Power System Analysis Lab Manual
Power System Analysis Lab Manual
SUBMITTEDTO: ENGR.M.JUNAID
DEPARTMENT OF ELECTRICAL ENGINEERING (A CONSTITUENT COLLEGE: RACHNA COLLEGE OF ENGINEERING & TECHNOLOGY GUJRANWALA) UNIVERSITY OF ENGINEERING & TECHNOLOGY LAHORE, PAKISTAN
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
01
To plot the daily load curve for the given data using MATLAB
02
03
Evaluate the value of voltages for a 4-BUS system using node equations in MATLAB
04
Modeling and Load flow analysis of RCET power distribution network using ETAP
05
06
To study the Concept of Modifications of an Existing BusImpedance Matrix & Implementing in MATLAB
07
ASADNAEEM 2006RCETEE22
Application of Gauss-Siedal and Newton-Raphson method for load flow studies on a three bus system using MATLAB
POWERSYSTEMANALYSISLABMANUAL
08
Harmonic Load Modeling using built-in and user defined models of ETAP Impact of personal computer load on power distribution network of RCET Flow of triplen harmonics (zero-sequence harmonics) during 5 different schemes of connection for a 3-phase transformer with presence of large non-linear load using ETAP Three phase short circuit analysis (3-phase faults-device duty) for a given power system using ETAP Three phase short circuit analysis (3-phase faults-30 cycle network) for a given power system using ETAP Three phase short circuit analysis (LG, LL, LLG, & 3-Phase Faults - Cycle) for a given power system using ETAP Three phase short circuit analysis (LG, LL, LLG, & 3-Phase Faults - 1.5 to 4 Cycle) for a given power system using ETAP Three phase short circuit analysis (LG, LL, LLG, & 3-Phase Faults - 30 Cycle) for a given power system using ETAP
09
10
11
12
13
14
15
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
EXPERIMENT#01
Toplotthedailyloadcurveforthegivendatausing MATLAB Givendata: Intervalfrom 12A.M 2 6 9 12P.M 2 4 6 8 10 11 Requirements: 1. 2. 3. 4. Findaveragevalueofload Findpeakvalueofload Findtheloadfactor Plottheloadcurve To 2A.M 6 9 12 2P.M 4 6 8 10 11 12A.M LoadMW 6 5 10 15 12 14 16 18 16 12 6
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
Theory
Loads:
Loads of power systems are divided into three main categories that are given below. 1. Industrial Loads 2. Commercial Loads 3. Residential Loads Very large industrial loads are served through the transmission lines. Large industrial loads are served directly from the sub-transmission level. And small industrial loads are served directly from the primary distribution network. The industrial loads are composite loads and induction motors from a high proportion of these loads. These composite loads are functions of voltage and frequency and form a major part of the system load. Commercial and residential load consist largely of lighting, heating and cooling. These loads are independent of frequency and consume negligibly small reactive power. The real power of loads is expressed in terms of kilowatts or megawatts. The magnitude of load varies throughout the day and power must be available to the consumer on demand. The daily load curve of a utility is a composite of demands made by various classes of users. The greatest value of load during a twenty four hours is called the peak or maximum demand. Smaller peaking generators may be commissioned to meet the peak load that occurs for only a few hours. In order to asses the usefulness of the generating plant the load factor is defined. The load factor is the ratio of average load over a designated period of time to the peak load occurring in that period. Load factor may be given for a day, a month or an year. Yearly or annual load factor is the most useful since a year represents a full cycle of time. The daily load factor is
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
Daily load factor = average load / peak load Multiplying the numerator and denominator by a time period of 24 hr we have Daily load factor= average load*24 hr / (peak load*24 hrs) = energy consumed during 24 hr/ (peak load*24 hr) The annual load factor is Annual load factor = total annual energy / (peak load*8760 hr) Todays typical system load factors are in range of 55-70%. In Pakistan WAPDA standard for urban areas load factor is 60% and that of rural areas is 65%.
Matlab code:
data=[0 2 6; 2 6 5; 6 9 10; 9 12 15; 12 14 12; 14 16 14; 16 18 16; 18 20 18; 20 22 16; 22 23 12;
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
23 24 6]; p=data(:,3); Dt=data(:,2)-data(:,1); w=p'*Dt; pavg=w/sum(Dt) peak=max(p) LF=pavg/peak*100 L=length(data); tt = [data(:,1) data(:,2)]; t = sort(reshape(tt, 1, 2*L)); for n = 1:L pp(2*n-1)=p(n); pp(2*n)=p(n); end plot(t,pp) xlabel('TIME,Hr'),ylabel('P,MW')
Matlab results:
pavg=11.5417 peak=18 LF=64.1204
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
18
16
14
12 P,MW
10
4 0
10 TIME,Hr
15
20
25
COMMENTS:
In this experiment we learn how to find the daily load curve for any power system using MATLAB. Load curve is very important as we can achieve very important information from it like: Peak load Average load Load factor These quantities are very helpful for understanding any power system.
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
EXPERIMENT#02
IntroductiontobasicsofElectricalTransientsAnalyzer Program(ETAP) What is ETAP?
ETAP is the most comprehensive analysis platform for the design, simulation, operation, control, optimization, and automation of generation, transmission, distribution, and industrial power systems.
Project Toolbar
TheProjectToolbarcontainsiconsthatallowyoutoperformshortcutsofmany commonlyusedfunctionsinPowerStation. Create Open Save Print Cut Createanewprojectfile Openanexistingprojectfile Savetheprojectfile PrinttheonelinediagramorU/Gracewaysystem CuttheselectedelementsfromtheonelinediagramorU/Graceway systemtotheDumpster CopytheselectedelementsfromtheonelinediagramorU/Graceway systemtotheDumpster PasteelementsfromaDumpsterCelltotheonelinediagramorU/G system MagnifytheonelinediagramorU/Gracewaysystem ReducetheonelinediagramorU/Gracewaysystem Resizetheonelinediagramtofitthewindow Checkthesystemcontinuityfornonenergizedelements
Copy
ZoomtoFitPage CheckContinuity
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
PowerCalculator
ActivatePowerStationCalculatorthatrelatesMW,MVAR,MVA, kV,Amp,andPFtogetherwitheitherkVAorMVAunits
Help
PointtoaspecificareatolearnmoreaboutPowerStation
Mode Toolbar
ETAPoffersasuiteoffullyintegratedsoftwaresolutionsincludingarcflash,loadflow, shortcircuit,transientstability,relaycoordination,cableampacity,optimalpowerflow, andmore.Itsmodularfunctionalitycanbecustomizedtofittheneedsofanycompany, fromsmalltolargepowersystems.
EditMode
Editmodeenablesyoutobuildyouronelinediagram,changesystemconnections,edit engineeringproperties,saveyourproject,andgenerateschedulereportsinCrystal Reportsformats.TheEditToolbarsforbothACandDCelementswillbedisplayedtothe rightofthescreenwhenthismodeisactive.Thismodeprovidesawidevarietyoftasks including:
ASADNAEEM 2006RCETEE22
Drag&DropElements ConnectElements ChangeIDs Cut,Copy,&PasteElements MovefromDumpster InsertOLEObjects Cut,Copy&OLEObjects MergePowerStationProject Hide/ShowGroupsofProtectiveDevices RotateElements SizeElements ChangeSymbols EditProperties RunScheduleReportManager
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
Example implementation:
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
EXPERIMENT#03
Evaluatethevalueofvoltagesfora4BUSsystemusing nodeequationsinMATLAB
REACTANCE DIAGRAM
In the first step, we draw the reactance diagram of the given one-line diagram as shown below:
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
SOURCE TRANSFORM
After making the reactance diagram, we apply source transformation on the given network by replacing the voltage sources with current sources Replace all the reactance by admittances using the relation: Y=1/X The resultant diagram now can be shown as:
NODE EQUATIONS
Now, using the above figure write the node equations of the system: Applying KCL at node-1: I1= (V1-0) y10 + (V1-V4) y14+ (V1-V3) y13 I1= (y10+y14+y13) V1 + 0V2 + (-y13) V3+ (-y14) V4
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
Applying KCL at node-2: I2= (V2-0) y20 + (V2-V3) y23+ (V2-V4) y24 I2= 0V1+ (y20+y23+y24) V2 + (-y23) V3+ (-y24) V4 Applying KCL at node-3: I3= (V3-0) y30 + (V3-V1) y31+ (V3-V4) y34 + (V3-V2) y32 I3= (-y31) V1+ (-y32) V2+ (y30+y31+y34) V3 + (-y34) V4 Applying KCL at node-4: 0= (V4-V1) y14+ (V4-V3) y43 + (V4-V2) y42 0= (-y14) V1+ (-y42) V2 + (-y34) V3+ (y14+y43+y42) V4 Matrix form of the node equations is:
Where:
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
CALCULATIONS
MATLAB CODE
YBUS= [0-9.80i 0 0+4.00i 0+5.00i 0 0-8.30i 0+2.50i 0+5.00i 0+4.00i 0+2.50i 0-15.30i 0+8.00i 0+5.00i; 0+5.00i; 0+8.00i; 0-18.00i];
MATLAB RESULTS
V= 1.4111 - 0.2668i 1.3831 - 0.3508i 1.4059 - 0.2824i 1.4010 - 0.2971i
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
COMMENTS:
In this experiment we learn that using the bus impedance or admittance matrix we can find the voltages and currents for all buses of a given power system. Moreover, we use MATLAB for the calculation of these quantities by just entering the bus impedance matrix and one given quantity (current or voltage) and MATLAB gives the results of very complex networks within no time.
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
EXPERIMENT#04
ModelingandLoadflowanalysisofRCETpower distributionnetworkusingETAP INTRODUCTION:
POWERSYSTEMANALYSISLABMANUAL
allows you to select from several different methods in order to achieve the best calculation efficiency and accuracy.
Report Manager
STEPS Modeling of the main network Modeling of composite networks Running of load flow analysis Complete report from ETAP load flow analyzer
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
OLD BUILDING:
NEW BUILDING:
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
HOSTEL-A,B:
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
HOSTEL-E:
Complete ETAP load flow analysis report of the given network is attached with this experiment.
COMMENTS:
In this experiment we learn how to: Model a power system in ETAP Model composite networks in a basic network Assign properties of components added Study the load flow analysis for that network
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
EXPERIMENT#05
Buseliminationofa4BUSsystemusingMATLAB
REACTANCE DIAGRAM
It is given that the transformer and generator at bus-3 are disconnected, so the reactance diagram now becomes:
SOURCE TRANSFORM
After making the reactance diagram, we apply source transformation on the given network by replacing the voltage sources with current sources Replace all the reactance by admittances using the relation: Y=1/X The resultant diagram now can be shown as:
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
Part1:EliminationofBus3&4
MATRIX FORM
Where:
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
MATLAB CODE
>>YBUS= [0-9.80i 0 0 0+4.00i 0+5.00i 0-8.30i 0+2.50i 0+5.00i 0+4.00i 0+2.50i 0-14.5i 0+8.00i 0+5.00i; 0+5.00i; 0+8.00i; 0-18.00i];
>>K= [0-9.80i 0; 0 0-8.30i]; >>L= [0+4.00i 0+5.00i; 0+2.50i 0+5.00i]; >>M= [0-14.5i 0+8.00i; 0+8.00i 0-18.00i]; >>LT= [0+4.00i 0+2.50i; 0+5.00i 0+5.00i]; >>N=inv (M); >>P=L*N*LT; >>Ybus=K-P
MATLAB RESULTS
Ybus = 0 - 4.8736i 0 + 4.0736i
ASADNAEEM 2006RCETEE22
0 + 4.0736i 0 - 4.8736i
POWERSYSTEMANALYSISLABMANUAL
Part-2: Elimination Bus-4
MATLAB CODE:
>>Ybus=[-9.8i 0 4i 5i 0 -8.3i 2.5i 5i 4.0i 2.5i -14.5i 8i 5i; 5i; 8i; -18i];
>>K=[-9.8i 0 4i;0 -8.3i 2.5i;4i 2.5i -14.5i]; >>L=[5i;5i;8i]; >>M=[-18i]; >>P=L'; >>T=inv(M); >>A=K-L*T*P
MATLAB RESULTS
A= 0 -11.1889i 0 - 1.3889i 0 + 1.7778i 0 - 1.3889i 0 - 9.6889i 0 + 0.2778i 0 + 1.7778i 0 + 0.2778i 0 -18.0556i
MATLAB CODE:
>>P=[-11.1889i -1.3889i;-1.3889i -9.6889i]; >>Q=[1.7778i;0.2778i];
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
MATLAB RESULTS
B= 0 -11.3639i 0 - 1.4163i
0 - 1.4163i 0 - 9.6932i
COMMENTS:
Bus impedance matrix is a very important tool for the calculation of voltages and currents at all the buses of a given network. Suppose that any fault occurs in the power system then we can get a task to modify the bus impedance matrix by eliminating the faulty node which will reduce the order of matrix by eliminating the faulty node. In this experiment we learn how to: Eliminate last two nodes together Eliminate only one last node
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
EXPERIMENT#06
TostudytheConceptofModificationsofanExistingBus ImpedanceMatrix&ImplementinginMATLAB
IMPEDANCE MATRIX
Impedance matrix is a very important tool in power system analysis. Using this matrix we can find: Voltages at all buses when currents are given Currents at all buses when voltages are given So it is very important that how to modify the bus impedance matrix when any new impedance is add into the original system. Suppose a power system with n-buses having the impedances matrix of order n*n:
There are four cases that can take place while adding a new impedance Zb in the system: Adding Adding Adding Adding Zb Zb Zb Zb from a new bus-P to reference bus from a new bus-P to an existing bus-K from an existing bus-K to reference bus between two existing buses
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
MODIFICATION CASES
CASE1:ADDINGZbFROMANEWBUSTOREFERENCEBUS
This condition is explained in the following diagram:
Clearly, Vp-0=Ib*Zb Vp=Ib*Zb Hence the modified matrix will take the form as:
MATLAB CODE
function [Z]=Case1(Zorg,Zb) Zorg=[1 2 3 4;2 5 6 7;3 6 8 9;4 7 9 10]
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
Zb=17; l=length(Zorg); for i=1:l+1 for j=1:l+1 if i<=l && j<=l Znew(i,j)=Zorg(i,j); elseif i==l+1 && j==l+1 Znew(i,j)=Zb; else Znew(i,j)=0; end end end Znew
MATLAB RESULTS
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
CASE2:ADDINGZbFROMANEWBUSPTOANEXISTINGBUSK
This condition is explained in the following diagram:
Clearly, Vp-Vk,new=Ip*Zb Vp=Vk,new+Ip*Zb Where, Vk,new=Vk,org+Ip*Zkk Vp= Vk,org+Ip(Zkk+Zb) Hence the modified matrix will take the form as:
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
MATLAB CODE:
function [Z]=CASE2(Zorg,Zb) Zorg=[1 2 3 4;2 5 6 7;3 6 8 9;4 7 9 10] Zb=5; l=length(Zorg); row =Zorg(l,:); column =Zorg(:,l); for i=1:l+1 for j=1:l+1 if i<=l && j<=l Znew(i,j)=Zorg(i,j); elseif i==l+1 for p=1:l Znew(i,p)=row(p); end elseif j==l+1 for q=1:l Znew(q,j)=column(q); end end if i==l+1 && j==l+1 Znew(i,j)=Zb+Zorg(l,l); end end end Znew
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
MATLAB RESULTS
CASE3:ADDINGZbFROMANEXISTINGBUSKTOREFERENCE BUS
This condition is explained in the following diagram:
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
Here we can apply the same case as in case-2 and then put Vp=0. This task can be achieved by eliminating the last row and column of the Znew matrix.
Now this matrix is of the order (n+1)*(n+1), we have to achieve a matrix of order n*n using formula: Zkj(new)=Zkj(org)-(Zk(n+1)Z(n+1)j/Zkk+Zb) In this case, K=n
MATLAB CODE:
function [Z]=CASE3(Zorg,Zb) Zorg=[1 2 3 4;2 5 6 7;3 6 8 9;4 7 9 10] Zb=5; l=length(Zorg); row =Zorg(l,:); column =Zorg(:,l); for i=1:l+1 for j=1:l+1
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
if i<=l && j<=l Znew(i,j)=Zorg(i,j); elseif i==l+1 for p=1:l Znew(i,p)=row(p); end elseif j==l+1 for q=1:l Znew(q,j)=column(q); end end if i==l+1 && j==l+1 Znew(i,j)=Zb+Zorg(l,l); end end end Znew for a=1:l for b=1:l K(a,b)=Znew(a,b); end
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
MATLAB RESULTS
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
CASE4:ADDINGZbBETWEENTWOEXISTINGBUSES
This condition is explained in the following diagram:
In this case, Zbb=Zb+Zjj+Zkk-2Zjk Hence the modified matrix will take the form as:
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
Here again we have to eliminate the last row and column to achieve the final matrix.
MATLAB CODE:
function [Z]=CASE4(Zorg,Zb) Zorg=[1 2 3 4;2 5 6 7;3 6 8 9;4 7 9 10] Zb=5; l=length(Zorg); R1 =Zorg(l,:); C1 =Zorg(:,l); R2 =Zorg(l-1,:); C2 =Zorg(:,l-1); for i=1:l+1 for j=1:l+1 if i<=l && j<=l Znew(i,j)=Zorg(i,j);
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
elseif i==l+1 for p=1:l Znew(i,p)=R1(p)-R2(p); End elseif j==l+1 for q=1:l Znew(q,j)=C1(q)-C2(q); End End if i==l+1 && j==l+1 Znew(i,j)=Zb+Zorg(l,l)+Zorg(l-1,l-1)-(2*Zorg(l,l-1)); end end end Znew for a=1:l for b=1:l K(a,b)=Znew(a,b); end end for a=1:l
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
MATLAB RESULTS
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
COMMENTS:
Bus impedance matrix is a very important tool for the calculation of voltages and currents at all the buses of a given network. Suppose that any improvement occurs in the power system then we can get a task to modify the bus impedance matrix by adding the new impedance in the system. The new impedance can be added in four different conditions: Addition of new bus Addition of new bus Addition of new reference bus Addition of new impedance from a new bus to reference impedance from a new bus to existing impedance from an existing bus to impedance between two existing buses
In this experiment we learn how to modify the bus impedance matrix for all four cases using MATLAB.
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
EXPERIMENT#07
ApplicationofGaussSiedalandNewtonRaphsonmethodforload flowstudiesonathreebussystemusingMATLAB(Implimentation ofexample#6.7,6.8&6.10fromPOWERSYSTEMANALYSISbyHadi Saadat)
EXAMPLE 6.7
Given figure shows the one line diagram of a simple three bus system with generation at bus-1. The magnitude of voltage at bus-1 is adjusted to 1.05 per unit. The scheduled loads at buses-2 and 3 are as marked on the diagram. Line impedances are marked in per unit on a 100-MVA base and the line charging susceptances are neglected.
(A) Using the Gauss-Siedal method, determine the phasor values of the voltage at the load buses 2 and 3 (P&Q buses) accurate to four decimal places (B) Find the slack bus real and reactive power (C) Determine the line flows and line losses. Construct a power flow diagram showing the direction of line flow
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
SOLUTION
Line impedances are converted to admittances:
At the P-Q buses, the complex loads expressed in per unit are: S2sch=-(256.6+j110.2)/100= -2.566-j1.102 pu S3sch=-(138.6+j45.2)/100= -1.386-j0.452 pu Starting from an initial estimate of V2(0)=1.0+j0.0 and V3(0)=1.0+j0.0
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
GAUSS-SIEDEL FARMULA
MATLAB CODE
y12=10-j*20; y13=10-j*30; y23=16-j*32; V1=1.05+j*0; %CODE FOR PART-A iter=0; s2=-2.566-j*1.102; s3=-1.386-j*0.452; V2=1+j*0.0; V3=1+j*0.0; for I=1:10; iter=iter+1; V2=(conj(s2)/conj(V2)+y12*V1+y23*V3)/(y12+y23); V3=(conj(s3)/conj(V3)+y13*V1+y23*V2)/(y13+y23); end V2 V3
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
%CODE FOR PART-B Pslack=conj(V1)*[V1*(y12+y13)-(y12*V2+y13*V3)] %CODE FOR PART-C I12=y12*(V1-V2) I21=-I12 I13=y13*(V1-V3) I31=-I13 I23=y23*(V2-V3) I32=-I23 s12=V1*conj(I12) s21=V2*conj(I21) s13=V1*conj(I13) s31=V3*conj(I31) s23=V2*conj(I23) s32=V3*conj(I32) SL12=s12+s21 SL13=s13+s31 SL23=s23+s32
MATLAB RESULTS
PART-A RESULTS
V2 = 0.9800 - 0.0600i V3 = 1.0000 - 0.0500i PART-B RESULTS SLACK-BUS POWER Pslack = 4.0949 - 1.8900i
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
LINE LOSSES SL12 = SL13 = SL23 = 0.0850 + 0.1700i 0.0500 + 0.1500i 0.0080 + 0.0160i
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
EXAMPLE 6.8
Given figure shows the one line diagram of a simple three bus system with generators at buses-1 and 3. The magnitude of voltage at bus-1 is adjusted to 1.05pu. voltage magnitude at bus-3 is fixed at 1.04 pu with a real power generation of 200MW. A load consisting of 400MW and 250MVAR is taken from bus-2. Line impedances are marked in per unit on a 100MVA base, and the line charging susceptances are neglected. Obtain the power flow solution by the Gauss-Siedal method including line flows and line losses.
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
FARMULAS
S3=conj(V3)*(y33*V3-y13*V1-y23*V2) Q3=-imag(conj(V3)*(y33*V3-y13*V1-y23*V2))
MATLAB CODE
y12=10-j*20; y13=10-j*30; y23=16-j*32; y33=y13+y23; V1=1.05+j*0; format long iter=0; s2=-4.0-j*2.5; p3=2; V2=1+j*0.0; Vm3=1.04; V3=1.04+j*0; for I=1:10; iter=iter+1; E2=V2; E3=V3; V2=(conj(s2)/conj(V2)+y12*V1+y23*V3)/(y12+y23) DV2=V2-E2; Q3=-imag(conj(V3)*(y33*V3-y13*V1-y23*V2)) s3=p3+j*Q3; Vc3=(conj(s3)/conj(V3)+y13*V1+y23*V2)/(y13+y23); Vi3=imag(Vc3); Vr3=sqrt(Vm3^2-Vi3^2);
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
V3=Vr3+j*Vi3 DV3=V3-E3; end V2 V3 Q3 format short I12=y12*(V1-V2); I21=-I12; I13=y13*(V1-V3); I31=-I13; I23=y23*(V2-V3); I32=-I23; s12=V1*conj(I12); s21=V2*conj(I21); s13=V1*conj(I13); s31=V3*conj(I31); s23=V2*conj(I23); s32=V3*conj(I32); I1221=[I12,I21]; I1331=[I13,I31]; I2332=[I23,I32]; SL12=s12+s21 SL13=s13+s31 SL23=s23+s32 S1=(s12+s13) S2=(s23+s21) S3=(s31+s32) S12=s12 S21=s21 S13=s13 S31=s31 S23=s23 S32=s32
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
POWERSYSTEMANALYSISLABMANUAL
V3 = 1.039961668920058 - 0.008929007616053i 6THITERATION V2 = 0.970612037114234 - 0.045646940090561i Q3 = 1.459469889628077 V3 = 1.039961037734205 - 0.009002221658867i 7THITERATION V2 = 0.970607253520093 - 0.045685276728252i Q3 = 1.460818201396914 V3 = 1.039960775170297 - 0.009032502820155i 8THITERATION V2 = 0.970605276281561 - 0.045701131870879i Q3 = 1.461375872168914 V3 = 1.039960666313617 - 0.009045027392915i 9THITERATION V2 = 0.970604458527297 - 0.045707689707255i Q3 = 1.461606535170454 V3 = 1.039960621244008 - 0.009050207830587i 10THITERATION V2 = 0.970604120282796 - 0.045710402176455i Q3 = 1.461701943643423 V3 = 1.039960602594413 - 0.009052350604469i
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
FINALRESULTS:
V2 = 0.970604120282796 - 0.045710402176455i V3 = 1.039960602594413 - 0.009052350604469i Q3 = 1.461701943643423 SL12 = 0.0839 + 0.1679i SL13 = 0.0018 + 0.0055i SL23 = 0.0985 + 0.1969i S1 = 2.1841 + 1.4085i S2 = -3.9999 - 2.5000i S3 = 2.0000 + 1.4618i S12 = 1.7936 + 1.1874i S21 = -1.7096 - 1.0195i S13 = 0.3906 + 0.2212i S31 = -0.3887 - 0.2157i S23 = -2.2903 - 1.4805i S32 = 2.3888 + 1.6775i
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
EXAMPLE 6.10
Given figure shows the one line diagram of a simple three bus system with generators at buses-1 and 3. The magnitude of voltage at bus-1 is adjusted to 1.05pu. voltage magnitude at bus-3 is fixed at 1.04 pu with a real power generation of 200MW. A load consisting of 400MW and 250MVAR is taken from bus-2. Line impedances are marked in per unit on a 100MVA base, and the line charging susceptances are neglected. Obtain the power flow solution by the Newton-Raphson method including line flows and line losses.
-10+j20
-10+j30
POWERSYSTEMANALYSISLABMANUAL
-10+j20 -10+j30
26-j52 -16+j32
-16+j32 26-j62];
FARMULAS
P1=V1^2*Y11*cos(11)+V1*V2*Y12*cos(12-d1+d2)+... V1*V3*Y13*cos(13-d1+d3) Q1=-V1^2*Y11*sin(11)-V1*V2*Y12*sin(12-d1+d2)-... V1*V3*Y13*sin(13-d1+d3) Q3=-V3*V1*Y31*sin(31)-d3+d1)-V3*V2*Y32*... sin(32-d3+d2)-V3^2*Y33*sin33
MATLAB CODE
V=[1.05;1.0;1.04]; d=[0;0;0]; Ps=[-4;2.0]; Qs=-2.5; YB=[20-j*50 -10+j*20 -10+j*30 -10+j*20 26-j*52 -16+j*32 -10+j*30 -16+j*32 26-j*62]; Y=abs(YB); t=angle(YB); iter=0; pwracur=0.00025; %power accuracy DC=10; %set the maximun power residue to a high value while max(abs(DC))>pwracur iter=iter+1 P=[V(2)*V(1)*Y(2,1)*cos(t(2,1)d(2)+d(1))+V(2)^2*Y(2,2)*cos(t(2,2))+... V(2)*V(3)*Y(2,3)*cos(t(2,3)-d(2)+d(3)); V(3)*V(1)*Y(3,1)*cos(t(3,1)d(3)+d(1))+V(3)^2*Y(3,3)*cos(t(3,3))+... V(3)*V(2)*Y(3,2)*cos(t(3,2)-d(3)+d(2))];
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
Q=-V(2)*V(1)*Y(2,1)*sin(t(2,1)-d(2)+d(1))V(2)^2*Y(2,2)*sin(t(2,2))-... V(2)*V(3)*Y(2,3)*sin(t(2,3)-d(2)+d(3)); J(1,1)=V(2)*V(1)*Y(2,1)*sin(t(2,1)-d(2)+d(1))+... V(2)*V(3)*Y(2,3)*sin(t(2,3)-d(2)+d(3)); J(1,2)=-V(2)*V(3)*Y(2,3)*sin(t(2,3)-d(2)+d(3)); J(1,3)=V(1)*Y(2,1)*cos(t(2,1)d(2)+d(1))+2*V(2)*Y(2,2)*cos(t(2,2))+... V(3)*Y(2,3)*cos(t(2,3)-d(2)+d(3)); J(2,1)=-V(3)*V(2)*Y(3,2)*sin(t(3,2)-d(3)+d(2)); J(2,2)=V(3)*V(1)*Y(3,1)*sin(t(3,1)-d(3)+d(1))+... V(3)*V(2)*Y(3,2)*sin(t(3,2)-d(3)+d(2)); J(2,3)=V(3)*Y(2,3)*cos(t(3,2)-d(3)+d(2)); J(3,1)=V(2)*V(1)*Y(2,1)*cos(t(2,1)-d(2)+d(1))+... V(2)*V(3)*Y(2,3)*cos(t(2,3)-d(2)+d(3)); J(3,2)=-V(2)*V(3)*Y(2,3)*cos(t(2,3)-d(2)+d(3)); J(3,3)=-V(1)*Y(2,1)*sin(t(2,1)-d(2)+d(1))-2*V(2)*Y(2,2) *sin(t(2,2)) ... V(3)*Y(2,3)*sin(t(2,3)-d(2)+d(3)); DP=Ps-P; DQ=Qs-Q; DC=[DP;DQ] J DX=J\DC d(2)=d(2)+DX(1); d(3)=d(3)+DX(2); V(2)=V(2)+DX(3); V, d, delta=180/pi*d; end P1=V(1)^2*Y(1,1)*cos(t(1,1))+V(1)*V(2)*Y(1,2)*cos(t(1,2)d(1)+d(2))+... V(1)*V(3)*Y(1,3)*cos(t(1,3)-d(1)+d(3)) Q1=-V(1)^2*Y(1,1)*sin(t(1,1))-V(1)*V(2)*Y(1,2)*sin(t(1,2)d(1)+d(2))-... V(1)*V(3)*Y(1,3)*sin(t(1,3)-d(1)+d(3)) Q3=-V(3)*V(1)*Y(3,1)*sin(t(3,1)-d(3)+d(1))-V(3)*V(2)*Y(3,2)*... sin(t(3,2)-d(3)+d(2))-V(3)^2*Y(3,3)*sin(t(3,3))
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
MATLAB RESULTS
1STITERATION DC = -2.8600 1.4384 -0.2200 J= 54.2800 -33.2800 -33.2800 -27.1400 DX = -0.0453 -0.0077 -0.0265 V= 1.0500 0.9735 1.0400 d= 0 24.8600
-0.0453 -0.0077
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
2NDITERATION DC = -0.0992 0.0217 -0.0509 J= 51.7247 -31.7656 -32.9816 -28.5386 DX = -0.0018 -0.0010 -0.0018 V= 1.0500 0.9717 1.0400 d= 0 -0.0471 -0.0087 21.3026
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
3RDITERATION DC = 1.0e-003 * -0.2166 0.0382 -0.1430 J= 51.5967 -31.6939 -32.9339 -28.5482 DX = 1.0e-005 * -0.3856 -0.2386 -0.4412 V= 1.0500 0.9717 1.0400 d= 0 21.1474
-0.0471 -0.0087
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
COMMENTS:
Power system calculations are mostly very complex for large power systems. To analyze such power systems, there are two very important iterative methods: Gauss Siedel Method Newton Raphson method In this experiment we learn how to apply these two methods using MATLAB. Gauss-Seidel iteration has two advantages:
Errors do not accumulate during the calculation. If the procedure converges, it approaches the correct answer without rounding errors such as can occur during inversion of large matrices. The method can be used for nonlinear sets of equations.
While Newton Raphson method is readily applied to nonlinear equations, and can use finite-difference estimates of the derivatives to evaluate the gradients.
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
EXPERIMENT#08
HarmonicLoadModelingusingbuiltinanduserdefined modelsofETAP
HARMONIC ANALYSIS
Becauseofthewideandeverincreasingapplicationsofpower electronicdevices,suchasvariablespeeddrives,uninterruptible powersupplies(UPS),staticpowerconverters,etc.,powersystem voltageandcurrentqualityhasbeenseverelyaffectedinsome areas.Intheseareascomponentsotherthanthatoffundamental frequencycanbefoundtoexistinthedistortedvoltageand currentwaveforms.Thesecomponentsusuallyaretheinteger multipliersofthefundamentalfrequency,calledharmonics.In additiontoelectronicdevices,someothernonlinearloads,or devicesincludingsaturatedtransformers,arcfurnaces, fluorescentlights,andcycloconvertersarealsoresponsibleforthe deteriorationinpowersystemquality.
HARMONIC SOURCES
Thefollowingcomponentscanbemodeledasaharmonicvoltage sourceinPowerStation: PowerGrid SynchronousGenerator Inverter Charger/Converter
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
StaticLoad
IMPORTANT DEFINITIONS
Transients
Longdurationvariationsencompassrootmeansquare(rms) deviationsatpowerfrequenciesforlongerthan1minute.
Overvoltage
Anovervoltageisanincreaseinthermsacvoltagegreaterthan 110percentatthepowerfrequencyfordurationlongerthan1
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
min.Overvoltagesareusuallytheresultsofloadswitching(e.g., switchingoffalargeloadorenergizingacapacitorbank).
Under voltage
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
Thepowerfactorofthefundamentalfrequencycomponentsof thevoltageandcurrentwaveforms
Power factor (true)
Theratioofactivepower(watts)toapparentpower(volt amperes)
Total harmonic distortion (THD)
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ROCKWELL (12-Pulse-VFD)
ROCKWELL (18-Pulse-VFD)
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ROCKWELL (6-Pulse-VFD)
TOSHIBA (PWM-ASD)
TYPICAL (LCI)
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
TYPICAL-IEEE (12-Pulse1)
TYPICAL-IEEE (12-Pulse2)
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
TYPICAL-IEEE (18-Pulse-CT)
TYPICAL-IEEE (18-Pulse-VT)
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
TYPICAL-IEEE (6-Pulse1)
TYPICAL-IEEE (6-Pulse2)
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
TYPICAL-IEEE (Fluorescent)
TYPICAL-IEEE (Large-ASD)
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
TYPICAL-IEEE (SPC)
TYPICAL-IEEE (XFMR-Magnet)
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
COMMENTS
In this experiment, we learnt: How to model a harmonic load using built-in models How to built a user-defined harmonic model How to model a harmonic load using user-defined models So, ETAP is a very powerful tool for harmonic analysis of any power distribution network.
EXPERIMENT#09
Impactofpersonalcomputerloadonpowerdistribution networkofRCET
Harmonics
Harmonicsaresinusoidalvoltagesorcurrentshavingfrequencies thatareintegermultiplesofthefrequencyatwhichthesupply systemisdesignedtooperate(termedthefundamental frequencyusually50or60Hz).
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
%THD
91.63 86.61 69.87 44.76 54.81 46.44 46.44 33.05 24.70 11.74 7.900 5.120 178.97
5th 7th 9
th
19th 23rd 25
th
29th %THD
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
POWERSYSTEMANALYSISLABMANUAL
BUS-5:
BUS-11:
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
BUS-27:
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
BUS-33:
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
POWERSYSTEMANALYSISLABMANUAL
CABLE-2:
CABLE-7:
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
CABLE-11:
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
CABLE-18:
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
COMMENTS
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
In this experiment, we learnt: How to apply harmonic analysis to a power distribution network How to perform load flow analysis on a power distribution network How to perform harmonic analysis on a power distribution network How to get harmonic spectra at required locations
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
EXPERIMENT#10
Flowoftriplenharmonics(zerosequenceharmonics) during5differentschemesofconnectionfora3phase transformerwithpresenceoflargenonlinearloadusing ETAP
Harmonic No.
3rd
ASADNAEEM 2006RCETEE22
%THD
91.63
POWERSYSTEMANALYSISLABMANUAL
86.61 69.87 44.76 54.81 46.44 46.44 33.05 24.70 11.74 7.900 5.120 178.97
15th 17th 19
th
23rd 25th 29
th
%THD
SECONDARY SIDE
Y-Ungrounded Y-Grounded Delta Delta Delta
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
OBSERVATIONS:
Harmonic source is connected on the LT side of transformer, so the triplen harmonics are blocked due to ungrounded Yconnection. The magnitude of remaining harmonic components is reduced on the HT side of transformer.
CASE-2:
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
OBSERVATIONS:
Harmonic source is connected on the LT side of transformer, so the triplen harmonics are not blocked due to grounded Yconnection. The triplen harmonics are also present on the HT side of transformer as that is also Y-grounded.
CASE-3:
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
OBSERVATIONS:
Harmonic source is connected on the LT side of transformer, so the triplen harmonics are blocked due to deltaconnection. The triplen harmonics are also blocked on the HT side of transformer as there are no triplen harmonics on secondary side of transformer.
CASE-4:
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
OBSERVATIONS:
Harmonic source is connected on the LT side of transformer, so the triplen harmonics are blocked due to deltaconnection. The triplen harmonics are also blocked on the HT side of transformer as there are no triplen harmonics on secondary side of transformer.
CASE-5:
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
OBSERVATIONS:
Harmonic source is connected on the LT side of transformer, so the triplen harmonics are blocked due to deltaconnection. The triplen harmonics are also blocked on the HT side of transformer as there are no triplen harmonics on secondary side of transformer. Moreover, primary side is also delta-connected.
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
EXPERIMENT#11
Threephaseshortcircuitanalysis(3phasefaultsdevice duty)foragivenpowersystemusingETAP
Short-Circuit Toolbar
This toolbar is active when you are in Short-Circuit mode and the standard is set to ANSI in the Short-Circuit Study Case Editor.
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
POWERSYSTEMANALYSISLABMANUAL
Generators and motors are modeled by their positive sequence sub-transient reactance.
FAULTY POINT
BUS-15 There is a short circuit fault on bus-15.
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
COMMENTS:
In this experiment, we use three phase fault-device duty analysis to analyze the effect of fault on the system. Following results are obtained in this experiment: At bus-15: Current Power flow Before fault 568A 345KW After fault 4.8KA 3.6KW
We observe that the current flowing through bus-15 is increased up to many times as compared to the current before fault. We observe that the power flowing through bus-15 is decreased up to many times as compared to the power before fault due to the short circuit at bus-15 as the load connected to that bus is now shorted and no power is flowing into that load.
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
EXPERIMENT#12
Threephaseshortcircuitanalysis(3phasefaults30cycle network)foragivenpowersystemusingETAP
FAULTY POINT
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
COMMENTS:
In this experiment, we use three phase fault-device duty analysis to analyze the effect of fault on the system. Following results are obtained in this experiment: At bus-15: Current Power flow
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
We observe that the current flowing through bus-15 is increased up to many times as compared to the current before fault. We observe that the power flowing through bus-15 is decreased up to many times as compared to the power before fault due to the short circuit at bus-15 as the load connected to that bus is now shorted and no power is flowing into that load.
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
EXPERIMENT#13
Threephaseshortcircuitanalysis(LG,LL,LLG,&3Phase FaultsCycle)foragivenpowersystemusingETAP
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
FAULTY POINT
BUS-15 There is a short circuit fault on bus-15.
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
COMMENTS:
In this experiment, we use three phase fault-device duty analysis to analyze the effect of fault on the system. Following results are obtained in this experiment:
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
At bus-15: Current Power flow Before fault 568A 345KW After fault 6.2KA 5.1KW
We observe that the current flowing through bus-15 is increased up to many times as compared to the current before fault. We observe that the power flowing through bus-15 is decreased up to many times as compared to the power before fault due to the short circuit at bus-15 as the load connected to that bus is now shorted and no power is flowing into that load.
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
EXPERIMENT#14
Threephaseshortcircuitanalysis(LG,LL,LLG,&3Phase Faults1.5to4Cycle)foragivenpowersystemusing ETAP
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
FAULTY POINT
BUS-15 There is a short circuit fault on bus-15.
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
COMMENTS:
In this experiment, we use three phase fault-device duty analysis to analyze the effect of fault on the system. Following results are obtained in this experiment:
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
At bus-15: Current Power flow Before fault 568A 345KW After fault 5.7KA 5KW
We observe that the current flowing through bus-15 is increased up to many times as compared to the current before fault. We observe that the power flowing through bus-15 is decreased up to many times as compared to the power before fault due to the short circuit at bus-15 as the load connected to that bus is now shorted and no power is flowing into that load.
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
EXPERIMENT#15
Threephaseshortcircuitanalysis(LG,LL,LLG,&3Phase Faults30Cycle)foragivenpowersystemusingETAP
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
FAULTY POINT
BUS-15 There is a short circuit fault on bus-15.
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
COMMENTS:
In this experiment, we use three phase fault-device duty analysis to analyze the effect of fault on the system. Following results are obtained in this experiment:
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
At bus-15: Current Power flow Before fault 568A 345KW After fault 4.8KA 4.8KW
We observe that the current flowing through bus-15 is increased up to many times as compared to the current before fault. We observe that the power flowing through bus-15 is decreased up to many times as compared to the power before fault due to the short circuit at bus-15 as the load connected to that bus is now shorted and no power is flowing into that load.
ASADNAEEM 2006RCETEE22
POWERSYSTEMANALYSISLABMANUAL
3phasefaults deviceduty 3phasefaults30 cyclenetwork LG,LL,LLG,&3 PhaseFaults Cycle LG,LL,LLG,&3 PhaseFaults1.5to 4Cycle LG,LL,LLG,&3 PhaseFaults30 Cycle
4.8
5.7
4.8
4.8
ASADNAEEM 2006RCETEE22