EST EST3 Intelligent Control For Large and Medium Sized Applications
EST EST3 Intelligent Control For Large and Medium Sized Applications
EST EST3 Intelligent Control For Large and Medium Sized Applications
GE Security
Submittal Guide
imagination at work
EST3 Network
Initiating Devices
It is with great pleasure that we provide this submittal for an EST3 Unified Control Platform. This guide includes a comprehensive presentation of related system components and devices. Products we are submitting for your consideration are indicated by a checkmark in the margins of the pages that follow. More detailed information can be found in individual catalog sheets dedicated to each product. All these sheets, along with guide specifications and other useful product information, are available electronically on our LifeLines CDROM. This exhaustive collection of life safety related literature is fully searchable and includes a utility for printing multiple catalog sheets. Thank you for giving us the opportunity to provide this submittal. Please do not hesitate to contact us should you require further information.
____________________________
EST3 Network
Submittal Guide
Initiating Devices Notification Appliances Hazardous Location Devices Door Holders & Relays
iii
EST3 Submittal Guide Intelligent control for large and medium sized applications
Published by GE Security Copyright 2005 General Electric Company All rights reserved. 8985 Town Center Parkway, Bradenton, FL 34202 85010-0099, Issue 8
Wiring diagrams provided herein are for information and reference only and are not to be used for installation purposes. Consult the appropriate installation documents for wiring and configuration details. This guidebook is for information only and is not intended as a substitute for verbatim legislated requirements. For authoritative specifications regarding the application of life safety, security, and access control systems, consult current editions of applicable codes and standards. For authoritative interpretation of those codes and standards, consult your local authority having jurisdiction. While every effort has been made to ensure the accuracy and completeness of this guidebook, the authors and publishers assume no responsibility for errors, inaccuracies, omissions, or any inconsistencies herein. EST, Synergy, Genesis Series, and Signature Series are trademarks of GE Security.
Also from GE Security: Security and Access Control Handbook A practical guide to application and system design Handbook of Visual Notification Appliances for Fire Alarm Applications A practical guide to regulatory compliance Glossary of Fire Alarm and Security Terminology A desk reference for life safety and security professionals Remote Booster Power Supply A summary of typical wiring and configuration for everyday and advanced applications Installers Wire Guide A concise pocket reference to wire and cable requirements for GE Security products and systems QuickStart Submittal Guide Intelligent/conventional life safety for small to mid-sized applications EST2 Submittal Guide Networkable intelligent life safety with voice audio
EST3
M EA
EST3 Network
EST3 Network
Introduction ............................................................................................... 1 EST3 Riser Diagram .............................................................................. 2 Crentral Proccessor Unit ..................................................................... 3 Local Rail Modules ................................................................................. 4 Control, Display, and Annunciation ............................................... 8 Ethernet Networking .......................................................................... 12 Network Audio ...................................................................................... 13 Security and Access Control ......................................................... 15 Cabinets & Chassis ............................................................................ 19 Power Supplies .................................................................................... 20 Network Accessories ........................................................................ 22
Initiating Devices
25
Notification Appliances
Notification Appliances
Wall Horns, Strobes and Chimes ................................................ 39 Wall Speakers and Speaker/strobes ....................................... 40 Signal Master ......................................................................................... 40 Ceiling Horns, Speakers and Strobes ....................................... 41 Harsh Environment Signals ............................................................ 42 Firefighers Telephones .................................................................... 43 Fire Alarm Bells and Single-stroke Chimes ............................ 43 Bell Strobe Plates ................................................................................. 44 Mounting Accessories ...................................................................... 44
38
Hazardous Location Devices
45
48
Index
50
vi
EST3
Network
p. 2 p. 4
EST3 Network
Ethernet Networking p. 12 Network Audio p. 13 Security and Access Control p. 15 Cabinets & Chassis p. 19 Power Supplies p. 20
EST3 Network
EST3 is a modular system uniquely designed to easily meet the needs of standalone single node systems or multi-node networks. Fire alarm, security, access control and audio functions use the same fundamental components, simplifying system layouts. A powerful System Definition Utility program helps define system operations in a fraction of the time required by previous methods. Virtually all EST3 operating features are software controlled. This gives EST3 great site flexibility and ensures operational changes and upgrades will be possible years after the initial installation. Highly Flexible Applications EST3 is a superbly adaptable life safety system, lending itself to medium and large building applications. Cabinets are available with room for system batteries up to 65 Amp hours. With EST3, one 24-volt battery supports up to four power supplies. Each supply will support up to 7 Amp load. With four supplies, 28 Amps of current is available all backed up by a common battery.
Network Accessories p. 22
Initiating Devices Notification Appliances Hazardous Location Devices Door Holders & Relays
Powerful Networking EST3 operates on a multi priority peer-to-peer token ring network. The multi-priority token ring gives EST3 exceptional response. Response time for all functions, including fire, security, and access control, is less than three seconds across the network regardless of the total number of nodes. EST3 token ring network configuration also permits vast distances between nodes. The allowable distance between nodes on #18AWG (0.75mm2) is 5,000ft (1,523m). With 64 nodes supported on a network, the total network length is in excess of 300,000 ft (91,400m), or nearly 60 miles! A single node supports up to 10 Signature loop controllers with 250 devices per loop, (2,500 points total per node). EST3 also makes field wiring easy with building wiring terminations that use removable terminal blocks on local rail modules. Panel design allows for the required separation of high voltage and power-limited wiring.
Eight-channel Audio EST3 audio design provides the emergency user with a comCONTROL LOCAL munication package that INNER Fully-listed User Interfaces OUTER CHASSIS DISPLAY RAIL DOOR DOOR MODULES MODULES COVER minimizes switch selections. BOX The user interface layer is This facilitates simple, accumade up of a Liquid Crystal DisSystem components arrange in layers starting with the wallbox system and rate and fast evacuation conplay module and a system of ending with inner and outer doors. trol announcements. EST3 progeneric modules designed to vides simple paging controls. Pressing All Call selects all pagmaximize design flexibility for custom systems. ing zones for message delivery. Pressing Page To Evacuation In addition to front panel control and annunciation, EST3s automatically selects all areas in evacuation. Similarly, the powerful FireWorks color graphics package provides desktop user can Page To Alert. Zoned paging requires the user to control and messaging in the familiar Windows environment. simply select zone paging switches. Fireworks unique four-quadrant display gives the user acTaking full advantage of digital technology, up to eight cess to all EST3 functions including fire alarm, security, acchannels of audio sources can be sent over a single twisted cess control, and CCTV in one simple and intuitive interface. pair of wires between nodes. Coupling the inherent reliability And because FireWorks is an integral part of the EST3 netand performance of zoned amplifiers with EST3 simplified user work, it is listed by UL not only under fire alarm standards, interfaces makes audio system design and operation both easy but under access control, local burglar, and proprietary moniand dependable. toring standards as well. In fact, EST3 panels and FireWorks EST3 is the right choice for any medium to large application. Its are the only such systems with this range of qualifications. multiplex functions are second to none in the industry today.
EST3
EST3 Network
Network
DOOR
DOOR
J J
MD
MM
CRITICAL PROCESS MONITOR
1 Tw/Sh Pr.
MD
CC
2 Pr.
2 Tw. Pr.
CPU, power supply & booster, dual loop module 3 amplifiers, & batteries 1 Pr 2 Tw. Pr. 1 Tw/Sh Pr.
CC
1 Tw/Sh Pr.
CR
J
F
J
CR
ELEVATOR CAPTURE
SEC
SECURITY INPUTS
CT CT
2nd FLOOR
2 Tw. Pr.
2 Pr.
I J J
2 Pr.
R J
1 Pr.
CR
HVAC CONTROL
MM
HVAC MONITOR
Page
F S
R
1 Pr.
SEC
SECURITY INPUTS
MD
SEC
KPDISP
CC
1 Tw/Sh Pr.
F
KPDISP
Access Control Data Base Central Monitoring Station Paging Company
DOOR
CRC
CRC
2 Tw. Pr.
CC
CR CT
MM
TELCO
CPU w/display, power supply & booster, dual loop module, audio source module w/master firefighter's telephone, 2 amplifiers, & batteries GROUND FLOOR
Printer
MD
Manual Pull Station Smoke detector with relay base Smoke detector with isolator base Smoke detector with standard base Motion detector Combination speaker/strobe Firefighters telephone Security module Keypad Display Card Reader Controller Signal module Control relay module Input module Monitor module End-of-line resistor Junction box
34 26 26 26 27 39 42 33 15 16 30 30 29 31
CC
1 Tw/Sh Pr. 2 Pr.
2 Pr.
L E G E N D
FIRE DAMPER
F MD
MM
SECURITY INPUTS
DOOR
CRC
CRC
DOOR
CRC
F
WATER LEVEL MONITOR
SECURITY INPUTS
SEC
1 Pr.
Whether for fire alarm only, or for total life safety protection including security and access control, the EST3 network is the most survivable system available. EST3 uses distributed database technology, designed to survive the rigors of fire and firefighting. In Class B configuration a single break on the network wiring will isolate the system into two groups of one or more nodes. Each group of nodes continues functioning as a peer-to-peer network, working with their combined databases. In Class A configurations a single break or short on the network wiring causes the system to isolate the fault. Network communication continues uninterrupted. If multiple faults occur, the network re-configures into multiple networks. This means a system continues to respond to activations from every node that can transmit and receive network messages. Local responses always execute because the local database resides at each node. Exceptional survivability extends to every EST3 function, including security and access control. These devices (highlighted in yellow) reside on the network alongside fire alarm components. They share wiring, power sources and the inherent stability of a fire alarm network engineered to meet standards far beyond those of ordinary security systems.
CC
1 Tw/Sh Pr. 2 Pr.
2 Pr.
HVAC CONTROL
HVAC MONITOR
FIRE DAMPER
1 Pr.
CR
MM
MM
KPDISP
2 Tw. Pr.
CRC
CRC
2 Pr.
2 Pr.
F
WATER LEVEL MONITOR
SECURITY INPUTS
SEC
F
DOOR
CRC
CRC
DOOR
CRC
SEC
F
DOOR
CRC
EST3
Central Processor Unit
The 3-CPU3 is the heart of the EST3 network node. As a single node standalone system, a single 3-CPU3 controls up to 19 local rail modules. For larger systems, up to 64 nodes interconnect on a peerto-peer multi-priority token ring protocol network.
Network
SUBMIT
EST3 Network
3-CHAS7
J9 J8
COM. TROUBLE
N.O. TROUBLE
J11 J10
N.C. TROUBLE
N.O. ALARM
COM ALARM
N.C. ALARM
N.O. SUPV.
Power Supply
Power Supply
J9 J8
J11 J10
10
3CPU3
L R M
L R M
L R M
L R M
L R M
Initiating Devices
The 3-CPU3 controls all local panel responses to automatic, user initiated, or network reported events. As a network node, it is an equal among peers: there is no master on the network. Multi-priority token ring means that a node with a new alarm has priority on the network. This gives exceptional response times over the network less than three seconds.
20
19 18
17 16 15
14 13 12 11
10
(2) RXD
PIN 1
PIN FUNCTION
PLUG PIN #
OR
DB25 FEMALE (REAR VIEW)
PIN 13 PIN 25
Class A only
(3) RXD (2) TXD
PIN 14 PIN 1
Notification Appliances
PIN 13
PIN 25
TO PRINTER OR REMOTE Each 3-CPU3 provides connectors for mounting COMMAND SYSTEM. network, RS-232, and memory expansion cards. Removable terminal blocks on the 3-CPU3 support connection of network and audio data wiring. On-board common relays also terminate at the 3-CPU3 terminals. To aid in troubleshooting and service, status LEDs monitor local rail, network, RS232 and audio data communications.
(7) COM (3) RXD (2) TXD
PIN 14 PIN 1
3-CPU3
EST3
SUBMIT
Network
EST3 Network
The 3-SSDC1 and 3-SDDC1 Signature Driver Controller modules provide an intelligent interface between the 3-CPU(1.3) module and Signature Series devices. Each module contains its own microprocessor used to coordinate, process and interpret information received from and sent to Signature devices. Power and communications is received directly from the control panel rail assembly. The 3-SSDC1 Single Signature Driver Controller module supports one Signature Data circuit, while the 3-SDDC1 Signature Dual Driver Controller module supports two Signature circuits. Both modules occupy one rail space in the fire alarm control cabinet and provide removable field wiring terminals to aid installation. Innovative design gives the 3-SSDC1/3-SDDC1 and Signature devices truly distributed intelligence. Signature detectors and modules have their own on-board microprocessor communicating with the loop controller in a fully digital communication format. This increases the accuracy of the information coming to and from the loop controller by reducing the effects of capacitance and noise.
Class A Configuration Shown (Typical)
+
1 2 3 4 5 6 7 8 9 10
Circuit #1
TB1
With decentralized intelligence much of the decision making moves from the loop controller to the devices. Advanced fire detection algorithms processed within the Signature devices effectively end unwanted alarms. Environmental compensation and multiple sensing element decision making operations are resident in the devices. Intelligent devices allow the Signature Controllers to execute communication and system functions with greater speed and low baud rates, increasing the accuracy of information transmitted between the loop controller and devices. To enhance survivability of the system the 3-SSDC1/3-SDDC1 supports a standalone mode for Signature devices. Two catastrophic failure modes are supported. If the 3-CPU(1/3) fails, the loop controller will continue to poll its devices. If an alarm is detected it will be sent on the local rail communication bus and received by other local rail modules. A common alarm condition throughout the panel will result. If the local rail module (3-SSDC1/3SDDC1) fails, and a device (smoke or module) detects an alarm, specialized circuitry will make the node aware of the alarm condition. The 3-CPU(1/3) will communicate the alarm condition to the rest of the network. Having multiple redundant modes is paramount in a life safety system.
Catalog Sheet: 85010-0129 Catalog Sheet: 85010-0129 Catalog Sheet: 85010-0129 Catalog Sheet: 85010-0129
TB2
Circuit #2
Single Signature Driver Controller, c/w one 3-SDC1 Dual Signature Driver Controller, c/w two 3-SDC1s Signature Device Card - upgrades a 3-SSDC1 to a 3-SDDC1 Driver Controller Motherboard (no 3-SDC1 device cards)
Signature Detectors and Bases, p. 26; Signature I/O Modules, p. 28; Signature Pull Stations, p. 34 4
EST3
Network
SUBMIT
CLASS A WIRING
EST3 Network
LOOP
MONITOR IONIZATION ISOLATION PHOTO THERMAL MODULE SMOKE MODULE ELECTRIC DETECTOR DETECTOR SMOKE DETECTOR
MONITOR MODULE
MONITOR MODULE
CONTROL MODULE
ISOLATION MODULE
10
The 3-AADC1 Addressable Analog Circuit Module is a local rail module used on the EST3 system. The module requires one connection on the rail chassis. The module can support 99 addressable analog sensors and 99 addressable modules. The controller also features a hinged front panel for a Control Display Module, available in a variety of LED and/or switch configurations.
3-AADC1 Addressable Analog Module Catalog Sheet: 85010-0128
Initiating Devices
Flexibility built right into the IDC module allows connection of normally open contact devices, and traditional 2-wire smoke detectors. The 3-IDC8/4 also configures for use with N.O. contacts and supports supervised supervisory and monitor circuits with latching or non-latching operations. When the monitor operation is used with the non-latching function, the circuit serves as a supervised event follower. This efficiently covers critical fan and damper operations. Circuits can annunciate on the 3-LCD, control display modules, or at any other display device on the network. Up to 30 photoelectric or 50 ionization smoke detectors are supported per circuit. All circuits may be programmed for non-verified or verified smoke operation. Ranges include open circuit, shorted condition, and high and low impedance (relative to the main impedance setting). This allows the use of various detectors of similar impedance, as well as 4-state European alarm circuit operation.
1
IDC/NAC #2
NAC IN 1/2
IDC #3
IDC #4
Notification Appliances
10
To TB1 on Module
TB1
RX TX
JP1 JP2 3 2 1 3 2 1
1 1 2 2 3 3 JP3 JP4
TB2
10
IDC/NAC #8
1 4
EOL
2 3
Four of the eight 3-IDC8/4 circuits are convertible to Class B notification appliance circuits. The circuits employ traditional reversing polarity operation for polarized bells, horns, and strobes. Notification appliance circuits are arranged in pairs. Each pair distributes 3.5 Amps at 24 Vdc from the local rail or a single riser. Riser sources supported include 24 V @ 3.5 A, which can be pulsed (temporal pattern) for audible signals, or up to 70 Vrms @ 100W audio source for speakers.
Detector Base
Detector Base
IDC/NAC #7
NAC IN 7/8
IDC #6
IDC #5
+ -
+ -
+ -
+ -
+ -
+ -
EOL
EST3
SUBMIT
Network
EST3 Network
New style reverse polarity operation allows the 3-OPS to output three independent reversing polarity signals. These are alarm, supervisory, and trouble. In each case an active condition causes the terminal output voltage to reverse. Should the central station detect a loss of voltage, the condition is due to line failure. When configured for new style operation, a set of trouble contacts is available. City Tie connection. In this configuration the 3-OPS has terminals for a local energy master fire alarm box. The module operates into a 14 ohm coil and supervises the city tie connection for open conditions. Trouble relay contacts are configurable for normally-open or normally-closed.
10 9 8 7 6 5 4 3 2 1
10
TROUBLE RELAY TERMINALS 1 & 2 (+) ALARM (+) (+) TROUBLE SUPERVISORY
MASTER BOX
3-OPS
RX
B AUDIO
A +
OUT IN A B B - + -
Network
B DATA
A audio
A DATA
TX
TX
RX
A data B data
RX TX RX TX
RX TX RX TX
Network
B AUDIO
TX RX TX RX
RX TX RX TX
A AUDIO A AUDIO
A DATA
TX
RX
RX
TX
B data
B DATA
TX
RX
RX
TX
A DATA
TX
A data
RX
Network
TX RX TX RX
RX TX RX TX
RX TX
B AUDIO
B data
B DATA
TX
RX
RX
TX
A data
RX
Network
TX RX TX RX
RX TX RX TX
TX
RX TX
B data
B AUDIO
B DATA
TX
RX
RX
TX
Fiber Optic Communications Interface c/w 3-CHAS7/3-CAB5 mounting brackets Plug-In standard output single mode transceiver for 3-FIBMB Plug-In high output single mode transceiver for 3-FIBMB Plug-In standard output multi mode transceiver for 3-FIBMB
Catalog Sheet: 85010-0131 Catalog Sheet: 85010-0131 Catalog Sheet: 85010-0131 Catalog Sheet: 85010-0131
EST3
Modem Communicator
Network
SUBMIT
EST3 Network
The Modem Communicator is a two-way local rail module that performs a variety of off-premise communications functions for the EST3 system unavailable on any other system. The module has provisions for supervising two loop-start telephone lines. It features a modular jack for telephone line connections, as well as database download from a PC. The Modcoms configuration and firmware can also be updated from any network node. Modcom series modules occupy a single local rail space and can be mounted in any node on the network. Any EST3 Control/Display module can be mounted on the face of a Modcom series module. Power for the Modcom is supplied by the EST3 system supply.
Initiating Devices
The Modcom provides an enhanced level of survivability in the event of a network CPU failure by notifying the Central Monitoring Station of the failure and entering a degraded mode of operation. In degraded mode, the Modcom can transmit a default fire alarm message during a fire alarm condition. Two versions of the Modcom are available: 3-MODCOM - This internal modem is a V.32bis 14.4K baud full duplex modem. The modem permits the remote upload and download of system data via a telephone line. 3-MODCOMP In addition to all modem and dialer (DACT) functions of the 3-MODCOM, the 3-MODCOMP can dial directly into paging systems using Telelocator Alphanumeric Protocol (TAP). Alphanumeric system data can be sent to a single pager or groups of pagers. Some pager services can SURGE forward messages via e-mail and Fax. PROTECTOR RING Each Modcom can buffer up to 500 events in its event queue. It reviews all active events in the queue and identifies the highest priority event and dials the associated receiver. The Modcom then YELLOW 4 3 identifies all other events in the queue that are destined to the same receiver as the highest priority event. All event 2 BLACK 1 information for that receiver is then transmitted. The next PREMISES PHONES high priority event is identified and the process repeated. The Modcom series has been designed for installation on the same phone lines with other devices such as faxes and answering machines. The module makes its first dial out attempt on either of the two phone lines that is not in use. This prevents unnecessary interruption of calls in progress by the line seizure relays. In the event that both lines are busy, the module seizes one of the busy lines. A fixed DACT testing time can be set at an off-hour, e.g. 2:00am, again minimizing interruptions. The answering machine override feature permits Modcom modules to be installed on a standard telephone line. The Modcom series also has the ability to detect Type 2 and Type 3 distinctive ringing patterns, permitting it to share its phone lines with other devices and still have a unique phone number for incoming calls.
3-MODCOM 3-MODCOMP Modem/Dialer (DACT) version Modem/Dialer (DACT) w/TAP Protocol
(RED)
Notification Appliances
5 6
TIP (GREEN) RJ31X 8 PIN MODULAR CONNECTOR FOR PHONE LINE #1 TO PHONE LINE #2 (WIRED SAME AS PHONE LINE #1)
4 3 5 6
7 8
2 1 8
7 Ft. (2.13 M)
LINE 1
LINE 2
MODCOM
(front view)
EST3
SUBMIT
Network
EST3 Network
J9 J8
J11
J10
Power L Supply R M
Power Test
CPU Fail GND Fault
Disable
Reset
Alarm Silence
Panel Silence
Drill
J9 J8
J11
EST3 system
J10
Alarm
Sup'y
Trouble
Monitor
Previous
1 4 7
2 5 8 0
3 6 9
Message Next
LCD display modules provide system control and annunciation from any network node location at which they are installed. Modules feature backlit high-contrast supertwist graphical displays and mount to the local rail over the nodes central processing unit (3-CPU3). Simple-tounderstand LEDs and switches help the emergency user display information and execute system commands with confidence. 3-LCDXL modules feature large screens that support 24 lines of text 40 characters in length enough space to display eight events simulaneously. It occupies four local rail module spaces. 3-LCD modules support eight lines of text 21 characters in length. They occupy two local rail module spaces. EST3 networks can support any combination of 3-LCDXL and 3-LCD display modules.
3-LCDXL 3-LCD 21 Line Liquid Crystal Display Module 8 Line Liquid Crystal Display Module Catalog Sheet: 85010-0135 Catalog Sheet: 85010-0071
Display/Control Module: 12 switches with 1 green and 1 yellow LED per switch Catalog Sheet: 85010-0055 Display/Control Module: 12 switches with 1 red and 1 yellow LED per switch Display/Control Module: 12 switches with 2 yellow LEDs per switch Catalog Sheet: 85010-0055 Catalog Sheet: 85010-0055
Display/Control Module: 6 groups of 3 switches, 1 LED each: green, yellow, yellow Catalog Sheet: 85010-0055 Display/Control Module: 6 groups of 3 switches, one LED each: green, yellow, red Catalog Sheet: 85010-0055
EST3
FireWorks
Network
SUBMIT
EST3 Network
FireWorks is a family of software and hardware options designed to work in concert with GE Security life safety and property protection systems. FireWorks provides a simple user interface, taking what could be an overwhelmingly large amount of information and presenting it in an easy-tounderstand format. It does this by dividing major system functions into easy-to-manage quadrants that make the system very intuitive to use because information is presented logically. To further enhance usability, FireWorks is event driven. This greatly increases the user's ability to deal with system events by eliminating the confusion sometimes experienced when systems present all information at once. FireWorks automatically prioritizes the events for the user in an Event Quadrant. Here the highest priority event is displayed first, and the lowest priority event is displayed last. This allows the user to quickly determine which events warrant the most immediate attention.
The FireWorks four-quadrant display provides easy access to fire, security, access control, and CCTV functions. FireWorks operates with Windows 2000 or Windows XP operating systems.
For FireWorks specifications and ordering information, please refer to catalog sheet 85006-0048. For FireWorks operation and application, please refer to catalog sheet 85006-0047.
Initiating Devices
Each of the other three quadrants provides one specific piece of information that relates to the event highlighted in the Event Quadrant. Related information may include event action information (specific tasks the user may need to perform in response to the event), or information about the area where the event has taken place (any hazardous materials present in the area, etc.). Still images, CCTV, video, audio messages and graphical maps may also be presented to aid in the understanding of an event and how it should be managed.
FW3UL3 (3 Port) FW5UL3 (5 Port) FW-19LCDTS FW-21MN (21)
Notification Appliances
Standalone workstations
UL 864 listed 19 LCD Monitors, black, touch screen, rack mountable UL 864 listed CRT Monitors, beige RKU-61-24 FW-RACKMN FW-RACKLCD19 FW-RACKPC FW-RACKKB FW-RACKSD Blank EIA panel plates MFC-A PCCA FW-19MN (19)
19" Rack mount enclosure - 35 EIA panel Spaces available Monitor Rack mount kit - 10 EIA panel spaces required. For FW-19MN monitors Monitor Rack mount kit - 10 EIA panel spaces required. For FW-19LCD(TS) monitors
Computer Rack mount - Hardware - 4 EIA panel spaces required. Order FW-RACKSD slides separately Keyboard Rack mount kit - Black - 2 EIA panel spaces required. Order FW-RACKSD slides separately Rack mount slides BP1 (one space) BP2 (2 spaces) BP3 (3 spaces)
Accessory Enclosure for mounting Mini-Mux at FireWorks workstation PC Conduit Adapter - Used for desk or tower mounting PC (See Note 4) FW-MOD (56k bd. V.90 modem) FW-SND (Sound card) FW-SNDSP (speakers, black)
PC options for UL/ULC systems FW-SP2 FW-VIDTVC FW-VIDVC2 Mini-Mux FCOM-FIB FW-XPC FW-XPL Color Graphics Software Access Control Database
Provides 2 serial ports for UL/ULC Listed FW3UL3 or FW2UL2 or FW2 workstations Card for UL/ULC listed systems. Required when using SV+ software with FW3UL3 or FW5UL3 Video card for dual monitors (FW3UL3 and FW5UL3)
Communication Interface Board - UL listed for extending FireWorks to Fire Panel Communications Fiber Optic data line card used with Mini-Mux RS-232 extender. Allows FireWorks with no common controls to communicate to Fire Panels RS-232 extender. Allows Fire Panel to communicate with FireWorks FW-CGS (no cmn. ctl., not for UL-listed PCs) ACDB8 (controls up to eight doors) SV FW-CGSUL (c/w cmn. ctl., requires UL-listed PC) ACDB8+ (controls more than eight doors) SV+ (with on-screen control) 9
EST3
SUBMIT
Network
EST3 Network
Power ON, Trouble, and Signal Silenced LEDs; System Reset , Silence, Trouble Silence, and Drill push button switches are available as panel feature options. Other panel options include system LCD displays and remote microphones.
24VDC TO NEXT POWER MODULE RS-485 NETWORK DATA FROM PREVIOUS PANEL RS-485 NETWORK DATA TO NEXT PANEL
ENVOY graphic panels are available in three standard sizes to fit the needs of most installations. Wall boxes are manufactured from 16-gauge cold rolled steel and finished with a textured black baked enamel. Panels can be surface mount or semi-flush mount. When semi-flush mounting, optional trim kits provide a finished look to the installation.
EV1 EV1B EV1T EV2 EV2B EV2T EV3 EV3B EV3T FSCS-1 FSCS-2 FSCS-3 FSCS-4 Envoy Graphic Annunciator (maximum 96 LEDs) EV1 Wallbox: textured black finish EV1 Semi-Flush Trim: textured black finish Envoy Graphic Annunciator (maximum 160 LEDs) EV2 Wallbox: textured black finish EV2 Semi-Flush Trim: textured black finish Envoy Graphic Annunciator (maximum 256 LEDs) EV3 Wallbox: textured black finish EV3 Semi-Flush Trim: textured black finish Envoy Smoke Control Graphic Panel Envoy Smoke Control Graphic Panel Envoy Smoke Control Graphic Panel Envoy Smoke Control Graphic Panel
or
BP1 Optional Flush Trim Separate Hinged Outer Door Optional 3-EVRMF Module Mounting Frame (7 EIA Panel spaces high)
Catalog Sheet: 85006-0037 Catalog Sheet: 85006-0037 Catalog Sheet: 85006-0037 Catalog Sheet: 85006-0037 Catalog Sheet: 85006-0037 Catalog Sheet: 85006-0037 Catalog Sheet: 85006-0037 Catalog Sheet: 85006-0037 Catalog Sheet: 85006-0037 Catalog Sheet: 85006-0037 Catalog Sheet: 85006-0037 Catalog Sheet: 85006-0037 Catalog Sheet: 85006-0037
See Page 8 for Control Display modules. See Page 14 for Remote Microphones.
10
EST3
Remote Annunciators
Network
SUBMIT
EST3 Network
To Backbox
NETWORK A
7 8 9
See Page 8 for Control Display modules. See Page 14 for Remote Microphones.
SPARE
Use EST3 remote annunciators wherever a comTo TB1 on 3-ANNCPU1 pact system status display is needed. Annunciator configurations include: LCD only display, LED only display, or combination LED and LCD display in a single enclosure. Display and control is provided by the 3-LCD and Control Display Modules. Control/Display modules install over any annunRear View ciator support module, maximizing annunciator design flexibility. A lamp test feature can program to any spare control switch. If a 3-LCD display is installed in the annunciator, simply operate the Alarm Silence and Trouble Silence switches simultaneously to lamp test all LEDs. 3-REMICA remote microphones can also be installed in annunciator cabinets.
TX RX TX RX TX RX TX RX
RX TX
RX TX
RX TX
RX TX
NETWORK B
10
Ground Lead
EARTH GROUND
24 VDC
24 VDC
Initiating Devices
3-LCDANN 3-6ANN 3-10ANN 3-ANNCPU3 3-ANNSM 3-LCD 3-ANNBF 3-EVDVRA 3-EVPWRA 3-EVDVRX
Remote LCD Command Module Annunciator Six-position Base Annunciator Ten-position Base Annunciator Annunciator CPU Annunciator Support Module Liquid Crystal Display Module Blank Filler Plate LED/Switch Driver Module Assembly for Third-party Graphics Power Supply Assembly with 19 rail mounting chassis assembly Plastic mounting extrusion 19-inch mounting
Catalog Sheet: 85010-0069 Catalog Sheet: 85010-0069 Catalog Sheet: 85010-0069 Catalog Sheet: 85010-0069
Notification Appliances
Catalog Sheet: 85010-0069 Catalog Sheet: 85010-0069 Catalog Sheet: 85010-0069 Catalog Sheet: 85010-0069 Catalog Sheet: 85010-0069 Catalog Sheet: 85010-0069
3-VDUT
11
EST3
SUBMIT
Network
EST3 Network
Ethernet Networking
Optional interface for monitoring applications. See pages 8-11 for UL-listed equipment suitable for common control applications.
Note: Refer to the Network Application Manual (p/n 3100576) for detailed information on network application.
12
EST3
Network
SUBMIT
Network Audio
TR RX TX
AUDIO DATA PRIMARY
SECONDARY TELEPHONE
EST3 Network
PAGE OUT
REMOTE MIC
KEY
AUDIO
AUX
RX TX
Configuring EST3 audio is a matter of selecting components for installation in standard fire alarm cabinet assemblies. EST3 uses zoned amplifiers. This reduces wire runs and space needs at a central location. Audio control equipment and zoned amplifiers use the same system power supplies as fire alarm components. All these components are supported by a common standby battery. Where multiple nodes make up the system, a single pair of wires carries eight channels of digital audio between nodes.
TB1
14
TX RX
TB1
J2 J3
J1
J6 DIN
J2
J1
J7 BOUT
J2
J1
J3
J4
CONNECT REVIEW PENDING ACK
1234
READY TO PAGE
BIN
J4
0 call(s) pending
ALL CALL
EMERGENCY TELEPHONE
Page to Evac
DISCONNECT REVIEW CONNECTED
Page to Alert
Page by Phone
Initiating Devices
Notification Appliances
SIGA-CC1
8 7 6 5 4 3 2 1
When the system requires paging, only the 3-ASU or 3-ASU/4 Audio Source Units provide a master paging microphone with common controls. Switch labeling makes the operation intuitive. Six LEDs and five switches cover paging operations. Audio Source Units mount in one chassis space of a EST3 Lobby Enclosure. In addition to the paging microphone, the 3-ASU/4 has mounting space for up to four local rail modules, including 20, 40, and 90 watt zone amplifiers, and up to four Control Display modules. This increases layout flexibility. The 3-ASU provides the same functionality as the 3-ASU/4 but is supplied with an inner door filler plate and no local rail module spaces. The 3-FTCU contains the master telephone handset that provides an analog telephone riser for two-way communications between the fire command station and firefighters telephone stations installed in the facility. The 3-FTCU features an alphanumeric display that indicates both incoming and connected calls. Up to five remote telephones may be connected to the riser simultaneously. The fire command center operator can also use the telephone circuit as a page source, permitting paging via the telephone system.
Catalog Sheet: 85010-0063
To Phones
Connect to TB1 on 3-CPU Module
10 9
3-CPU
To next panel 3-CPU Module
MAIN PROCESSOR MODULE
Connect to TB2 on 3-CPU Module
SIGA-CC1
8 7 6 5 4 3 2 1
20
19 18
17 16 15
14 13 12 11
10
Connect Shield to Earth Ground only at the panel. Maintain shield continuity.
3-ASU or 3-ASUFT
Audio Source Unit
EST3 Panel
Audio Source Unit with local microphone (provides four local rail spaces) Catalog Sheet: 85010-0063 Audio Source Unit with local microphone and inner door filler plate Firefighters Telephone Control Unit with inner door filler plate Catalog Sheet: 85010-0063 Catalog Sheet: 85010-0063
Audio Source Unit Memory Expansion (provides 32 minutes of message time)Catalog Sheet: 85010-0063 City of Chicago Interface
13
EST3
SUBMIT
Network
EST3 Network
10
10
10
10
10
10
COMMON ENCLOSURE
Amplifiers are available in 20, 40 or 95 watt verAUDIO NOTIFICATION sions, with supervised, power limited 25 Vrms or 70VRMS APPLIANCE CIRCUIT outputs. The amplifier output is wired to a single speaker zone. Each amplifier has a 1 KHz temporal tone generator used as evacuation signal in the event of a fault with the network audio circuit. In the event of an on-line amplifier failure, a standby amplifier may be configured for automatic replacement of any on-line amplifier configuration. 20 and 40 watt amplifiers also provide an independently controlled supervised, power limited 24 Vdc notification appliance circuit rated at 3.5 amps. All field wiring connections are made via plug-in connectors.
3-ZA20A 3-ZA20B 3-ZA40A 3-ZA40B 3-ZA95 20 Watt Zoned Amplifier w/Class A/B (Style Z/Y) Audio & Class A/B 24 VDC outputs 20 Watt Zoned Amplifier w/Class B (Style Y) Audio & Class B 24 VDC outputs 40 Watt Zoned Amplifier w/Class A/B (Style Z/Y) Audio & Class A/B 24 VDC outputs 40 Watt Zoned Amplifier w/Class B (Style Y) Audio & Class B 24 VDC outputs 95 Watt Zoned Amplifier w/Class A/B (Style Z/Y) Audio output Catalog Sheet: 85010-0057 Catalog Sheet: 85010-0057 Catalog Sheet: 85010-0057 Catalog Sheet: 85010-0057 Catalog Sheet: 85010-0057
Remote Microphones
The remote microphone panel is a supervised remote microphone, used with the 3-ASU Audio Source Units remote microphone input. The front panel provides Local Page Active, Remote Page Active, and Trouble LED indicators as well as an integral VU (Volume Unit) meter to indicate page volume level. All panels use a 24 Vdc power source and all wiring is supervised. One form C trouble contact is provided.
3-REMICP 3-REMICA Remote Microphone Chassis Mount Remote Microphone Annunciator Mounted Catalog Sheet: 85010-0105 Catalog Sheet: 85010-0105
+ 1 2 3 4 5 6 7 8 9 10
+ -
+ -
+ -
+ -
+ -
10
EST3
Network
SUBMIT
EST3 Network
Initiating Devices
10
The 3-SAC is used in combination with the Modcom Modem Communicator. The Modcoms dialer (DACT) function transmits alarms to one or more central monitoring stations and/or paging terminals. Additionally, information received by the Modcom can be downloaded through the 3-SAC to individual security devices. The EST3 network ensures that fire alarm events always receive the highest priority over routine signal processing. Power for the 3-SAC comes from the same highly-reliable power supply/battery combination used to power fire alarm components. Any Control Display module will mount in front of the 3-SAC, allowing great flexibility of the system user interface layout.
3-SAC Security/Access Control Module
CRC
KPDISP Keypad
CRC
Notification Appliances
Class B wiring
TB2
Not used
3-SAC Module
A B RS-485 Ground RS-485 + G G + Not used
10
CRC
KPDISP Keypad
CRC
CRC
CRC
Keypad/Display
The KPDISP is a combination keypad and dot-matrix display designed for use with the EST3 fire alarm/security/access control systems. The unit features a large LCD display and telephone-style keypad housed in an attractive Cycoloy case. A removable cover is provided to prevent accidental keypad activation and for protect against dirt.
24 Vdc supply
+
POWER
+ +
24 Vdc supply
To next device
+
RS-485 line
DATA
The KPDISP transmits and receives information from/to the 3-SAC security access control module installed in the EST3 system. Communication between the KPDISP and the 3-SAC is supervised, providing unprecedented reliability. Credential holder information is encrypted to provide an additional level of security. KPDISP data is stored in non-volatile memory. Power to the KPDISP is provided by the EST3, ensuring a reliable, supervised and backed-up power source.
KPDISP Keypad/Display Catalog Sheet 85006-0046
EST3
SUBMIT
Network
EST3 Network
In a life safety network environment, the PC is simply equipped with a conventional modem. The ACDB program then dials up the network and sends the encrypted database information via the network to the individual CRCs. This allows an ACDB to serve multiple sites. Dial-up data entry also permits multiple tenants to share a common access control system without sharing a common database. PCs may also be connected directly to the system using a direct serial connection.
NO
TB-1 J1
NC
10 11 12 13 14 15 16 17 18 19 20 21 22 23
2 1 Dry contact connections Reader wire connections From 3-SAC module or previous CRC 47 K 47 K EOL EOL
From Strike/maglock To next CRC or other device From power supply To next CRC or 120 W EOL if this is the last device on Class B or back to 3-SAC module if Class A. S1
CRC CRCXM CRCSND 12V1A2 CRCXF DLSM ACDB8 ACDB8+ ACDB-SVR ACDB-CLNT
Card Reader Controller w/memory for 8,000 cardholders Card Reader Controller w/memory for 36,000 cardholders CRC Sounder Module 12V @1.2AH Standby Battery Class 2, 16 Vac Plug in Transformer Data Line Supervisory Monitor Access Control Software - eight doors Access Control Software - eight-plus doors Access Control Database Server Application Software Access Control Database Client Application Software
Catalog Sheet: 85001-0528 Catalog Sheet: 85001-0528 Catalog Sheet: 85001-0528 Catalog Sheet: 85001-0528 Catalog Sheet: 85001-0528 Catalog Sheet: 85001-0528 Catalog Sheet: 85010-0098 Catalog Sheet: 85010-0098 Catalog Sheet: 85010-0098 Catalog Sheet: 85010-0098
16
Sounder
Data 0
Data 1
LED A
LED B
Loop 2 IN
Loop 1 IN
EST3
Proximity Card Readers
Network
SUBMIT
EST3 Network
EST3 card readers feature the latest proximity technology that allows cards to be read when they are held in the vicinity of the reader. This eliminates the need for reader adjustments required by swipe-type readers. Readers are rated for both indoor and outdoor applications and are constructed of rugged sealed polycarbonate, which provides a high degree of vandal resistance as well as protection from harsh environments.
Initiating Devices
5355AGK0009 Shown
The CR-5355 proximity card reader is available with or without a keypad. The keypad option provides the additional security offered by a Personal Identification Number (PIN). The CR5355 mounts on a one-gang electrical box. Dimensions (HWD): 5.0" x 5.0" x 1.0" (12.7 cm x 12.7 cm x 2.54 cm).
Standard Proximity Card Reader, Charcoal Gray HID Brand Proximity Card Reader with Keypad, Charcoal Gray Catalog Sheet 85001-0520 Catalog Sheet 85001-0520
CR-5355 5355AGK0009
Notification Appliances
17
EST3
SUBMIT
Network
EST3 Network
24DC12
18
EST3
Lobby Enclosures
Network
SUBMIT
EST3 Network
EST3 lobby enclosures provide space for control, monitoring and display modules. Ideal for mounting in lobbies where appearance is important, maximum mounting flexibility is provided with doors that will mount for right- or left-hand opening. Lobby enclosures come in several sizes housing one to three chassis and batteries. Lobby enclosure doors have viewing windows and are available in gray baked enamel or red baked enamel finishes.
3-CAB5(R) 3-CAB7B Cabinet with Wallbox and door five LRM spaces Wallbox only one chassis Catalog Sheet: 85010-0067 Catalog Sheet: 85010-0067 Catalog Sheet: 85010-0067 Catalog Sheet: 85010-0067 Catalog Sheet: 85010-0067 Catalog Sheet: 85010-0067 Catalog Sheet: 85010-0067
Initiating Devices
3-CAB7D(R) Inner and outer doors for 3-CAB7B 3-CAB14B Wallbox only two chassis
3-CAB14D(R) Inner and outer doors for 3-CAB14B 3-CAB21B Wallbox only three chassis
Notification Appliances
Chassis Assemblies
3-CHASS4 3-CHAS7 Provides space for 3-REMICA and four local rail modules Provides space for seven local rail modules Catalog Sheet: 85010-0067 Catalog Sheet: 85010-0067
Cabinet Accessories
3-BATS 3-TAMP 3-TAMP5 Battery Shelf for RCC Enclosures. Room for up to one 65 AH battery Tamper switch for 3-CAB7, 3-CAB14 and 3-CAB21 cabinets Tamper switch for 3-CAB5 Catalog Sheet: 85010-0067 Catalog Sheet: 85010-0067 Catalog Sheet: 85010-0067 Catalog Sheet: 85010-0067 Catalog Sheet: 85010-0067
3-TAMPRCC 3-TAMPRCC Tamper Switch for RCC series cabinets. Mounts to side of cabinet ATCK Attack rated door for 3-RCC7R
19
EST3
SUBMIT
Network
J9 J8
J11 J10
EST3 Network
Power Supplies
EST3 power supplies use a unique paralleling arrangement that ensures optimization of each supplys full capacity. Each power supply supports up to a 7 amp load. With four supplies, 28 Amps of current is available per cabinet as is battery charging capacity of up to 260 AmpHours.
Power Supply
L R M
J9 J8 J11 J10
EST3 Power supplies consist of two assemblies, a high efficiency switch mode power supply card and a power supply monitor module. Up to four power supplies may be combined in a single enclosure to provide up to 28 amps of available current. Battery backup is provided using from one to four sets of batteries, depending on standby power requirements to support up to 260 AH batteries
The power supply comes in two styles: a primary supply and a booster supply. Each power supply produces 7 amps of filtered and regulated 24 VDC. The primary power supply provides the system with battery charging and voltage regulation. Power The booster supplies work in Utility Power Supply concert with the primary Booster Booster Booster Master supply are available with or without battery charging capaPower Power Power Power Supply Supply Supply Supply bility. Software configuration configures the battery changing circuits for either 10-24 AH batteries or 30 65 AH batteries and Power 24Vdc * 24Vdc * 24Vdc * 24Vdc * Supply 2 x 3.5A 2 x 3.5A 2 x 3.5A 2 x 3.5A Monitoring controls the high/low charge rate. EST3 power supplies individually monitor batteries for load deficiencies, short circuits, and insufficient voltage levels and report trouble back to the 3-CPU3. The 3-LCD displays any troubles and the power supplys address, a specific trouble code, and a text message describing the specific trouble.
3-PPS/M 3-BPS/M 3-PPS/M-230 3-BPS/M-230 3-PPS/M-230-E 3-BPS/M-230-E 3-BBC/M 3-BBC/M-230 3-BBCMON
Master Power Supply Monitor Module
Rails
Primary Power Supply w/ local rail module 120V 50/60 Hz Booster Power Supply w/ local rail module 120V 50/60 Hz Primary Power Supply w/ local rail module 230V 50/60 Hz Booster Power Supply w/ local rail module 230V 50/60 Hz Primary Power Supply w/local rail module 230V 50 Hz, EN-54 Cert., CE Booster Power Supply w/local rail module 230V 50 Hz, EN-54 Cert., CE Booster/Charger Supply w/local rail module 120V 50/60Hz Booster/Charger Supply w/local rail module 230V 50/60Hz Booster/Charger Monitor Module with charger capability
Catalog Sheet: 85010-0059 Catalog Sheet: 85010-0059 Catalog Sheet: 85010-0059 Catalog Sheet: 85010-0059 Catalog Sheet: 85010-0059 Catalog Sheet: 85010-0059 Catalog Sheet: 85010-0059 Catalog Sheet: 85010-0059 Catalog Sheet: 85010-0059
Black
Red
12Volts
12Volts
EST3
Network
SUBMIT
EST3 Network
Initiating Devices
Simple switch selection provides a wide variety of operational configurations. Each remote booster power supply is supplied with its own enclosure providing ample space for additional interface modules and battery compartment. For security applications, space is provided to mount a tamper switch in the cabinet. When used for Fire Alarm notification with Genesis Notification appliances, the booster provides the ability to synNAC Series Connection Sense Up to ten boosters chronize strobes as well as horn signals. The booster can be connected together Booster flexibility allows synchronization with upstream dePower Supply vices, or, the booster may be used to synchronize downstream devices, as well as other boosters and their connected devices. Up to 10 boosters deep may be configured while maintaining strobe synchronization. Parallel Connection BPS notification appliance circuits easily configure for either of two signaling rates: 3-3-3 temporal or continuous. This makes the BPS ideal for applications requiring signaling rates not available from the main panel. It also allows independent setup of a notification appliance circuit without interfering with the main panel and its initiating circuits. In addition to the generated signal rates, the BPS can also be configured to follow the signal rate of the main panels notification appliance circuit. This allows seamless expansion of existing NACs.
The number of boosters that can be connected together is limited by wire run length and available current
NAC Circuit
Sense
NAC
Notification Appliances
Sense
NAC
Parallel Connection The number of boosters that can be connected together is limited by wire run length and available current
For comprehensive configuration and wiring details, refer to the BPS Application Guide, 85001-0582.
6.5 Amp Booster Power Supply 6.5 Amp Booster Power Supply (220V) 6.5 Amp Booster Power Supply with California rate 10 Amp Booster Power Supply 10 Amp Booster Power Supply (220V) 10 Amp Booster Power Supply with California rate Tamper switch
Catalog Sheet 85005-0125 Catalog Sheet 85005-0125 Catalog Sheet 85005-0125 Catalog Sheet 85005-0125 Catalog Sheet 85005-0125 Catalog Sheet 85005-0125 Catalog Sheet 85005-0125
21
EST3
SUBMIT
Network
EST3 Network
Network Accessories
Remote Diagnostic Utility
The Remote Diagnostic Utility (RDU) is a Windows-based communications program used to remotely access and download status and sensitivity information from EST3 fire alarm systems. The RDU can accommodate over 1,000 individual sites in its database. The RDU is ideal for multiple system owners and those responsible for systems located over a large geographic area. In the event of Trouble, system status can be quickly determined with a single phone call, before dispatching service personnel. The RDU computer communicates with the panel over telephone lines. At the remote panel location, a modem is connected to one of the panels serial ports and a conventional dial-up telephone line. Alternately, the RDU computer can be directly connected to the panel when visiting the panel site. System Status reports provide a detailed listing of the state of all devices at the time the data was downloaded. This information becomes a valuable troubleshooting aid and provides an insight into a panels condition, even before the panel door is opened. Alarm, trouble, and disabled/test filters are available to customize the data appearing on a status report. Sensitivity reports are available for both Signature Series and GE Security analog smoke detectors. Dirty and not clean filters are provided to customize sensitivity reports for ease of readability. PORT #2
DB9 FEMALE (REAR VIEW)
PIN 9
PLUG PIN #
OR
DB25 FEMALE (REAR VIEW)
PIN 13
PIN 25
(7) COM
After a systems information has been downloaded a few times, the trend analysis function can be used to identify the rates at which individual detectors are becoming dirty. A trend analysis report can be exported into spreadsheet software such as Microsoft Excel, where it can be easily converted into sensitivity versus time graphs. All system reports can be viewed on the screen, sent to a printer, or saved as a file for archive purposes.
(7) COM
RDUEU-E
Serial Printer
The PT-1 series printers are high-speed, nine-pin dot matrix type. They use standard, continuous tractor feed computer paper. The PT-1 is used to permanently record life safety system changes of state. All printed entries contain the date, time, event type and a user-defined message for each printed event. The printer is required in proprietary systems and requires a backup UPS power source. In auxiliary, local, or remote station systems, the printer is optional. Printer paper may be fed from the rear or bottom of the printer.
PT-1S PT-1S/220 Serial Printer Serial Printer 220/240 Vac Catalog Sheet: 270020 Catalog Sheet: 270020
22
EST3
RS-232 Optical Isolator Card
Network
SUBMIT
EST3 Network
The IOP3A is an optically isolated RS-232 card that electrically isolates the power between the CM1(N), CM2N, FCC, and 3-CPU(1). The IOP3A also provides power for use with short haul modems and fiber optic drivers. The IOP3A is a 1/2 size footprint card that is mounted in an enclosure adjacent to the CM1(N), CM2N, FCC, or 3-CPU(1). The module is powered by the system power supply that provides battery back up. The IOP3A, through its on-card regulator, generates isolated power for the RS-232 drivers. The on-card regulator also provides isolated 12 Vdc power for use with external modems and drivers. Two RS-232 ports are provided that operate parallel with each other. A DB-9 connector is available for a convenient point of connection for a system program download cable.
IOP3A Isolated RS-232 card Catalog Sheet: 270039
Initiating Devices
CDR-3 Coder
The CDR-3 Coder is an auxiliary circuit option module that provides two audio outputs, March Time and PSNI, (Positive, successive, non-interfering). Dry relay contacts are provided for PSNI code, march time and duration. For the PSNI code, the RS-232C input provides communications, between EST3s RS-232 communications card and the CDR-3. The RS-232 port is actively supervised by the CDR-3. If the coder senses a loss of communication, the CDR-3 begins operating in a fail safe mode. When the fail safe mode is active all outputs, (tone and dry contact) activate with a march time code. The CDR-3 provides buffering for up to fifty active codes. The mode and baud rates are dipswitch selectable. The coder outputs four rounds of code and then, through DIP switch selected options, will either: 1) stop and wait for next code; 2) continue; or, 3) change to march time code until reset.
CDR-3 PSNI Coder Module Catalog Sheet: 270009
EST3
SUBMIT
Network
EST3 Network
Pair two in
14 13
I T Circuit pair 1
3-2-1 P1
12
11
I T Circuit pair 2
D1 arth D Power
4
D2 Trou le F Contacts C C
3 2 1
To earth ground Polarity is not important From 24 Vdc on fire alarm panel
To supervisory module (i.e. Signature Series CT1 or CT2 module) or 3-IDC traditional zone card.
PHONE
LINE
SERIAL PORT IN
~~
COMMON
1234 56 78 INPUTS
POWER
Communications Bridge
The 3-SM8051-0139 Communication Bridge converts the EST3 External Communications Protocol (ECP) to a variety of commercial protocols that facilitate one-way and two-way communications between EST3 and other in-building systems and sensors using a common protocol via an Ethernet LAN.
3-SM8051-0139 3-SM8700-07 3-SM8700-19 3-SM8704-02 3-SM8700-39 8051-01-ESTPROG Communications Bridge BacNet Driver - ArcNet (Includes ArcNet Card) Driver, Metsys N2 BacNet Driver - Ethernet Dedicated EST Driver Custom Programming Catalog Sheet: 85010-0119 Catalog Sheet: 85010-0119 Catalog Sheet: 85010-0119 Catalog Sheet: 85010-0119 Catalog Sheet: 85010-0119 Catalog Sheet: 85010-0119
24
EST3
Signature Series
Detectors & Bases p. 26 Input/Output Modules p. 28 Pull Stations p. 34 Amplifiers & Power Supplies p.35
Accessories p. 36
Initiating Devices
Device mapping allows the Signature Loop Controller to discover: unexpected additional device addresses; missing device addresses; and, changes to the wiring in the circuit. Most Signature modules use a personality code selected by the installer to determine their actual function. Personality codes are downloaded from the controller during system configuration and are indicated during device mapping. Fast Stable Communication Built-in intelligence means less information needs to be sent between the device and the Signature Loop Controller. Other than routine supervisory polling responses, Signature devices only need to communicate with the controller when they have something new to report . This provides very fast control panel response and allows a lower baud rate (speed) to be used for communication on the circuit. The lower baud rate offers several advantages including: less sensitivity to circuit wire characteristics; less sensitivity to noise glitches on the cable; less emitted noise from the analog wiring; and, twisted or shielded wiring is not required. Testing & Maintenance Automatic self-diagnosis identifies when a Signature device is defective and issues a trouble message. The user-friendly maintenance program shows the current state of each device and other pertinent information. Single devices may be turned off temporarily, directly from the control panel.
Automatic Device Mapping The Signature Loop Controller learns where each devices serial number address is installed relative to other devices on Seamless Security The the circuit . The controller Type of Detector SIGA-MD Motion Detector SIGA-HRS, SIGA-PHS SIGA-IPHS keeps a map of all SignaSIGA-PS SIGA-HFS Photo/ Ion/Photo/ SIGA-IS Ion Photo and the SIGA-SEC2 Security ture Series devices con- Test Fire Heat Heat Heat Open Wood unsuitable very suitable Module bring all the feaoptimum optimum optimum nected to it . The System Wood Pyrolysis suitable unsuitable optimum optimum optimum tures and performance Definition Utility program Smoldering Cotton very suitable unsuitable optimum optimum optimum benefits of the Signature also uses this mapping Poly Urethane Foam very suitable very suitable suitable very suitable optimum n Heptane very suitable suitable optimum optimum optimum line of analog addressable feature. With interactive Liquid Fire, no Smoke unsuitable unsuitable very suitable optimum optimum devices into any applicamenus and graphic supTrue multisensor technology means that a single device can perform optimally under a tion that has a security port, the wired circuits be- wider range of conditions than any single-sensor detector. function. These devices tween each device can be share the same wiring and examined. Layout or As-Built drawing information showing loop controller as fire alarm devices, and do so without the branch wiring (T-taps), device types and their addresses are need for extra risers and associated wiring from the control stored on disk. This takes much of the mystery out of the panel. In fact, EST3 is the only system that offers this kind of installation and makes the preparation of As-Built drawings total co-existence among fire and security devices. fast and very efficient.
25
EST3
SUBMIT
Signature Series
EST3 Network
Initiating Devices
Signature Loop Controller, p.4; Initiating Device Circuit Module, p.5; Hazardous Location Detectors, p. 46 26
EST3
SIGA-MD SIGA-MDS
WIRING DIAGRAM
From Signature loop controller or previous device To next device Data in (+) Data in (-)
SUBMIT
Channel 1 input
TB1
The SIGA-MD is a Passive Infrared (PIR) motion detection module that connects directly to the Signature loop. The module uses adaptive signal processing with gliding focus mirror optics to analyze the size, speed and shape to determine the alarm threshold. A tamper switch notifies the host system when the cover is removed. The unit is designed for wall mounting. Curtains and masks are provided.
Passive Infrared Motion Detector Passive Infrared Motion Detector, swivel mount for 1-gang boxes
DS2 DS1
J1 SENS
Tamper switch. Engaged when the top cover is installed and activates when the cover is removed. Walk test LED Infrared light reflector (7 curtains, 2 masks included). Apply curtain block stickers to limit the amount of detection curtains.
Initiating Devices
Volume setting
Tone setting
24 Vdc in From power supply or previous base + Data in From Signature controller or previous device +
- 24 Vdc out + To next base or EOL relay - Data out To next Signature + device
Notification Appliances
Signature detector base provides room-side wiring terminals and includes a built-in line fault isolator. Models with integral switches allow the detector to be removed from its base without causing the isolator to operate. Mounts to North American one-gang box, 3 or 4-inch octagon boxes, or 4-inch square electrical boxes. Bases for 4-inch square boxes include the SIGA-TS4 Trim Skirt to conceal the electrical box and provide a finished appearance.
SIGA-IB SIGI-IBS SIGA-IB4 (with trim skirt) Isolator Detector Base Catalog Sheet: 85001-0245 Catalog Sheet: 85001-0245
EST3
EST3 Network
Alarm relay output HVAC unit
Supply air
Initiating Devices
SuperDuct detectors feature a unique design that speeds installation and simplifies maintenance. Removable dust filters, conformally coated circuit boards, and optional water-resistant gaskets keep contaminants away from components, ensuring years of trouble-free service. When cleaning is required, the assemblies come apart easily and snap back together in seconds.
Catalog Sheet: 85001-0584 SD-T24 (24) SD-T78 (78) SD-T36 (36) SD-T120 (120)
Intelligent SuperDuct Detector SD-T8 (8) SD-T42 (42) SD-TRM (magnetic) SD-T18 (18) SD-T60 (60) SD-TRM (keyed)
SIGA-LED (Remote alarm LED)) SD-MAG (Test magnet kit) SIGA-SDPCB (PCB/Signature sensor kit)
SD-GSK (cover gasket kit) SD-VTK (Air velocity test kit, stoppers only)
Signature Series
Input/Output Modules
Signature Series
input/output modules are extremely flexible and Plug-in UIOs with motherboard powerful devices that gather analog information from the slave devices connected to them and convert this data into digital signals. They are available in models that mount in standard one- or two-gang electrical boxes, as Standard two-gang mount well as versions that plug into UIO motherboards. The actual function of each module is determined by its installer-selected personality code. This is downloaded to the module from the Signature Loop Controller during system configuration. Because they are intelligent devices, all decisions are made at the module. This allows lower communication speed but very fast control panel response time and less sensitivity to line noise and loop wiring properties. As a result, twisted or shielded wire is not required. Signature Series intelligent input/output modules feature multiple user-set personality codes that define the modules behavior.
Application Voice messages Waterflow Switches Class A indicating and initiating circuits, 2-wire smoke detectors Module Digital Messaging Module Waterflow/Tamper Module Universal Class A/B Module Class B Input Module Class B Initiating Circuits: Door Closers, Fans, Dampers Monitor Module Control Relay Module Programmable I/O Module Telephone Power and Audible/Visual Signal Power Selector, Strobe Synchronization Sounder Base power Supervision of Telephone and Signal Power Fire Suppression Fault detection Signal Module Reversal Relay Module Riser Monitor Module Releasing Module Isolator Module
28
EST3
SUBMIT
Module mounting and installation options Signature Series input/output modules are available in models that feature two mounting options: standard mount and plug-in. Standard mount models are installed to North American two-gang or one-gang electrical boxes, making them ideal for locations where only one module is required. Separate I/O and data loop connections are made to each module. Plug-in UIO modules mount to UIO motherboards. Two- and sixmodule UIO motherboards are available, making them ideal for installations where more than one module is required. Motherboards can accommodate individual risers for each on-board module, or shared risers in any combination with their UIO modules. All wiring connections are made to terminal blocks on the motherboard. UIO assemblies may be mounted in either cabinets, or standard electrical enclosures.
UIO Motherboard
EST3 Network
Plug-in UIO
RM ALA FIRE DULE MO
Initiating Devices
1 2 3 4
MSG 1
The SIGA-MDM Digital Message Module provides custom prerecorded voice messaging. Two standard factory pre-recorded _ + messages are included. Each module can store two 30 second messages in its non-volatile EEPROM memory. A microphone/line-level audio input stereo jack and output stereo _ jack, as well as record and playback switches are conven+ iently located on top of the module. Programming in the Signature Data Controller provides all control instructions; extra wiring for monitoring or controlling circuits is not required. Up to 47 modules can be cascaded together. The SIGAMDM is available as a plug-in module only.
SDC SDC
CLIP ACTIVE CLIP ACTIVE
MSG 2
NORMAL
4 3 2 1
MIC.
MIC.
LINE
P1
LINE
REC.
P2
REC.
LINE
LINE
IN
IN
HEAD
PLAY
HEAD
TB15
PLAY
PHONES
PHONES
TB8
TB9
4 3 2 1
1 2 3 4
1 2 3 4
First
Downstream Jumper
Notification Appliances
SIGA-MDM
SIGA-UM SIGA-MAB
SIGA-CT1/CT2
SIGA-MCT2
UIO Motherboards, p. 32; Signature Loop Controller, p. 4; Initiating Device Circuit Module, p. 5 29
EST3
SUBMIT
EST3 Network
Signal Module
The Signal Module is used to connect, upon command from the loop controller, supervised Class B signal or telephone circuits to their respective power inputs. Models are available with one or two power inputs. These may be either polarized 24 Vdc to operate audible and visual signal appliances, or 25 and 70VRMS to operate audio evacuation speakers and firefighters telephones. The actual function of this module is determined by the personality code selected by the installer. A total of three personalities are available.
SIGA-CC1 SIGA-MCC1 SIGA-CC2 Single Input Signal Module (Two-gang standard mount) Single Input Signal UIO (Plug-in) Module Dual Input Signal Module (Two-gang standard mount) Dual Input Signal UIO (Plug-in) Module
SIGA-CC1/CC2
SIGA-MCC1/MCC2
Catalog Sheet: 85001-0237 Catalog Sheet: 85001-0237 Catalog Sheet: 85001-0237 Catalog Sheet: 85001-0237
Initiating Devices
SIGA-MCC2
SIGA-CR
SIGA-MCR
SIGA-MCRR
SIGA-RM1
SIGA-MRM1
UIO Motherboards, p. 32; Signature Loop Controller, p. 4; Initiating Device Circuit Module, p. 5 ; AB4G Sounder Base, p. 27 30
EST3
SIGA-CC1S SIGA-MCC1S
SUBMIT
SIGA-CC1S
SIGA-MCC1S
Initiating Devices
Input/Output Module
The Input/Output Module is an intelligent device that provides the following modes of operation: Output with monitor input Input/programmable output Input/direct output
SIGA-IO SIGA-MIO Input/Output Module (One-gang standard mount) Input/Output UIO (Plug-in) Module
SIGA-IO
SIGA-MMIO
Notification Appliances
Waterflow/Tamper Module
The SIGA-WTM Waterflow/Tamper Module is a two circuit intelligent module. Circuit 1 is for Class B normally-open waterflow alarm switches. When the input contact is closed for approximately 16 seconds, an alarm signal is sent to the loop controller. Circuit 2 is for Class B normally open dry contact supervisory and tamper switches. When the input contact is closed, an active signal is sent to the loop controller. Conditions on both circuits are latched at the module.
SIGA-WTM Waterflow/Tamper Module (One-gang standard mount)
SIGA-WTM
Isolator Module
The SIGA-IM Isolator Module is an intelligent device that allows part of the Signature data loop to continue operating in the event of a short circuit. The module can be wired into a Class A data loop at any point. A maximum of 96 isolator modules can be installed on one circuit. If a fault occurs, the isolator cuts power to all devices beyond the isolator on the loop. Once activated, the line fault isolator continuously checks the faulted side of the loop to determine if the short still exists. When the fault is cleared, the module automatically restores the entire data loop to its normal condition.
SIGA-IM Fault Isolator Module (Two-gang standard mount)
SIGA-IM
Monitor Module
The SIGA-MM1 is a single-circuit intelligent module that includes a Class B normally-open dry contact. This is used for monitoring input from devices such as fans, dampers, and doors. When the input contact is closed, an active signal is sent to the loop controller. The active condition is not latched at the module.
SIGA-MM1 Monitor Module (One-gang standard mount)
SIGA-MM1
31
EST3
SUBMIT
EST3 Network
Initiating Devices
Data Out
UIO motherboards mount inside the MFC-A cabinet Individual Riser 1 Input to each SIGA-UIO module or other suitable UL-listed electrical enclosure. Each MFC-A will hold one UIO2R motherboard or one UIO6 or UIO6R motherboard complete with their full complement of modules.
Universal Input/Output Module Board with Riser Inputs 2 Module Positions Universal Input/Output Module Board with Riser Inputs 6 Module Positions Universal Input/Output Module Board 6 Module Positions
Related Equipment
MFC-A 27193-11 27193-16 27193-21 27193-26 235196P SIGA-MP1 SIGA-MP2 SIGA-MP2L Multi-function Cabinet (for UIO and Releasing modules) Surface Mount Box - Red, One-gang Surface Mount Box - White, One-gang Surface Mount Box - Red, Two-gang Surface Mount Box - White, Two-gang Bi-polar Transient Protector (use with all Signal Modules) Signature Module Mounting Plate, 1 footprint Signature Module Mounting Plate, 1/2 footprint Signature Module Mounting Plate, 1/2 extended footprint
32
EST3
Dual Input Security Module
SUBMIT
The SIGA-SEC2 is an intelligent analog addressable device used to connect one or two normally-open or normally-closed dry contact security circuits. The actual function of this module is determined by the personality code selected by the installer. This code is downloaded to the module from the Signature loop controller during system configuration. The input module gathers data from the devices connected to it and converts them into digital signals. The modules on-board microprocessor WIRING analyzes the signal and decides whether or not to input an alarm, tamper, or maintenance condition. The module is housed in a small thermo-plastic enNotes closure designed for surface mounting.
From Signature Loop Controller or previous device Data In (+) Data In (-) Tamper Alarm Channel 1 input Alarm Tamper 6 5 To next Signature device Signature loop TB1 SIGA-SEC2
SIGA-SEC2
Releasing Module
The Signature Series Releasing Module (SIGA-REL) is an analog addressable module that works with fire suppression systems designed to release extinguishing gas such as Halon. Its primary function is the control of sprinkler preaction routines and the initiation of suppression system deluge functions. The module is easily configured in the field and offers a wide range of options that prevent the unnecessary release of extinguishing agent. The SIGA-REL is a network component consisting of: Two supervised release circuits Two supervised pre-release circuits One supervised manual release input circuit One supervised abort circuit for N/O abort switch One first alarm output relay (Form C Contact)
Abort Manual Release
The releasing module includes a built-in timer that inhibits the deluge function during the pre-action routine. One of four pre-action routines, may be selected by means of dip-switches on the module. The duration of automatic and manual time delays, as well as the abort time settings are also selectable with dip-switches. The SIGA-REL mounts inside an MFC-A cabinet or other suitable UL-listed electrical enclosure. Each MFC-A will hold one SIGA-REL. Available releasing module accessories include dedicated pull stations, abort switches and service switches. Together with the SIGA-REL, they comprise a complete fire suppression package.
SIGA-REL RELA-ABT RELA-SRV 276A-REL 278A-REL RELA-EOL Analog addressable releasing module Abort station Service disconnect station Manual releasing station (single-action) Manual releasing station (double-action) Polarized end-of-line relay
Security/Access controller, p. 15 33
+ + _
Basic Security
or
or
Tamper
Alarm
Initiating Devices
Tamper
TB2
Channel 2 input
Notification Appliances
_ + _ +
24 Vdc in 24 Vdc out
TB1
+ _ + _
DS1
SIGA-REL
TB4 _ _ + +
Catalog Sheet: 85001-0531 Catalog Sheet: 85001-0531 Catalog Sheet: 85001-0531 Catalog Sheet: 85001-0531 Catalog Sheet: 85001-0531 Catalog Sheet: 85001-0531
EST3
SUBMIT
EST3 Network
Signature Series
Signature Series manual pull stations are configured for Class B IDC operation. When the stations pull lever is operated, an alarm signal is sent to the loop controller. The alarm condition is latched at the station.
Initiating Devices
REAR VIEW
TB2
8 7
One Stage Fire Alarm Station, English Markings Two Stage (Pre-signal) Fire Alarm Station, English Markings Single Station Call Point (Europe only) GA Key for pre-signal station 20 Break-rods for SIGA-270 series Surface Mount Box, Red for SIGA-270 series
Catalog Sheet: 85001-0279 Catalog Sheet: 85001-0279 Catalog Sheet: 85001-0349 Catalog Sheet: 85001-0279 Catalog Sheet: 85001-0279 Catalog Sheet: 85001-0279
REAR VIEW
TB2
8 7
TB1
Double Action (One Stage) Fire Alarm Station, English Markings Surface Mount Box, Red for SIGA-278 series 20 Break-rods for SIGA-278 series
ADA Manual Station Relocator, p. 37; Stopper II, p. 37; Hazardous Location Pull Station, p. 46 34
EST3
Signature Series
SUBMIT
Audio Amplifiers
Shield Optional
Initiating Devices
Signature device From Signature Series amplifiers are high-effi- SignalChannel 1 Output Return Source Class A Only ciency switch mode audio amplifiers 1Vrms or 25Vrms From Output of From Backup Amp available in 30 and 50 watt sizes. Amplifi- SignalChannel 2 Source 1Vrms or 25Vrms ers have two input channels supporting To Backup Input To Next Amp of Next Amp Output Voltage dual channel or single channel audio ap- Channel 2 Input Selection Jumper To 24 VDC To Next From Previous plications. Signature amplifiers are ide- Signature Device Signature Device ally suited for distributed audio applications and small centrally banked applications. The audio output is configurable as 25VRMS or 70VRMS in Class B or Class A wiring configurations. Speakers can connect directly to the output of the amplifier or the amplifier output can run as an audio riser to Signature modules where speaker zone selection is made. Each amplifier has a built-in 1kHz tone generator and provision for a back up amplifier. On-board status LEDs provide quick visual indication of amplifier status.
Notification Appliances
SIGA-AA30 SIGA-AA50
The SIGA-APS is a switch-mode power supply that provides additional power for any fire alarm control panel Line 1 Line 2 24 VDC @ 3.2A that includes a Signature Data Circuit . The SIGA-APS Ground 24 VDC @ 3.2A Hot mounts with local fire alarm equipment or may be Neutral SIGA OUT SIGA IN mounted remotely to supply power to signaling devices, Ground amplifiers or system equipment. The power supply comTo Battery municates with the main control panel over the Signature Data Circuit. This eliminates the need to mount additional monitoring equipment when the power supply is mounted remote from the main control panel.
SIGA-APS SIGA-APS-220
Intelligent Auxiliary Power Supply 120Vac 50/60Hz Intelligent Auxiliary Power Supply 220Vac 50/60Hz
EST3
SUBMIT
EST3 Network
Signature Series
Accessories
Signature Detector Guard
Initiating Devices
Constructed of sturdy 16-guage steel, the SIGA-DG Smoke Detector Guard is designed to protect SIGA-IPHS 4D and SIGA-PS smoke detectors from damage or tampering. The advanced computer-designed louver system allows smoke detectors to be installed at their listed spacing and has no effect on operating sensitivity.
SIGA-DG SIGA-DGSA
SIGA-DMP
Remote LED
The remote LED connects to the SIGA-SB or SIGA-SB4 Standard Base. It features a North American size one-gang plastic faceplate with a white finish and red alarm LED.
SIGA-LED
Trim Skirt
Use the SIGA-TS Trim Skirt to give Signature detectors a finished look and hide surface imperfections around the detectors base. Supplied with all four-inch detector bases, the SIGA-TS4 can also be ordered separately. Use the black model with SIGA-IPHSB.
Detector Trim Skirt (white) Detector Trim Skirt (black) Detector Trim Skirt (white) for 4-inch box
EST3
Manual Station Relocator
SUBMIT
The Manual Station Relocator is designed to lower the height of a fire alarm pull station to meet ADA requirements. Most existing pull stations are mounted 60 inches (1524mm) or higher above the floor. The Relocator lowers the height to 48 inches (1220mm) without the need for pulling new wires or moving the existing electrical box.
Initiating Devices
RR-32RL
Stopper II
This unique device helps prevent false alarms without restricting legitimate ones. It consists of a tamper-proof clear LEXAN polycarbonate shield and frame that fits easily over manual pull stations. When lifted, it sounds a piercing warning horn.
Notification Appliances
STI-1130 (Surface) STI-1230 (Surface) STI-3004 (Conduit Insert) STI-3003 (Conduit Gasket)
Catalog Sheet: 85001-0491 Catalog Sheet: 85001-0491 Catalog Sheet: 85001-0491 Catalog Sheet: 85001-0491
EST3
EST3 Network
Notification Appliances
Notification Appliances
Genesis Speakers, p. 40
GE Security notification appliances are high-performance devices finely tuned to deliver maximum output in exchange for the lowest possible current draw. Covering the entire spectrum of life safety applications, these devices are durable, dependable, and virtually maintenance-free. And they support a wide range of mounting options that make them ideal for new construction and retrofit applications alike.
Initiating Devices
Visual/Audible Signals EST3 visual/audible signals include a wide range of exquisitely engineered strobes in combination with horns, speakers, and chimes. The Genesis and Enhanced Integrity families of visual/audible signals feature UL 1971 listed strobes that exceed Americans with Disabilities Act (ADA) requirements. All GE Security strobes are UL 1971 listed as visual signaling devices for the hearing impaired and surpass the latest UL sychronization requirements when used with a Signal Master accessory (see page 41) or the Signature Series Synchronization Output Module (see page 31). Genesis strobes represent a breakthrough in visual signaling technology that provides outstanding light distribution characteristics in a sleek low-profile design. Enhanced Integrity devices offer a full range of indoor and outdoor, and wall and ceiling rated options, including strobes in combination with horns, speakers and chimes. Typical Wiring All notification appliances may be configured for Class A or Class B wiring. Genesis combination horn-strobes, when used with the innovative Signal Master Module, support independent horn control over a single pair of wires and precision synchronization that exceeds UL requirements. This reduces wiring time while meeting the requirements of even the most demanding application.
Class B Notification Appliance Circuit with Genesis Signals and Signal Master for independent sounder and strobe control and synchronisation.
Notification Appliances
2 Pr.
1 Pr.
Notification Appliance Circuit Class B with separate strobe and horn circuits
2 Pr.
1 Pr.
Outdoor
Outdoor
Outdoor
Ceiling
Ceiling
Ceiling
Ceiling
Ceiling
Ceiling
Ceiling
Ceiling
38
Ceiling
Indoor
Indoor
Indoor
Indoor
Indoor
Wall
Wall
Wall
Wall
Wall
Wall
Wall
Wall
Wall
EST3
Genesis Series
Notification Appliances
SUBMIT
Notification Appliances
Genesis Horns and Horn-strobes reach output levels as high as 99 dB and features a unique multiple frequency tone that results in excellent wall penetration and an unmistakable warning of danger. Horns may be configured for either coded or non-coded signal circuits. They can also be set for low dB output with a jumper cut that reduces horn output by about 5 dB.
G1-HDVM G1R-HDVM G1F-HDV1575 G1RF-HDV1575 G1-HD G1R-HD G1-P G1R-P Horn-Strobe (15, 30, 75, or 110 cd output, high or low dB), white Horn-Strobe (15, 30, 75, or 110 cd output, high or low dB), white Horn-Strobe (fixed 15/75 cd output, high or low dB), white Horn-Strobe (fixed 15/75 cd output, high or low dB), red Temporal Horn (high or low dB output), white Temporal Horn (selectable high or low dB output), red Steady Horn (not compatible with Genesis Signal Master), white Steady Horn (not compatible with Genesis Signal Master), red Catalog Sheet: 85001-0573 Catalog Sheet: 85001-0573 Catalog Sheet: 85001-0573 Catalog Sheet: 85001-0573 Catalog Sheet: 85001-0573 Catalog Sheet: 85001-0573 Catalog Sheet: 85001-0573 Catalog Sheet: 85001-0573
Genesis chimes and chime-strobes produce a pleasing mellow tone. When steady (non-stroked) voltage is applied, the chime automatically pulses at 60 strokes per minute, or may be field-configured for temporal output. When installed with a GIM Signal Master Module, the chime may also be field-configured for coded operation, which enables the chime output to match the rate that voltage is applied to the circuit. The chimes 79 dBA (peak) output level makes this device suitable for many applications. Chimes may be set for low dB output with a jumper cut that reduces sound output by about 5 dB.
G1-CVM G1R-CVM G1-C G1R-C Genesis Chime-Strobe (15, 30, 75, or 110 cd output, high or low dB), white Catalog Sheet: 85001-0574 Genesis Chime-Strobe (15, 30, 75, or 110 cd output, high or low dB), red Catalog Sheet: 85001-0574 Genesis Chime (selectable high or low dB output), white Genesis Chime (selectable high or low dB output), red Catalog Sheet: 85001-0574 Catalog Sheet: 85001-0574
To specify housings with FIRE markings, insert an F before the hyphen in the model number. For submittal purposes, write an F in the Submit box instead of placing a checkmark there.
Genesis Trim Plate (for 2-gang or 4" square boxes) with "FIRE" markings, white Catalog Sheet: 85001-0573 Catalog Sheet: 85001-0573
G1RT-FIRE Genesis Trim Plate (for 2-gang or 4" square boxes) with "FIRE" markings, red
39
EST3
SUBMIT
Notification Appliances
Genesis Series
Initiating Devices
EST3 Network
#18 - #12 AWG terminals ideal for long runs, existing wiring
To listed fire alarm control panel (supervised amplifier signal circuit 25.2 or 70.7V rms)
Candela and wattage settings remain clearly visible even after final installation.
+
+
+
+
Polarity shown in alarm condition
Notification Appliances
To listed fire alarm control panel (supervised signal circuit 20-24 Vdc)
Genesis speakers are available with white or red housings and with FIRE markings.
Genesis Speakers and speaker-strobes ... G4-S2 (white) G4-S2VM (white) G4-S7 (white) G4-S7VM (white) G4B (white) G4R-S2 (red) G4R-S2VM (red) G4R-S7 (red) G4R-S7VM (red) G4RB (red) Multi-wattage 25 Volt Speaker Catalog Sheet: 85001-0549
All speakers feature selectable , , 1, or 2 watt operation. Strobes feature 15, 30, 75, or 110 candela output
SPKR
S+
S-
Multi-candela/wattage 25 Volt Speaker-strobe Catalog Sheet: 85001-0549 Multi-wattage 70 Volt Speaker Catalog Sheet: 85001-0549
Multi-candela/wattage 70 Volt Speaker-strobe Catalog Sheet: 85001-0549 Surface mount box Catalog Sheet: 85001-0549
SPKR
S+
S-
EST3
Genesis Series
Notification Appliances
SUBMIT
GCF-S2VMH (marked FIRE) Multi High-cd/wattage 25 V Spkr-strobe Catalog Sheet: 85001-0556 GCF-S7VM (marked FIRE) Multi-cd/wattage 70 V Spkr-strobe Catalog Sheet: 85001-0556
Notification Appliances
GCF-S7VMH (marked FIRE) Multi High-cd/wattage 70 V Spkr-strobe Catalog Sheet: 85001-0556 GCF-VM (marked FIRE) GCF-VMH (marked FIRE) GCF-HDVM (marked FIRE) Multi-cdStrobe Multi High-cdStrobe Multi-cdHorn-Strobe Catalog Sheet: 85001-0557 Catalog Sheet: 85001-0557 Catalog Sheet: 85001-0559 Catalog Sheet: 85001-0559
All speakers feature selectable , , 1, or 2 watt operation. All horns feature high or low dB output. Multi-Candela Strobes feature 15, 30, 75, or 95 candela output. Multi High-Candela Strobes feature 95, 115, 150, or 177 candela output.
Signal Master
The Signal Master is a simple-to-use accessory that adds enhanced features to Genesis and Integrity strobes and Horn-Strobes. It is a dualpurpose module that provides UL 1971 required precision synchronization for connected Integrity and Genesis strobes, and independent control for connected Genesis Horns over a single pair of wires. Two methods of Horn control are available: traditional Horn silence; or, normally-closed contact. Both methods may be used to silence Horns without turning off strobes on the same circuit. Two models are available. The Genesis piggyback model doesnt require a separate electrical box. It simply snaps to the back of the first G1 signal on the circuit. The remote mount model mounts in a North American 2 inch (64 mm) deep one-gang box.
G1M G1M-RM Genesis Signal Master Snap-on (piggyback) Genesis Signal Master Remote 1-Gang Mount
41
EST3
SUBMIT
Notification Appliances
Mounting Plate
EST3 Network
First Device
Horn/Strobe
H+ HS+ S-
Horn/Strobe
H+ HS+ S-
Initiating Devices
Temporal Horn-Strobe, 15/75cd Catalog Sheet: 85001-0341 Temporal Horn-Strobe, 110cd Catalog Sheet: 85001-0341
Notification Appliances
757-7A-RS25W (White) 25 V Re-entrant Speaker-Strobe, 15/75cd Catalog Sheet: 85001-0317 757-3A-RS25W (White) 25 V Re-entrant Speaker-Strobe, 30cd Catalog Sheet: 85001-0317
757-8A-RS25W (White) 25 V Re-entrant Speaker-Strobe, 110cd Catalog Sheet: 85001-0317 757-1A-R70W (White) 70 V Re-entrant Speaker Catalog Sheet: 85001-0317
757-7A-SS70W (White) 75 V Re-entrant Speaker-Strobe, 15/75cd Catalog Sheet: 85001-0317 757-3A-RS70W (White) 75 V Re-entrant Speaker-Strobe, 30cd Catalog Sheet: 85001-0317
EST3
Notification Appliances
SUBMIT
Audible Signals
Fire Alarm Bells
GE Security fire alarm bells are of the underdome type with heavy-duty mechanisms. Gongs are made of selected alloy steel to generate the loud, resonant tones. For weatherproof application, optional surface weatherproof backboxes are available.
323D-10AW (Grey) 439D-6AW (Grey) 439D-10AW (Grey) 323D-10AR (Red) 439D-6AR (Red) 439D-10AR (Red) 10-inch Single Stroke, Diode 20-24Vdc Catalog Sheet: 85001-0333 6-inch Vibrating, Diode 20-24Vdc 10-inch Vibrating, Diode 20-24Vdc Catalog Sheet: 85001-0333 Catalog Sheet: 85001-0333
Notification Appliances
Firefighters Telephones
Catalog Sheet: 85001-0423
Firefighters telephones are typically installed in corridors, lobbies, mechanical rooms, stairways, or other stategic locations. When lifted from its cradle, or plugged into a suitable wall jack, the handset activates audible and visible signals at the EST3 control panel.
6833-1 6830-3 (black) 6830-1 6830-5A 6830-6A 6831-1 (break-glass) 6831-3 (break-glass) 6830-NY-F 6830-NY-S 6832-1 Portable Handset Receptacle 1-gang Stainless-steel Faceplate for use with 6830-3 6700-0061 (red) Handset Assembly - Red Handset Assembly - Red, 3-state operation, Push to Talk button Handset Assembly - Red, 3-state operation, Push to Talk button, Armoured cable 6831-2 (non-break glass) 6831-4 (non-break glass) Warden Station - Flush. Warden Station - Surface Universal wallbox - Compatible with all fixed telephone handsets. Flush or Surface mount. Frontplate Flush, Red finish, c/w 2 keys Frontplate Surface, Red finish, c/w 2 keys Portable Firefighters Telephone
EST3
SUBMIT
Notification Appliances
EST3 Network
Accessories
Bell/Strobe Plate
The bell/strobe plate is ideal for renovation and retrofit projects, and new construction. It is equipped with an GE Security self-synchronizing strobe and is designed to allow on-site mounting of ESTs 439 series Vibrating Bell, providing instant conversion to Bell/Strobe audible/visual signal appliances. The strobe is designed for 20 to 24Vdc operation and must be connected to signal circuits which output a constant (not pulsed) voltage. A diode is used to allow full signal circuit supervision.
403-5A-R (15 cd) 403-7A-R (15/75 cd) 403-3A-R (30 cd) 403-8A-R (110 cd) Catalog Sheet: 85001-0441
Initiating Devices
Notification Appliances
LKW-4 (Wall orientation) LKW-5 (Wall orientation) LKW-6 (Wall orientation) LKW-7 (Wall orientation) LKW-8 (Wall orientation) LKW-9 (Wall orientation)
Mounting Accessories
Integrity Temporal Horn, Horn/strobe 757A-SB Surface Box, Red, Indoor 757A-SBW Surface Box, White, Indoor 757A-WB Weatherproof Box, Red, Surface 757A-WBW Weatherproof Box, White, Surface 757A-BDF Bi-directional Frame, Red 757A-BDFW Bi-directional Frame, White 757A-RR2 Two-gang Retrofit Ring, Red 757A-RR2W Two-gang Retrofit Ring, White Integrity Speakers, Speaker/strobes 960A-4SF Flush Box, Indoor 757A-SB Surface Box, Red, Indoor 757A-SBW Surface Box, White, Indoor 757A-BDF Bi-directional Mounting Frame, Red 757A-BDFW Bi-directional Mounting Frame, White 757A-RR Four-inch Retrofit Ring, Red 757A-RRW Four-inch Retrofit Ring, White Integrity Re-entrant speakers, Speaker/strobes 960A-4SF Flush Box, Indoor 757A-SB Surface Box, Red, Indoor 757A-SBW Surface Box, White, Indoor 757A-WB Weatherproof Box, Red, Surface 757A-WBW Weatherproof Box, White, Surface 757A-BDF Bi-directional Mounting Frame, Red 757A-BDFW Bi-directional Mounting Frame, White Integrity Chimes, Chime/strobes 757A-SB Surface Box, Red, Indoor 757A-SBW Surface Box, White, Indoor 757A-BDF Bi-directional Mounting Frame, Red 757A-BDFW Bi-directional Mounting Frame, White Genesis Signals 27193-11 27193-16 G4RB G4B
Horn-strobe Surface Box, Red, Indoor Horn-strobe Surface Box, White, Indoor Speaker Surface Box, Red, Indoor Speaker Surface Box, White, Indoor
8-inch Square Speakers 960A-8SF Square Flush Box, Indoor 960A-8SS Square Surface Box, Indoor 8-inch Round Speakers 960A-8RF Round Flush Box, Indoor 4-inch Round Speakers 960A-4RF Round Flush Box, Indoor Horn/siren Combination 349 Weatherproof Backbox Fire Alarm Bells and CS-405 Series 449 Weatherproof Backbox Genesis G4B Speaker Surface Box
44
EST3
Notification Appliances p. 47
GE Security hazardous location devices provide reliable life safety protection and emergency signaling in areas where atmospheres could become harsh or explosive. All hazardous location devices are UL rated under the full range of classifications set out in the National Electrical Code. The following classification definitions are an interpretive summary based on the 1996 edition of the National Electrical Code (NEC, NFPA 70). Refer to the latest editions of NFPA 497M, NFPA 70 and the UL Hazardous Location Equipment Directory for current and more detailed information. For more information on NEMA classifications, refer to NEMA Standards Publication No. 250.
Divisions
The Location Classes are broken down by the NFPA into Divisions 1 and 2, defining different levels of risk. In general, the risk of there being a hazardous presence of flammable/ combustible/ignitable materials is higher for Division 1 than for Division 2. The specifics differ between the three classes (I, II and III). Equipment suitable for Division 1 is also suitable for Division 2 locations.
Groups
Class I and II locations are divided by the NFPA into Group designations identifying specific gases, vapors and dusts by characteristic similarities that relate to specific equipment construction requirements. Class III locations are not divided into separate group designations. Class I Groups Group A. Atmospheres containing acetylene. Group B. Atmospheres containing hydrogen, fuel and combustible process gases containing more than 30 percent hydrogen by volume, or gases or vapors of equivalent hazard such as butadiene, ethylene oxide, propylene oxide, and acrolein. Group C. Atmospheres such as ethyl ether, ethylene, or other gases or vapors of equivalent hazard. Group D. Atmospheres containing acetone, ammonia, benzene, butane, cyclopropane, ethanol, gasoline, hexane, methanol, methane, natural gas, naphtha (petroleum), propane, or gases or vapors of equivalent hazard. Class II Groups Group E. Atmospheres containing combustible metal dusts, including aluminum, magnesium, and their commercial alloys, or other combustible dusts whose particle size, abrasiveness and conductivity present similar hazards in the use of electrical equipment. Group F. Atmospheres containing combustible carbonaceous dusts, including carbon black, charcoal, coal, or dusts that have been sensitized by other materials so that they present an explosion hazard. Group G. Atmospheres containing combustible dusts not included in Group E or F, including flour, grain, wood, plastic, and chemicals.
EST3
SUBMIT
EST3 Network
Initiating Devices
Weather/Explosion proof heat detectors
Series 500 heat sensors are designed for use in applications requiring protection against weather, moisture (internal condensation), and explosive atmospheres. Heat sensors are normally-open devices designed to close an electrical circuit upon activation. Sensors use dual action, electric fire detection thermostats that employ two independent methods of detection: rate-of-rise and fixed temperature.
EPBMPB (explosionproof/ moistureproof) WPBMPB (weatherproof/ moistureproof)
Weather/Moisture Proof Models (WPBMPB) consist of a cast metal box, gasket and special steel cover plate integrated with the sensor. A crossed wire guard is added for extra protection. The emerging wire points are sealed with epoxy, increasing resistance to moisture. The cast metal box has four wire entrances for -inch rigid conduit. The unit offers combined protection against weather and condensation in the conduit.
Initiating Devices
Explosion/Moisture Proof Models (EPBMPB) consist of a cast metal box, cover plate and modified 500 Series sensor. The backbox has two opposing wire entrances threaded for -inch rigid conduit. The box, cover and base are precision machined for extremely close tolerance fit. Explosion proof models are available in a moisture proof version, which includes a moisture-resistant gasket.
WPBMPB501 Weather/Moistureproof rate-of-rise and fixed temp. sensors (136F/58C) Explosion/Moistureproof rate-of-rise and fixed temp. sensors (136F/58C) Weather/Moistureproof rate-of-rise and fixed temp. sensors (190F/88C) Explosion/Moistureproof rate-of-rise and fixed temp. sensors (190F/88C) Weather/Moistureproof fixed temperature sensor (136F/58C) Explosion/Moistureproof fixed temperature sensor (136F/58C) Weather/Moistureproof fixed temperature sensor (190F/88C) Explosion/Moistureproof fixed temperature sensor (190F/88C) Catalog Sheet: 85001-0393 Catalog Sheet: 85001-0393 Catalog Sheet: 85001-0393 Catalog Sheet: 85001-0393 Catalog Sheet: 85001-0393 Catalog Sheet: 85001-0393 Catalog Sheet: 85001-0393 Catalog Sheet: 85001-0393
Notification Appliances
46
EST3
Class I, II, or III locations
106DEXPSTC-FJ 106DEXBSTC-FJ
SUBMIT
Notification Appliances
Hazardous Location, weatherproof Strobes
106DEX hazardous location strobes are diode polarized life safety signaling appliances designed for installation in hazardous environments. Rigid specifications and state-of-the-art technology provide for high visual output and low maintenance. Strobes are UL 1971 listed as visual signaling appliances for the hearing impaired in non-sleeping areas and may be used to meet ADA requirements.
Hazardous Location/ Weatherproof Strobe Pendant Mount Hazardous Location/ Weatherproof Strobe Bracket Mount Catalog Sheet: 85001-0547 Catalog Sheet: 85001-0547
430D series of hazardous location bells are diode-polarized, heavy duty fire bells for use in life safety applications where a diode supervised signal is required. They can be mounted to any solid surface using two 3/8 inch (10 mm) bolts and the supplied mounting brackets or to a rigid conduit. The integral explosion-proof housing is mechanically terminated to accept a standard 3/4 inch -14 National Pipe Taper (NPT) nipple.
439DEX-6AW (6") 438DEX-6N5 (6") 439DEX-8AW (8") 438DEX-8N5 (8") 439DEX-10AW (10") 438DEX-10N5 (10") Bell 24 Vdc Bell 120 Vac Catalog Sheet: 85001-0399 Catalog Sheet: 85001-0399
888D and 889D hazardous location horns are diode-polarized, heavy duty, high decibel vibrating horns intended for use in life safety systems in hazardous (classified) locations. These horns may be mounted to any solid surface using two bolts. Each unit is supplied with a sealing fitting for a 3/4 inch -14 National Pipe Taper (NPT) nipple, and wire leads for the electrical connection to the life safety system notification appliance circuit.
888D-N5 (120 Vac) 889D-AW (24 Vdc) Horn 120 Vac Catalog Sheet: 85001-0397
47
EST3
SUBMIT
EST3 Network
Door Holders
Electromagnetic Door Holders
GE Security electromagnetic door holders keep doors open until signaled by the fire alarm system, a heat detector, a smoke detector, or an electrical switch. Door holders should be installed wherever doors may be effectively used to confine smoke and fire, or where the release of a self-closing door from a remote location is required. Fail-safe operation is an inherent feature of these door holders. If power fails, doors are released automatically, but may be opened or closed manually at any time. All units are free of moving parts, are self-contained, and require no maintenance. Door holders have a holding force of approximately 15-25 Lbf (66-111N).
1502-AQN5 (Double Door) Floor Mounted Catalog Sheet: 85001-0421
Initiating Devices
1501-AQN5 (Single Door) 1504-AQN5 (Long Catch Plate) 1508-AQN5 (Surface) 1500-1 (1.5 Extension) 1500-7 (5.25 to 7.5 Extension)
1505-AQN5 (Short Catch Plate) Flush Wall Mounted Catalog Sheet: 85001-0421 1505-AQN9 (Completely flush) Wall Mounted 1500-2 (2.5 Extension) 1500-12 (7.5 to 12 Extension) CS2598-5 (long) Catch Plate Catch Plate Catalog Sheet: 85001-0421 Catalog Sheet: 85001-0421 Catalog Sheet: 85001-0421 Catalog Sheet: 85001-0421
Notification Appliances
CS2595-5 (short)
Replacement Armature
Relays
Four-Voltage SPDT/DPDT Control Relays
MR Series multi-voltage control relays are ideal for applications where local contacts are required for system status, remote contacts, or for control of electrical loads and general purpose switching. They are suitable for use with HVAC temperature control, fire alarm, security, energy management, and lighting control systems. Relays provide 10-Amp contacts, which may be operated by one of four input control voltages. Each relay position contains a red LED that indicates the relay coil is energized. Relays may be snapped apart from a standard four-module assembly and used independently.
MR-101/T (with mounting hardware) MR-104/T (with mounting hardware) MR-201/T (with mounting hardware) MR-204/T (with mounting hardware) MR-101/C (in metal enclosure) Single SPDT relay Catalog Sheet: 270062
MR-104/C (in metal enclosure) 4-position SPDT relay Catalog Sheet: 270062 MR-201/C (in metal enclosure) Single DPDT relay Catalog Sheet: 270062
MR-204/C (in metal enclosure) 4-position DPDT relay Catalog Sheet: 270062
MR-199AX-14/C (in metal enclosure) Power Relay 120 VDC Catalog Sheet: 270065
48
EST3
SUBMIT
SPDT Relays
Single-pull/double-throw relays are ideal for applications where local or remote contacts are required for control of electrical loads. They are suitable for use with HVAC, temperature control, fire alarm, security, energy management, and lighting control systems. Each relay position contains a high-intensity LED which, when illuminated, indicates the relay coil is energized. Individual relay circuits may be snapped apart from standard four- or eight-position modules, and are also available in a single-circuit configuration. The common power to each relay position is bussed on the printed wiring board, which permits power to be connected only once per multi-position module.
MR-604/S (with mounting spacers) 4-position SPDT relay Catalog Sheet: 270061 MR-608/S (with mounting spacers) 8-position SPDT relay Catalog Sheet: 270061
MR-804/S (with mounting spacers) 4-position SPDT relay Catalog Sheet: 270063 MR-808/S (with mounting spacers) 8-position SPDT relay Catalog Sheet: 270063
MR-704/S (with mounting spacers) 4-position SPDT relay Catalog Sheet: 270064 MR-708/S (with mounting spacers) 8-position SPDT relay Catalog Sheet: 270064
PAM-1
EST3
EST3 Network
Submittal Guide
Index
Model Description Lit #Guide P/N
85010-0051 85006-0049 85006-0047 85006-0048 85006-0046 85010-0095 85010-0071 85010-0135 85010-0055 85010-0129 85010-0103 85010-0069 85006-0037 85010-0117 270020 85010-0061 85010-0063 85010-0105 270041 85010-0085 85010-0057 85010-0089 85010-0011 270038 270009 85010-0059 85010-0111 85010-0087 85005-0107 85010-0067 85001-0309 85001-0495 85001-0425 85010-0107 85006-0057 85006-0058 85006-0059 85010-0131 85010-0075 85006-0045 85010-0101 85010-0113 85010-0115 85010-0109 85010-0098 85001-0528 85001-0523 85001-0521 85001-0522 85001-0520 85001-0524 85001-0525 85005-0111 2 9 9 9 15 3 8 8 8 4 5 11 10 11 22 5 13 14 14 14 14 35 14 14 23 20 20 35 21 19 44 44 44 7 12 12 12 6 6 24 22 23 24 15 16 16 17 17 17 17 18 18 18
Model
Description
Control Panel EST3 EST3 Fire/Security/Access Control Control and Annunciation FireWorks Software FireWorks Overview (Fire only) FireWorks Software FireWorks Overview (Synergy) FireWorks Hardware FireWorks Specifications KPDISP Keypad/Display 3-CPU3/3-RS485/232Central Processor Unit Module 3-LCD 8 Line Liquid Crystal Display Module 3-LCDXL 21 Line Liquid Crystal Display Module 3-LDSM Control Display Modules 3-SSDC1 Single Signature Driver Controller 3-AADC1 Addressable-Analog Device Controller 3-LCDANN, 3-xxANN Remote Annunciators ENVOY Graphic Annunciator 3-VDUT Video Display Utility for Text PT-1S/PT-1P System Event Printer 3-IDC8/4 Hardwired Module Audio 3-ASU series Audio and Telephone Masters 3-REMICA, 3-REMICP Remote Microphone ATP Amplifier Terminal Panel EST3 Series Central Banked Amplifiers 3-ZAxxx Series Audio Amplifiers SIGA-AA30, -AA50 Intelligent Audio Amplifiers 1B3125 Audio Power Amplifier 125 Watts URSM Universal Riser Supervisory Module CDR-3+B114/MTM Coders Power Supplies 3-PPS/M, 3-BPS/M EST3 Power Supplies 3-BTSEN Battery Distribution Kit SIGA-APS Intelligent Auxiliary Power Supply BPS6/BPS10 Remote Booster Power Supplies Enclosures and Wallboxes 3-CAB, 3-RCC EST3 Cabinets and Chassis 348/349/449 Weatherproof Backboxes 27193 Series Surface Mount Boxes Misc. Bell AccessoriesYard Hood, Full Cast Grid, Grille Communications 3-MODCOM Modem Communicator NETSW-EIS6-MM Ethernet Network Switching Hub NETCOM-1F Ethernet Network Interface NETCOM-1S Ethernet Network Interface 3-FIBMB Fiber Optic Communications Interface 3-OPS Off Premise Signaling Module API-8/232ME Alphanumeric Pager Interface RDU/RDUEU-E Remote Diagnostic Utility Program 3-NSHM1, 3-NSHM2 Network Short Haul Modem GFD Ground Fault Detection Module Security and Access Control 3-SAC Security/Access Control Module ACDB Access Control DataBase Software CRC, CRCXM Card Reader Controller CR-6005 Proximity Card Reader CR-5365 Proximity Card Reader CR-5395, C-5395x Proximity Card Reader CR-5355 Proximity Card Reader PC-1326, PC-1386 Proximity Access Cards PK-1346, PT-1391 Proximity Key Fobs and Tags 24DC12 12 Vdc Security Interface
Intelligent Input/Output Devices SIGA-UIO Series Universal I/O Module Motherboards 85001-0365 SIGA-CC1S/MCC1S Synchronization Output Module 85001-0543 SIGA-IO/MIO Input/Output Modules 85001-0533 SIGA-RM1/MRM1 Riser Monitor Modules 85001-0535 SIGA-CR/-MCR Series Control Relay Modules 85001-0239 SIGA-CT/-MCT Series Input Modules 85001-0241 SIGA-MM1/-WTM Input Modules 85001-0297 SIGA-CC/-MCC Series Signal Modules 85001-0237 SIGA-MDM Digital Message Module 85001-0363 SIGA-UM/-MAB Class A/B Modules 85001-0275 SIGA-IM Isolator Module 85001-0271 Intelligent Initiating Devices SIGA-SEC2 Dual Input Security Module 85001-0527 SIGA-MD/-MDS PIR Motion Detector Module 85001-0526 SIGA-270/-278 Manual Pull Stations 85001-0279 SIGA-IPHS Intelligent 4D Multisensor Detector 85001-0245 SIGA-PHS Intelligent 3D Multisensor Detector 85001-0247 SIGA-PS Intelligent Photoelectric Smoke Detector 85001-0269 SIGA-IS Intelligent Ionization Smoke Detector 85001-0291 SIGA-HFS/-HRS Intelligent Heat Detectors 85001-0243 SIGA-SD Intelligent Duct Detectors 85001-0584 SIGA-AB4G Audible (Sounder) Base 85001-0581 SIGA-DMP Detector Mounting Plate 85001-0255 SIGA-DG Smoke Detector Guard 85001-0359 Fire Suppression SIGA-REL Releasing Module 85001-0531 Notification Appliances Genesis G1 Series Field Configurable Horns and Strobes 85001-0573 Genesis G4 Series Wall Speakers and Speaker-Strobes 85001-0549 Genesis GC Series Ceiling Horn-Strobes 85001-0559 Genesis GC Series Ceiling Speakers, Speaker-Strobes 85001-0556 Genesis GC Series Ceiling Strobes 85001-0557 Genesis GC Series Ceiling Speakers 85001-0558 Genesis G1 Series Wall Chimes and Chime-Strobes 85001-0574 G1M, G1M-RM Signal Master 85001-0545 405 Series Synchronized Strobe 85001-0305 757 Series Temporal Horn and Horn-Strobe 85001-0341 757 Series Re-entrant Speaker and Speaker-Strobe 85001-0317 403 Series Bell-Strobe Plate 85001-0441 6830 Series Fire Alarm Telephones 85001-0423 300/400 Series Fire Alarm Bells 85001-0333 328D/329D Single Stroke Chimes 85001-0413 5530MD Multiple Tone Signal 85001-0415 Hazardous Location XAL-53 Hazardous Location Fire Alarm Station 85001-0371 500 Series Hazardous Location Heat Detectors 85001-0393 5522D/23D/24D Hazardous Location Horns and Sirens 85001-0385 5533BD/5534BD Hazardous Location Multiple Tone Signals85001-0387 888D-AW/-N5 Hazardous Location Horns 85001-0397 439DEX/438DEX Hazardous Location Bells 85001-0399 106DEX Series Hazardous Location Strobes 85001-0547 Accessories Batteries Rechargeable Valve Regulated Batteries 85010-0127 STI Series STI Series Stopper II 85001-0491 RR-32RL ADA Station Relocator 85001-0351 1500 Series Electromagnetic Door Holders 85001-0421 PAM-1 Multi-Voltage Control Relays 270066 MR-100/MR-200 Multi-Voltage Control Relays 270062 MR-199 Series Heavy Duty Power Relays 270065 MR-600 Series Manual Override Relays 270061 MR-700 Series Multi-Voltage Control Relays 270064 MR-800 Series Multi-Voltage Control Relays 270063
Hazardous Location
Notification Appliances
Initiating Devices
50
SUBMITTAL PLANNER
Rough out your submittal by indicating here the basic components of the package. Then, with this flap open, turn to the corresponding page and indicate the specific products to include. EST3 Network
Network Control Central Processor Unit, p. 3 Network Communication Card, p. 3 RS-232 Communication Card, p. 3 Short Haul Modem Interface, p. 3 Single Signature Driver Controller, p. 4 Addressable Analog Device Controller, p. 5 Initiating Device Circuit (Hardwired) Module, p. 5 Off Premise Signaling Module, p. 6 Fiber Optics Communications Interface, p. 6 Modem Communicator, p. 7 Liquid Crystal Display Modules, p. 8 Control Display Modules, p. 8 FireWorks, p. 9 Envoy Graphic Annunciator, p. 10 Remote Annunciators, p. 11 Remote Annunciator Cabinets, p. 11 Video Display Utility, p. 11 Ethernet Networking p. 12 Audio and Telephone Masters, p. 13 Audio Amplifiers (Banked), p. 14 Remote Microphones, p. 14 Security/Access Control Module, p. 15 Keypad/Display, p. 15 Card Reader Controller, p. 16 Proximity Card Readers, p. 17 Proximity Access Cards, p. 18 Proximity Key Fobs and Tags, p. 18 12 Vdc Regulator with Security Interface, p. 18 Lobby Enclosures, p. 19 Remote Closet Enclosures, p. 19 Chassis Assemblies, p. 19 Main Panel Power Supplies, p. 20 Battery Distribution Unit, p. 20 Remote Booster Power Supply, p. 21 Batteries, p. 21 Remote Diagnostic Utility, p. 22 Serial Printer, p. 22 RS-232 Optical Isolator Card, p. 23 CDR-3 Coder, p. 23 March Time Module, p. 23 Network Short Haul Modem, p. 23 Ground Fault Detection Module, p. 24 Communications Bridge, p. 24 Alphanumeric Pager Interface, p. 24
Step Four Fill out the bottom portion of this card, remove it from the back cover, and file it with your notes on the project for future reference.
Power Supplies
Network Accessories
Project _________________________________________ Date ___________________________________________ Firm ___________________________________________ Contact _________________________________________ Phone __________________________________________ Submitted by ____________________________________
Bases
Notes _______________________________________________ _______________________________________________ _______________________________________________ _______________________________________________ _______________________________________________ _______________________________________________ _______________________________________________ _______________________________________________ _______________________________________________ _______________________________________________ _______________________________________________ _______________________________________________ _______________________________________________
Detach before submitting this guide. Detach before submitting this guide.
Input/Output Modules
Notification Appliances
Visible/Audible Signals Genesis Wall Horns and Horn/strobes, p. 39 Genesis Speakers and Speaker/strobes, p. 40 Signal Master, p. 40 Genesis Ceiling Horns, Speakers, Strobes, p. 41 Integrity Harsh Environment Signals, p. 42 Single Stroke Chimes, p. 43 Multiple Tone Signals, p. 43 Fire Alarm Bells, p. 43 Firefighters Telephones, p. 43
Audible Signals
GE Security wishes you the best of luck with all your submittal plans!
GE Security
U.S. T 888-378-2329 F 866-503-3996 Canada T 519 376 2430 F 519 376 7258 Asia T 852 2907 8108 F 852 2142 5063 Australia T 61 3 9259 4700 F 61 3 9259 4799 Europe T 32 2 725 11 20 F 32 2 721 86 13 Latin America T 305 593 4301 F 305 593 4300 www.gesecurity.com
imagination at work
85010-0099, Issue 8