ADDC - Elctricity Wiring Rules

Download as pdf or txt
Download as pdf or txt
You are on page 1of 224

The Electricity Wiring Regulations

Issued by: the Regulation and Supervision Bureau for the Water, Wastewater and Electricity Sector in the Emirate of Abu Dhabi www.rsb.gov.ae

December 2007

Regulation and Supervision Bureau


for the Water, Wastewater and Electricity Sector in the Emirate of Abu Dhabi Tel: +971 2 642 6777 Fax: +971 2 642 4217 P.O. Box: 32800 Abu Dhabi, U.A.E e-mail: [email protected] www.rsb.gov.ae

Foreword
The Regulation and Supervision Bureau (the Bureau) was established in law to oversee the economic and technical activities of electricity and water companies that are licensed to operate in the Emirate of Abu Dhabi. These companies were formed following restructuring of the government-owned water and electricity sector, previously managed by the Water and Electricity Department (WED). In addition to its duties over licensed companies, the Bureau has certain responsibilities towards the general public, including the assurance of safe and efficient electricity and water supplies to customers. The Bureau has drafted these Regulations to promote the installation and operation of safe electricity wiring systems in all customers premises. These Regulations are based on the general principles defined in British Standard BS 7671 (otherwise known as the IEE Wiring Regulations, UK) which are also similar to the International Standard IEC 60364. Such principles have been common practice in Abu Dhabi and were adopted in previous documents, including the first Wiring Regulations issued by WED in 1972. The new Regulations are less prescriptive than previous documents, but provide closer definition of technical parameters compared with BS 7671. The Regulations also take account of the physical environment in Abu Dhabi and the typical skills and language diversity of the region. This publication contains a section of guidance notes which, although not part of the Regulations, provides useful data and advice to assist in the correct application of the Regulations. Copies of this document may be purchased from the Bureau. Updates and amendments will be posted on the Bureaus website, www.rsb.gov.ae.

N Carter Director General

Zaal M. Zaal Al Hameeri Chairman

The Electricity Wiring Regulations 2007

Acknowledgements
The Bureau gratefully acknowledges the contributions and comments provided by the following organisations: Government organisations: Abu Dhabi Water and Electricity Authority Al Ain Distribution Company Abu Dhabi Distribution Company Abu Dhabi Municipality Al Mirfa Power Company Dubai Electricity and Water Authority (DEWA) Dubai Municipality (Central Laboratory) Sharjah Electricity and Water Authority (SEWA) Federal Electricity and Water Authority (FEWA) Emirates Standardisation and Metrology Authority (ESMA) Private organisations: Benchmark Electrical Safety Technology Ltd Parsons International Ltd Schneider Electric FZE Voltas Limited, UAE Ian Banham Associates Pell Frischmann Consultants Gibb Ltd Power Economy Middle East WSP Middle East Ltd GHD Ltd (Aust/UAE) ABB Industries LLC (Dubai) Power Connections Ltd Reed Smith Richards Butler British Standards Institute Electrium Ltd In particular, the Bureau wishes to acknowledge permission granted by the Institute of Engineering Technology and the British Standards Institute for the use in this document of data and information taken from BS 7671 (The Electricity Wiring Regulations, UK).

The Electricity Wiring Regulations 2007

Document numbering
These Regulations use the following numbering system: Chapters: are referenced by integers (e.g. 1, 2, 3, etc)

Regulations: are referenced by one full stop between numbers (e.g. 1.1, 1.2, etc) Clauses: Notes: are referenced by two full stops between numbers (e.g. 3.1.2, etc) are indicated below the clause in square brackets and italic text. For Example, [Note: this clause does not apply
to Installations that have been ]

Chapter Regulation

Note

Clause

The Electricity Wiring Regulations 2007

List of revisions
Revision Number ED/R01/010 Issue 1 Date Prepared by: TK Checked by: LH Issued to:

Dec 2007

Publication

The Electricity Wiring Regulations 2007

Table of contents
Foreword Acknowledgements Document numbering List of revisions 1 Introduction 1.1 1.2 1.3 2 Citation and commencement Purpose and document structure Scope and enforcement 3 4 5 6 11 11 11 12 15 15 27 27 28 29 29 30 31 33 35 35 36 38 39 39

Definitions 2.1 Interpretation

General principles and safety requirements 3.1 3.2 3.3 3.4 3.5 3.6 3.7 Technical standards, materials and workmanship Approval of installations Extensions, alterations and repairs Licensed contractors Requirements for safety Labelling and identification Environmental conditions

Electricity supply intake and supply parameters 4.1 4.2 4.3 4.4 4.5 Electricity supply parameters Electricity supply intake The customer connection point Multiple occupancy premises Metering requirements

The Electricity Wiring Regulations 2007

Protection 5.1 5.2 5.3 5.4 5.5 5.6 5.7 General principles Overload and short-circuit protection Electric shock protection Earth leakage protected systems Earthed equipotential bonded systems Isolation and switching Insulation

41 41 41 43 44 47 50 51 53 53 53 54 55 56 58 59 60 60 63 63 65 66 68 71 75 76 77 79 81 81 83

Earthing 6.1 6.2 6.3 6.4 6.5 6.6 6.7 6.8 6.9 General principles Systems of earthing Main earth terminal Earth electrodes Earth conductors Exposed-metallic-parts Earth fault loop impedance Lightning protection Functional earthing and high leakage currents

Selection of components and installation requirements 7.1 7.2 7.3 7.4 7.5 7.6 7.7 7.8 7.9 Plugs and socket-outlets Switches and isolators Lighting Conduit, trunking and cable trays Cables Final circuits Busways, bus ducts and busbar risers Distribution boards LV switchboards

Inspection, testing and certification 8.1 8.2 Electrical installation certificates Routine inspection and testing

The Electricity Wiring Regulations 2007

Special locations and systems 9.1 9.2 9.3 9.4 9.5 9.6 9.7 Separated extra-low voltage (SELV) Protective extra-low voltage (PELV) Bathrooms and similar locations Swimming pools Water fountains Construction sites and outdoor supplies Street lighting

85 85 86 86 88 89 91 92 93 93 94 96 97 101 191

10

Capacitors and motors 10.1 10.2 10.3 10.4 General requirements Specifications for capacitors Electric motors and starters Standby generators

Appendices Guidance Notes

The Electricity Wiring Regulations 2007

10

The Electricity Wiring Regulations 2007

Introduction
1.1
1.1.1

Citation and commencement


These Regulations shall be cited as the Electricity Wiring Regulations 2007. These Regulations shall take effect from 1 January 2008. These Regulations are issued by the Regulation and Supervision Bureau through the powers vested in it under Article 62 of Law No (2) of 1998 (including amendments and re-enactments thereof). These Regulations supersede the following regulations: (a) (b) (c) ADWEA Wiring Rules and Regulations (3rd Edition 2003); WED Regulations for Electrical Installation Works (1980); and Earth Leakage Protection Regulations (2001).

1.1.2 1.1.3

1.1.4

1.2
1.2.1

Purpose and document structure


The purpose of these Regulations is to establish standards and principles that promote the design, construction and operation of safe and efficient systems of wiring in buildings and other Premises. The main part of this document is structured into chapters, regulations and clauses, see illustration on page 5. Regulations and clauses are mandatory. Notes which are included below clauses, in italic text, are not mandatory and are for guidance or to provide supporting technical information. The second part of this document consists of Appendices, which contain mandatory information, and Guidance Notes which contain supporting information.

1.2.2

1.2.3

The Electricity Wiring Regulations 2007

11

1.3
1.3.1

Scope and enforcement


These Regulations apply to all Distribution Companies, Customers, property Owners, Licensed Contractors, or any other persons involved in the design, construction, installation, maintenance or operation of Electrical Installations in any Premises or other place where there is an electricity supply provided by a Distribution Company. Such locations include, but are not limited to, domestic, commercial and industrial premises, public buildings, parks, farms, temporary supplies, construction sites, wedding tents, outbuildings, caravans, street lighting and traffic signs. The scope of these Regulations does not include the electricity distribution networks belonging to Distribution Companies, except such equipment that is required at the interface with Customers, as detailed in these Regulations.
[Note: requirements governing Distribution Companies networks are covered under the Electricity Supply Regulations 2007, as well as other relevant Licences, codes and standards.]

1.3.2

1.3.3

These Regulations shall apply to all new Electrical Installations constructed following the commencement date (clause 1.1.2). Requirements for extensions, alterations and repairs to existing Installations are covered under Regulation 3.3.
[Note: where the design of an Installation has been completed before the date of commencement of these Regulations advice must be sought from the Distribution Company before construction is commenced.]

1.3.4

For Electrical Installations constructed before the date of commencement, the clauses listed in Appendix A4(a) shall either not apply, or shall apply after 1 January 2010 or, if earlier, at the time of any extension work or re-certification of a Premises, as indicated in Appendix A4(a).

12

The Electricity Wiring Regulations 2007

1.3.5

These Regulations shall be enforced by the relevant Distribution Companies in the Emirate of Abu Dhabi, in accordance with procedures which shall be published by the Distribution Company and approved by the Bureau. See Regulation 3.2. Compliance with these Regulations requires compliance with other relevant technical standards, see Regulation 3.1. References to British Standards or other standards means the current edition of the standard cited or its replacement. For existing Installations clause 1.3.4 applies. Failure to comply with these Regulations, or any part thereof, shall be deemed as contrary to the Law and subject to punishment by the imposition of a fine. Any such failures will be addressed in accordance with the Law under Article 65(5) (notices served by the Bureau) and Article 66 (failure to comply and imposition of fines). Action may be taken against any Distribution Company, Customer, Owner, Licensed Contractor or other person to which these Regulations apply.
[Note: see Appendix A4(b) for a list of relevant Articles of Law No (2) of 1998.]

1.3.6

1.3.7

1.3.8

Relaxation of any of the requirements of the Regulations shall be approved by the Bureau upon written request from any Distribution Company, Customer, property Owner, Licensed Contractor or other person. In the event of a dispute between any parties mentioned in clause 1.3.1, the matter may be referred to the Bureau to advise a solution or recommended action. This does not preclude any party referring a matter to the relevant Court of Abu Dhabi. These Regulations and the rights and duties of any parties thereunder shall be governed by, construed and applied in accordance with the Laws of Abu Dhabi Emirate and the Federal Laws of the UAE as applied by the Courts of Abu Dhabi.

1.3.9

1.3.10

The Electricity Wiring Regulations 2007

13

1ntroduction

14

The Electricity Wiring Regulations 2007

Definitions
2.1 Interpretation
Words which are defined under this section are used in the Regulations beginning with capital letters. For example, all Earth Conductors within a Premises shall be .... Terms in common use are not defined here and normal dictionary definitions apply (e.g. circuit-breaker, plug, conduit). Words and expressions other than those described in this section, which are defined in the Law, shall have the meanings ascribed to them in the Law. Words using the singular or plural number also include the plural or singular number, respectively.
2.1.1

Accessory: a device, other than current-using equipment, associated with an Electrical Installation. Appliance: an item of current-using equipment. Arms Reach: a zone of accessibility to touch, extending from any point on a surface where a person may stand or move about, to the limits which such person may reach without assistance (i.e. without any tool or ladder, etc). Such a distance may be taken as 2.5 m height from the standing surface, and 1.25 m horizontally from the standing position. Bonding Conductor: Conductor. see Equipotential Bonding

2.1.2 2.1.3

2.1.4

2.1.5

Bureau: the Regulation and Supervision Bureau for the Water, Wastewater and Electricity Sector in the Emirate of Abu Dhabi, as established under the Law. Cable Tray: a cable support consisting of a continuous base with raised edges and no covering. A cable tray is considered to be perforated where more than 30% of the material is removed from the base.

2.1.6

The Electricity Wiring Regulations 2007

15

2.1.7

Cable Trunking: a manufactured enclosure for the protection of cables, normally of rectangular cross-section, of which one side is removable or hinged. Category 1 Circuit: a Circuit (other than a fire alarm or emergency lighting Circuit) operating at LV and supplied from the Distribution Company. Category 2 Circuit: a Circuit (other than a fire alarm or emergency lighting Circuit) which supplies telecommunications equipment (such as telephones, intruder alarms, data transmission, call bells, etc). Category 3 Circuit: a fire alarm or emergency lighting Circuit. Circuit: a set of phase and neutral conductors installed as a group to supply power to a location, and which originate from one Protective Device. The following are related definitions: (a) Ring Circuit: a Circuit which is wired from a single Protective Device, being run through an area to be supplied (via appropriate socket-outlets, connectors, etc) and returning back to the same Protective Device, thus forming an electrically continuous loop; Radial Circuit: a Circuit which is wired in a radial or branch configuration, emanating from a Protective Device, to the area to be supplied; Spur Circuit: a Circuit which is wired in a radial or branch configuration from any point on a Ring Circuit; Final Circuit: a Circuit which supplies Appliances (normally via socket-outlets or other types of connectors); and

2.1.8

2.1.9

2.1.10

2.1.11

(b)

(c)

(d)

16

The Electricity Wiring Regulations 2007

(e)

Distribution Circuit: a Circuit connecting between Distribution Boards (may also be referred to as a sub-Circuit).

2.1.12 2.1.13

Circuit Protective Conductor: see Earth Conductor. Class I Equipment: equipment which includes a means for connection of Exposed-Metallic-Parts of the equipment to the Earth Conductor, thus providing protection against electric shock in case of failure of the basic insulation of the equipment or other fault condition. Class II Equipment: equipment which does not include a means for connection to an Earth Conductor, and which provides supplementary insulation in addition to the basic insulation of the equipment such that a breakdown of the basic insulation will not present a dangerous voltage on Exposed-Metallic-Parts (also known as Double Insulated equipment). Class II Equipment is required to comply with BS 2754. See Appendix A18(b). Class III Equipment: equipment in which protection against electric shock relies on supply at SELV and in which voltages higher than SELV are not generated in the equipment, see BS 2754. Competency Licence: a licence issued by a Distribution Company to a Licenced Contractor assessed as competent for work on Electrical Installations. Connected Load: the aggregate load of Appliances and other electrical equipment at a Premises, summated using the method described under clause 3.2.5. See Guidance Note G2. Consumer Unit: an integrated unit which accepts the incoming supply to a domestic Premises, or other similar installation, and contains the main isolating device.

2.1.14

2.1.15

2.1.16

2.1.17

2.1.18

The Electricity Wiring Regulations 2007

17

Definitions

2.1.19

Customer: any person, corporate body, or company who has an agreement with a Distribution Company for the supply of electricity. Customer Connection Point (CCP): the point which defines the boundary between the Customers Installation and that of the Distribution Company (also known as the Point of Supply). This point will normally be at the incoming cable of the Main Distribution Board and before the main circuitbreaker, see Appendix A13. In special cases, an alternative definition of the Connection Point may be agreed between the Customer and the Distribution Company. Direct Contact: the contact with electricity by a person (accidental or otherwise) through the phase or neutral conductors of an Installation or Appliance, leading to an electric shock, see Guidance Note G4(a). Distribution Company: a company or body holding a Licence from the Bureau, pursuant to the Law. Danger: risk of injury to people or animals from fire, electric shock, burns, explosion or from mechanical movement of electrically controlled equipment, or the risk of damage to property. Distribution Board: an assembly designed for housing isolation switches and Protective Devices and for connecting multiple Circuits, including their associated neutral and Earth Conductors. The following are related definitions: (a) Main Distribution Board (MDB): the Distribution Board which accepts the main incoming LV supply from the Distribution Company or Customers transformer; Sub Distribution Board (SDB): any Distribution Board which is neither a Main Distribution Board nor a Final Distribution Board; and

2.1.20

2.1.21

2.1.22

2.1.23

2.1.24

(b)

18

The Electricity Wiring Regulations 2007

(c)

Final Distribution Board (FDB): a Distribution Board which supplies Final Circuits only.

2.1.25 2.1.26

Double Insulated Equipment: see Class II Equipment. Earth: the conductive mass of Earth, whose electrical potential (voltage) at any point is conventionally taken as zero. The following are related definitions: (a) Customer Earthed System (TT): a system of supply where the Customer provides a Main Earth Terminal for the Installation, which is connected to a sufficient number of local Earth Electrodes to provide a maximum Earth Resistance measured at the Customers Main Earth Terminal of not more than 10 Ohms. Distribution Company Earthed System (TN-S): a system of supply where the Distribution Company provides a connection to the Customers Main Earth Terminal, using the distribution network Earthing system, normally via the armouring or metallic sheath of the main incoming supply cable.
Distribution Company Earthed System with additional Customer Earth (TNSTT): a system of supply where the Distribution Company provides an Earth connection to the Customers Main Earth Terminal and a local Earth provided by the Customer is also connected to the same MET, having an Earth Resistance value of not more than 10 Ohms.

(b)

(c)

2.1.27

Earthing or Earthed: a general term used to describe the connection of metallic parts of an Electrical Installation or an Appliance to Earth.
[Note: the terms Grounding or Grounded are sometimes used outside these Regulations to mean the same as the above.]

The Electricity Wiring Regulations 2007

19

Definitions

2.1.28

Earth Conductor: a conductor used to connect ExposedMetallic-Parts of an Electrical Installation and associated Appliances to Earth, and providing a means for the safe passage of earth fault current. This includes the following defined terms: (a) Main Earth Conductor (MEC): conductors connected between Distribution Boards, Earth Electrodes and Main Earth Terminals; and
Circuit Earth Conductor (CEC): conductors connected from Final Distribution Boards and associated with Final Circuits, including Appliance Earth Conductors such as within a flexible cord. Outside these Regulations these may also be known as the Circuit Protective Conductor (CPC) or Earth Continuity Conductor (ECC).

(b)

2.1.29

Earth Electrode: a conductor or group of conductors in intimate contact with Earth, providing an electrical connection to Earth, and normally having a known and measurable value of Earth Resistance (may also be known outside these Regulations as Earth Rod, or Grounding Rod). Earthed Equipotential Bonding (EEB): the connection of Extraneous-Metallic-Parts within a Premises using designated conductors such that potential Touch Voltages are kept to a safe value during the passage of earth fault current (also known outside these Regulations as PME Bonding). This definition includes the following: (a) Main Equipotential Bonding: the connection of major Extraneous-Metallic-Parts, such as pipe services and metallic structures, at their point of entry into a Premises to the Main Earth Terminal in an Installation, using designated conductors; and

2.1.30

20

The Electricity Wiring Regulations 2007

(b)

Supplementary Equipotential Bonding: the connection of Extraneous-Metallic-Parts with each other or with Exposed-Metallic-Parts within an area where such parts are simultaneously accessible to persons, such that the potential Touch Voltage during an earth fault is kept to safe limts.
[Note: for disconnection times greater than 0.4 seconds a safe Touch Voltage limit may be taken as 50 V for dry conditions and 25 V for wet conditions.]

2.1.31

Earthed Equipotential Bonded System (EEBS): a system where protection against electric shock due to Indirect Contact is achieved by the provision of Earthed Equipotential Bonding conductors, in association with Protective Devices for the automatic disconnection of supply. Earth Leakage Protection (ELP): the provision of protection against electric shock due to Indirect Contact by the use of RCDs or other sensitive earth fault protective devices which automatically disconnect the supply sufficiently quickly so as to prevent danger to persons. Earth Leakage Protected System (ELPS): a system of supply where Earth Leakage Protection is provided on Final Circuits and back-up ELP is provided at the Supply Intake. Earth Resistance: the resistance (in Ohms) from any point on an Installation to Earth, being measured using an approved testing device and approved procedure. Earth Fault Loop Impedance (Zs): the total impedance presented to an earth fault current, comprising the impedance of the following parts of a system, illustrated in Appendix A5(g): (a) the Circuit Earth Conductor; (b) the Main Earth Terminal;

2.1.32

2.1.33

2.1.34

2.1.35

The Electricity Wiring Regulations 2007

21

Definitions

(c) the main Earth Conductors connecting to Earth Electrodes or the Distribution Company Earth; (d) the path of earth fault current through the general mass of Earth, or through the earth sheath or armouring of the Distribution Company cable; (e) the neutral earth connection at the Distribution Company transformer; (f) the distribution transformer winding; and (g) the phase conductor of the Circuit back to the point of fault.
2.1.36

Earth Leakage Circuit-Breaker (ELCB): see Residual Current Device.


[Note: the term ELCB is commonly used interchangeably with the term RCD.]

2.1.37

Electrical Installation (abbrv: Installation): an Electrical Installation comprises any fixed or temporary cable, switchgear, transformer or other electrical equipment or apparatus within a Premises or other place where there is an electricity supply (including outdoor locations). Fixed or portable electrical Appliances are not considered part of the Electrical Installation, although these Regulations do include requirements for the connection of Appliances (e.g. plugs and socket-outlets). Electrical Installation Certificate: a certificate in the format indicated in these Regulations which is issued by a Licensed Contractor after completion of work on an Installation and provided to the Customer or Owner of the Premises. Exposed-Metallic-Part: a metallic part of an Installation or Appliance which can be touched by persons and which is not normally live but may become live due to a fault condition. Exposed-Metallic-Parts are required to be connected to Earth, see Regulation 6.6.

2.1.38

2.1.39

22

The Electricity Wiring Regulations 2007

2.1.40

Extraneous-Metallic-Part: a metallic part, structure or any metalwork within a Premises which is not part of, and is unrelated to, the electrical Installation and which is not designed to carry current, but which may become live due to a fault condition. Extraneous-Metallic-Parts are required to be connected to Earth for Installations or parts of Installations classified as Earthed Equipotential Bonded Systems, see Regulation 5.5. Extra-Low Voltage (ELV): see Voltage. Final Circuit: see Circuit. Functional Earth: an Earth or Earthing system which is provided for special functions (such as reduction of radio frequency interference, noise filtering for computers, etc) and which is separate from other Earth Conductors in an Installation but is connected to the Main Earth Terminal. High Voltage: see Voltage. Indirect Contact: contact of a person with electricity through Exposed-Metallic-Parts of an Installation or Appliance, or through Extraneous-Metallic-Parts in a Premises which have become live during fault conditions, see Guidance Note G4(b). Installation: see Electrical Installation. Law: means Law No (2) of 1998 Concerning the Regulation of the Water, Wastewater and Electricity Sector in the Emirate of Abu Dhabi (as amended by Law No (19) of 2007). Licensed Contractor: a company which has been assessed by the Distribution Company as competent to work on Electrical Installations and issued a Competency Licence.

2.1.41 2.1.42 2.1.43

2.1.44 2.1.45

2.1.46 2.1.47

2.1.48

The Electricity Wiring Regulations 2007

23

Definitions

2.1.49 2.1.50

Low Voltage: see Voltage. Luminaire: equipment which is designed to house one or more electric lamps and which may include diffusers, fixtures, transformers and auxiliary Circuits but is taken to exclude the lamps themselves. Outside of these Regulations a Luminaire may commonly be referred to as a light fitting. Main Distribution Board: see Distribution Board. Main Earth Terminal (MET): the main connection point at which the nominal value of Earth Resistance for an installation is taken, and to which Earth Conductors from Earth Electrodes or the Distribution Company Earth are connected. This will normally be at or close to the Customer Connection Point. The Main Earth Terminal may also be known as the main earth bar. Owner: the legal owner of a building or property in which an Electrical Installation is installed and connected to a supply of electricity.
[Note: in some cases an Owner may also be a Customer.]

2.1.51 2.1.52

2.1.53

2.1.54

Premises: any occupied or unoccupied building or enclosure or other place where there is an electricity supply. Such locations would include, but are not limited to, domestic premises, commercial premises, industrial premises, public buildings, parks, farms, temporary supplies, construction sites, wedding tents, outbuildings, caravans, street lighting and traffic signs. Prospective Fault Current: the value of current that would flow due to a short-circuit fault of negligible impedance between live phase conductors, or between phase conductors and Earth, also known as fault level. The maximum Prospective Fault Current for an installation is normally taken at the Customer Connection Point.

2.1.55

24

The Electricity Wiring Regulations 2007

2.1.56 2.1.57

Protective Conductor: see Earth Conductor. Protective Device: a device installed at the start of a Circuit which will automatically disconnect the input of electricity in the event of a fault or overload occurring on that Circuit. Such devices include, but are not limited to, fuses, fuse links, miniature circuit-breakers (MCB), moulded case circuitbreakers (MCCB), earth leakage circuit-breakers (ELCB), and residual current devices (RCD). Radial Circuit: see Circuit. Residual Current Device (RCD): a Protective Device which is installed to automatically isolate the supply to a Circuit or Distribution Board when the vector sum of currents in the phase and neutral conductors reaches a preset value (referrerd to as the residual operating current or residual current rating). Ring Circuit: see Circuit. Sub Distribution Board: see Distribution Board. Supply Intake: a term used to describe the location or room housing the main cable and equipment provided by a Distribution Company to provision a supply of electricity to a Premises (includes the Customer Connection Point). Spur Circuit: see Circuit. Touch Voltage: the Voltage that would appear during an earth fault condition between Exposed-Metallic-Parts and Extraneous-Metallic-Parts which are simultaneously accessible to persons.
[Note: this term is used only in connection with protection against Indirect Contact and is not used to refer to Direct Contact with electricity. The seriousness of impact of Touch Voltage on a person will depend on the body resistance and the immediate surroundings, in particular the presence of water. See Guidance Note G4(h) and G5(b).]

2.1.58 2.1.59

2.1.60 2.1.61 2.1.62

2.1.63 2.1.64

The Electricity Wiring Regulations 2007

25

Definitions

2.1.65

Voltage: (a) High Voltage (HV): an a.c. voltage greater than Low Voltage and less than 36 kV between phases or 21 kV between any phase and Earth (internationally referred to as Medium Voltage); Low Voltage (LV): an a.c. voltage below 1000 V between phases, or below 600 V between any phase and Earth or, a d.c. voltage below 1500 V between conductors, or below 900 V between any conductor and Earth; Extra-Low Voltage (ELV): a voltage not exceeding 50 V a.c. or 120 V d.c. whether between live conductors or between live conductors and Earth; Separated Extra-Low Voltage (SELV): an Extralow Voltage system which is electrically separated from Earth in such a way that a single fault cannot give rise to the risk of electric shock. Protective Extra-Low Voltage (PELV): a system which has the same features as SELV except that connection of Exposed-Metallic-Parts to Earth is allowed; and Reduced Low Voltage (RLV): a voltage which does not exceed 55 V a.c. between phase and Earth or 110 V a.c. between phases.

(b)

(c)

(d)

(e)

(f)

26

The Electricity Wiring Regulations 2007

General principles and safety requirements


3.1
3.1.1

Technical standards, materials and workmanship


These Regulations provide guidelines and technical standards which are consistent with the principles contained in BS 7671:2001 (also known as the IEE Wiring Regulations 16th Edition). Where any provision in these Regulations contradicts any provision in BS 7671, the requirements, standards or specifications under these Regulations shall apply.
[Note: these Regulations are in some aspects more prescriptive than BS 7671, and take account of the physical environment of Abu Dhabi Emirate, as well as the typical skills and language diversity in the region.]

3.1.2

Where a provision or technical requirement is not covered by these Regulations, BS 7671 may be used as a guideline or specification, with prior approval from the Distribution Company and the Bureau. All materials used in Electrical Installations shall be of good quality and installed in a neat and orderly manner. All materials and equipment shall comply with relevant international standards which shall be mainly BS (British Standards) or IEC (International Electrotechnical Commission) standards, as referenced in these Regulations. Other international standards may be used, in particular where none are specified in these Regulations, with the prior approval of the Distribution Company and the Bureau. A list of BS and IEC standards applying to the main types of equipment is given in Appendix A3. The Distribution Company may issue specifications and requirements in addition to these Regulations, which will be endorsed or approved by the Bureau, and provided to interested parties on request.

3.1.3

3.1.4

3.1.5

The Electricity Wiring Regulations 2007

27

3.1.6

Reference must be made, where relevant, to UAE or Gulf standards which may be issued from time to time by the Emirates Standardisation and Metrology Authority (ESMA).

3.2
3.2.1

Approval of installations
Any Customer requiring a new supply or alteration to an existing supply must make an application to the Distribution Company using the appropriate forms and procedure published by the Company. The proposed design of an Installation must be approved by the Distribution Company before commencement of construction. Details of the proposed design must be submitted, together with appropriate calculations and wiring diagrams, using the standard symbols shown in Appendix A11. New Installations must be inspected and tested by the Distribution Company in accordance with the requirements of Chapter 8 of these Regulations, prior to providing an electricity supply. The Distribution Company may, where appropriate, seek evidence of compliance against relevant standards of equipment and components used in the Installation. The Customer must provide an estimate of the expected maximum electricity demand or Connected Load at the Premises. This must be calculated by the Customers appointed Licensed Contractor, design engineer or other qualified person using the guidelines given in Guidance Note G2.

3
3.2.2

3.2.3

3.2.4

3.2.5

28

The Electricity Wiring Regulations 2007

3.3
3.3.1

Extensions, alterations and repairs


No extension or alteration to an Electrical Installation may be made without prior notification to the Distribution Company or without approval, testing and certification in accordance with Regulation 3.2. All extensions or alterations to an existing Installation must comply with the requirements of these Regulations. Not withstanding clause 3.3.1 and 3.3.2, repairs to existing installations may be made using standards of equipment compliant with the old installation, but limited to work of an essential nature on a like-for-like basis. Work on any part of the Installation other than Final Circuits, including any Distribution Board and any items at the Supply Intake, must be notified to the Distribution Company. Any proposed increase greater than 10% of the total Connected Load at a Premises, or greater than 10% of the Connected Load at any Distribution Board, must be approved by the Distribution Company.

3.3.2

3.3.3

3.3.4

3.4
3.4.1

Licensed contractors
Work on Electrical Installations may only be carried out by Licensed Contractors who have been assessed and approved by the Distribution Company and issued a Competency Licence. The process for approval of Licensed Contractors shall be published by the Distribution Company and approved by the Bureau. A register of Licensed Contractors shall be kept up-to-date by the Distribution Company and provided on request to any person.

3.4.2

3.4.3

The Electricity Wiring Regulations 2007

29

Principles

3.5
3.5.1

Requirements for safety


The provisions of these Regulations require that all Electrical Installations are designed and constructed so as to ensure the safety of all persons who may operate, maintain or otherwise use or be affected by any part of an Installation. In addition to the requirements detailed under the relevant sections of these Regulations, the following general safety principles shall apply.
[Note: these Regulations do not include detailed requirements for the maintenance of Installations. However, the maintainability of Installations must be adequately catered for in their design and construction. In addition the requirements for periodic inspection and testing, as detailed in Chapter 8, may give rise to the need for maintenance and repair work.]

3.5.2

All parts of an Electrical Installation shall be designed and constructed so as to prevent Danger. All parts of an Electrical Installation shall be sufficiently sized and rated to safely carry out the function for which they are required. All parts of an Electrical Installation shall be insulated appropriate to the function they serve, in consideration of the expected operating environment, so as to prevent Danger, see Regulation 5.7. All Exposed-Metallic-Parts of an Installation and of Appliances must be connected to Earth via appropriate Earth Conductors, so as to protect against electric shock, see Regulation 6.6. Except in specified circumstances, all Electrical Installations shall be provided with Earth Leakage Protection at the source of supply, at all Final Circuits and at other appropriate points, see Regulation 5.3.4. Where Earth Leakage Protection is not provided the requirements for Earthed Equipotential Bonding shall apply, see Regulation 5.5).
The Electricity Wiring Regulations 2007

3.5.3

3.5.4

3.5.5

3.5.6

30

3.5.7

All Electrical Installations must be protected against damage caused by excess current due to a fault or overload by suitable Protective Devices, see Regulation 5.2. All Electrical Installations must be provided with a means of isolating the electricity supply at suitable sections, subsections and Circuits, and at points where Appliances are used, see Regulation 5.6. All parts of an Electrical Installation must be suitably located so as to provide safe access for operation, maintenance and repair and must be protected against accidental or deliberate interference or damage. Electrical Installations must be designed and constructed with particular consideration given to the risk of fire due to electrical faults and the propagation of fire through parts of the Installation. See clauses 6.1.1(c), 7.2.4, 7.4.5, 7.4.15, 7.5.3, 7.5.4, 8.1.4(g) and 10.3.2. All Electrical Installations must be inspected and tested at the time of first commissioning and at regular intervals thereafter to ensure ongoing safety, as detailed under Chapter 8 of these Regulations. Additional requirements for safety in special locations are covered in Chapter 9.

3.5.8

3.5.9

3.5.10

3.5.11

3.5.12

3.6
3.6.1

Labelling and identification


All Electrical Installations must be suitably labelled so as to give information on the electricity supply parameters, the source of supply, location in relation to other Installations, and any special precautions to be taken.
[Note: such information would normally be provided at the Supply Intake room; special precautions would include information on other sources of supply such as local generation or interconnection with other Premises.]

The Electricity Wiring Regulations 2007

31

Principles

3.6.2

The means of isolation of the main source of supply must be clearly labelled and accessible to authorised persons, see Regulation 5.6. The provision of Earth Leakage Protection (as required under Regulation 5.3.4) must be clearly indicated at appropriate isolation points, including a notice informing Customers of the need for regular testing of RCD devices, see Appendix A12(c). Individual Circuits (including neutral and Earth Conductors) must be identified by numbering at the source end and, where appropriate, at intervals along the route, see Guidance Note G7(f). For non-domestic Installations, all accessories and fittings must be marked with Circuit identification numbers.
[Note: Circuit identification numbers must indicate the Distribution Board from which an Accessory or fitting is supplied, and may be fixed externally or internally, i.e. either outside or inside cover plates.]

3.6.3

3
3.6.4

3.6.5

3.6.6

Load distribution schedules, as shown in Appendix A20(e), must be provided at each Distribution Board. An overall wiring diagram showing the location and interconnection of Distribution Boards must be provided at the Supply Intake. Where parts of an Installation are accessible or visible to the general public they must be labelled with a warning: LIVE 230/400 VOLTS DANGER OF DEATH or similar wording. This warning must be written in English and Arabic, see example in Appendix A12(a). However, parts of final Circuits and other points of normal use may be excluded from this requirement.

3.6.7

32

The Electricity Wiring Regulations 2007

3.7
3.7.1

Environmental conditions
All parts of an Electrical Installation must be suitably designed, constructed and maintained so as to operate safely and carry out their designed function in the expected operating environment. The following environmental conditions may be used as a guide if no other special factors apply: (a) maximum ground temperature (at 1 m depth): 35C; (b) soil resistivity: according to local conditions; (c) weather: mainly sunny, occasional fog (causing condensation on outdoor equipment), and occasional sandstorms; (d) air quality: frequently dusty; (e) maximum humidity: 100%; (f) maximum ambient (air) temperatures: outdoor (shaded): 50C outdoor (unshaded): temperature rise due to solar gain must be calculated for the relevant equipment or the maximum black bulb temperature may be used (typically 10 C above ambient temperature) indoor (not air conditioned): 40C indoor (air conditioned): 30C

[Note: in some situations the ambient temperature for indoor non-air-conditioned situations may reach the outdoor shaded temperature e.g. a small prefabricated building with little ventilation, or a garage which is open to the atmosphere.]

The Electricity Wiring Regulations 2007

33

Principles

34

The Electricity Wiring Regulations 2007

Electricity supply intake and supply parameters


4.1
4.1.1

Electricity supply parameters


The parameters for electricity supplies provided to Customers in the Emirate of Abu Dhabi are defined in the Electricity Supply Regulations 2007, issued by the Bureau. These are repeated below. Declared voltage and frequency

4.1.2

The declared supply voltage provided to Customers connected at LV shall be 230 V single-phase or 400 V three-phase.
[Note: this is a change to the previous supply voltage declared by Distribution Companies of 240/415 V. See Guidance Note G1.]

4.1.3

The permissible variation of the supply voltage shall be kept within + 10% and - 6% of the declared supply voltage. The declared supply frequency provided to Customers shall be 50 Hz. The permissible variation of supply frequency shall be +/- 0.1% (i.e. +/- 0.05 Hz). For Customers supplied at voltages above LV the permitted variation of supply voltage shall be +/- 10% and the permitted variation of frequency shall be +/- 0.1%. Harmonics, voltage disturbances and power factor

4.1.4

4.1.5

4.1.6

4.1.7

Customers Installations, and the use of electrical equipment therein, must be designed to avoid the generation of disturbances in the electricity supply. These may include voltage fluctuations, voltage dips, voltage unbalance and harmonics, which are of a magnitude that adversely affect other Customers.

The Electricity Wiring Regulations 2007

35

4.1.8

The permitted limits of such disturbances are given in the Electricity Distribution Code, Annex 1. Customers will be required to install filters or other equipment to mitigate against such disturbances that are outside the permitted limits (as explained in the Electricity Distribution Code). The power factor at the Connection Point between the Distribution Company and the Customers Installation must be maintained at 0.9 lagging or higher. Power factor correction equipment must be used where required to achieve this value, see Chapter 10. Prospective fault current

4.1.9

4
4.1.10

The maximum three-phase Prospective Fault Current (fault level) for LV supplies shall be 46 kA (1 second) at the LV busbar of the Distribution Companys HV or LV substation, or 30 kA (1 second) at an LV feeder pillar, or 25 kA (1 second) at an LV service turret. The maximum 3-phase Prospective Fault Current for HV supplies shall be 31.5 kA (for 3 seconds) or such lower value as otherwise agreed between the Distribution Company and the Customer.

4.1.11

4.2
4.2.1

Electricity supply intake


The electricity Supply Intake must be positioned in a dedicated room or housing. Other than in exceptional circumstances, and with prior approval from the Distribution Company, there shall be only one electricity Supply Intake for any Premises. The Supply Intake must be positioned in an area which is readily accessible to Distribution Company staff and other authorised persons, particularly in an emergency, and must be at or close to the outside perimeter of a Premises.

4.2.2

4.2.3

36

The Electricity Wiring Regulations 2007

4.2.4

The Supply Intake must not be positioned in an area controlled by one of the tenants in a multi-occupancy building. Equipment at the electricity Supply Intake must be located in a safe and accessible position, and kept clear of hindrance at all times. The use of Supply Intake rooms as storage rooms for any tools, equipment or other materials is prohibited. The Supply Intake must not be located on the reverse side of a bathroom or kitchen wall, or below a bathroom or kitchen. The Supply Intake must not be located below any water services or pipes, such as mains water supply, storage tanks, air conditioning chillers, or other liquids or hazardous materials. The Supply Intake room must be well ventilated, preferably without the need for forced air circulation. Where air conditioning is required in the Supply Intake room the requirement for fresh air circulation must also be provided to avoid condensation. At least one emergency lighting unit must be fitted in all Supply Intake rooms, which must be provided with a battery rated for minimum 2 hours illumination, and subject to adequate routine maintenance. Doors to Supply Intake rooms must be arranged to open outwards, be kept free from obstructions, and be capable of being opened from the inside without the use of a key. The need for delivery of heavy equipment to the Supply Intake room during construction and for future repair or alterations must be taken into account in the location of the Supply Intake room.

4.2.5

4.2.6

4.2.7

4.2.8

4.2.9

4.2.10

4.2.11

The Electricity Wiring Regulations 2007

37

Supply Intake

4.2.12

For Supply Intake rooms of greater than 6 m in length more than one door shall be provided as a means of emergency access. Installation layouts and minimum sizes of the electricity Supply Intake are given in Appendix A12(b) and A12(d). For large Installations the Supply Intake may consist of one or more LV switchboards, the requirements for which are given in Regulation 7.9.
Where an HV or LV substation is required for the supply of Premises, the design and construction requirements for the substation will be specified by the Distribution Company.

4.2.13

4.2.14

4.2.15

4
4.3
4.3.1

The customer connection point


Except where an alternative definition of the Customer Connection Point (CCP) has been agreed between the Customer and the Distribution Company, the CCP is deemed to be at the incoming cable connection from the Distribution Company. This is most commonly at the Main Distribution Board and before the main circuit-breaker. Metering equipment may be connected through a current transformer at a position remote from the Customer Connection Point. Equipment at the Customer Connection Point must be locked or sealed by the Distribution Company to prevent deliberate or accidental interference. Such locks or seals will include those for metering equipment, etc. The Customer Connection Point must always include a means of emergency isolation in the case of a fault or breakdown (e.g. main circuit-breaker) which is readily accessible and clearly labelled so as to be easily operated by the Customer. Such means of emergency isolation must be left unlocked at all times, except when locked in

4.3.2

4.3.3

38

The Electricity Wiring Regulations 2007

the open position to allow access to the Installation (e.g. for maintenance).

4.4
4.4.1

Multiple occupancy premises


Multiple occupancy Premises may be supplied by rising and lateral mains (cabling or busbars) which are connected directly to the Supply Intake from the Distribution Company. Rising and lateral mains will normally be owned and operated by the building Owner on behalf of all Customers in a Premises. The electricity metering for individual Customers for a rising or lateral mains system will normally be at the point nearest to each Customer, remote from the main Supply Intake.

4.4.2

4.5
4.5.1

Metering requirements
The requirements for Customer metering are contained in the Customer Metering Regulations 2005, issued by the Bureau. Additional detailed requirements and procedures will be provided by the Distribution Company where required.

The Electricity Wiring Regulations 2007

39

Supply Intake

40

The Electricity Wiring Regulations 2007

Protection
5.1
5.1.1

General principles
All Electrical Installations must be designed, constructed and maintained to provide protection against the following: (a) overload; (b) short-circuits (phase to phase or phase to Earth); and (c) electric shock (due to Direct or Indirect Contact with electricity).

5.1.2

Protection against conditions of overload and short-circuit will normally be provided by MCBs, MCCBs or similar devices, see Regulation 5.2 below. Protection of persons against electric shock due to Direct Contact or Indirect Contact must be provided by one of the methods detailed in Regulation 5.3 below.
[Note: see Guidance Note G4(a) and G4(b) for explanation of Direct and Indirect Contact.]

5.1.3

5.2
5.2.1

Overload and short-circuit protection


All Electrical Installations must be provided with devices that protect against thermal, electromagnetic and other detrimental effects caused by overload and short-circuits. Such devices must be located at suitable sections and Circuits so as to give effective automatic disconnection in such conditions. The main circuit-breaker at the Customer Connection Point must be of MCB or MCCB type and adequately rated for the maximum Prospective Fault Current. Fused cutouts must not be used except in special circumstances approved by the Distribution Company (e.g. street lighting supplies).

5.2.2

The Electricity Wiring Regulations 2007

41

5.2.3

All Circuits must be individually protected against overloads and short-circuits by suitable devices. Replaceable or re-wireable fuse links are not permitted for this purpose (except in the case of capacitor banks see Regulation 10.2). The time-current performance characteristics of Protective Devices must conform to the relevant reference standards listed in Appendix A3.
[Note: the time-current performance curves for MCBs are shown in Appendix A6(a) (d).]

5.2.4

5.2.5

To ensure protection against overload, Circuit conductors must be sized taking into account the time-current characteristic of the Protective Device.
[Note: in order to provide adequate protection against overload the Protective Device nominal rating must be not more than the maximum rating of the Circuit for which overload protection is required see Appendix A6(f).]

5
5.2.6

Protective Devices at the Main Distribution Board must have a maximum Prospective Fault Current rating above that declared by the Distribution Company for the relevant Customer Connection Point. Protective Devices downstream of the Main Distribution Board may have a reduced Prospective Fault Current rating, taking into account the energy let-through characteristic (I2t) of the upstream Protective Device, see Appendix A6(e). Where appropriate, an allowance may also be made for the attenuation of Prospective Fault Current due to the Circuit impedance.

5.2.7

42

The Electricity Wiring Regulations 2007

5.3

Electric shock protection


Direct contact

5.3.1

Protection of persons against the risk of Direct Contact with electricity must be provided by either physically preventing contact or by an inherently safe systems of supply, using one or more of the following measures: (a) insulated conductors, see Regulation 5.7; (b) secure enclosures, barriers or covers on live parts; (d) Protective Extra-Low Voltage (PELV) system.
[Note: SELV conductors at voltages of 12 V a.c. or 30 V d.c. may be un-insulated but must be provided with overload and short circuit protection.]

5.3.2

Residual Current Devices with a residual current rating of 30 mA and complying with IEC 60898 or BS 3871 may be used as a means of supplementary protection against Direct Contact. However, RCDs may not be used as the sole means of protection against Direct Contact i.e. one of items (a) to (d) above must be used in addition to RCD protection.
[Note: RCD devices with a residual current rating above 30 mA are not considered to provide adequate protection against Direct Contact but may be used to provide protection against Indirect Contact see Regulation 5.4. It should also be noted that earth leakage devices do not protect against electric shock between phase conductors or between phase and neutral.]

The Electricity Wiring Regulations 2007

43

Protection

(c) Separate Extra-Low voltage (SELV) system; or

Indirect Contact
5.3.3

Indirect Contact with electricity can occur when a voltage appears on Earthed parts of an Installation or Appliance due to the passage of earth fault current and whilst a person is in contact with either: (a) (b) (c) an Exposed-Metallic-Part and an ExtraneousMetallic-Part; or an Exposed-Metallic-Part and Earth; or an Extraneous-Metallic-Part and Earth.

5.3.4

Protection against the risk of electric shock in the above cases must be provided by either: (a) an Earth Leakage Protected System, where RCDs or similar devices are provided at Final Circuits and back-up RCDs or other sensitive earth fault protection is provided at the Supply Intake, see Regulation 5.4; or in parts of Premises where Earth Leakage Protection is not provided, or other specified circumstances, an Earthed Equipotential Bonded System, see Regulation 5.5.

5
(b)

5.3.5

Not withstanding clause 5.3.4(b) the requirement for Earth Leakage Protection on all Final Circuits where Appliances may be used by any person is made compulsory by these Regulations.

5.4
5.4.1

Earth leakage protected systems


An Earth Leakage Protected System (ELPS) is defined as one where protection against Indirect Contact is provided by the use of RCDs or other sensitive earth fault devices on all Final Circuits and back-up ELP is provided at the Supply Intake. Such a system is required to automatically disconnect the supply at a Final Circuit or at the Supply Intake sufficiently quickly so as to prevent Danger.

44

The Electricity Wiring Regulations 2007

5.4.2

For Final Circuits ELP devices must be of the RCD type whereby the device will trip if the vector sum of currents carried by the phase and neutral conductors is above a preset value, see Guidance Note G5(c). Voltage-operated earth leakage devices (ELCB) are not permitted.
[Note: modern RCDs are magnetically actuated whilst the older type of ELCB devices operate by detecting fault voltage and require a connection between a Main Earth Conductor and an Earth Electrode; these devices are therefore vulnerable to maloperation due to parallel earth paths.]

5.4.4

For Final Circuits which are liable to carry pulsating or d.c. currents RCD devices must be of type A (pulsating d.c. sensitivity) and for RCD devices requiring time-delayed operation type S devices must be used, see Guidance Note G5(d). Earth Leakage Protection provided at the Supply Intake must be set to discriminate with ELP devices at Final Circuits (i.e. earth faults on Final Circuits must be automatically disconnected by the closest ELP device, except in the case of back-up operation of devices at the Supply Intake). See Guidance Note G4(e).
[Note: such discrimination may be provided by time delayed devices at the Supply Intake.]

5.4.5

The Electricity Wiring Regulations 2007

45

Protection

5.4.3

RCD devices for Final Circuits must have a time-current performance characteristic complying with IEC 60898 or BS 3871. This requires that the device must operate within 200 milliseconds at its residual current rating and within 40 milliseconds at 5 times its residual current rating. It must not operate below 50% of its residual current rating, see Guidance Note G5(a).

5.4.6

The operating current setting for ELP devices at the Supply Intake must take into account the nature of the Installation (e.g. commercial, industrial, etc), the likelihood and magnitude of earth fault currents, and the requirement for protection against Indirect Contact, see Appendix A5(m) and Guidance Note G4(f). Earthed Equipotential Bonding is not required in an ELP system, although it may be provided as supplementary protection against Indirect Contact, see Guidance Note G4(d).
[Note: Earth Leakage Protection devices provide protection against electric shock by limiting the time that current may pass through the body of a person to Earth; they do not limit the magnitude of current, except by the feature of early cut-off for a rising current. In addition, ELP devices provide protection against high resistance earth faults that may persist in an installation if the fault current is too low to operate overcurrent devices such as MCBs. Such faults may cause overheating of Circuits or connections and lead to a fire.]

5.4.7

5.4.8

At each Distribution Board or other point where an RCD is provided a suitable label must be affixed to inform the Customer of the characteristics and mode of operation of the device and the need for routine testing, see Appendix A12(c). For domestic Premises the residual current rating for ELP devices must be 100 mA for Final Circuits supplying fixed equipment (e.g. lighting and air conditioning) and 30 mA for Final Circuits where Appliances may be used by persons (e.g. all socket-outlets, all kitchen Appliances, other Appliances accessible to persons), and 30 mA for all Circuits in a bathroom, see Regulation 9.3. A full list of applications and residual current ratings is provided in Appendix A5(m). Special Circuits within a Premises, where there would be significant detriment or danger from the tripping of the

5.4.9

5.4.10

46

The Electricity Wiring Regulations 2007

Earth Leakage Protection, may be excluded from the zone of Earth Leakage Protection. Such instances may include Circuits supplying fire protection equipment or safety alarms (not security alarms) or unoccupied sites (such as telecommunications stations, water pumping stations, etc). All such cases must be declared in the Electrical Installation Certificate for the site and approved by the Distribution Company. In these cases the requirements for an Earthed Equipotential Bonded System must be met for the relevant Circuits, see Regulation 5.5.

5.4.12

Notwithstanding clauses 5.4.10 and 5.4.11, all Circuits from which portable Appliances may be used, or any outdoor equipment accessible to persons, must be provided with Earth Leakage Protection devices with a residual current rating no greater than 30 mA. An earth leakage alarm may be provided for Circuits which are excluded from the zone of Earth Leakage Protection (e.g. an alarm that does not cause tripping of the Circuit but gives an audible and visible warning to appropriate persons in the Premises).

5.4.13

5.5
5.5.1

Earthed equipotential bonded systems


An Earthed Equipotential Bonded System (EEBS) is defined as one where protection against Indirect contact is provided by the installation of Earthed Equipotential Bonding such that voltage rises between Exposed-MetallicParts and Extraneous-Metallic-Parts are kept to a safe value for the duration of an earth fault (i.e. the time it takes for the relevant Protective Device to trip).

The Electricity Wiring Regulations 2007

47

Protection

5.4.11

Circuits with high earth leakage currents (e.g. electronic equipment or industrial machinery) may be provided with ELP devices with higher residual current ratings, up to 500 mA. These must be clearly stated on the Electrical Installation Certificate.

[Note: an EEB system relies on the principle that all ExposedMetallic-Parts and Extraneous-Metallic-Parts which are accessible to persons are connected to the Main Earth Terminal and therefore the prospective Touch Voltage between them is limited to a value which is safe when taking into account the operating time of the relevant Protective Device. In addition, it is assumed that a person cannot be in contact with Earth whilst touching any Metallic Part in a Premises see Guidance Note G4(b) and G4(h).] 5.5.2

For an EEB system the operating characteristics of Protective Devices must limit the duration of any earth fault to less than 0.4 seconds for Circuits supplying Appliances which are accessible to people, and less than 5 seconds for all other parts of the Installation. The most commonly used method for checking the prospective fault duration is by reference to data on the limiting values of earth loop impedance for the Protective Device concerned. For MCBs this is provided in Appendix A5(h), taken from BS 7671. Main Equipotential Bonding Conductors must be installed from the Main Earth Terminal to connect metallic service pipes and other Extraneous-Metallic-Parts at points closest to the entry of such parts to a Premises. In high risk areas Supplementary Equipotential Bonding must be provided so that the Touch Voltage between Exposed-Metallic-Parts and Extraneous-Metallic-Parts is kept to safe limits for the duration of an earth fault.
[Note: high risk areas may include bathrooms, kitchens, laboratories, garages, confined spaces or other locations where the normal resistance of the body is reduced or the consequence of an electric shock may lead to another accident, such as fall from a height. For disconnection times greater than 0.4 seconds safe Touch Voltage limits may be taken as 50 V for dry conditions and 25 V for wet conditions.]

5.5.3

5.5.4

5.5.5

48

The Electricity Wiring Regulations 2007

5.5.6

The method for calculation of Touch Voltage between Exposed-Conductive-Parts and Extraneous-Metallic-Parts is illustrated in Guidance Note G4(h). Items requiring Equipotential Bonding may include metallic pipes (particularly those connected to underground services such as water supply), steel beams, water tanks, baths, sinks and washbasins, etc. An illustration of typical Equipotential Bonding arrangements is given in Guidance Note G4(c). It is not necessary to provide Equipotential Bonding for standalone metallic items which: (a) (b) (c) do not pose any risk of providing a conductive path to Earth (are isolated from Earth); or do not pose any risk of providing a conductive path to any other Earthed part of the Installation; or do not pose any risk of becoming live as a result of an electrical fault in the Installation (i.e. are sufficiently remote from any Circuit or Appliance); or are out of reach of any person.

5.5.7

5.5.8

(d)

[Note: such items may include metal doors, window frames, inaccessible structural beams, small metallic fixings such as screws and brackets, etc.] 5.5.9

Where Circuit conductors are installed close to or within items of metalwork (such as mentioned in clause 5.5.8) consideration must be given to provide additional protection or double insulation of such conductors.
[Note: examples include situations where cables pass through walls containing steel frames, metal door frames, metallic floor grids, suspended ceilings, etc.]

5.5.10

The sizing of Equipotential Bonding Conductors is given in Appendix A5(j).

The Electricity Wiring Regulations 2007

49

Protection

5.5.11

The point of connection of an Equipotential Bonding Conductor to any item must be labelled: SAFETY EARTH BONDING DO NOT REMOVE, as illustrated in Appendix A5(d).

5.6
5.6.1

Isolation and switching


All Electrical Installations must be provided with a means of safe isolation at the Supply Intake, which must be lockable or otherwise provided with a means of preventing interference (e.g. by the removal of operating handles into the safe custody of a responsible person). Isolation for maintenance or other work may be provided by the Protective Device if it is lockable (except for HV equipment).
[Note: mechanical equipment should be provided with a means of isolation close to the equipment which can be locked and kept under the control of the person performing maintenance.]

5
5.6.2

An Installation must be further sectionalised by means of isolation at the origin of each Circuit, in order to provide ease of access for safe working. Each socket-outlet or other connection point to an Appliance or other electrical equipment must be provided with a switch as a means of isolation. Such switches must be provided with a neon indicator where it is desirable to have a visual indication of the presence or absence of power (e.g. fridge, fire alarm, gas or smoke alarm, and water heater). Emergency switching (e.g. push-button switch) must be provided for moving machinery which may require immediate manual disconnection from the supply in the case of an accident or other situation to avoid Danger. Such equipment may include large motors, ventilation equipment, industrial machinery, etc. Emergency push switches must operate on all phases and neutral of the supply, must be clearly marked and must be located in an easily accessible position.

5.6.3

5.6.4

50

The Electricity Wiring Regulations 2007

5.6.5

Emergency switches must be designed so that their operation retains the switch in the off position until it is intentionally unlocked or reset. The release of the emergency switch must not automatically restart the related Appliance or machinery. Functional switching devices required for control or operation of equipment and not for safety reasons need not comply with the requirements of clauses 5.6.1 to 5.6.5. Semiconductor devices cannot be used as a means of isolation for safety.

5.6.6

5.6.7

5.7
5.7.1

Insulation
All Electrical Installations must be sufficiently insulated to protect against electric shock from Direct Contact by any person (clause 5.3.1). Such insulation must be capable of withstanding wear and tear during normal use of the equipment. Supplementary insulation or double insulation may be used where additional robustness is required. The application of paints, resins, varnishes and similar materials is not considered to satisfy the requirements of clause 5.7.1 and additional insulation, barriers or obstacles are required to prevent Direct Contact by any person.
[Note: an example may be a motor winding which is enamelled or resin coated and therefore must be guarded against Direct Contact by persons.]

5.7.2

5.7.3

Live conductors are required to be inaccessible without the use of a special key or tool, available only to authorised persons and only for the purpose of testing, using special equipment and procedures.

The Electricity Wiring Regulations 2007

51

Protection

5.7.4

Uninsulated equipment may be used at voltages not exceeding 12 V a.c. or 30 V d.c. and only where supplied by a SELV source, see Regulation 9.1. The insulation resistance of Circuit conductors must be measured as part of the test procedures given in Chapter 8 and must be greater than the values given in Appendix A19(f). Where an Installation is supplied by underground cables no special provisions are required for protection against over-voltages arising from atmospheric origin or from switching. Where an Installation is supplied by overhead lines advice should be sought from the Distribution Company or the requirements of BS 7671 Chapter 44 may be used.

5.7.5

5.7.6

52

The Electricity Wiring Regulations 2007

Earthing
6.1
6.1.1

General principles
Earthing of Exposed-Metallic-Parts of an Installation and of Appliances in a Premises is required to serve the following functions of safety: (a) (b) allow the passage of fault current in the event of a live conductor touching an Exposed-Metallic-Part; ensure that the magnitude of fault current is sufficient to operate Protective Devices, including Earth Leakage Protection devices, within 0.4 seconds for Final Circuits supplying Appliances which are accessible to any person and within 5 seconds for all other parts of an Installation; and ensure that, in association with Protective Devices, a high resistance fault to Earth does not persist so as to cause overheating or fire.

(c)

6.1.2

The necessary requirements to achieve the above functions of safety are detailed in the following sections.

6.2
6.2.1

Systems of earthing
Customers must be provided with a supply operating under either of the following earthing systems: (a)
Customer Earthed System (TT): the Customer provides a Main Earth Terminal for the Installation, which is connected to a sufficient number of local Earth Electrodes to provide a maximum Earth Resistance measured at the Customers Main Earth Terminal of no greater than 10 Ohms (referred to in BS 7671 as a TT system); Distribution Company Earthed System (TN-S): the Distribution Company provides a connection to the Customers Main Earth Terminal, using the distribution network Earthing system, normally via the armouring or metallic sheath of the incoming

(b)

The Electricity Wiring Regulations 2007

53

supply cable (referred to in BS 7671 as a TN-S system). The Distribution Company system is earthed at the distribution transformer (11 kV or 400 V) and separate earth and neutral conductors are used throughout the distribution network; or (c)
Distribution Company Earthed System with additional Customer Earth (TN-S-TT): the Distribution Company provides an earth connection to the Customers Main Earth Terminal and a local Earth provided by the Customer is also connected to the same MET, having an Earth Resistance value of no greater than 10 Ohms.

[Note: These types of earthing systems are illustrated in Appendix A5(a) A5(c).] 6.2.2

6
6.2.3

The preferred earthing system to be used in Abu Dhabi Emirate is TN-S-TT. However, either TN-S or TT systems may be used where agreed between the Distribution Company and the Customer. The type of earthing system must be stated on the Electrical Installation Certificate and clearly labelled at the Main Distribution Board. In all cases the neutral and Earth Conductors must be kept separate and not connected together at the MET or at any other point in the Customers Installation.

6.3
6.3.1

Main earth terminal


The Main Earth Terminal must be provided close to or within the Main Distribution Board or other switchgear at the Supply Intake. A means of removing the connection to Earth (such as by a detachable metal link) must be provided at the Main Earth Terminal to facilitate testing of the earthing of the installation and the source of supply, see Appendix A5(e).

6.3.2

54

The Electricity Wiring Regulations 2007

6.3.3

The Earth Resistance measured at the MET must be recorded on the Installation Certificate in accordance with the procedures described in Chapter 8. Methods of measuring Earth Resistance are shown in Appendix A19(a).

6.4
6.4.1

Earth electrodes
Earth Electrodes must be provided at Premises which are supplied by a Customer Earthed System (TT) or a Distribution Company Earthed System with additional Customer Earths (TN-S-TT). For Premises consisting of more than one building, where either a TT or TN-S-TT system is used, Earth Electrodes must be provided at each building that is more than 30 m distance from the Supply Intake. Earth Electrodes will normally comprise of 15 mm diameter steel-cored copper rods driven to a minimum depth of 3 m. The top of each Earth Electrode must be housed inside a 300 mm x 300 mm x 300 mm inspection pit which is clearly labelled and accessible for routine testing, see Appendix A5(d). Alternative types of Earth Electrodes may be used with prior approval of the Distribution Company (e.g. plate or wire mesh type, or structural steelwork in a building). Where more than one Earth Electrode is required to achieve the required Earth Resistance value these must be separated at a distance greater than their mutual resistance zone.
[Note: a minimum separation of twice the earth electrode depth is considered to give adequate separation of the mutual resistance zones. See BS 7430 for further advice on spacing of Earth Electrodes.]

6.4.2

6.4.3

6.4.4

The Electricity Wiring Regulations 2007

55

Earthing

6.4.5

The condition of the ground in which an Earth Electrode is placed must be taken into account to ensure its longterm performance. In particular, potential corrosion effects and ground moisture content is of critical importance. Proprietary chemical or salt materials may be used around the Earth Electrode to maintain moisture content but these must be stable and sustain their chemical properties over time. For supplies of 500 A rating and above, at least two independent Earth Electrodes must be provided, regardless of the Resistance Value achieved for each Earth Electrode, and connected to the same Main Earth Terminal, see Appendix A5(k). Metallic service pipes (such as water, gas, etc) must not be used as Earth Electrodes.

6.4.6

6.4.7

6.5

Earth conductors
In these Regulations the following terminology is used to refer to Earth Conductors in an installation, see illustration in Appendix A5(f): (a) Main Earth Conductors (MEC): conductors connected between Distribution Boards, Earth Electrodes and Main Earth Terminals; and Circuit Earth Conductors (CEC): conductors connected from Final Distribution Boards and associated with Final Circuits, including Appliance Earth Conductors such as within a flexible cord. Outside these Regulations these may also be known as the Circuit Protective Conductor (CPC) or Earth Continuity Conductor (ECC).

6.5.1

(b)

56

The Electricity Wiring Regulations 2007

6.5.2

All Earth Conductors must be covered with green/yellow PVC insulation and terminated with purpose made lugs or fixings. Where associated with Circuits, all Earth Conductors must be labelled at their termination points with Circuit identification numbers, see Guidance Note G7(f). The connection of Earth Conductors to Earth Electrodes must be made using corrosion resistant clamps. Where Earth Conductors are buried below ground they must be mechanically protected (e.g. in plastic or metal duct or pipe and, where necessary, with additional tiles or plates laid above the duct or pipe, see Appendix A5(d) and Guidance Note G6. The connection of Earth Conductors to the Main Earthing Terminal must be made using purpose made lugs or other fixings and the connection must be clearly labelled as shown in Appendix A5(d). All Circuits must have a Circuit Earth Conductor sized in accordance with Appendix A5(j). Circuit Earth Conductors must, where practicable, run alongside the associated phase and neutral conductors.
[Note: this minimises the risk of a Circuit Earth Conductor being damaged or disconnected without any damage or fault indication being detected via the phase conductors.]

6.5.3

6.5.4

6.5.5

6.5.6

6.5.7

6.5.8

6.5.9

For metal sheathed or armoured cables, the sheath or armouring may be used as the Earth Conductor where it is rated to the equivalent of the conductor sizes shown in Appendix A5(j). The metal sheath or armouring must be terminated by suitable cable glands with appropriate connection to an Earth Condutor, see Guidance Note G7(i). However, where such cables are installed underground a separate Earth Conductor must be laid alongside the power cable.
The Electricity Wiring Regulations 2007 57

Earthing

6.5.10

The use of metal conduit, trunking, busbar trunking or switchgear metal enclosures as Earth Conductors is not permitted without the prior approval of the Distribution Company. In such cases, the provision of additional measures such as resistance measurements or supplementary Earth Conductors will normally be required.
[Note: metal conduit, although not to be used as an Earth Conductor, must nevertheless be effectively connected to Earth since it comprises an Exposed-Metallic-Part. See Guidance Note G7(j).]

6.5.11

No switches, isolators or circuit-breakers may be installed in the electrical path of any Earth Conductor. Removable links may be installed to allow testing at the Main Earth Terminal.

6.6
6.6.1

Exposed-metallic-parts
All Exposed-Metallic-Parts of an Installation, including Appliances, must be connected to Earth via Earth Conductors which in accordance with the requirements of Regulation 6.5. Exceptions to clause 6.6.1 may include internal parts of equipment or Appliances which cannot be accessed without first disconnecting the electricity supply. Class I Appliances having Exposed-Metallic-Parts must be provided with a suitable connection point or plug & socket arrangement which includes connection to the Circuit Earth Conductor. Class II Appliances do not require an Earth connection, see illustrations in Appendix A18(a) and A18(b). All connection points in an Installation must include an Earth Conductor for future use.
[Note: an example would be a plastic light switch which does not require a Circuit Earth Conductor but one must be provided in any case for future use see Guidance Note G7(d).]

6
6.6.2

6.6.3

6.6.4

58

The Electricity Wiring Regulations 2007

6.6.5

Items within an Installation where it is mandatory for a connection to be made to an Earth Conductor are listed in Appendix A5(l). The requirement for connection of Extraneous-MetalicParts to Earth Conductors depends on the type of protection system used in an Installation, as explained under Regulation 5.5.

6.6.6

6.7
6.7.1

Earth fault loop impedance


The Earth Fault Loop Impedance (Zs) is defined as the total impedance presented to an earth fault current, comprising the impedance of the following parts of a system, illustrated in Appendix A5(g): (a) (b) (c) the Circuit Earth Conductor (including the Appliance Earth Conductor); the Main Earth Terminal; the main Earth Conductors connecting to local Earth Electrodes (TT system) or the Distribution Company Earth (TN-S system); the path of earth fault current through the general mass of Earth, or through the earth sheath or armouring of the Distribution Company cable; in the case of a Customer Earthed System (TT system) the neutral earth connection at the Distribution Company transformer; the distribution transformer winding; and the phase conductors of the Circuit back to the point of fault.

(d)

(e)

(f) (g)

6.7.2

All Installations must be designed and tested such that the Earth Fault Loop Impedance at any point in the Installation is of a sufficient value to operate Protective Devices within 0.4 seconds for Final Circuits supplying Appliances which

The Electricity Wiring Regulations 2007

59

Earthing

are accessible to any person and within 5 seconds for all other parts of an Installation.
[Note: this requirement is important for parts of Installations where protection against Indirect Contact is provided by Earthed Equipotential Bonding rather than by Earth Leakage Protection, see Regulations 5.4 and 5.5.] 6.7.3

The maximum Earth Fault Loop Impedance values required to meet the disconnection times in clause 6.7.2 for MCB devices are given in Appendix A5(h). The method for testing Earth Fault Loop Impedance (including the external earth fault loop impedance) is given in Appendix A19(b) and A19(c).

6.7.4

6.8
6.8.1

Lightning protection
Lightning protection systems and associated earth electrodes must be separate from the electrical Installation earthing system. A minimum distance of 7 m must be provided between lightning protection earth electrodes and the Installation Earth Electrodes. Lightning protection systems must be designed, constructed and maintained in accordance with BS 6651, except that the lightning protection system is not to be bonded to the Installation Main Earth Terminal.
[See clause 5.7.6 for requirements for protection against overvoltages.]

6.8.2

6.8.3

6.9
6.9.1

Functional earthing and high leakage currents


Functional Earth conductors may be required for purposes such as, but not limited to, radio frequency noise reduction,

60

The Electricity Wiring Regulations 2007

filters for computers and other equipment with high earth leakage currents.
6.9.2

Functional Earth conductors must be separate from other parts of the Installation Earthing system, except at their connection to the Main Earth Terminal where a suitable label must be provided, see Appenix A5(f). Equipment which produces high earth leakage currents (above 10 mA) may be provided with a Functional Earth and in any case must be provided with duplicate Circuit Earth Conductors to the Main Earth Terminal. Such equipment must remain connected to Earth at all times to avoid the risk of electric shock from Exposed-Metallic-Parts of the equipment.
[Note: metallic conduit may be considered as one of the duplicate Earth Conductors required for high leakage equipment. Alternatively, Circuit Earth Conductors in a Ring Circuit are also accepted as providing a duplicate earth path. This requirement safeguards against electric shock due to Indirect Contact if only one Circuit Earth was provided and was damaged or broken.]

6.9.3

The Electricity Wiring Regulations 2007

61

Earthing

62

The Electricity Wiring Regulations 2007

Selection of components and installation requirements


7.1
7.1.1

Plugs and socket-outlets


For domestic Installations all single-phase plugs and socketoutlets must comply with BS 1363 and be fitted with a switch. The use of any other type of single-phase plugs and sockets-outlets, such as BS 546 (3 round pins) is not permitted.
[Note: BS 1363 requires plugs to have partly insulated live and neutral pins and include a fuse complying with BS 1362. Socketoutlets are required to have tamper-proof shutters on the live, neutral and Earth connections.]

7.1.2

For single-phase applications in non-domestic Installations either BS 1363 or BS 546 type plugs and socket-outlets are permitted. However, BS 546 plugs and socket-outlets must be restricted to specialist applications such as high load Appliances (BS 546 15 A plug) or where it is desirable not to intermix certain Appliances, see Appendix A17(a).
[Note: examples of the use of BS 546 plugs include table lamps in hotel rooms which are switched from a dedicated lighting Circuit (3 A or 5 A) or self contained air conditioning units (15 A). In the latter case 15 A BS 546 socket-outlets must be supplied from a dedicated Radial Circuit.]

7.1.3

The use of 2-pin plugs such as the Euro CEE7/16 plug and the Shuko CEE7/7 plug is strictly prohibited, unless provided with an approved adaptor converting such plugs for use on BS 1363 type sockets, see Appendix A17(a).
[Note: adapters must be approved by a recognised international approvals authority such as KEMA, NSAI, ASTA, etc.]

7.1.4

An allowable exception to clause 7.1.1 is the use of shaver supply units in bathrooms, complying with BS 3535. For these types of socket-outlet, which are supplied by a SELV safety isolating transformer, a 2-pin plug may be used but which must also comply with BS 3535. See Appendix A17(c).

The Electricity Wiring Regulations 2007

63

7.1.5

No socket-outlets shall be installed in a bathroom except for a socket-outlet complying with BS 3535 (shaver socketoutlet including a safety isolating transformer). Three-phase and industrial plugs and socket-outlets must comply with BS 4343 and BS EN 60309, see Appendix A17(b). The rating of three-phase socket-outlets must be selected according to the load of the Appliance or equipment to be connected.
[Note: BS 4343 plugs and socket-outlets are not fused and are not shuttered and therefore must not be used in any domestic application.]

7.1.6

7.1.7

Socket-outlets for normal use must be positioned at a height of 450 mm above floor level or 100 mm above work surfaces, see Appendix A16. Where required, low level or skirting height may be used (e.g. in offices) at a minimum of 100 mm above the floor level, and where adequate precautions are taken against damage. Access for limited ability persons must be given due consideration in such cases (e.g. alternative socket-outlets provided). Floor socket-outlets may be used where there is no undue risk of water ingress or flooding and which are designed to relevant international standards. Socket-outlets in kitchens or other areas where water is used must be positioned at least 1.0 m away from sources of water (e.g. sinks, basins, filter units, supply taps). Consideration must be given to the use of splash proof socketoutlets (IP 56). The recommended minimum number of socket-outlets for domestic Installations is given in Appendix A15. All socket-outlets in one room or service area shall be connected to the same phase.

7.1.8

7.1.9

7.1.10

7.1.11

64

The Electricity Wiring Regulations 2007

7.1.12

The maximum number of single-phase socket-outlets on each Ring or Radial Circuit shall be determined according to the anticipated load and usage of Appliances. The assumed loads given in Guidance Note G2 may be used in the absence of other loading information. Three-phase socket-outlets must be connected on individual Radial Circuits. Outdoor socket-outlets must be of the weather protected type (IP55) and incorporate a 30 mA RCD, see Guidance Note G7(c).

7.1.13

7.1.14

7.2
7.2.1

Switches and isolators


All switches provided for local isolation of Appliances and equipment (including lighting) must comply with BS 3676. The rating of switches must be selected based on the expected load, taking into account any capacitive or inductive effects. For outdoor locations, damp or wet areas, weather-protected switches must be used (BS 3676). Wall-mounted switches must not be installed in bathrooms, shower rooms or other locations where normal body resistance is reduced due to the presence of water. In such locations, ceiling mounted cord-pull switches may be used or wall-mounted switches may be used outside the room. Wall-mounted switches may be used in kitchens but at least 2 m from a sink or other source of water. For areas with higher than normal risk of fire or explosion gas-sealed switches must be used (BS 5345). For example, in gas storage areas, battery rooms, etc. The normal mounting height for switches shall be 1.3 m from floor level. Other mounting heights may be used where there is a specific need, such as, but not limited to,

7.2.2

7.2.3

7.2.4

7.2.5

The Electricity Wiring Regulations 2007

65

Components

the prevention of access by children or the requirement for access by disabled persons.
7.2.6

Switches with neon indicators must be provided for Appliances such as water heaters, air conditioning units, fridges and freezers, where a visual indication of the presence of power is desirable. Double-pole switches must be provided for water heaters, air conditioning units and other fixed Appliances operating with or near water supplies. Cooker control units (isolators) for domestic Installations must comply with BS 4177. The use of cooker control units with an integral 3-pin socket-outlet is prohibited except where the Final Circuit supplying the cooker control unit is protected by an RCD with a residual current rating of 30 mA, in accordance with clause 5.4.9.
[Note: in addition to the above restriction it is considered undesirable to use cooker control units with integral socketoutlets where there is a risk of Appliances or flexible cables supplied by the socket-outlet being damaged by heat from the cooker.]

7.2.7

7.2.8

7.2.9

Flexible cables from switches or isolators to fixed Appliances (such as water heaters, cookers, etc) must be adequately rated and securely fixed with a purpose-made flex outlet plate (which may be integral with or separate from the switch or isolator unit).

7.3
7.3.1

Lighting
Lighting Circuits will normally be fed from 6 A, 10 A or 16 A MCBs from a Final Distribution Board. The rating of lighting Circuits shall be selected in accordance with the number of connection points to be supplied, the type and rating of luminaires to be used, and

7.3.2

66

The Electricity Wiring Regulations 2007

the expected loading. The standard rating and diversity factors given in Appendix A6(f) and Guidance Note G2 may be used in the absence of other specific information.
7.3.3

Lighting Circuits supplying small Edison screw (SES) or small bayonet cap (SBC) fittings must be supplied from Protective Devices of nominal current rating no greater than 6 A. Switching of Circuits containing discharge lighting or other lighting with high inductance may require special consideration due to high switching voltages that may occur. In order to accommodate the switching voltage in discharge lighting Circuits, the rating of the switch shall be suited to the conditions expected and shall not be less than twice the load current. High voltage discharge lighting (such as neon signs) must comply with BS 559 and be provided with an emergency isolation switch which must be clearly marked and located in an easily accessible position.
[Note: such switches may be marked Firemans Switch for Neon Sign or similar wording.]

7.3.4

7.3.5

7.3.6

The connection of mains-operated clocks to lighting Circuits other than through a clock connector unit is prohibited. All Luminaires must be connected to Final Circuits using a ceiling rose or other purpose made connection point and not directly to such Circuits. Where cables are run within Luminaires they shall be of the heat resistant type, or protected by heat resistant sleeving. See Guidance Note G7(b). Lighting Circuits in false ceilings or voids must be installed in conduit or trunking in compliance with clauses 7.5.12 and 7.5.13. However, short lengths (less than 3 m) of flexible or sheathed cables may be provided between a lighting

7.3.7

7.3.8

The Electricity Wiring Regulations 2007

67

Components

connection point or ceiling rose and a Luminaire, provided that provision is made for future access and maintenance. In addition, the use of purpose made plug and socket connection systems for Luminaires is not precluded, provided that approval is sought from the Distribution Company. See Guidance Note G7(h).
7.3.9

Luminaires and other light fittings must be installed with due consideration to the weight taken by fixings and supports, and the need for adequate ventilation and heat dissipation. Heat resistant cables and flexible cords should be used for the connection of high temperature luminaires. See Guidance Note G7(b). Where light switch boxes contain more than one phase (for large groups of lighting) they must be labelled to indicate the presence of a 400 V supply, and suitable phase barriers should be provided inside the box. Outdoor lighting should be of suitable weatherproof construction with appropriate connection points and fittings. Underwater lighting must be supplied by a Separated Extra-Low Voltage System (SELV) not exceeding 12 V a.c. or 30 V d.c. Emergency light fittings must comply with BS 5266 and shall be provided with a battery of minimum 2 hours rating.

7.3.10

7.3.11

7.3.12

7.3.13

7
7.3.14

7.4
7.4.1

Conduit, trunking and cable trays


All plastic conduit and trunking must comply with BS 4607 and be suitable for the ambient conditions expected. All metal conduit and trunking must comply with either BS 4568, BS EN 60423 or BS EN 50086. Cable tray must comply with BS EN 61537.

7.4.2

68

The Electricity Wiring Regulations 2007

7.4.3

Flexible conduit must be of metal construction, PVC covered and comply with BS 731 part 1. Flexible conduit may be of plastic construction only in indoor locations, where damage is unlikely and where it contains only sheathed conductors or Earth Conductors. Metal conduit, trunking or cable tray may not, on their own, be used as Circuit Earth Conductors; separate Circuit Earth Conductors must be run inside the conduit, trunking or cable tray, see also clause 6.5.10). This does not obviate the requirement to comply with clause 6.6.1 (i.e. metal conduits are required to be Earthed), see Guidance Note G7(j). Plastic conduit or trunking must not be used in situations subject to higher than normal temperatures or fire risk (e.g. near industrial machinery, generator rooms, workshops, petrol stations, etc). Where plastic conduit is installed outdoors it should be suitable for exposure to solar radiation. Where conduit is buried in a wall, floor or ceiling it must be installed at a minimum depth of 50 mm from the surface. If installed at a shallower depth, then metal conduit must be used. See Guidance Note G7(e). Conduit, trunking and cable tray must be installed so as to provide ease of access to cable Circuits throughout the route. Sufficient inspection plates and pulling points must be provided to enable inspection, repair and drawing out of cables throughout the life of the Installation. The ends of conduit, trunking and cable tray shall be provided with bushes or other finished ends such that cables do not sustain damage during installation or throughout the life of the Installation, and must be suitably sealed against the ingress of water. Where such bushes or ends are not provided any sharp angles, burrs or projections must be removed, see Guidance Note

7.4.4

7.4.5

7.4.6

7.4.7

7.4.8

The Electricity Wiring Regulations 2007

69

Components

G7(g). Care must be taken not to leave sections of cable exposed at ends of conduit or trunking. See Guidance Note G7(a).
7.4.9

Plastic conduit boxes for accessories shall be provided with copper or brass earth terminals. See Guidance Note G7(d). Single-insulated cables may not be installed in slotted (perforated) trunking or cable trays. The minimum internal radius of any bend or elbow fitting in a conduit shall be 2.5 times the diameter of the conduit. Elbow fittings of trunking may be 90 formation only where the cover is removable so that cables may be installed without the need for pulling through. Conduit shall be installed with a maximum of two 90 bends or three 120 bends between inspection or pulling points. Cable trunking and cable tray shall be run exposed or otherwise accessible after installation, throughout its length, for the purpose of removing or installing cables. Where cable trunking or cable tray passes through walls, floors or other barriers it shall be provided with a continuous cover and an internal fire barrier where fire separation is specified for the Premises. See Guidance Note G3(a). Where trunking or cable tray is used for the combined provision of power, telecommunications and other Circuits adequate segregation must be provided, together with suitably sealed service boxes and connection boxes. Category 3 Circuits (fire and emergency lighting) may not be installed in the same conduit or trunking as Category 1 (mains supplied) Circuits or Category 2 (telecommunications) Circuits.

7.4.10

7.4.11

7.4.12

7.4.13

7.4.14

7.4.15

7.4.16

7.4.17

70

The Electricity Wiring Regulations 2007

7.4.18

Category 1 and Category 2 Circuits may only be installed in the same conduit or trunking if the latter are insulated to the level of Category 1 Circuits.
[Note: trunking or conduit referred to in clauses 7.4.17 and 7.4.18 may be metallic or non-metallic.]

7.4.19

Under floor cable trunking shall be used only in areas which are not susceptible to water ingress or flooding. Suitable junction boxes, flush service boxes and inspection compartments shall be provided according to the design of the under floor trunking system. The maximum number of cables for typical sizes of conduit and trunking are given in Appendix A9. Where conduit or trunking is installed on the Distribution Companys side of the Customer Connection Point, these must be provided with a means of locking or sealing against unauthorised interference.

7.4.20

7.4.21

7.5
7.5.1

Cables
For fixed wiring within Premises PVC (thermoplastic), rubber (thermosetting) or XLPE insulated cables with stranded copper conductors must be used, complying with the reference standards given in Appendix A3. Solid-core or Aluminium conductor cables are not permitted. For locations subject to a higher than normal risk of interference or damage armoured cables are recommended. For locations with higher than normal fire risk either cables must be installed in metal conduit or mineral-insulatedcopper-clad (MICC) cables must be used (complying with BS 6207). In addition, safety Circuits such as fire alarms, emergency lighting and control Circuits, which are required to remain operational in the event of a fire, must be installed in metal conduit or supplied by MICC cables.

7.5.2

7.5.3

The Electricity Wiring Regulations 2007

71

Components

7.5.4

The location and selection of cables must take into consideration any special requirements for the prevention of spread of fire. Fire barriers, low smoke insulation or other measures may be required (relevant building regulations should be referenced). General-purpose flexible cables and cords for Appliances must be PVC insulated, with a PVC oversheath, stranded copper conductors, and comply with BS 6500. Cables for high temperature Appliances (e.g. electric heaters, irons, pendant lighting, connections within luminaries) must be heat resistant rubber insulated, with oversheath, stranded copper conductors, and comply with BS 6141. Cables under repetitive mechanical strain (e.g. lifts, heavy outdoor machinery, etc) must comply with BS 6977. Where cables are installed underground they must be installed in ducts to protect against mechanical damage and enable future removal, see Guidance Note G6. Cables for meter tails (at 230 V) shall be single-core, PVC insulated, with oversheath, and comply with BS 6004. The cross-section of cables must be selected according to the expected load, voltage drop, ambient temperature and installation conditions using Appendix A7(a) - A7(h) including appropriate grouping factors. The maximum voltage drop from the Customer Connection Point to the remote end of any Final Circuit must not exceed 4%, except in special cases where equipment has been designed to operate under a greater voltage drop (such cases must be clearly stated in the Installation design and approved by the Distribution Company). The use of single-core armoured cables should be avoided due to the possibility of induced heating effects. However, such cables may be used where there is an exceptional need, with the written consent of the Distribution Company

7.5.5

7.5.6

7.5.7

7.5.8

7.5.9

7.5.10

7.5.11

72

The Electricity Wiring Regulations 2007

and where adequate precautions are taken to avoid induced heating effects. Such precautions may include the appropriate spacing of phases to balance induced currents, Earthing at one end only and the use of non-ferromagnetic armouring, cable glands, and switchgear gland plates, see Guidance Note G7(l).
7.5.12

Other than as allowed under clause 7.5.15, all cables which are not armoured must be installed in plastic or metal conduit or trunking throughout their entire length. Cables running through inaccessible areas such as walls, floors and solid ceilings shall be installed, without exception, in conduit or trunking so as to be withdrawable in the future. In such cases, suitable inspection plates and pulling out points must be provided. Non-sheathed cables must not be installed in concrete ducts. Exceptions to clause 7.5.12 may be allowed only for sheathed or flexible cables which will remain accessible but in locations free from undue risk of damage or interference (e.g. above head height, or in unoccupied areas). Such cables must be securely supported by cable clips, cable tray or other fixings at suitable intervals.
[Note: although flexible cords must not be used as fixed wiring this clause covers Appliance connection cables which should be limited to 3 m in length where practicable. In addition, proprietary plug and fit connection systems may be installed from a suitable connection point in the fixed wiring system, provided they are suitably supported, mechanically protected, or otherwise located in areas where there is minimal risk of damage or interference. See Guidance Note G7(h).]

7.5.13

7.5.14

7.5.15

7.5.16

All cables must be installed between purpose-made termination points (switches, junction boxes, Distribution Boards) and be terminated with purpose-made lugs, crimps, screw connectors or other connectors. Joints between

The Electricity Wiring Regulations 2007

73

Components

such points are strictly prohibited. Termination points and junction boxes must remain accessible to facilitate future inspection, repair and alteration. See Guidance Note G7(k).
[Note: terminations for MICC cables must be suitably sealed against the ingress of moisture.] 7.5.17

Where cables are terminated at high temperature Appliances their insulation must be suitable for the expected operating temperature or, where necessary, shall be protected by heat resistant material. See Guidance Note G7(b). Armoured cables must be terminated using suitable cable glands which incorporate a suitably rated Earth tag or other purpose-made connection to the armouring of the cable and to the metallic sheath if present. See Guidance Note G7(i). Cables must not be installed in lift shafts other than those serving lift functions.
[Note: although a lift shaft may be a convenient means of providing a cable route through a building this creates unwarranted risk when accessing such Circuits for maintenance and also provides a vulnerable route for the propagation of fire.]

7.5.18

7.5.19

7.5.20

The colour identification Appendix A8.

for

cables

is

given

in

[Note: although the identification colours for cables has recently been changed in European countries a similar change is not currently proposed for Abu Dhabi Emirate. For fixed wiring in an Installation the phase colours remain as red, yellow and blue whilst neutral remains as black. However, for flexible sheathed cables supplying single-phase Appliances brown is used for live and blue is used for neutral see Appendix A8.]

74

The Electricity Wiring Regulations 2007

7.6
7.6.1

Final circuits
The sizing of Final Circuits must take into account the diversity of use of Appliances and equipment as well as possible increases in load requirements. See Guidance Note G2 for advice on load diversity factors. Radial Circuits should be provided to large Appliances, particularly those in continuous or near continuous operation, or those of importance for safety or other priority functions within a Premises. Examples include main water pumps, air conditioning units, water heaters, room heating, fire or intruder alarms, cookers and ovens, etc. Ring Circuits should be provided to areas within a property which can be most economically served by several Appliances sharing the same cable feed, arranged in a loop, from one circuit-breaker on the Final Distribution Board. This is particularly suitable where Appliances are expected to operate at diverse times of the day. Ring Circuits would typically be installed in bedrooms, living rooms, kitchens (except major Appliances such as cookers), partitioned office areas, etc. Circuits supplying a kitchen must not be used to supply any other area. However, ceiling lighting Circuits from a kitchen may be common to other areas. For domestic Premises all Circuits supplying one room must be on the same phase, other than for kitchens, and for ceiling lighting. Typical Radial and Ring Circuit arrangements for domestic Premises are shown in Appendix A14.

7.6.2

7.6.3

7.6.4

7.6.5

7.6.6

The Electricity Wiring Regulations 2007

75

Components

7.7
7.7.1

Busways, bus ducts and busbar risers


Busways, bus ducts, busbar risers or other similar systems may be used in Premises for the supply of large loads where they provide a more economic or practical option than cables. Busways, bus ducts and busbar risers shall comply with the relevant reference standards given in Appendix A3. Busways, bus ducts and busbar risers shall be totally enclosed (non-perforated) for protection against mechanical damage, moisture, dust and other environmental effects. Busways, bus ducts and busbar risers shall not be located in areas prone to mechanical damage or where they may be exposed to hazardous materials, liquids or gases, unless special precautions are taken. Busways, bus ducts and busbar risers shall be located so that they are accessible for future maintenance and repair throughout their length. They shall not be installed in habitable areas such as flats, offices, shops, etc (a separate riser shaft or room must be provided). Busways, bus ducts and busbar risers shall have neutral conductors of equal size to the phase conductors and shall have a dedicated Earth Conductor. The use of the metal casing as an Earth Conductor shall not be permitted. The current rating of busways, bus ducts and busbar risers shall be based on the Connected Load of the relevant part of the Installation being supplied. However, additional diversity factors may be applied for high-rise buildings or other large installations rather than taking the sum of Connected Loads. Any applied diversity factors must be justified and submitted with the design for approval by the Distribution Company, see Regulation 3.2.

7.7.2

7.7.3

7.7.4

7.7.5

7.7.6

7.7.7

76

The Electricity Wiring Regulations 2007

7.7.8

Purpose made plug-in circuit-breaker units may be used with busbar risers systems where they are mechanically interlocked to prevent removal whilst energised. See Guidance Note G3(a). The number of busways, bus ducts or busbar risers required for a high-rise building and the number of floors served by each must be selected by taking due account of the future accessibility, maintainability and safety of the system, whilst limiting the extent of power outage to serviced areas.
[Note: a typical arrangement may be to serve each 10 floors of a 30 storey building by a separate bus riser; however, other arrangements are not precluded.]

7.7.9

7.8
7.8.1

Distribution boards
All Distribution Boards must be factory assembled, type-tested and comply with BS EN 60439. Distribution Boards must be of robust construction, capable of withstanding expected electrical, thermal, and environmental stresses in normal service and during faults. Apparatus forming part of the assembly of Distribution Boards shall have electrical isolation clearances sufficient to withstand normal voltages, surge voltages and creepages as defined in BS EN 60439-1. Each Distribution Board must have a neutral bar which is mounted on insulators and which has a sufficient number of terminal points of adequate size for the largest cable expected to be used. Each Distribution Board must have an Earth bar which has a means of connection to the incoming Earth Conductor and cable gland of the incoming cable, see Appendix A5(e) and A12(c).

7.8.2

7.8.3

7.8.4

7.8.5

The Electricity Wiring Regulations 2007

77

Components

7.8.6

All Final Distribution Boards must have at least two busbar sections (split busbars) so as to provide for different levels of Earth Leakage Protection (e.g. 100 mA RCD and 30 mA RCD). See Appendix A12(c).
[Note: for additional levels of Earth Leakage Protection individual RCBO devices may be provided for the relevant Final Circuits.]

7.8.7

Other than for small 2-storey buildings each floor of a Premises shall be provided with at least one Final Distribution Board installed in an easily accessible location. The number of Final Distribution Boards and Sub Distribution Boards provided in a Premises shall take into account the future accessibility, maintainability and safety of the system, whilst limiting the extent of possible power outages to serviced areas.
[Note: to meet the above requirement Final Distribution Boards should be limited to a maximum capacity of 14 ways 3-phase i.e. 42 Circuit positions.]

7.8.8

7.8.9

Single-phase Distribution Boards may be permitted in a Premises where adequate provision is made for balancing the total load at the Supply Intake between the three phases.
[Note: single-phase Distribution Boards would normally be used for small load applications such as hotel rooms, garages, small out buildings.]

7.8.10

The phase and neutral busbars in all Distribution Boards shall be identified by the colours given in Appendix A8. The phase and neutral conductors in all Distribution Boards shall be of the same cross sectional area. Neon indicators, voltmeters and ammeters must be provided for Distribution Boards rated at 400 A and above, and where

7.8.11

7.8.12

78

The Electricity Wiring Regulations 2007

reasonably practicable for other Distribution Boards.


[Note: where practicable, maximum demand meters and power factor meters should also be provided] 7.8.13

All Distribution Boards must be provided with only circuitbreakers (such as CBs, MCBs, MCCBs, RCDs, etc) and shall not contain fuses of any kind, except for capacitor banks. See Regulation 10.2. All Distribution Boards must be installed in locations easily accessible for inspection, operation and maintenance, preferably at the entrance to the area they serve. Such locations must be secured from unauthorised interference. Distribution Boards of rating 200 A and above shall be installed in a dedicated room. See Appendix A12(b). Distribution Boards shall not be installed in locations where water is used (e.g. kitchens, bathrooms, pump rooms), within 2 metres of any pipe or other source of water, or in difficult-to-access positions (such as stairways). Distribution Boards must be provided with sufficient numbers of Protective Devices so as to enable every outgoing Circuit to be connected to an individual Protective Device and shall include not less than 10% spare Protective Devices or blank positions.

7.8.14

7.8.15

7.8.16

7.8.17

7.9
7.9.1

LV switchboards
Where prefabricated Distribution Boards of sufficient rating are not available, LV switchboards, consisting of cubicle panel switchgear, may be provided. LV switchboards must consist of type-tested assemblies which satisfy the requirements of BS 5486 or BS EN 60439.

The Electricity Wiring Regulations 2007

79

Components

7.9.2

Switchboards must be located in a dedicated room to provide for safe access and egress at all times, including during maintenance, repair and replacement work. LV switchrooms must meet the requirements of Supply Intake rooms listed in Regulation 4.2. Typical layouts and minimum space requirements for LV switchrooms are given in Appendix A12(d). Switchboards rated above 400 A must be provided with instruments for voltage, current, maximum demand and power factor measurement, as well as phase indicating lamps. Where more than one incoming supply cable is provided at the Supply Intake these must be connected to separate switchboards (or separate sections of the same switchboard) which have the facility for interconnection through a bus coupler circuit-breaker or switch. In order to prevent parallel connection of the incoming supply cables the bus coupler circuit-breaker or switch must be interlocked to prevent its closure when both incoming supply cables are live. Bus switches and circuit-breakers must be capable of closure onto a fault unless interlocked so as to only be operated whilst dead. All busbars in switchboards must be tinned copper and rigidly supported throughout their length. The neutral and earth busbars must run throughout the length of the switchboard. The neutral busbar must be of the same crosssectional area as the phase busbars. The main incomer circuit-breaker(s) must be clearly marked and left unlocked to allow immediate operation in an emergency, see clause 4.3.3.

7.9.3

7.9.4

7.9.5

7.9.6

7.9.7

80

The Electricity Wiring Regulations 2007

Inspection, testing and certification


8.1
8.1.1

Electrical installation certificates


Every new Installation shall, on completion and before being energised, be inspected and tested by a Licensed Contractor who shall duly complete the relevant test reports and submit these to the Distribution Company (with the exception of tests that can only be done after energising).
[Note: see Regulation 3.4 for details of contractor licencing.]

8.1.2

In order to verify compliance with these Regulations the Licensed Contractor shall complete and sign an Electrical Installation Certificate in the format shown in Appendix A20(a), as shall the designer and installer of the Installation (may be the same person or company). Two original copies of the Electrical Installation Certificate and associated test results shall be provided, one to the Customer or Owner of the Premises, and one to the Distribution Company. An additional copy must be affixed at the Main Distribution Board or Supply Intake position, see Appendix A12(b). The Distribution Company shall verify on site the test results for Earth Resistance at the Main Earth Terminal and inspect or test other items as deemed appropriate, including as a minimum: (a) (b) (c) (d) (e) connection of conductors; identification of equipment; conductors and labelling of

8.1.3

8.1.4

routing of cables and their protection against mechanical damage; cross-sectional area of conductors for currentcarrying capacity and voltage drop; connection of single-pole devices for protection or switching in phase conductors only;

The Electricity Wiring Regulations 2007

81

(f) (g) (h) (i) (j) (k)


8.1.5

correct positioning and connection of accessories and equipment; presence of fire barriers and protection against thermal effects; methods of protection against electric shock, both Direct and Indirect Contact; inspection of integrity of Main Earth Conductors and Earth Electrodes; presence and correct location of isolation; and devices for

measurement of Earth Fault Loop Impedance.

The Distribution Company may carry out intermediate inspection(s) prior to the final inspection mentioned in clause 8.1.4. This is to verify compliance of concealed parts of the Installation (e.g. conduit, buried cables and Earth Conductors). Internal checks and inspection shall be carried out on a 10% sample of the Installation, relevant to the items listed under clause 8.1.4. After any extension or alteration to an electrical Installation a Licensed Contractor is required to issue an amended Electrical Installation Certificate, together with a copy of the original certificate, and stating the details of the work carried out, see Regulation 3.2 and 3.3.

8.1.6

8.1.7

82

The Electricity Wiring Regulations 2007

8.2
8.2.1

Routine inspection and testing


The responsibility for routine inspection and testing of Electrical Installations lies with the Owner of the Premises who shall request the services of a Licensed Contractor at the intervals shown in the table below. The Owner must also ensure that any neccessary rectification work is carried out.
Internal Installation Domestic Non-domestic (commercial, industrial, farms, etc) Premises used by the public (schools, hospitals, hotels, malls, parks, wedding tents, mosques) Special locations (construction sites, swimming pools and fountains, street lighting) 5 years 3 years External Installation 5 years 3 years

3 years

2 years

1 year

1 year

8.2.2

Electrical Installations which were constructed before the date of commencement of these Regulations (clause 1.1.2) shall be inspected and tested within the time indicated above from the date of commencement. Routine inspection and testing shall be recorded on the standard forms shown in Appendices A20(b) A20(d) and shall include: (a) (b) (c) continuity of Ring and Final Circuit conductors; continuity of Earth Conductors including Equipotential Bonding Conductors; insulation resistance;

8.2.3

The Electricity Wiring Regulations 2007

83

Inspection

(d) (e) (f) (g) (h) (i)

protection against Direct Contact; protection against Indirect Contact; polarity of Circuits; Earth Fault Loop Impedance; Earth Electrode Resistance; and operation of Earth Leakage Protection devices.

[Note: see Appendix A19(a) to A19(g) for relevant test procedures.] 8.2.4

The continuity test shall be carried out with an instrument having a no-load voltage between 4 V and 24 V d.c or a.c. and a short-circuit current not less than 200 mA, in accordance with the procedure in Appendix A19(d). The insulation resistance tests between live conductors and between each live conductor and Earth shall be measured with a test voltage of 500 V d.c, in accordance with the procedure in Appendix A19(f).

8.2.5

84

The Electricity Wiring Regulations 2007

Special locations and systems


9.1
9.1.1

Separated extra-low voltage (SELV)


SELV systems are used where an inherently safe system of supply is required such that a breakdown of primary insulation will not lead to the risk of electric shock. This is achieved by electrical separation of the Final Circuit from the source of energy, typically using a safety isolating transformer, see illustration in Appendix A18(c). For a Separated Extra-Low Voltage system the Final Circuit voltage shall not exceed extra-low voltage i.e. 50 V a.c. or 120 V d.c. between conductors or to Earth. The source of SELV power shall be provided by either: (a) a safety isolating transformer complying with BS 3535, in which there is no connection between the output winding and the body or with the Circuit Earth Conductor, if any; or a battery source.

9.1.2

9.1.3

(b)
9.1.4

All components of a SELV system (including conductors, switches, relays, etc) shall be physically separated from those of any other live system. No Exposed-Metallic-Part of a SELV system shall be connected to any of the following: (a) (b) (c) Earth; any Earthed Metallic Part of another system or Extraneous-Metallic-Part; or an Earth Conductor of any system.

9.1.5

9.1.6

Insulation against Direct Contact of the conductive parts of a SELV system is required if the operating voltage exceeds 12 V a.c. or 30 V d.c. Insulation is not required if the operating voltage is at or below these values.

The Electricity Wiring Regulations 2007

85

9.2
9.2.1

Protective extra-low voltage (PELV)


A PELV system is one where the same provision for electrical separation is provided as for SELV, i.e. between the source of energy and the Final Circuit. However, in a PELV system the connection to Earth of Exposed-MetallicParts is permitted. See Appendix A18(d).

9.3
9.3.1

Bathrooms and similar locations


Special provisions are required for the protection against electric shock of persons in locations containing a bath or shower. Such provisions, as listed in the following clauses, must also be applied in other similar situations where persons are likely to be partly clothed and in contact with water, with or without footwear.
[Note: similar locations would include washrooms, toilets, wudu areas in mosques, etc. The requirements for swimming pools are listed in Regulation 9.4.]

9.3.2

The following principal requirements must be met for bathrooms and similar locations: (a) all Final Circuits must be protected by an RCD of residual current rating 30 mA and complying with IEC 60898 or BS 3871. Such protection may be grouped across several Circuits at the Final Distribution Board; no socket-outlets are permitted except those supplied by an isolating transformer and complying with BS 3535 (e.g. shaver socket-outlet); all Appliances, Luminares and other Accessories must have a minimum level of moisture ingress protection of IPX4; Appliances, Luminares or other Accessories may not be installed within Arms Reach from a bath, shower or similar facility. However, such items are permitted

(b)

(c)

(d)

86

The Electricity Wiring Regulations 2007

within the room containing a bath or shower at a distance greater than Arms Reach from the bath, provided that the requirements of clauses 9.3.2(a) to 9.3.2(c) above are complied with. In addition, all switches associated with such equipment must be installed outside the bathroom or provided with a cord-pull switch; and (e) Appliances, Luminares or Accessories which are within Arms Reach from a bath, shower or similar facility must be supplied by SELV or PELV and have a minimum level of ingress protection of IPX7. Underwater lighting must be supplied by SELV at a maximum voltage of 12 V a.c. or 30 V d.c.

[Note: items which are within a distance of Arms Reach but are inaccessible to persons need not comply with clause 9.3.2(e). For example, water pumps installed under a bath which are not accessible without removal of covers requiring a tool.] 9.3.3

The Electricity Wiring Regulations 2007

87

Special Locations

The provision of Earthed Equipotential Bonding is not required in a bathroom or similar location where the Installation is classified as an Earth Leakage Protected System, as described under Regulation 5.4. In particular, the requirement for Earth Leakage Protection on Final Circuits, along with back-up earth fault protection at the Supply Intake must be met. Earthed Equipotential Bonding and Supplementary Equipotential Bonding are required where back-up earth fault protection is not provided, even where RCD protection has been provided at the Final Distribution board supplying the bathroom or similar location.

9.4
9.4.1

Swimming pools
The requirements for protection against electric shock for swimming pools are similar to those of bathrooms, with some exceptions, as follows: (a) all Final Circuits must be protected by an RCD of residual current rating 30 mA and complying with IEC 60898 or BS 3871. Such protection may be grouped across several Circuits at the Final Distribution Board. Exceptions may be allowed for high current applications where RCD protection of 100 mA residual current rating may be allowed, but only where such equipment is out of reach of persons;
[Note: an example of Circuits where 30 mA RCD protection may not be practical is floodlighting or large water pumps. Such items must be out of reach of any person using the swimming pool or any associated washing areas.]

(b)

no socket-outlets are permitted within Arms Reach from a swimming pool. Socket-outlets may be provided outside this distance for purposes such as cleaning of the pool, which must have a minimum ingress protection of IPX6 and must have an integral RCD of residual current rating 30 mA, see Guidance Note G7(c); all Appliances, Luminares and other Accessories must have a minimum level of moisture ingress protection of IPX4; no Appliances, Luminares or other Accessories may be installed within Arms Reach from a swimming pool. However, such items are permitted within the swimming pool area (but not shower room area) at a distance greater than Arms Reach from the pool, provided that the requirements of clauses 9.4.1(a) to 9.4.1(c) above are complied with; and

(c)

(d)

88

The Electricity Wiring Regulations 2007

(e)

Appliances, Luminares or Accessories which are within Arms Reach from a swimming pool must be supplied by SELV or PELV and have a minimum level of ingress protection of IPX7. Underwater lighting must be supplied by SELV at a maximum voltage of 12 V a.c. or 30 V d.c.

9.4.2

The provision of Earthed Equipotential Bonding is not required in swimming pools and associated wash facilities where the Installation is classified as an Earth Leakage Protected System, as described under Regulation 5.4. In particular the requirement for Earth Leakage Protection on Final Circuits, along with back-up earth fault protection at the Supply Intake, must be met. EEB and Supplementary Equipotential Bonding will be required where back-up earth fault protection has not been provided, even where RCD protection has been provided at the Final Distribution Board supplying the swimming pool and associated areas.

9.5
9.5.1

Water fountains
The requirements for protection against electric shock for water fountains are similar to those required for swimming pools, with some exceptions, as follows:
[Note: it is assumed that persons may enter a water fountain for the purpose of maintenance, or other reason, and the exposure to electric shock is therefore similar to that of swimming pools.]

(a)

All Final Circuits must be protected by an RCD of residual current rating 30 mA and complying with IEC 60898 or BS 3871. Such protection may be grouped across several Circuits at the Final Distribution Board. Exceptions may be allowed for high current applications where RCD protection of 100 mA residual current rating may be allowed, but only where such equipment is out of reach of any person;

The Electricity Wiring Regulations 2007

89

Special Locations

[Note: an example of Circuits where 30 mA RCD protection may not be practical is floodlighting or large water pumps. Such items must be out of reach of persons whilst standing within the water fountain.]

(b)

no socket-outlets are permitted within Arms Reach from a water fountain. Socket-outlets may be provided outside this distance for purposes such as cleaning of the water fountain, which must have a minimum ingress protection of IPX6 and must have an integral RCD of residual current rating 30 mA, see Guidance Note G7(c); all Appliances, Luminares and other Accessories must have a minimum level of moisture ingress protection of IPX4; no Appliances, Luminares or other Accessories may be installed within Arms Reach from a water fountain. However, such items are permitted at a distance greater than Arms Reach from the water fountain, provided that the requirements of clauses 9.5.1(a) to 9.5.1(c) above are complied with; and Appliances, Luminares or Accessories which are within Arms Reach from a water fountain must be supplied by SELV or PELV and have a minimum level of ingress protection of IPX7. Underwater lighting and submerged water pumps must be supplied by SELV at a maximum voltage of 12 V a.c. or 30 V d.c.

(c)

(d)

(e)

9.5.2

The provision of Earthed Equipotential Bonding is not required for water fountains where the Installation is classified as an Earth Leakage Protected System, as described under Regulation 5.4. In particular the requirement for Earth Leakage Protection on Final Circuits, along with back-up earth fault protection at the Supply Intake, must be met. EEB and Supplementary Equipotential Bonding will be required where back-up earth fault protection has not been provided, even where RCD protection has been provided at the Final Distribution Board supplying the water fountain and associated areas.

90

The Electricity Wiring Regulations 2007

9.6
9.6.1

Construction sites and outdoor supplies


This Regulation applies to construction sites and other permanent or temporary outdoor supplies such as exhibitions, wedding tents, parks, gardens, etc. Due to the additional risks of damage and interference to outdoor installations the following precautions should be catered for in the design and construction of such systems: (a) all cables which are not installed in conduit or trunking must be armoured and adequately protected against accidental or deliberate interference by persons, and against the effects of weather;
[Note: type HO7 RN-F braided or armoured cables complying with BS 6007 are recommended.]

9.6.2

(b)

outdoor Electrical Installations must have a minimum ingress protection level of IP53 and switchgear assemblies must comply with BS 4363 and BS EN 60439-4; cables passing on or over walkways and access roads must be adequately enclosed to avoid Danger. Buried cables must be installed so as to afford adequate protection against damage, see Guidance Note G6; particular attention should be given to the location, signing and protection of equipment where the public may have access, in particular children; equipment should be located and adequate notices displayed so that emergency disconnection of the electricity supply can be effected without delay. Locking arrangements should be such that these can be removed in an emergency (e.g. panic bar or keys available in break-out box); the requirements for periodic inspection and testing must be strictly complied with (Regulation 8.2); and an Earth Leakage Protected System must be provided in line with Regulation 5.4. In addition, outdoor

(c)

(d)

(e)

(f) (g)

The Electricity Wiring Regulations 2007

91

Special Locations

socket-outlets must be provided with integral RCD protection with a residual operating current of 30 mA or less.
[Note: water coolers and drinking fountains must be provided with individual RCD protection, in addition to that provided at the Final Distribution Board.] 9.6.3

Consideration should be given to the use of a reduced voltage supply (RLV) for portable tools where there is a high exposure to potential damage, or where persons are required to operate such equipment in confined spaces or other hazardous circumstances.
[Note: RLV may be preferred on construction sites compared with supply by ELPS to avoid nuisance tripping and the potential failure of RCDs in harsh outdoor environments.]

9.7
9.7.1

Street lighting
The detailed installation requirements for supplies to street lighting and other street equipment (traffic signals, signs, etc) shall be specified by the Distribution Company. Protection against electric shock for street lighting shall be provided by either an Earth Leakage Protected System (Regulation 5.4) or by an Earthed Equipotential Bonded System (Regulation 5.5). In the latter case, the street light column or other structure shall be connected to a means of Earthing, which will normally be from the Distribution Company supply cable. Temporary supplies taken from street lights, such as for decorative lighting or signboards, must be provided with Earth Leakage Protection using RCDs of residual current rating no greater than 30 mA where within reach of persons, or 100 mA where not within reach of persons. Time delayed devices may be used to avoid nuisance tripping. Alternatively, such supplies may be provided by SELV or RLV.

9.7.2

9.7.3

92

The Electricity Wiring Regulations 2007

Capacitors and motors


10.1
10.1.1

10

General requirements
The power factor of every Installation shall be controlled to between 0.9 lagging and unity by means of power factor correction capacitors. These may be connected so as to provide individual compensation, group compensation, or centralised compensation. Power factor correction capacitors shall normally be of dry or oil-filled, encapsulated, sealed type. The use of oil containing PCB (poly-chlorinated biphenyls) is strictly prohibited. Power factor correction capacitors shall be provided with a means of prompt discharge on disconnection of the supply voltage. The discharge Circuit shall be permanently or automatically connected to the capacitor. Manual means of switching or connecting the discharge circuit is not permitted. Air conditioning units, motors, large electrical machines, fluorescent or discharge lighting, etc, shall be provided with integral power factor correction. For group compensation, automatically regulated capacitor banks shall be used which provide, as far as reasonably practicable, a smoothed power factor throughout the range of operation. The rating of each capacitor step shall be such that the initial steps have less kVAr rating and the rating of subsequent steps increase progressively to the desired maximum kVAr. For induction motors, the capacitor rating must not exceed 90% of the no-load reactive power of the motor.
[Note: this is required in order to avoid the high overvoltage across the terminals due to the occurrence of self excitation on run-down condition of the motor.]

10.1.2

10.1.3

10.1.4

10.1.5

10.1.6

The Electricity Wiring Regulations 2007

93

10.1.7

The occurrence of harmonics while employing variable speed drives, welding machines or similar devices in Circuits can lead to disturbances in the system and may cause capacitor failure. To minimise this risk harmonic filters must be employed in series with capacitors.

10.2
10.2.1

Specifications for capacitors


Capacitors shall be capable of continuous operation provided that none of the following limitations is exceeded: (a) (b) (c) 135% of the rated reactive power; 110% of the rated voltage (rms), including harmonics but excluding transients; and 180% of the rated current (rms), including fundamental and harmonic current.

10.2.2

Built-in discharge resistors for capacitors shall be sized to ensure safe discharge of the capacitor to less than 50 V in one minute after a switch off. Each capacitor shall be provided with a permanent nameplate, which includes the following information: (a) (b) (c) (d) (e) (f) (g) (h) name of the Manufacturer; serial No; year of Manufacture; rated reactive power; rated voltage (rms); number of phases; rated frequency; statement of discharge device; short-circuit current; and statement of liquid fill (if any).

10.2.3

10

(i) (j)

94

The Electricity Wiring Regulations 2007

10.2.4

Capacitors shall be able to withstand up to 30 times In caused by harmonics. Capacitors shall have provision for effective Earth connection of the case to the capacitor mounting frame and to the Circuit Earth Conductor. Capacitors and related components such as regulators, indicating instruments, contactors, etc, shall be capable of withstanding local environmental conditions. Contactors shall be designed for capacitive switching and be able to withstand switching surges. Contactors shall be rated for 1.5 to 1.8 times the normal rated current of the capacitor and shall isolate all three phases on switch off. Each capacitor step shall be protected by means of HRC fuses (current limiting type). The capacitor panel must be provided with a suitably rated main incomer isolating switch. This shall be a three-pole isolator or MCCB as the case may be. The handle of the incomer isolator shall be interlocked with the door to ensure that the capacitor bank is de-energized when the door is open.

10.2.5

10.2.6

10.2.7

10.2.8

10.2.9

The Electricity Wiring Regulations 2007

95

Capacitors and Motors

10.2.10

A capacitor bank shall not be a part of the motor control centre, main LV panel or sub-main panel, but it shall be accommodated in a separate cubicle.

10

10.2.11

Capacitor banks shall conform to the latest relevant international standards, including the following:
Relevant international standards for capacitors LV switchboard Degree of protection LV circuit-breaker and disconnector Power factor correction capacitors Power factor regulator Capacitor switching contactors Detuning reactors IEC 60439-1 IEC 60529 IEC 60947 (1-5) IEC 60831 (1-2) IEC 60664 and IEC 1010-1 IEC 60070 and IEC 60831 IEC 60289 and IEC 60076

10.3
10.3.1

Electric motors and starters


The installation of electric motors supplied from the LV distribution system is permitted up to a maximum of 5 HP (3.7 kW) for single-phase and 150 HP (110 kW) for three-phase. Where it is proposed to install more than one motor of rating 150 HP the relevant diagrams, operation information, protection arrangements, etc. must be provided to the Distribution Company to gain approval for connection. All electric motors shall be adequately protected against overload, short-circuit, loss of one or more phases and voltage dips, etc. as appropriate for each application. Emergency fire fighting motors or pumps are excluded from this clause as they may be required to operate to failure without the provision of protective devices.
[Note: motor control and protection equipment must be arranged so that re-starting is not automatic after automatic tripping due to a fault or other disturbance mentioned in clause 10.3.2 above.

10.3.2

10

96

The Electricity Wiring Regulations 2007

It is recommended that air conditioning units above 3kW should be provided with under-voltage tripping relays operating at 75% of the nominal supply voltage and with an auto-reset timer set at between 5 and 10 minutes.] 10.3.3

All electric motors above 5 HP must be provided with protection against mechanical overload. All single-phase motors above 1 HP and three-phase motors above 3 HP shall be provided with current limiting starting equipment to effectively keep the starting current within the following limits:
Rating of motor 1 HP to 5 HP Above 5 HP and up to 50 HP Above 50 HP and up to 150 HP Maximum permissible starting current 5 x full-load current 2 x full-load current 1.5 x full-load current

10.3.4

[Note: any form of motor starter may be used to achieve the values in the table above, including direct on-line starter, primary resistance starter, auto transformer or electronic soft starter.] 10.3.5

10.4
10.4.1

Standby generators
Installation and connection of standby generators in any Installation, for the purpose of maintaining power in the case of a failure of the incoming supply, shall be permitted only with the prior approval of the Distribution Company. The changeover circuit-breaker shall have 4 poles for a three-phase generator and 2 poles for a single-phase generator, to ensure that all live and neutral conductors are disconnected at the same time.

10.4.2

The Electricity Wiring Regulations 2007

97

Capacitors and Motors

Wiring and control diagrams must be permanently fixed adjacent to motors.

10

10.4.3

The installation and changeover arrangements must ensure that there is no possibility of paralleling the generator and incoming mains supply. If paralleling arrangements are required these must be specifically assessed and approved by the Distribution Company. The requirements for such arrangements (including earthing arrangements) are provided in the Electricity Distribution Code Annex 1: Engineering Recommendation No. 3 Connection of Embedded Generation Plant up to 5 MW.

10

98

The Electricity Wiring Regulations 2007

Appendices

The Electricity Wiring Regulations 2007

99

Capacitors and Motors

10

10

100

The Electricity Wiring Regulations 2007

Appendices
A1. A2. A3. A4. Glossary of terms and abbreviations Recomended books and references Reference standards Legal references (a) (b) A5. List of regulations and clauses which do not apply to existing installations Relevant extracts of Law No (2) of 1998 114 116 105 108 111

Earthing (a) (b) (c) (d) (e) (f) (g) (h) (i) (j) (k) (l) Distribution company earthed system (TN-S) Customer earthed system (TT) Distribution company earthed system with additional earth (TN-S-TT) Earth electrode pit and standard labels Main earth terminal (MET) at main distribution board (MDB) Main earth conductors (MEC) and circuit earth conductors (CEC) Components of earth fault loop impedance Earth fault loop impendance values required for MCBs (at 230 V) Resistance per metre of copper conductors for calculation of R1+R2 123 124 125 126 127 128 129 130 131

Sizing of earth conductors and equiptential bonding conductors 132 Minimum number of earth electrodes Mandatory connections to earth conductors 134 135

The Electricity Wiring Regulations 2007

101

(m) A6.

Residual operating current settings for RCDs and ELP devices

136

MBC characteristics (a) (b) (c) (d) (e) (f) (g) Time-current characteristic of MCBs as multiple of rated current Time-current characteristic of Type B MCBs Time-current characteristic of Type C MCBs Time-current characteristic of Type D MCBs Typical energy let-through characteristics of MCBs MCBs selection criteria Internal construction of MCB 138 139 140 141 142 143 145

A7.

Current ratings for cables (a) (b) (c) (d) (e) (f) (g) (h) Current ratings for PVC single core cables (non-armoured) Current ratings for PVC multi-core cables (non-armoured) Current ratings for PVC multi-core cables (armoured) Current ratings for thermo-setting multi-core cables (armoured) Current ratings for MICC cable Cable ratings and voltage drop for flexible cords Temperature correction factors for cables Grouping factors for cables 146 147 149 150 151 152 153 154 155 156

A8. A9.

Colour identification for cables Capacity of conduits and trunking

102

The Electricity Wiring Regulations 2007

A10. A11. A12.

IP coding for ingress protection Standard wiring diagram symbols Supply intake (a) (b) (c) (d) Danger of death sign Typical layout of supply intake room Typical layout of final distribution board (FDB) and RCD label Typical layout of LV switchroom

157 158

160 161 162 163 164 165 166 167

A13. A14. A15. A16. A17.

Boundary of customer connection point and scope of the Regulations Typical layout for ring circuits and radial circuits Minimum number of socket-outlets and connection points Mounting height for accessories and socket-outlets Plugs and socket outlets (a) (b) (c) Approved and prohibited plugs and socket-outlets (domestic) Industrial plugs and socket-outlets BS 3535 shaver socket-outlets for bathrooms

168 169 170

A18.

Special systems (a) (b) (c) (d) Class I equipment (earthed metallic parts) Class II equipment (double insulated) Separated extra-low voltage (SELV) supply Protective extra-low voltage (PELV) supply 171 172 173 174

The Electricity Wiring Regulations 2007

103

(e) A19.

Reduced low voltage (RLV) supply

175

Test procedures (a) (b) (c) (d) (e) (f) (g) Measurement of earth electrode resistance Measurement of external earth fault loop impedance Measurement of internal earth fault loop impedance Circuit continuity tests Circuit polarity tests Insulation resistance tests Sequence of testing for new installations 176 177 178 179 180 181 182

A20.

Forms and certificates (a) (b) (c) (d) (e) Electrical Installation certificate Inspection report (front) Inspection report (back) Installation testing report Load distribution schedule 183 184 185 186 187

104

The Electricity Wiring Regulations 2007

A1.
A a.c.

Glossary of terms and abbreviations


Amps or Amperes alternating current Abu Dhabi Water and Electricity Authority The Association of Short-circuit Testing Authorities (UK) British Standard British Standard which has been published under the European Normalisation procedure British Standards Institute Circuit-Breaker Customer Connection Point (see definitions) Circuit Earth Conductor (see definitions) Circuit Protective Conductor (see definition for CEC) direct current Earth Continuity Conductor (see definition for CEC) Earthed Equipotential Bonding (see definitions) Earthed Equipotential Bonded System (see definitions) Earth Fault (protective device) Earth Leakage Circuit-Breaker (see definitions) Earth Leakage Protection (see definitions) Extra-Low Voltage (see definitions) European Normalisation standard document Earth Leakage Protected System (see definitions) Emirates Standardisation & Metrology Authority Final Distribution Board (see definitions) Horse-Power (= 0.746 kW)

A1

ADWEA ASTA BS BS EN BSI CB CCP CEC CPC d.c. ECC EEB EEBS E/F ELCB ELP ELV EN ELPS ESMA FDB HP

The Electricity Wiring Regulations 2007

105

A1.
HRC HV IEC In kA KEMA kV LV m MCB MCCB MDB MEC MET MICC ms NSAI C PELV PVC r.m.s RCBO RCCB RCD RLV

continued...
High Rupture Capacity (fuse) High Voltage (see definitions) International Electrotechnical Commission Nominal current rating or current setting of a Protective Device kilo-Amps Testing Laboratory of Netherlands kilo-Volts Low Voltage (see definitions) metres Miniature Circuit-Breaker Moulded Case Circuit-Breaker Main Distribution Board (see definitions) Main Earth Conductor (see definitions) Main Earth Terminal (see definitions) Mineral Insulated Copper-Clad (type of cable) milli-seconds National Standards Authority of Ireland degrees Celsius Protective Extra-Low Voltage (see definitions) Poly-vinyl Chloride (insulation for LV cables) root-mean-square (value of voltage, current etc) Residual Current Breaker (With) Overcurrent Protection Residual Current Circuit-Breaker Residual Current Device (see definitions) Reduced Low Voltage (see definitions)

A1

106

The Electricity Wiring Regulations 2007

A1.

continued...

Table of content HERE s seconds

A1

S SDB SELV TN-S TN-S-TT TT Uo WED Ze Zs Zr1+r2

cross-sectional area (of conductors, mm) Sub Distribution Board (see definitions) Separated Extra-Low Voltage (see definitions) a Distribution Company earthed Installation (see definitions) a Distribution Company earthed Installation with additional Customer Earths (see definitions) a Customer Earthed Installation (see definitions) nominal phase voltage Water and Electricity Department (Abu Dhabi) External Earth Fault Loop Impedance Total Earth Fault Loop Impedance (see definitions) Internal Loop Impedance (R1 = resistance of circuit conductor, R2 = resistance of earth conductor)

The Electricity Wiring Regulations 2007

107

A2.
Books: (1)

Recomended books and references

A2

Requirements for Electrical Installations (BS 7671: 2001) The Institution of Engineering and Technology (formerly the Institution of Electrical Engineers) IEE Guidance Note 8 - Earthing & Bonding The Institution of Engineering and Technology IEE Guidance Note 7 Special Locations The Institution of Engineering and Technology IEE Guidance Note 5 Protection Against Electric Shock The Institution of Engineering and Technology Exam Success The IEE Wiring Regulations 2381 The Institution of Engineering and Technology, City & Guilds The IEE On-site Guide to BS 7671:2001 The Institution of Engineering and Technology The Electricians Guide 8th Edition John Whitfield, EPA Press Testing Electrical Installations A Hinsley, Castleknight Publications Advanced Testing Techniques A Hinsley, Castleknight Publications Inspection, Testing and Certification The Electrical Safety Council (NICEIC) Snags and Solutions Part 1 Earthing & Bonding The National Inspection Council for Electrical Installation Contracting (NICEIC) Snags and Solutions Part 2 Wiring Systems The National Inspection Council for Electrical Installation Contracting (NICEIC)

(2)

(3) (4) (5)

(6) (7) (8) (9) (10) (11)

(l2)

108

The Electricity Wiring Regulations 2007

A2.
(13)

Continued...
Domestic Electrical Installation Guide The National Inspection Council for Electrical Installation Contracting (NICEIC) Regulations:

A2

(14) (15) (16) (17) (18) (19)

ADWEA Wiring Rules and Regulations for LV Installations 2003, Abu Dhabi Water and Electricity Authority Regulations for Electrical Installation Works 1980 Water and Electricity Department (WED) of Abu Dhabi The Earth Leakage Protection Regulations 2001 The Regulation and Supervision Bureau Regulations for Electrical Installations 1997 Dubai Electricity Authority Rules and Regulations of Electrical Connections Sharjah Electricity and Water Authority The Australian & New Zealand Wiring Rules AS/NZS 3000:2000 Standards Australia/Standards New Zealand The Electricity Safety (Installations) Regulations 1999 Government of Victoria (Australia) The Electricity Safety (Network Assets) Regulations 1999 Government of Victoria (Australia) Industry Standard for Electrical Installations on Construction Sites Office of the Chief Electrical Inspector, Victoria (Australia) New Zealand Code of Practice for Homeowner / Occupiers Electrical Wiring Work, Energy Safety Service, Wellington, New Zealand Code of Practice for Safe Electrical Work Office of the Chief Electrical Inspector, Victoria (Australia)

(20) (21) (22)

(23)

(24)

The Electricity Wiring Regulations 2007

109

A2.
(25)

Continued...
The Electricity Safety, Quality and Continuity Regulations (2002) Her Majestys Stationary Office, UK The Plugs and Sockets etc. (Safety) Regulations 1994 Her Majestys Stationary Office, UK The Low Voltage Electrical Equipment (Safety) Regulations 1989 (Adoption of the Low Voltage Directive No. 73/23/EEC) Her Majestys Stationary Office, UK The Electrical Equipment (Safety) Regulations 1994 Her Majestys Stationary Office, UK Reference Papers:

A2

(26) (27)

(28)

(29) (30) (31) (32) (33)

Cahier Technique no. 172 Earthing Systems in LV B Lacroix, R Calvas, Schneider Electric Cahier Technique no. 173 Earthing Systems Worldwide B Lacroix, R Calvas, Schneider Electric Neutral Earthing in LV Networks A Robert, J Hoeffelman, CIRED Conference June 2001 Plugs and Sockets Around the World Conrad H. McGregor, World Standards The Distribution Code Annex 1 E/R 1 Limits for Harmonics in the Electricity Supply System Approved by the Regulation and Supervision Bureau The Distribution Code Annex 1 E/R 7 Limits for Voltage
Fluctuations in the Electricity Supply System

(34)

Approved by the Regulation and Supervision Bureau (35) The Distribution Code Annex 1 E/R 10 Limits for Voltage Unbalance in the Electricity Supply System Approved by the Regulation and Supervision Bureau Designing for Low Resistance Grounding Lightning Eliminators & Consultants, Inc

(36)

110

The Electricity Wiring Regulations 2007

A3.

Reference standards

Components Cables Power & lighting (70C PVC, thermoplastic) Power and lighting (90C rubber, thermosetting) Mineral insulated (copper-clad) Flexible cables & cords (domestic) Flexible cables & cords (industrial) Flexible cables (high temperature) Armoured cables (70C PVC, thermoplastic) Low smoke (90C rubber, thermosetting) Armoured cables (90C rubber, thermosetting) Switchgear and control wiring Flexible cables for lifts Cable glands, crimp connectors Conduits & trunking Steel PVC Flexible Steel Cable tray Trunking Electrical accessories General Ceiling roses Cooker Control Units

BS

IEC

A3

6004 6007, 7889 6207 6500 7919 6141 6346 7486, 7211, 6724, 7629 5467 6231 6977 6121, 4579

502

702 227 245

4568, 60423*, 50086*, 31 4607 731 61537* 4678

423, 614

5733 67 4177

The Electricity Wiring Regulations 2007

111

A3.

Continued...

A3

Components Accessories continued... Household Appliances Plugs & Socket-outlets (domestic) Plugs & Socket-outlets (industrial) Switches (domestic) Lighting Emergency lighting Signs and discharge lighting Isolating (safety) transformers LV switchgear & assemblies General Contactors & motor starters Circuit-Breakers (MCB, MCCB) Circuit-Breakers (RCD, RCBO) Fuses Busbar trunking systems General Fire / combustibility test Degrees of protection & ingress Assemblies for construction Sites Hazardous areas Lightning protection Earthing Wiring diagram symbols Identification and marking of the man-machine interface

BS

IEC

3456, 60355* 546, 196, 1363, 4573 4343, 60309* 3676, 60669* 4533, 60598* 5266 559 3535, 60742*, 61558*

60439*, 5486 60947* 60898*, 3871 4293, 61008*, 61009* 88, 1361, 60269* 60439-2

439 947 898 755

439-2

476, 6458 60529* 4363 5345, 60079*, 50014*, 5501 6651 7430, 951, 4444 60617* 60446* 364-5-54 529 364-7-704

112

The Electricity Wiring Regulations 2007

A3.
Note: 1: Note: 2:

Continued...
British Standards marked with an asterix * are also issued as European Standards under the same number (labelled as BS EN). For compliance requirements under the Regulations see clause 3.1.2 and 3.1.4.

A3

British Standards are issued by the British Standards Institute (BSI), a UK National Standards body. The UK Wiring Regulations (BS 7671) are published jointly by BSI and the IET (formerly known as the IEE). The BSI represents the UK in international standards work through the British Electrotechnical Committee (BEC) which is a member of the International Electrotechnical Commission (IEC) and also a member of the European Committee for Electrotechnical Standardisation (CENELEC). There are 24 member countries of CENLEC (formed in 1973) whose role is to prepare standards for the European market. CENELEC issues EN standards which are adopted by the member countries, and HD standards which are adopted in their general technical content by member countries. The IEC (formed in 1906) has 48 member countries and IEC standards may be adopted voluntarily by any country.

The Electricity Wiring Regulations 2007

113

A4(a) List of regulations and clauses which do not apply to existing installations
The Electricity Wiring Regulations are effective from 1 January 2008. For any installations which were constructed prior to this date, the following Regulations and clauses either: (a) (b) do not apply; or shall apply by 1 January 2010, or the date of the next inspection or re-certification, whichever is the earlier.

A4(a)

Clause or Regulation Clause 3.1.4

Reason Installation components to meet international standards

Application Does not apply retrospectively (see also Clause 3.3.3 referring to repairs to existing installations) ELP is a requirement from 1 January 2008 for all Final Circuits where Appliances may be used by persons (see note 1); the requirement for ELP or EEB at the main Supply Intake shall be met by 1 January 2010 Shall be met by 1st January 2010, or at the date of the next inspection, whichever is the earlier Does not apply retrospectively.

Clause 3.5.6, Clause 5.3.4, Clause 5.3.5,

Requirement for Earth Leakage Protection (ELP) and/or Earthed Equipotential Bonding (EEB)

Regulation 3.6, Clause 5.4.8, Clause 6.5.3

Requirement for labelling of parts of the Installation

Clause 4.2.9 Clause 7.1.1

Emergency lighting in Supply Intake rooms

Does not apply Prohibition of BS 546 plugs and socket-outlets retrospectively but it is recommended to in domestic premised replace BS 546 socketoutlets with BS 1363 type

114

The Electricity Wiring Regulations 2007

A4(a) Continued ...

Clause / Regulation Clause 7.8.6

Reason / Comment Final Distribution Boards to have split busbars to allow for minimum of 2 RCDs

Application Does not apply retrospectively if a single RCD of residual operating current 100 mA is fitted to cover the whole DB. Does not apply retrospectively where Final Circuits are covered by 100 mA RCD protection

A4(a)

Clause 9.3.2(a)

30 mA Earth Leakage Protection for all bathroom Circuits.

Note 1:

The requirement for Earth Leakage Protection was introduced in Abu Dhabi Emirate in 2001 by implementation of the Earth Leakage Protection Regulations (issued by the Bureau). The Electricity Wiring Regulations reiterate this same requirement and replace the ELP Regulations.

The Electricity Wiring Regulations 2007

115

A4(b) Relevant extracts of Law No (2) of 1998


Relevant Extracts of Law No (2) of 1998 Concerning the Regulation of the Water, Wastewater and Electricity Sector (as amended by Law No (19) of 2007) Article (54) - General Duties The Regulation and Supervision Bureau shall have the duty to exercise its functions under this Law in the manner which it considers best calculated to (1) (2) (3) (6) ensure the security of the supply of water and electricity in the Emirate; ensure the connection and supply of water and electricity to all consumers on reasonable demand; ensure the availability of health and safety guidance in relation to water and electricity supply to the public; have special regard to the interestes of those persons whose lives may be endangered by the lack of potable water and/or electricity and others with special needs in connection with the cost and method of supply of water and electricity and the use of appliances and fitting;

A4(b)

Article (55) - Functions of the Regulation and Supervision Bureau (3) the establishment, maintenance, review and amendment as appropriate of technical and performance standards for the water and electricity sector and the monitoring and enforcement of compliance with such technical standards;

Article (60) - Inspectors (1) The Regulation and Supervision Bureau may appoint qualified persons whose duties shall include duties to ... (c) inspect and test, where required, such plant and equipment at the consumer's premises;

116

The Electricity Wiring Regulations 2007

A4(b) Continued...
Article (62) - Powers to make regulation The Regulation and Supervision Bureau may, in consultation with the Authority, make such regulations as it sees fit for the purposes set out in Articles (63) and (68) of this Law1. Article (63) - Supply regulations Regulations made pursuant to Article (62) of this Law may be made for the following purposes, namely to (1) (2) (3) (8) (9) secure regular and efficient supplies of water and electricity; protect the general public from danger related to electrical and water works and installations; eliminate or reduce the risk of personal injury; ensure water and electricity fittings installed and used by persons to whom water and electricity are to be supplied are safe; and promote the conservation of water and the efficient use of water and electricity.

A4(b)

Article (65) - Contents of supply regulations - specific Regulations made under Article (62) of this Law may (1) (2) (3) (4) prohibit transmission or supply in specified circumstances; require notification of accidents, failures of supply and/or transmission or distribution facilities; require plans, maps etc to be kept and made available for inspection and copying; relieve the Abu Dhabi Water and Electricity Company and classes of licensed operators specified in the regulations from obligations to supply water and electricity in specified circumstances;

Article 68 relates to Street Works and Access Regulations

The Electricity Wiring Regulations 2007

117

A4(b) Continued...
(5) require compliance with notices served by the Regulation and Supervision Bureau which are intended to prevent or end a breach of regulations made under Chapter Three of Part Four of this Law; or eliminate/reduce risk of personal injury or property damage or interference with property; (6) (7) (8) provide for deemed compliance with technical standards and requirements; provide for exemptions from the requirements of regulations made under Chapter Three of Part Four of this Law; restrict or require the use of certain, products, substances or processes or forbid unapproved substances, products and processes; require substances, products and processes to comply with standards or other requirements established by the regulations; provide for certain persons/organisations to give approvals required by the regulations and for such approvals to be subject to conditions or modification and revocation; require the provision of information to prescribed persons; require the publication of water quality information; forbid the use or installation of fittings which have not been approved; require electricity or water fittings to be of a prescribed size, nature, strength or workmanship; impose requirements as to installation, arrangement, connection, testing, disconnection, alteration and repair; impose requirements regarding earthing of installations, electrical voltage and frequency; and electrical

A4(b)

(9) (10)

(11) (12) (13) (14) (15) (16)

118

The Electricity Wiring Regulations 2007

A4(b) Continued...
(17) enable the Regulation and Supervision Bureau to authorise any departures from the regulations as may be required and to make those departures subject to conditions.

A4(b)

Article (66) - Failure to comply with regulations


[Note: amended by Article (18) of Law No (19) of 2007, see overleaf.]

Article (67) - Regulations disputes The court with the appropriate jurisdiction shall hear disputes relating to regulations made under Article (62) of this Law. Article (106) - Duty to enforce by final order Subject to Article (107) of this Law, where the Regulation and Supervision Bureau is satisfied that licensed operator is contravening or is likely to contravene any condition of its licence, the Regulation and Supervision Bureau shall as soon as practicable by a final order make such provision as appears to the Regulation and Supervision Bureau to be requisite so as to secure compliance with that condition. Article (114) - Power to fine A final order may include a requirement on the licence holder to pay a fine of such amount, being not less than Dirhams 50,000, as the Regulation and Supervision Bureau determines to be appropriate.

The Electricity Wiring Regulations 2007

119

A4(b) Continued...
The following Articles of Law No (19) of 2007 Concerning the amendment of some provisions of Law No (2) of 1998 Concerning the Regulation of the Water and Electricity Sector in the Emirate of Abu Dhabi2 Article 12 Article (54) of Law No. (2) of 1998 is replaced by the following statement: The Bureau, when performing its functions and duties under this Law, is committed to execute in its best ways, functions that achieve the following: (1) (2) (3) Ensure the security of supply of water, wastewater and electricity services in the Emirate. Supply customers with water and electricity and connecting them to sewerage grids. Provision of special regulations of health and safety related to supply of water, electricity and wastewater services to the general public. Publish information related to the performance level of licensed operators. Take account of local and international standards for the environment which can have an effect on the water, wastewater and electricity sector. In addition to, coordination with concerned parties of environment in the Emirate and the Country, for the benefit of the Consumer and the Sector. Take account of people with special needs who can be threatened by lack of potable water or unavailability of electricity, whether it was a cost or supply method of water and electricity, or through use of devices and installations. Promote competition in the water, wastewater and electricity sector.

A4(b)

(4) (5)

(6)

(7)

unofficial translation

120

The Electricity Wiring Regulations 2007

A4(b) Continued...
(8) (9) Operation and development of a safe, efficient and economic sector for the water, wastewater, and electricity in the Emirate. Protect the interest of consumers of water and electricity as to terms and conditions and price of supply (whether consumption is domestic, commercial or industrial). Protect the interests of users of sewerage services in the Emirate.

A4(b)

(10)

Article (13) Paragraphs (1), (4), (6), (7) and (8) of Article (55) of Law No. (2) of 1998, shall be replaced by the following paragraphs: (1) (4) Revision of Provision Plans of water, wastewater and electricity in the Emirate. Establishment, maintenance, revision and supervision of safety standards for the water, electricity and sewerage services supervision of compliance with such safety standards. Regulation of tariff applied on water and electricity customers and consumers of sewerage services, and the methodology of applying and collecting such tariff. Approval of conditions and special statements concerning the supply of water, electricity and sewerage services to domestic customers and supervision on compliance with such condition and statements and amending them. Approval of modifications to water and electricity transmission and distribution codes, and operating codes of providing sewerage services.

(6)

(7)

(8)

Article (15) "In consultation with the Authority" in Article (62) of Law No. (2) of 1998, is replaced by "in consultation with who sees appropriate".

The Electricity Wiring Regulations 2007

121

A4(b) Continued...
Article (16) Paragraphs (1), and (2) of Article (63) of Law No. (2) of 1998, is replaced by the following two paragraphs: (1) (2) Ensure supply of water and electricity and provision of regular and efficient sewerage services. Protect the general public from danger resulted from electricity, water and wastewater works and installations.

A4(b)

A new paragraph given number (10) shall be added to this article as follows: (10) Ensure compliance of sewerage connections with standards determined by the Regulation and Supervision Bureau.

Article (17) Provisions of Paragraphs (2), and (4), and (14) of Article (65) of Law No. (2) of 1998, is replaced by the following paragraphs: (2) Notification of any accidents, failures of supply or transport or distribution of water and electricity when providing sewerage services. Relieving ADWEC, in certain circumstances, or any licensed body from obligations to supply water, electricity and sewerage services. Require electricity, water and wastewater installations to be of a prescribed size, nature, strength and quality.

(4)

(14)

Article (18) Article (66) of Law No. (2) of 1998 is replaced by the following: "Failure of any person to comply with regulations stated under this Article (62) of this Law shall be punished with a fine of not less than AED 250,000. In case the same failure is repeated by such person, the fine is doubled".

122

The Electricity Wiring Regulations 2007

A5(a) Distribution company earthed system (TN-S)

A5(a)
[ see Regulation 6.2 ]

Distribution Company Transformer

Distribution Network Conductors

L1 L2 L3 N E
Earth fault current through Distribution Company cable Earth sheath or armour of Distribution Company Cable is connected to Customers Installation Customers Main Distribution Board Main Earth Terminal Earth fault in Appliance

A
Transformer Neutral Point Earth

Earth fault current

The Electricity Wiring Regulations 2007

123

A5(b) Customer earthed system (TT)


[ see Regulation 6.2 ]

A5(b)

Distribution Company Transformer

Distribution Network Conductors

L1 L2 L3 N E

Transformer Neutral Point Earth Earth sheath or armour of Distribution Company Cable not connected to Customers Installation

A
Earth fault current through ground / soil Customers Main Distribution Board

A
Main Earth Terminal Customers Earth Electrode

Earth fault current

Earth fault in Appliance

Insulated cable gland

124

The Electricity Wiring Regulations 2007

A5(c) Distribution company earthed system with additional earth (TN-S-TT)


[ see Regulation 6.2 ]

A5(c)
Distribution Company Transformer Distribution Network Conductors

L1 L2 L3 N E
Earth fault current Transformer Neutral Point Earth Earth sheath or armour of Distribution Company Cable is connected to Customers Installation

A
Earth fault current shared between Customer Earth Electrode and Distribution Company Earth Customers Main Distribution Board

A
Main Earth Terminal Customers Earth Electrode

Earth fault current

Earth fault in Appliance

The Electricity Wiring Regulations 2007

125

A5(d) Earth electrode pit and standard labels

A5(d)
Main Earth Conductor 300 x 300mm Inspection cover

SAFETY EARTH CONNECTION DO NOT REMOVE


Standard safety label for Main Earth Connections

SAFETY EARTH BONDING DO NOT REMOVE


Standard safety label for main and supplementary bonding connections

[ see clause 6.4.3, 6.5.6, 5.5.11 ]

126

The Electricity Wiring Regulations 2007

A5(e) Main earth terminal (MET) at main distribution board (MDB)

A5(e)
Circuit Earth Conductors for sub-main circuits CEC To SDB1

To SDB2

A
MET

Main Circuit Breaker

Neutral Bar

MEC to Customer Earth Electrode

Earth connection to metal door

Earth conductor labels at MET

DB2 MAIN EARTH CONDUCTOR DB1 MAIN EARTH CONDUCTOR

Test Link
CUSTOMER EARTH ELECTRODE DISTRIBUTION COMPANY EARTH

B
Distribution Company Earth

Note: Illustration shows Distribution Company Earthed System with additional Customer Earth (TN-S-TT) [ see Regulation 6.3 and 6.2 ]

The Electricity Wiring Regulations 2007

127

A5(f) Main earth conductors (MEC) and circuit earth conductors (CEC)

A5(f)

CEC to switches and Accessories

Final Distribution Board Earth Bar

CEC to xed Appliance

CEC in metal or plastic conduit MEC

Main Distribution Board Main Earth Terminal MEC CEC in appliance exible cord

Functional Earth (see clause 6.9.2)

Main Earth Conductor to Earth Electrode

Distribution Company Earth

Note: Common terminology (outside these Regulations) includes CPC (Circuit Protective Conductor) and ECC (Earth Continuity Conductor ) in place of CEC illustrated above. [ see Regulation 6.2 ]

128

The Electricity Wiring Regulations 2007

A5(g) Components of earth fault loop impedance


[ see Regulation 6.7 ]
Distribution Network Conductors Distribution Company Transformer
9 10

A5(g)

L1 L2 L3 N E

11

Transformer Neutral Point Earth

X
7 1

Supply Intake Circuit Breaker

L E

MET Main Earth Terminal

Earth fault in Appliance

1 Internal earth loop impedance 2 3 4 5 6 7 Source earth loop impedance, Ze 8 9

Impedance of Circuit phase conductor Resistance of fault Impedance of Circuit Earth Conductor (CEC) Impedance of Local Earth Electrode Impedance of fault path through ground Impedance of transformer neutral earth point Impedance of supply cable earth conductor / armouring Impedance of network cable earth conductor / armouring Distribution Company transformer winding

10 Live conductor of distribution network cable 11 Live conductor of Supply cable

The Electricity Wiring Regulations 2007

129

A5(h) Earth fault loop impendance values required for MCBs (at 230 V)

A5(h)
Device rating (A)

Maximum earth fault loop impedance (Ohms) MCB type1 MCB type 2 MCB type 3 and type C 4.80 4.00 2.40 1.60 1.50 1.20 0.96 0.80 0.75 0.60 MCB type B MCB type D

5 6 10 15 16 20 25 30 32 40

12.00 10.00 6.00 4.00 3.75 3.00 2.40 2.00 1.88 1.5

6.86 5.71 3.43 2.29 2.14 1.71 1.37 1.14 1.07 0.86

8.00 4.80 3.00 2.40 1.92 1.50 1.20

2.00 1.20 0.75 0.60 0.48 0.38 0.30

[from table 41B2 of BS 7671] Note 1: The above values are given for conductor temperatures of 70C. As measurements are normally taken at room temperature the measured values must be approximately 20% less than tabulated above. The above values are used as an alternative to calculating the disconnection time for each specific situation. i.e. MCBs will operate in the instantaneous mode if the Earth Fault Loop Impedance value is kept below the above levels. For EFL Impedance values higher than shown above it is still possible to comply with the requirement of 0.4 s disconnection for Circuits accessible to persons, and 5 s for other Circuits (clause 5.5.2) if a check is made against the manufacturers time-current performance chart. Circuit-breakers types 1, 2 and 3 to BS 3871 were known as Miniature Circuit-Breakers (MCBs). Since the 1990s these have been superseded by devices to BS EN 60898, i.e. Types B, C and D, which are now simply called Circuit-Breakers (CBs). The term MCB is commonly used to apply to both types of devices, and is used in this context in these Regulations.

Note 2:

Note 3:

130

The Electricity Wiring Regulations 2007

A5(i)

Resistance per metre of copper conductors for calculation of R1+R2

Conductor cross-sectional area (mm) 1.0 1.5 2.5 4.0 6.0 10.0 16.0 25.0

Resistance per metre (milli-ohms) 18.1 12.1 7.41 4.61 3.08 1.83 1.15 0.73
[above values at 20C]

A5(i)

Note:

To allow for the increase in resistance with increased temperature under fault conditions these values must be multiplied by 1.2 for PVC insulated cables.

The Electricity Wiring Regulations 2007

131

A5(j)

Sizing of earth conductors and equiptential bonding conductors

A5(j)

Cross sectional area of phase and neutral conductors (S) (mm2)

Minimum crosssectional area of earth conductors [see note 1] (mm2) S (not less than 2.5 see note 2) 16

Minimum crosssectional area of equipotential bonding conductors (mm2) S/2 (not less than 4 or 6, see note 3) 10

S <= 16

16 < S <= 35

S > 35

S/2

S/4 (but not exceeding 25)


[from table 54G of BS 7671]

Note 1:

For Main Earth Conductors between Earth Electrodes and the Main Earth Terminal of an Installation, S should be taken as the cross-sectional area of the conductors of the incoming supply cable. For other Earth Conductors S should be taken as the cross-sectional area of the circuit phase conductors. Earth Conductors should always be insulated and a cross-sectional area of less than 2.5 mm2 should not be used unless they are an integral part of a sheathed cable (e.g. an Appliance flexible cord). Precautions should be taken against corrosion and damage (e.g. installed in conduit or ducts). Main Equipotential Bonding Conductors should be sized according to the live conductors of the incoming supply, but should not be less than 6 mm2. Supplementary Bonding Conductors should be sized according to the live conductors of the circuit to which they are connected but should not be less than 4 mm2.

Note 2:

Note 3:

132

The Electricity Wiring Regulations 2007

A5(j)
Note 4:

Continued...
As an alternative to using the above selection table, the sizing of Earth Conductors and Equipotential Bonding Conductors may be calculated using the adiabatic equation provided in the IEE Wiring Regulations BS7671:2001 paragraph 543-01-03.This normally allows smaller sizes of Earth Conductor to be used. For example: 4.0 mm2 earth for 6 mm2 circuit conductor 2.5 mm2 earth for 4 mm2 circuit conductor 1.5 mm2 earth for 2.5 mm2 circuit conductor

A5(j)

The Electricity Wiring Regulations 2007

133

A5(k) Minimum number of earth electrodes


The number of Earth Electrodes required at a Premises will be determined primarily by the value of Earth Resistance that can be achieved from each. However, the minimum number in any case shall be as shown below:
Main incoming circuitbreaker rating (Amps) Minimum number of earth electrodes 1 1 1 1 2 2 2 2 2 2 2 Minimum size of main earth conductor (mm2)

A5(k)

60/100 200 300 400 500 600 800 1000 1600 2000 2500
Note:

16 50 50 70 70 70 70 70 70 150 150

Standard earth electrode diameters are 9 mm, 12.5 mm or 15 mm for copper-clad steel, or 16 mm for stainless steel. Standard lengths are 1.2 m or 1.5 m (see also BS 7430).

134

The Electricity Wiring Regulations 2007

A5(l)

Mandatory connections to earth conductors

The following items must be connected to the Circuit Earth Conductor, which should be provided separately for each Final Circuit, insulated with green/yellow PVC sheath, be of the appropriate size (Appendix A5(j)) and be installed in the same conduits or routes as the phase and neutral conductors.

A5(l)

Items where connections must be made to the Circuit Earth Conductor Distribution Boards: exposed-metallic-parts (frame, door etc) at start and end of runs, at pulling points and inspection boxes exposed-metallic-parts (frame, door etc) exposed-metallic-parts exposed-metallic-parts (mounting boxes, cover plates) exposed-metallic-parts (mounting boxes, cover plates) exposed-metallic-parts (metal casing etc)

Metal conduits and trunking: Switchgear: Luminaires: Switches: Socket-outlets: Fixed appliances and machinery:

Note 1:

The earthing of cover plates should not rely solely on the connection of fixing screws to an earthed mounting box (due to the possibility of poor connections, corrosion etc); a short flexible Earth Conductor should be connected between the mounting box and the plate. See Guidance Note G7(d). The circuit Earth Conductor should be terminated in the connection box for a Luminaire even if it is plastic (to provide for future use). See Guidance Note G7(d).

Note 2:

The Electricity Wiring Regulations 2007

135

A5(m)

Residual operating current settings for RCDs and ELP devices

A5(m)

Equipment 13 A switched-socket outlets Water heaters Kitchen fixed Appliances (e.g. washing machine) Domestic water pumps Swimming pool pumps, or jacuzzi Underwater lighting General fixed lighting Floodlighting Window or split type air conditioning Air handling, a/c fan coils etc Central or package a/c units Irrigation pump Electric Cooker (not provided with a 13 A socket-outlet) Industrial machines etc Elevators, escalators, lifts Neon signs School areas (e.g. laboratory for children) LV main circuit breakers or switchboards

Residual operating current settings (mA) 30 30 30 30 30 SELV only 100 100 - 300 100 100 100 - 300 100 100 100 - 300 300 - 500 300 10 300 - 500

Note:

Where two values are indicated the higher value is allowed only where the equipment is not normally accessible to any person.

136

The Electricity Wiring Regulations 2007

A5(m)

Continued...

The table opposite shows the required residual operating current values for RCDs and other Earth Leakage Protection devices. These are intended to provide for electric shock protection (Direct and Indirect Contact), particularly in high-risk areas, as well as protection against high resistance earth faults which may not operate overcurrent devices and pose a risk of overheating or fire, see Regulation 5.4. All Final Circuits where Appliances may be used by any person must be provided with Earth Leakage Protection (clause 5.3.5 ) and backup Earth Leakage Protection must be provide at the main Supply intake for Installations classed as an Earth Leakage Protected System, see Regulation 5.4.

A5(m)

The Electricity Wiring Regulations 2007

137

A6(a) Time-current characteristic of MCBs as multiple of rated current

A6(a)

2 HRS 1 HR

1,000

100

OPERATING TIME IN SECONDS

10

1.0

0.1

Type B

Type C

Type D

0.01 0.001 1 3 5 10 20 100 1,000

SHORT CIRCUIT CURRENT AS A MULTIPLE OF RATED CURRENT

Reproduced with permission of Crabtree / Electrium Ltd.

138

The Electricity Wiring Regulations 2007

A6(b) Time-current characteristic of Type B MCBs


100 A 125 A 16 A 20 A 25 A 32 A 40 A 50 A 80 A 63 A 10 A 6A

10 000

Time / current characteristics for Type B circuit-breakers to BS EN 60898 and RCBOs to BS EN 61009 Current for time 0.1 sec to 5 secs

1000

100

TIME, SECONDS

10

Rating 6A 10 A 16 A 20 A 25 A 32 A 40 A 50 A 63 A 80 A 100 A 125 A

Current 30 A 50 A 80 A 100 A 125 A 160 A 200 A 250 A 315 A 400 A 500 A 625 A

The Electricity Wiring Regulations 2007

0.1

For prospective fault currents in excess of those providing instantaneous operation refer to the manufacturers let-through energy data.
10 100 1 000 10 000

00.1

PROSPECTIVE CURRENT, r.m.s. AMPERES [ from g. 3.4 of BS 7671 ]

139

A6(b)

A6(c)

140
100 A 125 A 16 A 20 A 25 A 32 A 40 A 50 A 80 A 63 A 10 A 6A

A6(c) Time-current characteristic of Type C MCBs

10 000

Time / current characteristics for Type C circuit-breakers to BS EN 60898 and RCBOs to BS EN 61009 Current for time 0.1 sec to 5 secs

1000

100

TIME, SECONDS

10

Rating 6A 10 A 16 A 20 A 25 A 32 A 40 A 50 A 63 A 80 A 100 A 125 A

Current 60 A 100 A 160 A 200 A 250 A 320 A 400 A 500 A 630 A 800 A 1000 A 1250 A

The Electricity Wiring Regulations 2007

0.1

For prospective fault currents in excess of those providing instantaneous operation refer to the manufacturers let-through energy data.
10 100 1 000 10 000

00.1

PROSPECTIVE CURRENT, r.m.s. AMPERES [ from g. 3.5 of BS 7671 ]

A6(d) Time-current characteristic of Type D MCBs


100 A 125 A 16 A 20 A 25 A 32 A 40 A 50 A 80 A 63 A 10 A

6A

10 000

Time / current characteristics for Type D circuit-breakers to BS EN 60898 and RCBOs to BS EN 61009 Current for time 0.1 sec to 5 secs

1000

100

TIME, SECONDS

10

Rating 6A 10 A 16 A 20 A 25 A 32 A 40 A 50 A 63 A 80 A 100 A 125 A

Current 120 A 200 A 320 A 400 A 500 A 640 A 800 A 1000 A 1260 A 1600 A 2000 A 2500 A

The Electricity Wiring Regulations 2007

0.1

For prospective fault currents in excess of those providing instantaneous operation refer to the manufacturers let-through energy data.
10 100 1 000 10 000

00.1

PROSPECTIVE CURRENT, r.m.s. AMPERES [ from g. 3.6 of BS 7671 ]

141

A6(d)

A6(e) Typical energy let-through characteristics of MCBs

A6(e)

105

I2t energy let-through in A2s (50Hz sine wave) one complete 1/2 cycle

50&63A 40A 32A 20A 16A

2.5mm2

10A 1.5mm2

TOTAL LET-THROUGH ENERGY (I2t)

6A 1.0mm2 104

103 0.1 1.0 10 16 100.0

PROSPECTIVE FAULT CURRENT (kA)


Reproduced with permission of Crabtree / Electrium Ltd.

142

The Electricity Wiring Regulations 2007

CABLE CONDUCTOR SIZES

A6(f) MCBs selection criteria


Operating characteristics of MCB types and the required earth fault loop impedance values are given in Appendix A6(a) to A6(d) and Appendix A5(h). MCBs for common cable sizes and Circuits are shown in the following table:

A6(f)

MCB nominal rating Amps

Cable size mm2

Cable rating at 30C, PVC A, (kW) 17.5 (3.4) 24.0 (4.7) 24.0 (4.7) 32.0 (6.3) 41.0 (8.0) 41.0 (8.0) 57.0 (11.1)

Cable rating at 40C, PVC A, (kW) 15.2 (3.0) 20.9 (4.1) 20.9 (4.1) 27.8 (5.4) 35.7 (7.0) 35.7 (7.0) 49.6 (9.7)

Typical circuit application

6 10 16

1.5 2.5 2.5

Lighting (light load) Lighting (heavy load) Radial Circuit to socket-outlets Radial Circuit to fixed appliance (e.g. a/c unit) Ring Circuit to socket-outlets Radial Circuit to large Appliance (e.g. cooker) Radial Circuit to machinery (e.g. chiller unit)

20

4.0

32

6.0 6.0

32

40

10.0

Note:

Cable rating should be at least 20% greater than MCB nominal rating to afford overload protection for the cable. Cable ratings are taken from Appendix A7(a) with temperature correction factors applied from Appendix A7(g) and assuming 2 cables cores installed in conduit. kW ratings assume 0.85 power factor at 230V.

The Electricity Wiring Regulations 2007

143

A6(f)

Continued...
Circuit-breakers types 1, 2 and 3 to BS 3871 were previously known as Miniature Circuit-Breakers (MCBs). Since the 1990s these have been superseded by devices to BS EN 60898, i.e. Types B, C and D, which in modern terminology are simply called Circuit-Breakers (CBs). However, the term MCB is commonly used to apply to both types of devices, and is used in this context in these Regulations. The difference between Type B, C or D devices is their ability to handle surge currents without tripping. These are, typically, inrush currents associated with discharge lighting, induction motors, air conditioning units, etc. The classification of Types B, C or D is based on the fault current rating at which magnetic operation occurs to provide short time protection (typically less than 100 ms) against short-circuits. See Appendix A6(a). Type B devices are designed to trip at fault currents of 3-5 times rated current (In). For example a 10 A device will trip at 30-50 A Type C devices are designed to trip at 5-10 times In Type D devices are designed to trip at 10-20 times In

A6(f)

Type B devices are generally suitable for domestic applications. Type C devices are the normal choice for commercial and industrial applications where large groups of fluorescent lighting, motors etc, are used. Type D devices have more limited applications, where high inrush currents may be expected. For example, large battery systems, motors, transformers, etc. Sometimes failure of tungsten filament lamps can trip Type B circuitbreakers in domestic and retail environments. This is caused by high arcing currents occurring at the time of failure and is generally associated with inferior quality lamps. A Type C device may be substituted for a Type B device where unwanted tripping persists, especially in commercial applications. A change from Type C to Type D devices should only be taken after careful consideration of the installation conditions, in particular the operating times required by Regulation 5.5. (Selection criteria for type B, C, D devices referenced from www.voltimum.co.uk)

144

The Electricity Wiring Regulations 2007

A6(g)

Internal construction of MCB

A6(g)

Arc runner

25mm2 max tunnel terminal

15 plate arc chamber

Moving contact

Arc runner

Latch mechanism

Thermo-metal element

Fixed contact

Calibration mechanism Operating handle

DIN rail mounting

Coil assembly

25mm2 max Jaw terminal

Trip bar

Reproduced with permission of Wylex / Electrium.

The Electricity Wiring Regulations 2007

145

A7(a)

Current ratings for PVC single core cables (non-armoured)

A7(a)

Standard cable ratings and Voltage drop for single core, PVC (70C thermoplastic), non-armoured, stranded copper conductor (BS6004 and BS6346), with or without sheath, installed in buried or surface conduit or trunking.

Cross sectional area (mm)

In conduit in thermal insulation (A) 2 cables 11 14.5 19.5 26 34 46 61 80 99 119 151 3 or 4 cables 10.5 13.5 18 24 31 42 56 73 89 108 136

In conduit on wall or in concrete (A) 2 cables 13.5 17.5 24 32 41 57 76 101 125 151 192 3 or 4 cables 12 15.5 21 28 36 50 68 89 110 134 171

Voltage drop (mV/A/m)

2 cables 44 29 18 11 7.3 4.4 2.8 -

3 or 4 cables 38 25 15 9.5 6.4 3.8 2.4 -

1.0 1.5 2.5 4.0 6.0 10 16 25 35 50 70

At 30C ambient temperature

[see Appendix A7(g) for grouping factors]

Note 1: Note 2:

Data from table 4D1A and 4D1B of BS 7671. For voltage drop for cables above 25 mm2 refer to BS 7671.

146

The Electricity Wiring Regulations 2007

A7(b)

Current ratings for PVC multi-core cables (non-armoured)

Standard cable ratings and voltage drop for PVC (70C thermoplastic) multi-core cables (sheathed), non-armoured, stranded copper conductor (BS6004), installed in buried or surface mounted conduit or trunking, or on exposed, perforated cable tray.
On perforated cable tray or in free air (A) 2 core 17 22 30 40 51 70 94 119 148 180 232 282 328 379 3 or 4 core 14.5 18.5 25 34 43 60 80 101 126 153 196 238 276 319

A7(b)

Cross sectional area (mm)

In conduit on wall or in concrete (A) 2 core 13 16.5 23 30 38 52 69 90 111 133 168 201 232 258 3 or 4 core 11.5 15 20 27 34 46 62 80 99 118 149 179 206 225

Clipped direct to a wall (A) 2 core 15 19.5 27 36 46 63 85 112 138 168 213 258 299 344 3 or 4 core 13.5 17.5 24 32 41 57 76 96 119 144 184 223 259 299

1.0 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150

At 30C ambient temperature Note 1: Note 2:

[see Appendix A7(g) for grouping factors]

Data taken from table 4D2A and 4D2B of BS 7671. 2-core refers to single-phase circuits, 3 or 4-core refers to three-phase circuits.

The Electricity Wiring Regulations 2007

147

A7(b)

Continued...

A7(b)
Voltage drop (mV/A/m) 2 core 3 or 4 core 1.0 44 38 1.5 29 25

Cable size (mm) 2.5 18 15 4 11 9.5 6 7.3 6.4 10 4.4 3.4 16 2.8 2.4

Note 1:

For voltage drop for cables above 16 mm refer to BS 7671.

148

The Electricity Wiring Regulations 2007

A7(c)

Current ratings for PVC multi-core cables (armoured)

Standard cable ratings and Voltage drop for multi-core armoured, PVC (70C thermoplastic) cables, stranded copper conductor (BS 6346 and BS 5467), installed exposed (clipped to a wall) or on perforated cable tray.

A7(c)

Cross sectional area (mm)

Clipped direct to a wall (A) 2 core 21 28 38 49 67 89 118 145 175 222 269 310 356 405 476 547 3 or 4 core 18 25 33 42 58 77 102 125 151 192 231 267 306 348 409 469

On perforated cable tray (A) 2 core 22 31 41 53 72 97 128 157 190 241 291 336 386 439 516 592 3 or 4 core 19 26 35 45 62 83 110 135 163 207 251 290 332 378 445 510

Voltage drop (mV/A/m)

2 core 29 18 11 7.3 4.4 2.8 -

3 or 4 core 25 15 9.5 6.4 3.8 2.4 -

1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300

At 30C ambient temperature Note 1: Note 2: Note 3:

[see Appendix A7(g) for grouping factors]

Data taken from table 4D4A and 4D4B of BS 7671. 2 core refers to single-phase circuits, 3 or 4 core refers to three-phase circuits. For voltage drop for cables above 16 mm refer to BS 7671.

The Electricity Wiring Regulations 2007

149

A7(d) Current ratings for thermo-setting multicore cables (armoured)


Standard cable ratings and voltage drop for multi-core, 90C thermosetting plastic insulated, armoured cable, stranded copper conductor (BS6004), surface mounted or on cable tray

A7(d)

Cross sectional area (mm)

Clipped direct to a wall (A) 2 core 27 36 49 62 85 110 146 180 219 279 338 392 451 515 607 698 3 or 4 core 23 31 42 53 73 94 124 154 187 238 289 335 386 441 520 599

On perforated cable tray (A) 2 core 29 39 52 66 90 115 152 188 228 291 354 410 472 539 636 732 3 or 4 core 25 33 44 56 78 99 131 162 197 251 304 353 406 463 546 628

Voltage drop (mV/A/m)

2 core 31 19 12 7.9 4.7 2.9 -

3 or 4 core 27 16 10 6.8 4.0 2.5 -

1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300

At 30C ambient temperature

[see Appendix A7(g) for grouping factors]

Note 1:

From table 4E4A and 4E4B of BS 7671] [2 core refers to single-phase circuits, 3 or 4 core refers to three-phase circuits]. For voltage drop for cables above 16 mm refer to BS 7671.

Note 2:

150

The Electricity Wiring Regulations 2007

A7(e) Current ratings for MICC cable


Standard cable ratings and voltage drop for mineral insulated copperclad cables installed on a wall (clipped direct). PVC sheathed cable assumes 70C sheath temperature, bare copper-clad cable assumes 105C sheath temperature.
Bare sheath 105C 2 x single Bare sheath 105C 3 x single PVC sheath (70C) 2 x single or twin PVC sheath (70C) 3 core Cross-sectional area

A7(e)

(mm) 1.0 Light duty 500 V 1.5 2.5 4 1 1.5 2.5 4 Heavy duty 750 V 6 10 16 25 35 50
At 30C ambient temperature Note 1:

(A) 18.5 23 31 40 19.5 25 34 45 57 77 102 133 163 202

(A) 15 19 26 35 16 21 28 37 48 65 86 112 137 169

(A) 22 28 38 51 24 31 42 55 70 96 127 166 203 251

(A) 19 24 33 44 20 26 35 47 59 81 107 140 171 212

[see Appendix A7(g) for grouping factors]

For MICC cable installed in perforated cable tray the current rating is approximately 5 - 10%, greater than shown above, see BS 7671 table 4J1A and 4J2A. Where the sheath temperature may be above 70C care should be taken that the cable is not within reach of any person or in contact with combustible materials.

Note 2:

The Electricity Wiring Regulations 2007

151

A7(f)

Cable ratings and voltage drop for flexible cords

A7(f)

Standard current ratings and voltage drop for flexible cords60C conductor temperature (PVC or rubber insulated), stranded copper conductors to BS 6500 (domestic applications).

Cross sectional area (mm) 0.5 0.75 1.0 1.25 1.5 2.5 4.0

Single phase

Three phase

Voltage drop (singlephase) (mV/A/m) 93 62 46 37 32 19 12

Voltage drop (threephase) (mV/A/m) 80 54 40 27 16 10

Mass supportable by twin flexible cord (kg) 2 3 5 5 5 5 5

(A) 3 6 10 13 16 25 32

(A) 3 6 10 16 20 25

At 30C ambient temperature

[from table 4H3A of BS 7671]

For Ambient temperatures above 30C the following correction factors may be applied for flexible cords:
Ambient temperature (C) Correction factor

35 0.91

40

45 0.71

50 0.58

55 0.41

0.82

152

The Electricity Wiring Regulations 2007

A7(g) Temperature correction factors for cables


Ambient temperature correction factors (relative to 30C) for cable ratings shown in Appendices A7(a) to A7(e).

A7(g)

Type of cable insulation 90C thermosetting plastic 1.02 1.00 0.96 0.91 0.87 0.82 0.76 0.71 mineral insulated (70C sheath) 1.03 1.00 0.93 0.85 0.77 0.67 0.57 0.45 mineral insulated (105C sheath) 1.02 1.00 0.96 0.92 0.88 0.84 0.80 0.75

Ambient temperature (C) 25 30 35 40 45 50 55 60

70C PVC 1.03 1.00 0.94 0.87 0.79 0.71 0.61 0.50

[from table 4C1 of BS7671:2001]

The Electricity Wiring Regulations 2007

153

A7(h) Grouping factors for cables


Because of mutual heating effects the following correction factors should be applied to the tables in Appendix A7(a) to A7(e) for situations where a number of cables are installed close together. These factors assume all cables are fully loaded; however, if an individual cable is loaded below 30% of its rating it may be excluded from the total number in the group.
Method of installation Enclosed in conduit (surface or buried) or bunched on a nonmetallic surface Single layer, clipped to a non-metallic surface Single layer multi-core on a perforated cable tray Single layer singlecore on a cable tray (touching) Horizontal 0.90 0.85 -

A7(h)

Number of cables

Touching

Touching

Spaced

Spaced

2 3 4 5 6 7 8 9 10 12 14 16 18 20

0.80 0.70 0.65 0.60 0.57 0.54 0.52 0.50 0.48 0.45 0.43 0.41 0.39 0.38

0.85 0.79 0.75 0.73 0.72 0.72 0.71 0.70 -

0.94 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90 0.90

0.86 0.81 0.77 0.75 0.74 0.73 0.73 0.72 0.71 0.70 -

0.91 0.89 0.88 0.87 0.87 -

0.85 -

[ - correction factor not tabulated]

[taken from table 4B1 of BS7671

154

The Electricity Wiring Regulations 2007

Vertical

A8.

Colour identification for cables

Conductor Non-flexible fixed wiring and all three-phase cables: Phase 1 Phase 2 Phase 3 Neutral Earth conductors Functional Earth Red Yellow Blue Black

Colour

A8

Green / yellow Cream

Flexible cables for single-phase Appliances: Phase 1 Neutral Earth conductors Functional Earth Brown Blue Green / yellow Cream

Note:

The harmonised cable colours now implemented in Europe (BS EN 60446 effective from Jan 2006) of Brown, Black and Grey for phase 1, phase 2, and phase 3 respectively have not been adopted for the Emirate of Abu Dhabi.

The Electricity Wiring Regulations 2007

155

A9.

Capacity of conduits and trunking

A9
Conductor ( mm2 ) 20

Diameter of Conduit (mm2) 25 Maximum number of conductors 1.5 2.5 4.0 6.0 10.0 16.0 25.0 7 5 3 12 9 6 5 3 12 9 8 6 4 3 32

Note:

For cable trays and trunking the space factor (total cross-sectional area of cables compared with the interior cross-sectional area of trunking) must not exceed 50%.

156

The Electricity Wiring Regulations 2007

A10. IP coding for ingress protection

Ingress protection : IP codes First digit : protection against ingress by solid objects X 0 1 2 3 4 5 Not tested or not applicable No protection Human hand or objects > 50mm Human finger or objects > 12mm Objects > 2.5mm (e.g. tools or wires) Objects > 1.0mm (e.g. small wires) Limited protection against dust (to the extent that does not harm the equipment or impair safety) Totally protected against dust Second digit : protection against ingress of water X 0 1 2 3 4 5 Not tested or not applicable No protection Vertically falling water Sprays of water < 15 from vertical Sprays of water < 60 from vertical Splashes of water (from any direction) Low pressure jets of water (from any direction)

A10

6 7 8

Strong jets of water (from any direction) Temporary immersion Total immersion

The IP coding system is specified in BS EN 60529: 1992 (adopted from IEC 529: 1989). The first digit specifies protection against ingress of foreign objects of varying size, ranging from human hands or fingers to fine dust particles. The second digit specifies protection against ingress of water, ranging from free falling water, to immersion in water. BS EN 60529 does not specify protection against the risk of explosion, humidity or corrosive gases. If enclosures of equipment are drilled or knockouts removed, suitable measures should be taken to restore the equipment to the original IP rating.

The Electricity Wiring Regulations 2007

157

A11. Standard wiring diagram symbols

A11

Symbol

Description
Main Distribution Board (MDB) Sub Main Distribution Board (SMDB) Distribution Board (DB) Air Circuit Breaker (ACB) Moulded Case Circuit Breaker (MCCB) Miniature Circuit Breaker (MCB) Earth Leakage Protective Device (RCD) Fuse Link kWh meter (direct reading) kWh meter (ct operated) Switched line (e.g. connecting all outlets controlled by one switch) Circuit line (e.g. connecting all outlets on the same circuit) 13 A switched socket outlet 15 A switched socket outlet 20 A double pole switch with neon indicator 30 A double pole switch Shaver socket to BS 3535 Cooker control unit

Note: Additional wiring symbols may be taken from BS EN 60617

158

The Electricity Wiring Regulations 2007

A11. Continued...

A11

Symbol

Description

Note: Additional wiring symbols may be taken from BS EN 60617

The Electricity Wiring Regulations 2007

159

A12(a) Danger of death sign

A12(a)

160

The Electricity Wiring Regulations 2007

A12(b) Typical layout of supply intake room

A12(b)
Copy of Installation Certicate and Wiring Diagram [ see clause 8.1.3 ] Meters
13A socket outlet

Main Distribution Board

Main Supply Cable

Capacitor bank

Main Earth Conductor Main cable pulling pit 600 x 600

Earth cable pit 300 x 300 Louvered door (for non-air conditioned room [ see Regulation 4.2 ]

Standard size of supply intake rooms Main circuit breaker rating (A) Intake room dimensions (m)

600 - 1000 350 - 600 100 - 300

2.5 x 2.5 2.5 x 2.0 2.0 x 2.0

The Electricity Wiring Regulations 2007

161

A12(c)

Typical layout of final distribution board (FDB) and RCD label

A12(c)

Load distribution schedule xed to door

R Y B R Y B R Y B

Main Earth Terminal

Main Isolator

RCD 1 100mA

RCD 2 30mA

Neutral Bar

earth tail for door buried conduits

RCD Operation & Test Customer Notice This Distribution Board is tted with Residual Current Devices (RCDs) which will detect any fault current to earth and switch off the device. Note this Distribution Board is tted with ____ number RCDs. If the device will not switch on after tripping consult a licensed electrical contractor or your local Electricity Supply Company.

RCD Operation Label [ see clause 5.4.8 ]

162

The Electricity Wiring Regulations 2007

A12(d) Typical layout of LV switchroom

A12(d)
Emergency light (2 hour battery)

Outgoing busbar risers

min 0.75 m

Outgoing circuits

HRC fuses min 0.75 m rear clearance R OO FL ND DB 2 S B FD OO R

ER OM NC I

R OO FL ST DB 1 S

capacitor bank automatic control panel

min 1.5 m front clearance

Incoming cables from Distribution Company Transformer

2nd access door for personnel if switchroom is greater than 6 m in length

Access doors for equipment delivery

Note: LV Switchroom to be sized to accomodate the number of panels required (including spare positions) with minimum access clearances shown above.

The Electricity Wiring Regulations 2007

163

A13.

Boundary of customer connection point and scope of the Regulations

A13

FDB Customer Connection Point LV Feeder Pillar MDB Meter FDB

To Distribution Company Transformer 11 kV/400V

Distribution Network
Electricity Supply Regulations 2007

Customers Installation
Electricity Wiring Regulations 2007

[ see Regulation 4.3 and clause 1.3.2 ]

164

The Electricity Wiring Regulations 2007

A14.

Typical layout for ring circuits and radial circuits

A14

Spur socket-outlet

Fused spur to xed appliance

Spur socket-outlets

To Final Distribution Board

15A BS 546 socket-outlet (non-domestic premises only)

[ see clause 7.6.2 , 7.6.3 ]

The Electricity Wiring Regulations 2007

165

A15.

Minimum number of socket-outlets and connection points

A15
Room

Minimum number of outlets for domestic premises Single Double

Kitchen: 13 A switched socket-outlets (BS 1363) 20 A spur connection points (for washing machine, dryer etc) 45 A cooker control unit Bedrooms Lounge or dining Hall or corridor Bathrooms
Note:

4 3 1 4 4 1 Only BS3535 shaver socket

Socket-outlets should be located to avoid the need for customers to use extension cables and doubling adapters.15 A BS 546 socket-outlets are not permitted in domestic Premises, see clause 7.1.1.

166

The Electricity Wiring Regulations 2007

A16.

Mounting height for accessories and socket-outlets

A16

Min 1.3m

Min. 1.0 m from sink

Cooker control unit Min 450mm

Flex outlet

Note: Mounting height may be varied for special circumtances such as access for disabled persons or children, etc. [ see clause 7.1.7 , 7.2.5 and 7.1.9 ]

Min. 100mm from worktop

The Electricity Wiring Regulations 2007

167

A17(a) Approved and prohibited plugs and socket-outlets (domestic)


[ see Regulation 7.1 ]

A17(a)

Approved BS 1363 plug and socket (13 A fused)

Approved BS 546 plug and socket (15 A or 5 A unfused)

(non-domestic only)

Prohibited CEE7/7 shuko plug and socket EE7/7

Type CEE7/16 europlug permitted only with a correct adapter

168

The Electricity Wiring Regulations 2007

A17(b) Industrial plugs and socket-outlets

A17(b)

[ BS 4343 and BS EN 60309 ]

[ see clause 7.1.6 ]

The Electricity Wiring Regulations 2007

169

A17(c)

BS 3535 shaver socket-outlets for bathrooms

A17(c)

230V 115V
N E Isolating transformer complying with BS 3535

230V

shavers only

[ see Regulation 9.3 and clause 7.1.4 ]

170

The Electricity Wiring Regulations 2007

A18(a) Class I equipment (earthed metallic parts)

A18(a)

Earth fault

Earth fault

[ see clause 6.6.3 ]

The Electricity Wiring Regulations 2007

171

A18(b) Class II equipment (double insulated)

A18(b)
Dummy (plastic) earth pin

Live conductors are double insulated or enclosed in plastic case

Unearthed metallic part (see note)

Plastic Case

Live conductors are double insulated or enclosed in plastic case

2-pin plug for use in BS 3535 socket-outlet (see A17c)

Note: Metallic parts of Class II appliances are sufciently remote from live conductors so as not to require a connection to earth. (see clause 6.6.3)

172

The Electricity Wiring Regulations 2007

A18(c)

Separated extra-low voltage (SELV) supply

A18(c)

Isolated metallic parts

230V

max 50V a.c. or 120V d.c.

N E overcurrent protection

Symbol for safety isolating transformer complying with BS EN 60742 or BS 3535

[ see clause 5.3.1 , 5.7.4 , 7.3.13 and 9.1.1 ]

The Electricity Wiring Regulations 2007

173

A18(d) Protective extra-low voltage (PELV) supply

A18(d)

Earthed metallic parts

230V max 50V a.c. or 120V d.c. N E

[ see clause 9.2.1 ]

174

The Electricity Wiring Regulations 2007

A18(e)

Reduced low voltage (RLV) supply

A18(e)

L 55V 230V 55V N 110V

[ see clause 5.3.1 and 9.6.3 ]

The Electricity Wiring Regulations 2007

175

A19(a) Measurement of earth electrode resistance

A19(a)
Red Yellow P E Green

Earthed Electrode under test

5 - 10m

5 - 10m Auxilliary Earth Spikes

(i) (ii) (iii) (iv) (v) (vi)

a proprietary earth electrode test device should be used auxiliary earth spikes should be applied at least 5 m apart and 5 m distant from the electrode under test an earth resistance value of less than 10 ohms is required for a Customer Earthed System [ see Regulation 6.2 ]. an additional number of electrodes may be required (or deeper electrodes) to achieve the required earth resistance value due consideration should be given to future changes in soil condition (e.g. drying out) sufcient time should be allowed if special chemicals or salts are added to the ground to improve the earth resistance values

Earth Pit

Earth Test Spike

176

The Electricity Wiring Regulations 2007

A19(b) Measurement of external earth fault loop impedance


Main Distribution Board

A19(b)

MCCB + E/F

MCCB + E/F

External Earth Loop Impedance Tester Main Earth Terminal


A

Main Earthed Equipotential Bonding To Earth Electrode A Earth Bar Test Link removed and Earth Electrode Connection removed

Notes: 1. Caution: this test is carried out under live conditions but with the main isolator secured in the off position. 2. Ze may be measured directly at the Supply Intake with a specialist Earth Loop Impedance tester. Such devices apply a resistance (typically 10 ohms) between a phase conductor and the earth conductor of the incoming supply. The test draws a current of around 20A but is only applied for a few cycles (e.g. 40ms). The device measures the drawn current and divides this into the measured supply voltage to give the loop impedance (the test resistance applied by the device is subtracted). 3. As an alternative Ze may be calculated from measurement of the total earth fault loop impedance measured within the installation (see A19c) using the formula: ZS = Ze + ZR1+R2 Where: Zs = total Earth Fault Loop Impedance Ze = Distribution Company supply impedance ZR1+R2 = impedance of the longest circuit in the Installation, taken by measuring a circuit phase conductor impedance R1, and the same circuits Earthing Conductor impedance R2. 4. For further advice see reference book Advanced Testing Technique.

The Electricity Wiring Regulations 2007

177

A19(c)

Measurement of internal earth fault loop impedance

A19(c)
Final Distribution Board

R Y B R Y B R

Main Distribution Board

Y B

RCD

RCD

from FDB Bonding Conductors

to switch (must be ON)

Earth Electrode Incoming Supply Cable

to Test Instrument

Notes:

to light (bulb removed from pendant)

1. Caution: this test is carried out under live conditions with the circuits under test energised but no load is connected. The Main Earth Conductor to the local earth electrode (if any) is disconnected and the Main Equipotential Bonding Conductors are also disconnected. 2. A specialist instrument is used which measures the total Earth Loop Impedance Zs using a similar principle as described in A19(b). The instrument must not operate any RCD in circuit. 3. The instrument may be directly connected to a socket-outlet (using the test plug provided) and should be used at the farthest point on a radial circuit or the mid point of a ring circuit. Alternatively, the instrument may be used at an accessory connection point (e.g. lighting ceiling rose) with the appropriate test probes. 4. For further advice see reference book Testing Electrical Installations.

178

The Electricity Wiring Regulations 2007

A19(d) Circuit continuity tests

A19(d)
Final DB

A
R Y B R Y B R Y B

Neutral Bar

B
Test Instrument

Earth Bar

Ring Circuit

Radial Circuit

Notes: 1. This test is carried out on dead circuits. The main isolator must be secured in the off position. 2. Circuit continuity tests must be measured for all circuits and the resistance values recorded on the test report, see Appendix A20(d). Alternative methods are illustrated as above. 3. Method A tests the combined phase and earth resistance (R1 + R2) for each circuit by shorting together the two conductors at the distribution board, and measuring from the terminals of the farthest connection point or socket-outlet. For ring circuits the two phase and earth conductors from the ring are cross connected as illustrated above. 4. In method B a shorting cable is applied between the neutral and earth bar at the distribution board. Measurement at any connection point gives a value Rn + R2 (neutral conductor resistance + circuit earth conductor) which approximates to R1 + R2.

The Electricity Wiring Regulations 2007

179

A19(e)

Circuit polarity tests

A19(e)
To Final DB

To switch (must be ON)

To Light holder

Final DB to Test Device

OFF

A
Earth Bar Shorting cable applied at Final DB between phase conductor and earth conductor of circuit under test

Notes: 1. This test is carried out on dead circuits. The main isolator must be secured in the OFF position. 2. The polarity test is required to conrm that all single pole devices, and lamp holders with an outer neutral contact (i.e. ES screw type) are correctly connected 3. Single pole devices ( eg. light switches ) must only be connected in the live conductor. 4. The test is carried out by measuring continuity between the earth terminal and live terminal at an accessory such as an ES pendant light tting , after a shorting cable has been applied between the relevant phase conductor and earth bar at the Final Distribution Board.

180

The Electricity Wiring Regulations 2007

A19(f)

Insulation resistance tests

Circuit Nominal Voltage SELV and PELV up to 500 V

Test Voltage (d.c.) 250 500

Minimum insulation resistance (M ohms) 0.25 0.5

A19(f)

1.

Insulation resistance should be checked between all live conductors, and between live conductors and Earth. For SELV and PELV systems insulation resistance should be measured between the extra-low voltage and higher voltage conductors at 500 V. The test instrument should be capable of producing a d.c. test voltage of 500 V when loaded to 1 mA and be capable of measurement of up to 200 M ohm. The minimum acceptable value of insulation resistance for any test is 0.5 M ohm for LV systems and 0.25M ohm for SELV and PELV systems. The supply should be disconnected and all current-using equipment switched off (including neon indicator lamps, voltmeters, electronic devices such as dimmer switches, starters, RCDs with amplifiers etc). Alternatively, a limited test can be carried with the phase and neutral conductors connected together and testing to earth. Insulation measurements should be made at each Distribution Board between each pair of phases in turn, between each phase and neutral, and between each phase and Earth. A final test should be made between the neutral bar and Earth; if a reading of less than 2 M ohm is observed, then each neutral conductor should be tested separately to Earth.

2.

3. 4.

5.

6.

The Electricity Wiring Regulations 2007

181

A19(g) Sequence of testing for new installations

A19(g)

Correct sequence for safe testing Before supply is connected: 1. 2. 3. 4. 5. 6. Continuity of earth conductors (Main Earth Conductors and Circuit Earth Conductors) Continuity of main and supplementary bonding conductors Continuity of Ring Circuit conductors Insulation resistance Polarity tests Earth electrode resistance

After supply is connected: 1. 2. 3. 4. 5. 6. External earth fault loop impedance test Re-confirm polarity Earth fault loop impedance Operation of RCD and earth fault devices Operation of switches and isolators Prospective fault current measurement

Note:

Safety precautions must be observed during testing, including locking off isolators and switches, safeguarding against contact with test voltages, replacement of test links and removal of tools after completion. The order of test sequence must be observed, in particular testing of Earth Conductors (dangerous test voltages can appear on the installation metalwork if Earth Conductors are inadvertently disconnected or broken).

182

The Electricity Wiring Regulations 2007

Electrical Installation certificate


Project / Building Name:................................................................................ Address / Location: .............................................................................................. Details of Client / Customer: Certificate No. / Ref: .......

................... ...................

Electricity account no. / contact details: New or modified installation:

... New: Modification: Existing:

A20(a)

Brief description of work carried out: . Supply Characteristics: Earthing System: (TT, TN-S, TN-S-TT); Incoming Cable Size & Type: Main CB type & rating: Protective System (ELPS, EEBS); Max Prospective Fault Current: Meter ref. nos and type: ......... ......... ......... ......... ......... Earth Electrode(s )Resistance: Earth Electrode(s) Location: Main Earth Conductor Size: Earth Fault Loop Impedance: Total Connected Load: ............ ............ ............ ............ ............ Previous Certificate number:.........................

................................................................................................................................

Details of Designer: ................................... Contact Details: ...................................

We hereby declare that the work completed by us in relation to the above named installation, and detailed in the reference drawings and documents listed below, has been carried out with due skill and care, and in accordance with the Electricity Wiring Regulations 2007 published by the Regulation & Supervision Bureau for the Water, Wastewater and Electricity Sector in Abu Dhabi: Authorised signatory & name: .... .... Reference drawings and schedules: Details of Installer: Contact Details: .. Company Stamp: ................ Date: .....................

...............

Licence Number: .....................

....................

We hereby declare that the work completed by us in relation to the above named installation, and detailed in the reference drawings and documents listed below, has been carried out with due skill and care, and in accordance with the Electricity Wiring Regulations 2007 published by the Regulation & Supervision Bureau for the Water, Wastewater and Electricity Sector in Abu Dhabi: Authorised signature & name: Date: .....................

..... Reference drawings and schedules: ..... Company Stamp: ............

The Electricity Wiring Regulations 2007

183

Inspection report (front)


Project / Building Name:................................................................................ Address / Location: .............................................................................................. Details of Client / Customer: ................... ................... Electricity account no. / contact details: New or modified installation: ... New: Modification: Existing: Report No

A20(b)

Reason for Inspection (first inspection, routine inspection, other): .....................................................................

............................................................................................... Installation Certificate number: ..


Supply Characteristics: Earthing System: (TT, TN-S, TN-S-TT); Incoming Cable Size & Type: Main CB type & rating: Protective System (ELPS, EEBS): Max Prospective Fault Current: Meter ref. nos and type: ......... ......... ......... ......... ......... Earth Electrode(s) Resistance: Earth Electrode(s) Location: Main Earth Conductor Size: Earth Fault Loop Impedance: Total Connected Load: .............. .............. .............. .............. ..............

.............................................................................................................................

General Details of Inspection & Testing: Date of last inspection & test: Any modifications noted: ....................................................................................................... Details: ........................................................................

No Yes

Estimated age of installation & estimated age of modifications: ............................................................... Date of next planned inspection: ....................................................................................................... Any dangerous conditions or urgent work required (give details over leaf): Any work or improvements recommended (give details over leaf): No Yes No Yes

Extent of inspection: All: Part: Areas not tested / inspected:........................................................... Inspection carried out by: Contact Details: ................. .............

We hereby declare that the inspection and testing completed by us in relation to the above named installation, and detailed over leaf, has been carried out with due skill and care, and in accordance with the Electricity Wiring Regulations 2007 published by the Regulation & Supervision Bureau for the Water, Wastewater and Electricity Sector in Abu Dhabi:

Authorised signature & name:....

Date:....................

...

Company Stamp: .............................

184

The Electricity Wiring Regulations 2007

Inspection report (back)


Equipment Inspected:

satisfactory not applicable

not satisfactory (give details /comments)

urgent work required



A20(c)

Main intake room condition: Metering Equipment: Main Distribution Board: Main Isolation Device (CB): Main LV switchboard (if any): Incoming supply cable(s): Main earth conductor, earth pits, and MET; Sub Distribution Boards (give ref. nos):

....................................................................................... ....................................................................................... ....................................................................................... ....................................................................................... ....................................................................................... ....................................................................................... ....................................................................................... ....................................................................................... ....................................................................................... .......................................................................................

Distribution Cables (between DBs):

....................................................................................... .......................................................................................

Main Earth Leakage Protective Device(s): Circuit cables (where visible): Power factor correction equipment: Standby generation equipment: Power points & socket outlets:

....................................................................................... ....................................................................................... ....................................................................................... ....................................................................................... ....................................................................................... .......................................................................................

Internal Inspection of sample points (10% sample): List circuits/connections inspected ....................................................................................... .......................................................................................


185

.......................................................................................

The Electricity Wiring Regulations 2007

A20(d)

The Electricity Wiring Regulations 2007


see note 1 see note 1

mm

R1 + R2

Polarity

186

Installation testing report


Document No./Ref................................... Tested by................................................. Date:....................................................... Date:.......................................................
Insulation Resistance L-L Live-Earth

Project/Building Name:

.................................................................................

Test Instruments ( serial no.s) Loop impedance tester:..................... Continuity tester:................................ Insulation tester:................................. Functional Test RCD time (ms) Other Remarks

Address/Location:

.................................................................................

Distribution Board No./Ref:

................................................................................

Fed from:
Continuity Test (ohms) Circuit name R2 Ring

.................................................................................

CCT Identity No.

CCT ref. No.

MCB rating (A)

Phase & Neutral size

Earth wire size

mm2

Total Earth Loop Impenance (zs)

Deviation from Wiring Regulations & Special Notes:

Testing carried out by: Company name/stamp: Date:

................................................................................. ................................................................................. .................................................................................

Note1: for L-L or L-E insulation resistance tests enter the lowest value measured for either R-Y, Y-B, R-B.

Load distribution schedule

Project/Building Name

Address/Location

Distribution Board No./Ref

................................................................................. Incoming Cable size / type and ECC: ......................................................... .......................................................................................................................................................................................................................... ................................................................................. Main breaker type & rating: ......................................................... .......................................................................................................................................................................................................................... ................................................................................ Date: ................................ ..........................................................................................................................................................................................................................

Fed from:
Circuit Load in Watts R Y B

Document No / Ref............................... ..........................................................................................................................................................................................................................

CCT Identity No. Circuit name / Point reference No. of points Watts per point

CCT ref. No.

MCB rating (Amps)

Phase & Neutral Size

Earth Conductor size

Remarks

mm2

mm2

The Electricity Wiring Regulations 2007


TOTAL CONNECTED LOAD TOTAL LOAD AFTER DIVERSITY ............................KW Remarks: ............................KW Remarks:

187

A20(e)

188

The Electricity Wiring Regulations 2007

Guidance notes

The Electricity Wiring Regulations 2007

189

190

The Electricity Wiring Regulations 2007

Guidance notes
G1. G2. G3. Guidance note on supply voltage change Estimation of connected load and diversity factors Photographs (a). Photograph of busbar riser 196 197 193 194

(b). Photograph of final distribution board G4. Electric shock, ELP and EEB systems (a) (b) (c) (d) (e) (f) (g) (h) G5. Direct contact with electricity Indirect contact with electricity Main and supplementary earthed equipotential bonding (EEB) Illustration of earth leakage protected system (ELPS) Grading of RCDs in an ELP system ELP system supplied from LV switchroom Calculation of touch voltage (ELP system) Calculation of touch voltage (EEB system)

198 199 200 201 202 203 204 205

Electric shock and RCD characteristics (a) (b) (c) (d) (e) RCD operating characteristics and electric shock Typical values of body resistance and physiological effects RCD operating principle Types of RCDs Sources of nuisance tripping of RCDs 206 207 208 209 210 211

G6.

Protection of buried cables

The Electricity Wiring Regulations 2007

191

G7.

Common errors (a) (b) (c) (d) (e) (f) (g) (h) (i) (j) (k) (l) Exposed unsheathed cables at termination points Protection of high temperature connections Weather protected outdoor socket-outlets Earth tails in accessories and connection boxes Minimum depth of buried plastic conduit Circuit identification numbers on accessories and earth conductors Missing grommets and sharp edges on cable tray Cables in ceiling-voids Cable glands for earthing of armoured cable Earth continuity connections across cable tray and conduit Prohibited terminal blocks and taped connections Slotting of steel gland plates for single core cables 212 213 214 215 216 217 218 219 220 221 222 223

192

The Electricity Wiring Regulations 2007

G1.

Guidance note on supply voltage change

Distribution Companies in the UAE have traditionally based the design of their networks on the UK power system. Previously, the voltage of supply was declared to be 240 V single-phase or 415 V three phase, with an allowed variation in voltage of +/- 6%. With the harmonization of supply voltages in Europe (in line with IEC 38) the UK has adopted a supply voltage of 230 V or 400 V +/- 10% . These Regulations have adopted the same nominal voltage of supply, but with a narrower range of +10% - 6% (clause 4.1.3). This range has been adopted to allow existing distribution network assets to continue to operate without modification, and also provides a superior voltage range to Customers. With an allowed voltage drop of 4% within a Customer's Installation (clause 7.5.10) this ensures the total voltage drop to Appliances will not exceed 10% of the nominal voltage of 230/400 V.

G1

225.6
-6%

240
+6%

254.4
Old UK supply voltage range previously used in Abu Dhabi

207.0
-10%

230
+10%

253.0
IEC.38 supply voltage

216.2
-6%

230
+10%

253.0

IEC.38 supply voltage operated under a restricted range as adopted in the Wiring Regulations (2007)

200

210

220

230

240

250

260

The Electricity Wiring Regulations 2007

193

G2.

Estimation of connected load and diversity factors

Estimation of connected load for domestic premises Applied diversity factor

Type of load

Assumed connected load

G2
sum of wattage of all luminaries or assume 100 W for each lighting point (except chandelier points) chandelier lighting points 1,000 W 1.8 x lamp wattage for fluorescent lighting 200 watts per socket-outlet (except kitchen) for kitchen worktop socket-outlets assume 1,000W each kitchen appliance connection points (flex outlet) assume 3,000 W each (e.g. washing machine, dryer, dishwasher, etc) cooker rating of oven plus 2 larzgest rings fridge full rating (e.g. 300 W)

Lighting

75%

13A socketoutlets

100%

Kitchen power points

75%

Other power points

water heater full rating motors (e.g. lifts) full rating split air conditioning units full rating window air conditioning units full rating central a/c units, (see note 2)

30-50%

Air conditioning

90%

Note 1: Note 2:

The diversity factors indicated in column 3 may be applied to each group of loads in order to calculate the 'diversified connected load'. A 90% diversity factor may be applied for split or window type air conditioning units; diversity factors for central a/c units should be based on manufacturers data or load readings taken from other similar installations (during summer temperature conditions).

194

The Electricity Wiring Regulations 2007

G2.

Continued...

The total estimated load at a Premises must be calculated and submitted to the Distribution Company in order to make an application for a new supply of electricity or alteration of an existing supply (clause 3.2.5). Normal practice is to calculate the Diversified Connected Load rather than simply take the sum of all equipment and Appliances in the Installation. This method avoids oversizing of the Installation as well as the Distribution Company supply. Firstly, the design and layout of an installation should be detailed in the format of load distribution schedules as shown in Appendix 20(e). A These schedules should list all connection points and fixed Appliances in each circuit. For domestic Premises the total Diversified Connected Load can be derived using the guidelines in the table above. For non-domestic Premises the above rules and diversity factors do not apply and estimation of loads must be made by a qualified designer or engineer with knowledge of the proposed usage of the Installation. For example, the connected load of industrial machinery in continuous operation would be taken as 100%. In contrast, equipment operating in short duration cycles (e.g. a few minutes) could have a diversity factor as low as 20%. Another example could be a warehouse with automatic motion-operated lighting, which may result in a diversity factor as low as 10%. Alternatively, the average load per m2 of floor area can be used if such data is available from other similar Premises e.g. 50 W or m2 for normal use offices, 100 W or m2 for high density offices, 150 W or m2 for computer rooms, etc. Floor area loading data normally excludes central air conditioning demand which is calculated separately. G2

The Electricity Wiring Regulations 2007

195

G3(a). Photograph of busbar riser

G3

Typical busbar riser system including plug-in circuit breaker

196

The Electricity Wiring Regulations 2007

G3(b). Photograph of final distribution board

G3

The Electricity Wiring Regulations 2007

197

G4(a)

Direct contact with electricity

G4(a)

[ see Regulation 5.3 ]

198

The Electricity Wiring Regulations 2007

G4(b)

Indirect contact with electricity

1. Contact between Exposed-Metallic-Part and Extraneous-Metallic-Part 2. Contact with Exposed-Metallic-Part 3. Contact with Extraneous-Metallic-Part

MDB

G4(b)

MET EEB Conductor

Supply Cable CEC

3 2

Earth Fault

Extraneous Metallic Part (water pipe)

Extraneous Metallic Part (building structure)

Note: Illustration shows TN-S supply system i.e. Distribution Company Earthed with Earthed Equipotential Bonding (EEB) of Extraneous metalwork. Live conductors are not shown for clarity.

[ see Regulation 5.3 and 5.5 ]

The Electricity Wiring Regulations 2007

199

G4(c)

Main and supplementary earthed equipotential bonding (EEB)

G4(c)
MCCB

Distribution Circuits FDB

CEC CEC

CIRCUIT B

MCCB

MCCB

MEC MET

CIRCUIT A

Isolator

Supplementary EEB

Main EEB

Supply Cable (TN-S)

Note 1. Live conductors are not shown for clarity. Note 2. Characteristics of MCBs for Final Distribution Boards must be coordinated against earth loop impedance values to give a maximum of 0.4 sec tripping for circuit A (socket-outlet supplying portable appliances) and 5 sec for circuit B (xed appliances only). Also, MCCBs must coordinate to give a maximum of 5 sec tripping time for distribution circuits. ( see clause 5.5.2 and 5.5.3 )

[ see Regulation 5.5 ]

200

The Electricity Wiring Regulations 2007

G4(d)

Illustration of earth leakage protected system (ELPS)

FDB

G4(d)
RCD RCD

MEC MCCB + E/F


MCCB + E/F MCCB + E/F

CEC

MET Isolator

Main Supply (TN-S-TT) System

Note: Main Distribution Board includes MCCB with sensitive earth fault setting (provides backup to RCDs in Final Distribution Board). Live conductors are not shown for clarity. [ see Regulation 5.4, clause 5.4.7 ]

The Electricity Wiring Regulations 2007

201

G4(e)

Grading of RCDs in an ELP system

G4(e)

MDB

FDB

RCD type S (see Note 1)

RCD 100mA

RCD 30mA

30mA

Outdoor socket-outlet with 30mA RCD

Note 1: Type S RCDs provide time delayed operation in order to discriminate with RCDs at the Final Distribution Board. Alternatively, for high current applications a MCCB with sensitive earth fault (E/F) relay may be used. Note 2: 30mA RCD protection is required for socket-outlets serving portable appliances; 100mA RCD protection is required for xed appliances and circuits

[ see Regulation 5.4, clause, 5.4.5, 5.4.6 ]

202

The Electricity Wiring Regulations 2007

G4(f)

ELP system supplied from LV switchroom

G4(f)
SDB with MCCBs

R Y B R Y B R Y B

RCD

RCD

100mA 30mA

Final DB with 100mA and 30mA RCDs

Earth Leakage Protection Relay

Main Circuit Breaker

I Incoming Supply Cables

[ see clause 5.4.5 and 5.4.6 ]

The Electricity Wiring Regulations 2007

203

G4(g)

Calculation of touch voltage (ELP system)

G4(g)

N L I F R2

Extraneous Metallic Part

MET Ze

Vt

Vf

Notes 1.Touch Voltage Vt is approximately equal to the fault voltage Vf assuming that the Extraneous-Metallic-Part is in good contact with Earth. 2. Ze is the resistance of the earth electrode (TT system) or the incoming supply earth fault loop impedance (TN-S) system. 3.The illustration shows unbonded Extraneous-Metallic-Parts, such as in a Earth Leakage Protected System (ELPS).

[ see Regulation 5.5 ]

204

The Electricity Wiring Regulations 2007

G4(h)

Calculation of touch voltage (EEB system)

N L I

R1 F Rs R2 VR2

Extraneous Metallic Part t

G4(h)

Supplementary EEB

MET Ze RMET

Main EEB

Vt

VR2

Notes: Without supplementary EEB the touch voltage Vt is approximately equal to the voltage drop across the Circuit Earth Conductor resistance R2 . To calculate Vt : Vt Where : VR2 = IF x R2 = Uo x R 2 Zs

UO = supply voltage to earth Zs = total earth fault loop impedance

Example: For an appliance supplied by an MCB (type C) of nominal rating 16A the maximum earth fault loop impedance to give a 0.4 sec disconnection time, given under appendix A5(h) is 1.5 Ohms. R2 is measured as 0.9 Ohms. Hence: 230 x R2 = 138 V 1.5 If the measured earth loop impedance is higher than 1.5 Ohms the time-current characteristic of the MCB will need to be checked to see if a disconnection time of 0.4sec can be achieved (the touch voltage will be higher), otherwise RCD protection will be required. If supplementary bonding is applied then the touch voltage is dramatically reduced (the voltage drop equates to the current passing through the supplementary bonding times the resistance of the supplementary bonding Rs). Vt =

The Electricity Wiring Regulations 2007

205

G5(a)

RCD operating characteristics and electric shock

G5(a)

These Regulations include a compulsory requirement for provision of Earth Leakage Protection (ELP) on all Final Circuits where Appliances may be used by any persons (clause 5.3.5). This is normally achieved with RCD devices complying with IEC 60898 or BS 3871 which must operate within 200 ms at their residual current rating (tripping current) and within 40 ms at 5 times their residual current rating. RCDs must not operate at below 50% of their residual current rating. RCD devices with a residual operating current of 30 mA or less may be used for supplementary protection against Direct Contact, whilst devices rated above this value provide protection against Indirect Contact only (see clause 5.3.2). ELP devices do not protect against electric shock between phase conductors or between phase and neutral. The response of the human body depends on the time and magnitude of current that may pass at the time of an electric shock incident. The low risk and high risk range of current against time is illustrated below, along with the operating times of typical RCD devices (from IEC 60479).
10,000 5,000

C1 C2 C3

IEC 60479

2,000 1,000

Time in milliseconds

500

1
200 100 50

20 10 0.1

0.2 0.3 0.5

10

20 30 50

100 200 300 500 1,000 2,000 3,000 5,000 10,000

Current in milliamperes (RMS) 30mA RCD 100mA RCD Typical current limits due to body resistance at 230V.

Response of human body vs. RCD characteristics: Zone 1: Zone 2: Zone 3: Zone 4: usually no reaction shock sensation, but usually no harmful effects likelihood of muscular contraction, and temporary cardiac arrest without ventricular brillation in addition to the effects of zone 3, the probability of ventricular brillation is increased by 5% for curve C2 and 50% for curve C3; harmful effects such as cardiac arrest, breathing arrest and burns are likely to occur

206

The Electricity Wiring Regulations 2007

G5(b)

Typical values of body resistance and physiological effects

Human Resistance for Various Skin Contact Conditions (k Ohms) Touch area Finger touch Hand hold on wire Hand hold on pipe Palm touch Dry 40 1,000 15 50 1 3 3 8 Wet 4 15 3 6 0.5 1.5 1 2

G5(b)

Internal body resistance (including skin) = 0.2 1 k Ohms

Electric Current (1 second contact)

Physiological Effect

Voltage required to produce the current with assumed body resistance: 100 k Ohms 1 k Ohms 1 V 5 V

1 mA 5 mA

Threshold of feeling, tingling sensation Accepted as maximum harmless current Beginning of sustained muscular contraction ("Can't let go" current.) Ventricular fibrillation, fatal if continued. Respiratory function continues

100 V 500 V

10-20 mA

1000 V

10 V

100-300 mA

10000 V

100 V

The Electricity Wiring Regulations 2007

207

G5(c)

RCD operating principle

G5(c)

RCD devices measure the vector sum of currents passing through the phase and neutral conductors in a circuit, via a magnetic coil and electronic amplifier. The device will trip if these are out of balance by more than the residual operating current, in accordance with the manufacturer's time-current performance curve. See Guidance Note G5(a). The older type of voltage-operated earth leakage devices (ELCB) are not permitted (clause 5.4.2) since they operate by detecting fault voltage and require a connection between a Main Earth Conductor and an Earth Electrode; these devices are therefore vulnerable to maloperation due to parallel earth paths.
Three-phase RCD: Test button

Test resistor

L1 L2 L3 N
Incoming supply

L1 L2 L3 N
Load circuits

Trip relay

Single-phase RCD: Test button

Test resistor

L N
Incoming supply

L N
Load circuits

Trip relay

208

The Electricity Wiring Regulations 2007

G5(d)

Types of RCDs

Because of the use of semiconductor devices in an Installation there may be situations when an earth fault current is not purely sinusoidal but contains a d.c. or chopped waveform. This may de-sensitise or disable standard a.c. operated RCDs. Special devices are available which are designed to continue to function for non-sinusoidal supply waveforms, complying with IEC1008, IEC1009 (indicated by the symbols shown below). For RCD devices installed at a Main Distribution Boards time delayed operation is usually required to avoid tripping when a fault occurs in a Final Circuit (the FDB RCD should trip first). Time delayed RCD devices are labelled 'S type'.

G5(d)

TYPE AC normal ac sensitivity

TYPE A pulsating dc sensitivity

ON
RCD
32A 100m A WRs122

ON
RCD
SGA 30m A WR5102

Reproduced with permission of Wylex / Electrium.

The Electricity Wiring Regulations 2007

209

G5(e)

Sources of nuisance tripping of RCDs

Type of fault

Reason Direct contact by persons Indirect contact (during earth fault) Incorrect discrimination with series Loose connections Crossed neutral connections on split busbar distribution board Neutral to earth fault High earth conductor currents (e.g. IT equipment, filters, etc) Moisture in circuit conductors (especially joints in MICC cables) Moisture in appliances (e.g. cooker heating element) Double pole switching (capacitive effects) Transient voltages caused by large inductive loads (e.g. industrial motors) Damage circuits (e.g. nails in walls) Loose connections Mains borne disturbances (e.g. surges, lightning, transients from overhead lines) Disturbing loads (e.g. machinery, lift motor, etc) connected RCDs (e.g. between MDB and FDB)

G5(e)

Downstream of RCD

Upstream of RCD

Note:

RCDs may also trip (correctly) because of Direct Contact by a person or Indirect Contact (during earth fault)

210

The Electricity Wiring Regulations 2007

G6.

Protection of buried cables

Cable marker plate Concrete or steel protective tiles Min 600mm in footpath Min 750mm in road

G6

Min 100mm

Note: cables should be installed in ducts to allow for future removal (clause 7.5.8)

The Electricity Wiring Regulations 2007

211

G7(a)

Exposed unsheathed cables at termination points

G7(a)

[ see clause 7.4.8 and 7.5.12 ]

212

The Electricity Wiring Regulations 2007

G7(b)

Protection of high temperature connections

G7(b)

Heat resistant sleeve required for high temperature connections [ see clause 7.5.17 ]

The Electricity Wiring Regulations 2007

213

G7(c)

Weather protected outdoor socketoutlets

G7(c)

30m 30mA 30mA 0m

PUSH PUS PU H PUSH US USH TEST TEST TEST TEST ES

IP66 weather protected socket outlet with 30mA RCD

[ see clause 7.1.14, 9.4.1(b), 9.5.1(b), 9.6.2(g) ]

214

The Electricity Wiring Regulations 2007

G7(d)

Earth tails in accessories and connection boxes

G7(d)

Double socket-outlet

Plastic light switch

[ see clause 6.6.4 ]

The Electricity Wiring Regulations 2007

215

G7(e)

Minimum depth of buried plastic conduit

G7(e)

Min 50mm

Buried plastic conduits in walls or ceilings must be min 50mm depth or metal conduit must be used (see clause 7.4.6 )

216

The Electricity Wiring Regulations 2007

G7(f)

Circuit identification numbers on accessories and earth conductors

G7(f)

(Circuit identication numbers, See clause 3.6.4 , 3.6.5)

[ see clause 6.5.3 ]

The Electricity Wiring Regulations 2007

217

G7(g)

Missing grommets and sharp edges on cable tray

G7(g)

[ see clause 7.4.8 ]

218

The Electricity Wiring Regulations 2007

G7(h)

Cables in ceiling-voids

G7(h)

See clause 7.3.8 and 7.5.15 (exible connections to be limited to 3m in length and securely xed; plug & t connection systems may be used after the main supply connection)

The Electricity Wiring Regulations 2007

219

G7(i)

Cable glands for earthing of armoured cable

G7(i)

Earth conductor size must be in accordance with Appendix A5(j)

[ see clause 7.5.18 ]

220

The Electricity Wiring Regulations 2007

G7(j)

Earth continuity connections across cable tray and conduit

G7(j)

[ see clause 6.6.1 and 7.4.4 ]

The Electricity Wiring Regulations 2007

221

G7(k)

Prohibited terminal blocks and taped connections

G7(k)

[ see clause 7.5.16 ]

222

The Electricity Wiring Regulations 2007

G7(l)

Slotting of steel gland plates for single core cables

Slot

Steel Plate

G7(l)

Note: Single core cables in a steel enclosure will cause electromagnetic currents in the steel and possible overheating. This can be avoided by ensuring that a non-ferromagnetic material is used around the cables (e.g. brass plate) or slots are cut in the steel between the phase conductors. [ see clause 7.5.11 ]

The Electricity Wiring Regulations 2007

223

224

The Electricity Wiring Regulations 2007

You might also like