24
2.76/2.74
2.31/2.28
CDB
Model
2.39/2.37
45
60
Indoor unit
FHB45FV1
FHB60FV1
Outdoor unit
R50GV1
R60GV1K
Power supply
60
FHC60KVE
71
FHC71KVE
100
FHC100KVE
125
FHC125KVE
125
FHYC125KVE
140
FHYC140KVE
Outdoor unit
R50GVAL
R60GVAL
R71FUVAL
R100FUVAL
R125FUTAL
R125KUYALK
R140KUTALK
R140KUYALK
VE: 1 phase, 220-240 V/220 V, 50/60 Hz/VAL: 1 phase, 220 V, 60 Hz/TAL: 3 phase, 220 V, 60 Hz/YAL: 3 phase, 380 V, 60 Hz
Cooling capacity
Btu/h
17,700/17,400
22,500/22,200
*1 (1)/(2)
kcal/h
4,500/4,400
5,700/5,600
kW
5.19/5.1
6.6/6.5
kW
2.33/2.32
2.78/2.76
2.23/2.20
2.37/2.36
RT
1.6/1.3
1.9/1.6
2.3/1.9
3.2/2.6
Cooling capacity
Btu/h
19,100/15,400
23,200/19,100
27,600/22,900
38,900/30,700
48,800/42,700
48,800/42,700
53,900/47,800
*1 (1)/(2)
kcal/h
4,800/3,900
5,800/4,800
7,000/5,800
9,800/7,700
12,300/10,800
12,300/10,800
13,600/12,000
1.9/1.8
4.1/3.6
4.1/3.6
kW
5.6/4.5
6.8/5.6
8.1/6.7
11.4/9.0
14.3/12.5
14.3/12.5
15.8/14.0
kW
2.21/2.5
2.73/3.14
3.34/4.2
4.54/5.80
6.08/7.00
5.50/6.80
5.70/
2.53
2.49
2.43
2.51
2.35
2.60
CDB
19.4 to 54
2.77
21 to 54
71
100
125
FH50BVE
FH60BVE
FH71BVE
FH100BVE
FH125BVE
R50GVAL
R60GVAL
R71FUVAL
R100FUVAL
R125FUTAL
Power supply
VE: 1 phase, 220-240 V/220 V, 50/60 Hz/VAL: 1 phase, 220 V, 60 Hz/TAL: 3 phase, 220 V, 60 Hz/YAL: 3 phase, 380 V, 60 Hz
RT
1.5/1.3
1.8/1.6
2.3/1.9
3.2/2.6
4.1/3.6
Cooling capacity
Btu/h
17,900/15,400
22,200/19,100
27,600/22,900
38,900/30,700
48,800/42,700
*1 (1)/(2)
kcal/h
4,500/3,900
5,600/4,800
7,000/5,800
9,800/7,700
12,300/10,800
kW
5.25/4.5
6.5/5.6
8.1/6.7
11.4/9.0
14.3/12.5
kW
2.3/2.5
2.84/3.2
3.44/4.2
4.67/5.80
6.25/7.00
2.28
2.29
2.35
2.44
2.29
Conversion rates
kcal/h = kW x 860
Btu/h = kW x 3412
RT = kW x 0.284
60
Indoor unit
Outdoor unit
CDB
19.4 to 54
21 to 54
11
4.5/4.0
KUTALK.....6.80, KUYALK.....7.10
19.4 to 54
50
FHC50KVE
COP *1 (1)
1 phase, 220-240 V, 50 Hz
1.5/1.4
Indoor unit
Power supply
19.4 to 54
CDB
3.0/3.0
26,600/26,300
6.6/6.5
COP *1 (1)/(2)
2.2/2.2
Btu/h
2.8/2.78
RT
R125FUY1
kcal/h
2.36/2.34
COP *1 (1)/(2)
R100FUY1
*1 (1)/(2)
5.19/5.1
R71FUY1
Cooling capacity
2.40/2.37
21 to 52
125
FV125LAVE
R100FUV1
RT
3.7/3.6
2.16/2.15
19.4 to 54
100
FV100LAVE
R71FUV1
VE: 1 phase, 220-240 V/220 V, 50/60 Hz/V1: 1 phase, 220-240 V, 50 Hz/Y1: 3 phase, 380-415 V, 50 Hz
kW
CDB
71
FV71LAVE
Outdoor unit
Power supply
kW
COP *1 (1)/(2)
Operation range (Outdoor temp.)
Indoor unit
Model
*1 (1)/(2)
kW
kW
7.8/7.7
3.00/2.98
VE: 1 phase, 220-240 V/220 V, 50/60 Hz/V1: 1 phase, 220-240 V, 50 Hz/Y1: 3 phase, 380-415 V, 50 Hz
9,100/9,000
2.60/2.58
Outdoor unit
36,200/35,800
6,700/6,600
6.44/6.4
Cooling capacity
Model
26,600/26,300
kcal/h
2.63/2.62
Power supply
3.0/3.0
Btu/h
*1 (1)/(2)
2.45/2.44
Indoor unit
Model
R100FUY1
Cooling capacity
5.34/5.3
Model
R71FUY1
2.2/2.2
2.64/2.64
21 to 52
R100FUV1
VE: 1 phase, 220-240 V/220 V, 50/60 Hz/V1: 1 phase, 220-240 V, 50 Hz/Y1: 3 phase, 380-415 V, 50 Hz
2.02/2.01
19.4 to 54
100
FA100FVEK
R71FUV1
RT
3.7/3.6
kW
CDB
71
FA71FVEK
Outdoor unit
Power supply
kW
COP *1 (1)/(2)
Operation range (Outdoor temp.)
Indoor unit
Model
Conversion rates
kcal/h = kW x 860
Btu/h = kW x 3412
RT = kW x 0.284
12
Model
100
Indoor unit
FA71FVEK
FA100FVEK
Outdoor unit
R71FUVAL
R100FUVAL
Power supply
Model
3.2/2.7
Cooling capacity
Btu/h
27,600/22,900
38,900/32,400
*1 (1)/(2)
kcal/h
7,000/5,800
9,800/8,200
kW
8.1/6.7
11.4/9.5
kW
3.27/4.1
4.41/5.70
2.48
2.59
COP *1 (1)
Operation range (Outdoor temp.)
CDB
Outdoor unit
21 to 54
71
100
125
FV71LAVE
FV100LAVE
FV125LAVE
R71FUVAL
Power supply
R100FUVAL
R125FUTAL
2.3/1.9
3.2/2.6
4.1/3.6
Cooling capacity
27,600/22,900
38,900/30,700
48,800/42,700
*1 (1)/(2)
kcal/h
7,000/5,800
9,800/7,700
12,300/10,800
kW
8.1/6.7
11.4/9.0
14.3/12.5
kW
3.40/4.3
4.62/5.90
6.20/7.10
2.47
2.31
2.38
CDB
125
FHYC125KVE
Outdoor unit
RY50GVAL
RY60GVAL
RY71FUVAL
RY100FUVAL
RY125FUTAL
VE: 1 phase, 220-240 V/220 V, 50/60 Hz/VAL: 1 phase, 220 V, 60 Hz/TAL: 3 phase, 220 V, 60 Hz/YAL: 3 phase, 380 V, 60 Hz
RT
Btu/h
1.6/1.4
1.8/1.6
2.3/1.9
3.2/2.6
4.1/3.6
4.5/4.0
19,800/17,100
22,200/19,100
27,600/22,900
38,900/30,700
48,800/42,700
53,900/47,800
4,990/4,300
5,590/4,800
7,000/5,800
9,800/7,700
12,300/10,800
13,500/12,000
RT
1.8/1.7
2.0/2.0
2.6/2.4
3.6/3.4
4.6/4.3
5.1/4.8
Heating capacity
Btu/h
21,500/20,500
24,500/24,200
30,700/29,000
43,700/40,300
55,300/51,200
61,800/58,000
*2 (1)/(2)
kcal/h
5,420/5,200
6,180/6,100
11,000/10,100
12.8/11.8
13,900/12,900
16.2/15.0
15,600/14,600
18.1/17.0
Operation range
(Outdoor temp.)
Cooling *1 (1)/(2)
Heating *2 (1)/(2)
Cooling
*1 (1)
Heating
*2 (1)
Conversion rates
kcal/h = kW x 860
Btu/h = kW x 3412
RT = kW x 0.284
5.8/5.0
Heating
8.1/6.7
6.5/5.6
11.4/9.0
14.3/12.5
15.8/14.0
kW
6.3/6.0
7.19/7.1
7,700/7,300
9.0/8.5
kW
kW
2.03/2.34
2.66/3.06
3.72/4.30
4.69/5.90
5.88/6.60
5.70/7.30
1.87/1.85
7.19/7.1
9.0/8.5
12.8/11.8
16.2/15.0
18.1/17.0
2.86
3.37
2.44
2.92
2.18
2.43
2.43
2.77
2.59
2.90
CDB
CWB
Cooling
19.4 to 54
3.23
3.01
-5 to 54
-10 to 15
-10 to 15
-10 to 15.5
50
FHY50BVE
RY50GVAL
Indoor unit
Outdoor unit
Power supply
60
FHY60BVE
RY60GVAL
71
FHY71BVE
RY71FUVAL
100
FHY100BVE
RY100FUVAL
125
FHY125BVE
RY125FUTAL
VE: 1 phase, 220-240 V/220 V, 50/60 Hz/VAL: 1 phase, 220 V, 60 Hz/TAL: 3 phase, 220 V, 60 Hz
RT
1.6/1.4
1.8/1.6
2.3/1.9
3.2/2.6
4.1/3.6
Cooling capacity
Btu/h
19,800/17,100
22,200/19,100
27,600/22,900
38,900/30,700
48,800/42,700
*1 (1)/(2)
kcal/h
4,990/4,300
5,590/4,800
7,000/5,800
9,800/7,700
12,300/10,800
RT
1.8/1.7
2.0/2.0
2.6/2.4
3.6/3.4
4.6/4.3
Heating capacity
Btu/h
21,500/20,500
24,500/24,200
30,700/29,000
43,700/40,300
55,300/51,200
*2 (1)/(2)
kcal/h
5,420/5,200
6,180/6,100
7,700/7,300
11,000/10,100
13,900/12,900
21 to 54
140
FHYC140KVE
RY140KUTALK
RY140KUYALK
kcal/h
VE: 1 phase, 220-240 V/220 V, 50/60 Hz/VAL: 1 phase, 220 V, 60 Hz/TAL: 3 phase, 220 V, 60 Hz/YAL: 3 phase, 380 V, 60 Hz
RT
COP *1 (1)
100
FHYC100KVE
Cooling capacity
COP
Btu/h
71
FHYC71KVE
*1 (1)/(2)
Power comsumption
Indoor unit
60
FHYC60KVE
kW
50
FHYC50KVE
Power supply
RT
Indoor unit
kW
Power comsumption
COP
Operation range
(Outdoor temp.)
Cooling *1 (1)/(2)
Heating *2 (1)/(2)
Cooling *1 (1)
Heating *2 (1)
Cooling
Heating
5.8/5.0
6.5/5.6
8.1/6.7
11.4/9.0
14.3/12.5
kW
6.3/6.0
7.19/7.1
9.0/8.5
12.8/11.8
16.2/15.0
kW
kW
2.14/2.34
2.77/3.06
3.82/4.30
4.82/5.90
6.05/6.60
1.98/1.86
2.57/2.44
3.60/3.80
4.57/5.00
5.58/5.42
2.35
2.12
2.37
2.36
2.80
2.50
2.80
2.90
2.71
3.18
CDB
CWB
19.4 to 54
-5 to 54
-10 to 15
-10 to 15.5
71
100
125
Indoor unit
FHYB71FVAL
FHYB100FVAL
FHYB125FVAL
Outdoor unit
RY71FUVAL
RY100FUVAL
RY125FUTAL
Power supply
2.3/1.9
3.2/2.6
4.1/3.6
Cooling capacity
Btu/h
27,600/22,900
38,900/30,700
48,800/42,700
*1 (1)/(2)
kcal/h
7,000/5,800
9,800/7,700
12,300/10,800
kW
8.1/6.7
11.4/9.0
14.3/12.5
RT
2.6/2.4
3.6/3.4
4.6/4.3
Heating capacity
Btu/h
30,700/29,000
43,700/40,300
55,300/51,200
*2 (1)/(2)
kcal/h
7,700/7,300
11,000/10,100
13,900/12,900
Power comsumption
COP
Operation range
(Outdoor temp.)
Cooling *1 (1)/(2)
Heating *2 (1)/(2)
kW
9.0/8.5
12.8/11.8
16.2/15.0
kW
kW
3.82/4.30
4.76/5.90
6.05/6.70
3.57/3.80
4.49/5.00
5.56/5.60
Cooling
*1 (1)
2.12
2.39
2.36
Heating
*2 (1)
2.52
2.85
2.91
Cooling
CDB
-5 to 54
Heating
CWB
-10 to 15.5
Notes : *1: Nominal cooling capacities are based on the following conditions:
(1) Return air temperature: 27CDB, 19.0CWB, Outdoor temperature: 35CDB Equivalent ref. piping: 5 m (Horizontal)
(2) Return air temperature: 29CDB, 19.0CWB, Outdoor temperature: 46CDB, 24CWB Equivalent ref. piping: 7.5 m (Horizontal) (SSA385/386)
*2: Nominal heating capacities are based on the following conditions:
(1) Return air temperature: 20CDB, Outdoor temperature: 7CDB, 6CWB Equivalent ref. piping: 5 m (Horizontal)
(2) Return air temperature: 21CDB, Outdoor temperature: 7CDB, 6CWB Equivalent ref. piping: 7.5 m (Horizontal) (SSA385/386)
13
Conversion rates
kcal/h = kW x 860
Btu/h = kW x 3412
RT = kW x 0.284
14
Simultaneous Operation SystemTwin & Triple & Double Twin Multi Application Operation
100
Indoor unit
FAY71FVE
FAY100FVE
Outdoor unit
RY71FUVAL
RY100FUVAL
Power supply
2.3/1.9
3.2/2.6
Cooling capacity
Btu/h
27,600/22,900
38,900/30,700
*1 (1)/(2)
kcal/h
7,000/5,800
9,800/7,700
kW
8.1/6.7
11.4/9.0
RT
2.6/2.4
3.6/3.4
Heating capacity
Btu/h
30,700/29,000
43,700/40,300
*2 (1)/(2)
kcal/h
7,700/7,300
11,000/10,100
kW
9.0/8.5
12.8/11.8
kW
kW
3.67/4.20
4.61/5.80
3.44/3.70
4.36/4.90
2.21
2.47
Power comsumption
Cooling *1 (1)/(2)
Heating *2 (1)/(2)
COP
Cooling
Heating
Operation range
(Outdoor temp.)
Cooling
Heating
*1 (1)
2.62
*2 (1)
2.94
-5 to 54
CDB
CWB
-10 to 15.5
Note: This type of system does not allow individual control or independent operation of
indoor units. It is not the best choice for large rooms with partitions.
71
Model
100
125
Indoor unit
FVY71LAVE
FVY100LAVE
FVY125LAVE
Outdoor unit
RY71FUVAL
RY100FUVAL
RY125FUTAL
Power supply
VE: 1 phase, 220-240 V/220 V, 50/60 Hz/VAL: 1 phase, 220 V, 60 Hz/TAL: 3 phase, 220 V, 60 Hz
Cooling capacity
*1 (1)/(2)
2.3/1.9
3.2/2.6
4.1/3.6
Btu/h
27,600/22,900
38,900/30,700
48,800/42,700
12,300/10,800
kcal/h
7,000/5,800
9,800/7,700
kW
8.1/6.7
11.4/9.0
14.3/12.5
RT
2.6/2.4
3.6/3.4
4.6/4.3
Heating capacity
Btu/h
30,700/29,000
43,700/40,300
55,300/51,200
*2 (1)/(2)
kcal/h
7,700/7,300
11,000/10,100
13,900/12,900
kW
9.0/8.5
12.8/11.8
16.2/15.0
kW
kW
3.78/4.40
4.77/6.00
6.00/6.70
3.55/3.90
4.52/5.15
5.53/5.60
2.14
2.39
2.38
2.83
2.93
Power comsumption
Cooling *1 (1)/(2)
Heating *2 (1)/(2)
COP
Cooling
Heating
Operation range
(Outdoor temp.)
Cooling
Heating
*1 (1)
2.54
*2 (1)
CDB
CWB
-5 to 54
-10 to 15.5
Notes : *1: Nominal cooling capacities are based on the following conditions:
(1) Return air temperature: 27CDB, 19.0CWB, Outdoor temperature: 35CDB Equivalent ref. piping: 5 m (Horizontal)
(2) Return air temperature: 29CDB, 19.0CWB, Outdoor temperature: 46CDB, 24CWB Equivalent ref. piping: 7.5 m (Horizontal) (SSA385/386)
*2: Nominal heating capacities are based on the following conditions:
(1) Return air temperature: 20CDB, Outdoor temperature: 7CDB, 6CWB Equivalent ref. piping: 5 m (Horizontal)
(2) Return air temperature: 21CDB, Outdoor temperature: 7CDB, 6CWB Equivalent ref. piping: 7.5 m (Horizontal) (SSA385/386)
Indoor units include the super cassette type, duct connection low and middle static pressure type and ceiling suspended type.
RT
Conversion rates
kcal/h = kW x 860
Btu/h = kW x 3412
RT = kW x 0.284
*Typical combination
15
16
Simultaneous Operation SystemTwin & Triple & Double Twin Multi Application Operation
(For specifications of duct connection series, please refer to P35-P40.)
Model
Indoor unit
250
200
250
FHYC100KVEX 2
FHYC125KVEX 2
FHY100BVEX 2
FHY125BVEX 2
FHYC71KVEX 3
Outdoor unit
Power supply
RT
FHYC50KVEX 4
FHYC60KVEX 4
R200KUY1
R250KUY1
Model
Indoor unit
FHY71BVEX 3
Outdoor unit
Power supply
RT
FHY50BVEX 4
FHY60BVEX 4
RY200KUY1
RY250KUY1
Cooling capacity
Btu/h
76,800/75,700
92,500/90,800
Cooling capacity
Btu/h
76,800/75,700
92,500/90,800
*1 (1)/(2)
kcal/h
19,400/19,100
23,300/22,900
*1 (1)/(2)
kcal/h
19,400/19,100
23,300/22,900
kW
22.5/22.2
27.1/26.6
kW
22.5/22.2
27.1/26.6
7.7/7.6
9.7/9.7
RT
6.4
8.1
2.92/2.92
2.79/2.74
Heating capacity
Btu/h
77,500
96,900
*2 (1)
kcal/h
19,500
24,400
kW
(1)/(2)
CDB
-5 to 52
Power comsumption
Indoor unit
200
250
FHY100BVEX 2
FHY125BVEX 2
FHY71BVEX 3
Model
Outdoor unit
Power supply
RT
FHY50BVEX 4
FHY60BVEX 4
R200KUY1
R250KUY1
Btu/h
76,800/75,700
92,500/90,800
*1 (1)/(2)
kcal/h
19,400/19,100
23,300/22,900
kW
22.5/22.2
27.1/26.6
kW
7.7/7.6
CDB
Cooling
*1 (1)/(2)
Heating
*2 (1)
22.7
kW
kW
7.7/7.6
28.4
9.7/9.7
6.5
9.2
2.92/2.92
2.79/2.74
3.49
3.09
Conversion rates
kcal/h = kW x 860
Btu/h = kW x 3412
RT = kW x 0.284
9.7/9.7
2.92/2.92
(1)/(2)
Heating *2 (1)
kW
Notes : *1: Nominal cooling capacities are based on the following conditions:
(1) Return air temperature: 27CDB, 19.5CWB, Outdoor temperature: 35CDB Equivalent ref. piping: 5 m (Horizontal)
(2) Return air temperature: 27CDB, 19.0CWB, Outdoor temperature: 35CDB Equivalent ref. piping: 5 m (Horizontal)
*2: Nominal heating capacities are based on the following conditions:
(1) Return air temperature: 20CDB, Outdoor temperature: 7CDB, 6CWB Equivalent ref. piping: 5 m (Horizontal)
Cooling capacity
COP *1
COP
Cooling *1 (1)/(2)
2.79/2.74
-5 to 52
Model
Indoor unit
200
250
FHYC100KVEX 2
FHYC125KVEX 2
FHYC71KVEX 3
Outdoor unit
Power supply
RT
FHYC50KVEX 4
FHYC60KVEX 4
RY200KUY1
RY250KUY1
Cooling capacity
Btu/h
76,800/75,700
92,500/90,800
*1 (1)/(2)
kcal/h
19,400/19,100
23,300/22,900
kW
22.5/22.2
27.1/26.6
RT
6.4
8.1
Btu/h
77,500
96,900
Heating capacity
*2 (1)
kcal/h
Power comsumption
Cooling *1 (1)/(2)
Heating *2 (1)
Cooling *1 (1)/(2)
COP
Heating
*2 (1)
19,500
22.7
kW
kW
7.7/7.6
9.7/9.7
6.5
9.2
2.92/2.92
2.79/2.74
3.49
3.09
Notes : *1: Nominal cooling capacities are based on the following conditions:
(1) Return air temperature: 27CDB, 19.5CWB, Outdoor temperature: 35CDB Equivalent ref. piping: 5 m (Horizontal)
(2) Return air temperature: 27CDB, 19.0CWB, Outdoor temperature: 35CDB Equivalent ref. piping: 5 m (Horizontal)
*2: Nominal heating capacities are based on the following conditions:
(1) Return air temperature: 20CDB, Outdoor temperature: 7CDB, 6CWB Equivalent ref. piping: 5 m (Horizontal)
17
24,400
kW
28.4
Conversion rates
kcal/h = kW x 860
Btu/h = kW x 3412
RT = kW x 0.284
18
Simultaneous Operation SystemTwin & Triple & Double Twin Multi Application Operation
(For specifications of duct connection series, please refer to P35-P40.)
200
250
140
FHYC71KVEX 2
FHYC100KVEX 2
FHYC125KVEX 2
FHYC71KVEX 2
Indoor unit
FHYC71KVEX 3
FHYC50KVEX 3
Model
Outdoor unit
R140KUTALK
Power supply
FHYC60KVEX 4
FHYC50KVEX 4
R200KUTAL
R250KUTAL
R200KUYAL
R250KUYAL
Model
4.5/4.0
6.3/5.7
7.6/6.8
Cooling capacity
Btu/h
53,900/47,800
75,700/68,200
90,800/82,200
*1 (1)/(2)
kcal/h
13,500/12,000
19,100/17,200
22,900/20,700
kW
15.8/14.0
22.2/20.0
26.6/24.1
kW
5.70/6.80
8.20/10.0
10.20/12.5
2.77
2.71
2.61
CDB
21 to 54
Heating capacity
*2 (1)/(2)
COP
Operation range
(Outdoor temp.)
140
FHY71BVEX 2
Indoor unit
200
FHY100BVEX 2
FHY50BVEX 3
Outdoor unit
R140KUTALK
Power supply
RY250KUTAL
RY250KUYAL
Cooling *1 (1)/(2)
kW
Heating *2 (1)/(2)
kW
Cooling *1 (1)
Heating *2 (1)
Cooling
CDB
Heating
CWB
4.5/4.0
53,900/47,800
13,500/12,000
15.8/14.0
5.1/4.8
61,900/58,000
15,600/14,600
18.1/17.0
5.7/6.9
5.6/5.7
2.77
3.23
-5 to 54
6.3/5.7
75,800/68,300
19,100/17,200
22.2/20.0
6.4/6.4
77,500/76,500
19,500/19,300
22.7/22.4
8.2/10.0
7.0/7.1
2.71
3.24
7.6/6.8
90,800/82,300
22,900/20,700
26.6/24.1
8.1/8.0
97,000/95,600
24,400/24,100
28.4/28.0
10.2/12.5
9.7/9.9
2.61
2.93
0 to 54
-10 to 15
250
FHY125BVEX 2
RT
FHY50BVEX 4
FHY60BVEX 4
R200KUTAL
R250KUTAL
R200KUYAL
R250KUYAL
VE: 1 phase, 220-240 V/220 V, 50/60 Hz/TAL: 3 phase, 220 V, 60 Hz/YAL: 3 phase, 380 V, 60 Hz
6.3/5.7
7.6/6.8
Cooling capacity
Btu/h
4.5/4.0
53,900/47,800
75,700/68,200
90,800/82,200
*1 (1)/(2)
kcal/h
13,500/12,000
19,100/17,200
22,900/20,700
kW
15.8/14.0
22.2/20.0
26.6/24.1
kW
5.70/6.90
5.7/6.9
8.20/10.0
8.2/10.0
10.20/12.5
10.2/12.5
2.77
2.71
2.61
COP *1 (1)
Operation range (Outdoor temp.)
FHYC60KVEX 4
FHY71BVEX 3
Model
RT
Btu/h
kcal/h
kW
RT
Btu/h
kcal/h
kW
*1 (1)/(2)
Power comsumption
250
FHYC125KVEX 2
VE: 1 phase, 220-240 V/220 V, 50/60 Hz/TAL: 3 phase, 220 V, 60 Hz/YAL: 3 phase, 380 V, 60 Hz
Cooling capacity
-5 to 54
FHYC50KVEX 3
RY140KUTALK
Power supply
VE: 1 phase, 220-240 V/220 V, 50/60 Hz/TAL: 3 phase, 220 V, 60 Hz/YAL: 3 phase, 380 V, 60 Hz
RT
Indoor unit
Outdoor unit
200
FHYC100KVEX 2
FHYC50KVEX 4
FHYC71KVEX 3
RY200KUTAL
RY200KUYAL
CDB
-5 to 54
Notes : *1: Nominal cooling capacities are based on the following conditions:
(1) Return air temperature: 27CDB, 19.0CWB, Outdoor temperature: 35CDB Equivalent ref. piping: 5 m (Horizontal)
(2) Return air temperature: 29CDB, 19.0CWB, Outdoor temperature: 46CDB, 24CWB Equivalent ref. piping: 7.5 m (Horizontal) (SSA385/386)
Model
Outdoor unit
Power supply
RT
Cooling capacity
Btu/h
*1 (1)/(2)
kcal/h
kW
RT
Conversion rates
kcal/h = kW x 860
Btu/h = kW x 3412
RT = kW x 0.284
Heating capacity
Btu/h
*2 (1)/(2)
kcal/h
kW
Power comsumption
COP
Operation range
(Outdoor temp.)
Cooling *1 (1)/(2)
200
250
FHY100BVEX 2
FHY125BVEX 2
X
FHY71BVE 3
FHY50BVEX 3
FHY60BVEX 4
FHY50BVEX 4
RY200KUTAL
RY250KUTAL
RY140KUTALK
RY200KUYAL
RY250KUYAL
VE: 1 phase, 220-240 V/220 V, 50/60 Hz/TAL: 3 phase, 220 V, 60 Hz/YAL: 3 phase, 380 V, 60 Hz
4.5/4.0
6.3/5.7
7.6/6.8
53,900/47,800
75,700/68,200
90,800/82,200
13,500/12,000
19,100/17,200
22,900/20,700
15.8/14.0
22.2/20.0
26.6/24.1
5.1/4.8
6.4/6.4
8.1/8.0
61,800/58,000
77,500/76,400
96,900/95,500
15,600/14,600
19,500/19,300
24,400/24,100
18.1/17.0
22.7/22.4
28.4/28.0
8.2/10.0
6.0/7.2
10.2/12.5
5.9/6.0
7.0/7.1
9.7/9.9
2.63
2.71
2.61
3.07
3.24
2.93
0 to 54
-5 to 54
-10 to 15
FHY71BVEX 2
Indoor unit
kW
Heating *2 (1)/(2) kW
Cooling *1 (1)
Heating *2 (1)
Cooling
CDB
Heating
CWB
Notes : *1: Nominal cooling capacities are based on the following conditions:
(1) Return air temperature: 27CDB, 19.0CWB, Outdoor temperature: 35CDB Equivalent ref. piping: 5 m (Horizontal)
(2) Return air temperature: 29CDB, 19.0CWB, Outdoor temperature: 46CDB, 24CWB Equivalent ref. piping: 7.5 m (Horizontal) (SSA385/386)
*2: Nominal heating capacities are based on the following conditions:
(1) Return air temperature: 20CDB, Outdoor temperature: 7CDB, 6CWB Equivalent ref. piping: 5 m (Horizontal)
(2) Return air temperature: 21CDB, Outdoor temperature: 7CDB, 6CWB Equivalent ref. piping: 7.5 m (Horizontal) (SSA385/386)
19
Conversion rates
kcal/h = kW x 860
Btu/h = kW x 3412
RT = kW x 0.284
20
Indoor Units.................................24
VRV II Series...............................25
VRV K Series...............................27
VRV II Series
Rising energy and general building services running costs have led end users to
expect a truly complete and acceptable air conditioning system. It must be energy
efficient, economic to run, easy to install, flexible, reliable and user friendly.
Featuring inverter technology and individual control, the VRV system
revolutionised building air conditioning the world over by meeting all these
requirements, and has been installed in various buildings throughout the world for
the last 20 years.
RT
6.4
8.0
12.7
14.3
15.9
19.1
20.7
22.3
23.9
Btu
76400
95500
152900
172000
191100
229300
248400
267500
286600
kW
22.4
28.0
44.8
50.4
56.0
67.2
72.8
78.4
84.0
10
16
18
20
24
26
28
30
HP
Capacity
Line Up
R410A
Series
Heat pump
Type
50 Hz
Heat pump
Type
60 Hz
Note: Specifications for RT, Btu and kW are based on the following conditions;
Cooling : Indoor temp. of 27-CDB, 19.0CWB, and outdoor temp. of 35.0CDB.
VRV K series
HRV
(Heat Reclaim Ventilation)
VAM150
21
VAM250
VAM350
VAM500
VAM650
VAM800
VAM1000
VAM1500
VAM 2000
22
Indoor Units
The
series comprises a wide range of indoor units designed
to meet virtually any installation site requirement.
Indoor units
Ceiling Mounted
Cassette Corner Type
FXCQ-MVE
FXFQ-MVE
FXSQ-MVE
Concealed
Floor Standing Type
FXLQ-MVE
FXAQ-MVE
FXHQ-MVE
FXMQ-MVE
FXDQ-NVE(T)*
FXKQ-MVE
Ceiling Mounted
Built-in Type
FXNQ-MVE
Capacity
Model
name
Type
1.0 ton 1.3 ton 1.6 ton 2.0 ton 2.6 ton 3.2 ton 4.0 ton 6.4 ton 8.0 ton
12300 15400 19100 24200 30700 38200 47800 76400 95500
31.25
40
50
62.5
80
100
125
200
250
1.25 HP 1.6 HP 2 HP 2.5 HP 3.2 HP 4 HP
5 HP
8 HP 10 HP
Floor S tanding
FXAQ-MHV1
FXUQ-MV1
FXLQ-MHV1
BEVQ-MVE
Capacity
Model
name
Type
RT
0.6 ton
Btu
7500
Index
20
HP
0.8 HP
Wall Mounted
FXAQ-MHV1
Floor Standing
FXLQ-MHV1
New Ceiling Suspended Cassette
FXUQ-MV1
Notes: Specifications for RT and Btu are based on the following conditions;
0.8 ton
9600
25
1 HP
1.0 ton
12300
31.25
1.25 HP
1.3 ton
15400
40
1.6 HP
1.6 ton
19100
50
2 HP
2.3 ton
27300
71
3 HP
3.2 ton
38200
100
4 HP
4.0 ton
47800
125
5 HP
Connectable
Outdoor
Unit
H/P
H/P
H/P
Indoor units in the 63 class are not available for the above models.
Connection unit BEVQ-M is necessary for each indoor unit.
Indoor unit
20
Power supply
Cooling capacity (1)/(2)
Heating capacity
RT
Btu/h
kcal/h
kW
RT
Btu/h
kcal/h
kW
0.7/0.6
7,800/7,500
2,000/1,900
2.3/2.2
0.7
8,500
2,200
2.5
25
23
32
40
50
63
71
80
100
125
200
250
24
RT
6.4
8.0 12.7 14.3 15.9 19.1 20.7 22.3 23.9
Btu 76400 95500 152900 172000 191100 229300 248400 267500 286600
Series
kW 22.4 28.0 44.8 50.4 56.0 67.2 72.8 78.4 84.0
HP
8
10
16
18
20
24
26
28
30
Heat pump type
8, 10 HP
16, 18, 20 HP
RXYQ8MY1K(E)
RXYQ10MY1K(E)
(50 Hz)
Note: Specifications for RT, Btu and kW are based on the following conditions;
Cooling : Indoor temp. of 27-CDB, 19.0CWB, and outdoor temp. of 35.0CDB.
RXYQ16MY1K(E)
RXYQ18MY1K(E)
RXYQ20MY1K(E)
RXYQ10MY1K(E)
RXYQ16MY1K(E)
RXYQ18MY1K(E)
RXYQ20MY1K(E)
RXYQ8MY1K(E)
RXYQ8MY1K(E)
RXYQ8MY1K(E)
RXYQ10MY1K(E)
RXYQ10MY1K(E)
RXYQ10MY1K(E)
Power supply
Heating capacity
(*5)
MODE
RXYQ8MYLK(E)
RXYQ10MYLK(E)
RXYQ16MYLK(E)
RXYQ18MYLK(E)
RXYQ20MYLK(E)
RXYQ8MYLK(E)
RXYQ8MYLK(E)
RXYQ8MYLK(E)
RXYQ10MYLK(E)
RXYQ10MYLK(E)
RXYQ10MYLK(E)
RT
6.6/6.5
8.0/6.8
13.1/13.0
14.6/13.3
16.0/13.7
Btu/h
78,800/77,800
96,200/82,200
157,600/155,600
175,000/160,000
192,400/164,500
Constituent
Units
13.1/13.0
14.6/13.3
16.0/13.7
Btu/h
78,800/77,800
96,200/82,200
157,600/155,600
175,000/160,000
192,400/164,500
kcal/h
19,900/19,600
24,300/20,700
39,700/39,200
44,100/40,300
48,500/41,500
kcal/h
19,900/19,600
24,300/20,700
39,700/39,200
44,100/40,300
48,500/41,500
kW
23.1/22.8
28.2/24.1
46.2/45.6
51.3/46.9
56.4/48.2
kW
23.1/22.8
28.2/24.1
46.2/45.6
51.3/46.9
56.4/48.2
RT
6.4/6.4
8.0/6.8
12.7/12.7
14.3/13.2
15.9/13.7
RT
6.4/6.4
8.0/6.8
12.7/12.7
14.3/13.2
15.9/13.7
Btu/h
76,400/76,400
95,500/82,200
152,900/152,900
172,000/158,700
191,100/164,500
Btu/h
76,400/76,400
95,500/82,200
152,900/152,900
172,000/158,700
191,100/164,500
kcal/h
19,300/19,300
24,100/20,700
38,500/38,500
43,300/40,000
48,200/41,500
kcal/h
19,300/19,300
24,100/20,700
38,500/38,500
43,300/40,000
48,200/41,500
kW
22.4/22.4
28.0/24.1
44.8/44.8
50.4/46.5
56.0/48.2
kW
22.4/22.4
28.0/24.1
44.8/44.8
50.4/46.5
56.0/48.2
RT
7.1
8.9
14.2
16.0
17.9
RT
7.1
8.9
14.2
16.0
17.9
Btu/h
85,300
107,500
170,600
192,800
215,000
Btu/h
85,300
107,500
170,600
192,800
215,000
21,500
27,100
43,000
54,200
31.5
50.0
56.5
63.0
7.60/9.58
12.6/18.8
13.9/19.0
15.2/19.2
6.01/9.16
7.58/9.56
12.0/18.3
13.6/18.7
15.2/19.1
11.6
13.2
14.8
3.69/2.47
3.71/2.52
3.73/2.45
3.69/2.52
3.73/2.45
3.71/2.48
3.69/2.52
4.30
4.26
4.30
4.27
4.26
-5 to 50
-20 to 16
RXYQ28MY1K(E)
RXYQ30MY1K(E)
RXYQ8MY1K(E)
RXYQ10MY1K(E)
RXYQ10MY1K(E)
RXYQ10MY1K(E)
RXYQ10MY1K(E)
RXYQ10MY1K(E)
RT
19.7/19.4
21.1/19.8
22.6/20.2
24.0/20.5
Power supply
27,100
43,000
50.0
56.5
63.0
12.6/18.8
13.9/19.0
15.2/19.2
6.01/9.16
7.58/9.56
12.0/18.3
13.6/18.7
15.2/19.1
5.82
7.40
11.6
13.2
14.8
3.66/2.42
3.71/2.52
3.66/2.42
3.69/2.47
3.71/2.52
3.73/2.45
3.69/2.52
3.73/2.45
3.71/2.48
3.69/2.52
4.30
4.26
4.30
4.27
4.26
-5 to 50
Heating CWB
-20 to 16
RXYQ24MYLK(E)
RXYQ26MYLK(E)
RXYQ28MYLK(E)
RXYQ30MYLK(E)
Constituent
Units
RXYQ8MYLK(E)
RXYQ8MYLK(E)
RXYQ8MYLK(E)
RXYQ8MYLK(E)
RXYQ8MYLK(E)
RXYQ10MYLK(E)
RXYQ8MYLK(E)
RXYQ10MYLK(E)
RXYQ10MYLK(E)
RXYQ10MYLK(E)
RXYQ10MYLK(E)
RXYQ10MYLK(E)
RT
19.7/19.4
21.1/19.8
24.0/20.5
Btu/h
236,500/233,400
253,900/237,800
271,300/242,300
288,700/246,700
59,600/58,800
64,000/59,900
68,400/61,100
72,800/62,200
84.6/72.3
kW
69.3/68.4
74.4/69.7
79.5/71.0
84.6/72.3
23.9/20.5
RT
19.1/19.1
20.7/19.6
22.3/20.1
23.9/20.5
Btu/h
229,300/229,300
248,400/235,100
267,500/240,900
286,600/246,700
kcal/h
57,800/57,800
62,600/59,300
67,400/60,700
72,200/62,200
kW
67.2/67.2
72.8/68.9
78.4/70.6
84.0/72.3
RT
21.3
23.1
25.0
26.8
Btu/h
255,900
278,100
300,300
322,400
236,500/233,400
253,900/237,800
271,300/242,300
288,700/246,700
59,600/58,800
64,000/59,900
68,400/61,100
72,800/62,200
kW
69.3/68.4
74.4/69.7
79.5/71.0
RT
19.1/19.1
20.7/19.6
22.3/20.1
Btu/h
229,300/229,300
248,400/235,100
267,500/240,900
286,600/246,700
kcal/h
57,800/57,800
62,600/59,300
67,400/60,700
72,200/62,200
kW
67.2/67.2
72.8/68.9
78.4/70.6
84.0/72.3
RT
21.3
23.1
25.0
26.8
Btu/h
255,900
278,100
300,300
322,400
75,700
54,200
31.5
7.60/9.58
CDB
MODE
48,600
25.0
kcal/h
Btu/h
70,100
Cooling
21,500
6.31/9.41
Power supply
kcal/h
64,500
RXYQ8MY1K(E)
RXYQ8MY1K(E)
RXYQ10MY1K(E)
Heating (*5)
kW
3.66/2.42
RXYQ26MY1K(E)
kcal/h
Cooling (*1)/(*2)
7.40
RXYQ8MY1K(E)
RXYQ8MY1K(E)
RXYQ8MY1K(E)
kW
Heating capacity
(*5)
3.71/2.52
RXYQ24MY1K(E)
kcal/h
Cooling capacity
(*3)/(*4)
5.82
Constituent
Units
Cooling (*1)/(*2)
Cooling capacity
(*1)/(*2)
3.66/2.42
CDB
MODEL
48,600
25.0
6.31/9.41
Heating CWB
Heating capacity
(*5)
RXYQ24MYLK(E)
RXYQ26MYLK(E)
RXYQ28MYLK(E)
RXYQ30MYLK(E)
8.0/6.8
kW
Cooling capacity
(*3)/(*4)
Note: Specifications for RT, Btu and kW are based on the following conditions;
Cooling : Indoor temp. of 27-CDB, 19.0CWB, and outdoor temp. of 35.0CDB.
6.6/6.5
kcal/h
Cooling capacity
(*1)/(*2)
16, 18, 20 HP
RXYQ16MYLK(E)
RXYQ18MYLK(E)
RXYQ20MYLK(E)
RT
Cooling (*1)/(*2)
Operation range
8, 10 HP
RXYQ8MYLK(E)
RXYQ10MYLK(E)
(60 Hz)
Power supply
Cooling capacity
(*3)/(*4)
RT
6.4
8.0 12.7 14.3 15.9 19.1 20.7 22.3 23.9
Btu 76400 95500 152900 172000 191100 229300 248400 267500 286600
kW 22.4 28.0 44.8 50.4 56.0 67.2 72.8 78.4 84.0
HP
8
10
16
18
20
24
26
28
30
Heat pump type
Series
MODEL
Cooling capacity
(*1)/(*2)
Capacity
Line Up
Capacity
Line Up
81,300
75.0
81.5
88.0
94.5
18.9/28.2
20.2/28.4
21.5/28.6
22.8/28.7
18.0/27.5
19.6/27.9
21.2/28.3
22.7/28.7
Cooling capacity
(*1)/(*2)
Cooling capacity
(*3)/(*4)
Heating capacity
(*5)
kcal/h
kW
Cooling (*1)/(*2)
64,500
70,100
75,700
81,300
75.0
81.5
88.0
94.5
18.9/28.2
20.2/28.4
21.5/28.6
22.8/28.7
18.0/27.5
19.6/27.9
21.2/28.3
22.7/28.7
17.5
19.0
20.6
22.2
17.5
19.0
20.6
22.2
3.66/2.42
3.68/2.45
3.70/2.49
3.71/2.52
3.66/2.42
3.68/2.45
3.70/2.49
3.71/2.52
3.73/2.45
3.71/2.47
3.70/2.50
3.69/2.52
3.73/2.45
3.71/2.47
3.70/2.50
3.69/2.52
4.30
4.28
4.27
4.26
4.30
4.28
4.27
4.26
Cooling
CDB
Heating CWB
-5 to 50
-20 to 16
Note : 1. Optional models (-E type) feature components treated for heat and rust corrosion resistance, such as external panels, fan motor, and electric component box, in addition to the fins of
the heat exchanger. These models are designed specifically for use in areas which are subject to salt damage and atmospheric pollution. Please contact Daikin for more information.
2. Specifications are based on the following conditions;
Cooling : (*1) Indoor temp. of 27CDB, 19.5CWB, and outdoor temp. of 35CDB.
(*2) Indoor temp. of 27CDB, 19.5CWB, and outdoor temp. of 46CDB.
Conversion rates
(*3) Indoor temp. of 27CDB, 19.0CWB, and outdoor temp. of 35CDB.
(*4) Indoor temp. of 27CDB, 19.0CWB, and outdoor temp. of 46CDB.
kcal/h = kW x 860
Heating : (*5) Indoor temp. of 20CDB, and outdoor temp. 7CDB/6CWB.
Btu/h
= kW x 3412
Sound level : (*4) Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. During actual operation,
RT = kW x 0.284
these values are normally somewhat higher as a result of ambient conditions.
25
Heating (*5)
Cooling
CDB
Heating CWB
-5 to 50
-20 to 16
Note : 1. Optional models (-E type) feature components treated for heat and rust corrosion resistance, such as external panels, fan motor, and electric component box, in addition to the fins of
the heat exchanger. These models are designed specifically for use in areas which are subject to salt damage and atmospheric pollution. Please contact Daikin for more information.
2. Specifications are based on the following conditions;
Cooling : (*1) Indoor temp. of 27CDB, 19.5CWB, and outdoor temp. of 35CDB.
(*2) Indoor temp. of 27CDB, 19.5CWB, and outdoor temp. of 46CDB.
Conversion rates
(*3) Indoor temp. of 27CDB, 19.0CWB, and outdoor temp. of 35CDB.
(*4) Indoor temp. of 27CDB, 19.0CWB, and outdoor temp. of 46CDB.
kcal/h = kW x 860
Heating : (*5) Indoor temp. of 20CDB, and outdoor temp. 7CDB/6CWB.
Btu/h = kW x 3412
Sound level : (*4) Anechoic chamber conversion value, measured at a point 1 m in front of the unit at a height of 1.5 m. During actual operation,
RT = kW x 0.284
these values are normally somewhat higher as a result of ambient conditions.
26
The individual control of the air conditioning system for 45 rooms can be realized
by more simple and lesser installation work.
Shops
Office
ON/OFF signal
Cooling/Heating mode signal
Set temperature signal
Ventilation signal
Humidifier ON/OFF signal
Housing
Others
Type
Model
name
Capacity
shop
Indoor unit
RT
1.0 ton
Btu
12300
Index 31.25
HP
1.25 HP
1.3 ton
15400
40
1.6 HP
1.6 ton
19100
50
2 HP
2.0 ton
24200
62.5
2.5 HP
2.6 ton
30700
80
3.2 HP
3.2 ton
38200
100
4 HP
4.0 ton
47800
125
5 HP
6.4 ton
76500
200
8 HP
FXC-LVE
FXFL-LVE
FXK-LVE
FXYD-KAVE
FXS-LVE
FXM-LVE
FXH-LVE
FXA-LVE
FXL-LVE
FXN-LVE
Daikin's HRV recovers heat energy lost through ventilation and holds
down room temperature changes caused by ventilation, thereby
maintaining a comfortable and clean environment.
The HRV is interlocked to Daikin's
system, SkyAir and other air
conditioning systems and automatically switches over ventilation mode,
further increasing the effects of energy conservation.
31.25
40
Power supply
Cooling capacity (1)/(2)
Heating capacity
RT
Btu/h
kcal/h
kW
RT
Btu/h
kcal/h
kW
1.1/1.0
12,600/12,300
3,200/3,100
3.7/3.6
1.1
13,600
3,400
4.0
1.3/1.3
16,000/15,400
4,000/3,900
4.7/4.5
1.4
17,100
4,300
5.0
50
62.5
80
100
125
200
4.1/4.0
49,500/47,800
12,500/12,000
14.5/14.0
4.5
54,600
13,800
16.0
6.5/6.4
78,500/76,400
19,800/19,300
23.0/22.4
7.1
85,300
21,500
25.0
Power comsumption
COP
RSNY8KTAL
22.4kw(8HP)
27
Cooling (*1)/(*2)
Heating
Cooling (*1)/(*2)
Heating
VAM350FAVE
VAM500FAVE
VAM1000FAVE
R emote C ontroller
VAM1500FAVE
VAM2000FAVE
Model
RSNY8KTAL
Power supply
Conversion rates
kcal/h = kW x 860
Btu/h = kW x 3412
RT = kW x 0.284
Outdoor Unit
VAM150FAVE
Note: Specifications for RT and Btu are based on the following conditions; Cooling : Indoor temp. of 27-CDB, 19.0CWB, and outdoor temp. of 35.0CDB.
Model
HRV
LCD remote controller
for indoor unit
RT
Btu/h
kcal/h
kW
RT
Btu/h
kcal/h
kW
kW
kW
3 phase, 220 V, 60 Hz
6.4/7.1
76,400/85,300
19,300/21,500
22.4/25.0
7.1
85,300
21,500
25.0
8.9/8.5
11
2.52/2.94
2.27
Notes: 1. Optional models (-E type) feature components treated for heat and rust corrosion
resistance, such as external panels, fan motor, and electric component box, in
addition to the fins of the heat exchanger. Please contact Daikin for more
information.
2. Specifications are based on the following conditions;
Cooling: (*1) Indoor temp.: 27.0CDB, 19.0CWB, Outdoor temp.: 35.0CDB
(*2) Indoor temp.: 29.0CDB, 19.0CWB, Outdoor temp.: 46.0CDB
Heating: (*3) Indoor temp.: 20.0CDB, Outdoor temp.: 7.0CDB/6.0CWB.
Conversion rates
kcal/h = kW x 860
Btu/h = kW x 3412
RT = kW x 0.284
Model
Power supply
External Static
Pressure (Pa)
[50 Hz/60 Hz]
Temp. exchange
efficiency (H/L)
Enthalpy exchange
efficiency (H/L)
Ultra-High
150/150
250/250
350/350
500/500
650/650
800/800
1,000/1,000
1,500/1,500
2,000/2,000
High
150/150
250/250
350/350
500/500
650/650
800/800
1,000/1,000
1,500/1,500
2,000/2,000
Low
110/110
155/145
230/210
350/300
500/440
670/660
870/800
1,200/1,200
1,400/1,400
Ultra-High
69/98
64/98
98/142
98/147
93/162
137/225
157/196
137/206
137/196
High
39/54
39/54
70/85
54/54
39/69
98/118
98/108
98/118
78/88
Low
20/24
20/20
25/15
25/20
25/34
49/69
78/69
49/69
59/69
72/77(72/77)
75/78(75/78)
% For heating
50 Hz (60 Hz)
64/69(64/71)
64/68(64/69)
65/67(65/68)
66/68(66/71)
66/68(66/68)
66/70(66/70)
% For cooling
50 Hz (60 Hz)
58/64(58/66)
58/62(58/63)
60/62(60/63)
61/63(61/66)
61/64(61/64)
61/66(61/66)
28
Control Systems
Control Systems
DCS302C61
Combination with Unified ON/OFF controller, schedule timer and BMS system
Airflow volume and direction can be controlled individually for indoor units in each group operation.
Ventilation volume and mode can be controlled for Heat Reclaim Ventilation (HRV).
DCS301B61
The same operation modes and settings as with wired remote controllers are
possible.
DST301B61
Wireless remote
controller
(Installed type)
Part name
Model No.
DCS302A52
DTA102A52
DTA107A55
Concealed type
Exposed type
29
DTA103A51
Function
Interface between the central monitoring board and central
control units. Combined with the central remote controller,
this adaptor enables the central monitoring board to
centralize such functions as the on/off control, operation
status monitoring, and normal/malfunction monitoring.(*1)
30
Control Systems
Daikin's advanced air-conditioning control systems
New
New
Function 4
Air Conditioning
Network Service System
modem for connections
Unification adaptor
for computerized control
[DCS302A52]
PCMCIA
Flash
Memory
New
Function 2
Pi Port
DCS601C51
RS-232C
New
Function 5
D -NET
New
Function 3
Trouble reports
Trouble reports
Mobile Phone
New
Function 3
DIII-NET
Plus Adapter
(option)
Indoor Unit
Via
internet
e
rad
Upg New
Ai unit
D -NET
Dio unit
DAM602A51/52/53
New
Contact signal
Remote PC
Light/Fan
Daikin Central
Air Conditioning
System
Ethernet
D -NET
VRV System
Local
monitoring
& control
Sub PC
HRV
New
Function 2
New
Function 3
New
Function 4
New
Function 5
New
Function 1
New
Function 6
e
rad
Upg New
Function 7
New
D -NET
Multi-PC
New
Function 6
Function 7
Air Conditioning
1
Network Service System
(Optional Maintenance Service)
D -NET
*2
Monitoring of room
enter/exit sign
Di Unit
HRV
WatchDOG
Remote
Control pump,
lighting
New
Function 1
N e w F u n c t io n s
Features control and monitoring functions for central
A/C products and an Air Conditioning Network
Service function.
Using an external contact via DIII-NET, monitors and
controls equipment such as lighting, fans, or
building security systems.
Interface for
Ethernet
BMS
VRV System
Fire alarm
Security
Elevator
Pump
Lighting
...etc
Power supply facility
HRV
DMS502A51
DMS504B51
Local Controller
*5
I/F unit
INTERNET
ACC center
Mainfunction information
by E-mail
Up to 40 outdoor units and 256 indoor uit groups on one gateway. (optional adapter)
Local dealers
are restrictions in applicable areas and release times, therefore please consult us separately for details.
*1.2. There
name varies upon the system size.
*3. Model
trademark of American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE).
* BACnet is aisregistered
a registered trade mark of Echelon Corporation.
*4.5. LForONWanORKS
one of the following can be selected: L oc al C ontroller, intelligent touch Controller, or intelligent Manager II.
*6. EthernetI/Fisunit,
a registered trademark of Xerox Corporation.
*
31
32
PACKAGEDAIR CONDITIONERS
Note: Availability of the products shown in this catalogue varies by country.
Line Up
Daikins duct connection type packaged air conditioners are the best choice
for stores and offices. By placing the air conditioner in the ceiling, the design
and finish of all areas remain attractive and unblemished. With minimal
operating sound, people nearby are almost unaware of the units presence.
And simultaneous operation of 2 to 4 indoor units with a single outdoor unit is
possible. When indoor units are distributed taking sunlight and human
occupation patterns into consideration, a comfortable air flow is effectively
spread throughout the room.
Air cooled packaged water chillers are also available.
Such systems can easily meet all the air-conditioning requirements of
factories and other large areas.
Type
Model Name
Air cooled
packaged
duct connection
series
Low static
pressure type
FDBG
Air cooled
packaged
duct connection
series
Middle static
pressure type
FDMG
Air cooled
packaged
duct connection
series
High static
pressure type
Air cooled
single packaged
air conditioners
Roof top type
FDB
Capacity
PACKAGEDAIR CONDITIONERS
RT
Btu
kW
HP
1.6
1.8
2.3
3.2
4.1
4.5
6.8
8.3
13.6 16.6 27.5
19100 22200 27600 38900 48800 53900 81900 99600 163400 199300 331000
5.6
6.5
8.1
11.4 14.3 15.8 24.0 29.2 47.9 58.4 97.1
2
2.5
3
4
5
6
8
10
15
20
30
50 Hz
C/O
60 Hz
50 Hz
FDYB
FD(Y)M
H/P
60 Hz
50 Hz
C/O
Simultaneous
operation
system
60 Hz
50 Hz
FDM
H/P
FD
C/O
FDY
H/P
UAT
C/O 50 Hz
60 Hz
UATY
H/P 50 Hz
60 Hz
60 Hz
50 Hz
60 Hz
50 Hz
60 Hz
Note: Specifications for RT, Btu and kW are based on the following conditions; Power supply: 60 Hz; Cooling: Indoor temp. of 27CDB, 19.0CWB, and outdoor temp. of 35.0CDB.
The values given for 2 HP to 3 HP are for the FDB model, 4 HP to 6 HP are for the FDM model and 8 HP to 20 HP are for the FD model.
The values given for 30 HP are for the UAT model and based on the following conditions; Power supply: 50 Hz; Cooling: Indoor temp. of 27C DB, 19.5C WB, and outdoor temp. of 35.0C DB.
WATER CHILLERS
Type
Air cooled
packaged
water chillers
33
HP
kW
Model Name
2
50
2.5
100
3
150
4
200
5
250
6
300
7.5
400
10
500
15
600
20
700
30
800
50 Hz
UWA
C/O
60 Hz
34
PACKAGEDAIR CONDITIONERS
Air Cooled Packaged Air ConditionersFD(Y)B(G) Series
Whisper Quiet
Durable
Handy
FDBG60/71AVE
FDB60/71KVE
FDBG50AVE
FDB50KVE
FDMG71AV1
Durable
The special acryl precoated fin (PE fin) for anti-corrosion
treatment on the outdoor unit heat exchanger ensures
greater resistance against salt damage and atmospheric
pollution than ever.
R emote C ontroller
For FDMG models
Outdoor Unit
For FD(Y)M models
Central control
FDYB60/71KAVE
R emote C ontroller
FD(Y)M04FAVAL
FDYM05/06FAVAL
FD(Y)M03FAVAL
Easy to Use
Easy to Use
FDMG100/125AV1
LCD wired
remote
controller
Digital Remote
Controller
Signal
Receiver
Unit
Outdoor Unit
Remote
Controller
Wireless Remote
Controller
Digital Remote
Controller
Remote
Controller
LCD Wired
Remote
Controller
Signal
Receiver
Unit
Indoor unit
Model
60
71
Indoor unit
FDBG50AVE
FDBG60AVE
FDBG71AVE
Outdoor unit
R50GV1
R60GV1K
Cooling capacity
*1 (1)/(2)
CDB
Model
Outdoor unit
Power Supply
*1 (2)/(3)
Heating capacity
*2 (1)/(2)
Power comsumption
COP
Operation range
(Outdoor temp.)
Cooling*1 (2)/(3)
Heating*2 (1)/(2)
Cooling*1 (2)
Heating *2 (1)
Cooling
Heating
R71FUV1
RT
Btu/h
kcal/h
kW
RT
Btu/h
kcal/h
kW
kW
kW
CDB
CWB
Model
R100FUV1
R125FUV1
R71AY1
R100FUY1
2.5/2.5
30,000/29,700
7,600/7,500
8.80/8.7
3.15/3.13
2.79/2.78
CDB
3.7/3.7
44,700/44,000
11,200/11,000
13.1/12.9
4.89/4.85
2.68/2.66
71
100
125
140
Indoor unit
FDM03FAVAL
FDM04FAVAL
FDM05FAVAL
FDYM06FAVAL
Outdoor unit
R71FUVAL
R100FUVAL
R125FUTAL
R140KUTALK
Power Supply
Cooling capacity
*1 (2)/(3)
50
60
71
50
60
71
FDB60KVE
FDB71KVE
FDYB50KAVE
FDYB60KAVE
FDYB71KAVE
R50GVAL
R60GVAL
R71FUVAL
RY50GVAL
RY60GVAL
RY71FUVAL
Notes: *1: Nominal cooling capacities are based on the following conditions:
(1) Return air temperature: 27CDB, 19.5CWB, Outdoor temperature: 35CDB Equivalent ref. piping: 5 m (Horizontal)
(2) Return air temperature: 27CDB, 19.0CWB, Outdoor temperature: 35CDB Equivalent ref. piping: 5 m (Horizontal)
(3) Return air temperature: 29CDB, 19.0CWB, Outdoor temperature: 46CDB, 24CWB Equivalent ref. piping: 7.5 m (Horizontal) (SSA385/386)
*2: Nominal heating capacities are based on the following conditions:
(1) Return air temperature: 20CDB, Outdoor temperature: 7CDB, 6CWB Equivalent ref. piping: 5 m (Horizontal)
(2) Return air temperature: 21CDB, Outdoor temperature: 7CDB, 6CWB Equivalent ref. piping: 7.5 m (Horizontal) (SSA385/386)
Shows net capacities. When cooling it is the value minus the heat of the indoor unit fan motor. When heating, the heat of the fan motor is added.
35
R71AV1
FDB50KVE
2.10/2.41
2.70/3.29
3.30/3.78
2.67
2.41
2.45
19.4 to 54
21 to 54
RT
Btu/h
kcal/h
kW
kW
R71FUY1
Indoor unit
Cooling capacity
VE: 1 phase, 220-240 V/220 V, 50/60 Hz/V1: 1 phase, 220-240 V, 50 Hz/Y1: 3 phase, 380-415 V, 50 Hz
1.5/1.5
2.0/2.0
2.2/2.2
18,200/18,100
24,000/23,800
26,600/26,300
4,590/4,560
6,050/6,000
6,700/6,600
5.34/5.30
7.03/6.97
7.80/7.70
2.06/2.05
2.76/2.75
2.82/2.8
2.59/2.59
2.55/2.53
2.77/2.75
19.4 to 54
21 to 52
RT
Btu/h
kcal/h
kW
kW
125
FDMG125AV1
Outdoor unit
*1 (1)/(2)
Power Supply
100
FDMG100AV1
Power Supply
Cooling capacity
Model
71
FDMG71AV1
Conversion rates
kcal/h = kW x 860
Btu/h = kW x 3412
RT = kW x 0.284
RT
Btu/h
kcal/h
kW
kW
2.3/1.9
27,600/22,900
7,000/5,800
8.10/6.7
3.44/3.92
2.35
CDB
4.5/4.0
53,900/47,800
13,500/12,000
15.8/14.0
5.80/7.00
2.72
Model
71
100
125
140
Indoor unit
FDYM03FAVAL
FDYM04FAVAL
FDYM05FAVAL
FDYM06FAVAL
Outdoor unit
RY71FUVAL
RY100FUVAL
RY125FUTAL
RY140KUTALK
Power Supply
Cooling capacity
*1 (2)/(3)
Heating capacity
*2(1)/(2)
RT
Btu/h
kcal/h
kW
RT
Btu/h
kcal/h
kW
kW
kW
2.3/1.9
27,600/22,900
7,000/5,800
8.1/6.7
2.6/2.4
30,700/29,000
7,700/7,300
9.00/8.50
3.82/4.37
3.57/3.59
2.12
2.52
Cooling*1 (2)/(3)
Heating*2 (1)/(2)
Cooling *1 (2)
COP
Heating *2 (1)
Operation range Cooling
CDB
(Outdoor temp.) Heating
CWB
Notes: *1: Nominal cooling capacities are based on the following conditions:
(1) Return air temperature: 27CDB, 19.5CWB, Outdoor temperature: 35CDB Equivalent ref. piping: 5 m (Horizontal)
(2) Return air temperature: 27CDB, 19.0CWB, Outdoor temperature: 35CDB Equivalent ref. piping: 5 m (Horizontal)
(3) Return air temperature: 29CDB, 19.0CWB, Outdoor temperature: 46CDB, 24CWB Equivalent ref. piping: 7.5 m (Horizontal) (SSA385/386)
*2:Nominal heating capacities are based on the following conditions:
(1) Return air temperature: 20CDB, Outdoor temperature: 7CDB, 6CWB Equivalent ref. piping: 5 m (Horizontal)
(2) Return air temperature: 21CDB, Outdoor temperature: 7CDB, 6CWB Equivalent ref. piping: 7.5 m (Horizontal) (SSA385/386)
Shows net capacities. When cooling it is the value minus the heat of the indoor unit fan motor. When heating, the heat of the fan motor is added.
For FDMG models, capacities show gross capacities which do not include a deduction for evaporator fan motor heat.
Power comsumption
4.5/4.0
53,900/47,800
13,500/12,000
15.8/14.0
5.1/4.8
61,800/58,000
15,600/14,600
18.10/17.00
5.80/7.00
5.80/5.90
2.72
3.12
-10 to 15
Conversion rates
kcal/h = kW x 860
Btu/h = kW x 3412
RT = kW x 0.284
36
PACKAGEDAIR CONDITIONERS
Air Cooled Packaged Air ConditionersFD(Y) Series
Model
200
250
Indoor unit
FDY08KAY1
FDY10KAY1
FDY15KAY1
FDY20KAY1
Outdoor unit
RY200KUY1
RY250KUY1
RY200KUY1X 2
RY250KUY1X 2
76,800/75,700
6.4/6.3
76,800/75,700
19,300/19,100
22.5/22.2
23.2
6.6
79,200
20,000
23.2
7.2/7.1
76,800/75,700
6.1
19,300/19,100
3.13/3.13
23.2
3.8
184,000/181,000
15.3/15.1
184,000/181,000
183,900/180,800
46,400/45,600
53.9/53.0
56.8
16.1
194,000
193,800
48,800
56.8
18.5/18.3
184,000/181,000
17.6
46,400/45,600
2.91/2.90
56.8
3.23
Power Supply
Cooling capacity
*1 (1)/(2)
Compact
FD03KY1
FD03KVAL
FD04KY1
FD04KVAL
FD05KY1
FD05KTAL
Heating capacity
*2(1)
Durable
Power comsumption
COP
Cooling*1 (2)/(3)
Heating*2 (1)
Cooling*1 (1)/(2)
Heating *2 (1)/(2)
RT
Btu/h
kcal/h
kW
RT
Btu/h
kcal/h
kW
kW
kW
400
500
Super Quiet
Indoor unit with the industry's lowest level of sound.
FD06KY1
FD06KTAL
Central control
FD(Y)08K(A)Y1
FD(Y)08K(A)TALYAL
FD(Y)10K(A)Y1
FD(Y)10K(A)TALYAL
Indoor unit
Model
Outdoor unit
200
250
FDY08KATAL
FDY10KATAL
FDY15KATAL
FDY20KATAL
FDY08KAYAL
FDY10KAYAL
FDY15KAYAL
FDY20KAYAL
RY200KUTAL
RY200KUYAL
Power Supply
FD(Y)15KAY1
FD(Y)15KATALYAL
R emote C ontroller
Cooling capacity
FD(Y)20KAY1
FD(Y)20KATALYAL
*1 (2)/(3)
Outdoor Unit
Heating capacity
*2(1)/(2)
Power comsumption
Signal
Receiver
Unit
COP
LCD wired
remote controller
(Only for Heat Pump)
Operation range
(Outdoor temp.)
Remote
Controller
(Only for Cooling Only)
71
100
125
140
200
250
400
500
Indoor unit
FD03KY1
FD04KY1
FD05KY1
FD06KY1
FD08KY1
FD10KY1
FD15KY1
FD20KY1
Outdoor unit
R71FUY1
R100FUY1
R125FUY1
RU06KY1
RU08K(U)Y1
RU10K(U)Y1
RU08K(U)Y1X 2 RU10K(U)Y1X 2
2.3/2.2
27,600/27,000
7,000/6,800
8.1/7.9
2.5/2.48
3.24/3.19
3.1/3.1
37,500/36,800
9,500/9,300
11.0/10.8
3.52/3.48
3.13/3.10
4.0/3.9
47,800/47,100
12,000/11,800
14.0/13.8
4.19/4.15
3.34/3.33
8.4/8.3
101,300/99,600
25,500/25,100
29.7/29.2
9.9/9.8
3.00/2.98
13.8/13.6
16.8/16.6
165,800/163,400 202,300/199,300
41,800/41,200
51,000/50,200
48.6/47.9
59.3/58.4
15.0/14.8
19.8/19.6
3.24/3.24
2.99/2.98
Power Supply
Cooling capacity
*1 (1)/(2)
RT
Btu/h
kcal/h
kW
kW
CDB
Cooling*1 (2)/(3)
Heating*2 (1)/(2)
Cooling*1 (2)
Heating *2 (1)
Cooling
Heating
RT
Btu/h
kcal/h
kW
RT
Btu/h
kcal/h
kW
kW
kW
CDB
CWB
6.3/5.6
75,700/67,600
19,100/17,000
22.2/19.8
6.6/6.5
79,200/78,100
20,000/19,700
23.2/22.9
7.7/9.4
6.6/6.7
2.88
3.52
400
500
RY250KUTAL
RY200KUTALX 2
RY250KUTALX 2
RY250KUYAL
RY200KUYALX 2
RY250KUYALX 2
Notes: *1: Nominal cooling capacities are based on the following conditions:
(1) Return air temperature: 27CDB, 19.5CWB, Outdoor temperature: 35CDB Equivalent ref. piping: 5 m (Horizontal)
(2) Return air temperature: 27CDB, 19.0CWB, Outdoor temperature: 35CDB Equivalent ref. piping: 5 m (Horizontal)
(3) Return air temperature: 29CDB, 19.0CWB, Outdoor temperature: 46CDB, 24CWB Equivalent ref. piping: 7.5 m (Horizontal) (SSA385/386)
*2: Nominal heating capacities are based on the following conditions:
(1) Return air temperature: 20CDB, Outdoor temperature: 7CDB, 6CWB Equivalent ref. piping: 5 m (Horizontal)
(2) Return air temperature: 21CDB, Outdoor temperature: 7CDB, 6CWB Equivalent ref. piping: 7.5 m (Horizontal) (SSA385/386)
15.1/13.4
180,800/161,400
45,600/40,700
53.0/47.3
16.1/16.1
193,800/193,100
48,800/48,700
56.8/56.6
19.4/23.8
18.6/19.0
2.73
3.05
Conversion rates
kcal/h = kW x 860
Btu/h = kW x 3412
RT = kW x 0.284
100
125
140
200
Indoor unit
FD03KVAL
FD04KVAL
FD05KTAL
FD06KTAL
FD08KTAL
Outdoor unit
R71FUVAL
R100FUVAL
R125FUTAL
RU06KTAL
RU08K(U)TAL
2.4/2.0
29,000/24,200
7,300/6,100
8.5/7.1
3.22/3.70
2.64
3.4/2.6
40,600/30,700
10,200/7,700
11.9/9.0
4.37/5.02
2.72
21 to 54
Power Supply
Cooling capacity
*1 (2)/(3)
RT
Btu/h
kcal/h
kW
kW
CDB
250
400
500
FD10KTAL
FD15KTAL
FD20KTAL
Notes: *1: Nominal cooling capacities are based on the following conditions:
(1) Return air temperature: 27CDB, 19.5CWB, Outdoor temperature: 35CDB Equivalent ref. piping: 5 m (Horizontal)
(2) Return air temperature: 27CDB, 19.0CWB, Outdoor temperature: 35CDB Equivalent ref. piping: 5 m (Horizontal)
(3) Return air temperature: 29CDB, 19.0CWB, Outdoor temperature: 46CDB, 24CWB Equivalent ref. piping: 7.5 m (Horizontal) (SSA385/386)
37
13.6/12.4
16.6/15.1
163,400/149,400 199,300/181,900
41,200/37,700
50,200/45,800
47.9/43.8
58.4/53.3
16.60/20.20
20.60/25.30
2.89
2.83
Conversion rates
kcal/h = kW x 860
Btu/h = kW x 3412
RT = kW x 0.284
38
PACKAGEDAIR CONDITIONERS
Simultaneous Operation SystemTwin, Triple & Double Twin Multi Application Operation
Indoor unit
FDYM04FAV1X 2
FDYM05FAV1X 2
FDYM03FAV1X 3
Outdoor unit
RY200KUY1
RY250KUY1
RY200KUY1
Power Supply
In large interior spaces a single indoor unit may not be able to provide uniform comfort. Installation of 2 to 4 units, distributed to
consider sun light and human gathering patterns, can provide an effective solution.
Cooling capacity
*1(1)/(2)
Heating capacity
In a single-floor restaurant, for example, positioning 4 units at strategic locations achieves comfortable air flow that reaches
every inch of the room.
Lower cost of installation than for individual pair type
*2(1)
Power comsumption
COP
Cooling*1 (1)/(2)
Heating*2 (1)
Cooling*1 (1)/(2)
Heating *2 (1)
RT
Btu/h
kcal/h
kW
RT
Btu/h
kcal/h
kW
kW
kW
VE: 1 phase, 220-240 V/220 V, 50/60 Hz/V1: 1 phase, 220-240 V, 50 Hz/Y1: 3 phase, 380-415 V, 50 Hz
6.4/6.3
7.7/7.6
6.4/6.3
76,800/75,700
92,500/90,800
76,800/75,700
19,400/19,100
23,300/22,900
19,400/19,100
22.5/22.2
27.1/26.6
22.5/22.2
6.4
8.1
6.4
77,500
96,900
77.500
19,500
24,400
19,500
22.7
28.4
22.7
7.7/7.6
9.9/9.9
8.0/7.9
6.5
9.4
6.8
2.92/2.92
2.69/2.74
2.81/2.81
3.49
3.02
3.34
Note: This type of system does not allow individual control or independent operation of indoor units. It is not the best choice for large rooms with partitions.
Indoor unit
Model
Outdoor unit
*1(2)/(3)
250
200
FDYM05FAVALX 2
FDYM03FAVALX 3
R200KUTAL
R250KUTAL
R200KUTAL
R200KUYAL
R250KUYAL
R200KUYAL
6.3/5.7
75,700/68,200
19,100/17,200
22.0/20.0
8.2/10.0
2.71
6.3/5.7
75,700/68,200
19,100/17,200
22.2/20.0
8.5/10.3
2.61
Power Supply
Cooling capacity
200
FDYM04FAVALX 2
RT
Btu/h
kcal/h
kW
kW
CDB
FDYB60KAVEX 4
FDYB71KAVEX 3
RY250KUTALYAL
RY200KUTALYAL
Cooling capacity
Model
*1(2)/(3)
200
250
200
Indoor unit
FDYM04FAV1X 2
FDYM05FAV1X 2
FDYM03FAV1X 3
Outdoor unit
R200KUY1
R250KUY1
R200KUY1
6.4/6.3
76,800/75,700
19,400/19,100
22.5/22.2
7.7/7.6
2.92/2.92
6.4/6.3
76,800/75,700
19,400/19,100
22.5/22.2
8.0/7.9
2.81/2.81
Power Supply
RT
Btu/h
kcal/h
kW
kW
Cooling capacity
*1(1)/(2)
200
FDYB50KAVEX 4
RY200KUTALYAL
Power Supply
250
Indoor unit
Outdoor unit
Heating capacity
*2(1)/(2)
RT
Btu/h
kcal/h
kW
RT
Btu/h
kcal/h
kW
kW
kW
CDB
CWB
VE: 1 phase, 220-240 V/220 V, 50/60 Hz/TAL: 3 phase, 220 V, 60 Hz/YAL: 3 phase, 380 V, 60 Hz
6.3/5.7
7.6/6.8
6.3/5.7
75,700/68,200
90,800/82,200
75,700/68,200
19,100/17,200
22,900/20,700
19,100/17,200
22.2/20.0
26.6/24.1
22.2/20.0
6.4/6.4
8.1/8.0
6.4/6.4
77,500/76,400
96,900/95,500
77,500/76,400
19,500/19,300
24,400/24,100
19,500/19,300
22.7/22.4
28.4/28.0
22.7/22.4
8.2/10.0
10.2/12.6
8.20/10.00
7.0/7.1
9.7/10.0
7.0/7.1
2.71
2.61
2.71
3.24
2.93
3.24
0 to 54
-10 to 15
Indoor unit
FDYB50KAVEX 4
FDYB71KAVEX 3
FDYB60KAVEX 4
Outdoor unit
RY200KUY1
RY200KUY1
RY250KUY1
Power Supply
Cooling capacity
*1(1)/(2)
Heating capacity
*2(1)
Power comsumption
COP
Cooling*1 (1)/(2)
Heating*2 (1)
Cooling*1 (1)/(2)
Heating *2 (1)
RT
Btu/h
kcal/h
kW
RT
Btu/h
kcal/h
kW
kW
kW
VE: 1 phase, 220-240 V/220 V, 50/60 Hz/V1: 1 phase, 220-240 V, 50 Hz/Y1: 3 phase, 380-415 V, 50 Hz
6.4/6.3
6.4/6.3
7.7/7.6
76,800/75,700
76,800/75,700
92,500/90,800
19,400/19,100
19,400/19,100
23,300/22,900
22.5/22.2
22.5/22.2
27.1/26.6
6.4
6.4
8.1
77,500
77,500
96,900
19,500
19,500
24,400
22.7
22.7
28.4
7.7/7.6
7.7/7.6
9.7/9.7
6.5
6.5
9.2
2.92/2.92
2.92/2.92
2.79/2.74
3.49
3.49
3.09
Notes: *1: Nominal cooling capacities are based on the following conditions:
(1) Return air temperature: 27CDB, 19.5CWB, Outdoor temperature: 35CDB Equivalent ref. piping: 5 m (Horizontal)
(2) Return air temperature: 27CDB, 19.0CWB, Outdoor temperature: 35CDB Equivalent ref. piping: 5 m (Horizontal)
(3) Return air temperature: 29CDB, 19.0CWB, Outdoor temperature: 46CDB, 24CWB Equivalent ref. piping: 7.5 m (Horizontal) (SSA385/386)
*2: Nominal heating capacities are based on the following conditions:
(1) Return air temperature: 20CDB, Outdoor temperature: 7CDB, 6CWB Equivalent ref. piping: 5 m (Horizontal)
(2) Return air temperature: 21CDB, Outdoor temperature: 7CDB, 6CWB Equivalent ref. piping: 7.5 m (Horizontal) (SSA385/386)
39
Conversion rates
kcal/h = kW x 860
Btu/h = kW x 3412
RT = kW x 0.284
Model
200
250
200
Indoor unit
FDYM04FAVALX 2
FDYM05FAVALX 2
FDYM03FAVALX 3
Outdoor unit
RY200KUTALYAL
RY250KUTALYAL
RY200KUTALYAL
Power Supply
Cooling capacity
*1(2)/(3)
Heating capacity
*2(1)/(2)
RT
Btu/h
kcal/h
kW
RT
Btu/h
kcal/h
kW
kW
kW
6.3/5.7
75,700/68,200
19,100/17,200
22.2/20.0
6.4/6.4
77,500/76,400
19,500/19,300
22.7/22.4
8.2/10.0
7.0/7.1
2.71
3.24
Notes: *1: Nominal cooling capacities are based on the following conditions:
(1) Return air temperature: 27CDB, 19.5CWB, Outdoor temperature: 35CDB Equivalent ref. piping: 5 m (Horizontal)
(2) Return air temperature: 27CDB, 19.0CWB, Outdoor temperature: 35CDB Equivalent ref. piping: 5 m (Horizontal)
(3) Return air temperature: 29CDB, 19.0CWB, Outdoor temperature: 46CDB, 24CWB Equivalent ref. piping: 7.5 m (Horizontal) (SSA385/386)
*2: Nominal heating capacities are based on the following conditions:
(1) Return air temperature: 20CDB, Outdoor temperature: 7CDB, 6CWB Equivalent ref. piping: 5 m (Horizontal)
(2) Return air temperature: 21CDB, Outdoor temperature: 7CDB, 6CWB Equivalent ref. piping: 7.5 m (Horizontal) (SSA385/386)
6.3/5.7
75,700/68,200
19,100/17,200
22.2/20.0
6.4/6.4
77,500/76,400
19,500/19,300
22.7/22.4
8.5/10.3
7.3/7.4
2.61
3.11
Conversion rates
kcal/h = kW x 860
Btu/h = kW x 3412
RT = kW x 0.284
40
PACKAGEDAIR CONDITIONERS
WATER CHILLERS
UAT08 09 1012KA
UATY08 09 1012K
UAT06KA
UATY06K
Efficient cross fin coils are used: the unique waffle louver
fins*1 maximize heat exchange efficiency, while the Hi-XA
copper tube*2, featuring an inner spiral groove, fully exploits
refrigerant turbulence to help increase heat exchange
efficiency. The result is substantial energy savings.
UWA55JAY1
UWA138JY1
UWA80JATJ
Energy saving.
R emote C ontroller
UAT30H
UAT15 1821KA
UATY15 1821K
Remote Controller
(Only for Cooling Only)
Model
UAT30HY1
UAT30HTO
Power Supply
Y1: 3 phase, 380-415 V, 50 Hz/TAL: 3 phase, 220 V, 60 Hz/YAL: 3 phase, 380 V, 60 Hz/TO: 3 phase, 200/200-220 V, 50/60 Hz
RT
5
6
7.5
9
10
12.5
15
17.5
27.5/30
Cooling capacity *1
Btu/h
60,300
75,000
90,000
107,200
120,000
150,000
180,000
210,400
331,000/368,000
(50/60 Hz)
kcal/h
15,200
18,900
22,700
27,000
30,200
37,800
45,300
53,000
83,500/92,600
kW
17.7
22.0
26.4
31.4
35.1
43.9
52.7
61.6
97.1/107.7
Btu/h
52,900
67,600
81,200
96,600
107,800
135,200
162,100
189,400
284,000/330,700
Cooling capacity *2
(50/60 Hz)
kW
15.5
19.8
23.8
28.3
31.6
39.6
47.5
55.5
83.1/96.9
TAL
8.26
9.74
9.18
8.86
9.52
8.64
8.98
EER *3
(Cooling)
YAL
8.28
9.78
9.21
8.94
9.52
8.64
9.00
UATY06KY1
UATY06KTAL
UATY06KYAL
Model
Power Supply
Cooling capacity *2
(50/60 Hz)
Heating capacity *3
(50/60 Hz)
EER *3
(Cooling)
EER *4
(Heating)
Power comsumption *1
(Cooling)
Power comsumption
(Heating)
RT
Btu/h
kcal/h
kW
Btu/h
kW
Btu/h
kcal/h
kW
TAL
YAL
TAL
YAL
Y1
kW
TAL
YAL
Y1
TAL
YAL
kW
5
60,300
15,200
17.7
52,900
15.5
62,000
15,600
18.1
8.26
8.28
9.45
9.47
5.8
6.8
6.8
5.3
6.2
6.2
UATY08KY1
UATY08KTAL
UATY08KYAL
UATY09KY1
UATY09KTAL
UATY09KYAL
UATY10KY1
(50 Hz Only)
UATY12KTAL
UATY12KYAL
(60 Hz Only)
UATY15KY1
UATY15KTAL
UATY15KYAL
UATY18KY1
UATY18KTAL
UATY18KYAL
8.86
9.52
8.64
9.78
9.21
8.94
9.52
8.64
11.44
10.22
9.81
11.23
9.74
11.49
10.25
9.87
11.24
9.74
6.3
8.2
9.9
13.0
17.1
6.8
8.9
11.8
13.6
18.6
6.8
8.9
11.8
13.6
18.6
5.7
7.7
9.4
11.8
15.8
5.7
8.3
11.3
12.4
17.4
5.7
8.3
11.3
12.4
17.4
UATY21KY1
UATY21KTAL
UATY21KYAL
UWA37JAY1
UWA47JAY1
Power supply
Cooling capacity *1
Cooling capacity *2
kW
Btu/h
USRT
kW
Btu/h
USRT
Model
UWA75JAY1
UWA80JAY1
Power supply
Cooling capacity *1
Cooling capacity *2
kW
Btu/h
USRT
kW
Btu/h
USRT
17.5
210,400
53,000
61.6
189,400
55.5
214,400
54,000
62.8
8.98
9.00
9.99
10.01
19.8
20.6
20.6
18.5
19.4
19.4
2. Cooling capacities marked with *2 are based on 29CDB (84FDB) 19.0CWB (66FWB) indoor temp. and 46CDB (115FDB) outdoor temp.
3. Heating capacities are based on 21CDB for indoor temp. 7CDB/6CWB for outdoor temp.
Net capacity (Btu/h)
4. The figures of *2 is reference value.
EER =
5. *3: EER Cooling conditions: 27CDB (80FDB) and 19.5CWB (67FWB) for indoor temp. 35CDB (95FDB) for outdoor temp.
Unit power comsumption (W)
6. *4: EER Heating conditions: 20CDB for indoor temp. 7CDB/6CWB for outdoor temp.
(Compressor + Outdoor fan motor)
UWA55JAY1
UWA63JAY1
3 phase, 380-415 V, 50 Hz
137.2
161.3
468,200
550,400
39.0
45.8
124.8
149.9
425,800
511,500
35.4
42.6
108.4
369,800
30.8
97.4
332,500
27.7
186.0
634,900
52.9
167.4
571,400
47.6
UWA93JAY1
UWA109JAY1
3 phase, 380-415 V, 50 Hz
250.6
272.7
855,100
930,500
71.2
77.5
225.5
250.8
769,400
855,900
64.1
71.3
219.1
747,600
62.3
197.1
672,600
56.0
319.2
1,089,200
90.7
290.5
991,200
82.6
UWA120JY1
UWA138JY1
Power supply
Operation range
5 to 52
Cooling CDB
(Outdoor temp.)
Heating CWB
-10 to 15.5
Notes: 1. Cooling capacities marked with *1 are based on 27CDB (80FDB) 19.5CWB (67FWB) indoor temp. and 35CDB (95FDB) outdoor temp.
41
Cooling capacity *1
(50/60 Hz)
Cooling capacity *1
kW
Btu/h
USRT
351.6
1,201,500
99.9
404.4
1,380,800
115.0
UWA162JY1
UWA192JY1
3 phase, 380-415 V, 50 Hz
474.7
562.8
1,620,600
1,921,500
135.0
160.0
UWA228JY1
UWA270JY1
667.9
2,280,400
189.9
791.0
2,700,800
224.7
UWA27JATJ
UWA32JATJ
UWA43JATJ
UWA53JATJ
UWA62JATJ
79.0
269,800
22.4
71.0
242,000
20.1
94.3
320,600
26.7
82.0
280,900
23.4
3 phase, 208-230 V, 60 Hz
125.0
426,600
35.5
111.0
378,900
31.5
162.0
553,500
46.1
145.0
494,000
41.0
185.0
632,100
52.6
171.0
584,100
48.6
UWA70JATJ
UWA80JATJ
UWA90JATJ
UWA108JATJ
UWA122JATJ
253.0
865,000
72.0
219.0
746,400
62.1
3 phase, 208-230 V, 60 Hz
274.0
936,400
78.0
248.0
845,200
70.4
324.0
1,107,000
92.2
285.0
972,200
81.0
370.0
1,262,000
105.0
335.0
1,145,000
95.3
Power supply
Cooling capacity *1
Cooling capacity *2
kW
Btu/h
USRT
kW
Btu/h
USRT
Model
Power supply
Cooling capacity *1
Cooling capacity *2
kW
Btu/h
USRT
kW
Btu/h
USRT
212.0
722,200
60.0
191.0
653,100
54.2
Notes : *1 Cooling capacity is based on the following conditions: Leaving chilled water temp. 6.7C (44F), entering water temp. 12.2C (54F) outdoor temp. 35C (95FDB).
*2 Cooling capacity is based on the following conditions: Leaving chilled water temp. 6.7C (44F), entering water temp. 12.2C (54F) outdoor temp. 46.0C (115FDB).
42