Cat 65kva
Cat 65kva
Cat 65kva
Output Ratings
Generating Set Model 380-415V,50Hz Prime* 60.0 kVA 48.0 kW 480V, 60 Hz 68.8 kVA 55.0 kW * Refer to ratings definitions on page 4. Ratings at 0.8 power factor. Standby* 65.0 kVA 52.0 kW 75.0 kVA 60.0 kW
Technical Data
Engine Make & Model: Alternator Model: Base Frame Type: Circuit Breaker Type: Frequency: Engine Speed: RPM Fuel Tank Capacity: litres (US gal) Fuel Consumption, Prime: l/hr (US gal/hr) Fuel Consumption, Standby : l/hr (US gal/hr) 13.8 (3.6) 15.1 (4.0) Perkins 1103A-33TG2 LL2014H Heavy Duty Fabricated Steel 3 Pole MCB / 3 Pole MCCB 50 Hz 1500 175 (46.2) 15.9 (4.2) 17.4 (4.6) 60 Hz 1800
Lubrication system
Oil Filter Type: Total Oil Capacity l (US gal): Oil Pan l (US gal): Oil Type: Cooling Method: Spin-On, Full Flow 8.3 (2.2) 7.8 (2.1) AP1 CG4 15W-40 Water
Performance
Engine Speed: RPM Gross Engine Power: kW (hp) -Standby: -Prime: BMEP: kPa (psi) -Standby: -Prime: Regenerative Power: kW
50 Hz
1500 60.5 (81.0) 55.0 (74.0)
60 Hz
1800 69.6 (93.0) 63.3 (85.0)
1467.0 (212.8) 1407.0 (204.0) 1333.0 (193.4) 1279.0 (185.5) 7.0 9.0
Fuel System
Fuel Filter Type: Replaceable Element Recommended Fuel: 110% Load Prime 50 Hz 60 Hz Standby 50 Hz 60 Hz 15.1 (4.0) 17.4 (4.6) 11.1 (2.9) 13.0 (3.4) 7.7 (2.0) 9.3 (2.5) 15.1 (4.0) 17.4 (4.6) 13.8 (3.6) 15.9 (4.2) 10.3 (2.7) 12.0 (3.2) 7.3 (1.9) 8.8 (2.3) Class A2 Diesel Fuel Consumption: l/hr (US gal/hr) 100% Load 75% Load 50% Load
Air System
Air Filter Type: Combustion Air Flow: m/min (cfm) -Standby: -Prime: Max. Combustion Air Intake Restriction: kPa (in H2O) Radiator Cooling Air Flow: m/min (cfm) External Restriction to Cooling Air Flow: Pa (in H2O)
50 Hz
Replaceable Element 3.9 (138) 3.8 (134) 8.0 (32.1)
60 Hz
(based on diesel fuel with a specific gravity of 0.85 and conforming to BS2869, Class A2)
Cooling System
Cooling System Capacity: l (US gal) Water Pump Type: Heat Rejected to Water & Lube Oil: kW (Btu/min) -Standby: -Prime: Heat Radiation to Room: kW (Btu/min) -Standby: -Prime: Radiator Fan Load: kW (hp)
50 Hz
10.2 (2.7)
60 Hz
10.2 (2.7)
Exhaust System
Silencer Type: Silencer Noise Reduction Pressure Drop Across Silencer System: kPa (in Hg) Silencer Noise Reduction
50 Hz
Level 1
60 Hz
SD80 (1) 0.98 (0.289) 1.22 (0.360) 19 10.0 (3.0) 10.4 (367) 10.1 (357) 571 (1060) 557 (1035) 18 15.0 (4.4) 12.5 (441) 11.8 (417) 564 (1047) 534 (993)
Centrifugal
37.7 (2144) 35.2 (2002) 16.7 (950) 15.2 (864) 1.0 (1.3)
42.8 (2434) 41.0 (2332) 17.9 (1018) 17.0 (967) 1.7 (2.3)
Level: dB Max. Allowable Back Pressure: kPa (in. Hg) Exhaust Gas Flow: m/min (cfm) -Standby: -Prime: Exhaust Gas Temperature: C (F) m/min (cfm) -Standby: -Prime:
Cooling system designed to operate in ambient conditions up to 50C (122F). Contact your local Olympian dealer for power ratings at specific site conditions.
60 Hz
240/120V 208/120V 230/115V 440/254V 220/127V
148
139
128
164
163
109
127
119
140
300
300
300
300
300
300
300
300
300
Xd X'd X''d
Reactances shown are applicable to standby ratings. * Based on 30% voltage dip. ** With optional Permanent Magnet generator or AREP excitation.
Operating Data
Overspeed: RPM Voltage Regulation (steady state) (%): Wave Form NEMA = TIF: Wave Form IEC = THF: Total Harmonic Content LL/LN: Radio Interference: 2250 +/- 0.5 50 2.0% 4.0%
Radiant Heat: kW (Btu/min) -50 Hz: -60 Hz: 5.8 (330) 6.9 (392)
Technical Data
Voltage
kVA
415/240V 400/230V 380/220V 230/115V 220/127V 220/110V 200/115V 60.0 60.0 60.0 60.0 60.0 60.0 60.0
Prime
kW
48.0 48.0 48.0 48.0 48.0 48.0 48.0
Standby
kVA
65.0 65.0 65.0 65.0 65.0 65.0 65.0
Voltage
kW
52.0 52.0 52.0 52.0 52.0 52.0 52.0 480/277V 220/127V 380/220V 240/120V 230/115V 440/254V 220/110V 208/120V 240/139V
Prime
kVA
68.8 68.8 68.7 68.8 68.8 68.8 68.7 68.8 68.8
Standby
kW
55.0 55.0 55.0 55.0 55.0 55.0 55.0 55.0 55.0
kVA
75.0 75.0 75.0 75.0 75.0 75.0 75.0 75.0 75.0
kW
60.0 60.0 60.0 60.0 60.0 60.0 60.0 60.0 60.0
Dimensions: mm (in)
Length Width Height 2150 (84.6) 752 (29.6) 1366 (53.8)
Note: General configuration not to be used for installation. See general dimension drawings for detail.
Definitions
Standby Rating
These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3).
General Data
Documents
A full set of operation and maintenance manuals and circuit wiring diagrams.
Quality Standards
BS4999, BS5000, BSEN60034, BSEN61000, IEC60034.
Prime Rating
These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours.
Warranty
All equipment carries full manufacturer's warranty.
Market: International
LEHF5247-05 03/09
Information contained in this publication may be considered confidential. Discretion is recommended when distributing. Materials and specifications are subject to change without notice. CAT, CATERPILLAR, their respective logos and ''Caterpillar Yellow'', as well as corporate and product identity used herein, are trademarks of Caterpillar and may not be used without permission.