Diagramas de Mollier
Diagramas de Mollier
Diagramas de Mollier
A ccum ulator
Transfair Engineering: Designing and Prototyping of Refrigerator and Freezer Cooling Circuits. Contents
p. 2
CONTENTS
1. 1.1. 1.2. 1.3. 1.3.1 1.3.2 1.3.3 1.4. 1.4.1 1.4.2 1.5. 1.5.1 1.5.2 INTRODUCTION Refrigeration Cycle -Definitions Designing of Refrigerator and Freezer Cooling Circuits Standards and Climate Classes Refrigerator and Freezer Performance Standards Climate Classes Electrical Safety Standards Refrigeration Capacity Calculation of Thermal Losses and Freezing Power Measurement of the Cabinet Constant Reduction of Thermal Losses Foam Insulation Thickness Polyurethane Foam Tests Measurement of the Foam Density in Refrigerators and Test Shots Dimensional Stability Verification of Reaction Parameters, Cream Time, String Time, Rise Time Assurance of a Continuous Quality Thermal Bridges Sealing between Door and Cabinet Reduced Space between Food liner and Door liner Design of Door Gasket, Air Tightness Test of Door Gaskets 8 8 9 9 9 9 10 10 11 13 13 14 14 14 14 15 15 15 16 16 16
1.5.3
2. COMPRESSOR
2.1. 2.2. 2.2.1 2.2.2 2.2.3 2.2.4 2.3. Replacements of CFC-12 Compressors Energy Efficiencies, Drop-in Solutions, Reliabilities and Lifetimes Compressor Dimensions and Spaces, Investments and Costs Compressor Capacities HP Value Nominal Displacement Refrigeration Capacity Coefficient of Performance Starting Characteristics Low or High Starting Torque, RSIR, RSCR, CSIR, CSR Start Capacitor, PTC, Relay, High Starting Torque Compressor, Run Capacitor Electrical Diagrams Lifetime Heavy Duty Evaporating Temperature LBP, MBP, HBP Comparison between R134a and R12 Compressors Pressure-/Enthalpy Diagram of R12 and R134a
17 17 17 17 18 18 18 18 18 19 19 19 19 20 20 21 21 21 21 21 22 22 23 23 23
24
25 25 25 26 26 26
Transfair Engineering: Designing and Prototyping of Refrigerator and Freezer Cooling Circuits. Contents
p. 3
of Compressors, R134a Lubricant, R134a Sludge Formation, R600a Solubility and Foaming, R600a Flammability, Compressor Costs Energy Optimised Compressors Variable Capacity Compressor Compressor Performance Tests and Test Methods Labelling of Compressors with Flammable Gas (R600a, R290 etc.)
27 27 28 29 29
3. CONDENSER
3.1. 3.1.1 3.1.2 3.1.3 3.1.4 3.1.5 3.1.6 3.2 3.2.1 3.2.2 3.2.3 3.2.4 3.3. 3.4. 3.5. 3.5.1 3.5.2 3.6. 3.6.1 3.6.2 3.6.3. Static Condensers Wire-on-Tube Condensers Tube-on -Finned -Plate Condensers Condenser Constant Condenser Capacity Condenser Transmission Coefficient or U-Value Condenser Surface Skin Condenser Skin Condenser on a Refrigerator or Freezer Cabinets Skin Condenser on a Chest Freezer Relation between Volume, Tube Length, Tube Distance and k-Value Necessary Increase of Insulation of Skin Condenser Refrigerators and Freezers Sheet Cover on Condenser Anti-Dew Coil Oil Cooling Condenser Fan Cooled Condenser Fin Coil Characteristics Possible Solutions for the Air Ducts Testing Condensers Calorimetric Measurement Comparison Test of Condenser Capacities Standards of condenser performance testing and test methods
31 31 31 31 31 31 32 33 33 34 34 35 35 35 36 36 37 37 38 38 38 39 40
42 42 43 44
5. EVAPORATOR
5.1. 5.1.1 5.1.2 5.1.3 5.1.4 Evaporator Capacity and k-Value Roll-Bond Evaporators Suction Accumulation Channel Cross Section Samples Evaporator Types, Sizes and Forms Cold Cabinets Evaporator Surface Screening and Drip Trays Two Temperature Cabinets Connection of Refrigerator and Freezer Evaporators in Series Tube-on-Sheet, TOP or Skin Evaporators Chest Freezers Evaporators Chest Freezer Pull-Down Test Chest Freezer Evaporator Tube Length Working Process to mount Chest Freezer Evaporators Aluminium Tube Evaporators, Steel Tube Evaporators Cold Cabinet Evaporators Flatted evaporator tube with vertical u-bend
5.2.2
46 46 46 46 47 47 47 48 48 49 49 50 51 51 51 52 52 52 53 53
Transfair Engineering: Designing and Prototyping of Refrigerator and Freezer Cooling Circuits. Contents
p. 4
5.2.3
5.2.4
5.2.5
5.3. 5.3.1. 5.3.2. 5.3.3. 5.4. 5.4.1 5.5. 5.5.1 5.5.2 5.5.3 5.5.4 5.5.5 5.5.6 5.6. 5.7. 5.7.1 5.7.2 5.7.3
Evaporators for one Door Refrigerator with Freezer Compartment Evaporators for one-Door ** Refrigerator Evaporators for one-Door*** Refrigerator Evaporators of two-Door Refrigerator Evaporator in the Refrigerator Part Tube-on-Sheet-Evaporator: Roll Formed Sheet-on-Tubes Evaporator, Aluminium sheet or foils Working Process to mount Tube-on-Sheet or Skin Evaporators on Refrigerators Surface of Tube-on-Sheet Evaporator Freezer Part inside 2 Door Model, Freezer up to and above 60l Tube-on-Plate Freezer Evaporator, Wire-on-Tube Freezer, Evaporators in Series Skin versus Roll-Bond Evaporators Cost Comparison, Processing and Painting, Aesthetic Aspects, Corrosion and Service Cross Section Optimisation of Evaporators Evaporator Channels or Tubes and their Cross Sections Speed of refrigerant and Pressure Drop Measurement Liquid-Gas Separator and Accumulator Sizes of Upright Freezer Evaporators Pull-Down Test of Upright Freezers NO FROST Evaporators Surface of Fins and Air Charge Tube Size and Fin Distances Defrosting of No Frost Evaporators Air Ducts in NO Frost Refrigerators Damper Thermostat Tandem System Refrigerant Circuit Scheme, Electrical Scheme Fridge ventilator Evaporator Tests Pressure Drop Tests Measurement of Temperature Distribution in Multi-Evaporator Systems with one Control Pull Down Tests Vertical Freezers, Chest Freezers, Fridge-Freezers and Cabinets with or without Freezer Compartment
54 54 55 55 55 55 56 56 56 57 58 58 58 59 59 59 59 60 60 61 61 61 61 62 62 63 63 64 64 64 65 65 65
6. DRYER/DESICCANT
6.1. 6.2. Filter Dryer characteristic Refrigerant Dryer Test Standards and Methods
67 67 68
7. REFRIGERANT
7.1. 7.1.1 7.1.2 7.1.3 7.1.4 7.1.5 7.1.6 7.1.7 7.1.8 7.1.8 7.2. Thermodynamic Characteristics of Different Refrigerants Efficiencies (COP-Coefficient of Performance) Volumetric Capacities Pressure Differences Pressure Ratios Suction Pressure Superheat Pressure Enthalpy Diagram (Mollier-h, lg p-Diagram) of R134 Pressure enthalpy diagram (Mollier-h, lg p-Diagram) of R600a Pressure enthalpy diagram (Mollier-h, lg p-Diagram) of a R290/R600a Blend Purity and Cleanness Standards Cleanness Standards Measurement of Cleanliness and Purity Working with R134a in the Refrigerator Laboratory and in the Production R134a Refrigerant General Characteristics of R134a, Ester Oil Evacuation Pumps Cleaning Technology for Vacuum Pumps for R134a Polyol Ester Oil or PFPE Oil, Cleaning process R134a Charging
70 70 71 71 72 72 72 73 74 75 76 77 77 77 78 78 78 78 78 78 79
Transfair Engineering: Designing and Prototyping of Refrigerator and Freezer Cooling Circuits. Contents
p. 5
7.4.4 7.4.5 7.4.6 7.4.7 7.4.8 7.4.9 7.4.10 7.5. 7.5.1 7.5.2 7.5.3 7.5.4
Brazing Leak Detection Working with R134a Circuit Elements Mixed Production during Transition from R12 to R134a or from R134a to R600a: Anti-Suck Valves, Suction Oil Separators or Glass Trap in Vacuum Pump Working with R600a in the Refrigerator Laboratory and in the Production Flammability and Hazardous Situations Flammability of R600a, Safety Precautions, Hazardous Situations Handling of Hydrocarbon Refrigerant Handling Precautions, Hydrocarbon Cylinders, Transportation, Storage Evacuation Pumps R600a Charging Service Charging Equipment, Hydrocarbon Charging Boards, Charging Liquid into Suction, Safety Approved Production Charging Equipment Exhaust and Ventilation of the Charging Area Alarm Board with Gas Sensors Fire Precautions and Fire Extinguishers Grounding and Anti-Static Floor Brazing Leak Detection Pressure Test, Mass Spectrometric Leak Test Further Precautions Determination of Refrigerant Filling Quantity Conversion from R12 to R134a, Conversion from R12 to R600a Refrigerant charging: Liquid or Vapour? Charging Accuracy Charging Methods Charging with Dial-A-Charge Cylinder, Charging by Weight, Charging by Sight Glasses Fine Tuning and Control of Charge Charging for Proper Superheat (Superheat Method) Charging for Proper Sub-cooling (Sub-cooling method)
79 79 80 80 81 81 81 81 81 82 83 83 83 84 85 85 85 85 85 86 86 86 86 87 87 87 88 88 89
91
8.3. 8.3.1 8.3.2 8.3.3 8.3.4. 8.3.5. 8.3.6 8.3.7 8.3.8 8.3.9 8.3.10 8.3.11 8.3.12 8.4. 8.5. 8.5.1 8.5.2 8.5.3
91 91 92 93 93 94 94 94 94 95 95 95 95 95 95 96 96 96 96 96 97 97 97 98 98 98
Transfair Engineering: Designing and Prototyping of Refrigerator and Freezer Cooling Circuits. Contents
p. 6
Scratch Test of Refrigerators Charged with Hydrocarbon Testing of Standard Electric Components not Reachable by Flammable Refrigerant Testing and control of n Protected Electrical Components Used in Hydrocarbon Leak Areas
99 99 100
9. TEMPERATURE CONTROL
9.1. 9.1.1 9.1.2 9.1.3 9.1.4 9.1.5 9.1.6 9.1.7 9.1.8 9.1.9 9.2. 9.3. Capillary Tube Thermostat Operation Range, Adjustment Range, Switching Differential, Correlation between Adjustment Range and Switching Differential, Tolerances, Adjustment in the Refrigerator Factory and in Service, OFF-Position, Dial Layout Standard Thermostat Thermostat with Auxiliary Switch Thermostat with Heater Contact Thermostat with Signal Contact Thermostat with Semi-Automatic Defrost Push-Button Thermostat with Fast-Freeze Thermostat with Fixed Cut-In Temperature Thermostat with a 3-Way Solenoid Valve Control Thermostat with 2 sensors Bimetal Thermostat Electronic Control and Thermocouples Child safe Switch-off, fuzzy logic for running modes: SuperCool, SuperFrost, DuraFreeze, SuperFrost, Frostmatic, Holiday, LCD display control, No-frost freezer defrost control, 3rd compartment near 0C Temperature, ice and water spender control, control of variable compressor speed Special Controls for NO Frost Models Defrost Timers and Defrost Thermostats Damper Thermostats Temperature Control Tests
101 101 101 102 102 102 103 103 103 103 104 104 104 105 105
108 108 109 109 109 109 109 110 110 110 110 111 111 111 111 112 113 113 113 113 113 113 113 114 116 117 117 117 117 117
Transfair Engineering: Designing and Prototyping of Refrigerator and Freezer Cooling Circuits. Contents
p. 7
Test of Absence of Odour and Taste Refrigerator Performance Test Calorimetric Tests 10.12. Refrigeration Circuit Measurement Positions Evaporator Temperature, Condenser Temperature Suction Condition, Delivery Condition, Liquid Return, High and Low Pressure 10.13. Test Panel 10.14. Refrigeration Performance Calculation 10.14.1 Properties 10.14.2 Equation of State 10.14.3 Extended Antoine Equation 10.14.4 Latent Heat of Evaporation 10.14.5 Ideal Gas Heat Capacity 10.14.6 Saturated Liquid Enthalpy 10.14.7 Liquid Density 10.14.8 Liquid Viscosity 10.14.9 Liquid Thermal Conductivity 10.14.10 Surface Tension 10.14.11 Saturated Vapour Density 10.14.12 Vapour Viscosity 10.14.13 Vapour Thermal Conductivity 10.14.14 Vapour Speed of Sound 10.15. Tables 10.15.1 R134a Liquid and Saturated Vapour Enthalpy and Latent Heat 10.15.2 R134a Liquid Density and Viscosity and Surf Tension 10.15.3 R134a Saturated Vapour Density and Viscosity, Thermal Conductivity and Speed of Sound 10.15.4 R600a Saturated Vapour Pressure 10.15.5 R600a Superheated Vapour Pressure Properties 10.16. Electromagnetic Compatibility Test 10.17. Cooling Circuit Pressure Test according to PED 11. 11.1. 11.2. 12. 12.1. Converting Household Refrigerators Converting Household Refrigerators from CFC-12 to HFC-134a Systems Converting Household Refrigerators from HFC-134a HC-600a Systems Standards EN Standards for refrigerators Household refrigerator, Safety Standards for Refrigerators and Freezers, Electric Components, EMC Electromagnetic compatibility, Commercial refrigerator, Absorption refrigerator, Valves, Compressor, Condenser, Filter Dryer, Acoustical noise, EU Directives ISO Standards IEC standards Some selected US Standards for refrigerators For refrigerators relevant EU Directives EU DIRECTIVE 2003/66/EC Energy labelling of household refrigerators amending Directive 94/2/EC EU Low Voltage Directive (73/23/EEC) as amended 93/68/EEC. EU Pressure Equipment Directive (PED) 97/23/EC EU ATEX Directives, ATEX Manufacturers Directive 94/9/EC, ATEX User Directive 99/92/EC CE Marking process
10.10. 10.11.
117 118 118 118 119 119 119 120 121 121 121 121 121 122 122 122 122 122 122 122 123 123 123 123 123 124 125 127 131 131 132 132 133 135 135
138 138 138 138 140 140 141 142 144 144 145 152
12.6.
ANNEXES Annex 1. Refrigerator and freezer appliances Annex 1.1. European Commission DIRECTIVE 92/75/EEC Energy labelling and standard product information of the consumption of energy and other resources by household appliances Annex 1.2. EU DIRECTIVE 2003/66/EC energy labelling of household electric refrigerators, freezers and their combination
I like to thank Danfoss and his employees in the research for the strong technical support granted to me, the received data and detailed information, without all these support this booklet could not have been written.
Transfair Engineering: Designing and Prototyping of Refrigerator and Freezer Cooling Circuits. 1. Introduction: Refrigeration Cycle - Definitions p. 8
1. INTRODUCTION
1.1. Refrigeration Cycle - Definitions
Total Heat Rejected (Enthalpy difference between compressor delivery and expansion device inlet Isothermal condenser temperature High Pressure (Isobaric condenser pressure) Subcooling (the enthalpy drop
between the saturated liquid in condenser and expansion device inlet) Liquid Return (temperature at inlet of expansion device)
Superheat (enthalpy difference between compressor suction and evaporator saturated vapour condition) Heat of compressor (Enthalpy rises as result of the compression process) Compressor Delivery (enthalpy of the super-heated vapour at the end of compression/ at compressor discharge) Delivery Condition (Temperature at
end of compression)
Pressure Ratio: derived from the condenser and evaporator pressure Refrigeration Effect (the
enthalpy difference between evaporator saturated vapour condition and the expansion valve condition)
Volume Flow/Mass Flow (based on the Low pressure (isobaric evaporator pressure) Isothermal evaporator temperature End of Evaporation (saturated vapour condition at
the evaporation temperature and pressure) refrigeration duty and the specific volume at the compressor inlet condition)
Specific enthalpy are calculated at a number of points around the cycle (100KJ/kg 0C liquid) Delta H Values: derived from specific enthalpy differences around the circle COP: Coefficient of Refrigerator Performance defined on the ratio of the refrigeration effect to the heat of compression. The basis of the refrigeration cycle and its circuit elements are explained in DANFOSS: Refrigeration - an Introduction to the basis, Nordborg, March 1978, http://www.danfoss.com/BusinessAreas/RefrigerationAndA irConditioning/Training+and+Education+New+design/ or on a profound level in: Althouse, A.D., Turnquist, C.H. and Bracciano, A.F.: Modern refrigeration and air conditioning, South Holland (Ill.) 1975; and Dossat, Roy J.: Principles of refrigeration. N.Y., 1981, which we cannot repeat here.
Transfair Engineering: Designing and Prototyping of Refrigerator and Freezer Cooling Circuits. 1. Introduction: Refrigeration Capacity, Thermal Losses p. 9
1.2.
The most important factor for a design of the refrigeration circuit, the compressor power etc., is to face the thermal leakage of the refrigerator or freezer cabinet or chest to be kept under special temperatures (for example < -18 C in a *** freezer, < -12C in a ** freezer, < -6C in a * freezer, < +5C (or <+7C) in a refrigerator against an ambient temperature of 32C or even 43C for a tropical version, depending on which standard will be applied. In case of a freezer we have to add the power which is necessary to freeze down a quantity of lean meat in addition to the thermal losses of a cabinet or chest. In standards it is fixed how much lean meat in which time has to be frozen down and to which temperature, for example according to one of the ISO EN standards, min 4.5 kg lean meat (=Tylose package) per 100l volume in 24 h, respective for >45l volume at least 2kg in 24h. Normally freezing power is in the range of 8-12 kg/100l/24h. These 2 factors together plus some reserves will decide about the size of the compressor power and the dimensions of other circuit elements. Some reserves are needed because not all the circuit elements are optimal and such systems have also to cover ageing processes. The system must be sealed to avoid leakage of refrigerant (see Transfair: Cooling circuit sealing chapter 5). In general the design of the refrigeration circuit depends on a quite considerable number of strictly connected variables. Not optimal conditions in evaporators, condensers and capillary tubes can reduce the balances and heat transmissions and the used power of the compressor and can increase the consumption of energy.
1.3.
1.3.1.
Following international (ISO), not only in Europe (EN) valid standards for refrigerators and freezers performance testing exists (for electric international standardisation it is the IEC, see chapter 1.3.3. Electric Safety): ISO EN 15502 (2005) specifies the essential characteristics of household refrigerating appliances, factory-assembled and cooled by internal natural convection or forced air circulation, and establishes test methods for checking the characteristics. It revises the following 4 standards, which are now withdrawn: ISO EN 7371 - Performance of household refrigerating appliances refrigerators with or without low temperature compartment; ISO 8187 EN 28187 - Household refrigerating appliances Refrigerators-freezers' characteristics and test methods; ISO EN 5155 - Household refrigerating appliances - Frozen food storage cabinet and food freezers characteristics and test methods; ISO EN 8561 Household Frost free refrigerating appliances, refrigerators, refrigerator-freezers characteristics and test methods.
Often under same number this standard are translated in EU national standards like AT (ON), BE (IBN/BIN), CH (SNV), CY (CYS), CZ ( CNI), DE ( DIN), DK ( DS), EE ( EVS), ES ( AENOR), FI ( SFS), FR ( AFNOR), GB (BSI), GR (ELOT), HU (MSZT), IE (NSAI), IS (IST), IT (UNI), LT (LST), LU (SEE), LV (LVS), MT (MSA), NL (NEN), NO (SN), PL (PKN), PT (IPQ), RO (ASRO), SE ( SIS), SI (SIST), SK (SUTN), and other ISO member countries have same or similar standards like JP (JIS), RU (GOST), US (ANSI/ASHREA/UL), IN (BIS), CN (SAC), BR (ABNT), CA (SCC) etc.
Such standards regulate which kind of performance tests has to be applied on all refrigerators and freezers types (see chapter 11) to make type approval (CE etc.), which ones on all refrigerators and which ones only on samples from the running production and how the volumes and consumption values have to be measured. For energy efficiency and labelling systems for household appliances, refrigerators and freezers exist in Europe EN153 (1995, new 2006), and rules 92/75/EEC, 94/2/EC and 2003/66/EC and in other arias similar regulations (see www.worldenergy.org ). In 2002 20% of sold refrigerators were of class A (low energy consumption, while 2002 already 47% as result of this labelling system. So 2003 A+ and A++ classes were introduced and since 2004 a new labelling scaling are under consideration. See Chapter 10.6. and Annex. For commercial refrigerators, not part of our booklet there exist adequate standards: EN ISO 23953 (2006) Refrigerated display cabinets Part 1 Vocabulary, Part 2: Classification, requirements and test conditions. And for its energy labelling of commercial refrigerators it is EN 441. For absorption refrigerator there exists the EN 732 (1998): Specifications for dedicated liquefied petroleum gas appliances Absorption refrigerators.
Transfair Engineering: Designing and Prototyping of Refrigerator and Freezer Cooling Circuits. 1. Introduction: Refrigeration Capacity, Thermal Losses p. 10
1.3.2.
Climate Classes
In these standards all refrigerators and freezers are classified according to the ambient temperatures under which they can conserve the requested inner temperatures (C): A freezer in a fridge-freezer model often only temperature controlled in the fridge, can defrost if kept in colder ambient as its climate class (see chapter 9.) Climate class Ambient Temperature from [C] to [C] Extended SN +10 +32 Temperate N +15 +32 Subtropical ST +18 +38 Tropical T +18 +43 Fresh food storage compartment t1, t2, t3 [C] tm [C] 0 10 +5 0 10 +5 0 10 +5 0 10 +5 *** [C] < -18 < -18 < -18 < -18 ** [C] < -12 < -12 < -12 < -12 * [C] < -5 < -5 < -5 < -5 Cellar compartment from [C] to [C] +8 +14 +8 +14 +8 +14 +8 +14
1.3.3.
There exist special standards which regulate the electrical safety requirements of refrigerators and freezers type approvals (CE etc.), their control and testing. Models using Isobutane or Propane have additional safety demands on their design and type approval tests (see chapter 8.2.-8.5). Furthermore the manufacturer has to insure that each produced refrigerator and freezer follow the requirement fixed for the type approval, by quality controls and inspection. Often following electrical safety tests are applied on all produced refrigerators and freezers (class 1 with PE): Earth test, continuity of electric bounding circuit test High voltage Test (=flash test or Dielectric strength test Insulation test and electric strength Power and current absorbed test Leakage current test Residual Voltage test (if the refrigerator and compressor performance is improved by a capacitor). Details see in chapter 8.5.1. In addition other parameters like correct wiring, earth connection, IP54 sealing, functioning of all electrical components like switches, thermostats, signal lights, light switches, light should be inspected and/or tested. The safety standards specify which electrical safety rules the manufacturer have to respect, which electrical components acc. to which electrical standard he can use in the appliances and which kind of approval he needs. Following meanwhile international valid safety standards exist for household refrigerators and freezers: - IEC-EN-UL-J-GOST etc. Standard 60335 (2002), Part 1: Safety of household and similar electric appliances, and - IEC-EN-UL-J-GOST etc. Standard 60335, Part 2-24 (2002): Particular requirements for refrigerators and food freezers. Amendment 1 (2005) and Amendment 2 (2007) or consolidated Standard 60335, Part 2-24 Version 6.2 (2007). - IEC-EN-UL-J-GOST etc. Standard 60335, Part 2-89 (2007): Particular requirements for commercial refrigerating appliances with an incorporated or remote refrigerant condensing unit or compressor, Vers. 1.2. The electric safety of commercial refrigerators are described in IEC 60335-2-89 and of commercial dispensing appliances and vending in IEC 60335-2-75. The IEC 60335-2-24 and 2-89 was amended 2002 and 2005 to cover potential risks originated from the use of flammable refrigerants; for refrigerators and freezers using flammable refrigerants (R600a, R290) following was integrated into this standard - to carry out risk assessment of flammable gar refrigerants according to CEN/TR 14739 (2004): Scheme for carrying out a risk assessment for flammable refrigerants in case of household refrigerators and freezers; and - to control flammability risk according to CENELEC Test Schedule TS 95006; see chapter 8.5.. The Amendment of 2007 did not touch test procedures, but text and reference to other changes or cancelled standards. Such safety standard has to be applied in addition to the performance standards of refrigerators: EN ISO 15502 (previously the 7371, 8187, 8561 and 5155, now withdrawn). The above mentioned IEC 60335-2-24 amended in (2005-04) should be respected today in case Hydrocarbon is used as refrigerant. It based on the application of the existing electrical safety standard IEC 60079-15 Electrical apparatus for explosive gas atmospheres, Electric apparatus with type of protection n". For further details see chapter 8.
Transfair Engineering: Designing and Prototyping of Refrigerator and Freezer Cooling Circuits. 1. Introduction: Refrigeration Capacity, Thermal Losses p. 11
To simplify the calculation an average thickness of sloping surface can be considered as well as an average material transmission coefficient [x mm polyurethane + y mm S/B (high impact polystyrene)].
Transfair Engineering: Designing and Prototyping of Refrigerator and Freezer Cooling Circuits. 1. Introduction: Refrigeration Capacity, Thermal Losses p. 12
We neglect in the 2 door models the heat transmissions between refrigerator and freezer compartment as their sum is 0 kcal/h.
Calculation:
= thermal losses
= 9,12 kcal/h = 3,65 kcal/h = 3,14 kcal/h = 3,14 kcal/h = 4,21 kcal/h = 13,51 kcal/h = 9,15 kcal/h = 8,29 kcal/h = 5,83 kcal/h = 7,49 kcal/h = 3,04 kcal/h = 6,34 kcal/h = 7,94 kcal/h 84,85 kcal/h
Refrigerator door area: (1/0,035) x 0,02 Crisper supper area: (1/0,035) x 0,02 Crisper back area: (1/0,035) x 0,02 Compressor upper area: (1/0,035) x 0,02 Crisper side area: (1/0,035 x 0,02 Refrigerator side area: (1/0,035) x 0,02 Refrigerator back area: (1/0,035) x 0,02 Refrigerator door gasket: (1/0,017) x 0,07 Freezer side area: (1/0,05) x 0,02 Freezer back area: (1/0,05) x 0,02 Freezer door area: (1/0,05) x 0,02 Freezer upper area: (1/0,05) x 0,02 Freezer door gasket: (1/0,017 x 0,07 Total transmission losses:
The various figures of t in the different sections of the cabinet show that the insulation thickness on the backside of the cabinet and the compressor area should be increased to reduce thermal loss and that also the space for heat transmission through the door gaskets should be as much as possible reduced and the door gaskets should be improved to improve the refrigerators. These 84,88 kcal/h are needed to face all dispersions at 43C ambient temperatures. To obtain the thermal losses for an ambient temperature of 32C we have to multiply the a.m. items instead of 38C with 27C in the refrigerator and instead of 66C with 55C in the freezer (only the refrigerator's backside remains at 50C, freezer's backside at 78C and the compressor area at 55C). The formula to determinate the power necessary to freeze 5 kg lean meat (Tylose packs) in 24 hours is following: P = 1/24[(G*C* +t1) + (G*Cl) + (G*C* t2)] whereby: P = G = c = t1 = Cl = t2 = 1/24 Input power in kcal/h weight to be frozen in kg specific heat in kcal difference between external temperature and 0C latent heat in kcal/kg difference between 0C and - 18C to calculate freezing power per hour instead of freezing inside 24 hours.
The specific heat and the latent heat for lean meat (Tylose pack) values are as following: C = 0,77 kcal Cl = 60 kcal/kg so in this case we come to following freezing power: P = 1/24 [(5*0,77 kcal*32)+ (5*60) + (5*0,77*18)] = 20,52 kcal/h This freezing power has to be added to the 84,85 kcal thermal transmission losses to determine the needed compressor power which is in this case 105,37 kcal/h. As a compressor should not run permanently, but only in the range of 60-65% and 15% should be added as reserve for not optimal circuits, the compressor power should be in the range of 105,37 kcal/h * (100 +15)/62,5% = 193,88 kcal/h Transfair can provide an Excel simulation and optimization program to minimize thermal losses and foam consumption.
Transfair Engineering: Designing and Prototyping of Refrigerator and Freezer Circuits. 1. Introduction: Cabinet Constant, Reduction of Thermal Losses p. 13
Transfair Engineering: Designing and Prototyping of Refrigerator and Freezer .Circuits. 1. Introduction: Polyurethane Foam Tests, Thermal Bridges p. 14
Measurement of the foam density in case of test shots. Usually, approx. 800 g of material are shot into a polyethylene bag, presenting a diameter of about 30cm. 2 to 4 hours later, a sample of 10cm x 10cm x 10cm is cut from the middle of the foam produced in this way. This test specimen is weighed and the weight either divided by the calculated volume or by the weight of water pushed away by the test specimen dipped in water according to the a.m. principle of Archimedes. The quotient from mass and volume is defined as free rise density.
Dimensional Stability. The dimensional stability can be determined in the following way: - Cut/saw a test specimen, size approx. 10 cm x 10 cm, off the refrigerator. - Remove the cover sheets. - Determine the dimensions of the test specimens (height, width, length). - Store one test specimen for 24 hours at -30C, another one for 24 hours at +80C. - Determine the dimensions again afterwards.
Compression Strength. Foam samples of about 30x30x30 up to 40x40x40mm of cabinet measured in 2 directions (in PU foam flow direction and 90 to flow direction).
Transfair Engineering: Designing and Prototyping of Refrigerator and Freezer .Circuits. 1. Introduction: Polyurethane Foam Tests, Thermal Bridges p. 15
2x4 foam samples taken of side walls 300mm from front side (2x2 in side walls of fridge compartment, 2x1 in middle separator, 2x1 in side walls of freezer compartment) 1 sample top, 1 sample bottom, 3 samples in back wall (2 in fridge back wall, 1 in freezer back wall).
For Cyclopentane driven PU foam minimum compression strength should be 140-145kPa. For Cyclopentane/Isopentane driven PU foam minimum compression strength should be 135-140kPa. Such compression strength measurement replaces today in praxis more and more the foam density distribution measurements.
Verification of the Reaction Parameters in the Laboratory. Following material and equipment is needed: a beaker of hard paper of about 0.6-1 litres (for examples Messrs. Kamphemann, No. 600, non-waxed, Volume 660 cm from Heinrich Kamphemann, P.O.Box 2604, D-49016 Osnabrck, Tel.: 0541-32037, Fax: 0541- 23565, laboratory stirrer, 0, 5W, 1300/min) with disk 60-65mm, laboratory balance 0,1g accuracy, water bath, knife/saw and glass bar to be used in following procedure to determine the reaction parameters: The components are tempered in a water bath at 20C +/- 1C. The paper beaker is put onto the balance and tarred. Component A is submitted first, and component B is added subsequently in the corresponding mixing ratio; the weighed-in quantity should be in total 70g. Both components are then mixed at 1300m-1 for approx. 10 sec. The stop-watch is started as stirring begins. Tests: Cream Time is defined as time interval from start of stirring to visible volume expansion in the beaker. String Time is defined as time interval from start of stirring to the moment when it is possible to draw fibres out of the reaction mixture by means of a glass bar. Rise Time is defined as time interval from start of stirring to visible termination of volume expansion. Raw Density. After the foam surface has cured, the foam is cut off directly at the edge of the beaker. The beaker is put onto the balance. The mass indicated is divided by the volume of the beaker (660 cm ).
Assurance of a Continuous Quality. A continuous quality control should measure regularly the following: Measurement of the foam reaction INSPECTIONS INTERVALS parameters of test shots: the free rise Free rise density of the core at least twice a day density and string time at least twice a String time at least twice a day day; Shot weight at least twice a day Comparison of set and really reached Dimensional stability at least twice a day shot weight every day by random Compressive strength at least twice a day sampling. Mixing ratio once a day Dimensional stability: samples should be Distribution of core density once a day taken from refrigerators/doors every day in order to check the dimensional Operational compressions/pressures of the machine at least twice a day stability, and if possible, the compressive strength as well. The verification of the correct mixing ratio is also necessary.
Transfair Engineering: Designing and Prototyping of Refrigerator and Freezer .Circuits. 1. Introduction: Polyurethane Foam Tests, Thermal Bridges p. 16
Testing of the air tightness of door or lid seals. The purpose of this test is to ensure that the gaskets of the doors or lids of the appliance adequately prevent any abnormal ingress of the surrounding air. The test are executed under an ambient temperature between 16-32C on the switched off appliance with the same temperature inside the cabinet. A strip of paper 50mm wide and 0.08 mm thick and with a suitable length shall be inserted at any point of the seal, and the door or lid closed normally on it. The seal shall be assessed by checking that the strip of paper does not slide freely. The most unfavourable point can be found by lightening the closed cabinet from inside and checking the light from outside of all seals. The test should be repeated after the durability test acc. New ISO 15502 (previously according to chapter 11 of the a.m. ISO standards 7371, 5155 and 8187 (see in chapter 10.3. of this booklet under Mechanical tests).
Door Gasket
Only in freezer: AntiDew coil
Foamed Door
Foamed Cabinet
Transfair Engineering: Designing and Prototyping of Refrigerator Circuits. 2. Compressor, Replacement of CFC-12 Compressors, Compressor Capacity p. 17
2. COMPRESSOR
In this chapter we can and will not consider how compressors can be developed or optimised using different geometrical, electrical and other characteristics and different kind of refrigerants with different pressure ratios, swap volumes etc. Such considerations should be part of compressor manufacturing study which is not part of our work. We only have to concentrate on the correct selection and use of already optimised compressors in the cooling circuit of household refrigerators.
Transfair Engineering: Designing and Prototyping of Refrigerator Circuits. 2. Compressor, Replacement of CFC-12 Compressors, Compressor Capacity p. 18
2.2.1. HP Value
The previously used HP designation has been more and more abandoned, because the HP value does not define any refrigeration characteristics of the compressor.
Transfair Engineering: Designing and Prototyping of Refrigerator andCircuits. 2. Compressor, Starting Characteristics, Electrical Diagram, Lifetime
p. 19
Transfair Engineering: Designing and Prototyping of Refrigerator andCircuits. 2. Compressor, Starting Characteristics, Electrical Diagram, Lifetime
p. 20
Pay attention: R134a and R600a COP optimised compressors are often not designed for developing countries with difficult electrical and climate conditions. Especially R600a compressor made for this conditions are still rare. A run capacitors in a RSCR or RSR system normally increases the efficiency (COP) of a compressor by 8-10 %; therefore it can reduce the energy consumption by 3-5 %. In case of a HC-600a compressors with a general temperature decrease in the compressor the effect of the run capacitor is even significantly higher.
2.5. Lifetime
In general the compressor life depends on how far the compressor is protected against motor overloads. The careful dimensioning of the refrigeration system, a thorough assessment of the operating conditions of the compressor at expected limit of loads. If it is over dimensioned the energy efficiency will be reduced, if it is under dimensioned the lifetime will be reduced. Long working life and problem free operations of hermetic compressors depend on 4 conditions: 1. 2. 3. 4. The compressor must have enough starting torque to overcome the pressure conditions in the refrigeration system at moment of start. The motor must have sufficient breakdown torque to overcome the loads which occur in connection with start run-ups and during operation. To allow refrigeration systems with LST compressors a pressure equalisation the stand still time is minimum 3 min. often even 5 min. which must be insured by the thermostat. Very important is the well-dimensioned condenser surface and a good ventilation of the compressor. The max. condensing temperature must not exceed 60C, at peak time 70C in the highest ambient temperature. The winding temperature of the compressor motor should not exceed 110C for a R12 system, 120C for an R134a system and 125C for an R600a system plus 10C during short peak loads.
Compressors working with lower voltages as designed for increase their temperature during operation in a way that after few years running the compressor oil becomes greasy so that the mechanical resistance will even increase under the bad electrical power supply conditions and the compressor coil inside the oil will burn down. That is the main reason why the life time of compressors in developing countries are often less than 6 years while in developed countries it is very, very seldom that a compressor in a household refrigerator has to be replaced during the time the refrigerator is used (about 10-12 years in developed countries).
Transfair Engineering: Designing and Prototyping Circuits. 2. Compressor, Heavy duty, Comparison between and R12 and R134a Compressors
p. 21
Often such heavy duty compressors are over dimensioned in comparison to the nominal refrigeration duty for such application. The oversized compressor will surely increase the energy consumption, but will last much longer.
Transfair Engineering: Designing and Prototyping Circuits. 2. Compressor, Heavy duty, Comparison between and R12 and R134a Compressors
p. 22
Parameters Evaporating pressure (-25C) bar Condensing pressure (55C) bar Enthalpy i2 (-25C/32C) kJ/kg Enthalpy i1 (55C liquid) kJ/kg Enthalpy difference i2- i1 kJ/kg Compressor capacity W kg/h Mass flow ( capacity/(i2- i1) x3600/1000 ) Gas temperature -inlet cylinder C Specific volume m/kg Volume flow - inlet cylinder m/h Inlet throttling device C Specific volume dm/kg Volume flow dm/h kJ/kg Enthalpy i1 (55C liquid) Enthalpy is (32C liquid) kJ/kg kJ/kg Enthalpy difference i1- is Capacity with sub cooling to 32C: Mass flow i2-is kJ/h Capacity without sub cooling to 32C:Mass flow i2-i1kj/h Performance relation (i2- is )/(i2- i1 )
R12 1.237 13.66 373 254 119 95 2.87 94 0.2 0.57 55 0.841 2.41 254 231 23 407.5 341.5 1.19
R134a 1.067 14.912 431 279 152 87 2.06 84 0.28 0.57 55 0.927 1.91 279 244 35 385.5 313.1 1.23
Transfair Engineering: Designing and Prototyping Circuits. 2. Compressor, Heavy duty, Comparison between and R12 and R134a Compressors
p. 23
pores). But the thermal reliability and stability of R134a/esteroil systems in comparison to R12/mineral oil systems are better. One severe quality problem of compressors is the humidity already in oil, which should not exceed 1/10 of dryer capacity (about 1g), that means 100mg water (125ppm for 280ml oil). 9. If system components are not changed 10% less R134a charge are needed in comparison to R12. 10. R134a can escape through minor leaks than R12. Therefore higher standards in soldering operations, in sealing the circuit and in leak detection are needed.
By switching from R12 to R134a compressors and by switching from R134a to R600a compressors the leading manufacturers of compressors and also the leading refrigerator producers have made a lot of efforts to improve the energy efficiency of their systems. In comparison to old R12 systems the new CFC free systems are much more efficient and the energy consumption much lower. But some of this improvement cannot be used in developing countries with low voltages and clock problems as some of the new compressors are more sensitive in this aspect as old not optimised ones. Further details can be taken in the following chapters.
2.8.3. A Comparison Test of R134a and R12 Compressors from National Matsushita
Furthermore please find enclosed the 2 tables with comparison data of reciprocal using a piston and of rotary compressors of National Matsushita for CFC 12 and for HFC 134a refrigerants which came to similar results: R12 vs. R134a reciprocal compressor comparison (on model D120LRAA 115V 6HZ0) R12 vs. R134a rotary compressor comparison on a 13 cu ft (370l) cabinet (Model NR-D37V1) kWh/day Energy Consumption Btu/h Kcal/h Capacity
Amount of Charge Refrigerant Condenser size Compressor model (100V 60 Hz) Refrigerant charge g Energy consumption acc. to JIS kWh/mo % Running time at 30C % at 15C % CFC-12 A RA48L 185 36.6 Base 57.9 29.8
Evaporation Temperature HFC-134a A RA48L 185 38.8 +6.0% 63.5 31.3 A+B RA48L 190 37.1 +1.0% 59.0 32.9
Transfair Engineering: Designing and Prototyping Circuits. 2. Compressor, Heavy duty, Comparison between and R12 and R134a Compressors
p. 24
Freezer C Fresh food C Evaporator inlet C Evaporator outlet C Discharge 2 C Shell C Condenser outlet C Condenser pressure kgf/cmG(psig) Suction pressure kgf/cmG(psig)
It will be described later how condensers and evaporators can be improved and the system can be optimised. We only want to mention how thermal losses can be eliminated. First the door gasket sector, the construction but also the welding of the door gasket can be improved by avoiding air leakage in the corners and by reducing the space between door and cabinet. The construction of this closing sector and of the door gasket can be improved by using specialised companies like Rehau in Erlangen/Germany or Ilpea in Malgesso/Italy, the 2 mayor suppliers of door gaskets in Europe.
We also recommend looking carefully at the construction of the door cabinet section of such refrigerators and freezers which have very low energy consumption to find an optimal own construction. Last not least areas towards the backside condenser and towards the hot compressor department need bigger insulation as it could easily be seen on the calculation of thermal losses in the previous chapter. With all these efforts an increase of power of the compressor by switching from R12 to R134a systems can be avoided.
2.9. Comparison Tests of R600a, R134a and R12 Compressors from Necchi
Necchi has compared in test series different compressors already optimised for the refrigerant used. They have first tested the compressors only with a calorimeter, than they have mounted them on household refrigerators from running productions. Following tests results were achieved:
Transfair Engineering: Designing Circuits. 2.9. Compressor, Comparison between R600a, R134a and R12 Compressors (Necchi), Energy optimized p. 25
Displace- Cooling capa- Energy efficiency ment (cc) city (kcal/h) ratio (w/w) 3.50 65 0.93 4.10 75 0.98 5.12 101 1.07 5.55 112 1.10 7.00 127 1.16 7.75 148 1.15 8.20 160 1.17 10.60 212 1.15
2.9.2. Fridge/freezer Tests using R600a, R290/R600a Mixture, R134a and R12 Compressors
Aim of these tests of Necchi was to identify the behaviour of refrigerators on charges of different gases and compressors. Only the charge quantity and capillary tube were optimised while the evaporators and condenser were not modified. Necchi uses refrigerator models from running productions.
Vertical Freezer
Nominal Volume Refrigerant Charge (g) Compressor type(cc) Freezing temperature(C) Energy conservation(kWh/24h) Running % 120 l R12 95 5.5 -18 1.43 40 290 l 250 l 140 l R290/ R600a R290/ R12 R600a R12 R134a R600a R600a R600a 55 54 50 160 65 110 100 37 5.5 13 8.5 7 11 4 5 8 -18 -18 -18 -18 -18 -18 -18 -18 1.50 1.41 1.48 1.86 1.62 1.25 1.37 1.24 49 35 40 55 62 56 55 51
Transfair Engineering: Designing Circuits. 2.9. Compressor, Comparison between R600a, R134a and R12 Compressors (Necchi), Energy optimized p. 26
Conclusions (Part 3)
Cooling capacities. The R134a application is producing a slightly lower capacity than the R12. The cooling capacity of R600a is approximately 50% in all evaporating temperatures that mean that the displacement of the compressor must be increased to reach the same performance on a given application. R290/600a mixtures were very similar in this point to R12 applications. Coefficient of performances. R600a applications show in these tests better COP values than R134a applications. The difference even will be increased by applying run capacitors in so called high efficiency versions which seems to increase the R600a version slightly stronger than the R134a version. But this needs further systematic studies. R600a displacement increase. The needed increase of displacement of an R600a compressor was smaller than theoretical expected. The actual temperatures of compressors along the thermostatic controlled cycles were lower than calculated for R600a with the effect that the gas densities and consequently the volumetric efficiency of R600a compressors were better than calculated. Run capacitors will even increase this effect. Charge tolerances. The sensitivity on charge tolerances differ very strongly between R134a and R12 on one side and R600a on the other side. R12 and R134a household refrigerator systems tolerate 10-20 g charge variations without a significant effect on the energy consumption while R600a reacts - not only because of a much lower quantity of charge - very sensitive on deviations from the optimal charge quantity. +/-5 g deviations changes the behaviour of the system very much. (Personal remark: Many refrigerator producers try to keep the charging tolerance of R600a household refrigerators in the limit of 1g). R290/R600a drop-in solution. HC blends can be considered as drop-in solutions for existing appliances for R12 as long as the refrigerator fulfils the safety requirements and tests according to IEC600335-2-24 (1997-08). Noise. R600a compressors produce 2 dB(A) less noise than R12 compressors and 3-4 dB(A) less than R134a compressors. But on some models a slight increase in noise were noticed and the cause was not understood and need further studies. Overall dimension of compressors. 160kcal/h can be obtained by 8 cc R134a or by 13 cc R600a. The increase of displacement of an R600a compressor cannot be always made inside the same housing and in some cases a step-up in the compressor family is required. Lubricant. R134a needs the use of Polyol ester lubricant with some bad consequences in comparison to R600a and R12 systems: - much higher hydroscopic in comparison to mineral oil used in R600a compressors, - slightly lower thermal stability in connection with anti-wear additives, - solubility, not all ester oils get it at all temperature ranges, - limited material compatibility (chlorine etc.). Sludge formation. Such lubricant problems of R134a systems have bad effects on the performance as a result of the so called sludge formation of the capillary tube which does not exist in R600a or R12 systems. Reasons for the sludge formations are: - Excessive moisture content. Through hydrolyse of the ester oil an acid can be produced which react to carbossilates (a metallic salt) This effect can be reduced by strong cleanness controls on all circuit components and by much more efficient dryers (3A pores on molecular sleeves). Any additive which can act as catalyst must be avoided. -Excessive oxidation of the oil. As final result of oxidation, ester decomposition and their reaction with metal ions can be a metal salt, which can be avoided by high vacuum before charging. - Chlorine. Chlorine in combination with heat decomposes ester with the same result as mentioned above. Therefore chlorine often used in productions as cleaning material must be avoided and such pollution need to be controlled. -Temperature. Under bad conditions higher temperatures are reached with R134a as with R600a systems. Such higher temperatures causes deterioration on ester oil, if not compensated by higher quality requirements for ester oil for R134a as required for mineral oil for R12 and for R600a. Such effects are strongly increased by impurities coming from system pollution (mineral oils, oligomers extracted from plastics, etc. The stricter control on cleanness of all R134a refrigeration circuit components is vital for its long life, but it improves the efficiency of all systems. Solubility of R600a in mineral oil and foaming. But also the selection of mineral oil in R600a systems and the quantity of R600a in the oil is not unproblematic. If in big refrigerators the quantity of R600a becomes too high the lubricant viscosity can be strongly effected and microscopic foam can be built between the friction surfaces so that the film can break if traditional naphtenic lubricant were used. So also the selection of lubricant is important for R600a compressors.
Transfair Engineering: Designing Circuits. 2.11. Compressor, Energy and High Energy Optimised Compressors, Variable Capacity Compressor
p. 27
Humidity. The humidity is also a problem for R600a systems to reach high quality. Humidity can be removed from evaporator and condenser by dry air, but it is today practically impossible in the refrigerator factories to remove it from the refrigerant itself and from the compressor oil. These are the 2 severe quality problems as it is already in the refrigerant and in the oil, both should not exceed 1/10 of dryer capacity (about 1g), that means for the compressor oil 100mg water (125ppm for 280ml oil). Flammability. The flammability of R600a is their weak point even it is relatively small risk because of the small charging quantity present in domestic appliances. On the compressor the risk can be prevented by using a flame-quenching overload protector and PTC starting device which eliminates any ignition point near the compressor. (Other measures to be taken concerning light and thermostat etc. will be considered in Chapter 8). Compressor costs. As consequences of the above mentioned items needed for R134a compressors, especially the higher costs of the Polyol ester oil and needed the higher purity and cleanness standard for R134a the R600a compressor price should be equal or lower than the R134a compressor. But this cost calculation is only valid for displacement ranges reachable inside the same overall dimension so that no upsizing is needed. (Other costs concerning other electrical components of the refrigerator like ex-proof lamps or thermostats - if needed in single cases of constructions - are not considered here, but will be considered in Chapter 8). Necchi came to the conclusion that R600a systems for household refrigerators are under economical, ecological and efficiency point of view feasible and the global overall costs should be not higher than the one for R134a, considering the changes needed to prevent any risks coming from the flammability of the gas. E. Biscaldi: CFC substitutes (R600a and R134a): performance, manufacturing, and costs from the compressor point of view. ECO-Refrigeration. Conference on Hydrocarbon Fluids in Domestic and Commercial Refrigeration Appliances. 13-14.2.1996.
Transfair Engineering: Designing Circuits. 2.11. Compressor, Energy and High Energy Optimised Compressors, Variable Capacity Compressor
p. 28
Embraco VCC models. Electronic controls as needed to control the variable speed of the compressors are normally also used to control the temperatures of the food compartments (by thermocouples instead of thermostats).
Danfoss grant a program called RS +3 which allow to calculate and select the right Danfoss compressors upon fundamental cooling circuit data under
http://www.danfoss.com/Germany/BusinessAreas/RefrigerationAndAirConditioning/Product+Selection+Tools+details/R Splus3.htm
Transfair Engineering: Designing and Prototyping of Refrigerator and freezer Cooling Circuits. 2.12. Compressor testing and performance data
p. 29
US-Standard ANSI/ASHRAE 23(2005): Methods of Testing for Rating Positive Displacement Refrigerant Compressors and Condensing Units. This standard applies to the methods of testing for rating single-stage positive-displacement refrigerant compressors and condensing units that (a) do not have liquid injection and (b) are operated at subcritical (saturated) temperatures of the refrigerant. It also applies to the methods of testing for rating single-stage positive-displacement refrigerant compressors and condensing units that (a) incorporate liquid injection that is controlled by a steady flow rate method and (b) are operated at subcritical (saturated) temperatures of the refrigerant.
EN 13771-1 (2003 /2005): Compressors and condensing units for refrigeration - Performance testing and test methods - Part 1: Refrigerant compressors. This part 1 of the European Standard applies only to refrigerant compressors and describes a number of selected performance test methods. These methods provide sufficiently accurate results for the determination of the refrigerating capacity, power absorbed, refrigerant mass flow, isentropic efficiency and the coefficient of performance. This standard applies only to performance tests conducted at the manufacturer's works or wherever the equipment for testing to the accuracy required is available. The type of measuring instrument and the limits within which measurements shall be made are listed in normative annex A.
The electric safety of compressors have to be controlled by compressor manufacturer according to IEC EN 60335-1 and IEC EN 60335-34 and a CE conformity declaration of compressor manufacturer including the conformity to EU Low Voltage Directive 73/22/EC and the EU PED 93/23/EC has to become part of type approval of the refrigerator.
Transfair Engineering: Designing and Prototyping of Refrigerator and freezer Cooling Circuits. 2.12. Compressor testing and performance data
p. 30
Transfair Engineering: Designing and prototyping of Refrigerator Circuits. 3.2. Condenser, Skin Condenser on Refrigerator or Freezer Cabinets
p. 31
3. CONDENSER
3.1. Static Condensers
Static condensers are air cooled condensers mounted on the back side of a refrigerator or freezer. There exist 2 types:
Ks = whereby:
Ks = condenser constant in kcal/h C t = the temperature difference between the condensing temperature and the ambient temperature which is normally in the range of 23C. In our sample the condenser should have the Ks value Ks = 190*1,25/23 =10,33.
This Ks value allows us already to determine from the condenser suppliers' catalogue (for example Bundy or Benteler) which condenser with which Ks value can be selected inside the maximum size of the cabinet width and height. There exist tubing of 5mm or 6mm, different serpentine's radius and different distances and diameter of wires (pitches) welded on the serpentines (in case of wire-on-tube condensers is selected).
Transfair Engineering: Designing and prototyping of Refrigerator Circuits. 3.2. Condenser, Skin Condenser on Refrigerator or Freezer Cabinets
p. 32
Qk = Qo + N - Qh (kcal/h) whereby: Qo = N = Qh = Evaporator capacity and increase of enthalpy up to the cylinder Compression work in kcal/h Heat emission from compressor pot.
The N and Qh values can be received from the compressor manufacturer for the selected compressors. By this way the condenser's capacity can be calculated out of the evaporator capacity or vice versa. For an air-cooled condenser the condenser capacity Qk can be also calculated according to the formula: Qk = k * A * t(kcal/h) whereby: k= A= t = Transmission coefficient (Kcal/h x m x C) Effective condenser area (m) Temperature difference between condensing temperature and air temperature in C.
The transmission coefficient and the effective condenser area can be granted by the condenser manufacturer. The t will be defined by the measured ambient and condensing temperatures; therefore we can calculate out of the needed condenser capacity value Qk the condenser size, which has the maximum width of the refrigerator and the length according to the calculated condenser area. The condenser capacity can also be expressed by the circulated quantity of the refrigerant in the following way: Qk = G * i = G * (i1-i2) whereby: G= i = t1 (i1) t2 (i2) the circulated quantity of refrigerant [kg/h] enthalpy loss from the condenser inlet to the condenser outlet [kcal/kg) designate temperature and enthalpy respectively at the compressor discharge connector/ condenser inlet; the condition at the condenser outlet, while t3 is the ambient temperature at the condenser's surface and air.
Out of this data which can be taken from similar systems by measurement or during optimisation of the system itself we can calculate the effective condenser area in the following way: A= ( G* i)/(k* t) = [Gx(i1-i2)]/[k*(t2-t3)*m]
Transfair Engineering: Designing and prototyping of Refrigerator Circuits. 3.2. Condenser, Skin Condenser on Refrigerator or Freezer Cabinets
p. 33
By varying the distance of the tube (see the next table underneath) the Uvalue of the condenser is influenced. For example for tube spacing of 45 mm the U-value is nearly double as high as for tube spacing of 100mm. But the reduction of the tube spacing has limits and it strongly increases the material costs. Often lowest relative material costs per output unit are reached with a tube spacing of 60 mm. The wire spacing is economically at 6mm with wire diameter of 1,5 mm. The tube size selected is normally 5-6 mm dia. The 5 mm needs fewer refrigerants but for a larger refrigerator or freezer it needs high maximum condensing pressure. The bigger tube results in longer pressure equalising time of the system and this can cause starting trouble. The reduced charge inside a 5 mm condenser results in lower equalisation pressure and improves the starting conditions for smaller compressors during initial start-up. But the 5mm condenser and discharge tube causes larger pressure drops and during start and pull-up of the compressor the starting capacity of the compressor will be reduced, especially if it starts from high equalising pressure.
Transfair Engineering: Designing and prototyping of Refrigerator Circuits. 3.2. Condenser, Skin Condenser on Refrigerator or Freezer Cabinets
p. 34
Transfair Engineering: Designing and prototyp Circuits. 3.2. Condenser, Skin Condensers on Chest Freezes, Condenser Capacity, Increase of Insulation p. 35
Skin type condenser for chest freezer (32C ambient temperature): Relation between gross volume, tube length, tube distance and k-value (go along the array inside the 3 grids):
Transfair Engineering: Designing and prototyping of Refrigerator Circuits. 3.6. Condenser, Testing Condensers, Condenser Capacity, Comparison Test p. 36
Door Gasket Upright freezer or fridge freezers need an anti-dew coil because of the high Magnetic Strip temperature difference between outside and inside to raise the temperature of the Plastic Liner cabinet front area beside the door to avoid dew fall. In addition this coil is a part of Plastic Liner Anti-Dew Coil Anti-Dew Coil the condenser which will reduce the condensing temperature. Important for the construction is to avoid thermal bridges between the inside and the outside Steel Side cabinet; this depends mainly on the link between the steel cabinet and the plastic Panel food liner. In so called cold bridges the heated steel warms up the inside. To insert it into the front profile can cause tension in the steel liner joint and can cause planetary problems. There are 2 ways of connecting this coil to the system: 1. the most efficient anti-dew way is to connect it between the discharge Foamed Door Foamed Door connector of the compressor and the inlet of the condenser. But it can cause a thermal bridge. 2. The other way is between condenser outlet Door Gasket Door Gasket Magnetic Strip Magnetic Strip and capillary inlet, in which anti- dew coil temperature is already Plastic Liner Plastic Liner lower.
Foamed Cabinet
Anti-Dew Coil
Anti-Dew Coil
Foamed Cabinet
Foamed Cabinet
Only if bad links are used and if insulation thickness is low the dew coil effect should be reduced by inserting the coil between the condenser outlet and the capillary inlet and their position should be placed more away from the front side. Optimal position of anti-dew coil and insulation to inside
In the a.m. figure the Mollier diagram (i-log p) is shown and refers with t1, t2, t3 to the oil cooling condenser. In this diagram it can be seen that a large portion of the superheat of the compressed refrigerant between the t1 and t2 points are removed by the oil cooler. The optimum oil cooling is reached by dimensioning the oil cooling condenser to remove the superheat of the compressed gas and a partial condensation of the refrigerant is produced to prevent the thermal increase in the cooling coil from creating superheat. In his way the increased enthalpy of i3-i2 is achieved to reach the lowest temperature as possible in the entire oil-cooler and to reach an optimum value of the internal heat transmission coefficient of the oil cooling coil. To reach an optimum oil cooler the temperature's increase on the oil cooler coils between the oil cooler should be measured. It is recommended that 50% of the total condenser surface should be used for an oils cooling condenser. Oil cooling condensers need compressors with oil outlet and oil inlet tubes.
Foamed Cabinet
Transfair Engineering: Designing and prototyping of Refrigerator Circuits. 3.6. Condenser, Testing Condensers, Condenser Capacity, Comparison Test p. 37
The advantages of such a fan cooled system are that the condensers need less space and it can be often easier installed or serviced. The disadvantage is the fan noise, more frequent services (fan failures, collected dirt in the condenser) and it is often more expensive than a static condenser. The U-value is highest when the condenser is mounted horizontally and lowest at vertical position. The capacity increases by the air velocity. (See: Literature: Cube, H.L.V., and Tofahr, G.: Formes conomiques de condenseurs pour armoires frigorifiques mnagers).
Transfair Engineering: Designing and prototyping of Refrigerator Circuits. 3.6. Condenser, Testing Condensers, Condenser Capacity, Comparison Test p. 38
The compressor capacity is expressed by the compressor displacement in cm. The table applies to a 2 poles 50 Hz compressor in the range of M/LBP (-40C to - 5C) and HBP (-5C to +15C). The recommended condenser surface is sufficient for ambient temperature of up to 32C and the air velocity at the condenser inlet is approximately 1m/sec. For higher ambient temperature the compressor size and the condenser size have to be increased by using the calculation used in the last part of this chapter about condensers.
Transfair Engineering: Designing and prototyping Circuits. 3.6. Condenser, Comparison Test of Condenser Capacity, Condenser performance Standards p. 39
Qk = G*(t2-t3) = K*A* T=k*A*(t2-t3)[kcal/h] The U-value is calculated on the bases of the condensing temperature minus the temperature at the condenser inlet.
It is easier for small household refrigerators (see figure) to use a calorimeter instead of the flow meter, so that the circulated quantity of refrigerant can be calculated out of the measured temperatures by the formula: Qk = G*C(t1-t2) whereby: G = Quantity of refrigerant (kg/h) C = Specific heat content (kcal/kg x C) to be taken out of the data sheet of the refrigerant t1 = temperature at inlet (C) t2 = temperature at outlet C)
The same formula can be used to compare different condenser types by using water as refrigerant.
Transfair Engineering: Designing and prototyping Circuits. 3.6. Condenser, Comparison Test of Condenser Capacity, Condenser performance Standards p. 40
Transfair Engineering: Designing and prototyping Circuits. 3.6. Condenser, Comparison Test of Condenser Capacity, Condenser performance Standards p. 41
Transfair Engineering: Designing and prototyping of Refrigerator Cooling Circuits. 4. Capillary Tube, Heat Exchangers, Capacity Calculation and Tests p. 42
For example a particular refrigerator operating at the condition -25C and at super-heating to 32C with a R12 compressor of 95W and an R134a compressor of 87W had following mass flow: R12-system: 0.17m/kg x 2.87 kg/h = 0.488 m/h = 8.13 l/min R134a-system: 0.23m/kg x 2.07kg/h = 0.476 m/h = 7.93 l/min This would result in a tube with an internal diameter of 5mm to a gas velocity of 6.9m/sec for R12 and of 6.7m/sec for R134a. To explain the a.m. formula we assuming following condition: 1. The condensing temperature is 55C, 2. The selected compressor has a displacement of 2,6 kg/h of R134a. 3. The evaporating temperature to be reached is -30C and an absolute pressure of 0.864 kg/cm acc. to the Mollier diagram of R134a and the system is nearly ideal acc. to the Mollier diagram for R134a, that means the outlet of the capillary is vapour only. In such a case following specific volumes can be assumed: - liquid: 0.72 l/kg. - vapour: 0.2245 m/kg. In such a case the Capillary capacity for R134a in l/min is as following: Pc[l/min] = Pf [kg/h] x Psv [m/kg] x 1000/60 = 2.6 x 0.2245 x 1000 /60 = 9.728 l/min There exist also a formula about the capillary capacity as a result of condensation pressure, diameter and length of the capillary using Nitrogen passing the capillary as follows: ________________ Va = 2.35 x p -1 x d 2.5 x l -0.5 whereby: Va = capillary capacity with Nitrogen gas passing in l/min
Transfair Engineering: Designing and prototyping of Refrigerator Cooling Circuits. 4. Capillary Tube, Heat Exchangers, Capacity Calculation and Tests p. 43
P = condensation pressure in kg/cm at 55C d = capillary internal diameter in mm l = length of capillary in mm _______________ ________________________ For example: Va = 2.35 x p -1 x d 2,5 x l -0.5 = 9.728 l/min = 2.35 x (14.907 -1) x 0.712,5 x l -0.5 l -0.5 mm= 9.728l/min /(2.35 x 14.28 x 0.424 ) = 0.684 l = 3.2 m But according to our experience such formulas are a first approach and the length and the diameter should be finally tested with methods as described in the next chapter. If other system components are not changed in a LBP system and same compressor capacities are chosen and similar gas velocities are reached the refrigerant charge by switching from R12 to R134a refrigerant should be about 10 % less. We recommend asking the supplier of the compressor which capillary tube diameter (normally 0,71 or 0,79mm inner dia.) and which length (about 3-4 m for the R 134a) he recommends as minimum and maximum length and there seem to be no way as to determine the optimal length of the capillary but by laboratory tests. Like usually such test first test each refrigeration circuit element separate (see for example the testing method of capillary tubes) and after optimisation of each element the system in total have to be tested as later explained to control interference between the elements on each other. Danfoss grant a program to select upon cooling circuit data the right capillary tube diameter and length called DanCapTM 1.0 http://www.danfoss.com/Germany/BusinessAreas/RefrigerationAndAirConditioning/Product+Selection+Tools+details/DanCap. htm
Test Apparatus
But the capillary can be also optimised by varying their length or diameter and by measuring the reached pressure drop with following test apparatus consisting of a gas bottle, a reducer with a manometer, a capillary tube with known capillary characteristics, a second manometer and the capillary tube to be tested. With such a test apparatus and variations of parts to be used different tests can be made: 1. It is possible to measure the pressure drop of a capillary tube. If the capillary tube C2 is not connected to the manometer 2 the pressure p2 on manometer 2 is equal to the atmospheric pressure; if the capillary tube C2 to be tested is connected to the manometer 2 the difference between the now measured pressure p3 on the manometer 2 to the atmospheric pressure at the outlet of the tested capillary tube C2 is equal to the pressure drop inside the capillary tube C2. 2. By positioning of the gas bottle on a balance and removing the capillary C1 and manometer 2 it is possible to measure the weight of gas passing the capillary in time and to calculate the corresponding capillary capacity in l/min for the used liquid or gas. 3. On this apparatus such a test can even be made with liquid R134a pressurised to the 14.9 bar at 55C, so that real conditions as existing in a refrigeration circuit can be simulated. Also R600a pressurized to 6,7bar at 55C in water bath can be used , if R600a
Transfair Engineering: Designing and prototyping of Refrigerator Cooling Circuits. 4. Capillary Tube, Heat Exchangers, Capacity Calculation and Tests p. 44
is exhausted to open air. If a capillary tube is too short or has a too large diameter, so that too much refrigerant liquid enters into the evaporator and reduces the evaporation surface can also be measured by the temperature increase in the entry area of the evaporator. So the size of this area filled liquid can be measured. Following standard can be applied: ANSI/ASHRAE Standard 28 (1996) (RA 2006): Method of Testing Flow Capacity of Refrigerant Capillary Tubes. It provides a uniform procedure for testing capillary tubes by determining the dry nitrogen flow capacity under specific test conditions so the procedures may serve as a primary standard for use by all test laboratories. Provides a basis for agreement between capillary tube manufacturers and users, and provides a standard procedure against which all other methods of tests may be checked. Dual units of measurement.
Transfair Engineering: Designing and prototyping of Refrigerator Cooling Circuits. 4. Capillary Tube, Heat Exchangers, Capacity Calculation and Tests p. 45
Transfair Engineering: Designing Cooling Circuits. 5. Evaporator, Cold Cabinet Tube-on-Sheet, TOP or Skin Evaporators, with Freezer, Two-door
p. 46
5. EVAPORATOR
There exist different types of evaporators and it depends on the construction of the refrigerator which type can be used.
This formula is only a first approach because it disregards certain thermal losses, caused for example by pressure drops in the suction line.
Transfair Engineering: Designing and Prototyping Cooling Circuits. 5.2 Evaporator, 2-Door Tube-Sheet Evaporators, Vertical Freezer Evaporators
p. 47
Samples: The channel cross sections are in the range of 22mm. If by this cross section the channel length exceeds 8m +/- 2m -depending on the compressor size and the evaporator temperatures, the pressure drops will already strongly reduce the utilised capacity. To avoid such pressure drops with larger channels length, parallel flow has to be used.
In practice bent roll bond refrigerators always face pressure drops in the bent area because of reduction of the channel cross area on the bends. To avoid pressure drop a doubling of the channel to 2 parallel channels in the bending area or an increase of the channel size will help.
Transfair Engineering: Designing and Prototyping Cooling Circuits. 5.2 Evaporator, 2-Door Tube-Sheet Evaporators, Vertical Freezer Evaporators
p. 48
Roll bond forms A and B are typical for so called "cold cabinets", refrigerators without freezer compartment. Form C and D are typical for *star refrigerators and form E and F are typical for ** star refrigerators. *** star refrigerators are made out of form E and F by adding a rear plate to E and side plates to F and to isolate the freezer section from the refrigerator section. Normally *** star refrigerators have a separate evaporator for the refrigerator because it is very difficult to reach the different temperatures in the 2 sections of the *** star refrigerator by one evaporator and screening (see underneath chapter "Screening and drip trays").
Evaporator Surface
The needed evaporator surface per cooled volume is in the following range for roll-bond evaporators: These are approximate values which can vary. To reduce for example costs for compressors and consumption of energy today often the evaporator size is increased by about 10-15 % to be able to use a smaller compressor. But this can only be finally decided by a series of tests. This sizing must be increased in the same range of the compressor's capacity increase if sub-tropical or tropical climatic conditions are selected (see chapter of refrigeration capacities). The values are valid for roll bond evaporators. In case tubeon-sheet evaporators behind the inner liner are selected, the surface has to be increased by 10-15% if the inner liner are plastic and by 5-8% if the inner liners are metal (chest freezer or freezer compartment with metal inner walls) depending also if the tubes are fitted to the sheet with heat transmission paste or not, and on the k-values of the materials between refrigerant tube and refrigerator and freezer inside. "Cold cabinets" are normally provided with a thermostat with a constant cut-in temperature of above 0C so that the evaporator is defrosting only during the stand still period: so called "cycle defrost cabinets". With drip groove on the backside the water of the evaporator is caught and drained outside the cabinet, normally on a tray on the top of the compressor for evaporative cooling of the compressor.
Transfair Engineering: Designing and Prototyping Cooling Circuits. 5.2 Evaporator, 2-Door Tube-Sheet Evaporators, Vertical Freezer Evaporators
p. 49
Example for a ** star refrigerator: Air circulation around the roll bond evaporator ensured in the typical ** star refrigerator by the distance of 25 mm between the roll bond evaporator and the inner walls. This type of models are meanwhile vanished in markets in developed countries because of icing, manual defrost work and low energy efficiency. Customers prefer *** star models (next chapter).
What are technological the difference? *** star freezers needs compartments normally air tight separate by a door from fridge. If freezer and fridge is not air tight sealed, water from hot air from each opening of fridge will condense to ice on freezer evaporator. In areas with high humidity and stronger use evaporator will be full of ice. Ice is a very good insulator (Igloo-effect) and reduce evaporator efficiency. So manual defrosting and re-cooling of warmed up refrigerator is often needed, which also cause increased energy consumption. Energy labelling system often doesnt reflect such customer use conditions. During use normally fridge is opened at least 5 times more than the freezer. Each door opening the complete cold dry air is replaced by hot wet air. A modern fridge with back wall evaporator defrosts automatically all humidity from hot air (door opening) during compressor stop time. The fridge compartment is bigger than the freezer compartment so that main air humidity is already automatically removed without icing as water (fridge temperature <0C). The freezer (<-12C or <-18C) volume is often much smaller than the fridge with less air volume and as result less humidity inserted by hot air during freezer door openings. In combination with less freezer door openings as fridge door openings much lower ice needs to be defrosted in a model with sealed freezer in comparison to the described model above without air tight separated freezer. Suppose the freezer has 1/3 of volume of fridge and is opened in the average 5 times more frequent as the freezer, you would have 3*5=15 times less ice to be defrost as in a same model size with unsealed freezer, as you have described.
Transfair Engineering: Designing and Prototyping Cooling Circuits. 5.2 Evaporator, 2-Door Tube-Sheet Evaporators, Vertical Freezer Evaporators
p. 50
dimensioning of the evaporator for the refrigerator is more difficult because of the interconnection between the 2 evaporators. The problem is to maintain -18C in the freezer without letting the refrigerator temperature falling below 0C, especially at lower ambient temperatures. Therefore the refrigerator evaporator is always in the range of 12-15% smaller than the one in a refrigerator of a "cold cabinet" on the same size. The final size of the refrigerator evaporator in a two temperature refrigerator or 2 door model should be tested in a air conditioned room according to the operating temperatures (for example +12C up to +32C ambient temperature) requested on the market. A two temperature refrigerator only thermostatically controlled by the refrigerator will not start freezing in lower temperature environment even if the freezer temperature goes above -18C. These 2 problems have caused tremendous costs for example for Liebherr in their Chinese project in DXINGDAO, to replace their construction to the conditions that Chinese use refrigerators in cold ambient temperatures in the winter time, not foreseen in such refrigerator constructions.
An alternative, which for cost reasons is seldom used, is Lockring tube joint method, which costs in the range of 0.50 per joining ring. Hydraulic Press Lockring Assembly before and after Pressing
The problem with brazing (as well as the use of the Lockring system) is the Aluminium coated tubes. Aluminium coating must be removed completely in both cases to avoid leakage. Tubes have to be delivered with one end extended or have to be extended on one side locally which is difficult.
Transfair Engineering: Designing and Prototyping Cooling Circuits. 5.2 Evaporator, 2-Door Tube-Sheet Evaporators, Vertical Freezer Evaporators
p. 51
were important. Not painted or otherwise protected aluminium tubes could be damaged by the Hydrochloric acid inside foam. Roll bond channels not only in bending areas have partially reduced cross section with partial internal pressure increase (heating) of the evaporator. Especially by using R134a as refrigerant this effect can happen because such a gas does not separate completely from the ester oil so that small quantities of ester oil will pass the circuit. Skin evaporators use the refrigerator or freezer inside wall as evaporator. The first application in which such evaporators were introduced were chest freezers, but in principle all aluminium roll-bond can be replaced by such tube-on-sheet evaporators, TOP or skin evaporators named evaporators, but in practice not in all cases it is recommend and cheaper. Still in some few applications, like some freezers, which have to be cooled from inside and not only by the walls roll-bond remains as technical solution.
Transfair Engineering: Designing and Prototyping Cooling Circuits. 5.2 Evaporator, 2-Door Tube-Sheet Evaporators, Vertical Freezer Evaporators
p. 52
We can use this test and these values for a pull-down test to find out if a new developed chest freezer is suitable or need to be changed. The ISO and DIN standard also prescribes a pull-down test with smaller loads to determine the freezing capacity of the model (See standards). The distance between the evaporator coils and the mode of fixing is important; 85mm is a suitable distance between the tubes as well as a maximum of 40 mm from the upper and lower edges to the evaporators coils.
Steel Tube Evaporators in 2 versions. Better quality with a much longer lifetime as with aluminium tubes can be reached if zinc coated steel tubes or even aluminium-zinc coated steel tubes are used (see drawing at beginning of this chapter). No doubt the best would be copper tubes, but copper tubes are very expensive. Zinc coated tubes cannot rust as long as the freezer is running and the tubes under low temperatures. But if there are periods, that the freezer are not used, zinc coated steel will rust. To avoid even in this time any rust aluminium-zinc coated steel tubes for refrigerator evaporators with temperatures above 0C can be used. Such aluminium zinc coated tubes also reduce thermo-element effects to the Aluminium sheet. To avoid even in this time any rust aluminium-zinc coated steel tubes for refrigerator evaporators with temperatures above 0C can be used. Such aluminium zinc coated tubes also reduce thermo-element effects to the Aluminium sheet.
Transfair Engineering: Designing and Prototyping Cooling Circuits. 5.2 Evaporator, 2-Door Tube-Sheet Evaporators, Vertical Freezer Evaporators
p. 53
Disadvantage of this tubes are the more difficult manufacturing process of steel tube evaporators. Either the tubes are pre-bent on a special machine to be placed on the liners horizontally with tubes as made like on the last picture and drawing or purchased and mounted by hand. Also such serpentines (see picture beside) can be used. The flat serpentines can be bent by hand round the chest liner by turning a tube by 90 on a corner position:
Transfair Engineering: Designing and Prototyping Cooling Circuits. 5.2 Evaporator, 2-Door Tube-Sheet Evaporators, Vertical Freezer Evaporators
p. 54
Todays most used evaporator version for cold cabinets without freezer. In such models the liquid refrigerant enters directly into the refrigerator evaporator and could pass liquid into the compressor if there is no accumulator between. Accumulators today are removed to increase efficiencies (class A-models). To avoid that liquid refrigerant can return through the suction tube into the compressor, which could destroy the compressor, the vertical bend is made. There are different ways of connecting the evaporator tubes and Aluminium sheet or foil to the inner liner Version with roll formed sheet is too expensive is the solution to insert tubes into a roll formed aluminium sheet (drawing right side). Also a double adhesive tape (1,50-1,70/m) is much more expensive as a hot melt glue (Teroson 7/kg 80g/m) applied on aluminium sheet and cold pressed on the liner so that a hot melt roller press investment amortize inside 1 year if more than 2500000-300000 refrigerators are produced in a year. Today - especially in countries with higher salaries - an adhesive Aluminium foil is most used (see its specification in next chapter 2 -Door Refrigerators).
Freezer Evaporator
Refrigerator Evaporator
Subcooling Heat Exchanger
The food liner will be formed with a tilted freezer block during thermoforming to allow sheet material to be inserted between freezer and refrigerator compartment.
Transfair Engineering: Designing and Prototyping Cooling Circuits. 5.2 Evaporator, 2-Door Tube-Sheet Evaporators, Vertical Freezer Evaporators
p. 55
The tube distances are between 4050mm for a tube of 5/16inch (=8mm dia).
Flat serpentine Evaporator for freezer box of a 12 cu.ft Two-Door refrigerator, Tube: Single wall O.D. 8 x 0.7 mm hot-dip zinc coated
Transfair Engineering: Designing and Prototyping Cooling Circuits. 5.2 Evaporator, 2-Door Tube-Sheet Evaporators, Vertical Freezer Evaporators
p. 56
4th Solution: Adhesive Aluminium foils TOP evaporator. Most used version today is adhesive Aluminium foils on tubes evaporator. Especially in countries with higher wages it is cheapest and therefore most used, as this can be done automatically. Transfair can provide a video of such machines.
The adhesive Aluminium foil TOP evaporator are made as following: with spenders with Aluminium foil rolls, cut in length according to models are placed near the cabinet preassembly to facilitate mounting.
Freezer Part inside 2-Door Model Up to 60l freezer. A freezer up to 60l does not need inside the freezer compartment cooling evaporators; cooling from the wall (behind the inner liner) is sufficient.
In this case the same construction of tube-on-sheet evaporator like the freezer compartment as previously mentioned for the one door model can be used or the following construction: The surface of tubes is always frozen (-24C), so that aluminium coating is not needed and zinc coating is sufficient, but in case such a system is not always running an aluminium coating is better.
Transfair Engineering: Designing and Prototyping Cooling Circuits. 5.2 Evaporator, 2-Door Tube-Sheet Evaporators, Vertical Freezer Evaporators
p. 57
A freezer of 60l and above cannot be cooled from the walls of the inner liner if the old still valid DIN standards are applied. 1-3 evaporator trays are needed inside the freezer. Few existing tube-on-sheet solution for this (Zanussi) do not look as nice as roll bond evaporators and the investment on machines is very high. Depending from each model itself and the cost of the components and processing mixed solution could be in some cases useful.
Theoretically there should be nice solutions. But all solutions for vertical freezers really made till now according to the old DIN standard we can not recommend for smaller scale production, because of high investment costs. Therefore in this area roll bond is still better. To connect the roll bond evaporator tube by brazing special Aluminium Copper joint made by pulsed electrical induction are needed, which can be purchased. Even the a.m. Lockrings allow direct connection of the Aluminium tube to the steel or copper tube in the circuit. Freezers have the highest temperature at the top of the cabinet. To improve the freezer quality often the top evaporator coil are doubled or of a larger size; or higher number of wires or 2mm wires instead of 1,5 mm wires are used. Tube-on-plate freezer evaporator. A Tube-on-plate evaporator with 50mm spacing between the tubes has approximate a value of 6,9 W/m**K. The connection to the tubes is reached by some flanges of the plate being bent round the evaporator coil. Wire-on-tube freezer evaporator. A wire-ontube freezer evaporator with tube coil spacing of 6080mm and 1,5mm wires in distance of 10mm at both sides reaches a Lambda value of 8,5W/m**K.
Transfair Engineering: Designing and Prototyping of Refrigerator Cooling Circuits. 5.5 Evaporator, No Frost Damper Thermostat, Tandem System
p. 58
Evaporators in series. Single evaporators are connected in series. A circuit with inlet in the upper section and outlet in the lower section should be selected.
Transfair Engineering: Designing and Prototyping of Refrigerator Cooling Circuits. 5.5 Evaporator, No Frost Damper Thermostat, Tandem System
p. 59
which is very seldom. The failure rate on-tube-on-sheet-evaporators behind the inner liner is much lower than with any roll bond evaporator solution. Overall because of costs, European refrigerator producers have already replaced roll bond in a.m. cases by skin or tube-on-sheetevaporators with the effect that the mayor European roll bond production were closed down. Cross section. But the mayor advantage - beside of costs - are the improvement of cross sections reachable with evaporator tubes instead of roll bond channels. Tubes do not have any reductions in bending areas which is very important for the performance efficiency especially if R134a or R600a as refrigerants are used.
5.3. Optimisation of Evaporators 5.3.1. Evaporator Channels or Tubes and their Cross Sections
Since 1991 the R 12 refrigerant is replaced by R 134a refrigerant and size 1994 R134a refrigerant mainly in Europe is more and more replaced by R600a. Both need an improvement of the channels and cross sections in comparison to R12 systems. Cross section and efficiency. In general for all refrigerants optimised cross sections of channels improve strongly the efficiency. There exist for each compressor displacement and system design an optimum size of the channel cross section, depending on the discharge of the compressor and the length of the tubes or channels. If it is too small, the pressure drops too much across the evaporator with the result that the compressor capacity cannot be completely utilised. If the cross section is too large the speed of the refrigerant optimal at 4-5m/sec - becomes to low and oil can accumulated in the evaporator with the effect that the evaporative capacity reduces. Such accumulation of oil can even put the oil pumps in the compressor out of order. This effect can be increased by the use of R134a which does not separate as well as the R12 between gas and oil so that ester oil can pass the whole refrigeration circuit. Therefore any reduction of the cross section or pockets in which the oil can be accumulated must be avoided in HCF-134a systems much more than in CFC-12 systems.
Transfair Engineering: Designing and Prototyping of Refrigerator Cooling Circuits. 5.5 Evaporator, No Frost Damper Thermostat, Tandem System
p. 60
evaporator tube lengths reduction, without sucking liquid into compressor, which would happen, if the evaporator size would be reduced without an accumulator. In past it was used only in chest freezers and upright freezers, but seldom in fridge-freezers. Such accumulator even allow to charge slightly more refrigerant, without reducing coefficient of performance, so the cooling system could tolerate even small leaks near 1g/a and by this slightly overcharging, without reducing superheat (+3-4K), in this case it will increase lifetime of such small leaking refrigerator, but only if leak is really small. Modern high efficient fridge-freezer combinations with low energy consumption (A and A+ models) are often quite slow in pulldown of the refrigerator temperature cause by a quite long fridge evaporator tube length. Using an accumulator allow to shortening of evaporator tube length and size of fridge evaporator by 15-20% it increases the speed of refrigerator pull down time. So this accumulator is an instrument to compensate this bad side effect of energy saving efforts, which in past often slow down refrigerator compartment cooling.
Transfair Engineering: Designing and Prototyping of Refrigerator Cooling Circuits. 5.5 Evaporator, No Frost Damper Thermostat, Tandem System
p. 61
5.5.
NO FROST Evaporators
No frost design separates the evaporator from the storage space and removes from time to time automatically the frosting from the evaporator finned coil by heat so no frost are visible inside the cabinet. Such system exists for 2 temperature cabinets and for freezers. A fan is used to draw the warm air from the storage space across a finned coil evaporator and back to the storage. The defrosting of the coil is made automatically by electrical heaters and controlled by a timer. During opening of doors the fan stops. In a HC-600a or HC-290 design the electrics must be N protected or outside the reach of a leak (see chapter 8.); the heater surface temperature should not go above 350C (underneath the ignition temperature of HC-600a, which can be reached by limiting the electric heating power per surface to 1,5W/cm by resistance wire and limiters. furthermore the electric terminals should be outside the R600a leaking area (or with special fixings see chapter 8.3.1.). IR heaters cannot be used.
5.5.3. Defrosting
The frosting up is much faster than in a normal freezer evaporator; therefore such systems need 3 or 4 times per 24 hours defrosting. A special timer to start and stop automatically every 6-8h the defrosting heater for some minutes is needed inside a No-frost model. This heater is passing the finned coil. Heating up of coil evaporators to remove 3-4 times per day is the main reason why No-frost models increase energy consumption, but it can be limited by some tricks (chapter 9.4.1). In case of HC-600a or HC-290 the surface temperature of the heater should never go above 350C. This could be easily realized by electric resistance heaters limiting the electric heating power per surface to 1,5W/cm and additional limiters, but not with IR heaters (see chapter 8.3.9.).
Transfair Engineering: Designing and Prototyping of Refrigerator Cooling Circuits. 5.5 Evaporator, No Frost Damper Thermostat, Tandem System
p. 62
Transfair Engineering: Designing and Prototyping of Refrigerator Cooling Circuits. 5.5 Evaporator, No Frost Damper Thermostat, Tandem System
p. 63
Electrical Scheme
For further details see: K.Kim, B. Kopco and R. Rademacher: Experimental Research and Development of Tandem System Domestic Refrigerator. Department of Mechanical Engineering. Center for Environment Energy Engineering. University of Maryland. College Park MD 20742.
Transfair Engineering: Designing Cooling Circuits. 5.6. Evaporator, Evaporator Tests, Pressure Drop Test, Temperature Distribution, Pull-Down Test p. 64
Warm air contains more humidity as cold air. Such warm air humidity entering during fridge door opening condensate to water drops, mainly to cold backside wall, but also on already cold foods which in case of cheese and sausage can reduce their storage time. By ventilation this water drops on fresh food would be reduced. Too strong ventilation of fruits and vegetables would dry them. So they should be stored inside separate not ventilated area like inside a vegetable crisper or box.
Transfair Engineering: Designing Circuits. 5.6. Evaporator, Evaporator Tests, Pressure Drop Tests, Temperature Distribution, Pull-Down Tests
p. 65
Chest freezer pull down test. Several chest freezers show following average values during a pull-down test with big loads. According to DIN 8953 or ISO 5155 the pull-down test will be made by 25 kg Tylose parcels per 100l chest volume. The chest freezers should reach following sequences of the evaporating temperatures. In the new standard 25C is used while in the old standard 32C ambient temperatures were used. Ambient Temperature 32C 25C Maximum -10C -13C During crystallisation -21C -24C At stationary conditions -31.5C -33.5C
Pull down test for fridge-freezers and cabinets with or without freezer compartment. Following values of the evaporator should be reached according to the valid standards: Climate SN N ST T Ambient temperature 10-32C 16-32C 18-38C 18-43C Cabinet temperatures -1C </= t1, t2, tm = max +7C 0C </= t1, t2, tm = max +5C 0C </= t1, t2, tm = max +7C 0C </= t1, t2, tm = max +7C t3 </= +10C t3 </= +10C t3 </= +12C t3 </= +12C Max. temperature in freezer compartment (inside test packs) * - 6C ** -12C
t1, t2 and t3 are mean temperatures for top, middle and bottom measured in copper cylinders. tm is the mean temperature of t1, t2 and t3 . Four star cabinets with large freezing sections normally have 2 independent systems or one system with separated control by a three-way valve.
More detailed description how such pull down tests have to be executed are described in the ISO standard 5502 (in past ISO 7371, ISO 5155, ISO 8187) which we will not repeat here.
Transfair Engineering: Designing Circuits. 5.6. Evaporator, Evaporator Tests, Pressure Drop Tests, Temperature Distribution, Pull-Down Tests
p. 66
Transfair Engineering: Designing and Prototyping of Refrigerator and Freezer Cooling Circuits. 6. Dryer/Desiccant, types, Standards and Tests
p. 67
6.
6.1.
DRYER/DESSICANT
Filter Dryer characteristic
The requests on dryers for R600a did not change to the ones for R12 systems. As a desiccant a molecular sleeve with pore sizes of 4 Angstrom like 4A-XH-5 of Union Carbide is used in household refrigerators and freezers working with R12 and R600a. For HFC134a refrigerant systems more efficient dryers with following desiccants are required: XH-7 or XH-9 (UOP-Union Carbide) which also can be used for R600a. In this case the molecular sleeve has pore sizes of 3 Angstrom. So also other dryers with desiccant using 3A molecular sleeve pores, like Siliporite H3R (CECA) can be used. In general the dryer should be selected in a way that the hygroscopic percentage level of a dryer is below 4% after operating the system and that the moisture level of the dryer remains below 10mg. The dryer's volume in case of HC-600a models remains the same as for the same CFC-12 model. For HFC-134a models the desiccant volume should be increased by about 20% in comparison to R12 dryer's volume in the same model. The total household refrigerator system should not contain more than 150mg moisture. To improve the quality of the refrigerator, especially in humid climate, to speed up evacuation, to remove moisture on high and low pressure sides of the cooling system a filter dryer with a third 6mm tube is recommended to evacuate on both sides of the circuit parallel.
It is very important for R134a and for R600a refrigerators to dry the evaporators and condensers before assembly by dry air or dry nitrogen with dew point <-50C. Furthermore is quality wise important to open the filter dryer and compressor, specially the R134a compressor with hydroscopic ester oil, last moments before cooling circuit brazing to prevent entry of humidity. Even under these precautions we still have regularly 2 sources of humidity the refrigerant and the compressor oil,
Transfair Engineering: Designing and Prototyping of Refrigerator and Freezer Cooling Circuits. 6. Dryer/Desiccant, types, Standards and Tests
p. 68
6.2.
ANSI/ASHRAE Standard 63.1 (1995) (RA 2001): Method of Testing Liquid Line Refrigerant Driers. It prescribes test methods for determining flow capacity and water capacity performance characteristics of liquid line refrigerant driers. It applies to driers that employ a desiccant. The water capacity test method prescribed can be used to test a drier either "as received" or after being reactivated in accordance with manufacturer's recommendations. Dual units of measurement. ANSI/ASHRAE Standard 63.2 (1996): Method of Testing Liquid Line Filter-Drier Filtration Capability. It prescribes a laboratory test method for evaluating the filtration capability of filters and filter-driers used in liquid lines of refrigeration systems.
ANSI/ASHRAE Standard 78 (1985) (RA 2003): Method of Testing Flow Capacity of Suction Line Filters and Filter-Driers. It establishes a method for measuring the flow capacity of refrigerant suction line filters and filterdriers. Intended for use on both sealed model and replaceable element type suction line filters and filter-driers of all types. Dual units of measurement.
It is useful to received from manufacturer of filter dryer corformity declaration to these standards and capability test results.
Transfair Engineering: Designing and Prototyping of Refrigerator and Freezer Cooling Circuits. 6. Dryer/Desiccant, types, Standards and Tests
p. 69
Transfair Engineering: Designing Cooling Circuits. 7. Refrigerants, Thermal Characteristics; COP, Volume Capacities, Pressure Diff./Ratios, Superheat p. 70
7. REFRIGERANT
Today the selection of refrigerant depends on following aspects: - environmental aspects (phasing our of CFC's like CFC 12) - high energetic efficiency - non toxicity - chemical stability in use - compatibility to other materials in use and last not least - costs and availability. REFRIGERANTS Dichlordifluormethan Propylene Propane Propadiene Cyclo-Propane Tetrafluorethan Dimethylether Isobutane Butene Butane R12 R1270 R290 R1250 RC270 R134a E170 R600a R600 Formula CCl2F2 C3H6 C3H8 C3H4 C3H6 C 2H 2F 4 C2H6O C4H10 C4H8 C4H10 Mol weight [kg/kmol] 120,93 42,081 44,094 40,065 42,081 102,030 46,069 58,124 56,108 58,124 Tnbp [C] -29,8 -47,6 -42,0 -34,4 -32,8 -26,4 -24,8 -11,7 - 6,2 - 0,4 Tcrit [C] 112,0 91,8 96,7 119,9 124,7 101,1 126,9 135,1 146,5 152,1 Pcrit [bar] 41,2 46,0 42,5 54,7 54,9 40,6 52,4 36,5 40,2 38,0
At moment only 2 CFC free refrigerants are used in the refrigerator household appliances - HFC-134 a (tetrafluorethane) and - HC-600a (Isobutane). Propane HC-290 which has also an excellent efficiency is not used in the household as it works under higher pressure which causes a higher noise and shorter lifetime for the compressors. Also the mixtures of propane and Isobutane (the so called Dortmunder mixture, invented by Prof. Rosin) and first used by the company Foron upon recommendation of Greenpeace, is now more and more vanished from the market in developed countries for noise reasons, problems of lifetime and in some cases efficiency problems caused by the temperature glide of condensation and evaporation; but it could be possible that it will have success in developing countries, specially in retrofitting of existing appliances if the retrofitted system can pass safety tests needed for using inflammable refrigerant or as replacement of R12 in R12 compressors because the thermodynamic behaviour (displacement volume) is similar to the one of R12 and so no mayor change in designs of the compressor or other circuit components except electrics are needed. We concentrate on the development of new appliances and therefore on HFC-134a and HC-600a as refrigerants.
Transfair Engineering: Designing Cooling Circuits. 7. Refrigerants, Thermal Characteristics; COP, Volume Capacities, Pressure Diff./Ratios, Superheat p. 71
7.1.1. Efficiencies
Following refrigeration efficiencies (COP-coefficient of performance) can be reached in comparison to the one of R12:
Transfair Engineering: Designing Cooling Circuits. 7. Refrigerants, Thermal Characteristics; COP, Volume Capacities, Pressure Diff./Ratios, Superheat p. 72
Transfair Engineering: Designing Cooling Circuits. 7. Refrigerants, Thermal Characteristics; COP, Volume Capacities, Pressure Diff./Ratios, Superheat p. 73
7.1.6. Superheat
The superheat (=enthalpy difference between the compressor suction and the evaporator saturated vapour conditions) for the different refrigerants reaches following values:
p. 74
p. 75
Transfair Engineering: Designing Cooling Circuits. 7. Refrigerant, R270/R600a Pressure-Enthalpy Diagrams (Care 30)
p. 76
Transfair Engineering: Designing Circuits. 7.2 Refrigerant, Working with R600a, Purity and Cleanliness, Flammability and Hazardous Situations
p. 77
<100ppm Non condensable gas - O 2, H 2 - N2 n-Butane n-C4H10 <2500 ppm Propane C3H8 <4000 ppm Unsaturated C4 , especially <100 ppm -1,3 Butadiene CH2:CH-CH:CH2 <1ppm < 10 ppm Water content Acids <1 ppm - CO, CO2 <20ppm < 0,01vol. % High boiling fluids 0 ppm Solid particles Sulphur 0 ppm 0 ppm Chlorinated and fluoridated HCs Total impurities <5000 ppm 1) Purity %age by weight 2) Impurities of other gases and liquids by volume
<15 ppm <50ppm <2500 ppm <4000 ppm <100 ppm <1ppm < 12 ppm <1 ppm < 20 ppm < 0,01vol. % 0 ppm 1 ppm 0 ppm <5000 ppm
Measurement of Cleanliness and Purity. The cleanliness and purity can be measured by Gas chromatographs with FID and TCD (HWD) Sensors (mainly HCs and critical non condensable gases), humidity by capacitive Gold/Aluminiumoxid sensor or Karl-Fischer apparatus, Acid by test titration, boiling test, solid residue measurement (scale) and non-condensable gas test also by gas chromatographic or by Oxygen sensor acc. to US- ARI or German DIN standard. The mayor analytic problem is the splitting of signals of N-butane in ppm quantities inside of Isobutane with concentration above 99.5%, so only good laboratories in the world can measure correctly such small n-Butane quantities in Iso-Butane using Gas Chromatographs. Atom Emission Detectors in this area n- i- butane splitting are easier to use. Supplier for each batch of supply should approve it. See Transfair Engineering: Refrigerator Laboratory and Quality Control. Non-condensable gas from the circuit can be removed during evacuation (see Transfair Engineering: Evacuation, charging, leak detection 9/2003, p.9ff) and moisture from evaporator and condensers by dry air, but it is difficult remove it from the refrigerant itself and from the compressor oil in the refrigerator factories. These are the 2 severe quality problems as it is already in the refrigerant and in the oil. Refrigerant and oil humidity should not exceed 1/10 of dryer capacity (about 1g), that means for the compressor oil <100mg water (<125ppm for 280ml oil). The refrigerant value of <10ppm are often not reached by R600a suppliers. As hydrocarbons are mixable with all common types of oil except polyglycols there does not exist such problems like with R134a concerning humidity, solution of soldering etc. The selected viscosity grades are normally the same as for R12 or slightly higher, because Hydrocarbon is more soluble inside mineral oil than R12. It is a strong advantage for R600a that the compressor swept volume is 80% higher in comparison to R12, but it is a disadvantage that the pressure difference is lower, that the stress on moving parts is higher and that the housing of the compressor in same cases is bigger. The mayor obstacle for the world-wide introduction of Isobutane as refrigerant, especially in developing countries could be perhaps the service problem. It is not only the problem of inflammability of hydrocarbons which will prevent the strong introduction in developing countries. Also the charging has to be made with a maximum tolerance of +/- 1 g because of the much lower charging quantities in comparison to R12. But meanwhile adequate equipment for a reasonable price is available. Charging without any adequate device as practised in the past in some developing countries from the informal sector cannot be made anymore.
Transfair Engineering: Designing Circuits. 7.3 Refrigerant, Working with R134a, Evacuation pumps and cleaning
p. 78
7.3. Working with R134a in the Refrigerator Laboratory and in the Production
7.3.1. R134a Refrigerant
General characteristics of R134a. R134a (1,1,1,2-Tetrafluorethane) has a faintly ethereal odour, is colourless, chemically stable, free of acid, non explosive, non flammable, non- irritating and non-corrosive. Their toxicity is very low. Under normal temperatures it is a gas; the boiling point at 1.013 bar is -26,3C. At 25C it can be kept liquid only under pressure of 6,5 bar. To avoid freeze burn any direct contact with the refrigerant like with R12 have to be avoided and the same measures have to be taken (gloves, Eye glasses etc.). Ester oil. R134a can be mixed with Ester oil necessary for the compressor. Ester oil is hydroscopic; it is absolutely important to avoid any contact of R134a to mineral oil and humidity (above the very low limits fixed), because as a result of these contacts the ester oil will increase the acidity with drastical consequences for the life of the machine. In addition such contacts will cause residue in the circuit which will block the capillary tube and stop the circulation. Furthermore the Safety data sheet and first aid recommendations of the supplier should be respected.
Transfair Engineering: Designing Circuits. 7.3 Refrigerant, Working with R134a, Evacuation pumps and cleaning
p. 79
Middlesbrough, Cleveland TS6 8JE; United Kingdom, Fax: 0044-642-432 444) or the synthetic mineral oil called PFPE 140 with very vapour pressure from Hls for both systems.
Cleaning process:
1. 2. 3. Replace the hose from the vacuum pump to the connector (Hansen coupling) for the service tube of the compressor (or filter) with a new one: The connector (Hansen coupling) can still be used for HFC 134a refrigerator system; Remove the oil out of the pump still warm from operation; Load the vacuum pump till tank minimum level (about 50-100cm synthetic or ester oil) and start the vacuum pump. Let it run for minutes; Repeat step 3 3 times with new synthetic or ester oil; Remove the oil out of the pump, charge the pump with new synthetic or ester oil up to the maximum level; Connect the vacuum pump to an HFC 134a refrigeration system and evacuate the system down to the specified vacuum level; Connect the refrigeration system to the HFC 134a charging board and re-evacuate. Charge again with the specified amount of HFC 134a; Start the compressor and let the system run for about one hour.
4. 5. 6. 7. 8.
If some mineral oil or chlorine is still left in the vacuum pump on the suction side, it will be transferred to the HFC 134a refrigeration system and the capillary tube will be blocked after few minutes. Note: If the vacuum pump has been washed with ester oil and not with the recommended synthetic oil with low volatility, it should only be used for HFC 134a refrigeration systems. If it is used for the evacuation of R12 or R600a systems it should have an anti-suck device or at least an efficient suction filter to avoid that mineral oil of the compressor can enter into the pump. The pumps, which are used, for R134a evacuation should be never used for re-evacuation of systems before filled with R12. or R600a and vice versa, if there is no anti-sucking device mounted.
7.3.5. Brazing
R134a is more aggressive to brazing materials as R12. The selection of these materials and the way the joint are designed to avoid contact spaces are more relevant as in the past. Also the gas can pass smaller holes than R12, so that the system should be better sealed and controlled than in the past. How the brazing joints have to be designed and how to braze see Transfair: Cooling circuit sealing chapter 5).
Transfair Engineering: Designing Circuits. 7.3 Refrigerant, Working with R134a, Evacuation pumps and cleaning
p. 80
3.
4. 5. 6.
7. 8.
9.
7.3.8. Mixed Production during Transition from R12 to R134a or from R134a to R600a: Anti-Suck Valves, Suction Oil Separator or Glass Trap in Vacuum Pump
In cases such separation cannot be made in the production and the same evacuation and charging line have to be used for compressors charged with mineral oil and others charged with ester oil or both with synthetic oil of low volatility, special precautions has to be added to avoid charging of wrong refrigerant into the cooling system (R134a or R600a marking on the backside) and mixing of different oils from compressor and vacuum pump under normal operation and under power failure. In cause of power failure the already evacuated refrigerator cooling system will suck back oil from the pump is there is no anti-suck back valve built inside the vacuum pump. In such evacuation lines with HFC-134a systems mixed with HC600a (or CFC12) either the pumps should be filled with ester oil or with the expensive mineral oil with low volatility (SH200). Anti-suck back valve
To Refrigerator To pump
Oil Glas Trap for a mixed R600a-R134a Production
The repair of R134a and R600a on the same pumps is restricted by following conditions in addition to the a.m. conditions for mixed evacuation lines: - a system already charged with R600a must be evacuated with a burst free evacuation pump, and not with a standard pump,
Transfair Engineering: Designing Circuits. 7.3 Refrigerant, Working with R134a, Evacuation pumps and cleaning
p. 81
Refrigerators already running during evacuation as needed in case of R600a or during performance tests should be repaired on separate pumps, the R600a (or R12) ones on pumps with mineral oil and the R134a one on pumps filled with ester oil. The reason is that mineral and specially ester oil never completely separate from the refrigerant and will pass the cooling circuit and would enter into the hose and evacuation pump.
But it is possible to use the same evacuation pumps even for systems which have run already and which have oil in the condenser and evaporator the conditions, that an oil separator on the suction line must be installed on the pump, the pump must have an anti-suck back device, and the used oil is a synthetic mineral oil with low volatility.
7.4. Working with R600a or R290 in the Refrigerator Laboratory and Production
7.4.1. Flammability and Hazardous Situations
Isobutane and Propane safety data:
Media Isobutane Propane Flash point [C] - 83.15 -105 Ignition temp. [C] 460 432 Explosion group II A IIA Temperature class T2 T2 LEL/HEL vol. %
Depending of country
For R290/R600a blends the LFL is 1.95% blend in air and the upper flammability limit (UFL) is 9.1 % blend in air. Safety precautions. Concentrations between these limit values can be hazardous in presence of an ignition source like an open flame, an electrical spark from an electrical component or discharge of static electricity or a surface hotter than 460C. Important is that an explosive mixture can build up even below the calculable concentration if the equipment carrying hazardous gas or the surroundings are made in a way that an accumulation in dead spaces, ground channels, pits or other deepening is possible. A natural or artificial circulation (last one controlled by gas sensors and ventilator controls) of the air underneath the emission zones (R600a is heavier than air) should be insured and accumulations in the ground area or in a closed room should be avoided by using exhausts and ventilation. Clear instruction have to be granted to the operators and maintenance staff of the equipment which can come into contact with Hydrocarbon and their following needs to be regular trained and controlled. Hazardous situations. Following hazardous situations which needs partially different safety measures can happen: 1. Refrigerant leaks into the surrounding air. Any open fire, an electrical spark of electrical equipment or discharge of static electrical loading, a surface temperature of 460C or above can ignite or even can let explode the hazardous hydrocarbon/air mixture. Fire from outside which reaches Hydrocarbon filled equipment or their leaks can let explode and burn down the equipment filled with hydrocarbon. Air leaks into equipment filled with Hydrocarbon. Normally all hydrocarbon filled equipment and tubes are under pressure and so such implosion can not happen except on the filling tube of the charging equipment. Production charging units therefore clean the tube with nitrogen to avoid any accident. In all other cases the 3rd hazardous situation can be neglected.
2. 3.
Transfair Engineering: Designing Circuits. 7.4 Refrigerant, Working with R600a, Handling of Hydrocarbon Refrigerants, Evacuation pumps
p. 82
quantities can escape. Hydrocarbon replaces air so by escaping of relevant quantities are asphyxiate and can cause suffocation. But R600a or R290/R600a blends are not toxic. As they are heavier than air they will distribute on the ground level and can concentrate to a hazardous mixture in pits, ground channels, basements or any vessels underneath the leak. Therefore such areas need an additional ventilation to avoid explosion. Hydrocarbon cylinders. Such cylinders must be labelled being - inflammable with the ISO sign for it and marked with the - type of refrigerant the cylinder contains, like R600a, R290 or R290/R600a 50/50 Blend. In addition same rules as used for any high pressure gas cylinders have to be applied, like - Closing the protection cap of the valve when cylinder is not in use, - ensuring with a chain that the cylinder cannot fall down, - avoiding the exposure of the high pressure cylinder to high temperature (>45C) and sun, - if the cylinder must be heated to remove the gas, only a water bath or a PTC heater with a no -sparking limiter of temperature to max. 45C can be used, - the cylinder or valve have neither to be modified or repaired, nor refilled again (for recovery special marked cylinders should be used), - to check if a cylinder is empty a scale should be used and compared with the marked Tara weight on the cylinder. The pressure gauge mounted on the cylinder is not exact, - avoid decanting of the cylinder in smaller bottles. Such work needs special equipment and precautions. Let it only do from your qualified refrigerant supplier. Transportation. The rules of transportation are the same as used for LPG. Such cylinders should be transported in open or good ventilated vehicles only from drivers experienced, well trained and authorised for the transportation of such hazardous goods. Storage. The storage should be made like other light and inflammable LPG gases. The best is to store the cylinders - outside in an naturally ventilated area above ground and never underneath the ground, upright, secured against falling down, and the valve and cap closed when not in use, - protected from weather and direct sun by a roof and - the area should be closed by an air passing fence and locked so that no unauthorised person can enter and manipulate any valve. - Minimum 5-10 m around the area no ignition source (electrical installation) should exist and smoking, open fire, electrical maintenance work or welding in this area in presence of the cylinders have to be prohibited (ISO labels like symbol B 3.2 acc. to ISO 3864 or others according to local rules). - There should be neither a window nor a door, nor any pit, basement or channel near the storage area to avoid that leaked gas can accumulate into a closed room or into lower areas (R600a and R290 is heavier than air). - Fire extinguishers have to be installed in this area. The best would be if a water extinguisher is place in a way that it can be used even when there is a risk of explosion (behind a strong wall or corner. - Staffs have to be trained in handling of the cylinders and in case of accidents. There exist also guidelines to store such cylinders inside a building; depending from the local rules. Such guidelines build classes of risks by quantities of flammables gas; they normally require a gas alarm systems, natural or artificial ventilation, fire protections and other precautions. But as these rules differ strongly from country to country and the storage outside is always much safer we prefer not to describe such storage possibility to avoid generalisations. In all countries there exist rules and regulations how to use, to transport and to store such gases which belongs the group of LPG gas, and approvals for the installations and authorisations of their use are always required.
Transfair Engineering: Designing Circuits. 7.4. Refrigerant, Working with R600a, Exhaust and Ventilation of R600a Charging Area
p. 83
Transfair Engineering: Designing Circuits. 7.4. Refrigerant, Working with R600a, Alarm board with gas detectors for charging area
p. 84
hazardous gas underneath the lower explosion limit, for example on the level of 20% of the LEL. If artificial ventilation is safety relevant (depending from the released quantity, the existence of gas alarms and other local factors, than such a system have to be redundant, that means doubling of the ventilators, in case of any failure of a ventilator motor, and the ventilation has to be controlled (mechanical flow control inside the ventilation air stream or by measurement of the pressure differential. The formula for the ventilation is the following: The refrigerator charging area in the production need following ventilator output: Vc = a * 60 * Mair/MHC * 1/pair *100/LEL * 100/d % wherein: Vc = Required ventilator output a = Average emission of HC (g/hour) = max. 120 * 15g = 1800 g Mair = Molecular weight of air = 28.97 g/Mol MHC = Molecular weight of R600a = 58,12 g/Mol pair = Average density of air = 1200 g/m LEL = Lower Explosion Limit = 1.8 % volume d % = % to which one wishes to delude HC underneath The LEL = 20% Vc = a *60 * 28.97/58.12 * 1/1200 * 100/1.8 * 100/20 = a * 6.9 m/h Important for this formula is the amount of Hydrocarbon which can be released. To reduce this amount their exist a lot of safety devices: Between the Hydrocarbon tank and the charging machine a self closing quick action safety valves are installed, so that the larger amount of Hydrocarbon in the tank has not to be considered in case of leakage in the charging equipment. Also leakage on the sealing of the machine itself have to be and are normally controlled by the machine itself which will cause a closing of the operation and closing of the quick action closing valves between the machine and the tank, so that emissions around the machine in such cases are strongly minimised under normal operation conditions. Therefore it remains for the calculation of the required ventilation output the average emission of HC during the normal operation of the charging unit. In case of the Galileo charging machine Frigus H11 for example a dead space of 1.8 cm will be purged by Nitrogen into the atmosphere and have to be considered and in case of a leak in the machine only 100g Hydrocarbon can escape. With a density of 0.555 g/cm at 20C and a cycle time of 30 sec. the emitted g Hydrocarbon per hour could be 120g which is about 2.4 m Hydrogen-air mixture on LEL level and the needed ventilation output should be minimum 24 m/h to keep the concentration underneath 10% of LEL. In addition there exist under normal conditions rates of leakage on the manufactured refrigerators which will be minimised by a pressure rise test executed before charging can be executed. So only the small emission of remaining small leaks not identified by such a test has to be added. If we consider a 5% leak rate, an average charge of 50g and a cycle time of 30 sec. we have to add further 300g HC-emissions and further 60 m ventilation to keep the level underneath of 10% of the LEL value, totally 84 m/h, with reserves 100 m/h. Using such machines to charge household refrigerators with charges of 15- 40g for a small unit and 60-120g for large units a ventilation of the charging area is even not always needed, if an effective gas detector system is installed and if the machine controls their sealing and the safety quick reaction closing valve is closed automatically in case of leaks or alarms. But we still recommend the installation to avoid any accumulation and to increase the safety level. In case of an alarm and operation interruption the work can be restarted faster if a ventilation system is installed. It also has a positive effect on the detectable rate of leaks because the leak detectors near to the charging area are not disturbed. Standard electrical boards in the ex-zone area should be pressurised by air and the overpressure should be controlled by flow meters or differential pressure transducers to avoid entry of hazardous gas.
Transfair Engineering: Designing Circuits. 7.4. Refrigerant, Working with R600a, Welding and Brazing, Leak Detection, Further Precautions
p. 85
7.4.8. Brazing
How the brazing joints have to be designed and how to braze see Transfair: Cooling circuit sealing chapter 5). If the R600a charging tube is good closed by a crimping tool to be applied twice per tube, perhaps by a pneumatically driven one, it is possible to use normal welding to close even the filling tube. But todays standard is to close the filling tube by e ultrasonic welding machines (like Viper from Stapla, RSA3000 from Stado or Ultraseal from Amtech) because of the flammability of R600a.
Transfair Engineering: Designing Circuits. 7.5. Refrigerant, Determination of Refrigerant Filling Quantity, Liquid or Vapour Charging
p. 86
used Cyclopentane foam blowing agents already up to the level of 40-50g/year, so that such a system will cause often failure alarm. The only reliable method in this case is Helium leak detection lines. See Transfair Engineering text to Leak detection in the refrigerator industries today.
Transfair Engineering: Designing Circuits. 7.5. Refrigerant, Determination of Refrigerant Filling Quantity, Liquid or Vapour Charging
p. 87
In general a system can be charged either in liquid or vapour state. The upright refrigerant cylinder will allow saturated vapour charge, the upside down cylinder saturated liquid charge. Vapour charge is safer as it prevents that liquid is "slugging" the compressor. Liquid charging is much faster than vapour charging. Pay attention: If liquid refrigerant is charged into the suction line the compressor will be damages if the liquid is not evaporated before entering the compressor. The evacuation can be done in a way that the liquid charged refrigerant passes a capillary tube (1 m) before it reaches the suction. When you vapour charge a system that needs a complete charge, hook up the gauge manifold to the system in the normal way. The utility hose is connected to the refrigerant cylinder. With the system compressor off, and after you have bled the manifold hoses; open the refrigerant cylinder valve and the high and low pressure manifold valves. Control the refrigerant weight scale or charging cylinder. When it is obvious that the refrigerant is no longer entering the system or only entering very slowly, close the high pressure manifold valve and charge through the low pressure valve only. When 50-75% of the total charge has been entered the system starts the compressor if Hydrocarbon is not used to complete the charging. The compressor will cool down or even freeze the refrigerant cylinder. If the procedure will slow down, warm the cylinder in a water bath up to 50C or with PTC heater with thermal fuses to avoid overheat. Liquid charging is always down in the high side of the system with the compressor off. Some larger refrigeration systems have a liquid charging valve between condenser and metering device. The system and the refrigerant cylinder are hooked up through a gauge manifold. After the manifold hoses are purged, the refrigerant cylinder valves are opened. Often the entire charge can be introduced by this way. When the whole charge does not go in, close the high pressure and refrigerant cylinder valves, turn the refrigerant cylinder upside down and introduce the remaining quantity in the vapour low side of the system with the compressor running.
Transfair Engineering: Designing Circuits. 7.5. Refrigerant, Determination of Refrigerant Filling Quantity, Fine Tuning
p. 88
household refrigerators need an accuracy of +/-0.5 g. Register the starting weight and calculate the final desired weight before starting of charging. Some scales are even made to program the needed charge. The charging is completed when the final weight is archived. Do not move the gauge manifold and hoses during charging to avoid false weight indications. Charging by sight glasses. Systems with sight glasses in the liquid line close to the inlet of the entering device allow identifying the correct charges. A system with bubbles (mixture of liquid and gas) are undercharged. Only pure liquid should enter the metering device. But a clear slight glass can also indicate a severe undercharge if it is pure gas or an overcharge (liquid). Therefore this charging method allows only the charge starting from undercharging (clear sight glass caused by PURE gas or already bubbles caused by mixtures of gas and liquid refrigerant) till the sight glass- after passing the bubble stage - become clear. When this will happen saturated liquid is obtained. Some manufacturers require an extra charge above the saturated level to establish the desired sub cooling leaving the condenser; other manufacturers may instead indicate a desired liquid line temperature to be reached by adding smaller quantities during operation of the system. More charging increases the sub cooling and lowers the liquid line temperature. So pay attention in this method: clear sight glasses can be pure liquid (correct or overcharged) or purr gas (strongly undercharged).
Charging for proper superheat (Superheat method). One method to adjust the charging of a system already in operation and tested by performance test is to measure the refrigerant superheat in the vapour line. This approach can only be used for systems with fixed metering devices like a capillary tube in the household refrigeration but not with throttle devices. Superheat is the temperature added to the refrigerant vapour at the end of evaporation/compressor suction above its saturation temperature (typically for the household refrigerators: 2-5C and for air conditioners: 5-8C). Often as much superheat as possible should be obtained between evaporator outlet and compressor inlet. Probably performed the superheat method is a very accurate way of checking and adjusting the refrigerator charge: Only 1% changes of a system charge will cause a change of superheat by 1,7 C or more, if R134a is used. In case of R600a the increase can be even higher.
Measurement. - The system should run as "cooling-only" (bridging of the thermostat cut off). - Install one thermocouple on the suction line and insulated the probe well. - Install the pressure transducer in the suction line. - Run the system for 30 Minutes to allow system temperature and pressure stabilisation. - Take inside refrigerator and freezer temperatures and environmental temperatures and read the pressure and the temperature of the suction line. - Use the refrigerant pressure/temperature calculation program or table to determine the saturation temperature that matches the pressure for the suction line. - Subtract the saturation temperature from the actual suction line temperature, compare it with the requested superheat of 35C for household refrigerators respective 3-8C for air conditioners. By increasing the charge the superheat will drop, by reducing the charge the superheat will increase. If the superheat is 2-3C above the superheat value recommended for the system by the refrigerator design company and/or compressor manufacturer add - liquid refrigerant to the compressor inlet (compressor not running) or - vapour refrigerant through the low side service port with compressor running. It is too low by more than 2-3C, remove vapour refrigerant. After any charge adjustment repeat the measurements of temperatures and pressure to control if the system is adjusted to the required superheat.
Transfair Engineering: Designing Circuits. 7.5. Refrigerant, Determination of Refrigerant Filling Quantity, Fine Tuning
p. 89
Charging for proper sub cooling (Sub cooling method). The charge of systems using devices with thermostatic expansion valves (larger air conditioners and refrigeration machines) cannot be controlled by the superheat method as such devices maintain a constant superheat over a wide range of load and charge conditions. In such cases the measurement can be made in the liquid line using the sub cooling method. Sub cooling is the temperature removal from a refrigerant liquid below its saturation temperature. A typical sub cooling value for a refrigerant entering the metering device (expansion valve) of an air cooler air conditioners' system is in the range of 3-8C. The charts of the air conditioner manufacturer for the specific conditions and loads should be used for fixing the value of sub cooling which refrigerant charge should reached.
Measurement. Run the system for 20-30 Minutes to stabilise the pressure/temperature values with cooling-only (No thermostatic cuttings). - Register the temperature and pressure in the liquid line. If the system has a liquid charging valve, attach the high pressure hose to it and make your pressure readings there. If you have only a high side system access port near the compressor discharge, take the pressure readings there and subtract 0,07 bar (10psig) to allow for condenser pressure drop. -Use the refrigerant pressure/temperature calculation program or table to determine the saturation temperature that matches the pressure just found by the pressure transducer. Subtract the actual liquid line temperature from the saturation temperature. This figure is the system's sub cooling value. More charge will increase the sub cooling; less charge will reduce the sub cooling. If the sub cooling is too low by more than 1,7C, add vapour refrigerant through the low-side service port with the compressor running. If it is too high about more than 1,7C above the value recommended by the manufacturer, remove vapour refrigerant through the high-side access port (use recovery units). After any adjustments of charges repeat the measurement procedures to be sure that the charge is within the correct range.
Transfair Engineering: Designing Circuits. 7.5. Refrigerant, Determination of Refrigerant Filling Quantity, Fine Tuning
p. 90
Transfair Engineering: Designing Cooling Circuits. 8. Safety requirements, Special Safety Requirement for HC-Refrigerators, Electric Safety Tests
p. 91
Such standards have to be applied in addition to the performance standards of refrigerators as described in the next chapter and in addition to the electrical standards IEC/EN for each used electrical part and in Europe the EU Low Voltage Directive (73/23/EEC) as amended 93/68/EEC.
Transfair Engineering: Designing Cooling Circuits. 8. Safety requirements, Special Safety Requirement for HC-Refrigerators, Electric Safety Tests
p. 92
So refrigerators with inflammable R600a and R290 refrigerants need some special designs and precautions and type tests which can differ from the previous considerations of designing and specifications. In this chapter these special design problems and their solutions will be described. A small modification of IEC60335-2-24 become valid with amendment 2 on 2007-01 (compressor sound; warm damp equable climates). Its actual version in 2010 is Edition 7. IEC60335-2-89 was slightly amended in 2005 and in 2007. Its actual version in 2010 is Edition 2
Media
The IEC60335-2-24 (2005) Para 22.110 respective 89 (2002) Para 22.109 allow maximum surface temperature to be exposed to leakage of flammable refrigerator 100K underneath above mentioned ignition temperature >350C; that is why we specify T2<300C and not only T1<450C.
Concentrations between these low and high explosion limit values can be hazardous in presence of an ignition source like an open flame, an electrical spark from an electrical component or discharge of static electricity or a surface hotter than 470C respective 494C. Important is that an explosive mixture can build up even below the calculable concentration if the refrigerator construction is made in a way that an accumulation in dead spaces or deepening is possible. A natural circulation underneath the refrigerator cooling circuit should be insured by using the temperature differences during running. Also some user instructions were to place the refrigerator in the household and labelling of the refrigerator is needed. On the refrigerator appliance we can identify 2 potential hazardous situations which need partially different safety measures: 1. Refrigerant leaks into the surrounding air, 2. Refrigerant leaks into the food compartment, normally closed, so that a concentration above the lower flammability limit can easily be reached. Last can only happen if the evaporator is - inside the food compartment or if the evaporator is - foamed-in behind the food liner, has joints in the evaporator pipe work and if the inner compartment is not completely sealed, for example if there are holes for the thermostat capillary tube and for the power supply cable of the light-switch combination. The 2nd situation can be avoided, if the construction is made in a way that no leaks can go into the food compartment. Normally defrost models today are made in this way in Europe. But the sealing must be tested (see underneath). . The 3rd hazardous situation, air leaks into the system (as the suction pressure is underneath the atmospheric pressure) can be neglected. It would be very rare that there exist sufficient air inside the system for combustion. Even if combustion inside the system could happen, according to tests executed by Liebherr and others the maximum pressure peak of 12 bars created during explosion in the cooling circuit remains under the critical load of any cooling circuit components. Also the 4th hazardous situation that fire from outside will burn down a hydrocarbon filled refrigerator can be neglected. In comparison to conventional R12 or R134a refrigerators the risk to be injured is even lower. In 1997, fire tests executed by Calor Gas in Britain on commercial ice cream freezers showed that there was no significant difference in the fire intensity and fire duration of refrigerators filled with hydrocarbon in comparison to R12 filled systems. High fire intensity was required for failure of the pressure system. The compressor withstood the fire. Failure occurred through brazing joints. More important than the fire it was the observation on the fumes. People in case of fire are seldom killed by the fire itself but by toxic fumes, which in case of R12 is an important risk increase not existing with hydrocarbons. (See Calor Gas: Fire Test Report Application of CARE Refrigerants. Warwick 1997).
Transfair Engineering: Designing Cooling Circuits. 8. Safety requirements, Special Safety Requirement for HC-Refrigerators, Electric Safety Tests
p. 93
Transfair Engineering: Designing Cooling Circuits. 8. Safety requirements, Special Safety Requirement for HC-Refrigerators, Electric Safety Tests
p. 94
Fan motor and blade. A risk assessment and approval tests have to be carried out according to actual version of standard.
Transfair Engineering: Designing Cooling Circuits. 8. Safety requirements, Special Safety Requirement for HC-Refrigerators, Electric Safety Tests
p. 95
8.3.1.
Electric Connections
Electrical connection are considered as not normally sparking if they are made in a way that they cannot be disconnect by use, vibration or accidentally. Brazed or welded wire connections are acceptable. Also wires with crimped terminals screwed to a contact. Plugs and sockets are acceptable if the separation force exceeds 15N and if they meet in their construction the standard IEC600079-15, especially chapter 14. The quantity of electrical terminals in the hazardous area should be limited.
8.3.2.
Compressor Relay
The best is to use a sealed or solid state (PTC) relay which cannot give any spark. Other solutions with a sparking relay in a sealed box need an approval acc. to the valid standard like IEC 600079-15 and EN 60730-34. PTCs are better than sealed boxes because seals can be damaged by incorrect repairs.
8.3.3.
Standard external overload protectors (like Klixons) cannot be used except in sealed and approved boxes. Solid state or sealed protectors without any sparking can be used. Also special combined compressor relays and overload protectors made, sealed and approved acc. to the IEC 600079-15 can be used. Today R600a and R290 compressor models have to comply with IEC603352-34 and are not critical anymore.
8.3.4.
Even if the capacitors themselves cannot produce sparks the leads connected to them can! So called integral leads (flying leads) can fulfil the requirements of IEC 600079-15 and have to be used to fulfil IEC60335-2-34. International compressor manufacturers are supplying the HC compressors with approved electrical devices like terminals, relays, overload protectors and, if part of compressor, capacitors (chapter 8.5.1-4) acc. to the new standard IEC 60335-2-34, which integrated the Hydrocarbon safety requirements so that the refrigerator manufacturer does not need to make own constructions, tests and approvals on this components according to chapter 8.3.2.-8.3.4 and IEC60079-15.
8.3.5.
On-off switches of refrigerators are often not needed and can be easy eliminated. In single cases if they are still needed, they should be placed as far as possible away from the refrigeration circuit in the upper area of the refrigerator to avoid the risk being in flammable atmosphere. After the relocation it has to be tested that no explosive gas can reach it (chapter 8.5.3.; IEC60335-224 clause 22.109 or IEC60335-2-89 clause 22.108). If this separation from hazardous areas is not possible standard sparking switches cannot be used and must be replaced by non-sparking sealed versions as used out doors in a waterproof version and approved acc. to IEC 600079-15. The same has to be applied for the door light switch: If it is not placed inside the food compartment or outside the door in an area leaks can reach according to executed type tests only sealed door switches can be used (see Chapter 8.4.).
8.3.6.
First condition is that the temperature of the lamp is not exceeding 350C. Filament, tubular fluorescent or other discharge lamps can fulfil this condition. The lamp rating concerning temperature class T2 must be printed on the lamp and confirmed by the manufacturer. Even lamp holders, which are non-sparking in normal operations, shall be made in a way that arc, sparks or hot spots are minimised. Their construction have to follow IEC600079-15 Paragraph 21 and requires enclosure and special fixing, torque
Transfair Engineering: Designing Cooling Circuits. 8. Safety requirements, Special Safety Requirement for HC-Refrigerators, Electric Safety Tests
p. 96
strength of screw lamp holders and other specifications, like non-sparking plugs and sockets Para 20: A E14 respective B15 lamp to be fixed with 0,15Nm or a E27 respective B22 lamp to be fixed with 0,25Nm into its lamp holders shall withstand a push force and a pull force of 10N+/-1N for 1 min in direction of the axis of the lamp holder. A lamp holder used in a hazardous area, the way of its fixing and terminal connection should follow this standard. Often screw lamp holders with a rubber lid for water proof are fulfilling the requirements of this standard. Fluorescent lighting ballast and starter are normally made not to be ignition sources. Starters are tested by lamp manufacturers according to IEC60079-15 Para. 33.10 and declared to be confirm: Normally only sparks can happen on loose contacts, terminals plug and sockets so that the considerations of chapter 8.3.1 has to be applied.
8.3.7. Thermostat
Standard thermostats have bodies with open contacts which can spark and cannot be used in hazardous areas. Either the thermostat is relocated outside the ex-zone and their position is type tested according to the standard, that leaked refrigerant can not stagnate in areas with such a sparking component or only sealed or solid state thermostats can be used which follow the requirements of IEC 600079-15. Even a standard thermostat can be used if it is inserted in a sealed box following the IEC 600079-15 standard, but good thermostat manufacturers (Invensys, Danfoss etc.) have such sealed models with certificates from authorized bodies in the supply program with nearly same price as their standard thermostat version.
8.3.10. Defrost Probe, Temperature Cut-Out and Defrost Timer Control (in No Frost Models)
The existing defrosting probe, temperature and defrost timer controls as used on No Frost models can spark under normal operation conditions. Parts which are placed in areas with potential leaks must be replaced by ones which meet the IEC 60007915 requirements. Bimetal temperature probes can be quite easily sealed. But there exist often the possibility to relocate parts like timers in areas where no explosive mixture can be built up (for example in the table top) which should be checked first and tested according to the mentioned IEC 60335-2-24 standard clause 22.108 (our chapter 8.5.3.) to avoid often more expensive electrical components following the IEC 600079-15 standard.
Transfair Engineering: Designing Cooling Circuits. 8. Safety requirements, Special Safety Requirement for HC-Refrigerators, Electric Safety Tests
p. 97
fixed and that it cannot be removed during service or that it cannot be wrongly positioned. It is absolutely necessary to mark the lid of such sealing boxes with a label showing the importance of replacing the lid to maintain the sealing. The cable entries should be made via terminals permanently fixed to the box and through glands. Any possibility to use other, not sealed entries as the protected ones should be avoided by the construction of the box. This sample of sealed box and service precautions shows the problem which we can face in areas with informal refrigerator services. Any solution which separate the leak risk areas from the electrics by relocations and which can use standard electrical components are preferable to solutions which depend on qualified service which will not destroy the sealing.
8.3.12. Manufacturers test of electric component for flammable gas atmosphere, conformity declarations and markings
The manufacturer of all electric components used in potential leak zones of flammable refrigerant must execute type tests according to IEC60079-15 mainly para.33, grant the conformity declaration for it and mark its product including temperature class T2 or higher to allow refrigerator manufacturers to use them in such hazard zones. Components not tested and approved according to IEC60079-15 or other IEC60079 clauses are not allowed to be used in these potential leak areas.
Transfair Engineering: Designing Cooling Circuits. 8. Safety requirements, Special Safety Requirement for HC-Refrigerators, Electric Safety Tests
p. 98
High voltage (Dielectric strength) test at 1000V (often at 1250V) for basic insulation or 3750V for reinforced insulation with threshold <3,5mA; Leakage current test with 1.06x rated voltage I-PE <3,5mA and/or Insulation test with 500Vdc and threshold between L-N and PE>1M (basic insulation) or >7M (reinforced insulation) Absorbed current and power test with threshold value to be fixed per model to assure energy labelling class values; Residual voltage test (only needed for on models with capacitor) with rated voltage and threshold value <60V to avoid electrical shock on de-plugging.
In addition other parameters like correct wiring, earth connection, IP54 sealing, functioning of all electrical components like switches, thermostats, signal lights, light switches, light should be inspected and/or tested. The safety standards specify which electrical safety rules the manufacturer have to respect, which electrical components acc. to which electrical standard he can use in the appliances and which kind of approval he needs.
8.5.3.
Electric components and cooling circuits must be separated by construction (see our chapter 8.2.-8.3.) and the separation tested by leak simulation tests for type approval. We have to execute such tests for 3 different groups of appliances: 1. Appliances with protected hydrocarbon charged cooling systems without any part of the cooling system inside the food storage compartment, but with electrical components which do not comply with the IEC 600079-15 requirements (n protection, IP54); Appliances with protected hydrocarbon charged cooling systems where the cooling circuit parts located inside the food compartment are constructed with an additional at least double layer, each of min. 0.1 mm thickness; the bounded seams must have a minimum width of 6mm; or the cooling system inside the food compartment is built into a separate enclosure; in both cases the food compartment contain electrical components which do not comply with the IEC 600079-15 requirements ("n protection, IP54); item 2 is practically not used; Appliances without protected hydrocarbon charged cooling systems where the unprotected electrical components (thermostat, light switch, light etc. are relocated outside the cooling department in areas supposed to be free of refrigerants in case of leakage.
2.
3.
In all these cases leakage have to be simulated and the Hydrocarbon concentration to be measured near electric components by Hydrocarbon leak detectors. IEC/EN600335-2-24 in clause 22.107 describes test of protected cooling circuits in combination with unprotected electrical components which can cause arcs, sparks or hot surfaces while clause 22.108 describes test of unprotected cooling circuits in combination with n protected electrical components (IEC/EN 600079-15 n protection; IEC/EN 60335-2-24 Annex CC), certified by component manufacturers, inside food compartment and clause 22.109 the test of standard electrical components allocated to outside food compartment, if their location cannot anymore be reached by leaking refrigerant.
Transfair Engineering: Designing Cooling Circuits. 8. Safety requirements, Special Safety Requirement for HC-Refrigerators, Electric Safety Tests
p. 99
The leak simulation should be made from all critical points. All interconnecting points are considered as critical points as well as locations of a capillary tube which can be destroyed mechanically. At these points the leak has to be simulated through a capillary tube of 0.7 +/- 0.05 mm and 2-3 m length. In case a joint is foamed in also the leak capillary tube has to be foamed in, but in a way that the tube will not be blocked by foam. 80% of the nominal charge of appliances should be injected or the maximum which can be injected inside of 1 hour. Doors and lids should be closed during test to check if hazardous gas can be accumulating inside the compartment. The gas should be taken from the vapour side of a bottle with a temperature of 32 +/-1 C if leakages are simulated on low pressure side and 70 +/- 1 C if leakage is simulated on the high side pressure circuit. At the end of the test there must be liquid refrigerant left in the bottle. In case of blends this test has to be executed with the fraction which has the lowest LEL value. The instrument which measures the gas concentration, like calibrated infrared sensors, gas chromatographs or mass spectrometer should have a reaction time of max. 3 sec. and sampling should be take at least every 30 s inside and outside the compartment near electrical components for 1 h after injection of gas has stopped. Sampling must be limited to maximum 2 ml every 30 sec. not to influence test results (on/off valve on inlet to gas chromatograph or mass spectrometer; if Inficon Ecotec is used, remove capillary flow alarm setting during such tests). Best are IR sensors with gas flow control and return of sampling gas into the area, from which gas was taken (Drger PIR 7000 Type 334 with gas probe inlet and return system IWS). The measured value should not exceed 75 % of the LEL of the refrigerant and 50% of the LEL for a period exceeding 5 min. to pass this test. 30 min. after gas injection into close compartment is finished the door or lid is opened by 90 for 2-4s every 30s. Separate components such as thermostats which contain less than 0.5g of flammable refrigerant are not considered to cause a fire or explosion hazard in the event of a leakage of the component itself acc. to the standard IEC 600335-2-24.
Transfair Engineering: Designing Cooling Circuits. 8. Safety requirements, Special Safety Requirement for HC-Refrigerators, Electric Safety Tests
p. 100
8.5.6. Testing and Control of "N Protected Components Used in Hydrocarbon Leak Areas
Electrical
In cases where electric components are placed in areas in which potential leaks can happen or in which the a.m. appliances could not pass the leak simulation tests or the scratch test the electric components must fulfil the requirement of IEC 60079-15 with the protection n. Refrigerator producers have to insist on their suppliers of these electrical components to receive at least a declaration of conformity for the component and, better, test reports of a good, internationally reputed test institute. In case of any doubts it is better to insist of another independent test report or to replace such items by ones without any reserves. If the refrigerator manufacturer has a well equipped laboratory he can do such tests according to IEC600079-15 himself.
Transfair Engineering: Designing Cooling Circuits. 9. Temperature Control, Capillary Tube Thermostat
p. 101
9. TEMPERATURE CONTROL
Different types and kinds of temperature controls can be used to control the operation of refrigerators and freezers.
Following terms are used: Operating range. The operating range of a thermostat describes the temperature range in which the thermostat can operate. The whole needed temperature ranges in the household refrigerator section cannot be covered by one control type only, so different types working with different ranges are needed. Adjustment range. A mayor group of thermostatic controls are adjustable inside their operating ranges. The adjustment range is the difference between the cut-in point in warmest control positions to cut-in point in coldest control position. There exist some exceptions used in chest freezers with a constant cut-in feature. In such a case the adjustment range is the difference from cut-out point in warmest control position to cut-out point in coldest control position. The 2 temperature values of cut-in temperature range and the 2 of the cut-out temperature range are normally printed on the thermostat casing. Switching differential. The switching differential is the difference between cut-in and cut-out point of the temperature control. Correlation between adjustment range and switching differential. There a certain correlation between adjustment range and switching differential, i.e. the indicated limits cannot be assigned optionally. Tolerances. There exists a permissible deviation from nominal operating point. Adjustments in the refrigerator factory and in the service. The temperature control is set in the thermostat factory according to specified temperature values. In the refrigerator factory adjustments never should be made at the switch differential screw, but only on the range screw or the temperature screw: Such an adjustment will change the cut-in and cut-out value to be shifted in direction of cold or warm, but not the switch differential, if a standard thermostat is used which allows adjustment on the cut-in position. In case of a thermostat with constant cut-in is used, such adjustment will change the cut-out position and therefore in
Transfair Engineering: Designing Cooling Circuits. 9. Temperature Control, Capillary Tube Thermostat types
p. 102
addition the temperature differential. The new set point must be temperature controlled to ensure the correct operation of the thermostat. OFF-position. Temperature controls are available with and without OFF-position. The OFF-position will interrupt the operation even when the temperature is above the cut-in position. Dial layout. It seems that all manufacturers of adjustable capillary tube thermostats for household refrigerators follow the same dial layout: - A clockwise rotation of the dial shaft causes colder control settings. - The standard dial angles are the following: - Total adjustable range: 270 - Dead angle: For thermostats without OFF positions: 90 For thermostats with OFF position 45 and OFF position at 45 Following types of thermostats used for household refrigerators are on the market:
Transfair Engineering: DesigningCooling Circuits. 9. Temperature Control, Capillary Tube Thermostat, Standard Thermostats with Auxiliary Switch p. 103
9.1.3.
Transfair Engineering: Designing Cooling Circuits. 9. Temperature Control, Thermostats with Defrost Push Button, Fast Freeze
p. 104
temperature value can be fixed separately or parallel with the cut-off characteristic of the thermostat. The main switch is manually locked with starting the fast freeze cycle and if the fast freeze temperature is reached, the system automatically resets this lock, so that the system will go back to the standard cut-in cut-off control. In addition a manually reset is possible by turning the dial shaft to OFF position.
Terminal 2-3 opens at temperature rise. Terminal 3-4 closes at temperature rise. Terminal 3-6 opens in OFF position. This type comprises all features of the last type; but with an so called SPDT switch instead of an SPST switch between the terminals 23 a solenoid 3 way valve can be switched to control in function of the refrigerating part temperature and with that the refrigeration cycle to the evaporator of the freezing or of the freezing and refrigeration part. Further details can be granted from Danfoss about Thermostat type 077B63 and their 3 way valve or from Ranco about thermostat type K61.
Transfair Engineering: Designing Cooling Circuits. 9. Temperature Control, Thermostat with 2 Sensors, Bimetal Thermostat, Electronic Controls
p. 105
and +32C. There are different versions with fixed cut-in or with adjustable cut-in. Even a version with crossing cut-in and cutout exists.
Transfair Engineering: Designing Cooling Circuits. 9. Temperature Control, No Frost Defrost Timers and Thermostats, Damper Thermostats, Testing p. 106
instead of 58C fresh meat, fish, milk products, vegetables and fruits remain 2-3 times longer fresh, keeps 3 times longer taste, aromas, vitamins and minerals. This can be realized with a 3 door model, a 2 door model with movable or not movable inner insulation separators. The different temperature zones (5-12C, 0-3, >18C) can be kept already by evaporator and insulation designs without separate temperature controls up to a certain deviation range or - very accurate - by temperature controls on each zones with refrigerant valve or separate circuits and compressors (expensive solution). But such 3 temperature zone models will consume more energy as a 2-door (2-temperature) model, a part of fridge remain on -1-3C temperature while in the past only on 5-8C. Even a temperature range of -3C for fish, -1C for meat, +2C vegetables and fruits would be best, but it needs in this case a separate temperature control on this food storage part which can be easier and cheaper realized by an electronic control. This temperature zones are under freshness of food a very relevant aspect, but still not enough reflected in the Energy labelling system as it needs this additional model group to be compared and not to be compared with standard fridge-freezers. Ice and Water Spender. On side-by side models it is todays standard. It is sold as lifestyle product (party house bar). The operation needs further controls which can be integrated into the electronic control (temperature, levels, refilling of ice maker by tap water, if as often done the refrigerator is connected to tap water). Control of variable compressor speed. If a variable compressor is mounted the speed control can be integrated into the electronic control to let the compressor run according to temperatures and load conditions. This often can save 2033% of energy in comparison to conventional compressors with 1 speed to reach energy saving models (A+, A++).
Transfair Engineering: Designing Cooling Circuits. 9. Temperature Control, No Frost Defrost Timers and Thermostats, Damper Thermostats, Testing p. 107
cut-in temperature of -20C (at 736.6 mm Hg) will cut-in already on a 2+/-0.5 at 1500m respective a 4 +/-0.5K at 3000m lower temperature as calibrated, depending with which gas it is filled. All temperature switch settings of a system should be tested in this way. In addition electrical tests should be executed, like current (6A on main contact, 0.1 on signal contact) flash test 0-400Vac (0-180 sec), normally at 1000Vac, insulation test and electric strength 500Vdc (0-180 sec) 3-50 MOhm, depending which temperature control is used. The supplier of temperature control should guarantee a maximum failure rate of 0.7% and the measured rate should be in the range of 0.5% and not higher. To allow replacement already after the performance test inside the factory and in case of service, the feeler should be place in a plastic tube when it will be foamed in to allow the exchange of the unit.
100% control on temperature control device. Modern energy saving refrigerators for N and SN climate class need several hours for cut-off after first time of refrigerator running and often 1-2 days to cut-in again with closed doors, so the thermostat of all refrigerators cannot be tested by the short performance test and even not by the 2-4h performance test on samples. But up to 0,7 % is already a high failure rate of such temperature controls and cost relevant for maintenance service during guarantee beside of damage of trade mark by such a failure. Therefore good refrigerator manufacturers control cut-in and cut-off functioning and temperatures of 100% of used thermostats to reduce these high guarantee costs. We strongly recommend to do such 100% test - best inside factory of supplier of such controls, so that statistical sampling and additional control tests inside the refrigerator factory are sufficient - and to establish mounting and handling precautions to prevent damage of such thermostats during assembly.
Relevant remarks in operation manual of fridge/freezers with single temperature sensor control: Freezer defrosts in a fridge/freezer. In a cold location the freezer may begin to defrost or even completely defrost, so defrosted frozen food will spoil. Most fridge freezers will only operate satisfactorily in an ambient temperature down to +10 C, if made for SN climate class, or +18C if made for N climate class (see chapter 1.3.2.). This may seem strange but the fridge thermostat governs the operation of the freezer and if the ambient temperature drops to either of the figures above the fridge will switch off. That will not be a problem for the fridge which should be cool enough to keep its contents safe but it will mean that the freezer will cease to work and that will create a problem. Therefore the customer should be warned in the operation manual or by a warning sign to insure minimum ambient temperature to ensure functioning of freezer.
Transfair Engineering: Designing Cooling Circuits. 10. Final Rests, Definitions, Classifications, Designs, Characteristics of Household Refrigerators p. 108
In this chapter we will describe the final tests to be executed to optimise a refrigerator and/or freezer circuit after each circuit element was already optimised and tested and tests to be executed according to the applied standards. Many final tests to be executed are described in the a.m. ISO standard 15502, which replaces ISO 7371, 5155, 8187, like Testing of reached temperatures in the refrigerator and freezers Testing of storage temperatures Water vapour condensation test Energy consumption test Ice making test Test of percentage running time Temperature rise time (freezer) Freezing test (freezer)
The relevant standards are describing these tests in all needed details so that we have not to repeat them in this chapter in all details.
Transfair Engineering: Designing Cooling Circuits. 10. Final Rests, Definitions, Classifications, Designs, Characteristics of Household Refrigerators p. 109
Transfair Engineering: Designing Cooling Circuits. 10. Final Tests, Refrigerator Thermo-Insulated Test Room and Measurement Equipment
p. 110
Starting current. Following starting currents are needed: - At Un = 110 V and 115 V: 36 A - At Un = 220 V and 230 V: 18 A
Control Panel
Wh, V, A, Cos Phi, Hz
Temperatures
Monitor
Thermoregulator
Printer/ Plotter
Personal Computer
See Transfair Engineering: Refrigerator Test Room Equipment and Manuals. Dsseldorf 2000
Transfair Engineering: Designing Cooling Circuits. 10. Final Tests, Refrigerator Thermo-Insulated Test Room and Measurement Equipment
p. 111
- Electronic counters with BCD outlet for measuring speed (rev./min) on kWh meters All or parts of it can be integrated in a registration programme instead of the control panel. Connection panel (inside test room). Inside the test room on the backside wall there should be positioned a panel to connect the measurement signals and the power supply to the refrigerator(s). This panel should have following facilities: - Voltage supply - Connection for 2 pcs. pressure transducers (for example Hottinger & Baldwin type PM3) - Connection of minimum 16 pcs. thermo-elements cu/ko (for example type T specifications according to ANSI 96.1.82 or type J) with standardised plugs and plug sockets should be chosen. - 8 digital inputs (8 signals, 170-270 V, 50 and 60Hz; 60-140 V, 50 and 60 Hz). - Option: 8 digital outputs (8 signals, 220 V, 50 Hz; max load 1A).
Pressure:
Power: Current:
Energy: Voltage:
Range: 0 - 1200 W Accuracy: +/- 0,5% of measured value Range 1: 0 - 10 A at Un = 110 and 115 V, 50 and 60 Hz Range 2: 0 - .5 A at Un = 220 and 230 V, 50 and 60 Hz Accuracy: +/- 1% of measured value Measurement with approved gauges in the a.m. range of power and current and the accuracy of 1% at actual load. Range 1: 170-270 V, 50 and 60 Hz Range 2: 60-140 V, 50 and 60 Hz Accuracy: +/- 0,5% of measured value.
The selected Voltages and Frequencies depend for which market the refrigerators are developed. There are different ways possible to register the measured temperatures, pressures, humidity and electrical data and to register it.
Transfair Engineering: Designing Cooling Circuits. 10. Final Tests, Refrigerator Thermo-Insulated Test Room and Measurement Equipment
p. 112
Max. load for all a.m. transducers are: max. = 36 A for 5 sec. Un = 110 V/115 V and 50/60 Hz or max = 18 A for 5 sec. at Un = 220/230 V and 50/60 Hz This equipment is normally sufficient to measure 2 refrigerators or freezers for designing and optimisation purpose independently from each other. For performance tests to control the reached quality of the production the same equipment can be used; but in this case more refrigerators can be measured parallel, only limited by the measurement channels (each proposed interface has 8 analogue inputs, 2 units 16, 3 units 24 channels etc.). Transfair has developed such computerised measurement hard- and software by combining reliable and cheap standard components. See Transfair Engineering: Refrigerator Test Room Equipment and Manuals Description, Manuals, Technical Documentation. Dsseldorf 2000.
Transfair Engineering: Designing Cooling Circuits. 10. Final Tests, Mechanical, Storage Temperature, Water Vapour, Energy Consumption, Temp.rise p. 113
Thus, a G class model uses 125% or more energy of an "average" cold-appliance of the same type and the same adjusted volume, while an A class model uses less than 55% of an average appliance of the same type and adjusted volume. The energy consumed by an average appliance of a given type and adjusted volume is calculated from the appropriate average performance reference line equation given in Table 1 and based on the values measured under the norm EN 153. Table 2: Type of appliance and Ma and Na factor values Type of appliance Temperature of coldest compartment 1 Larger Fridge > 6 C 2 Refrigerator/chiller > 6 C 3 Refrigerator no star > 6 C 4 Refrigerator * 6 C * 5 Refrigerator ** 12 C ** 6 Refrigerator ***/ 18 C ***/*(***) 7 Fridge-freezer *(***) 18 C ***/*(***) 8 Upright freezer 18 C *(***) 9 Chest freezer 18 C *(***) 10 Multi-door or other appliance
M 0,233 0,233 0,233 0,643 0,450 0,777 0,777 0,539 0,472 (1)
N 245 245 245 191 245 303 303 315 286 (1)
Transfair Engineering: Designing Cooling Circuits. 10. Final Tests, Mechanical, Storage Temperature, Water Vapour, Energy Consumption, Temp.rise p. 114
(1) For these appliances, the temperature and star rating of the compartment with the lowest temperature will determine the values of M and N. Appliances with 18 C *(***) compartments shall be considered as fridge-freezers *(***).
Table 3: Correction factor Correction factor Value FF (frost-free) 1,2 1 CC (climate class) 1,2 1,1 1 BI (built-in) 1,2 1 CH (chill 50 Kwh/y compartment) 0
Condition For frost-free (ventilated) frozen food compartments Otherwise For tropical appliances For subtropical appliances Otherwise For built-in appliances (1) of under 58 cm in width. Otherwise For appliances with a chill compartment of at least 15 litres Otherwise
(1) An appliance is built-in only if it is designed exclusively for installation within a kitchen cavity with a need of furniture finishing, and tested as such.
New EN153 2006. The revised version EN153 2006 as result of new EN 15502 (2003) is still under vote and being expected to become valid End of 2006. It concerns following changes: The fridge mean temperature for the storage test (Table 2) is 4C with allowed maximum and minimum temperatures of 8C and 0C. (The fridge mean temperature for the energy test (Table 5) remains at 5C and must operate between 10C and 0C). Two tests and an interpolation can be carried out for forced-air (frost-free) appliances. (In the current EN ISO 8561, only one test is allowed so that there is no temperature deviation warmer than 15C during the defrost cycle). After the first stabilisation and test period, a further test should be carried out which must be within a temp of 0.5C and the energy should be within 3%. The temperature below the test platform is measured and should be within 1.5K of the ambient temperature (Clause 8.4). (This is currently not measured, the room ambient must be 25 0.5C). The new test voltage will be 230 V. The current EN 153 specifies 220 V. The energy consumption is adjusted by an ambient temperature correction factor (Clause 15.2.1). Background. The test for all appliances involves setting each compartment(s) to the characteristic temperature as follows: COMPARTMENT CHARACTERISTIC TEMPERATURE Cellar +8 to +14C Fresh food compartment (Fridge) mean of +5C Chill -2 to +3C 1 star No warmer than -6C 2 star No warmer than -12C 3 star No warmer than -18C 4 star (Freezer) No warmer than -18C A cellar compartment is useful for storing fruit, vegetables, beer and wine. The market share for these is very small. A chill compartment is useful for storage of delicate foodstuffs e.g. fish, meat and shellfish. Chill compartments are normally only available with frost-free fridge-freezers. The storage time for the various star compartments will be indicated on food packaging but typically it is: 1 star 1 week 2 star 1 month 3 star 3 months A 4 star compartment is a true freezer i.e. it can freeze down fresh food from room temperature and will have a freezing capacity an amount in kg which can be frozen in 24 hours declared on the rating plate. The freezing capacity test is also covered in EN 153. Exempting frost-free appliances cooled by forced air, once the region of the characteristic temperature has been found two 24 hour tests will be carried out; one slightly above and the other slightly below the characteristic temperature. An interpolation will determine the energy consumption at the precise temperature.
Transfair Engineering: Designing Cooling Circuits. 10. Final Tests, Mechanical, Storage Temperature, Water Vapour, Energy Consumption, Temp.rise p. 115
Compartments cooled by forced air are normally frost-free and currently undergo only one test run. This may change with the introduction of the combined standard (ISO EN 15502). This defrost cycle has temperature and time restrictions. Frozen food compartments are packed full of tylose which represents the thermal characteristics of lean beef. (The US test standard uses a sawdust mixture and the Australian standard uses nothing the compartment is empty!) The volume of the compartment is measured, this crucial to the energy label calculation. For the energy label consumption of the appliance on test is compared with a standard energy consumption for an appliance of that type and size or net volume. This net volume is typically 10 15% greater than the volume which can be realistically used by the consumer. Door opening. Unlike the test for commercial refrigeration (EN 441), neither the current or proposed EN 153 has any door opening aspect. Since the ambient temperature is 25C, there is an argument that this presents a similar situation to heat ingress that would be experienced with door opening. Comparative tests between door opening and doors shut have been conducted (See BNC11). MTP research[1] suggests that energy consumption measured for energy label information reflects real use, including compensating for a lack of any door openings and the more typical UK 20C ambient. However the energy label testing cannot present ingress of humidity particularly important for automatic frost-free appliances1[2]. This does not matter for timed frost-free appliances, they will defrost every 10-24 hours anyway. With the doors shut for the 3 days of the test, automatic or sensor frost-free appliances may not defrost for 75 hours. Yet in normal use, these will easily show defrost peaks twice per day. One possible solution therefore would be to have a door opening condition for (some) frost-free appliances during the test for energy. Alternatively, these appliances could loose their favourable 1.2 factor in the energy index calculation. Fit for purpose. Fridge temperatures are obviously important for food safety and therefore storage temperatures colder than 5C are to be welcomed. Appliances with longer cycling times may find it difficult to keep a mean of 4C within the boundaries of 0 and 8C. It is disappointing that the mean for the energy test in either the prEN 153 or ISO 15502 also has not moved to 4 or even 3C. Since 1.7.2010 EU forbid sales of household refrigerators class B-G and only allow sales of class A . furthermore the class is split into 4 groups A, A+, A++, A+++. Each extra + means a 20% higher efficiency respective a 20% less energy consumption, so that A+++ is 60% more effective as A. MTP research comparing the standard energy test with a 'real use' scenario shows that some fresh food compartments (fridges) do not quickly recover their correct temperatures. Further research is necessary to consider this issue. Energy Labelling EN 441 for commercial refrigeration. Similar labelling system exists for commercial refrigerators.
Gaussian function except that there is a long tail on the side of the inefficient models while the efficiency of the most efficient model is bounded.
Transfair Engineering: Designing Cooling Circuits. 10. Final Tests, Mechanical, Storage Temperature, Water Vapour, Energy Consumption, Temp.rise p. 116
2) The aim of the label is to encourage people to buy more efficient appliances - this means that it is not necessary to set the width of the efficiency classes such that there are an equal number of models in each class, but rather in such a way that it is a compromise between reflecting the real efficiency distribution of the market at the time that the label is introduced and the efficiency distribution one may hope to achieve after some years. Thirdly, that the highest efficiency class needs to be theoretically attainable even if it is not attained by any model at the time the label is introduced. When the cold-appliance energy label was introduced in 1994 there were almost no models in the A efficiency class available on the market; however, a detailed engineering analysis had shown that it was quite possible to manufacture A class models. Since that time several hundred A class models have become available on the EU market, justifying the principle of leaving the top efficiency class almost empty when a new labelling benchmark is set. Meanwhile C-G models vanished completely from the market mainly already as market result. An EU Voluntary Commitment for cold appliances is negotiated with industry, wherein the current C class appliances are phased out as per January 2004 followed by a "fleet" (i.e., weighted according to the sales of the different models for each manufacturer) average efficiency of new products, reaching the EEI=52 level by 2006. A new scaling is under negotiation in EU to be established soon.
Transfair Engineering: Designing and Prototyping of Refrigerator and Freezer Cooling Circuits. 10. Final Tests, R600a Properties Tables
p. 117
The first measurement stage is recommended by CECOMAF GT4-001 as basis for the catalogues' values of LBP compressors (LBP = Low Back Pressure = low evaporating temperature as used for our applications). The second measurement stage has relations to the operation conditions which we find at the stage just before the thermostat cut off to determine the standard energy consumption. Already out of these a.m. temperature measurements on the refrigerator system and the maintaining of the temperature in the cabinet according to the applied class of the standard we can calculate the reached performance. To improve the data set for performance calculation we should also register the high pressure reached on the condenser and, if existing, the temperatures on the oil cooler. So we will have - beside of the maintained temperatures - in the cabinet according to the supplied standard and class following ENTRY DATA set: Entry Data: Refrigerator duty Evaporator temperature Condenser temperature Suction condition Delivery condition Liquid return temperature High pressure Unit kW C C C C C bar abs. For example: 0,2KW -25C +55C +52C +60C +24C
CHEST FREEZERS
Transfair Engineering: Designing and Prototyping of Refrigerator and Freezer Cooling Circuits. 10. Final Tests, R600a Properties Tables
p. 118
Evaporator Temperature. Thermocouple feelers have to be positioned on the evaporator on the inner wall of the chest freezer or freezer's compartment of the refrigerator and on the refrigerator's evaporators as follows: - 1 probe near the entry point of the evaporator coil (Top), - 1 probe on half height (in case of horizontal coils) or in the middle of the side wall behind which the half of the length of the evaporator tube is positioned (in case of vertical serpentine tube evaporator) and - 1 probe at the exit of the evaporator (often at the bottom of the evaporator). The 3 probes can be replaced by one probe if the position of the probe represents the mean temperature of the evaporator according to different measurements. Condenser Temperature. Thermocouples' probes have to be positioned on the tube coils of the condenser. - 1 at the entry point of the condenser - 1 at the middle of the length of the coil and - 1 at the exist point of the condenser. After several trials the 3 measurement points can be replaced by 1 measurement point if the point represents the mean temperature of the condenser. Suction Condition. A small tube inside the foam beside the suction tube from the compressor compartment's side has to be made to place a thermocouple probe on the suction tube. Delivery Condition. A thermocouple has to be positioned on the delivery tube of the compressor. Liquid Return. A thermocouple can be positioned at the inlet of a capillary tube, if accessible, to measure the liquid return temperature. Often chest freezers have the capillary tube inside the foam. In this case the same hole as the one for the suction condition can be used to position the thermocouple probe. High Pressure. On the tube between compressor and condenser a small hole can be pierced with a special piercing tool and connector valve without soldering. For example: Refco tube piercing valve HP-41, or Refco Tupper valve E2 36-1 or Refco supper rap LT-36 (5mm, 3/16"), LT-46 (6mm, 1/4" ), LT-56 (8mm, 5/16"), LT-66 (10mm; 3/8); with soldering also the cheap connectors Refco A-31905, A-31906, A-31908, A-31910 can be used. A valve pressure gauge has to be connected to this valve. In case of the chest freezer also a hole can be pierced in the filter-dryer and a connector tube can be soldered to this hole. Low Pressure. A vacuum gauge on the compressor filling tube will be connected to measure the low pressure side with a vacuum gauge. The connection between tube and gauge can be a Hansen coupler to be able to fill the system again when needed.
Transfair Engineering: Designing and Prototyping of Refrigerator and Freezer Cooling Circuits. 10. Final Tests, R600a Properties Tables
p. 119
Such programs can also be received through the suppliers of refrigerants. For our customers we add a programme which can be used to calculate out of the a.m. measured entry data the reached performance of the refrigerator under good conditions, like Specific Enthalpies: End of Evaporation - Compressor suction - Compressor Delivery - Expansion valve/Capillary Delta Hs - Refrigeration Effect - Superheat - Compressor Work - Total Heat Rejected - Sub cooling Unit kJ/kg kJ/kg kJ/kg kJ/kg Unit kJ/kg kJ/kg kJ/kg kJ/kg kJ/kg
Such performance calculation bases on measurements and following refrigerant properties and formulas: FOR EXAMPLE FOR HFC 134a following calculations and tables are used. The US-National Institute of Standards and Technology (NIST) have issued such a program with a database Reference Fluid Thermodynamic and Transport Properties Database (REFPROP) which allows the calculation of thermodynamic properties under ideal conditions of different refrigerants. It can be purchased online for US$ 200 at http://www.nist.gov/srd/nist23.htm and the Manual can be seen at http://www.nist.gov/srd/webguide/nist23-7/23v7.htm#2.%20INSTALLATION . The comparison of measured data with these calculated optimal data allow the systematic improvement of the circuit by intervening in the areas with higher deviations.
MOhm. cm
Transfair Engineering: Designing and Prototyping of Refrigerator and Freezer Cooling Circuits. 10. Final Tests, R600a Properties Tables
p. 120
MOhm. cm % wt % wt
where Tr = T/Tc ,
For R134a:
X = 3.82825 B = 0.2124913803 K = 7.250023581 Tc, Pc, Vc = 374.15(K) Pc = 40.55(bara) Vc = 1.964058842(I/kg) A1 = -10.72969406 B1 = 5.0713498381
C1 = -467.15522467 A2 = 14.034313767 B2 = -8.6811368103 C2 = -679.27189635 A3 = -11.321632367 B3 = 8.0404407351 C3 = 1661.953119 A4 = 3.201606791 B4 = -2.3711553933 C4 = -620.50640774
For R600a:
10.14.3. EXTENDED ANTOINE EQUATION B Ln(P) = A + ----- + DT + ELn(T) where P = vapour pressure bara, T = temperature K
C+T
For R134a:
A = 123.5423 B = -5763.49
For R600a:
10.14.4. LATENT HEAT OF VAPORISATION DHvap = A + Bx + Cx + Dx + Ex4 where x = (1- (T/Tc)) (1/3) , T = Temperature K , Tc = Critical Temperature K, DHvap kJ/kg C = 194.56068 For R134a: For R600a:
A =0 B = 225.00842 D = -142.9851 E = 57.587846
10.14.5. IDEAL GAS HEAT CAPACITY Cp(ideal) = A + BT + CT + DT + E/T C =-2.866246E-06 For R134a:
A = 0.143897 B = 0.003005 D = 1.7812019E-09 E=0
Cp(ideal) kJ/kg.K
10.14.6. SATURATED LIQUID ENTHALPY Hliq = A+Bx+Cx+Dx+Ex4 where x = (1- (T/Tc)) (1/3) , T = Temperature K , Tc = Critical temperature K , Hliq kJ/kg C = 58.162283 For R134a: For R600a:
A = 289.6766 B = -120.9303 D = -610.8266 E = 166.65826
where x = (1- (T/Tc)) (1/3) , T = Temperature K, Tc = Critical temperature K, dliq kg/m C = 637.09745 For R600a:
D = -504.3096 E = 415.766
where
T = Temperature K ,
liq
cP
Transfair Engineering: Designing and Prototyping of Refrigerator and Freezer Cooling Circuits. 10. Final Tests, R600a Properties Tables
p. 121
For R134a:
A =-8.52527 B = 2984.6992
C =-275736 D=0
For R600a:
10.14.9. LIQUID THERMAL CONDUCTIVITY Kliq = A+Bx+Cx+Dx where x = (1- (T/Tc)) (1/3) , T = Temperature K , Tc = Critical temperature K , Kliq W/m. K For R134a: For R600a:
A = 0.078573 B = -0.146406 C = 0.265347 D=0
10.14.10. SURFACE TENSION where T = Temperature K , Tc = Critical temperature K , mN/m = A(1-T/Tc)1.26 For R134a: A = 60.4 For R600a: 10.14.11. SATURATED VAPOUR DENSITY dvap = A + Bx + Cx + Dx + Ex4 where x = (1- (T/Tc)) (1/3) ,T = Temperature K , Tc = Critical temperature K , dvap kg/m For R134a: -50 to 0C 0 to +80C For R600a:
A = -403.0344 B = 5002.9036 C = -14972.63 D = 17151.088 E = -6831.522 A = 455.45416 B = -493.8403 C = -1740 D = 2957.1827 E = -1108.366
10.14.12. VAPOUR VISCOSITY (SAT. VAPOUR) vap = A + BT + CT + DT where T = Temperature K, For R134a: For R600a:
A = -.049881 1323 B = 6.239809E-04 C =-2.21507E-06 D = 2.82253899E-09
vap cP
10.14.13. VAPOUR THERMAL CONDUCTIVITY(SAT.VAPOUR) K gas = A + BT + CT + DT where T = Temperature K, Kgas W/m.K For R134a:
A = -.012605 B = 1 .09279E-04 C = -1 .604876E-07 D = 3.0361 55E-10
10.14.14. VAPOUR SPEED OF SOUND (SAT. VAPOUR) = A + BT + CT + DT+ E/T where T = Temperature K, C = 0.037823 For R134a: For R600a:
A = 2619.19 B = -14.14725 D = -3.9099E-05 E =-171017.1
m/s
10.15. Tables
10.15.1 R134a LIQUID AND SATURATED VAPOUR ENTHALPY AND LATENT HEAT
TEMP C -50.0 -40.0 -30.0 -20.0 -10.0 0.0 10.0 LIQUID LATENT ENTH HEAT -----------kJ/kg----------35.26 232.00 47.85 225.83 60.60 219.39 73.53 212.66 86.65 205.59 100.00 198.13 113.59 190.23 SAT VAP LIQUID ENTH cP -----kJ/kg K--267.26 1.2507 273.67 1.2666 279.98 1.2838 286.18 1.3026 292.24 1.3233 298.13 1.3463 303.82 1.3723 ID.GAS cP 0.6916 0.7113 0.7308 0.7499 0.7687 0.7872 0.8055
Transfair Engineering: Designing and Prototyping of Refrigerator and Freezer Cooling Circuits. 10. Final Tests, R600a Properties Tables
p. 122
10.15.2 R134a LIQUID DENSITY AND VISCOSITY AND SURF TENSION TABLE:
TEMP C -50.0 -40.0 -30.0 -20.0 -10.0 0.0 10.0 20.0 25.0 30.0 40.0 50.0 60.0 70.0 80.0 VAPOUR PRESS Bara 0.294 0.512 0.844 1.328 2.005 2.924 4.136 5.697 6.628 7.669 10.118 13.116 16.742 21.081 26.229 LIQUID DENSITY kg/m 1444 1416 1388 1358 1327 1295 1261 1226 1207 1188 1147 1103 1053 997 929 LIQUID VISCOSITY cP 0.50 0.45 0.40 0.35 0.31 0.27 0.24 0.21 0.20 0.19 0.16 0.15 0.13 0.11 0.10 LIQ.THERM COND W/m.K 0.115 0.111 0.107 0.103 0.099 0.095 0.091 0.086 0.084 0.082 0.078 0.074 0.069 0.065 0.061 SURF TENSION mN/m 19.3 17.7 16.1 14.6 13.1 11.6 10.2 8.78 8.11 7.44 6.14 4.90 3.72 2.62 1.60
10.15.3 R134a SATURATED VAPOUR DENSITY AND VISCOSITY, THERMAL CONDUCTIVITY AND SPEED OF SOUND TABLE:
TEMP C -50.0 -40.0 -30.0 -20.0 -10.0 0.0 10.0 20.0 25.0 30.0 40.0 50.0 60.0 70.0 80.0 SAT.VAPOUR DENSITY kg/m 1.650 2.772 4.431 6.791 10.05 14.42 20.19 27.70 32.24 37.38 49.80 65.78 86.62 114.45 153.46 SAT.VAPOUR VISCOSITY cP 0.0104 0.0110 0.0115 0.0119 0.0124 0.0128 0.0133 0.0138 0.0141 0.0143 0.0150 0.0157 0.0165 0.0175 0.0185 SAT.VAPOUR SPEED THERM.COND OF SOUND W/m.K m/s 0.0072 140.9 0.0080 143.2 0.0088 144.9 0.0097 146.1 0.0106 146.7 0.0115 146.7 0.0124 146.2 0.0133 145.0 0.0138 144.1 0.0142 143.1 0.0152 140.3 0.0162 136.6 0.0172 131.8 0.0183 125.7 0.0193 118.2
Further details for R134a can be take from Transfair Calculation Performance Programme, from NIST REFPROP Version 4 of IIR thermodynamic basis, from different programmes of the refrigerant supplier and their tables. For R134a a wide range of offers of such data programmes and tables exist already on the market while such data for R600a and mixtures are not as available as for R134a. Therefore we publish it inside this booklet:
Transfair Engineering: Designing and Prototyping of Refrigerator and Freezer Cooling Circuits. 10. Final Tests, R600a Properties Tables
p. 123
Transfair Engineering: Designing and Prototyping of Refrigerator and Freezer Cooling Circuits. 10. Final Tests, R600a Properties Tables
p. 124
Transfair Engineering: Designing and Prototyping of Refrigerator and Freezer Cooling Circuits. 10. Final Tests, R600a Properties Tables
p. 125
-20 484,4 -15 494,7 -10 505,0 - 5 515,2 0 525,5 5 535,7 10 545,9 15 556,1 20 566,3 25 576,5 30 586,6 35 596,8 40 606,9 45 617,0 50 627,1 55 637,2 60 647,3 65 657,4 70 667,5 75 677,5 80 687,6 85 697,6 90 707,7 95 717,7 100 727,8 105 737,8 110 747,8 115 757,8 120 767,8 125 777,8
528,94 536,25 543,68 551,24 558,92 566,74 574,68 582,74 590,93 599,25 607,69 616,25 624,93 633,74 642,66 651,71 660,88 670,16 679,56 689,09 698,72 708,48 718,35 728,33 738,43 748,64 758,96 769,40 779,94 790,60
2,3066 2,3352 2,3637 2,3921 2,4205 2,4489 2,4772 2,5054 2,5336 2,5617 2,5898 2,6178 2,6457 2,6736 2,7015 2,7293 2,7570 2,7846 2,8122 2,8398 2,8673 2,8947 2,9221 2,9494 2,9766 3,0038 3,0309 3,0580 3,0850 3,1119
-15 400,2 535,63 2,3042 -10 408,6 543,08 2,3328 - 5 417,1 550,66 2,3613 0 425,5 558,36 2,3898 5 433,9 566,19 2,4182 10 442,3 574,15 2,4465 15 450,6 582,23 2,4748 20 459,0 590,43 2,5031 25 467,3 598,76 2,5312 30 475,7 607,21 2,5593 35 484,0 615,78 2,5874 40 492,3 624,48 2,6154 45 500,6 633,29 2,6433 50 508,9 642,23 2,6712 55 517,1 651,29 2,6990 60 525,4 660,46 2,7267 65 533,6 669,76 2,7544 70 541,9 679,17 2,7821 75 550,1 688,70 2,8096 80 558,4 698,35 2,8371 85 566,6 708,11 2,8646 90 574,8 717,99 2,8920 95 583,0 727,98 2,9193 100 591,2 738,08 2,9466 105 599,4 748,30 2,9738 110 607,6 758,63 3,0009 115 615,8 769,07 3,0280 120 624,0 779,63 3,0550 125 632,1 790,29 3,0819 130 640,3 801,06 3,1088
-10 333,2 - 5 340,3 0 347,3 5 354,2 10 361,2 15 368,1 20 375,1 25 382,0 30 388,9 35 395,8 40 402,6 45 409,5 50 416,4 55 423,2 60 430,0 65 436,9 70 443,7 75 450,5 80 457,3 85 464,1 90 470,9 95 477,6 100 484,4 105 491,2 110 497,9 115 504,7 120 511,5 125 518,2 130 524,9 135 531,7
542,37 2,3029 549,97 2,3315 557,70 2,3601 565,55 2,3886 573,52 2,4170 581,62 2,4453 589,84 2,4736 598,18 2,5018 606,65 2,5300 615,24 2,5581 623,94 2,5861 632,77 2,6141 641,72 2,6420 650,79 2,6699 659,98 2,6976 669,29 2,7254 678,71 2,7530 688,25 2,7806 697,91 2,8082 707,68 2,8356 717,56 2,8631 727,56 2,8904 737,68 2,9177 747,90 2,9449 758,24 2,9721 768,69 2,9992 779,25 3,0262 789,92 3,0532 800,70 3,0801 811,59 3,1069
-5 279,6 0 285,4 5 291,3 10 297,1 15 302,9 20 308,7 25 314,5 30 320,3 35 326,1 40 331,8 45 337,6 50 343,3 55 349,0 60 354,7 65 360,4 70 366,1 75 371,8 80 377,4 85 383,1 90 388,8 95 394,4 100 400,1 105 405,7 110 411,3 115 417,0 120 422,6 125 428,2 130 433,8 135 439,4 140 445,0
549,17 556,92 564,79 572,78 580,90 589,14 597,50 605,99 614,59 623,32 632,17 641,13 650,21 659,42 668,73 678,17 687,72 697,39 707,17 717,07 727,08 737,21 747,44 757,79 768,25 778,82 789,50 800,29 811,18 822,19
2,3027 2,3313 2,3598 2,3883 2,4168 2,4451 2,4734 2,5016 2,5298 2,5579 2,5859 2,6138 2,6417 2,6696 2,6973 2,7250 2,7527 2,7802 2,8077 2,8352 2,8626 2,8899 2,9171 2,9443 2,9714 2,9985 3,0255 3,0524 3,0793 3,1061
0 236,1 5 241,1 10 246,0 15 251,0 20 255,9 25 260,8 30 265,6 35 270,5 40 275,4 45 280,2 50 285,0 55 289,8 60 294,6 65 299,4 70 304,2 75 309,0 80 313,8 85 318,6 90 323,3 95 328,1 100 332,8 105 337,6 110 342,3 115 347,0 120 351,7 125 356,5 130 361,2 135 365,9 140 370,6 145 375,3
556,00 2,3033 563,90 2,3319 571,92 2,3605 580,07 2,3890 588,33 2,4175 596,72 2,4458 605,22 2,4741 613,85 2,5023 622,59 2,5305 631,46 2,5586 640,44 2,5866 649,54 2,6145 658,76 2,6424 668,09 2,6702 677,54 2,6980 687,11 2,7256 696,79 2,7533 706,59 2,7808 716,50 2,8083 726,52 2,8357 736,66 2,8630 746,91 2,8903 757,27 2,9175 767,74 2,9447 778,32 2,9718 789,01 2,9988 799,80 3,0257 810,71 3,0526 821,72 3,0794 832,84 3,1062
Transfair Engineering: Designing and Prototyping of Refrigerator and Freezer Cooling Circuits. 10. Final Tests, R600a Properties Tables
p. 126
Ts=5C p=187,0 kPa t v Enth h Entr s C dm3/kg kJ/kg kJ/kgK 5 200,7 562,87 2,3047 10 204,9 570,92 2,3334 15 209,1 579,09 2,3620 20 213,3 587,39 2,3905 25 217,5 595,80 2,4190 30 221,7 604,33 2,4474 35 225,8 612,98 2,4757 40 229,9 621,75 2,5039 45 234,1 630,64 2,5321 50 238,2 639,64 2,5601 55 242,3 648,76 2,5881 60 246,3 658,00 2,6161 65 250,4 667,35 2,6439 70 254,5 676,82 2,6717 75 258,6 686,40 2,6995 80 262,6 696,10 2,7271 85 266,7 705,91 2,7547 90 270,7 715,84 2,7822 95 274,7 725,88 2,8097 100 278,7 736,03 2,8371 105 282,8 746,29 2,8644 110 286,8 756,66 2,8916 115 290,8 767,15 2,9188 120 294,8 777,74 2,9459 125 298,8 788,44 2,9730 130 302,8 799,25 3,0000 135 306,7 810,17 3,0269 140 310,7 821,19 3,0537 145 314,7 832,32 3,0805 150 318,7 843,56 3,1072
Ts=10C p=220,9 kPa t v Enth h Entr s C dm3/kg kJ/kg kJ/kgK 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 145 150 155 171,6 175,2 178,8 182,4 186,0 189,6 193,1 196,6 200,2 203,7 207,2 210,7 214,2 217,6 221,1 224,6 228,0 231,5 234,9 238,3 241,8 245,2 248,6 252,0 255,4 258,8 262,2 265,6 269,0 272,4 569,76 577,97 586,29 594,74 603,30 611,98 620,78 629,69 638,72 647,86 657,12 666,50 675,99 685,59 695,31 705,14 715,08 725,14 735,30 745,58 755,97 766,47 777,07 787,79 798,61 809,54 820,58 831,72 842,97 854,33 2,3069 2,3356 2,3643 2,3928 2,4213 2,4497 2,4780 2,5062 2,5344 2,5625 2,5905 2,6184 2,6463 2,6741 2,7012 2,7294 2,7570 2,7845 2,8119 2,8393 2,8666 2,8938 2,9209 2,9480 2,9750 3,0020 3,0289 3,0557 3,0824 3,1091
15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 145 150 155 160
147,4 150,6 153,7 156,8 159,9 163,0 166,1 169,1 172,2 175,2 178,2 181,2 184,2 187,2 190,2 193,2 196,1 199,1 202,1 205,0 207,9 210,9 213,8 216,7 219,7 222,6 225,5 228,4 231,3 234,2
576,66 585,03 593,51 602,11 610,83 619,66 628,60 637,66 646,83 656,12 665,52 675,03 684,66 694,40 704,25 714,22 724,29 734,48 744,77 755,18 765,70 776,32 787,05 797,89 808,83 819,88 831,04 842,30 853,67 865,14
2,3097 2,3385 2,3672 2,3958 2,4243 2,4527 2,4810 2,5093 2,5375 2,5656 2,5936 2,6215 2,6493 2,6771 2,7048 2,7325 2,7600 2,7875 2,8149 2,8422 2,8695 2,8967 2,9238 2,9509 2,9778 3,0048 3,0316 3,0584 3,0851 3,1117
20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 145 150 155 160 165
127,3 130,1 132,8 135,5 138,2 140,9 143,6 146,2 148,9 151,5 154,1 156,7 159,3 161,9 164,5 167,1 169,6 172,2 174,8 177,3 179,8 182,4 184,9 187,4 190,0 192,5 195,0 197,5 200,0 202,5
583,57 592,10 600,74 609,50 618,37 627,35 636,44 645,65 654,97 664,40 673,95 683,60 693,37 703,24 713,23 723,33 733,54 743,86 754,28 764,82 775,46 786,21 797,07 808,03 819,10 830,27 841,55 852,93 864,41 876,00
2,3131 2,3419 2,3707 2,3993 2,4279 2,4563 2,4847 2,5130 2,5412 2,5693 2,5973 2,6252 2,6531 2,6808 2,7085 2,7362 2,7637 2,7912 2,8185 2,8459 2,8731 2,9003 2,9274 2,9544 2,9814 3,0082 3,0350 3,0618 3,0885 3,1150
25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 145 150 155 160 165 170
110,5 112,9 115,3 117,7 120,0 122,4 124,7 127,0 129,3 131,6 133,9 136,2 138,5 140,7 143,0 145,2 147,5 149,7 151,9 154,1 156,4 158,6 160,8 163,0 165,2 167,3 169,5 171,7 173,9 176,1
590,47 599,17 607,98 616,90 625,92 635,06 644,30 653,66 663,13 672,71 682,39 692,19 702,10 712,12 722,24 732,47 742,82 753,27 763,82 774,49 785,26 796,14 807,12 818,21 829,40 840,69 852,09 863,59 875,20 886,90
2,3170 2,3459 2,3748 2,4035 2,4321 2,4605 2,4889 2,5172 2,5454 2,5736 2,6016 2,6295 2,6574 2,6852 2,7129 2,7405 2,7680 2,7954 2,8228 2,8501 2,8773 2,9045 2,9316 2,9586 2,9855 3,0123 3,0391 3,0658 3,0925 3,1190
30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 145 150 155 160 165 170 175
96,2 98,4 100,5 102,6 104,7 106,7 108,8 110,8 112,9 114,9 116,9 118,9 120,9 122,9 124,9 126,8 128,8 130,8 132,7 134,6 136,6 138,5 140,4 142,4 144,3 146,2 148,1 150,0 151,9 153,8
597,37 606,23 615,21 624,29 633,47 642,77 652,17 661,68 671,30 681,02 690,86 700,80 710,85 721,01 731,27 741,64 752,12 762,70 773,39 784,19 795,09 806,10 817,20 828,42 839,73 851,15 862,67 874,29 886,02 897,84
2,3214 2,3504 2,3793 2,4081 2,4367 2,4652 2,4937 2,5220 2,5502 2,5784 2,6064 2,6344 2,6623 2,6900 2,7177 2,7453 2,7729 2,8003 2,8277 2,8550 2,8822 2,9093 2,9363 2,9633 2,9902 3,0170 3,0438 3,0705 3,0971 3,1236
35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 145 150 155 160 165 170 175 180
84,1 604,23 2,3261 86,0 613,27 2,3553 87,9 622,42 2,3842 89,8 631,67. 2,4131 91,7 641,02 2,4418 93,5 650,48 2,4704 95,3 660,04 2,4989 97,1 669,70 2,5272 98,9 679,47 2,5555 100,7 689,35 2,5837 102,5 699,33 2,6118 104,3 709,42 2,6397 106,0 719,62 2,6676 107,8 729,91 2,6954 109,5 740,32 2,7231 111,3 750,83 2,7507 113,0 761,44 2,7782 114,7 772,16 2,8057 116,4 782,99 2,8330 118,2 793,92 2,8603 119,9 804,95 2,8875 121,6 816,08 2,9146 123,3 827,32 2,9416 124,9 838,66 2,9686 126,6 850,10 2,9955 128,3 861,64 3,0223 130,0 873,28 3,0490 131,7 885,03 3,0757 133,3 896,87 3,1022 135,0 908,81 3,1287
Transfair Engineering: Designing and Prototyping of Refrigerator and Freezer Cooling Circuits. 10. Final Tests, R600a Properties Tables
p. 127
Ts=40C p=531,9 kPa t v Enth h Entr s C dm3/kg kJ/kg kJ/kgK 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 145 150 155 160 165 170 175 180 185 73,8 611,05 2,3312 75,5 620,28 2,3604 77,2 629,60 2,3895 78,9 639,02 2,4185 80,6 648,55 2,4473 82,2 658,17 2,4759 83,8 667,89 2,5045 85,5 677,72 2,5329 87,1 687,64 2,5612 88,6 697,68 2,5894 90,2 707,81 2,6175 91,8 718,05 2,6455 93,4 728,39 2,6734 94,9 738,83 2,7012 96,5 749,38 2,7289 98,0 760,03 2,7565 99,6 770,78 2,7841 101,1 781,64 2,8115 102,6 792,60 2,8389 104,1 803,66 2,8661 105,6 814,82 2,8933 107,1 826,09 2,9204 108,6 837,45 2,9474 110,1 848,92 2,9744 111,6 860,49 3,0012 113,1 872,16 3,0280 114,6 883,92 3,0547 116,1 895,79 3,0813 117,5 907,75 3,1079 119,0 919,81 3,1344
Ts=45C p=605,3 kPa Ts=50C p=686,1 kPa t v Enth h Entr s t v Enth h Entr s C dm3/kg kJ/kg kJ/kgK C dm3/kg kJ/kg kJ/kgK 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 145 150 155 160 165 170 175 180 185 190 65,0 66,5 68,1 69,6 71,1 72,5 74,0 75,4 76,9 78,3 79,7 81,1 82,5 83,9 85,3 86,7 88,1 89,4 90,8 92,1 93,5 94,8 96,1 97,5 98,8 100,1 101,4 102,7 104,1 105,4 617,82 627,24 636,75 646,35 656,05 665,84 675,73 685,72 695,81 705,99 716,28 726,67 737,16 747,75 758,45 769,24 780,13 791,13 802,22 813,42 824,72 836,11 847,61 859,21 870,90 882,69 894,59 906,57 918,66 930,84 2,3366 2,3659 2,3951 2,4242 2,4530 2,4818 2,5104 2,5389 2,5673 2,5955 2,6236 2,6517 2,6796 2,7074 2,7352 2,7628 2,7903 2,8178 2,8451 2,8724 2,8996 2,9267 2,9537 2,9806 3,0074 3,0342 3,0609 3,0875 3,1140 3,1405
Ts=65C p=976,8 kPa Ts=70C p=1091,4 kPa t v Enth h Ent r s t v Enth h Entr s C dm3/kg kJ/kg kJ/kgK C dm3/kg kJ/kg kJ/kgK
50 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 145 150 155 160 165 170 175 180 185 190 195
57,3 58,8 60,1 61,5 62,9 64,2 65,5 66,8 68,1 69,4 70,7 72,0 73,2 74,5 75,7 76,9 78,2 79,4 80,6 81,8 83,0 84,2 85,4 86,6 87,8 88,9 90,1 91,3 92,5 93,6
624,53 634,14 643,84 653,63 663,51 673,48 683,54 693,70 703,95 714,30 724,74 735,29 745,93 756,67 767,51 778,45 789,49 800,62 811,86 823,19 834,62 846,15 857,78 869,51 881,33 893,25 905,27 917,38 929,59 941,89
2,3421 2,3716 2,4010 2,4301 2,4591 2,4880 2,5166 2,5452 2,5736 2,6019 2,6301 2,6582 2,6861 2,7140 2,7417 2,7694 2,7969 2,8244 2,8518 2,8790 2,9062 2,9333 2,9603 2,9872 3,0140 3,0408 3,0675 3,0940 3,1205 3,1470
55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 145 150 155 160 165 170 175 180 185 190 195 200
50,7 52,0 53,3 54,5 55,8 57,0 58,2 59,4 60,6 61,7 62,9 64,0 65,2 66,3 67,4 68,5 69,6 70,7 71,8 72,9 74,0 75,1 76,1 77,2 78,3 79,3 80,4 81,4 82,5 83,5
631,14 640,97 650,87 660,85 670,92 681,07 691,31 701,64 712,06 722,58 733,19 743,89 754,69 765,58 776,57 787,66 798,84 810,12 821,50 832,97 844,54 856,20 867,96 879,82 891,77 903,82 915,97 928,21 940,54 952,97
2,3477 2,3775 2,4070 2,4363 2,4654 2,4943 2,5231 2,5518 2,5803 2,6087 2,6369 2,6650 2,6930 2,7209 2,7487 2,7763 2,8039 2,8314 2,8587 2,8860 2,9132 2,9403 2,9673 2,9942 3,0210 3,0478 3,0744 3,1010 3,1275 3,1539
60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 145 150 155 160 165 170 175 180 185 190 195 200 205
45,0 637,66 2,3535 46,2 647,71 2,3834 47,3 657,82 2,4131 48,5 658,01 2,4426 49,6 678,27 2,4781 50,7 688,61 2,5009 51,8 699,04 2,5298 52,9 709,55 2,5586 54,0 720,15 2,5872 55,1 730,83 2,6156 56,1 741,60 2,6439 57,1 752,47 2,6721 58,2 763,43 2,7001 59,2 774,48 2,7281 60,2 785,62 2,7559 61,2 796,86 2,7836 62,2 808,19 2,8112 63,2 819,61 2,8387 64,2 831,13 2,8666 65,2 842,75 2,8933 66,2 854,45 2,9205 67,1 866,26 2,9476 68,1 878,15 2,9746 69,1 890,14 3,0015 70,0 902,23 3,0283 71,0 914,41 3,0551 71,9 926,68 3,0817 72,9 939,04 3,1083 73,8 951,50 3,1347 74,7 964,05 3,1611
65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 145 150 155 160 165 170 175 180 185 190 195 200 205 210
40,0 41,1 42,2 43,2 44,3 45,3 46,3 47,3 48,3 49,2 50,2 51,1 52,1 53,0 53,9 54,9 55,8 56,7 57,6 58,5 59,3 60,2 61,1 62,0 62,8 63,7 64,6 65,4 66,3 67,1
644,04 654,33 664,67 675,08 685,55 696,09 706,71 717,40 728,18 739,04 749,99 761,02 772,14 783,35 794,65 806,04 817,53 829,10 840,76 852,52 864,37 876,31 888,34 900,47 912,69 925,00 937,40 949,89 962,48 975,15
2,3592 2,3894 2,4193 2,4490 2,4784 2,5077 2,5367 2,5656 2,5942 2,6222 2,6512 2,6794 2,7075 2,7355 2,7633 2,7911 2,8187 2,8462 2,8736 2,9009 2,9281 2,9552 2,9822 3,0091 3,0359 3,0627 3,0893 3,1158 3,1423 3,1687
70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 145 150 155 160 165 170 175 180 185 190 195 200 205 210 215
35,5 36,6 37,6 38,6 39,6 40,5 41,4 42,4 43,3 44,1 45,0 45,9 46,8 47,6 48,5 49,3 50,1 51,0 51,8 52,6 53,4 54,2 55,0 55,8 56,6 57,3 58,1 58,9 59,7 60,4
650,28 660,83 671,41 682,05 692,74 703,49 714,31 725,20 736,17 747,21 758,33 769,54 780,83 792,20 803,66 815,21 826,85 838,57 850,38 862,29 874,28 886,36 898,54 910,80 923,15 935,59 948,13 960,75 973,46 986,26
2,3648 2,3953 2,4255 2,4554 2,4851 2,5145 2,5437 2,5727 2,6015 2,6301 2,6586 2,6869 2,7151 2,7431 2,7710 2,7988 2,8265 2,8540 2,8815 2,9088 2,9360 2,9631 2,9901 3,0170 3,0438 3,0706 3,0972 3,1237 3,1502 3,1765
Transfair Engineering: Designing and Prototyping of Refrigerator and Freezer Cooling Circuits. 10. Final Tests, R600a Properties Tables
p. 128
Ts=75C p=1215,6 kPa t v Enth h Entr s C dm3/kg kJ/kg kJ/kgK 75 31,7 656,33 2,3703 80 32,6 667,16 2,4012 85 33,6 678,02 2,4317 90 34,5 688,90 2,4619 95 35,4 699,83 2,4917 100 36,3 710,80 2,5214 105 37,2 721,83 2,5507 110 38,0 732,93 2,5799 115 38,9 744,09 2,6088 120 39,7 755,32 2,6376 125 40,5 766,63 2,6652 130 41,3 778,01 2,6946 135 42,1 789,48 2,7228 140 42,9 801,02 2,7509 145 43,7 812,65 2,7729 150 44,4 824,36 2,8067 155 45,2 836,15 2,8345 160 45,9 848,03 2,8620 165 46,7 859,99 2,8895 170 47,4 872,04 2,9168 175 48,2 884,18 2,9441 180 48,9 896,41 2,9712 185 49,6 908,72 2,9982 190 50,3 921,13 3,0252 195 51,1 933,62 3,0520 200 51,8 946,19 3,0787 205 52,5 958,86 3,1053 210 53,2 971,61 3,1319 215 53,9 984,45 3,1533 220 54,6 997,38 3,1847
Ts=80C p=1349,4 kPa t v Enth h Entr s C dm3/kg kJ/kg kJ/kgK 80 85 90 95 100 105 110 115 120 125 130 135 140 145 150 155 160 165 170 175 180 185 190 195 200 205 210 215 220 225 28,2 662,16 2,3755 29,2 673,32 2,4068 30,1 684,46 2,4377 30,9 695,62 2,4682 31,8 706,79 2,4984 32,6 718,01 2,5282 33,4 729,26 2,5578 34,2 740,57 2,5871 35,0 751,94 2,6162 35,8 763,37 2,6451 36,5 774,87 2,6738 37,2 786,44 2,7024 38,0 798,08 2,7307 38,7 809,80 2,7589 39,4 821,60 2,7869 40,1 833,47 2,8148 40,8 845,43 2,8426 41,5 857,46 2,8702 42,2 869,58 2,8977 42,9 881,79 2,9251 43,6 894,07 2,9524 44,2 906,45 2,9795 44,9 918,90 3,0066 45,6 931,45 3,0335 46,2 944,08 3,0604 46,9 956,79 3,0871 47,5 969,59 3,1137 48,2 982,48 3,1403 48,8 995,45 3,1667 49,5 1008,51 3,1930
85 90 95 100 105 110 115 120 125 130 135 140 145 150 155 160 165 170 175 180 185 190 195 200 205 210 215 220 225 230
25,2 667,74 2,3803 26,1 679,26 2,4122 26,9 690,73 2,4436 27,8 702,18 2,4745 28,6 713,63 2,5050 29,3 725,09 2,5351 30,1 736,59 2,5649 30,8 748,13 2,5944 31,6 759,71 2,6237 32,3 771,35 2,6528 33,0 783,05 2,6816 33,7 794,81 2,7102 34,4 806,64 2,7387 35,0 818,54 2,7670 35,7 830,51 2,7951 36,3 842,55 2,8231 37,0 854,67 2,8509 37,6 866,87 2,8786 38,3 879,15 2,9061 38,9 891,51 2,9336 39,5 903,95 2,9609 40,1 916,47 2,9881 40,7 929,08 3,0151 41,4 941,76 3,0421 42,0 954,53 3,0689 42,6 967,39 3,0957 43,2 980,32 3,1223 43,8 993,35 3,1488 44,3 1006,45 3,1753 44,9 1019,64 3,2016
Transfair Engineering: Designing and Prototyping of Refrigerator and Freezer Cooling Circuits. 10. Final Tests, R600a Properties Tables
p. 129
-40 395,7 536,65 -35 405,0 543,53 -30 414,3 550,54 -25 423,5 557,68 -20 432,7 564,95 -15 441,9 572,33 -10 451,1 579,85 -5 460,2 587,49 0 469,4 595,26 5 478,5 603,15 10 487,6 611,16 15 496,7 619,30 20 505,8 627,56 25 514,8 635,94 30 523,9 644,45 35 532,9 653,07 40 542,0 661,82 45 551,0 670,69 50 560,0 679,68 55 569,0 688,78 60 578,0 698,01 65 587,0 707,35 70 596,0 716,81 75 605,0 726,39 80 613,9 736,08 85 622,9 745,89 30 631,8 755,81 95 640,8 765,85 100 649,7 776,00 105 658,7 786,26
2,4803 2,5095 2,5387 2,5677 2,5967 2,6256 2,6544 2,6832 2,7119 2,7405 2,7691 2,7976 2,8260 2,8543 2,8826 2,9109 2,9390 2,9671 2,9951 3,0231 3,0510 3,0788 3,1066 3,1343 3,1619 3,1895 3,2170 3,2445 3,2719 3,2992
-35 323,6 542,58 2,4662 -30 331,2 549,62 2,4955 -25 338,7 556,79 2,5246 -20 346,2 564,08 2,5537 -15 353,7 571,50 2,5827 -10 361,2 579,04 2,6117 -5 368,6 586,71 2,6405 0 376,1 594,49 2,6693 5 383,5 602,41 2,6980 10 390,9 610,44 2,7266 15 398,3 618,60 2,7552 20 405,6 626,88 2,7837 25 413,0 635,28 2,8121 30 420,4 643,80 2,8405 35 427,7 652,45 2,8687 40 435,0 661,21 2,8969 45 442,3 670,09 2,9251 50 449,6 679,09 2,9532 55 456,9 688,21 2,9812 60 464,2 697,45 3,0091 65 471,5 706,81 3,0370 70 478,8 716,28 3,0648 75 486,1 725,87 3,0925 80 493,3 735,57 3,1202 85 500,6 745,39 3,1478 90 507,8 755,33 3,1754 95 515,1 765,37 3,2028 100 522,3 775,53 3,2302 105 529,6 785,81 3,2576 110 536,8 796,19 3,2849
-30 267,1 548,52 -25 273,3 555,72 -20 279,5 563,05 -15 285,7 570,50 -10 291,8 578,08 -5 298,0 585,77 0 304,1 593,59 5 310,2 601,53 10 316,3 609,59 15 322,4 617,77 20 328,4 626,07 25 334,5 634,50 30 340,5 643,04 35 346,5 651,70 40 352,5 660,49 45 358,6 669,39 50 364,5 678,41 55 370,5 687,54 60 376,5 696,80 65 382,5 706,17 70 388,4 715,66 75 394,4 725,26 80 400,4 734,98 85 406,3 744,81 90 412,2 754,76 95 418,2 764,82 100 424,1 774,99 105 430,0 785,27 110 435,9 795,67 115 441,8 806,18
2,4537 2,4830 2,5123 2,5414 2,5705 2,5994 2,6283 2,6571 2,6858 2,7145 2,7431 2,7715 2,8000 2,8283 2,8566 2,8848 2,9129 2,9410 2,9690 2,9969 3,0247 3,0525 3,0802 3,1079 3,1354 3,1630 3,1904 3,2178 3,2451 3,2723
-25 222,2 554,46 -20 227,4 561,83 -15 232,6 569,32 -10 237,7 576,93 -5 242,8 584,67 0 247,9 592,52 5 253,0 600,49 10 258,1 608,58 15 263,2 616,79 20 268,2 625,12 25 273,2 633,57 30 278,2 642,14 35 283,2 650,83 40 288,2 659,63 45 293,2 668,56 50 298,2 677,60 55 303,1 686,76 60 308,1 696,03 65 313,0 705,42 70 318,0 714,93 75 322,9 724,55 80 327,8 734,28 85 332,7 744,13 90 337,7 754,09 95 342,6 764,16 100 347,5 774,35 105 352,4 784,65 110 357,2 795,06 115 362,1 805,58 120 367,0 816,21
2,4427 2,4721 2,5014 2,5306 2,5597 2,5887 2,6176 2,6465 2,6752 2,7039 2,7325 2,7610 2,7894 2,8177 2,8460 2,8742 2,9023 2,9304 2,9583 2,9862 3,0141 3,0418 3,0695 3,0972 3,1247 3,1522 3,1796 3,2070 3,2342 3,2614
Transfair Engineering: Designing and Prototyping of Refrigerator and Freezer Cooling Circuits. 10. Final Tests, R600a Properties Tables
p. 130
ts = -20,00C p = 240,5kPa t v h s C dm3/kg kJ/kg kJ/(kgK) -20 186,3 560,39 2,4330 -15 190,7 567,93 2,4625 -10 195,0 575,59 2,4919 -5 199,4 583,37 2,5212 0 203,7 591,26 2,5503 5 208,0 599,27 2,5794 10 212,2 607,40 2,6084 15 216,5 615,65 2,6372 20 220,7 624,01 2,6660 25 224.3 632,49 2,6947 30 229,1 641,09 2,7233 35 233,3 649,81 2,7518 40 237,5 658,64 2,7802 45 241,7 667,59 2,8086 50 245,9 676,66 2,8369 55 250,0 685,84 2,8651 60 254,2 695,13 2,8932 65 258,3 704,55 2,9212 70 262,4 714,07 2,9492 75 266,6 723,71 2,9771 80 270,7 733,47 3,0049 85 274,8 743,33 3,0326 30 278,9 753,31 3,0603 95 283,0 763,41 3,0879 100 287,1 773,61 3,1154 105 291,2 783,92 3,1429 110 235,2 794,35 3,1703 115 299,3 804,88 3,1976 120 303,4 815,53 3,2249 125 307,5 826,28 3,2520
ts = -15,00C p =287,7kPa t v h s C dm3/kg kJ/kg kJ/(kgK) -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 157,3 161,0 164,7 168,4 172,0 175,7 179,3 182,9 186,5 190,0 193,6 197,1 200,7 204,2 207,7 211,2 214,7 218,2 221,7 225,2 228,6 232,1 235,6 239,0 242,5 245,9 249,3 252,8 256,2 259,6 566,30 574,01 581,84 589,79 597,85 606,02 614,31 622,71 631,23 639,87 648,62 657,49 666,47 675,56 684,77 694,10 703,53 713,08 722,75 732,53 742,42 752,42 762,53 772,75 783,09 793,53 804,08 814,74 825,51 836,39 2,4245 2,4541 2,4836 2,5129 2,5422 2,5713 2,6003 2,6292 2,6581 2,6868 2,7154 2,7439 2,7724 2,8008 2,8290 2,8572 2,8854 2,9134 2,9414 2,9692 2,9971 3,0248 3,0524 3,0800 3,1075 3,1350 3,1623 3,1896 3,2168 3,2440
-10 133,7 572,17 -5 136,9 580,06 0 140,0 588,07 5 143,2 596,19 10 146,3 604,41 15 149,4 612,76 20 152,5 621,21 25 155,6 629,77 30 158,6 638,45 35 161.7 647,24 40 164,7 656,15 45 167,7 665,17 50 170,7 674,30 55 173,7 683,54 60 176,7 692,90 65 179,7 702,37 70 182,7 711,95 75 185,7 721,64 80 188,6 731,44 85 131,6 741,36 30 134,5 751,38 95 197,5 761,52 100 200,4 771,77 105 203,3 782,12 110 206,2 792,59 115 209,2 803,16 120 212,1 813,84 125 215,0 824,63 130 217,3 835,53 135 220,8 846,53
2,4171 2,4468 2,4764 2,5058 2,5351 2,5643 2,5934 2,6224 2,6513 2,6800 2,7087 2,7373 2,7657 2,7941 2,8224 2,8506 2,8788 2,9068 2,9348 2,9626 2,9904 3,0182 3,0458 3,0734 3,1009 3,1283 3,1556 3,1829 3,2101 3,2372
-5 114,2 0 117,0 5 119,7 10 122,5 15 125,2 20 127,8 25 130,5 30 133,1 35 135,8 40 138,4 45 141,0 50 143,6 55 146,2 60 148,8 65 151,3 70 153,9 75 156,5 80 159,0 85 161,5 90 164,1 95 166,6 100 169,1 105 171,6 110 174,1 115 176,6 120 179,1 125 181,6 130 184,1 135 186,6 140 189,0
577,98 586,07 594,26 602,55 610,95 619,47 628,09 636,82 645,66 654,61 663,67 672,84 682,13 691,52 701,03 710,64 720,37 730,20 740,15 750,20 760,37 770,64 781,02 791,51 802,11 812,82 823,63 834,54 845,57 856,70
2,4105 2,4404 2,4701 2,4997 2,5291 2,5584 2,5875 2,6166 2,6455 2,6743 2,7030 2,7316 2,7601 2,7886 2,8169 2,8451 2,8732 2,9013 2,9293 2,9571 2,9849 3,0126 3,0403 3,0678 3,0953 3,1227 3,1500 3,1773 3,2045 3,2316
0 98,1 5 100,6 10 102,9 15 105,3 20 107,7 25 110,0 30 112,3 35 114,6 40 116,9 45 119,2 50 121,4 55 123,7 60 125,9 65 128,2 70 130,4 75 132,6 80 134,8 85 137,0 90 139,2 95 141,4 100 143,5 105 145,7 110 147,9 115 150,0 120 152,2 125 154,3 130 156,5 135 158,6 140 160,8 145 162,9
583,74 592,01 600,39 608,87 617,45 626,14 634,94 643,84 652,84 661,96 671,18 680,51 689,95 699,50 709,15 718,92 728,79 738,77 748,86 759,06 769,36 779,77 790,29 800,92 811,65 822,49 833,43 844,48 855,63 866,88
2,4048 2,4349 2,4647 2,4944 2,5239 2,5533 2,5826 2,6117 2,6407 2,6696 2,6983 2,7270 2,7555 2,7840 2,8123 2,8406 2,8687 2,8968 2,9248 2,9526 2,9804 3,0082 3,0358 3,0633 3,0908 3,1182 3,1455 3,1728 3,1999 3,2270
5 84,7 589,41 10 86,8 597,89 15 88,9 606,46 20 91,0 615,13 25 93,1 623,90 30 95,1 632,77 35 97,2 641,74 40 99,2 650,82 45 101,2 659,99 50 103,2 669,28 55 105,1 678,66 60 107,1 688,15 65 109,1 697,75 70 111,0 707,46 75 112,9 717,27 80 114,9 727,18 85 116,8 737,21 90 118,7 747,33 95 120,6 757,57 100 122,5 767,91 105 124,4 778,36 110 126,3 788,91 115 128,2 799,57 120 130,0 810,33 125 131,9 821,19 130 133,8 832,17 135 135,6 843,24 140 137,5 854,42 145 139,3 865,70 150 141,2 877,09
2,3998 2,4300 2,4601 2,4899 2,5196 2,5491 2,5784 2,6076 2,6367 2,6656 2,6945 2,7232 2,7518 2,7803 2,8086 2,8369 2,8651 2,8932 2,9212 2,9491 2,9769 3,0046 3,0322 3,0598 3,0873 3,1146 3,1419 3,1692 3,1963 3,2234
Transfair Engineering: Designing and Prototyping of Refrigerator and Freezer Cooling Circuits. 10. Final Tests, R600a Properties Tables
p. 131
ts = 10,00C p = 635,5kPa t v h s C dm3/kg kJ/kg kJ/(kgK) 10 73,4 594,98 2,3954 15 75,3 603,67 2,4258 20 77,2 612,45 2,4561 25 79,0 621,32 2,4861 30 80,9 630,28 2,5159 35 82,7 639,34 2,5455 40 84,5 648,50 2,5750 45 86,2 657,75 2,6043 50 88,0 667,10 2,6335 55 89,8 676,56 2,6625 60 91,5 686,11 2,6914 65 93,2 695,77 2,7202 70 34.3 705,53 2,7488 75 96,6 715,39 2,7774 80 98,3 725,36 2,8058 85 100,0 735,43 2,8341 90 101,7 745,61 2,8623 35 103,4 755,89 2,8904 100 105,1 766,27 2,9184 105 106,7 776,76 2,9464 110 108,4 787,35 2,9742 115 110,0 798,04 3,0019 120 111,7 808,84 3,0295 125 113,3, 819,74 3,0571 130 114,9 830,75 3,0846 135 116,6 841,85 3,1119 140 118,2 853,06 3,1392 145 119,8 864,37 3,1665 150 121,4 875,79 3,1936 155 123,0 887,30 3,2206
ts =5,00C p = 731,5kPa t v h s C dm3/kg kJ/kg kJ/(kgK) 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 145 150 155 160 63,9 600,43 2,3915 65,6 609,34 2,4222 67,3 618,34 2,4526 68,9 627,42 2,4828 70,6 636,59 2,5128 72,2 645,84 2,5426 73,8 655,19 2,5722 75,3 664,62 2,6016 76,9 674,16 2,6309 78,4 683,79 2,6600 80,0 693,52 2,6890 81,5 703,35 2,7178 83,0 713,28 2,7466 84,5 723,30 2,7752 86,0 733,43 2,8036 87,5 743,66 2,8320 89,0 753,99 2,8603 90,5 764,42 2,8884 92,0 774,96 2,9165 93,4 785,59 2,9444 94,9 796,33 2,9722 96,3 807,17 3,0000 97,8 818,11 3,0276 99,2 829,15 3,0552 100,6 840,30 3,0827 102,1 851,54 3,1100 103,5 862,89 3,1373 104,9 874,33 3,1646 106,3 885,88 3,1917 107,8 897,52 3,2187
10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 145 150 155
73,4 75,3 77,2 79,0 80,9 82,7 84,5 86,2 88,0 89,8 91,5 93,2 34.3 96,6 98,3 100,0 101,7 103,4 105,1 106,7 108,4 110,0 111,7 113,3 114,9 116,6 118,2 119,8 121,4 123,0
594,98 603,67 612,45 621,32 630,28 639,34 648,50 657,75 667,10 676,56 686,11 695,77 705,53 715,39 725,36 735,43 745,61 755,89 766,27 776,76 787,35 798,04 808,84 819,74 830,75 841,85 853,06 864,37 875,79 887,30
2,3954 2,4258 2,4561 2,4861 2,5159 2,5455 2,5750 2,6043 2,6335 2,6625 2,6914 2,7202 2,7488 2,7774 2,8058 2,8341 2,8623 2,8904 2,9184 2,9464 2,9742 3,0019 3,0295 3,0571 3,0846 3,1119 3,1392 3,1665 3,1936 3,2206
15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 145 150 155 160
63,9 600,43 2,3915 65,6 609,34 2 ,4222 67,3 618,34 2,4526 68,9 627,42 2,4828 70,6 636,59 2,5128 72,2 645,84 2,5426 73,8 655,19 2,5722 75,3 664,62 2,6016 76,9 674,16 2,6309 78,4 683,79 2,6600 80,0 693,52 2,6890 81,5 703,35 2,7178 83,0 713,28 2,7466 84,5 723,30 2,7752 86,0 733,43 2,8036 87,5 743,66 2,8320 89,0 753,99 2,8603 90,5 764,42 2,8884 92,0 774,96 2,9165 93,4 785,59 2,9444 94,9 796,33 2,9722 96,3 807,17 3,0000 97,8 818,11 3,0276 99,2 829,15 3,0552 100,6 840,30 3,0827 102,1 851,54 3,1100 103,5 862,89 3,1373 104,9 874,33 3,1646 106,3 885,88 3,1917 107,8 897,52 3,2187
20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 35 100 105 110 115 120 125 130 135 140 145 150 155 160 165
55,8 605,73 2,3879 57,3 614,89 2,4189 58,8 624,12 2,4496 60,3 633,42 2,4800 61,8 642,79 2,5102 63,2 652,25 2,5401 64,7 661,80 2,5699 66.1 671,43 2,5995 67,5 681,15 2,6289 68,9 690,97 2,6581 70,2 700,88 2,6872 71,6 710,88 2,7162 72,9 720,98 2,7450 74,3 731,17 2,7736 75,6 741,47 2,8022 76,9 751,86 2,8306 78,2 762,35 2,8589 79,6 772,94 2,8871 80,9 783,62 2,9152 82,2 794,41 2,9431 83,4 805,30 2,9710 84,7 816,28 2,9988 86,0 827,37 3,0264 87,3 838,56 3,0540 88,5 849,84 3,0815 89,8 861,22 3,1089 91,1 872,71 3,1362 92,3 884,29 3,1634 93,6 895,97 3,1905 94,8 907,75 3,2175
25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 145 150 155 160 165 170
48,9 50,3 51,6 53,0 54,3 55,6 56,9 58,2 59,4 60,7 61,9 63,1 64,3 65,5 66,7 67,9 69,1 70,2 71,4 72,6 73,7 74,9 76,0 77,1 78,2 79,4 80,5 81,6 82,7 83,8
610,87 620,29 629,76 639,29 648,90 658,57 668,32 678,16 688,08 698,08 708,17 718,36 728,63 739,00 749,46 760,02 770,67 781,42 792,27 803,21 814,25 825,38 836,62 847,95 859,37 870,90 882,52 894,24 906,06 917,97
2,3846 2,4159 2,4469 2,4776 2,5080 2,5382 2,5681 2,5979 2,6274 2,6568 2,6860 2,7150 2,7439 2,7727 2,8013 2,8298 2,8581 2,8864 2,9145 2,9425 2,9704 2,9982 3,0259 3,0535 3,0810 3,1084 3,1357 3,1629 3,1900 3,2170
Transfair Engineering: Designing and Prototyping of Refrigerator and Freezer Cooling Circuits. 10. Final Tests, R600a Properties Tables
p. 132
ts=30,00C p=1084,OkPa t v h s C dm3/kg kJ/kg kJ/(kgK) 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 145 150 155 160 165 170 175 42,9 44,2 45,5 46,7 47,9 49,1 50,2 51,4 52,5 53,7 54,8 55,9 57,0 58,0 59,1 60,2 61,2 62,3 63,3 64,3 65,4 66,4 67,4 68,4 69,4 70,4 71,4 72,4 73,4 74,4 615,82 2,3814 625,52 2,4131 635,25 2,4445 645,03 2,4755 654,87 2,5062 664,78 2,5366 674,75 2,5667 684,79 2,5967 694,91 2,6264 705,12 2,6559 715,40 2,6852 725,77 2,7144 736,23 2,7434 746,77 2,7722 757,41 2,8009 768,14 2,8295 778,96 2,8579 789,87 2,8862 800,87 2,9144 811,97 2,9424 823,17 2,9704 834,46 2,9982 845,84 3,0259 857,32 3,0535 868,89 3,0810 880,56 3,1084 892,33 3,1358 904,19 3,1630 916,14 3,1901 928,19 3,2172
ts= 35,00C p=1225,0Pa t v h s C dm3/kg J/kg kJ/(kgK) 35 37,8 40 39,0 45 40,1 50 41,2 55 42,4 60 43,4 65 44,5 70 45,6 75 46,6 80 47,6 85 48,6 90 49,6 95 50,6 100 51,6 105 52,6 110 53,5 115 54,5 120 55,4 125 56,3 130 57,3 135 58,2 140 59,1 145 60,0 150 60,9 155 61,8 160 62,7 165 63,6 170 64,5 175 65,4 180 66,3 620,53 2,3783 630,54 2,4105 640,56 2,4422 650,61 2,4736 660,71 2,5046 670,85 2,5353 681,05 2,5657 691,32 2,5958 701,66 2,6257 712,07 2,6554 722,55 2,6849 733,11 2,7142 743,76 2,7433 754,49 2,7722 765,31 2,8010 776,21 2,8297 787,20 2,8582 798,28 2,8865 809,45 2,9147 820,71 2,9429 832,06 2,9708 843,51 2,9987 855,04 3,0265 866,67 3,0541 878,40 3,0817 890,21 3,10.91 902,12 3,1364 914,12 3,1637 926,22 3,1908 938,40 3,2178
40 45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 145 150 155 160 165 170 175 180 185
33,3 34,4 35,5 36,5 37,6 38,6 39,5 40,5 41,5 42,4 43,3 44,2 45,1 46,0 46,9 47,8 48,6 49,5 50,3 51,2 52,0 52,8 53,7 54,5 55,3 56,1 56,9 57,7 58,5 59,3
624,99 635,34 645,67 656,02 666,39 676,79 687,24 697,74 708,30 718,92 729,62 740,38 751,22 762,14 773,14 784,23 795,39 806,65 817,98 829,41 840,92 852,53 864,22 876,00 887,88 899,84 911,90 924,04 936,28 948,61
2,3751 2,4079 2,4401 2,4719 2,5032 2,5342 2,5649 2,5953 2,6254 2,6553 2,6849 2,7143 2,7436 2,7727 2,8016 2,8303 2,8589 2,8873 2,9156 2,9438 2,9718 2,9998 3,0275 3,0552 3,0828 3,1103 3,1376 3,1649 3,1920 3,2191
45 50 55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 145 150 155 160 165 170 175 180 185 190
29,4 30,4 31,5 32,4 33,4 34,3 35,2 36,1 37,0 37,9 38,7 39,5 40,4 41,2 42,0 42,8 43,5 44,3 45,1 45,9 46,6 47,4 48,1 48,9 49,6 50,4 51,1 51,8 52,5 53,3
629,12 639,86 650,55 661,22 671,88 682,56 693,27 704,02 714,82 725,67 736,58 747,56 758,60 769,72 780,91 792,18 803,53 814,96 826,47 838,07 849,75 861,51 873,37 885,31 897,33 909,45 921,65 933,95 946,33 958,80
2,3716 2,4051 2,4379 2,4701 2,5019 2,5333 2,5643 2,5949 2,6253 2,6554 2,6852 2,7148 2,7442 2,7734 2,8025 2,8313 2,8600 2,8885 2,9169 2,9451 2,9732 3,0012 3,0290 3,0568 3,0844 3,1119 3,1393 3,1665 3,1937 3,2208
50 26,0 632,88 2,3676 55 27,0 644,07 2,4020 60 27,9 655,16 2 ,4355 65 28,9 666,18 2,4684 70 29,7 677,17 2,5006 75 30,6 688,16 2,5324 80 31,5 699,15 2,5638 85 32,3 710,17 2 ,5947 90 33,1 721,21 2,6254 95 33,9 732,31 2,6557 100 34,7 743,45 2,6858 105 35,4 754,64 2,7156 110 36,2 765,90 2,7451 115 36,9 777,22 2,7745 120 37,7 788,61 2,8037 125 38,4 800,07 2,8326 130 39,1 811,61 2,8614 135 39,8 823,22 2,8901 140 40,5 834,91 2,9185 145 41,2 846,68 2,9468 150 41,9 858,53 2,9750 155 42,6 870,46 3,0030 160 43,3 882,48 3,0309 165 44,0 894,58 3,0587 170 44,7 906,76 3,0864 175 45,3 919,03 3,1139 180 46,0 931,39 3,1413 185 46,7 943,83 3,1686 190 47,3 956,36 3,1958 195 48,0 968,98 3,2229
55 60 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 145 150 155 160 165 170 175 180 185 190 195 200
22,9 23,9 24,8 25,7 26,5 27,4 28,2 28,9 29,7 30,4 31,1 31,9 32,6 33,2 33,9 34,6 35,2 35,9 36,6 37,2 37,8 38,5 39,1 39,7 40,3 40,9 41,5 42,1 42,7 43,3
636,20 647,92 659,46 670,89 682,24 693,56 704,85 716,15 727,47 738,82 750,20 761,62 773,10 784,64 796,23 807,89 819,62 831,42 843,30 855,24 867,27 879,37 891,56 903,82 916,16 928,59 941,10 953,70 966,37 979,14
2,3631 2,3985 2,4329 2,4665 2,4993 2,5316 2,5633 2,5947 2,6256 2,6562 2,6865 2,7166 2,7463 2,7758 2,8052 2,8343 2,8632 2,8919 2,9205 2,9489 2,9771 3,0052 3,0332 3,0610 3,0887 3,1163 3,1438 3,1711 3,1983 3,2255
Transfair Engineering: Designing and Prototyping of Refrigerator and Freezer Cooling Circuits. 10. Final Tests, R600a Properties Tables
p. 133
ts=60,00C p=2137,0kPa t v h s C dm3/kg kJ/kg kJ/(kgK) 60 20,3 638,98 2,3577 65 21,2 651,34 2,3945 70 22,1 663,42 2 ,4299 75 22,9 675,30 2,4643 80 23,7 687,06 2,4978 85 24,5 698,74 2,5307 90 25,3 710,37 2,5629 95 26,0 721,98 2,5947 100 26,7 733,58 2,6260 105 27,4 745,19 2,6569 110 28,0 756,83 2,6875 115 28,7 768,50 2,7177 120 29,4 780,21 2,7477 125 30,0 791,97 2,7774 130 30,6 803,78 2,8069 135 31,2 815,64 2,8362 140 31,9 827,57 2,8652 145 32,5 839,57 2,8941 150 33,1 851,63 2,9227 155 33,6 863,76 2,9512 160 34,2 875,96 2,9796 165 34,8 888,24 3,0078 170 35,4 900,60 3,0358 175 35,9 913,03 3,0637 180 36,5 925,54 3,0914 185 37,1 938,12 3,1191 190 37,6 950,79 3,1466 195 38,2 963,54 3,1739 200 38,7 976,37 3,2012 205 39,3 989,28 3,2284
ts = 65,00C p=2366,0kPa t v h s C dm3/kg kJ/kg kJ/(kgK) 65 70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 145 150 155 160 165 170 175 180 185 190 195 200 205 210 17,9 18,8 19,7 20,5 21,3 22,0 22,7 23,4 24,0 24,7 25,3 25,9 26,5 27,1 27,7 28,3 28,9 29,4 30,0 30,5 31,1 31,6 32,1 32,6 33,2 33,7 34,2 34,7 35,2 35,7 641,10 654,27 666,98 679,39 691,61 703,69 715,68 727,62 739,53 751,43 763,34 775,26 787,22 799,21 811,24 823,32 835,46 847,65 859,91 872,23 884,61 897,07 909,60 922,20 934,88 947,63 960,46 973,36 986,35 999,41 2,3510 2,3896 2,4264 2,4618 2,4962 2,5297 2,5625 2,5947 2,6264 2,6577 2,6885 2,7191 2,7493 2,7792 2,8089 2,8383 2,8675 2,8965 2,9253 2,9539 2,9823 3,0106 3,0387 3,0666 3,0945 3,1221 3,1497 3,1771 3,2044 3,2316
70 75 80 85 90 95 100 105 110 115 120 125 130 135 140 145 150 155 160 165 170 175 180 185 190 195 200 205 210 215
15,7 642,39 2,3427 16,7 656,60 2,3838 17,5 670,09 2,4223 18,3 683,12 2,4589 19,1 695,86 2,4942 19,8 708,39 2,5285 20,4 720,78 2,5619 21,1 733,08 2,5947 21,7 745,32 2,6268 22,3 757,53 2,6585 22,9 769,72 2,6897 23,5 781,91 2,7205 24,1 794,12 2,7510 24,6 806,35 2,7811 25,2 818,62 2,8110 25,7 830,92 2,8406 26,2 843,27 2,8700 26,7 855,67 2,8991 27,2 868,13 2,9280 27,7 880,64 2,9567 28,2 893,22 2,9853 28,7 905,86 3,0136 29,2 918,56 3,0418 29,7 931,34 3,0699 30,2 944,19 3,0978 30,7 957,10 3,1255 31,1 970,10 3,1531 31,6 983,16 3,1806 32,1 996,30 3,2079 32,5 1009,5 3,2351
75 80 85 90 95 100 105 110 115 120 125 130 135 140 145 150 155 160 165 170 175 180 185 190 195 200 205 210 215 220
13,8 14,7 15,6 16,4 17,1 17,8 18,4 19,1 19,6 20,2 20,8 21,3 21,9 22,4 22,9 23,4 23,9 24,4 24,8 25,3 25,8 26,2 26,7 27,1 27,6 28,0 28,4 28,9 29,3 29,7
642,59 2,3320 658,23 2,3766 672,68 2,4173 686,46 2,4555 699,79 2,4919 712,83 2,5271 725,66 2,5613 738,35 2,5946 750,95 2,6273 763,48 2,6594 775,97 2,6909 788,45 2,7221 800,93 2,7528 813,41 2,7832 825,92 2,8133 838,45 2,8431 851,02 2,8726 863,63 2,9019 876,30 2,9310 889,01 2,9599 901,78 2,9885 914,60 3,0170 927,49 3,0453 940,45 3,0734 953,47 3,1013 966,56 3,1291 979,71 3,1568 992,94 3,1843 1006,2 3,2117 1019,6 3,2390
80 85 90 95 100 105 110 115 120 125 130 135 140 145 150 155 160 165 170 175 180 185 190 195 200 205 210 215 220 225
12,0 13,0 13,9 14,7 15,4 16,0 16,7 17,3 17,8 18,4 18,9 19,4 19,9 20,4 20,9 21,3 21,8 22,2 22,7 23,1 23,6 24,0 24,4 24,8 25,2 25,6 26,0 26,4 26,8 27,2
641,29 659,01 674,71 689,37 703,39 717,00 730,32 743,43 756,41 769,29 782,11 794,88 807,63 820,38 833,14 845,91 858,71 871,54 884,41 897,33 910,30 923,32 936,39 949,53 962,73 975,99 989,31 1002,7 1016,2 1029,7
2,3180 2,3678 2,4113 2,4514 2,4893 2,5255 2,5605 2,5945 2,6277 2,6603 2,6923 2,7237 2,7548 2,7855 2,8158 2,8458 2,8755 2,9050 2,9342 2,9632 2,9919 3,0205 3,0489 3,0771 3,1052 3,1330 3,1608 3,1883 3,2158 3,2431
Transfair Engineering: Designing and Prototyping Cooling Circuits. 10.15 EMC Tests 10.16 Cooling Circuit Pressure Tests
p. 134
10.17.
Even if Isobutane explode inside the system, which theoretically could happen, according to tests executed by Liebherr and others the maximum pressure peak of 12 bars are created during explosion in the cooling circuit and this pressure should remains under the critical load of any cooling circuit components and joints. The IEC/EN 600335-2-24 section 22.7 requires a pressure test on circuit components for flammable refrigerants. They should withstand an absolute pressure of 3.5 times of the saturated vapour pressure of the refrigerant at 70C for parts exposed to the high side pressure during normal operation, that means 35 bar relative; 5 times of the saturated vapour pressure of the refrigerant at 20C for parts exposed to the low side pressure during normal operation, that means 10 bar relative; The pressures are gauged pressures. Also the European Pressure Equipment Directive (PED) 97/23/EC from 29 November 1999 requires that all items of pressure equipment placed on the market in the European Economic Area (EEA) after May 2002 must comply with this directive. So the complete cooling circuit, even the ones filled without flammable refrigerants, all without pressure relieve valve must be able to withstand the maximum pressure, which can be built up inside the circuit. We should add a 50% reserve before bursting. Such pressure is normally not critical for household refrigerator cooling circuit components and correctly made brazing and other joints, but it deforms Aluminium Roll Bond and other flat copper or aluminium components, like flat accumulators or receivers. A refrigerator manufacturer should insist today on the conformity declaration of components manufacturers (compressor, filter dryers, accumulators, valves, condensers, evaporators and tubes) and have to execute refrigerator type pressure tests for type approval and - to control the type approval conform manufacturing process - at least pressure tests on samples or on all refrigerators, if no deformation will happen, for example during Helium leak test (see Chapter 4.7. in Transfair Engineering: Evacuation, Charging, Leak Detection and Performance Testing in the Household Refrigerator production Today 2006, to stress the joints.
Transfair Engineering: Designing and Prototyping Cooling Circuits. 11. Converting refrigerators to 134a and to R600a Systems
p. 135
11.
Converting Household Refrigerators from CFC-12 to HFC-134a Systems and from HFC-134a to HC-600a Systems
Transfair Engineering: Designing and Prototyping Cooling Circuits. 11. Converting refrigerators to 134a and to R600a Systems
p. 136
the ideal conditions according to the table or program and the calculation in chapter 4.1.) that vapour come out of capillary (temperature difference of liquid and vapour at evaporator inlet), max. 7 % of evaporator in worse conditions should be liquid filled. (to be measured by identification of temperature zones in the evaporator inlet). The behaviour is changing not only by changing of capillary tube length, environmental temperatures and loads, but also it depends from refrigerant charge quantity to be optimized, so that all tests must be repeated several times till all parameters are optimal.
7. Sub cooling heat exchanger: Sub cooling of HFC-134a increases the nominal capacity by about 23%, 4% more than in a CFC-12 model. So it is a must for a HFC-134a system. The capillary tube should be winded round the cold suction tube of the compressor covered by a shrink film sleeve. 8. HFC- Refrigerant charge quantity: The optimal HFC-134a charge quantity is the one which reaches 3-5C superheat above the saturated temperature which matches the measured pressure (see table or use program) between evaporator outlet and compressor inlet. It is about 10% less than the CFC-12 charge quantity (if all condenser, compressor, filter and evaporator would be the same). Fine tuning of charge quantity is needed (see chapter 7.5.4.). By modifying other circuit parts the test must be repeated. 9. It is always useful to use the conversion to optimize the refrigerator in all areas, stating from thermal insulation, elimination of thermal bridges (Chapter 1.5.), using energy optimized compressors (chapter 2.10), eliminate accumulators by using vertical u-bends in refrigerator evaporator (chapter 5.2.2.), etc. The conditions for different models and climate classes are varying so much that some single items cannot be recommended in this chapter and therefore it is useful to go through all chapters and recommended measurements and tests again for the development of an optimal system. 10. The additional requirements on cleanliness in circuit components and during processing, the limited time of opening the compressor and filter dryer, the cleaning of condensers and evaporators, the higher demand on the brazing quality, all this can only be reached by strict quality control measures, which must accompany the introduction of R134a model manufacturing (see Chapter 7.3. and Transfair Engineering: Evacuation, Charging, Leak detection and Performance Testing in the Household Refrigerator Industries today, Dsseldorf 2001). Last not least all manufacturers though they dont like to admit it test regularly the models of their best competitors and compare their efficiency values with the ones of their own products to identify own weak areas to be improved. So also such an approach is strongly recommended.
Transfair Engineering: Designing and Prototyping Cooling Circuits. 11. Converting refrigerators to 134a and to R600a Systems
p. 137
electric coil and energy consumption by different cylinder sizes of HFC-134a and HC-600a are practically the same for the same cooling capacity. 4. The charge tolerances of HC-600a is much smaller, even less than expected from the lower charge quantity. The requirement on fine tuning of charge quantity, the charge accuracy must be inside the range of 1g and the leak detection inside the range of 1 g per year. Too high charge can cause oil film break on the cylinder. 5. If all are optimized HC-600a systems today are at least 5% more efficient as the HFC-134a models, if all other conditions are comparable. In addition in can be stronger improved by a run capacitor as HFC-134a models. 6. Normal mineral oil can be used in the HC-600a compressors and this eliminates a lot of cleanliness problems using HFC134a systems with hydroscopic ester oil (humidity, chlorine, oxidation, grease and mineral oil). But the demand on cleanliness has not been diminished, only changed. Because of much lower refrigerant quantity same absolute impurity has higher thermodynamic effects if it is a gas or can be vaporized. All non-condensable gases even diluted inside the compressor oil, must be removed by special evacuation processes under compressor run (see Transfair Engineering: Evacuation, Charging, Leak detection and Performance Testing in the Household Refrigerator Industries today, Dsseldorf 2001). Only by high cleanliness the efficiency advantage can be reached.
Except the a.m. points the designing of R600a is a standard refrigerator engineering work.
Transfair Engineering: Designing and Prototyping of Refrigerator and Freezer Cooling Circuits. 12. IEC and EN Standards
p. 138
12. 12.7.
The standards, as already mentioned in the booklet and applied, specify which tests according to which methods the household refrigerator manufacturer have to execute for household refrigerator type approval in Europe for example to issue CE conformity declaration, on manufactured samples or all made refrigerators to insure that his production is conform with type approval. Following international or relevant national standards exist for refrigerators and freezers:
Household refrigerator
-
EN ISO 15502 (2005): Household refrigerating appliances - Characteristics and test methods (ISO 15502:2005); it replaced the 4 withdrawn standards: ISO EN 7371 - Performance of household refrigerating appliances - refrigerators with or without low
temperature compartment; ISO 8187 EN 28187 - Household refrigerating appliances - Refrigerators-freezers' characteristics and test methods; ISO EN 5155 - Household refrigerating appliances - Frozen food storage cabinet and food freezers characteristics and test methods; ISO EN 8561 Household Frost free refrigerating appliances, refrigerators, refrigerator-freezers characteristics and test methods.
EN 153 (2006): Methods of measuring the energy consumption of electric mains operated household refrigerators, frozen food storage cabinets, food freezers and their combinations, together with associated characteristics
Safety Standards for Refrigerators and Freezers - IEC/EN/UL/J/GOST etc. Standard 60335, Part 1: Safety of household and similar electric appliances, and - IEC/EN/UL/J/GOST etc. Standard 60335, Part 2-24 (2005): Particular requirements for refrigerator appliances and ice makers. - IEC-EN-UL-J-GOST etc. Standard 60335, Part 2-89 (2007): Particular requirements for commercial refrigerating appliances with an incorporated or remote refrigerant condensing unit or compressor, Vers. 1.2. For flammable refrigerants (R600a) these standards specify to carry out risk assessment to control flammability risk by tests clauses 22. DIN 8964 (1996/2002): Circuit components for refrigerating systems - Part 1: Testing, Part 2: Sealed systems; Requirements, (2002): Part 3: Closed systems; Requirements To be applied on complete cooling circuit EU PED -Pressure Equipment Directive 97/23/EC by pressurization of the circuit by 15bar for R600a and 23 bar for R134a.
Electric Components
-
Electrical standards of IEC/EN for each used electrical part and in Europe the EU Low Voltage Directive (73/23/EEC) as amended 93/68/EEC. Fan motor electric safety EN 60335-2-80 and EN60335-2-24 Annex AA: locked-rotor test fan motor Pressure switch EN 60730-2-9 Compressor electric safety: EN60335-1 and 2-34 Electric terminal box on compressor and in zone with potential R600a leaks must be made in accordance with n protection (class IP 54 if flammable gas cannot accumulate or higher) according to IEC60079-15 and correspond to the required "Zone 2" regulations. The protection device must be connected according to the wiring diagram. The wires (PTC control circuit) between terminals) and compressor terminal plate must be either shielded or twisted cable (danger of inductance).
EMC Electromagnetic compatibility Directive 2004/108/EC. The new EMC Directive has been published in the Official Journal of the European Union, L 390/24, 31 December 2004, and will repeal Directive 89/336/EEC as from 20 July 2007. Products must be constructed so that they do not cause excessive electromagnetic interference and are not unduly affected by electromagnetic interference. How this new directive will apply to household refrigerators, which tests has really to be executed it still has to be
Transfair Engineering: Designing and Prototyping of Refrigerator and Freezer Cooling Circuits. 12. IEC and EN Standards
p. 139
clarified. But the manufacturer do not depend anymore on authorized bodies to approve and can make assessment on its own, which reduce costs. EN 55014-1:2001Electromagnetic compatibilityRequirements for household appliances, electric tools, and similar apparatusPart 1: EmissionProduct family standard. EN 55014-2:1997Electromagnetic compatibilityRequirements for household appliances, electric tools, and similar apparatusPart 2: ImmunityProduct family standard. EN 61000-part 3-2 (2006): Electromagnetic compatibility (EMC). Limits for harmonic current emissions (equipment input current < 16 A per phase) and part 3-3 Voltage fluctuation and flicker limits
This process will ultimately lead to affixing of a CE mark on the product when coupled with all other relevant requirements of applicable new approach directives.
Commercial refrigerator
EN ISO 23953 (2006) Refrigerated display cabinets Part 1 Vocabulary, Part 2: Classification, requirements and test conditions. EN 441: Methods of measuring the energy consumption, energy labelling of commercial refrigerators. EN378: For design, operation and maintenance of refrigeration plants with flammable refrigerants (Group L3), special safety regulations apply. Belonging to these regulations, amongst other things, are special protection devices against excessive pressure and special features in design and arrangement of electrical equipment. Moreover, steps are to be taken that in case of a refrigerant leak, it is harmlessly vented away so that no explosive mixture can occur. The exact design regulations are determined in the Standards, e.g. EN378 / In Germany VBG20 / draft DIN 7003 / DIN VDE 0165 / VDE 0100. With the present regulations, a separate agreement is to be met between the plant contractors and the operator. According to the design and refrigerant charge, individual authorisation from the industrial regulatory authority may also be required. Additionally, the designer of such plants must be certified in dealing with flammable refrigerants; for the operating personnel, qualified instruction is required. The present standards only cover design regulations for stationary plants.
Absorption refrigerator
- EN 732 (1998): Specifications for dedicated liquefied petroleum gas appliances - Absorption refrigerators.
Valves
- EN 12284 (2004): Klteanlagen und Wrmepumpen - Ventile - Anforderungen, Prfung und Kennzeichnung
Compressor
EN 12900 (2005): Refrigerant compressors - Rating conditions, tolerances and presentation of manufacturer's performance data. EN 13771-1 (2003 /2005): Compressors and condensing units for refrigeration - Performance testing and test methods Part 1: Refrigerant compressors. This part 1 of the European Standard applies only to refrigerant compressors and describes a number of selected performance test methods. These methods provide sufficiently accurate results for the determination of the refrigerating capacity, power absorbed, refrigerant mass flow, isentropic efficiency and the coefficient of performance. This standard applies only to performance tests conducted at the manufacturer's works or wherever the equipment for testing to the accuracy required is available. The type of measuring instrument and the limits within which measurements shall be made are listed in normative annex A.
Compressor safety - Compressor electric safety: EN60335-1 and 2-34 - EN 12693 (1997) Klteanlagen und Wrmepumpen - Sicherheitstechnische und umweltrelevante Anforderungen Kltemittel-Verdichter
Transfair Engineering: Designing and Prototyping of Refrigerator and Freezer Cooling Circuits. 12. IEC and EN Standards
p. 140
Condenser
EN 13771-2 (2003 /2005): Compressors and condensing units for refrigeration - Performance testing and test methodsPart 2: Condensing units. EN 13215 (2000): Condensing units for refrigeration - Rating conditions, tolerances and presentation of manufacturer's performance data. EN 327 Air cooled refrigerant condensers, Heat exchangers. Forced convection air cooled refrigerant condensers. Test procedure for establishing performance. EN 13136 (2005): Refrigerating systems and heat pumps - Pressure relief devices and their associated piping - Methods for calculation. EN 13313 (2002): Refrigerating systems and heat pumps - Competence of personnel. This European Standard establishes procedures for achieving and assessing the competence of persons who design, install, test and commission, maintain, repair and dispose of refrigerating systems with respect to health, safety, environmental and energy conservation requirements. This European Standard does not apply to those persons who carry out work on the basis of instructions if they are supervised by a competent person. EN 14276 (2002): Pressure equipment for refrigerating systems and heat pumps - Part 1: Vessels - General requirements;
Filter Dryer
DIN 8949 (2000): Refrigerant filter driers Testing
Acoustical noise
EN 28960 (1993) Refrigerators, frozen food storage cabinets and food freezers for household and similar use; measurement of emission of airborne acoustical noise (ISO 8960:1991).
EU Directives
http://europa.eu.int/comm/enterprise/electr_equipment/legislat.htm http://europa.eu.int/comm/enterprise/newapproach/standardization/harmstds/reflist.html
Transfair Engineering: Designing and Prototyping of Refrigerator and Freezer Cooling Circuits. 12. IEC and EN Standards
p. 141
12.8.
ISO Standards
ISO Standards are at least in our areas identical with EN and can be received by http://www.iso.org/
12.9.
IEC standards
IEC Standards can be received by http://www.iec.ch/ or by the national standard institutes of member countries or their publishers. In EU from the institutes or publishers as already mentioned in chapter 12.1.
12.10.
-
Household refrigerator
ANSI/AHAM HRF 1 (2004): Energy, Performance and Capacity of Household Refrigerators, RefrigeratorFreezers and Freezers. The purpose of this standard is to establish a uniform and repeatable procedure or standard method for measuring specified product characteristics of household refrigerators, household wine chillers and household freezers. This standard covers definitions, methods for computing volumes and shelf areas, methods for determining volumes of special features, performance test procedures, durability test procedures, methods for determining energy consumption and energy factor, and safety recommendations. The US-UL signed the above IEC 60335 1 and 2-24. In addition there exists ANSI/ASHRAE Standard 15-2004 Safety Standard for Refrigeration Systems. ANSI/ASHRAE 15-2004 is the newest version of one of ASHRAEs oldest standards. This version is a republication of ANSI/ASHRAE 15-2001, including addendum a. The reader is referred to that addendum as well as Appendix J of this standard for changes that have been made since the original publication of ANSI/ASHRAE 15-2001. Among those changes were changes to the treatment of flammable refrigerants, including correction of an omission in the 2001 standard. In addition, changes were made to the requirements for pressure vessel protection and references were updated. This standard is directed toward the safety of persons and property on or near the premises where refrigeration facilities are located. It includes specifications for fabrication of tight systems but does not address the effects of refrigerant emissions on the environment. For information on the environmental effects of refrigerant emissions, see ASHRAE Guideline 3-1996, Reducing Emission of Halogenated Refrigerants in Refrigeration and Air-Conditioning Equipment and Systems.
Safety Standards for Refrigerators and Freezers - UL 60335, Part 1: Safety of household and similar electric appliances, and - UL 60335, Part 2-24 (2005): Particular requirements for refrigerator appliances and ice makers. - UL 250: Standard for Safety Household Refrigerators and Freezers
Commercial refrigerator
ANSI/ASHRAE Standard 72 (2005): Method of Testing Commercial Refrigerators and Freezers. This revision of Standard 72 combines Standard 72-1998 for open refrigerators and Standard 117-2002 for closed refrigerators. It prescribes a uniform method of testing open and closed commercial refrigerators and freezers for rating so that comparative evaluations can be made of energy consumption, product temperature performance, refrigeration load, the suction pressures required, and other performance factors. The standard also clarifies door opening requirements, shelf loading, and test definitions, and includes requirements that improve the consistency of ambient temperatures. This standard should be useful to the design engineer responsible for rating open or closed commercial refrigerators. - ANSI-NSF 7-2001: Commercial Refrigerators and Freezers Electric safety standards: - UL 471Standard for Safety Commercial Refrigerators and Freezers, 2006 - UL 399 Standard for Drinking-Water Coolers - UL 541Standard for Refrigerated Vending Machines - UL 563Standard for Ice Makers - UL 621Standard for Ice Cream Makers -
Transfair Engineering: Designing and Prototyping of Refrigerator and Freezer Cooling Circuits. 12. IEC and EN Standards
p. 142
Compressor
ANSI/ASHRAE 23(2005): Methods of Testing for Rating Positive Displacement Refrigerant Compressors and Condensing Units. This standard applies to the methods of testing for rating single-stage positive-displacement refrigerant compressors and condensing units that (a) do not have liquid injection and (b) are operated at subcritical (saturated) temperatures of the refrigerant. It also applies to the methods of testing for rating single-stage positive-displacement refrigerant compressors and condensing units that (a) incorporate liquid injection that is controlled by a steady flow rate method and (b) are operated at subcritical (saturated) temperatures of the refrigerant. This standard applies to all of the refrigerants listed in the ASHRAE Handbook Fundamentals and in ANSI/ ASHRAE Standard 342 that fall within the scope defined above. UL 894: Safety of hermetic compressors.
Condenser
ANSI/ASHRAE Standard 20-1997 (RA 2006): Method of Testing for Rating Remote Mechanical-Draft Air-Cooled Refrigerant Condensers. This reaffirmation of ANSI/ASHRAE Standard 20-1997 prescribes methods of laboratory testing to measure the heat rejection capabilities of remote mechanical draft, air-cooled refrigerant condensers for refrigerating and air conditioning. The objective is to ensure uniform performance information for establishing ratings. The changes made for the 2006 reaffirmation were that the references were updated.
Capillary
ANSI/ASHRAE 28 (1996) (RA 2006): Method of Testing Flow Capacity of Refrigerant Capillary Tubes. It provides a uniform procedure for testing capillary tubes by determining the dry nitrogen flow capacity under specific test conditions so the procedures may serve as a primary standard for use by all test laboratories. Provides a basis for agreement between capillary tube manufacturers and users, and provides a standard procedure against which all other methods of tests may be checked. Dual units of measurement.
Filter dryer
ANSI/ASHRAE Standard 35 (1992): Desiccants for Refrigerant Drying, Method of Testing. This standard is under continuous maintenance, which is a process ASHRAE uses to keep standards current through the issuance of addenda, or revisions. When they are available, these addenda can be downloaded for free at the following page of the ASHRAE web site: http://www.ashrae.org/template/TechnologyLinkLanding/category/1631 . When they are available, interpretations of the standard, issued by the sponsoring technical committee, also may be downloaded for free at the following address: http://www.ashrae.org/template/TechnologyLinkLanding/category/1686 . Errata lists are issued occasionally and may be downloaded for free at the following address: http://www.ashrae.org/template/TechnologyLinkLanding/category/1685 ANSI/ASHRAE Standard 63.1 (1995) (RA 2001): Method of Testing Liquid Line Refrigerant Driers. It prescribes test methods for determining flow capacity and water capacity performance characteristics of liquid line refrigerant driers. It applies to driers that employ a desiccant. The water capacity test method prescribed can be used to test a drier either "as received" or after being reactivated in accordance with manufacturer's recommendations. Dual units of measurement. ANSI/ASHRAE Standard 63.2 (1996): Method of Testing Liquid Line Filter-Drier Filtration Capability. It prescribes a laboratory test method for evaluating the filtration capability of filters and filter-driers used in liquid lines of refrigeration systems. ANSI/ASHRAE Standard 78 (1985) (RA 2003): Method of Testing Flow Capacity of Suction Line Filters and FilterDriers. It establishes a method for measuring the flow capacity of refrigerant suction line filters and filter-driers. Intended for use on both sealed model and replaceable element type suction line filters and filter-driers of all types. Dual units of measurement. ARI STANDARD 710:86 Absorption Capacity of dryers
Transfair Engineering: Designing and Prototyping of Refrigerator and Freezer Cooling Circuits. 12. IEC and EN Standards
p. 143
10.6.2.
The manufacturer must put together a technical documentation which makes it possible to assess whether the product complies with the directive The manufacturer or the authorised representative must draw up a declaration of conformity. The manufacturer or the authorised representative must affix the CE marking
Advice on the applicability and completeness of standards to products Testing to harmonised, international, national standards, or clients own specification. Assessment for compliance with the LVD Assessment of the technical documentation A notified body report in accordance with article 11 of the LVD.
Transfair Engineering: Designing and Prototyping of Refrigerator and Freezer Cooling Circuits. 12. IEC and EN Standards
p. 144
Companies already ISO 9000 compliant can take advantage of their current quality systems and use this as a foundation to satisfy the Essential Safety Requirements of the PED. In which case compliance can be achieved through QA assessments from their appointed Notified Body only, rather than by third party Notified Body product inspection. If the manufacturer has not been formally accredited to the ISO 9000 series, Notified Body services under the PED QA approaches.
Assistance with technical file preparation PED compliant quality system preparation Gap analysis visits. Welding procedure qualification to ASME IX and/or EN ISO 15614 and welder qualification to ASME IX and/or EN 287 Brazing procedure qualification to both ASME IX and EN 13134 and brazer qualification to both ASME IX and EN 13133 Particular Material Appraisal approval to Annex 1 section 4.2b Specially arranged training courses and seminars on compliance tailored specifically to your needs, technical file preparation and compliance quality system preparation.
Product Services:
A complete compliance service on products including design assessment (modules B/B1), from fire extinguishers to major industrial installations. An expert and dedicated PED team to support you through every step of the certification process. Our understanding of the commercial realities under which you operate mean we help you achieve PED compliance with minimal or no interruption to production, inspections/audits focused on how the required standards can be implemented into todays engineering practices and consideration to keeping your costs down.
EU ATEX Directives
ATEX Manufacturers Directive 94/9/EC. This directive defines each of the following product groups for use in potentially explosive atmospheres:
Electrical and non-electrical equipment Electrical and non-electrical protective systems Electrical and non-electrical components Electrical and non-electrical safety devices
The directive places responsibilities on the manufacturer of these products. The main responsibility of the manufacturer is to prevent the formation and ignition of explosive atmospheres. This may be achieved by using one of the well-established protection concepts (such as flameproof protection, or intrinsic safety), or by proving compliance directly against a set of 'essential health and safety requirements', which are given in the directive. Note: This directive may also be heard described as ATEX '100a' or today as 'ATEX 95', after the enabling articles of European treaties. ATEX User Directive 99/92/EC This directive is concerned with the health and safety of workers with relation to potentially explosive atmospheres. It places responsibilities on an employer. Typical responsibilities include:
The assessment of risks Hazardous Area Classification Mitigation &/or removal of Risks Preparation of an Explosion Protection Document The provision of suitable warning signs for areas where explosive atmospheres may form
Note: This directive may also be heard described as ATEX '137', after the enabling article of the Treaty of Rome. Dangerous Substances and Explosive Atmospheres Regulations From July 2006 employers must have completed the risk assessment, classification and documentation of their workplace and personnel.
p. 145
p. 146
Energy Label Option 1 + Minimum considers the enforcing of an EU-wide mandatory minimum energy efficiency Energy Efficiency Requirement requirement at EEI=55 from January 2007 (via the revision of the Directive 96/57/EC) along with the upgrading of the energy labelling directive 94/2/EC according to the labelling scheme described in scenario EL1 starting January 2004. In practice this scenario represents the building of mandatory minimum energy efficiency requirements on top of the revised labelling scheme. (EL1+MER)
p. 147
Energy Label Option 1a+Minimum Energy Efficiency Requirement This is the repetition of scenario "EL1+MER", in which the labelling scheme is applied less effectively (EL1a+MER) Energy Label Option 2 + Voluntary This assumes that a Voluntary Commitment for cold appliances is negotiated with industry, wherein the current C class appliances are phased out as per January 2004 Agreement Target followed by a "fleet" (i.e., weighted according to the sales of the different models for each manufacturer) average efficiency of new products, reaching the EEI=52 level by 2006. Contemporarily the labelling scheme described in scenario EL2 is enforced through the revision of Directive 94/2/EC. Again, the voluntary target is built in parallel (EL2+VAT) with the revised labelling scheme
p. 148
79/530/EEC must therefore be replaced and Directive 79/531/EEC (5) applying to those electric ovens should be revised and subsequently integrated into the present scheme; Whereas a completely voluntary scheme would lead to only some appliances being labelled, or supplied with standard product information, with the risk that this might result in confusion for some consumers; whereas the present scheme must therefore ensure that for all the appliances concerned, the energy consumption is indicated by labelling and standard product fiches are provided; Whereas household appliances use a wide variety of forms of energy, with electricity and gas being the most important; whereas this Directive must therefore in principle cover appliances using any form of energy; Whereas Council Directive 86/594/EEC of 1 December 1986 on airborne noise emitted by household appliances (6) provides for an indication of noise emission to be included on energy labels, where appropriate; whereas provision must therefore be made for the incorporation of any other information and labelling covered by Community schemes; Whereas only those types of appliances whose aggregate energy use is significant and which afford adequate scope for increased efficiency need be included, HAS ADOPTED THIS DIRECTIVE: Article 1 1. The purpose of this Directive is to enable the harmonization of national measures on the publication, particularly by means of labelling and of product information, of information on the consumption of energy and of other essential resources, and additional information concerning certain types of household appliances, thereby allowing consumers to choose more energy-efficient appliances. This Directive shall apply to the following types of household appliances, even where these are sold for non-household uses: refrigerators, freezers and their combinations, washing machines, driers and their combinations, dishwashers, ovens, water heaters and hot-water storage appliances, lighting sources, air-conditioning appliances.
2. Further types of household appliances may be added to the list in this Article in accordance with Article 9 (b). 3. This Directive shall not apply to the rating plate or its equivalent affixed for safety purposes to such appliances. 4. For the purpose of this Directive: dealer means a retailer or other person who sells, hires, offers for hire-purchase or displays household appliances to endusers, supplier means the manufacturer or his authorized representative in the Community or the person who places the product on the Community market, information sheet means a standard table of information relating to the appliance in question, other essential resources means water, chemicals or any other substance consumed by an appliance in normal use, supplementary information means other information concerning the performance of an appliance, which relates to, or is helpful in evaluating, its use of energy or other essential resources.
5. There shall be no obligation to label or to provide fiches in respect of models of appliances of which production has ceased before the relevant implementing directive comes into effect, or second-hand appliances. Article 2 1. Information relating to the consumption of electric energy, other forms of energy and other essential resources and supplementary information shall be brought to consumers' attention by means of a fiche and a label related to household appliances offered for sale, hire, hire-purchase or displayed to end-users.
p. 149
2. Details relating to the label and the fiche shall be defined by directives relating to each type of appliance adopted pursuant to this Directive in accordance with Article 9. 3. Technical documentation shall be established which shall be sufficient to enable the accuracy of the information contained in the label and the fiche to be assessed. It shall include: a general description of the product, the results of design calculations carried out, where these are relevant, test reports, where available, including those carried out by relevant notified organizations as defined under other Community legislation, where values are derived from those obtained for similar models, the same information for these models.
4. The supplier shall establish the technical documentation described in paragraph 3. To this end it may use documentation already required on the basis of relevant Community legislation. The supplier shall make this documentation available for inspection purposes for a period ending five years after the last product has been manufactured. Article 3 1. All suppliers placing on the market the household appliances specified in the implementing directives shall supply a label in accordance with this Directive. The labels used shall in all respects comply with this Directive and with the implementing directives. 2. In addition to the labels, suppliers shall provide a product fiche. This fiche shall be contained in all product brochures. Where these are not provided by the supplier, he shall supply fiches with other literature provided with the appliance. The fiches used shall in all respects comply with this Directive and with the implementing Directives. 3. Suppliers shall be responsible for the accuracy of the labels and fiches that they supply. 4. The supplier shall be deemed to have given his consent to the publication of the information given on the label or the fiche. Article 4 In respect of labelling and product information, the following provisions shall apply: a) whenever an appliance specified in an implementing directive is displayed, dealers shall attach an appropriate label, in the clearly visible position specified in the relevant implementing directive, and in the relevant language version; b) the supplier shall supply the necessary labels free of charge, to dealers referred to in paragraph (a). Suppliers are free to choose their own system for delivery of labels. However, where a dealer sends a request for labels, the supplier must ensure that the requested labels are delivered promptly.
Article 5 Where the relevant appliances are offered for sale, hire or hire-purchase by mail order, by catalogue, or by other means which imply that the potential customer cannot be expected to see the appliance displayed, the implementing directives shall make provision to ensure that potential customers are provided with the essential information specified in the label or the fiche before buying an appliance. Article 6 The implementing Directives shall make provision for the inclusion on the label or on the fiche of information on airborne noise, where such information is provided pursuant to Directive 86/594/EEC and of other public information relating to the relevant appliance, which is provided pursuant to other Community legislation. Article 7 Member States shall take all necessary measures to ensure that: a) all suppliers and dealers established in their territory fulfil their obligations under this Directive;
p. 150
b) if this is likely to mislead or confuse, the display of other labels, marks, symbols or inscriptions relating to energy consumption which do not comply with the requirements of this Directive and of the relevant implementing directives is prohibited. This prohibition shall not apply to Community or national environmental labelling schemes; c) the introduction of the system of labels and fiches concerning energy consumption is accompanied by educational and promotional information campaigns aimed at encouraging more responsible use of energy by private consumers. Article 8 1. Where the provisions of this Directive and of the implementing directives are satisfied, Member States shall neither prohibit nor restrict the placing on the market of the household appliances covered by an implementing directive. 2. Unless they have evidence to the contrary, Member States shall deem labels and fiches to comply with the provisions of this Directive and the implementing directives. They may require suppliers to furnish evidence within the meaning of Article 2 (3) concerning the accuracy of the information supplied on their labels or fiches when they have reason to suspect it is incorrect. Article 9 The measures relating to the establishment and operation of the scheme shall be adopted and adapted to technical progress in accordance with the procedure set out in Article 10. These measures are: a) the implementing directives; b) the addition of further household appliances to the list in Article 1 (1) where significant energy savings are likely to be achieved. Article 10 The Commission shall be assisted by a committee composed of representatives of the Member States and chaired by the representative of the Commission. The representative of the Commission shall submit to the committee a draft of the measures to be taken. The committee shall deliver its opinion on the draft within a time limit which the chairman may lay down according to the urgency of the matter. The opinion shall be delivered by the majority laid down in Article 148 (2) of the EEC Treaty in the case of decisions which the Council is required to adopt on a proposal from the Commission. The votes of the representatives of the Member States within the committee shall be weighted in the manner set out in that Article. The chairman shall not vote. The Commission shall adopt the measures envisaged if they are in accordance with the opinion of the committee. If the measures envisaged are not in accordance with the opinion of the committee, or if no opinion is delivered, the Commission shall, without delay, submit to the Council a proposal relating to the measures to be taken. The Council shall act by a qualified majority. If, on the expiry of three months from the date of referral to the Council, the Council has not acted, the proposed measures shall be adopted by the Commission, save where the Council has decided against the said measures, by a simple majority. Article 11 After the expiry of a period of three years from the application of this Directive, the Commission shall make an assessment of the implementation thereof and the results obtained. The assessment shall be the subject of a report to be submitted to the European Parliament and the Council. Article 12 The implementing directives shall specify: a) b) c) d) the exact definition of the type of appliances to be included; the measurement standards and methods to be used in obtaining the information referred to in Article 1 (1); details of the technical documentation required under Article 2 (3); the design and content of the label referred to in Article 2, which as far as possible shall have uniform design characteristics;
p. 151
the location where the label shall be fixed to the appliance. Where appropriate they may provide for the label to be attached to or printed on the packaging; f) the content and where appropriate the format and other details concerning the fiche or further information specified in Article 3 (2). The information on the label shall also be included on the fiche; g) the information to be provided in the case of offers for sale covered by Article 5, and the manner in which it is to be provided. Article 13 Directive 79/530/EEC is hereby repealed, with effect from 1 January 1994. Directive 79/531/EEC shall be considered as implementing this Directive for electric ovens; however Member States may refrain from its compulsory introduction, until a date set in a revised implementing directive concerning ovens passed in accordance with the procedure laid down in Article 10. Article 14 1. Member States shall adopt the provisions necessary to comply with this Directive by 1 July 1993. They shall immediately notify the Commission of these measures. They shall bring these provisions into force by not later than 1 January 1994. 2. When Member States adopt these measures, they shall contain a reference to this Directive or shall be accompanied by such reference on the occasion of their official publication. The methods of making such a reference shall be laid down by the Member States. 3. Member States shall communicate to the Commission the main provisions of domestic law which they adopt in the field covered by this Directive. Article 15 This Directive is addressed to the Member States. Done at Brussels, 22 September 1992. For the Council The President R. NEEDHAM (1) OJ No C 235, 10. 9. 1991, p. 5. (2) OJ No C 125, 18. 5. 1992, p. 172 and OJ No C 241, 21. 9. 1992. (3) OJ No C 49, 24. 2. 1992, p. 32. (4) OJ No L 145, 13. 6. 1979, p. 1. (5) OJ No L 145, 13. 6. 1979, p. 7. (6) OJ No L 344, 6. 12. 1986, p. 24.
e)
ANNEX I THE LABEL Label design 1. The label shall be in accordance with the following illustrations: Notes on label 2. The following notes define the information to be included: Note: I. Supplier's name or trade mark. II. Suppliers model identifier.
p. 152
III. The energy efficiency class of an appliance shall be determined in accordance with Annex V. The appropriate letter shall be placed at the same level as the relevant arrow. IV. Without prejudice to any requirements under the Community Eco-label award scheme, where an appliance has been granted a 'Community Eco-label award' pursuant to Council Regulation (EEC) No 880/92 (1) a copy of the Eco-award mark (the flower) may be added here. The 'refrigerator/freezer label design guide' referred to below, explains how the Eco-award mark, may be included in the label. V. Energy consumption in accordance with standards referred to in Article 1 (2) but expressed in kWh per year (i.e. per 24 hours 365). VI. Sum of net storage volume of all compartments that do not merit a star rating (i.e. operating temperature > - 6 C). VII. Sum of net storage volume of all frozen food storage compartments which merit a star rating (i.e. operating temperature = - 6 C). VIII. Star rating of frozen food storage compartment, in accordance with standards referred to in Article 1 (2). Where this compartment does not merit any stars, this position shall be left blank. IX. Where applicable noise measured in accordance with Directive 86/594/EEC. NB: The equivalent terms in other languages to those described above are given in Annex VI. Printing 3. The following defines certain aspects of the label: >REFERENCE TO A GRAPHIC> Complete printing information is contained in a 'refrigerator/freezer label design guide' obtainable from: The Secretary of the Committee on Energy Labelling and Standard Product Information for Household Appliances Directorate-General for Energy DG XVII, Commission of the European Communities, 200 Rue de la Loi, B-1049 Brussels. (1) OJ No L 99, 11. 4. 1992, p. 1. ANNEX II THE FICHE The fiche shall contain the following information. The information may be given in the form of a table covering a number of appliances supplied by the same supplier, in which case it shall be given in the order specified, or given in the description of the appliance: 1. 2. 3. Supplier's name or trade mark. Supplier's model identifier. Type of appliance as follows: o Larger Fridge o Refrigerator/chiller o Refrigerator no star o Refrigerator * o Refrigerator ** o Refrigerator ***/ o Fridge-freezer *(***) o Upright freezer o Chest freezer o Multi-door or other appliance The energy efficiency class of the model as defined in Annex V, expressed as 'Energy efficiency class . . . on a scale of A (most efficient) to G (least efficient)'. Where this information is provided in a table this may be expressed by other means provided it is clear that the scale is from A (most efficient) to G (least efficient). Where the information is provided in a table, and where some of the appliances listed in the table have been granted a 'Community Eco-label award' under Regulation (EEC) No 880/92, this information may be included here. In this case the row heading shall state 'Community Eco-label award', and the entry shall consist of a copy of the Eco-award mark (the flower). This provision is without prejudice to any requirements under the Community Eco-label award scheme.
4.
5.
p. 153
6.
Energy consumption in accordance with standards referred to in Article 1 (2) but expressed in kWh per year (i.e. per 24 hours 365), described as: 'energy consumption XYZ kWh per year, based on standard test results for 24 h. Actual energy consumption will depend on how the appliance is used and where it is located.' Net storage volume of fresh food storage compartment (5 C) in accordance with standards referred to in Article 1 (2) omit for classes 8 and 9. Net storage volume of frozen food storage compartment, in accordance with standards referred to in Article 1 (2) - omit for classes 1, 2 and 3. For class 3 appliances the net volume of the 'ice box'. and 8. For classes 2 and 10 the net volume of each compartment should be listed, in accordance with standards referred to in Article 1 (2). Star rating of frozen food storage compartment, if any, in accordance with standards referred to in Article 1 (2). The mention 'no frost' may be included here when in accordance with the definitions given in the standards referred to in Article 1 (2). 'Power cut safe Z h' defined as 'temperature rise time' in accordance with standards referred to in Article 1 (2). 'Freezing capacity' in kg/24 h in accordance with standards referred to in Article 1 (2). 'Climate class' in accordance with the standards referred to in Article 1 (2). Where appliance is of 'temperate' climate class this may be omitted. 'Noise', where applicable, measured in accordance with Directive 86/594/EEC.
Where an appliance contains compartments other than a single fresh food compartment and a single frozen food compartment, extra lines may be added at 7, 8, 9, 10, 11, 12 and 13 to include the information in respect of these compartments. In this case the naming and order of listing of the compartments shall be consistent. Where the design temperature of a compartment does not conform to the star rating system, or the standard fresh food compartment temperature (5 C), this design temperature shall be given. The information contained in the label may be given in the form of a copy of the label, either in colour or in black and white. In this case the further information given only in the fiche must still be included. Note: The equivalent terms in other languages to those described above are given in Annex VI. ANNEX III MAIL ORDER AND OTHER DISTANCE SELLING Mail order catalogues and other printed communications referred to by Article 2 (5) of this Directive shall contain the following information, given in the order specified: 1. Energy efficiency class (Annex II, point 4) 2. Energy consumption (Annex II, point 6) 3. Net volume of fresh food compartment (Annex II, point 7) 4. Net volume of frozen food compartment (Annex II, point 8) 5. Star rating (Annex II, point 9) 6. Noise (Annex II, point 14) Where other information contained in the product information fiche is provided, it shall be in the form defined in Annex II and shall be included in the above list in the order specified for the fiche. The size and font, in which all the information referred to above is printed, shall be legible. Note: The equivalent terms in other languages to those described above are given in Annex VI. ANNEX IV CATEGORIES The appliances covered by this Directive shall be divided into the following 'categories': 1. Household refrigerators, without low temperature compartments. 2. Household refrigerator/chillers, with compartments at 5 C and/or 10 C. 3. Household refrigerators, with no-star low temperature compartments. 4. Household refrigerators, with low temperature compartments *. 5. Household refrigerators, with low temperature compartments **. 6. Household refrigerators, with low temperature compartments ***.
p. 154
7. Household refrigerator/freezers, with low temperature compartments *(***). 8. Household food freezers, upright. 9. Household food freezers, chest. 10. Household refrigerators and freezers with more than two doors, or other appliances not covered above. ANNEX V ENERGY EFFICIENCY CLASS The energy efficiency class of an appliance shall be determined in accordance with the following Table 1: (not more valid, see Annex 1.1) Where: 'energy efficiency index' (expressed as a percentage) = annual energy consumption of appliance (1) / standard annual energy consumption of appliance 'standard annual energy consumption of appliance' (expressed in kWh/year) = M adjusted net volume + N and adjusted net volume (expressed in litres) = net volume of fresh food compartment + ` net volume of frozen food compartment. The values of M, N and ` are taken from Table 2. (not more valid) (1) In accordance with Annex I, note V. ANNEXE VI EMPLACEMENT TABLE (not more valid)
p. 155
Article 1 Directive 94/2/EC is amended as follows: 1. In Article 1, paragraphs 2, 3 and 4 are replaced by the following: 2. The information required by this Directive shall be obtained by measurements made in accordance with harmonised standards adopted by the European Standardisation Bodies (CEN, CENELEC, ETSI) under mandate from the Commission in accordance with Directive 98/34/EC of the European Parliament and of the Council (*), the reference numbers of which have been published in the Official Journal of the European Union and for which Member States have published the reference numbers of the national standards transposing those harmonised standards. 3. The provisions in Annexes I, II and III requiring the giving of information relating to noise shall apply only where that information is required by Member States under Article 3 of Directive 86/594/EEC. This information shall be measured in accordance with that Directive. 4. In this Directive the definitions set out in Article 1(4) of Directive 92/75/EEC shall apply. 2. Article 2 is amended as follows: (a) In paragraph 1, the following subparagraph is added: Where the information relating to a particular model combination has been obtained by calculation on the basis of design, and/or extrapolation from other combinations, the documentation should include details of such calculations and/or extrapolations, and of tests undertaken to verify the accuracy of the calculations undertaken (details of mathematical model for calculating performance and of measurements taken to verify this model). (b) Paragraph 5 is replaced by the following: 5. Where the appliances are offered for sale, hire or hire purchase by means of a printed or written communication, or by other means which imply that the potential customer cannot be expected to see the appliance displayed, such as a written offer, a mail order catalogue, advertisements on the Internet or on other electronic media, that communication shall include all the information specified in Annex III. 3. Annexes I, II, III, and V are amended as shown in the Annex to this Directive. 4. Annex VI is deleted. Article 2 Member States shall allow the circulation of labels, fiches and communications referred to in Article 2(5) of Directive 94/2/ EC, containing the information as revised by this Directive, no later than 1 July 2004. They shall ensure that all labels, fiches and communications referred to in Article 2(5) of Directive 94/2/EC comply with the revised models, no later than 31 December 2004. Article 3 Member States shall adopt and publish the provisions to comply with this Directive no later than 30 June 2004. They shall immediately inform the Commission thereof. When Member States adopt those provisions, they shall contain a reference to this Directive or be accompanied by such a reference on the occasion of their official publication. Member States shall determine how such reference is to be made. Article 4 This Directive shall enter into force on the 20th day following that of its publication in the Official Journal of the European Union.
p. 156
Article 5 This Directive is addressed to the Member States. Done at Brussels, 3 July 2003. For the Commission Loyola DE PALACIO Vice-President _____________________________ (*) OJ L 204, 21.7.1998, p. 37; (1) OJ L 297, 13.10.1992, p. 16; (2) OJ L 45, 17.2.1994, p. 1; (3) OJ L 236, 18.9.1996, p. 36.
ANNEX (1) Annex I is amended as follows: (a) under the heading Notes on label, the final sentence NB: the equivalent terms in other languages to those described above are given in Annex VI, is deleted; (b) under the heading Printing: (i) the following text is inserted after the illustration: The indicator letter for A+ and A++ appliances shall be in accordance with the following illustrations, and shall be placed in the same position as the A indicator for A class appliances
(ii) the final text, commencing with the words: Complete printing information is contained in a refrigerator/freezer label design guide is deleted. (2) Annex II is amended as follows: (a) point 4 is replaced by the following: 4. The energy efficiency class of the model as defined in Annex V, expressed as Energy efficiency class on a scale of A++ (most efficient) to G (least efficient). Where this information is provided in a table this may be expressed by other means provided it is clear that the scale is from A++ (most efficient) to G (least efficient). (b) point 8 is replaced by the following: 8. Net storage volume of frozen food storage compartment, and of chill compartment when available, in accordance with standards referred to in Article 1(2) omit for classes 1, 2 and 3. For class 3 appliances the net volume of the ice box. (c) the following point 15 is added: 15. If the model is produced in order to be built-in, this should be stated. (d) the final Note is deleted. (3) Annex III is amended as follows: The final Note is deleted. (4) In Annex V the following text is inserted after the title ENERGY EFFICIENCY CLASS: PART 1: Definitions of Classes A+ and A++ An appliance shall be classified as A+ or A++, where the energy efficiency index alpha (I) is within the ranges specified in Table 1.
p. 157
Table 1 Energy efficiency index (I) 30 > I 42 > I 30 I 42 In Table 1 Energy efficiency class A++ A+ A to G (see below)
where: AC = annual energy consumption of appliance (in accordance with Annex I, note V) SC = standard annual energy consumption of appliance SC is calculated as
where: Vc is the net volume (in litres) of the compartment (in accordance with standards referred to in Article 1(2)). Tc is the design temperature (in C) of the compartment. The values of M and N are given in Table 2 and the values of FF, CC, BI and CH are given in Table 3 Table 2 Type of appliance Temperature of coldest compartment M N 1 Larger Fridge > 6 C 0,233 245 2 Refrigerator/chiller > 6 C 0,233 245 3 Refrigerator no star > 6 C 0,233 245 4 Refrigerator * 6 C * 0,643 191 5 Refrigerator ** 12 C ** 0,450 245 6 Refrigerator ***/ 18 C ***/*(***) 0,777 303 7 Fridge-freezer *(***) 18 C ***/*(***) 0,777 303 8 Upright freezer 18 C *(***) 0,539 315 9 Chest freezer 18 C *(***) 0,472 286 10 Multi-door or other appliance (1) (1) (1) For these appliances, the temperature and star rating of the compartment with the lowest temperature will determine the values of M and N. Appliances with 18 C *(***) compartments shall be considered as fridge-freezers *(***). Table 3 Correction factor FF (frost-free) Value Condition 1,2 For frost-free (ventilated) frozen food compartments 1 Otherwise CC (climate class) 1,2 For tropical appliances 1,1 For subtropical appliances 1 Otherwise BI (built-in) 1,2 For built-in appliances (1) of under 58 cm in width. 1 Otherwise CH (chill compartment) 50 KWh/y For appliances with a chill compartment of at least 15 litres 0 Otherwise (1) An appliance is built-in only if it is designed exclusively for installation within a kitchen cavity with a need of furniture finishing, and tested as such. If an appliance is not A+ or A++, it shall be classified in accordance with Part 2.