Trans Handbk
Trans Handbk
Trans Handbk
1
0. FOREWORD
The objective of this Transformer Handbook is to facilitate the physical understanding, selection,
ordering, operation and maintenance of the whole range of power and distribution transformers.
The target readers are personnel involved in the various stages of a transformer’s service life, from
planning the investment to the disposal of the transformer after use.
The handbook is arranged with the sections following the transformer’s life from initial
considerations and planning through ordering, installation, operation, maintenance and scrapping.
Other useful information, including more theoretical topics, is included.
Navigation through the handbook is facilitated through a three level contents list following this
foreword, and the Index Section 19 page 210 at the end. Each section may be read independently
of the other sections.
Some topics or phenomena are deliberately mentioned several places in the text for the purpose
that readers might not read the whole content of this book from the beginning to the end, but only
chapters of particular individual interest.
The first edition, Rev. 01, of this handbook issued at the end of 2003 was limited to distribution
transformers and the “IEC-world”.
Based on feedback from the readers and the fact that ABB has merged all transformer activities
into one Business Unit, Transformers, this second edition of the handbook now covers all
transformer types fulfilling the requirements of IEC and relevant ANSI/IEEE standards.
This handbook is based on ABB’s knowledge and experience, and is meant to be a guide to assist
the readers in handling transformer matters. ABB and the authors of the handbook cannot
however be held responsible for any legal, technical or commercial use of the information herein..
No advice or information contained in this handbook shall create any warranty or binding obligation
not expressly stated in an applicable written contract. Although data, technical drawings,
configurations and catalogue listings are believed to be accurate at the date of publication, the
readers should independently evaluate the accuracy of the information and the usefulness to their
particular needs of any product or service. However, technical data are only approximate figures.
Specifications for products and services are subject to change without notice.
ABB shall in no case be liable under, or in connection with, the handbook towards any person or
entity in view of any damages or losses - irrespective of the legal grounds. In particular ABB shall in
no event be liable for any indirect, consequential or special damages, such as – but not limited to –
loss of profit, loss of revenue, loss of earnings, Cost of capital or cost connected with an
interruption of business.
The standards, IEC, CENELEC and ANSI/IEEE, mentioned in the text refer to the edition given in
the list of standards. For practical use only latest editions of the standards should be used.
ABB Power Technologies Division thanks the International Electrotechnical Commission (IEC) for
permission to reproduce information from its International Standards. All such extracts are
copyright of IEC, Geneva, Switzerland. All rights reserved. Further information on the IEC is
available from www.iec.ch. IEC has no responsibility for the placement and context in which the
extracts and contents are reproduced by ABB Power Technologies Division; nor is IEC in any way
responsible for the other content or accuracy therein.
Similarly ABB Power Technologies Division thanks The American National Standards Institute
(ANSI) and The Institute of Electrical and Electronics Engineers, Inc. (IEEE) for permission to
reprint excerpts from its standards. All such excerpts are copyright of ANSI/IEEE the year
published. All rights reserved. Further information on the ANSI/IEEE is available from www.ansi.org
and www.ieee.org. ANSI/IEEE has no responsibility for the placement and context in which the
excerpts are reproduced by ABB Power Technologies Division. The ANSI/IEEE disclaims any
responsibility or liability resulting from the placement and use in the described manner.
Extracts from the ABB Switchgear Manual are quoted by kind approval by the issuer.
UK English has been selected for this document to comply with the language in IEC standards.
Also the use of “.” and “,” in numbers follows the practice used in IEC standards. There are no real
differences between the vocabulary applied in IEC and IEEE/(ANSI) standards. The only exception
is the use of the words “earth”/”earthed” (according to IEC) and “ground”/”grounded” (according to
IEEE).
Please also observe the Note at the end of the handbook.
1. INTRODUCTION 6
1.1. ABB-GROUP 6
1.2. ABB POWER TECHNOLOGIES BUSINESS UNIT TRANSFORMERS 6
6. TRANSFORMER DESIGN 77
6.1. CORES 77
6.2. WINDINGS 80
6.3. TANK 90
6.4. EARTH QUAKE WITHSTAND ABILITY 91
7. TRANSFORMER COMPONENTS 92
7.1. TERMINALS 92
7.1.1. BUSHINGS 92
7.1.2. CABLE CONNECTIONS 95
7.1.3. SF6 CONNECTIONS 96
7.2. COOLERS 96
7.2.1. RADIATORS 96
7.2.2. CORRUGATED TANKS 97
7.2.3. FANS 97
7.2.4. FORCED OIL, FORCED AIR HEAT EXCHANGERS 97
7.2.5. OIL-WATER COOLERS 98
7.2.6. OIL PUMPS 98
7.3. VOLTAGE REGULATION EQUIPMENT 99
7.3.1. OFF CIRCUIT TAP CHANGERS 99
7.3.2. ON LOAD TAP CHANGERS 100
7.3.3. AUTOMATIC VOLTAGE REGULATION 104
7.4. ACCESSORIES 104
7.4.1. TYPES OF ACCESSORIES 104
7.4.2. POWER TRANSFORMER AND OIL IMMERSED REACTOR ACCESSORIES 107
7.4.3. DISTRIBUTION TRANSFORMER ACCESSORIES 109
1.1. ABB-GROUP
ABB is a leader in power and automation technologies that enable utility and industry customers to
improve performance while lowering environmental impact. The ABB Group of companies operates
in around 100 countries and employs around 115,000 people (2004).
ABB Power Technologies serves electric, gas and water utilities as well as industrial and
commercial customers, with a broad range of products, systems and services for power
transmission, distribution and automation.
ABB Automation Technologies blends a robust product and service portfolio with end-user
expertise and global presence to deliver solutions for control, motion, protection, and plant
integration across the full range of process and utility industries.
As a business-to-business supplier ABB knows that value creation grows out of close relationships
with customers. That means the better we know our customers’ business challenges, the better we
can serve them. We strengthen our relationships by building trust as a socially responsible supplier
of environmentally sound products and services.
ABB offers a full range of transformers fulfilling the requirements in IEC, CENELEC, ANSI/IEEE,
other standards and customer-specific requirements.
Power transformers have primary voltages up to 800 kV. Liquid filled distribution transformers have
primary voltages up to 72,5 kV and dry-type transformers with open or encapsulated windings have
primary voltages up to 52 kV.
A wound type of core used in single-phase distribution transformers is shown in Figure 2-3.
Figure 2-3
Padmounted transformers
Power range 75 kVA - 20 MVA
Primary voltage Up to 46 kV
Secondary voltage Up to 25 kV
Available fluids Mineral oil, dimethyl silicone,
esters and synthetic
hydrocarbons
Transformers of this type are generally oil immersed and suitable for pole mounting.
They represent an economical option for certain networks, particularly those with
low population densities. Depending on customer requirements, transformers may
be connected between two phases of a three phase system (two HV bushings) or
from one phase to ground (single HV bushing). They are suitable for residential
overhead distribution loads, as well as light commercial or industrial loads and
diversified power applications.
Polemounted transformers
Power range - 1 Phase 5 kVA – 1 000 kVA
Power range - 3 Phase 30 kVA - 500 kVA
Primary voltage Up to 36 kV
Secondary voltage Up to 480 V
Available fluids Mineral oil, synthetic
hydrocarbons
The Mini-Pak is designed for cross feed (Type 2) loop feed or radial
feed on a grounded wye connection, underground distribution system.
It can be furnished in a complete line of ratings and in a wide range of
configurations to meet the reliability, safety and operating requirements
of any distribution system.
Vacuum cast means that the high voltage windings are cast-in in epoxy and cured in vacuum.
The high voltage windings are typically disc winding.
Resibloc® is an ABB patented process for the high voltage winding. The high voltage winding is
multi layer type with a cross wound glass fibre insulation soaked in epoxy, cured in open
atmosphere.
Special features:
• LV terminals are located at the bottom.
• No bottom frame or wheels.
• Option for a tertiary winding for auxiliaries load.
Liquid immersed
Power range up to 4000 kVA
Primary voltage up to 36 kV
Available fluids Dimethyl silicone or esters
Special features:
• Hermetically sealed
• Hot-dip zinc coated and painted
• Plug-in bushings on HV side
• Protected LV bushings
• Integrated protecting device; gas, oil level, temperature, pressure
The challenge with off-shore free flow oil production is the decreasing pressure inside the oil well.
The pressure drop decreases the production lifetime of the well and the production depth.
Sub sea booster pumps makes oil production at larger depth possible caused by an artificial lift to
the oil. The pumps are driven by low voltage electrical motors. The power is supplied by long HV
cables from the production vessels. The main reasons for using HV supply are to reduce the weight
of the cables as well as the voltage drop in the cables. Step-down transformers are installed at the
sea-bed near the booster pumps.
Transient overvoltages
One of the challenges is to enable the designer to predict
the transient voltage distribution within windings when
transient voltages of certain shapes are applied to the
transformer terminals. The voltage distribution varies,
depending on a number of winding parameters.
Comprehensive measurements with modern measuring
equipment on a large number of windings of various
types have been made in order to develop mathematical
models for calculation of the voltage distribution. This
development has in ABB gone on for many years with
gradually decreasing deviations between calculated and
measured values.
3 phase power
transformer 400 MVA
Figure 2-4
Figure 2-4 shows an example of the voltage distribution in a winding when a standard lightning
impulse (with 1,2 microsecond front time and 50 microseconds time from start to the voltage has
declined to half the peak value) is applied to the winding terminal. The length of the winding is
indicated along the L axis, and the time along the T axis. The measured voltages to earth are
indicated along the U axis.
The figure reminds one of a stony hill. Where the hill is very steep in the L direction, there are large
voltage differences between points in the winding that are nearby each other.
In underground hydro power stations the circuit breaker on the high voltage side is often located at
a distance of several hundred metres from the transformer. The transformer and the circuit breaker
are connected to each other by means of a cable. When energising the transformer from the high
voltage side, high frequency oscillations arise on the terminals due to travelling waves that are
reflected back and forth in the cable. See [1] Section 17.2 page 200.
Every transformer winding has a number of resonance frequencies, which can be identified by
means of measurements in the factory. At some of these frequencies high internal overvoltages
may arise if the frequency of the oscillations that occur during energisation coincide with one of the
critical resonance frequencies of the transformer winding. This potentially dangerous situation can
be avoided by energising the transformer from the generator side and then synchronising the
generator with the system by means of the circuit breaker at the high voltage side.
There may be a fixed connection between the transformer and the generator, or a circuit breaker
may be situated in between.
When there is a fixed electrical connection, the generator and the transformer are inseparable and
act as one unit. In case of failure on either side of the transformer, relays may quickly trigger the
circuit breaker on the high voltage side of the transformer to disconnect the unit from the system.
This sudden load rejection may cause higher voltage on the generator terminals and consequently
to overexcitation of the transformer. The magnitude and duration of this overexcitation depend of
the characteristics of the generator and its excitation system. The purchaser should inform the
transformer supplier about the maximum magnitude and duration of this temporary overvoltage as
early as possible in the project process and in any case in due time before the design of the
transformer is finally determined.
Overvoltage protection of the low voltage winding of generator step-up transformers needs special
consideration because of the often large difference in voltage and consequently insulation level on
the two sides and the magnitude of transferred transient and temporary overvoltages from the high
voltage to the low voltage side.
It is recommended that surge arresters be installed between each low voltage terminal and earth
and also between terminals of different phases and, in addition, capacitors between phase
terminals and earth. Typical capacitance that has been used is 0,25 µF.
The transferred overvoltages can be especially critical when the low voltage winding is
disconnected from the generator.
In several cases bus ducts enclose each phase conductor between the transformer and the
generator in order to minimise the risk of short circuits between the phase conductors. For large
generator step-up transformers the current in these conductors are very high with accompanying
strong magnetic fields, which may cause unanticipated circulating currents in transformer tanks and
covers, bushings and in the bus ducts themselves. The losses caused by these unanticipated
currents result in overheating if corrective measures are not included in the design. The
overheating of the transformer components depends upon the method of terminating the bus ducts
at the transformer end. In order to mitigate the heating problem it is suggested that design
coordination meetings be arranged between the bus duct supplier, the transformer manufacturer
and the purchaser prior to the design of the bus duct.
I II III N
i ii iii
Figure 2-6
The tappings are sometimes located at the neutral point of auto-connected transformers where
the voltage level to earth and the voltage differences between phases are lower than when the
tappings are situated at the auto tap. A simpler and cheaper tap changer can then be used. On
the other hand tappings at the neutral will need a larger number of turns in the tapping range to
achieve the same variation in the turn ratio as when the tappings are situated at the auto tap or
at the high voltage terminal.
The two main windings in an auto-connected transformer (or simply autotransformer) are called
the common winding and the series winding. The common winding is connected to the neutral and,
as the name indicates, the turns of this winding are common for both sides of the transformer.
The series winding is connected at one end to the common winding and at the other end to the
high voltage terminal.
The high voltage current flows through the series winding. The current flowing in the common
winding is the difference between the low voltage and the high voltage current. The current in
the common winding flows in the opposite direction to the current in the series winding.
The common winding and the series winding are arranged as concentric cylindrical shells,
and the ampere-turns in the two windings are equal in value and opposite in direction.
The advantage of an autotransformer compared to a transformer with separate windings is that the
autotransformer requires less material and consequently has smaller total dimensions, lower mass,
lower manufacturing costs and lower losses.
The equivalent separate two winding power rating of an autotransformer indicates the magnitude of
savings and is given by the following equation:
UrHV − UrLV
Se = Sr ⋅ (2.4.3.1)
UrHV
∆U
Z
G I G
U B
A
Figure 2-9
A and B in Figure 2-9 are two strong power systems connected by a line with impedance Z. To
transmit active power from system A to system B the voltage to the left of Z, U, must be leading in
relation to the voltage to the right of Z. To make the principle illustration simple, the real part of Z is
neglected and the power factor at B is assumed to be 1. The transformer is a phase-shifting
transformer, inserting a voltage ∆U in series with the impedance Z. The transformer is considered
to be ideal, that is, the transformer impedance is neglected.
The voltages at A and B are approximately equal, UA≈UB. ∆U is adjusted so that:
∆U – I•Z = 0
The following vector diagram applies:
I•Z
U UB
Figure 2-10
In another example there are two power systems that are linked together in two points. The power
flow goes then in two branches with impedances ZA and ZB. The value of the two impedances
determines the distribution of power flow through the two branches. This distribution may not
comply with the desired distribution.
∆U = 0 ∆U≠0
Figure 2-12
To achieve ∆U the phase-shifting transformer must at its secondary terminal provide a voltage UT,
which is higher than the primary voltage U1 and, in addition, displaced an angle δ in the positive
direction in relation to U1 (the positive direction defined counter-clockwise). δ can be calculated
from the vector diagram to the right and is in this case 11,9°.
If the total load current is only the half of 722A and the 50/50% distribution between system A and
B still is desired, the voltage drops across ZA and ZB becomes only the half of those in the last
example. The need for additional voltage to drive the desired current through ZB will then also be
only the half, that is 0,5 · 97 470 V = 48 735 V. The displacement angle δ becomes now 6°.
If ZB had been smaller than ZA, the direction of ∆U must the opposite to prevent that the current IB
would be too high in relation to the desired load distribution.
Also the power factor (cos φ) of the load current I influences the required displacement angle.
(U2)
Phase II
U2
U1
δ
Phase I
The angle displacement can be obtained in principle achieved by means of a single core three
phase transformer. However, the application of phase-shifting transformers is mainly in systems
with very high voltage, and the throughput power rating is quite large. In order to fit voltage and
current to available tap-changers, it may be necessary to use two separate transformers, one
magnetising transformer and one booster transformer. In the circuit where the tap-changer is
located the voltage can be chosen independently of the service voltage of the power system.
Figure 2-14
Figure 2-14 shows a principal diagram of how the magnetising transformer and the booster
transformer are connected together. The tap-changer is typically located at the secondary side of
the magnetising transformer.
A more detailed three-phase connection diagram is shownin Figure 2-15. A voltage, which can be
varied in size, from the secondary side of the magnetising transformer is applied to a different
phase of the primary side of the booster transformer. The voltage transferred to the secondary
(high) voltage side of the booster transformer will then be displaced an angle 2π/3 in relation to the
source side voltage. By varying the size of the voltage inserted by the booster transformer, a
variable angle δ is achieved between the voltage on the source side and the total voltage on the
load side of the phase shifting transformer, which is the vectorial sum of the voltage on the source
side and the 2π/3 displaced voltage provided by the booster transformer.
δ)
2Ssin(0,5δ
S
S δ
Figure 2-16
From the diagram it appears that Sδ = 2·S·sin(0,5·δ), where Sδ is the phase-shifting power and S the
apparent throughput power. The magnetising transformer as well as the booster transformer must be
rated for the maximum phase-shifting power.
Is for example the maximum angle δ = 30° and the rated apparent throughput power rating 1000
MVA, the rating of the magnetising and the booster transformer will be 520 MVA each
(1000·2·sin(30/2) = 520). The service voltage is in most cases also high.
In other words, the units are quite large. Because of transport limitations the two transformers are
usually placed in separate tanks.
Regarding differential relay protection of phase-shifting transformers it should be noted that a
considerable phase angle difference between the source and the load current causes a much higher
normal current difference than in ordinary power transformers, so a special differential scheme is
required.
A short-circuit in the circuit between the magnetising and booster transformer would be very harmful
to the transformers, and it is recommended that bus ducts are provided around the conductors
connecting the secondary side of the magnetising transformer and to the primary side of the booster
transformer.
In phase-shifting transformers with magnetising and booster transformer (two-core design) there is a
dielectric design question that needs special attention. If a transient voltage occurs at either side of
the series winding of the booster transformer, the connected winding of the magnetising transformer
will also be exposed to a high voltage, and high frequency oscillations may arise on the leads
connecting the two transformers. More comprehensive mathematical models may be required to
calculate the transient voltage distribution in this configuration than in a single core transformer.
A dialogue between the purchaser and the supplier regarding the overvoltage protection is
recommended.
Reference is also made to IEEE Std C57.135-2001TM IEEE Guide for the Application, Specification,
and Testing of Phase-Shifting Transformers. A revision of this standard might take place in a co-
operation between IEC and IEEE with the purpose to issue a new edition of the standard, which is
approved by both organisations and with an IEC-IEEE dual logo.
P
~ = ~
Figure 2-17
An HVDC transmission has a convertor station at each end of the line or cable. The main
components of the convertor stations are the transformers and the valves The alternating voltage
of a supply system is transformed to a voltage level suiting the convertor rectifier to transmit the
intended power. It is then rectified in a convertor arrangement with controlled valves consisting of
many thyristors semi conductors. At the receiving end of the line or cable there is another converter
station. This is operated as an inverter that converts the direct current back to alternating current,
which then is transformed to the voltage of the network being supplied. The direction of power flow
can easily be changed without interruption in the operation.
Example on harmonic current spectrum in p.u. of the fundamental frequency current in a 6-pulse
connection
Figure 2-18
Figure 2-18 shows that the 5th and 7th harmonics are the largest. Higher harmonics decrease with
increasing harmonic number.
6-pulse connection means that there are 6 pulses in the direct voltage per period of the fundamental
ac voltage, as shown in Figure 2-19 below.
Figure 2-19 shows how the direct voltage varies during one period of the ac system voltage. The
direct voltage consists of 6 pulses during one period. It is not an ideal straight line, the pulses
appear as a ripple on the direct voltage.
The ripple can be reduced by combining two 6-pulse valve bridges to a 12-pulse connection as
shown in Figure 2-20. Then the 5th and the 7th harmonics disappear from the current supplied from
the ac network. However, the 5th and 7th harmonics still circulate between the two transformers of
the 12-pulse group and may give considerable contributions to the total load losses in the
transformers. The 5th harmonic may amount to nearly 20% of the fundamental frequency current.
In the station where the dc current is converted to an ac current, the current can in principle be
converted to any frequency. The frequency can be given by the ac system itself or by a separate
synchronous machine. So an HVDC-link is suitable for connecting together ac systems with different
frequencies, for example 50 and 60 Hz.
Figure 2-20
Figure 2-21
Figure 2-21 illustrates the reduced ripple on the direct voltage of a 12-pulse connection compared to
the 6-pulse connection in Figure 2-19.
The relation between the ideal dc-voltage across the two bridges in Figure 2-20 and the phase-to-
phase voltage on the valve side of the transformers can in no load condition be written as:
6⋅ 3
UD = Uac ⋅ cos α (2-1)
π
In this equation
UD is the dc voltage across the two series-connected valve bridges in Figure 2-20
Uac is the phase-to-phase voltage on the valve side of the transformer
α is the valve delay angle (control angle)
For α = 0 the voltage UD becomes 2,7Uac. In loaded condition voltage drop in the transformer and
the valves reduces the conversion factor from 2,7 to the range 2,4 – 2,5 normally.
The losses in a converter bridge are around half a percent of the throughput power while the
inductive drop is 5 – 10%.
The valve-side winding for the lower bridge (the bridge closest to earth) in Figure 2-20 is exposed to
a dc-potential of around one fourth of the dc-line potential and the valve-side winding for the upper
bridge of three fourth of the same potential.
The voltage distribution between solid and fluid transformer insulation is capacitive when exposed to
ac. This means that the voltage distribution and dielectric stresses are determined by the permittivity
of the materials.
In contrast when exposed to dc-potential the voltage distribution and dielectric stresses are
determined by the resistivity of the materials. The insulation materials are basically the same,
mineral oil and cellulose products. Because the resistivity of the solid insulation materials is
considerably higher than the resistivity of the transformer oil, almost all the dc-voltage lies across
the solid insulation. Consequently HVDC transformers contain a much higher share of solid
insulation than in ac transformers, around three times as much.
• dc separate source voltage withstand test. See section 8.2.3 and 10.4.3 of IEC 61378-2;
• polarity reversal test. See section 8.2.4 and 10.4.4 of IEC 61378-2.
To control the service voltage HVDC transformers are equipped with a fairly large tapping range on
the line side. Further there is a need for strict control of the short circuit impedance of the
transformers. The deviation in impedance between individual phases must be kept small.
IEC 61378-2 specifies that the impedance variation at the principal tapping and the variation of the
impedance over the tapping range for transformers of duplicate or similar design for the purpose of
identical application in service or interchange ability shall not exceed ±3% of the mean test values.
The reason for this requirement is to a great extent the need for efficient cancelling of harmonics in
a 12-pulse bridge connection. Large variations between phases, units and star and delta connected
windings will increase the size of the filters.
Alternatively to the transformers shown in Figure 2-20 with two 3-phase transformers, one with delta
and one with star connected winding at the valve side, three single-phase transformers could be
used. In that case each transformer has two valve-side windings, one for d-connection and one for
y-connection in a bank with the two other single-phase transformers.
If a spare transformer is desired, the single-phase transformer solution has the advantage that just
one single-phase transformer can cover the need. The choice of solution, 3-phase or single-phase
transformers may also depend on restrictions in unit dimensions and weight.
The modern high voltage and high capacity converter is a sophisticated product requiring
experience and high skill in design and specific quality control in production.
Arc furnace transformers are used for melting scrap metal. Usually in combination with an arc
furnace, there is a ladle furnace The ladle furnace is used in the process of refining the metal
melted by the arc furnace. Arc furnace transformers are normally designed as three phase units.
Reduction furnace transformers are mainly used in the metallurgical industry. Production of ferro-
alloys is an important application. The major alloys are ferro-silicon, silicon metal and ferro-
manganese. Other significant alloys are ferro-nickel and ferro-chrome. Reduction furnaces are also
used in the production of non ferrous metals such as copper, nickel, tin, lead and zinc. Reduction
furnaces are also used in the production of calcium carbide. The most common design for
reduction furnace transformers is single phase.
Examples on furnace transformers for special purposes can be for production of electrode material
and electro slag refining, where the latter is production of very high quality steel.
Other applications can be chemical electrolysis, DC arc furnace (see section 2.4.4.1), graphitizing
furnaces, traction substations (see section 2.3.5), copper refining etc.
VSD transformers are used in applications where a variable speed is required on the motor shaft.
VSD are used in a wide variety of applications such as rolling mill drives, ship propulsion systems,
mine hoist drives, wind tunnels drives etc. Figure 2-22 shows a basic circuit diagram for a VSD
system configuration for a wind tunnel. The transformer is a 12-pulse unit that feeds two 6-pulse
rectifiers, which are coupled via a dc-link containing two
smoothing reactors that are connected to two inverters, which
in turn is connected to a synchronous motor. The transformer is
also equipped with a tertiary winding, which is connected to a
filter. The purpose of the filter is to reduce the harmonic voltage
distortion in the HV supply system as well as increasing the
power factor of the load.
Primary Secondary
Figure 2-23
A major improvement is found in this system where a booster transformer (unity ratio) is
implemented. The primary circuit is connected across a gap in the contact wire and the secondary
across an insulated rail section. In linear mode (when the booster transformer is not saturated), the
traction return current flowing through the secondary circuit is forced to be equal to the current
flowing through the overhead line and in the primary circuit. This system is commonly used.
Figure 2-26 shows system number 3, two phase feeding system with autotransformer.
2.5. REACTORS
This section describes reactors for a number of different applications.
Supplementary information can be found in IEC 60076-6 Part 6: Reactors (At present in process).
Figure 2-27
In this situation the capacitance to earth draws a current through the line, which may be capacitive.
When a capacitive current flows through the line inductance there will be a voltage rise along the
line.
To stabilise the line voltage the line inductance can be compensated by means of series
capacitors, and the line capacitance to earth by shunt reactors. Series capacitors are placed at
different places along the line while shunt reactors are often installed in the stations at the ends of
line. In this way the voltage difference between the ends of the line is reduced both in amplitude
and in phase angle.
Shunt reactors may also be connected to the power system at junctures where several lines meet
or to tertiary windings of transformers.
Transmission cables have much higher capacitance to earth than overhead lines. Long submarine
cables for system voltages of 100 kV and more need shunt reactors. The same goes for large
urban networks to prevent excessive voltage rise when a high load suddenly falls out due to a
failure.
Figure 2-28
When the reactor neutral is directly earthed, the winding are normally designed with graded
insulation in the earthed end. The main terminal is at the middle of the limb height, and the winding
consists of two parallel-connected halves, one below and one above the main terminal. The
insulation distance to the yokes can then be made relatively small. Sometimes a small extra
winding for local electricity supply is inserted between the main winding and yoke.
L
u = i⋅ (2.5.1.2)
C
When using modern SF6 circuit breakers, the size of the voltage due to the current chopping is
typically in the range 1,2 to 2,0 p.u. and somewhat higher for other types of circuit breakers. The
rate of voltage rise is relatively moderate.
However, when the arc in the circuit breaker is extinguished, a kind of competition starts in the
circuit breaker. The one competitor is the voltage increase between the two contacts in the circuit
breaker, the other is the increase in breakdown voltage between the circuit breaker contacts,
because the contact separation still continues and the distance between the contacts increases.
If the latter competitor wins, the voltage across the reactor will oscillate due to the energy that is
flowing forth and back between the stray capacitance C and the inductance L of the reactor. The
oscillation will be damped due to the resistance that always is present in a circuit. A typical course
of the voltage across the reactor is shown in Figure 2-30.
Figure 2-30
This voltage course, when disconnecting the reactor, will be harmless to the reactor and the
surroundings.
Figure 2-31
During such a voltage course the reactor winding is highly stressed, especially at the beginning of
the winding. These stresses may exceed the stresses that the winding is exposed to during the
standard transient voltage tests and may lead to breakdown in the winding. The stresses in the
winding are not only dependent on the size of the voltage change but also on how fast the voltage
changes (du/dt). So even transient voltages with peak value below the surge arrester protection
level may damage the reactor.
The root of the problem is the reignitions that may occur in all types of circuit breakers
(SF6, vacuum, oil, compressed air). A way to eliminate reignitions in the circuit breaker and thereby
avoid damage to the reactor and equipment in the surroundings is to apply synchronous opening of
the circuit breaker, also called point-on-wave controlled opening. The principle is illustrated in
Figure 2-32.
Figure 2-32
By starting the contact separation at a certain level on the rising part of the current curve, the level
being sufficiently high to avoid that the circuit breaker does not chop the current, the arc will burn
until the current has passed its maximum value and proceeds further towards its natural passage
through zero. At a certain level before the current reaches zero the circuit breaker will extinguish
the arc and chop the current, but then the contacts have had sufficient time to separate quite far
from each other. Consequently the break down voltage of the distance between the contacts has
also increased to a value high enough to prevent the recovery voltage to cause a break down
(reignition).
The signal for synchronisation comes from a capacitor voltage transformer (CVT).
Since synchronised switching was introduced, shunt reactor failures attributable to switching
operations seem to have disappeared. Encouraged by this good service experience ABB always
recommends equipment (SwitchsyncTM, [4]) for synchronised switching when offering circuit
breakers for shunt reactor switching.
More detailed information on controlled switching can be found in [4], available on request to the
nearest ABB office.
Figure 2-33
Figure 2-34
The air core reactors may require relatively
large space because the magnetic field
spreads freely in the surroundings and may
cause excessive heating in iron reinforcements
in concrete walls, floors and ceilings, wire
fences and other metal items. Appropriate
distance from the reactors must then be kept.
The distance should be sufficiently large to
keep the magnetic field below 80 A/m at the
floor and at the ceiling. At adjacent wall the
magnetic field should not exceed 30 A/m.
Figure 2-35
These field values are referred to continuous rated current through the reactor or to temporary
currents lasting more than a few minutes.
The thermal time constant of reinforcement iron and wire fences is short. The supplier should
inform the purchaser regarding necessary distances from the reactor, at which the magnetic field
values have declined to those mentioned above.
Figure 2-35 illustrates the magnetic field attributed to an air-core reactor without any shield.
Considerable forces due to the field can draw loose iron items in the vicinity into the reactor and
cause damage. So it is recommended to keep the surroundings clean.
Possible disturbing influence of the magnetic field on the functioning of other electrotechnical
product in the vicinity must be considered.
Humans should not regularly stay for longer time near the strong magnetic field from such reactors
when current is flowing through the windings.
NOTE: Persons bearing pacemaker should stay far away from such reactors.
Single-
phase
reactor with
frame core
3-phase
reactor with
frame core
Figure 2-36
When enquiring for a current-limiting reactor, the following information should be given:
• System voltage;
• Frequency;
• Short circuit power of the feeding system;
• Insulation level;
• Rated continuous current and/or rated short-time current and duration;
• Rated impedance of the reactor or alternatively, the reduced short circuit power after
including the impedance contribution from the reactor;
• Dry-type or oil-immersed;
• Indoor or outdoor installation.
C
L
Figure 2-37
A parallel resonant filter has a high impedance that blocks for currents of a certain frequency, while
a series resonant filter has a low impedance that leads away currents of a certain frequency from
parts of the power system where are undesired.
Filters are preferably located as close as possible to the spot where the harmonics are generated.
Tuning reactors are single-phase or three-phase reactors, oil-immersed or dry-type. The reactors
may be designed with means for adjusting the inductance value within a limited range either by
tappings or by movement of core and/or coils. The preferred or recommendable design solution in
each particular case should be indicated already in the enquiry or the tender.
Naked dry-type air core reactors might offer the lowest purchase price. However, when erected
outdoors at moist and heavily polluted locations, such reactors may be more vulnerable to dielectric
failure than oil-immersed reactors.
It is possible to provide the earthing transformer with a secondary winding for continuous auxiliary
station supply.
Earthing transformers are usually oil immersed and may be installed outdoor. In cases where a
separate reactor is connected between the transformer neutral and earth, the reactor and the
transformer can be incorporated in the same tank.
IcS
Ie
R
Ie Ce
Figure 2-39
Figure 2-39 shows to the left an energy source that might be a secondary winding of a transformer
with the terminals R, S and T. It is connected to a system where each phase has a capacitance to
earth Ce. This capacitance is distributed along the whole length of the conductors, but is indicated
as one concentrated capacitor Ce per phase. Assume that this capacitance is the same in all three
phases, which means that the phase conductors of overhead lines are perfectly revolved.
An earth fault is indicated in phase R. For the sake of simplicity we assume that the impedance at
the failure spot is so small that it can be neglected. In other words, the potential of phase R is equal
to the earth potential, which in undisturbed and symmetrical condition lies in or close to the neutral
point (star point) of the transformer winding.
Due to the earth fault the potentials to earth of phases S and T have increased. In normal operation
there is an exchange of currents between the system and earth in such a way that the capacitance
to earth of one phase serves as return path for the current through the capacitance of the two other
phases and vice versa.
The earth fault has altered this capacitive current flow. Now the return of the current to earth from
phase S and T goes through the earth fault and into phase R. Because of the increased potentials
to earth of phase S and T, the currents to earth from these phases have also increased. The vector
relationships between voltages and currents are shown in Figure 2-40.
T S
Ut Us
∆u
Ics
30o
Ie 30o R
Ict
Figure 2-40
In this example the potential in relation to earth on the sound phases S and T is assumed to be
equal to the normal system voltage U (line-to-line). In other words, the potential to earth on these
phases has increased by a factor of √3. (This factor may in practice be lower or higher than √3).
The neutral has shifted ∆u, which in this case is equal to the normal line-to-neutral voltage.
Ie = 2 ⋅ U ⋅ ω ⋅ C e ⋅ cos 30 o = 3 ⋅ U ⋅ ω ⋅ C e (2.5.7.2)
Depending on Ce, which is proportional to total length of lines and cables in the system, Ie may
become quite high and may sustain an arc at the failure spot.
S
T IcT
IcS
L Ie
R
IL Ce
Ie IL
IL
Figure 2-41
When connecting an arc-suppression reactor L between the neutral of the transformer winding and
earth, an inductive current flows through L to earth where it finds its return path through the earth
fault. The inductive current through the earth fault has the opposite direction of the capacitive
current provided by phases S and T.
T S
Ut Us
∆u
Ics
30o
Ie IL
30o R
Ict
Figure 2-42
Figure 2-42 shows the IL vector added to the previous vector diagram in Figure 2-41 before the
presence of the arc-suppression reactor. ∆u is the voltage that drives the current IL through the
reactor, and IL is naturally lagging 90° in relation to ∆u.
By adjusting the reactance of the reactor IL can be given the same numerical value as Ie, and
because Ie and IL have opposite directions, the resulting current through the fault will become zero
or close to zero. Then the arc at the failure spot is given a high probability to extinguish by itself,
and the operation of the power system can continue undisturbed and without any interruption of the
electricity supply.
Figure 2-43 a and b shows typical charging currents (earth fault currents) in an overhead line
system as functions of the line length, with the system voltages as parameters. The diagrams are
valid for 50 Hz. For 60 Hz the currents must be increased by 20%. From these diagrams the
capacitive fault current can easily be estimated. The nominal current of an arc-suppression reactor
should be the same as the capacitive fault current, which means that the reactor must be capable
to carry this current for a certain time, and in addition, the reactance of the reactor must be such
that it lets this current through when a certain voltage appear across the reactor. This voltage shall
be the highest voltage the reactor will be exposed to in service. In practice this is taken as the
highest system voltage divided by √3. That is the phase-to neutral voltage when the system is
balanced (symmetrical).
80
46 kV
60
34,5 kV
a
40 23 kV
13,8 kV
20
0
0 100 200 300 400 500 600
Length of overhead lines (km)
450
single line-to-earth fault at 50 Hz
Amperes charging current in a
230 kV
400
350
300
161 kV
250
138 kV
b
200 115 kV
150 92 kV
100
50
0
0 100 200 300 400 500 600
Length of overhead lines (km)
Figure 2-43
When also cables are parts of the system, the contribution from the cables to the earth fault current
must be taken into account. This should preferably be based on information from the cable
suppliers, but in case such information is lacking, we provide some data as guidance.
The capacitance to earth of cables may vary within a range of 0,1 – 0,7 µF/km depending on the
cable design and dimensions. We consider three different designs, which are shown in Figure 2-44.
Sheath
Figure 2-44
The earthing capacitance for each phase, Ce, expressed in µF/km cable is indicated on the
ordinate axis in the following Figure 2-45, Figure 2-46 and Figure 2-47.
0,45
0,4 µ F/km
0,35 7,2 kV
12 kV
Earth capacitance
0,3
17,5 kV
0,25 24 kV
0,2
0,15
0,1
0,05
0
Conductor area mm2
240
300
120
150
185
95
70
25
35
50
Figure 2-45
0,7 µF/km
12 kV
0,6
Earth capacitance 17,5 kV
0,5 24 kV
36 kV
0,4
52 kV
0,3 72,5 kV
0,2
0,1
0
Conductor area mm2
240
300
120
150
185
95
70
25
35
50
0,7
0,6 µ F/km
0,5 12 kV
Earth capacitance
24 kV
0,4 36 kV
72,5 kV
0,3 123 kV
0,2
0,1
0,0
Conductor area mm2
35
150
240
300
400
500
630
50
70
95
120
185
I e = 3 ⋅ 2 ⋅ π ⋅ f ⋅ Y ⋅ U ⋅ L c ⋅ 10 3 (2.5.7.3)
The zero sequence impedance may also be expressed in per cent of the reference (or base)
impedance of the transformer Zref:
Z 0 ⋅ 100
z0 = (2.5.7.5)
Z ref
U2
Z ref = (2.5.7.6)
Sr
in which U is the rated voltage (line-to-line) in kV and Sr is the reference power rating of the
transformer in MVA.
The zero sequence impedance may have several values because it may depend on how the other
winding or windings are connected or loaded. The key question is whether any other winding
provide balancing ampere-turns or not.
If there is a delta-connected winding in the transformer, balancing ampere-turns will be provided by
a current circulating within the triangle of the delta-connected winding. In this case the zero
sequence impedance will be approximately equal to the plus and minus sequence short-circuit
impedance of the pair of windings, star and delta.
Zigzag-connected windings have the special property that they can be connected in such a way
that they provide balancing ampere-turn themselves, because currents equal in size with opposite
polarity flow through the two halves of such windings on each of the three limbs. The current
creates a magnetic leakage field between the two winding halves, and the zero sequence
reactance of the zigzag-winding becomes low and equal to the short circuit reactance between the
two halves.
When the zero sequence reactance of the transformer is high compared to 1/3ωCe, XL should be
adjusted according to:
1 X
XL = − 0t (2.5.7.8)
3ωC e 3
Oil-immersed smoothing
reactor in the Rihand - Dehli
Figure 2-49 HVDC transmission
The purpose of the reactor is to provide high impedance to the flow of the harmonic currents,
reduce their magnitude and thus making the d.c. current more smooth. The higher reactor
inductance the smaller remaining harmonic currents (ripple), but at the same time higher reactor
costs and losses. The voltage drop across the reactor is the notches in the voltage from the
rectifier.
A smoothing reactor has no nominal power rating in the same sense as a.c. reactors. However, a
size comparison can be made on the base of the stored magnetic energy. In this respect the size of
a smoothing reactor in HVDC systems can be much higher than even the largest shunt reactors,
which also is reflected in the physical dimensions. Sometimes it is necessary to share the winding
(which naturally is single-phase) on two core limbs in order to keep the outer dimensions within the
transport profile.
Figure 2-50 shows an example where the vertical red line indicates the bias d.c. magnetisation
caused by the d.c. current flowing through the reactor. The two dotted horizontal lines indicate the
range of linked flux variation caused by the superimposed harmonic a.c. voltage. They are located
symmetrically around the d.c. linked magnetic flux. The two dotted vertical lines indicate the limits
for the corresponding harmonic a.c. current. The latter limits are located asymmetrically in relation
to the d.c. magnetising current.
a.c. current
ψ
a.c. voltage
Linked magnetic flux
d.c. magnetisation
Magnetising current i
Figure 2-50
Figure 2-51
The polarity reversal test is followed by an a.c. voltage test of 1 hour duration with PD
measurement.
The dielectric testing includes also a withstand test with d.c. voltage equal to 1,5 times the rated
service voltage of 1 hour duration and with PD measurement.
Supplementary information is found in:
• IEC 289 (1988) Reactors, which is in the process of being revised and will be issued with
the number IEC 60076-6;
• IEEE Std 1277-2000 IEEE Standard General Requirements and Test Code for Dry-Type
and Oil-Immersed Smoothing Reactors for DC Power Transmission.
3.1.1. Quality
The functional reliability of transformer installations depends of the suitability and quality of the
transformer, components and the processes employed. ABB transformer factories have adopted
the International standard of quality management system
ISO 9001:2000 Quality management systems
Requirements
This standard emphasizes customer satisfaction, process approach and continuous improvement.
Most ABB factories operate ISO 9001 certified management systems.
$ kW
Manufacturing cost
Losses
$ Manufacturing cost +
Money value of
l
Manufacturing cost
Figure 4-2
The black curve is the sum of the manufacturing cost and the money value of the losses, that is the
total costs. This curve has a minimum point as can be seen in Figure 4-2.
The customer’s best buy is a transformer that gives the minimum total costs, which is to be found
somewhere on the scale between the minimum purchase price and the price for a transformer
which from a pure technical point of view is more or less oversized. How much should then the
quantity of materials be increased to obtain the optimum loss transformer?
To answer this question the designer needs already at the enquiry stage money values per kilowatt
for the no load and the load losses, which must be provided by the purchaser. Based on these
values the transformer designer works out the best compromise between initial cost and power loss
expenditure.
The money values for the losses, the so-called capitalised loss values, express the maximum
amount of money the user is willing to invest to reduce the transformer losses by one kilowatt.
We will in this chapter describe a way to achieve reasonable capitalised loss values.
The losses in the transformer are traditionally expressed in terms of two separate quantities,
determined by two separate tests.
• No load loss at rated voltage
• Load loss at rated current
The no load loss figure is obtained in a test with rated voltage applied to one of the windings and all
other windings open-circuited.
The load loss is by definition taken as the active power consumed in a short-circuit test where rated
current of rated frequency is fed into one winding and another winding short-circuited. Possible
other windings shall be open. The loss is guaranteed and determined at a reference temperature in
the windings (75 ºC according to International Standards (IEC), 85 ºC according to ANSI/IEEE. The
reference temperature for dry-type transformers depends on the type of insulation material and the
corresponding permitted winding temperature).
No load loss
The no load loss is assumed to be present with its measured reference value for the whole time
that the transformer is energised. No account is taken of the difference between service voltage
and rated voltage, or of possible combination effects of leakage flux running through yoke parts. A
system intertie transformer or receiving transformer is energised continuously, but generating sets
may be started and stopped (peak load generation). Industrial process transformers may also have
intermittent duty cycles.
Relevant parameters
a) energy cost and how this evolves during the years the transformer will be in operation;
The energy cost per kWh is influenced by many factors, like fuel market price, supply and
demand of electricity, taxes, inflation, political situations and decisions, climatic variations
etc. It may increase or decrease from one year to another and may even fluctuate during
the 24-hour day. This makes a fine-tuned prediction of the evolution of the energy costs
impossible. In a perspective of a series of years, the energy costs will probably increase.
As an approximation the evolution of energy costs can be calculated by means of an
average increase rate per year. In a calculation model for the capitalised costs of the
losses, it is then possible to calculate several alternative increase rates in order to see
how the final result is influenced.
b) the loading pattern of the transformer;
The loading pattern may vary much from one transformer to another. In industrial
applications like for example aluminium electrolysis the transformers will be fully loaded
from the beginning and will run so continuously except for shut-down periods of the pot-
line due to maintenance, low aluminium prices due to market saturation or other reasons.
Transformers for operation in systems for general electricity supply to society normally have
a power rating which is considerably higher than the load just after installation, in order to
meet future needs and possible disturbance situations. The initial load may then be even
below one half the power rating of the transformer. This means that the load loss is below
one fourth of the reference loss. The low loading might prevail for several years before the
load current slowly approaches the nominal current of the transformer, if the need for spare
capacity permits that high loading. The capitalised load loss for a transformer with such a
loading pattern will naturally be significantly lower than for a transformer where the load
current is equal to the nominal current just after energising the transformer.
8760 ⋅ d ⋅ 1 + p
100
(4-1)
q = 1+ p (4-4)
100
the sum of the energy cost for
consuming 1 kW continuously during n years becomes:
(
8760 ⋅ d ⋅ 1 + q + q2 + ⋅ ⋅ ⋅ ⋅ + qn −1 ) (4-5)
where the expression within the
brackets is a geometric series with the quotient q. The sum s of this series is:
qn − 1
s= (4-6)
q −1
To calculate the total cost for 1 kW during n years the cost for the first year 8760·d must then be
multiplied with the factor s.
110
100 n n=20
1 + p −1
90
100 n=15
s=
Multiplication factor s
80 n=10
1 + 100 − 1
p
70 n=5
60
50
40
30
20
10
0
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Average annual increase in energy price p%
Figure 4-3
For example, the accumulated cost of 1 kW no load loss after 20 years is 41 times the cost of the
first year if the average annual increase in the energy price is 7%.
The diagram in Figure 4-4 shows the multiplication factor for the whole physical lifetime of the
transformer (say n=50 years) versus the average annual increase in energy price. It indicates that
during the lifetime of a transformer the saving potential by lowering the transformer loss might be
quite considerable.
8000
n
7000 1 + p −1
100
s=
1 + 100 − 1
6000 p
Multiplication factor s
n=50
5000
4000
3000
2000
1000
0
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
Average annual increase in energy price p%
Figure 4-4
The total return on the invested amount X to obtain 1 kW less no load loss should be equal to the
reduced energy cost for 1 kW less no load loss accumulated during n years of operation:
n
1 + p −1
100
8760 ⋅ d ⋅
1 + p −1
100
(4-12)
The following basic equation can then be written:
n
1 + p −1
a 100
n⋅ X⋅ = 8760 ⋅ d ⋅
100 1 + p −1
100
(4-13)
The expression on the left side of the equal sign in (4-13) represents the return requirement on the
investment X. The right side represents the economic value of the energy saving.
p
n
8760 ⋅ d ⋅ 1 + − 1
100
X= ⋅ 100 ⋅ 100
n⋅a⋅p (4-14)
To calculate an example with figures:
Average energy cost rate the first year of operation d = 0,085 $/kWh
Average annual increase in energy cost rate p=7%
Number of years before invested amount shall be paid back n=5
Average annual general inflation rate i=4%
Annual interest rate on invested amount X acc. to (10) a =24,33 %
constant · (4-16)
Introduce now a parameter called the equivalent loading current Ieq. That is a constant loading
current that consumes the same amount of energy during the 8760 hours of a year as according to
expression (4-16).
ΣIi2 ⋅ ∆t
I2eq =
8760 (4-17)
The load loss is proportional to the square of Ieq/IN. In the following Ieq will be expressed in p.u. of
the nominal current IN of the transformer. The load loss is then proportional to the square of Ieq.
The target is to find capitalised value for the load loss. One question is how much are the savings
of 1 kW reduced reference load loss (referred to nominal current IN and reference temperature)
accumulated over a certain number of years?
I2eqinit ⋅ 8760 ⋅ d
(4-18)
For the second year
(
I2eqinit ⋅ 1 + z
100
) ⋅ 8760 ⋅ d ⋅ 1 + p100
2
(4-19)
For the third year
( )
2 2
I2eqinit ⋅ 1 + z
2
⋅ 8760 ⋅ d ⋅ 1 + p
100 100
(4-20)
For the fourth year
( )
3 3
I2eqinit ⋅ 1 + z
2
⋅ 8760 ⋅ d ⋅ 1 + p
100 100 (4-21)
th
For the n year
( )
n−1 n−1
I2eqinit ⋅ 1 + z ⋅ 8760 ⋅ d ⋅ 1 + p
2
( ) ( )
+ ⋅ ⋅ ⋅
2 2
1 + 1 + z
2
⋅ 1 + p + 1 + z 2
⋅ 1 + p
100 100 100 100
I2
⋅ 8760 ⋅ d ⋅
( )
eqinit
z
2
n−1
p
n−1
+ 1 + 100 1 + 100
(4-23)
The expression within the main brackets is a geometric series with the quotient
q = 1+ z( ) ⋅ 1 + p100
100
2
(4-24)
and the sum
( )
n
1+ z 2
⋅ 1 + p − 1
q − 1
n 100 100
sn = =
q −1 1+ z
2
100
(⋅ 1 + p −1
100
)
(4-25)
In a shorter expression than (4-23) the accumulated savings during n years for 1 kW reduced load
loss become
( )
n
1+ z 2
⋅ 1 + p − 1
100 100
I2eqinit ⋅ 8760 ⋅ d ⋅
(
1+ z
2
100
)
⋅ 1 + p
100
−1
(4-26)
Analogous to the expressions (4-7) - (4-13) we can set up the following equation
( )
n
1+ z 2
⋅ 1 + p − 1
2
Ieqinit ⋅ 8760 ⋅ d 100 100
Y= ⋅ ⋅ 100
n⋅a (
1+ z
2
100
)
⋅ 1+ p
100
−1
(4-28)
Numerical examples:
Assume:
Ieqinit = 0,4 in p.u. of the nominal current of the transformer
The average energy price the first year in operation d = 0,085 $/kWh
The average increase in loading current per year z=5%
The average annual increase in energy cost rate p=7%
The average annual inflation rate i=4%
Number of years before the invested amount shall be paid back n=5
Annual interest rate on invested amount Y acc.to (4-11) a =24,33 %
Result:
Y = 700 $/kW
If the number of years n = 8, and the other free variables d, z, p and i remain unchanged, (observe
that a is a dependent variable of i and n), the result becomes:
Y = 1330 $/kW
If applicable the transformer is specified with alternative methods of cooling, the respective
lower power values are to be stated together with the rated power (which refers to the most
efficient cooling),
Typical specification could be 70% / 100% ONAN / ONAF, or as overload 100% / 130%
ONAN / ONAF.
• Rated voltage for each winding
• For a transformer with tappings:
Which winding is tapped,
the number of tappings, and
the tapping range or tapping step,
Whether 'off-circuit' or 'on-load' tap-changing is required,
If the tapping range is more than ±5 %, the type of voltage variation, and the location of
the maximum current tapping, if applicable, see IEC 60076 – 1 (2000-04) clause 5.4.
Normal specified type of voltage variation is CFVV (constant flux voltage variation) and in
special cases VFVV (variable flux voltage variation). But normal operation will often be CbVV
(combined voltage variation).
• Highest voltage for equipment (Um) for each winding (with respect to insulation, see IEC
60076-3),
This should be mentioned separately and may lead to additional cost and longer delivery
time.
Any information regarding the required corrosion resistance of the surface treatment in reference to
the geographic zone and pollution zone has to be stated.
6.1. CORES
This section describes various types of cores. The core material is described in section 13.1 page 159.
Figure 6-1 shows a three-phase core with three limbs, which are magnetically connected with each
other at the upper and lower ends by yokes. The space available for the windings is called the
window. Normally the limbs are arranged in one plane and with vertical orientation.
The design in Figure 6-3 is in general more economical than that in Figure 6-4. However, in certain
cases, for example when two generators are feeding one transformer, the two limb design may be
preferred because it is quite convenient to let one generator feed the low voltage winding on one
limb and the other generator feed the winding on the other limb.
Another advantage with single-phase transformers is that a single-phase stand-by spare unit is
cheaper than a three-phase one.
Sometimes the power rating of the transformer is so high that although the power rating is shared
among three single-phase transformers the single-phase windings must be placed on two wound
limbs of the single-phase core. A core steel frame consisting of two unwound side limbs and the
yokes with a cross section of half the cross section of the wound limbs must be provided in order to
keep the transformer height within the permitted transport profile. Figure 6-5 shows an example on
such a core.
Figure 6-5
General stacking pattern for a three-phase three limb core with conventional or step-lap joints.
Figure 6-6
In recent years the step-lap joint has been most applied. By making a stepwise shift of the joints it
is possible to reduce the magnetisation losses still further in the joints between the limbs and the
yokes. The two jointing methods are illustrated in Figure 6-6.
Generally the core laminations are insulated from earth and deliberately earthed in one point only.
It is then possible to reveal any unintentional earthing, which may give rise to circulating currents if
more than one point of the core has connection to earth. In customer specifications there is often a
clause saying that the core shall be earthed in one point only and that the dielectric withstand shall
be 2 kV ac.
The high number of the thin core steel sheets in the limbs is kept together by means of glue for the
smaller transformers, for the larger transformers by means of steel straps around the limbs or an
epoxy-cured stocking. Besides rigid mechanical properties the fabric stocking is made slightly
conductive in order to reduce the electric field stress around the sharp corners on the lamination
packets in the limb. Holes through the laminations are then avoided, which would disturb the
magnetic flux distribution within the core and set up additional losses. Core clamps with curved tie
bolts keep the yoke laminations together.
For clamping and support of the windings in their axial direction the centre portion of the yokes are
made with plane surfaces in the core window. These plane surfaces are extended outside the core
laminations and supported by the core clamps. On large units with high leakage flux the outer
section of this plane may be covered by core steel laminations (electromagnetic winding supports).
In addition to being a structural member it provides a low reluctance return
path via the core for the leakage flux. In modern transformers the insulation
requirement has also been extended to the core clamps.
The stacked core described in this section is the dominant type of core
used in large transformers. Wound cores are used is an economical type
for single-phase distribution transformers. This type is shown in Figure 6-7.
Figure 6-7
Figure 6-8
A special kind of winding conductor is the continuously
transposed cable. This cable is built up of two layers of
enamel lacquer insulated strands arranged axially upon
each other, as shown in Figure 6-9. By transposing the
outer strand of one layer to the next lazer with a regular
pitch and applzing common outer insulation a continuous
transposed cable is achieved.
When traversing the same flux for a whole transposition
cycle, all strand loops receive the same induced voltage,
and circulating currents between the strands are avoided.
Continuously transposed cable
Figure 6-9
A transposed cable may contain up to a hundred strands in parallel. With a transposition pitch of
10 cm, a full cycle is completed after some metres.
Transpositions of strands must also be made in windings with conventional conductors to avoid
circulating currents. These transpositions are then made during the work in the winding machine.
To make these transpositions is quite time consuming. The manufacturers of continuously
transposed cables make the transpositions in an automatic machine. If necessary for increased
mechanical strength the strands are covered with epoxy glue, which cures during processing the
winding. For lower voltages a netting around the transposed cable is used to keep the strands
together. For higher voltages insulation paper covers the cable.
Layer windings
The turns are arranged axially along the winding. The consecutive
turns are wound close to each other without any intermediate
space. The winding may be made as a single or multilayer winding.
Within ABB single and multilayer windings are used mainly for
small and medium size transformers. For large transformers this
winding type is used for regulating windings. Single layer or multi-
layer types are used.
Regulating winding in
layer type design
Figure 6-10
Figure 6-11
Helical windings
The helical winding can be seen as a variant of the multilayer winding but with spacers between
each turn or thread in the winding. The helical winding is suitable for high currents, where the
current is shared between several parallel strands. Then the dimensions of each strand can be
kept reasonably small in order to keep the eddy current losses low.
All cables (one or several strands in common paper covering) in a disc belong to the same
electrical turn, and they are all connected in parallel. The winding can be made as single threaded
or multi threaded with two or more discs electrically in parallel.
The parallel connected winding conductors and strands are situated in a magnetic field that varies
from point to point inside the volume occupied by the winding. To avoid circulating currents
between the strands the position of each strand along the winding is changed in such a way along
the winding that each strand encloses the same amount of magnetic field. The induced voltage in
each loop formed by each strand will then be the same.
Without this precaution (called transposition of conductors and strands) the current distribution
among the strands would be very uneven. Some strands would carry high currents while other
strands would carry low currents. This would create unnecessary high temperature spots and
increased losses.
The helical winding is the preferred concept when the number of turns and the total amount of
current permit. The quantity of conducting material that can be fitted inside a given volume is high
compared to other types of winding. It is said that helical windings have a high space factor, which
is beneficial for an overall total mass – total loss relation. Moreover it is mechanically robust and
easy to manufacture, particularly when continuously transposed cable is used.
Disc windings
Figure 6-12
Figure 6-13
Foil windings
Foil windings are made of wide copper or aluminium sheet, from some tenths of a millimetre up a
few millimetres thick. The main technical advantage is that axial mechanical forces acting on the
windings in the transformer during short circuit currents become insignificant because induced
eddy currents in the foil weaken the radial component of the magnetic leakage field at the top and
the bottom of the winding. A drawback is that these eddy currents cause additional losses in areas
close to the edges of the foil. Foil windings have the other advantage that the manufacturing time is
short.
Foil windings are widely applied in low voltage windings of distribution transformers. They are also
used in larger transformers and not at least in transformers that in normal service are frequently
exposed to high overcurrents of short duration.
Regulating windings
Tappings for turn ratio regulation of the voltage may be provided in windings when the winding
current is not too high and the regulation range is not too wide. However, if tappings are made in a
disc winding, a section of the winding will be with no ampere-turns. This will disturb the ampere-
turn balance with other windings in the transformer. A radial component of the magnetic flux will
arise, which in turn creates enhanced axial short circuit forces. The transformer can be designed to
withstand such forces provided the radial component of the magnetic field is not too large.
For larger regulating ranges the regulating turns are arranged in a separate winding shell. The
height of this regulating winding is approximately the same as of the other windings. The winding
type is layer or helical. The turns of each regulating step are distributed along the whole or nearly
the whole winding height. The turns of each regulating step are connected in series by means of
cable connections outside the winding. Cables provide connections between each regulating step
and the tap changer.
The most economical design solution is to locate the regulating winding (electrically) at the neutral
point of a star connected winding where the potential difference between the three phases is small.
This gives the simplest and cheapest tap changer.
Figure 6-14
Tap changers for operation during load (OLTC) as well as the cheaper type only operable in de-
energised condition are available. The latter type is called off-circuit tap changer (OCTC), to
emphasize that it cannot be operated when the transformer is energised. Just no current through
the tap changer contacts is an insufficient condition to allow operation of an OCTC.
The tap changer and the regulating winding arrangement can be made in three different ways,
either as linear, plus-minus or coarse-fine regulation. For small regulating ranges (say 10 % of
nominal value) it is common to use linear regulation. This means that the voltage across the
regulating winding is added to the voltage across the main winding; see the left sketch in Figure
6-14.
For larger regulating ranges a plus-minus regulation may be more suitable, see middle sketch. In a
plus-minus regulation the tapped winding is connected to the main winding via a separate plus
minus switch. This switch permits the voltage across the tapped winding to be added to or
subtracted from the voltage across the main winding.
A third arrangement is coarse-fine regulation where the regulation function is spilt into two
windings, one for the coarse step and one for the fine steps.
The choice of tapping arrangement affects among others:
• The number of leads to the tap changer;
• The loss pattern over the tapping range;
• The relative number of turns in the main and the regulating winding.
Figure 6-15
Figure 6-16
Figure 6-16 also shows the arrangement with shield rings. A shield ring with its large edge radii and
insulation improve the stress pattern at the winding ends. In addition the shield ring increases the
series capacitance of disc windings, which in turn reduces the non-linearity of the voltage
distribution along the winding during transient voltage conditions and lower dielectric stresses
within the winding is achieved.
The shield ring has a core of hard pressboard. A metal foil is wound around this core, but the foil
does not form a closed turn. The foil is connected to a winding conductor close to the winding end.
Outside the foil is a paper covering.
Figure 6-17
In most transformers the oil circulation through the windings is drawn automatically from the free
volume in the tank by thermosiphon effect. The flow will adjust itself to an equilibrium between the
thermosiphon driving head and the flow resistance in the duct. Another important physical property
of the oil then appears, namely its viscosity characteristic under varying temperature.
Figure 6-17 shows a transformer with natural oil circulation. Curve 1 in the diagram to the right is
the temperature profile in winding and tank. Curve 2 is the temperature profile in the radiators. The
shaded area between the two curves indicates available driving head.
In hot climate this is of little concern, but in an artic climate there may be real problems with “cold
start”, that is, when a transformer has been disconnected for some time and has to be started up
from a very low temperature. It may be so bad that pump motors stall. Or in a self-cooled unit the
circulation between tank and radiators does not start although the temperature in the tank has gone
up.
In cold climate, therefore, an oil with a lower viscosity index is usually specified. The requirements
regarding viscosity are expressed in terms of a highest allowable viscosity at a specified low
temperature and a highest allowable “pour point” temperature, that is, the temperature where the
oil just barely flows at all.
In some countries it is tradition to design very large transformers with “forced, guided” oil flow, that
is, the oil is pumped in a closed system of ducts right into the windings. The pump forces a defined
and constant flow, and it is secured even with considerable flow resistance in the cooling ducts. In
other countries this practice is denounced because any loss of auxiliary power would necessitate
tripping of the transformer with very short notice.
Figure 6-18
The maximum permissible radial force on an inner winding is set by the buckling strength. The
failure mode can be described as a radial slide of one or several sections of the winding shell. The
winding buckles. Due to the cylindrical shape of the winding the radial force cause a tangential
stress in the conductor material.
In order to visualise a buckling failure mode a disc section of the
winding (helical or disc winding) can be represented by a number
of parallel beams between two spacers. The beams are secured
from twisting by the spacers, the angle between the spacer and
the beam remains unchanged, but the spacer together with the
beam ends are free to move axially.
With this model it can be seen that the buckling withstand
increases with increasing conductor width. However, in addition
other factors or important, such as the free length of the beam,
that is the distance between two spacers, and the modulus of
elasticity of the conductor.
The buckling withstand is often a dimensioning factor of an inner
winding and consequently of the whole transformer.
ABB’s design and manufacturing practice is based upon the
experience from short circuit testing of about one hundred power
transformers. The service record of ABB transformers is excellent
Typical example on buckling regarding their ability to withstand short circuit currents.
of an inner winding
Figure 6-19
Figure 6-20
Before filling the oil the tank with the active part inside it is evacuated in order to remove all air that
would endanger the dielectric strength of the transformer insulation. Consequently the tank is
designed to withstand the pressure from the atmosphere with a minimum of deformations. The
tightness at outside and inside overpressure is verified through suitable tests.
The cover may be bolted or welded to the tank frame. Some users prefer a bell type tank where the
tank is welded or bolted to the tank bottom.
To keep the tank dimensions within the specified transport profile and, at the same time, enclose
the active part in the tank in with necessary insulation clearances and still obtain a reasonably
simple design often makes the designer’s task a considerable challenge when designing large
transformers.
Another phenomenon to take into account when designing tanks is that a coincidence of sound
frequencies generated by the transformer core and the resonance frequencies of parts of the tank
may enhance the sound radiated to the environment.
Figure 6-21
The tank is designed to permit the temperature dependent expansion of the oil. Most often a
separate expansion vessel is installed, also called conservator. Since the conservator is vented to
the air the oil pressure in the transformer remains fairly constant and independent of the
temperature. The free access of the surrounding air is limited. Good dielectric properties of the oil
require that the oil is clean and has low moisture content. Moisture in the oil will also accelerate the
ageing of the cellulose insulation. Air entering the conservator is therefore filtered and
dehumidified. In addition a diaphragm in form of a rubber sack that separates the oil in the
conservator from the air is recommended on power transformers. See Figure 6-21.
With increasing transformer power rating the effects of large currents in and out of the transformer
influence the design. The same goes for the leakage flux inside the tank. Inserts of non-magnetic
material around high current bushings reduce the risk of excessive heating. Tank lining with high
conductive shields expels the flux from entering the tank wall. Alternatively low reluctance material
takes care of the flux before it enters into the tank wall.
7.1.1. Bushings
Terminals device in form of bushing brings the connection from the transformer insulation medium
to the external insulation medium, which in most cases are air, but can also be oil in a cable
termination box or SF6 in a gas insulated switchgear. In transformer designs with gas cushion the
lower part of the bushing has to be extended to reach down into the transformer insulation medium.
The bushings provide the necessary insulation between the windings electrical connection and the
main tank, which is at earth potential. They provide also necessary insulation in the external
medium. They need to fulfil necessary current capacity. This makes a wide range of requirements
and accordingly a wide range of solutions.
The airside of an oil-to-air bushing may be done in a simpler way if only for indoor use.
7.1.1.1. Low voltage bushings
A simple low voltage oil-to-air bushing may be a rod of conducting material
inserted into a porcelain tube. This has a central current-carrying bolt, usually
of copper, and the insulation is provided by a combination of the porcelain
shell and the transformer oil. Under oil the porcelain surface creep strength is
very much greater than in air, so the oil portion of the bushing is short and has
a more or less plain porcelain surface. The air portion is longer and has shed
profile in order to provide a very much longer creep path, a portion of which is
protected so that it remains dry in rainy or foggy conditions. There are gaskets
sealing between rod and porcelain and between porcelain and tank wall to
prevent oil leaks.
The normal limit for these simple porcelain bushings is up to 45 kV system
voltage and current up in range of 10 kA.
Special low voltage bushings are available where extra efforts are put into the
design to get very low partial discharge levels.
7.2. COOLERS
The cooling equipment collects hot oil at the top of the tank and returns cooled oil lower down on
the side. The cooling arrangement can be seen as two oil circuits with an indirect interaction, one
inner and one outer circuit. The inner circuit transfers the loss energy from the heat producing
surfaces to the oil. In the outer circuit the oil transfer the heat to a secondary cooling medium. The
ambient air normally cools transformers.
It is possible to build air coolers with forced air circulation more compactly than cooler with natural
draught. However, such a cooler also has fairly high impedance to the oil circulation in the internal
circuit, which necessitates that the oil be pumped through the cooler. For built in transformers, e.g.,
deep underground power caverns or in some industrial application oil to water heat exchangers are
used; as in such cases, sufficient air for cooling may not be available. The system also permits
small physical dimensions. The disadvantage of the compact design is that auxiliary power must
always be available.
Present standards give clear definitions of the different types of cooling together with special
designations. The examples below are taken from IEC:
ONAN – Oil natural – air natural
ONAF – Oil natural – air forced
OFAN – Oil forced – air natural
OFAF – Oil forced – air forced
OFWF – Oil forced – water forced
On the oil side the oil can be directed to the heat producing surfaces by the oil pumps:
OD – Oil directed
A given transformer can have a combination of cooling types to permit a change in the type of
cooling e.g. ONAN/ONAF etc.
Pumps as well as fans sometimes suffer breakdowns. It must be possible to exchange such
components without emptying the transformer or even taking it out of service. All cooling circuits
should therefore be provided with necessary valves for shutting off each separate oil circuit.
The letter O is used for mineral oil and insulating liquid with fire point ≤ 300 °C.
The letter K is used for insulating liquid with fire point > 300 °C.
The letter L is used for insulating liquid with no measurable fire point.
7.2.1. Radiators
Radiators are available in various patters. They almost consist basically of number of flat passages
of edge-welded plates connecting a top and bottom header. It is possible to make the radiators
slightly higher than the tank so that the top header has a swan-necked shape, this has the added
benefit that it also improves the oil circulation by increasing the thermal head developed in the
radiator. The radiators have a venting plug in the top header and a draining plug in the bottom
header. Radiators are almost flanged direct to the transformer tank or to the headers in
freestanding cooler banks through a butterfly valve permitting individual radiators to be shut off and
even easily removed.
7.2.3. Fans
For larger units it is possible to suspend fans below or on the side of radiators to provide a forced
draught, and achieve ONAF cooling arrangement. This might enable the transformer loading
capacity to be increased by some 25%. The radiators have to be grouped in such a way to obtain
coverage by the fans.
The cooling fans will generate a low frequency noise, which will be added to the noise from the
transformer itself. The intensity depends on fan size, rotation speed and the design of the fan
blade. Fans are available in a rich several of designs. In basic it is a standard squirrel cage motor
totally enclosed with a propeller mounted direct to the shaft and in a casing provided with
necessary wire guards.
Fan is also a part of a forced air heat exchanger
Double-tube cooler may be applied. With such an arrangement the oil and water circuits are
separated by an interspaced so that any fluid leakage will be collected in this space and will raise
an alarm.
The on-load tap-changer has to provide uninterrupted current flow during the transition operation
from one tap to the other. The current flow must be maintained uninterrupted without partial short-
circuiting of the tapped winding.
As early as between 1905 and 1910 arrangements were introduced for changeover between
tappings of the transformer without interruption of supply.
When only limited regulating range, up to 10% of nominal value, is required it is common to
arrange the regulating winding for linear regulation. This means that the induced voltage in the
regulating winding is added to the voltage in the main winding. For larger regulation range so-called
plus-minus regulation may be more adequate. In a plus-minus regulation the tapped winding is
connected to the main winding via a separate plus minus switch. This switch permits the induced
voltage in the tapped winding to be added to or subtracted from the voltage in the main winding.
The third arrangement is a coarse-fine regulation where the voltage regulation function is split into
two winding, one for the coarse step and one for the fine steps.
Some comparisons of the three arrangements:
• All three need the same total number of turns in the windings.
• Linear need double number of steps in a fine winding compared to plus-minus or
coarse-fine which is a disadvantage when larger regulation range. Both due to the
design of the winding and complexity of the tap-changer.
• Plus minus need one separate winding less compared to coarse-fine.
• Coarse-fine give less load losses in the minus part of the regulation range compared to
plus minus.
• The plus-minus tap-changer and the coarse-fin tap-changer are almost equal; the
selector in both contains a changeover selector.
There are several different ways of arranging the regulation with regard to the size and the location
of the regulation winding. A regulating winding is difficult and expensive to manufacture and it
represents an insulation risk because those parts that are not connected in circuit will oscillate
freely when the transformer is subjected to over voltage surges. There is every reason to make the
regulating range and the regulating winding as small as possible.
In high voltage systems transformer, the windings are normally Y-connected. The location of the
regulating windings can then preferably be in the vicinity of the neutral point. The insulation level to
earth and between phases in the tap-changer may then be low.
Tap- changers are provided with counter that indicated the number of executed changeover
operations, and of course with an indicator for the actual tapping that is connected. It is often
required that this indication shall also be remotely available in the control room.
For the driving of the tap-changer there is a need for auxiliary motor power and in addition auxiliary
voltages for control and monitoring circuits and indicators.
The tap-changer is a moving mechanism and actually they are the only vital parts of the
transformer that do move and it should be serviced regularly.
7.4. ACCESSORIES
An alternate name for this gas-actuated relay is Buchholz relay after its inventor.
Free gas may be an indication of an incipient fault within the transformer. The gas is collected in
the gas relay. The gas will displace the liquid in the relay and a float will sink down. The protection
is therefore arranged in such a way that when a minor amount of gas is collected in gas relay an
alarm signal is actuated. If an additional amount of gas is collected tripping contact may be
actuated.
When a serious fault as arcing occurs in the transformer the gas evolution will push a burst of oil up
towards the conservator vessel and a flap is actuated. Sudden increase in oil flow is normally
judged to be a serve indication and the signal from the flap is then wired to tripping circuit.
Relay with only one of the two functions is utilized. For instance hermetically sealed transformers
without gas cushion has a small chamber on top of the cover with a float, which will actuate a
contact if gas is collected. This simple relay can also be used on small transformers even if a
conservator exists. A relay only sensitive to oil flow may be used between tap changer diverter
switch chamber and its conservator tank.
7.4.1.2. Temperature indication
Thermometers are normally installed for measurement of top oil temperature and winding hot spot
indication.
The top oil temperature can be measured directly by sensor in the oil top layer in the tank. For
remote indication of top oil a Pt 100 element can be arranged as the thermometer sensor.
The measurement of winding temperature is carried out in an indirect way. The winding hot spot is
assumed to be near the winding top end where it is surrounded by oil at top oil temperature.
Further the temperature gradient between winding hot spot and the top oil is dependent on the
losses in the winding, which in turn are proportional to the square of the current. The thermometer
therefore measures the top oil temperature to which it adds the temperature difference of the
winding to surrounding oil.
The winding thermometer is then arranged as a sensor inside a resistor immersed in the top oil. A
current transformer, which reflects the winding current, feeds the resistor. A shunt across the
resistor is adjusted to give a temperature contribution equal to the winding gradient as calculated or
measured during heat run test.
For remote indication of winding hot spot a Pt 100 element can be arranged as the thermometer
sensor.
Some winding thermometer designs perform the winding gradient addition in the thermometer
display unit using only the top oil temperature sensor and the winding current transformer out put.
The intention of using only spark gaps overvoltage protection of a transformer should be stated in
the technical specification.
Better protection is achieved by surge arrestors located close to the terminals as possible, direct on
the transformer tank or adjacent to the transformer. Also the ground connection between the
arrestor pad and the transformer tank should be as short and direct as possible.
If over voltage protection has to be situated some distance apart from transformer due to for
instance direct connection to SF6 switchgear or direct cable connection this has to be taken into
consideration when selecting transformer insulation level.
See also section 15.2 page 167.
8.1. GENERAL
8.1.1. Responsibilities
For power transformers, the installation and commissioning are normally performed by ABB.
Distribution transformers are normally installed and commissioned by the buyer.
In some cases the installation and commissioning is e.g. performed by the customer and
supervised by ABB.
Responsibilities are defined in the purchase contract with reference to General conditions, e.g.
ORGALIME.
Limitation of responsibilities should be defined, e.g. when recommended protection is not installed.
8.3.1. Energising
Prior to energising, the transformer has to be checked. If applicable the following items should be
reviewed:
• Inspection of transformer
• Check impact recorder:
o If impacts above a certain level are recorded the transformer must be checked for
transport damage,
• Check, painting, leakages and fastening:
o Conservator, cover, tank and coolers
• Bleeding:
o Cover, bushings, tap changer, Buchholz relay, cooling equipment
• Earthing of:
o Transformer, cabinets, current transformers, surge arresters, RC-network, tap-
changers, oil filter etc.
• Cooling equipment:
o OFWF: Check the mounting direction of oil pumps, oil flow-, and water flow
indicators. Adjust water- and oil flow indicators. Check the rotation direction of the
motors, motor voltage, motor protection. Check that all valves are open
o OFAF: Check the mounting direction of oil pumps, oil flow indicators. Adjust oil flow
indicators. Check the rotation direction of the motors, motor voltage, motor
protection. Check that valves are open.
o ONAF: Check the rotation direction of the motors, motor voltage, motor protection,
check that valves are open
o ONAN: Check that valves are open
• Tap-changer, oil filter and motor drive unit:
o Should be checked according to guidelines given by the manufacturer for this
equipment, e.g. locking of shaft connections, mounting direction protective relay,
symmetrical coupling, motor voltage, phase rotation, motor protection, end limit
switches (electrical and mechanical), emergency stop – raise and lower switch,
step by step, remote controlling etc. The checklist may vary depending on selected
manufacturer, type of tap-changer and equipment installed.
• Current transformers:
o Check polarity, and that all secondary CT circuits are closed before energising the
transformer. If a current transformer is not in use it has to be short cirquited and
earthed. An open circuited current transformer gives hazardous voltages and is
dangerous to personnel and equipment. It can result in personal injury, death or
property damage.
• Protective equipment:
o Check that all alarm signals from protective equipment is functioning, such as
thermometers, oil level indicators, Buchholz relay, oil flow-, water flow indicators etc.
o Check that all trip signals from protective equipment is functioning, such as
thermometers, oil level indicators, Buchholz relay, tap-changer protective relay,
etc. Trip signals are hard wired to the circuit breaker and all trip signals should be
checked to verify that the circuit breaker opens when a trip signal is activated.
After the transformer has been found to be in good condition and the protective equipment is found
in order according to the above list, the transformer is ready to be connected to the network
(energised).
In particular, when connecting distribution transformers to the network, fuses may blow immediately
caused by high inrush current. This does not necessarily mean that there is a fault in the
transformer. Replace blown fuses and try energising again because the magnitude of the inrush
current is a statistical variable with large spread. Modern over-current and differential relays contain
a filter which makes the relays insensitive to inrush currents. Older relays may trip the circuit
breaker immediately. See also section 11.7 page 141, paragraph “Inrush current”. After the
transformer has been connected to the network, gas may be present which cause the gas relay to
trip to give an alarm. It could be a false alarm caused by an air bubble, trapped under the cover,
and then moved into the gas relay. Air is colourless and odourless. If not air, a gas and an oil
sample should be taken for analysis.
Date for formal take-over can vary, but shall be clearly stated in the contract between supplier and
purchaser. This can be after the transformer is energised or after a test period of the transformer. A
hand-over protocol should be established, signed by both parties, see also section 8.1.2 page 110.
8.3.2. Documentation
The following documentation will be handed over to the purchaser at time of take-over as
applicable:
• Transformer specification
• Outline drawing
• Transport drawing
• Schematic drawing
• Wiring diagram
• Assembly, operation and maintenance manual
• Technical documentation from sub suppliers (bushings, tap-changer, coolers etc)
• Data sheet transformer oil
• Test protocol (FAT)
• Transport (shipping) documentation
• Trouble shooting guide
• Commissioning report.
• Take-over protocol
9.2. OPERATION
9.2.1. Lifetime
The lifetime of a transformer can be divided into two categories; economical and technical.
Economical lifetime:
Economical lifetime ends when the capitalized cost of continued operation of the existing
transformer exceeds the capitalized cost of a new investment.
In practical terms; typically when the cost of the total losses of the old transformer are too high.
Consequential risks and costs associated with electricity downtime are of increasing importance.
Technical lifetime - The ageing process of cellulose:
The cellulose materials undergo chemical degradation – ageing – in service. The dominant
processes have the character of oxidation and result in breaks of the long cellulose chain
molecules into shorter fragments, and the material becomes gradually more brittle. Old paper
breaks up into small flakes. But even in this state the dielectric breakdown voltage is hardly
affected at all.
The practical consequence of the ageing is a higher risk of mechanical rupture and metal-to-metal
contact as a result of mechanical shock and vibrations.
The cellulose molecule has a ring structure as shown to the left in Figure 9-1. Several of these
molecules are linked together to a chain by oxygen atoms. This is called polymerisation.
Figure 9-1
There is a standardised method of chemical analysis which provides information of the average
number of rings in the chains of cellulose molecules. This number is called the degree of
polymerisation, or abbreviated, the DP number. Virgin paper made of slow growing pine in cold
climate has typically a DP number of 1200 – 1400. There is a correlation between the DP number
and the tensile strength of the material and the degree of ageing can be expressed by the
decrease in DP number. When the DP number has fallen to 200, the material is quite brittle. It is
common to express the condition of the material by means of the DP number instead of the tensile
strength because the DP number can be determined with less measurement uncertainty than the
tensile strength when the ageing process has come to a certain stage.
The ageing is a cumulative process depending on influences from the environment in the
transformer. The rate of the chemical reaction rises with the temperature. V. M. Montsinger’s rule,
established after many years of intensive research, states that the rate of the chemical
deterioration process is doubled for each 6-7 °C temperature rise. However, this rate is
considerably increased by the presence of water molecules and free oxygen dissolved in the oil.
Figure 9-2
35
30
Breakdown electric field (kV/mm)
25
20
15
10
0
0 10 20 30 40 50 60 70 80 90 100
Moisture content in the oil (ppm )
Figure 9-3
The moisture content in the oil when performing the delivery test on a new transformer is maximum
5 ppm. It should be noted that the ac breakdown field declines quite much as soon as the moisture
content exceeds 20 ppm. Consequently there will be a fall also in the dielectric strength and the
service reliability of the transformer.
Figure 9-4 shows how the DP number decreases with the time in a test at 120 °C. In a new
transformer the moisture content in the solid insulation is dried to 0,5%. The curve in Figure 9-4 is
the result of a material test where samples with 3% and samples with 0,5% moisture content at the
beginning of the test were exposed to 120 °C. The vertical axis indicates the quotient of
simultaneous values of DP numbers. The declining curve that the DP number for the samples with
3% moisture is reduced at a higher rate than the samples with 0,5% moisture [5].
DP3%/DP0,5%
0,7
0,6
0,5
0,4
0,3
0,2
0,1
0
0 1 2 3 4 5 6 7 8
Weeks
Figure 9-4
Keeping the moisture content in the solid insulation and in the oil low increases the probability of
reliable transformer operation during many years, often more than half a century.
IEC 60076-7 Ed. 1: Loading guide for oil-immersed power transformer provides simplified methods
on how a theoretical consumption of insulation life can be calculated when overloading
transformers continuously and temporarily.
Practical experience shows that many transformers have been operated satisfactorily until a
change in system voltage has necessitated a replacement.
9.2.4. Frequency
A transformer designed for 50 Hz can be used for 60 Hz but not vice versa, however electric
equipment for accessories should be considered.
9.2.5. Protection
9.2.5.1. Overcurrent protection
There are two types of overcurrent protection:
• Fuses,
• Overcurrent relays which send tripping signals to the circuit breaker.
Overcurrent protection is mainly intended for protection against high overcurrents due to
external short-circuits.
9.2.5.2. Differential protection
Differential relays react upon different ampere-turns on the two sides of the transformer which
indicates that there may be an internal fault in the transformer.
9.3. MONITORING
9.3.1. General
Most transformers are equipped with protection systems to avoid damage to the transformers, the
network or both, in the event of non-normal operation of the transformer or the network. Examples
of such protection systems are the network and transformer protection current transformers
mounted usually at the transformer terminals feeding relays (overcurrent, differential), the gas and
oil activated relay (Buchholz) and the winding and oil temperature indicators (WTI and OTI). These
systems are common to most power transformers, including some distribution transformers.
However, monitors are mostly confined to medium to large power transformers, in particular those
that are strategically important in a network or, as in the case of generator step-up transformers
and HVDC converter transformers, where the transformers are the only means of power transfer in
networks. An unplanned transformer outage in these networks can have severe technical and
economic consequences for the network operator. The main purpose of fitting monitors to these
transformers is for condition assessment with the purpose of mitigating some of the above
difficulties [Draft IEC 61378-3 Convertor transformers - Part 3: Application guide].
Monitoring of transformers can roughly be divided in high and low level monitoring.
• High level
o On-line monitoring
• Low level
o Periodic recording of a few parameters, visual inspection
o Oil condition monitoring
o Off-line monitoring
Figure 9-5
Older transformer can be equipped with a monitoring system called T-Monitor.
9.4.1. General
The primary purpose of transformer maintenance is to ensure the internal and external parts of the
transformer and accessories are kept in good condition and “fit for purpose” and able to operate
safely at all times. A secondary and equally essential purpose is to maintain a historical record of
the condition of the transformer [draft IEC 61378-3 Convertor transformers - Part 3: Application
guide].
Transformer maintenance can be done periodically or as condition based maintenance. The latter
is usually the most economical way of doing maintenance. Recommended maintenance are then
done based on one or more of the following; inspections, analysis of oil samples, electrical
measurements, test of equipment, measurement of temperatures by using a heat sensitive camera,
monitoring (off-line and/or on-line).
For dry-type transformers the off-circuit tap changing is generally done by means of bolted links.
9.4.11. Coolers
Coolers are cleaned by means of e.g. brushing inside the water tubes or air side vacuum cleaning
when necessary. Need for cleaning is indicated by increased pressure loss, decreased
temperature-difference oil/water/air in/out, increased transformer temperature, decreased water
flow etc. See the supplier’s documentation.
10.2. REUSE
Transformers contain valuable materials, which may be reused either as is or after reprocessing.
Examples are:
• Copper,
• Aluminium,
• Oil,
• Steel.
Insulation material, pressboard and paper, represent energy.
10.3. LANDFILL
Materials not re-circulated go to landfill or energy production. The landfill portion of the transformer
should be minimized.
p = 3 ⋅ R ⋅ I2 (W) (1)
At a system voltage U the transmitted active power is:
Figure 11-1
If the loop is replaced by a coil with N number of series-connected turns, the same induced voltage
will take place in each of the turns. The voltage induced in the whole coil will then be:
dΦ
ui = −N ⋅ (V) (7)
dt
The other physical phenomenon is that a conductor carrying an electrical current is surrounded by
a magnetic field.
H
I
Figure 11-2
To create a magnetic field that varies in time in a transformer a sinusoidal voltage is applied to the
primary winding which creates a magnetising current.
The windings are made as concentric shells around a central core of laminated steel plates, which
is formed as a closed loop for the magnetic field. Due to the magnetic properties of the steel the
magnetic flux will be several thousand times higher than it would have been without the steel core,
which makes the magnetic coupling between the windings strong.
or
N2
U 2 = U1 ⋅ (V) (9)
N1
When the secondary winding is loaded, the voltage ratio may differ considerably from the turn ratio
(see 6.5.), while the ratio between the primary and secondary currents fulfils the equation:
I1 ⋅ N1 = I 2 ⋅ N 2 (10)
with a deviation of one percent or less.
I2
Z0 U20 U2 ZL
Figure 11-3
In no load condition (open secondary terminals) the total magnetising current and the active power
consumption are measured at rated voltage. The current has one dominant inductive component
and one smaller active component. These can be calculated from the measurements, and the real
and the imaginary components of transformer’s no load impedance Z0 can be found. This
impedance is not constant but will vary non-linearly with the applied voltage due to the non-linearity
of the magnetisation curve. The real part of Z0 represents the no load losses.
The other impedance in the diagram, Z, is found by short-circuiting the secondary terminals and
applying a voltage at the primary side. The current in the windings during this measurement shall
be equal to the rated current. To achieve this current an applied voltage of just a fraction of the
rated voltage will be sufficient. This voltage is called the short-circuit voltage and is usually
expressed as a percentage of the rated voltage. The impedance of the circuit is given by the
quotient of the short-circuit voltage divided by the rated current. The circuit is a parallel connection
of Z0 and Z. Because Z0>>Z the impedance of the parallel connection is equal to Z with a negligible
difference. The real part of Z represents the load losses of the transformer, and the imaginary part
is attributed to the magnetic leakage field. That is the part of the magnetic field, which is situated
outside the core.
∆U2
φ
U20 ux φ
ur
I2
U2
Figure 11-4
From the vector diagram in Figure 11-4 the following relationship appears:
(V) (11)
∆U2 = I2 ⋅ r ⋅ cos ϕ + I2 ⋅ x ⋅ sin ϕ + U 20 − U220 − (I2 ⋅ r ⋅ sin ϕ − I2 ⋅ x ⋅ cos ϕ)
2
∆U2 is the voltage drop, the arithmetic difference between U20 and U2. ur and ux are the active and
the reactive short-circuit voltages at rated current related to the rated voltage U20.
To calculate the relative voltage drop at any relative loading n (see (13)) equation (11) can be
rewritten as
∆U2 (12)
= n(ur cos ϕ + ux sin ϕ) + 1 − 1 − n2 (ur sin ϕ − ux cos ϕ)
2
U20
I2 (13)
n=
I 2N
In other words, when a transformer with these values for ur and ux is loaded with rated current with
a power factor of 0,8 inductive the voltage on the secondary terminals decreases to 95,5% of the
voltage at no load.
1,1
U2/U20 1,05
1
n=0,5
0,95 n=1
n=1,3
0,9
0,85
-90 -60 -30 0 30 60 90
Angle ϕ (degrees) of loading current
Figure 11-5
Figure 11-5 shows an example of how the secondary voltage varies with various angles of ϕ and
load currents for the particular values ur = 0,74% and ux = 10 %. Negative angles of ϕ mean
lagging (inductive) load current. Positive angles of ϕ mean leading (capacitive) load current.
Note that at angle φ above a certain positive value the secondary voltage increases compared to
voltage at no load.
0,99
0,98
0,97
0,96
U2/U20
0,95
Powerfactor=1
0,94
Powerfactor=0,9
0,93 Powerfactor=0,8
Powerfactor=0,7
0,92
0,91
0 2 4 6 8 10 12
ux %
Figure 11-6
Figure 11-6 shows another example of how the secondary voltage may vary at various values of
the short circuit reactance ux and of cosφ. In general the secondary voltage decreases with
increasing ux. Note that for example at ux=10 % and cosφ=0,8 the secondary voltage has dropped
to 93% of the no load voltage.
11.6. Efficiency
The efficiency of a transformer is calculated according to:
1
η% = ⋅ 100
P + PL ⋅ n 2
1+ 0
P2 ⋅ n
where
P0 is the no load loss k(W) at rated voltage
PL is the load loss (kW) at rated current
P2 is the active power (kW) supplied to the load
n is the relative degree of loading. At rated current n=1.
T=Vs/m2
d
B
e
f c
H
A/m
Figure 11-7
At point e the current has decreased to zero. And again there is a remanent flux floating in the
core, this time with the opposite direction compared to the remanent flux at point b. Increasing the
current now in the negative direction, the flux decreases further and becomes zero at point f. From
point f on the flux changes direction and increases in the negative direction until it reaches point a.
Now one cycle of the applied voltage is completed.
The physical explanation for the described course of events is, expressed in the following simplified
way, a ferromagnetic material has numerous small magnets attached to its crystalline molecular
structure. Within certain domains these magnets have the same orientation. In the original state of
the material these domains are randomly orientated, and the magnetic field from each of them
practically cancels each other so there is no resulting magnetic field.
If the material is placed in an external magnetic field, this will have an impact on the orientation of
the domains. As the external field is increasing, more and more of the domains will change their
direction so the direction of their magnetic field coincides with the direction of the external field.
If the external field gradually decreases, more and more domains will slide out of the orientation
they obtained due to the external field. But when the external field has disappeared, there will still
be a considerable number of domains, which remain in the same direction as they were under the
influence of the foregoing external field.
Exposed to an increasing external field of opposite direction, more and more domains will change
orientation. At a certain value of the external field, the orientation of the domains will be so mixed
that there is no resulting magnetic field from them. Further increase of the external field will cause
more and more domains to change their direction gradually so the direction of their magnetic field
coincides with the new direction of the external field.
Due to the many magnetic domains that become unidirectional, the total magnetic field will be
thousands of times higher than the original external field that directed the domains.
Figure 11-8
Figure 11-8 shows a typical shape of this current, which can be constructed from the hysteresis
loop. It has a short peak value due to the low slope of the magnetising curves (the right and the left
strings of the hysteresis loop) at high flux densities. It is non-symmetrical on the two sides of the
peak value due to the width of the hysteresis loop.
The no load current measured at the delivery test and noted in the test report is the r.m.s.-value of
the non-sinusoidal no load current. For three-phase transformers the average value for the three
phases is noted.
Eddy current losses
Another component of the no load losses is the eddy current losses. The time-variable magnetic
flux induces currents running in paths perpendicular to the direction of the flux. These currents
produce losses in the core plates. These losses can be calculated by means of the following
formula:
u = dΦ (V) (18)
dt
This can also be seen the opposite way, the magnetic flux is the time integral of the voltage:
dΦ = u ⋅ dt (Vs) (19)
Φ = ∫ u ⋅ dt (Vs) (20)
Assuming that the voltage is sinusoidal and the integral is taken over the first half cycle of the
voltage, that is from 0 to π, where 0 is the time when the circuit breaker makes and π is the time
when the voltage changes direction:
π
Φ = ∫ U ⋅ sin(ωt ) ⋅ d(ωt ) = U(− cos π − ( − cos 0)) = 2U (Vs) (21)
0
To compare this result with the situation when the circuit breaker makes at the peak value of the
voltage, the integral is taken between the limits π/2 and π.
π
Φ=
π
∫ U ⋅ sin(ωt ) ⋅ d(ωt ) = U(− cos π − (− cos π 2)) = U (Vs) (22)
2
Φ t = 2Φ + Φ r (Vs) (23)
which makes the inrush current even higher.
Figure 11-9
Figure 11-9 illustrates the situation. The light grey curve marked Φ’ is the magnetic flux in the
normal stationary condition.
u z% ⋅ U r u z% 2
Z= = ⋅ Ur Ω (26)
100 ⋅ Ir 100 Sr
for single phase transformers and
u z% ⋅ Ur u z% 2
Z= = ⋅ Ur Ω (27)
3 ⋅ 100 ⋅ Ir 100 Sr
R ⋅ Ir
ur% = ⋅ 100 % (32)
Ur
For three-phase transformers a factor √3 is inserted in the nominator. There is a simple relation
between ur, the load losses PL and the rated power Sr of the transformer:
u x = u 2z − u r2 p.u.
(34)
or %
X= Z2 − R2 Ω (35)
While X0 is mainly linked to the magnetic field in the core, X is linked to magnetic leakage field,
which mainly runs through the windings and the ducts between windings.
Figure 11-10
When the transformer is energized but not loaded, the practically the whole magnetic field goes in
the core. When loading the transformer with a lagging current, a part of the magnetic field is drawn
out from the core to the core window where the windings are situated. See Figure 11-10. The
magnetic flux in the core becomes smaller. Typically for distribution transformers the high voltage is
applied to the outer winding. The secondary low voltage winding is the inner winding where the
voltage decreases.
If a capacitive load is added the resulting current decreases because the capacitive current partly
compensates the inductive current. The leakage field becomes smaller and the flux in the core
increases and makes the voltage drop on the secondary side smaller.
If the transformer is loaded with a leading current, that is a current with a resulting reactive current,
which is capacitive, this capacitive load supplies reactive power to the transformer. The magnetic
flux in the core and the secondary voltage increase.
The reactive power of the magnetic energy of the leakage field is
Dimensions in meter. N is the number of turns in the winding on the side to which X shall be
referred. See Figure 6-11.
t1 t12 t2
Figure 11-11
In the formula (37) L1 and L2 are the mean circumference for the inner and outer windings
respectively. The formula is based on the assumption that the magnetic field lines goes vertically
along the whole height hw of the windings. This is in reality not the case. It can be seen from Figure
11-10 that some of the field lines towards the ends of the windings have an increasing horizontal or
radial component. The German professor W. Rogowski made a careful study on how to
compensate for this deviation from the assumption in the formula. The result of this study
(published early in the last century) was a correction factor
(t 1 + t 12 + t 2 ) −
πh w
kR = 1− 1 − e (t1 + t12 + t 2 ) (38)
πh w
This factor has is known as the the Rogowski factor. In most practical cases its numerical value is
within the range 0,95 – 0,99. It makes the length of the leakage field duct a little longer, hw/kR
instead of hw.
The formula for ux expressed as a percentage of the rated voltage Ur is
u x = 2( t 12 +
t1 + t 2 L1 + L 2
) kR
(IN) f 10 −2
% (39)
3 hw e t 0 50
where et0 is the number of volts per turn in no load condition.
Corresponding hand formulas exist also for more complicated winding arrangements. The short-
circuit reactance or short-circuit voltage calculated by means of these formulas comply very well
with the measured values. However, for high currents an addition for the reactance in the lead
assembly must be made.
U
I sc = kA (40)
3 ⋅ (Z + Z s )
Where Zs is the short-circuit impedance of the system.
U 2s
Zs = In ohms per phase (equivalent star connection) (41)
S
R X
Û sin( ωt + α )
i(t
Figure 11-12
Consider the circuit in Figure 11-12. Assume that the switch makes at the instant t = 0, thus
simulating a short-circuit. The current i(t) is expressed by the following equation:
i( t ) = Î ⋅ (sin(ωt + α − ϕ) − e
−t
τ
⋅ sin(α − ϕ)) A (43)
in which
Û
Î = A (44)
Z
that is the peak value of the symmetrical, stationary short-circuit current
Z = R + jωL [Ω]
α = switching angle of the voltage u(t) at the instant of the short circuit [rad]
ϕ = phase angle of the circuit impedance (=arctg ωL/R) [rad]
τ = L/R = tgϕ/ω [s] (the time constant of the circuit)
ω = 2·π·f [s-1]
π −t
i( t ) = Î ⋅ (sin(ωt − ) + e τ ) A (45)
2
The first current peak closely corresponds to the time when ωt = π.
2
1,5
Isc 1
p.u. 0,5
0
0 20 40 60 80
-0,5
-1
t
Figure 11-13
i = Î ⋅ k = I sc ⋅ 2 ⋅ k = I sc max A (46)
where the asymmetry factor k is
− πR (47)
k = 1+ e X
k√2
2,2
2,0
1,8
1,6
1,4
1 10 100
X/R
Figure 11-14
Mechanical forces in the windings
Current flows through the winding conductors, which are situated in the magnetic leakage field. The
conductors are then subject to mechanical forces.
These forces are not static. They are pulsating. Each time the current passes through zero the
forces are also zero. At normal load current the forces are small. They increase with the square of
the current, so during the high overcurrents that arise if a short-circuit in the system occur, the
forces must be given attention when designing the transformer. The short circuit current may
amount to 10 – 20 times the rated current of the transformer, which means that the forces in the
windings may be 100 – 400 times larger at a short circuit than in normal service. For transformers
with extremely low short circuit impedance the figures might be still higher.
The forces cause large movements in the windings. These movements are invisible for the human
eye. But rapid film recordings played in slow motion show the size of the movements and illustrate
the violence of the forces.
I
B
F=IХB
Figure 11-15
When considering the ability of a design to withstand it is usual to split the forces into radial and
axial components as indicated in Figure 11-15, which shows an upper part of an outer winding. The
radial force is directed outwards and causes a tensile force in the winding conductors. In the
corresponding inner winding the radial component is directed inwards. That may cause buckling of
the winding if it has not been made robust enough.
The axial forces are caused by the radial component of the magnetic field at the ends of
the windings. These forces may lead to tilting of the conductors between the axial spacers in
the winding. The force on each turn or disc adds together. The sum of the forces is balanced at
the other end of the winding. The whole winding is subject to a strong axial pressure. See
Figure 11-16.
Figure 11-16
The ability to withstand tilting of the conductors depends on the diameter of the winding, the
distance between the spacers around the circumference and the dimensions of the conductor.
In case of axial “openings” in the winding, that is one or more places along the height of the
winding where there are no ampere-turns, there will be axial forces directed towards the yokes.
The framework keeping the core and windings together must be designed to be able to withstand
such forces.
A more comprehensive treatment of the short-circuit topic is given in the book “SHORT-CIRCUIT
DUTY OF POWER TRANSFORMERS – THE ABB APPROACH” by Giorgio Bertagnolli, issued by
ABB. The book is available from ABB at request.
p2
L p = 10 ⋅ lg dB (48)
p 02
where p is the sound pressure measured by a microphone. Sound pressure is a scalar quantity,
which means it has magnitude only.
To provide a feeling of how a few well-known types of sound are situated on the dB-scale some
values are listed below.
Source of sound Sound pressure level in dB
Quiet living area 45
Normal conversation at 1 m distance 60
Medium factory noise 75
Factory maximum limit 85
City street with heavy traffic 95
Circle saw at 1 m distance 105
Comprehensive investigations are made to correlate human perception of ‘loudness’ at various
frequencies and sound pressures. The curves in Figure 11-17 are results of such investigations.
These curves will vary somewhat from one person to another, but they can be regarded as average
curves for how young persons with healthy ears respond.
Each curve represents sound that is perceived as ‘equally loud’ across the whole frequency range.
The lowest curve that goes through zero dB sound pressure at1000 Hz represents the hearing
threshold. The human ear is not able to hear anything below this curve. It appears that the ear is
most sensitive in the frequency range between 3 and 4 kHz, where a sound pressure even below
20 µPa is audible.
For frequencies below 700 Hz the threshold curve ascends, which means that for the lower
frequencies the sound pressure has to be increased to make the sound audible. The curve also
rises at frequencies above 4 kHz.
The three upper curves go through 40, 70 and 100 dB at 1 kHz. A microphone responds quite
differently to sound pressure. In order to imitate the response curves of the human ear filters are
inserted in the measuring equipment. Three different filters are standardized, named A, B and C
filters. They imitate the curves going through 40, 70 and 100 dB at 1 kHz respectively.
Measurement results made with one of the three filters inserted are denoted dB(A), dB(B) or dB(C).
120
C-weighted filter
110
100
90 B-weighted filter
Sound pressure (dB)
80
70
60 A-weighted filter
50
40
30
20 Hearing threshold
10
0
-10
10 100 1000 10000 100000
Sound frequency (Hz)
Figure 11-17
W
L w = 10 ⋅ lg db (49)
W0
In this formula W0 is an arbitrarily chosen reference value equal to 10-13 Watt, which corresponds to
a quite weak sound source. This reference value is chosen without regard to the previously
mentioned reference value for sound pressure.
The sound power of one of the strongest sound power sources of concern, a large jet motor, has a
sound power of about 100 000 Watts. The total power range to deal with is then 1018. Instead of
working with such extremely high figures in acoustical subjects, the whole power range is covered
by 180 dB.
Based on the measured sound pressure the sound power of the transformer in dB can be
calculated according to formulas given in IEC 60076-10 Ed. 1.0.
In a large free field the sound pressure at larger distances from the transformer can be calculated.
In practice there are often one or more walls or other items in the surroundings of the transformer
that will reflect sound from the transformer and make a prediction of the sound pressure at various
places in the neighbourhood difficult.
Sources of sound generation
The dominant generating source of transformer sound is magnetostriction. Magnetostriction is the
change in dimensions which takes place in certain materials when they are subjected to a change
in magnetic flux. In magnetic core steel the dimensional change is in the range of 10-7 to 10-5
meters per meter length at typical induction levels.
The effect does not depend on the sign of the flux, only on its magnitude and orientation relative to
certain crystallographic axes of the material. Therefore, when excited by a sinusoidal flux, the
fundamental frequency of the dimensional change will be twice the exciting frequency. The effect is
highly non-linear, especially at high, near saturation, induction levels. The non-linearity results in a
significant harmonic content in the vibration spectrum of the core.
In three-phase cores the change in dimension in each core limb does not occur simultaneously,
which means that the whole core will be subject to pulsating distortions that also generate sound.
A DC bias in addition to the AC magnetization of the core may significantly increase the vibration
amplitudes of the core and consequently the sound level. The DC bias may also cause a
considerable difference in the positive and negative peaks of the flux density, which in turn makes
the fundamental frequency of the sound equal to the frequency of the service voltage instead of
twice this frequency.
Figure 12-1
The primary, secondary and tertiary sides of a transformer may in principle be connected
individually in any of the three ways indicated above. This offers several different combinations
of connections in a transformer with different characteristics, which also may be influenced by
the type of core. In this handbook the description will be limited to the most frequently used
connection combinations.
The Y-connection is the natural choice of connection for the highest voltages and when the
neutral is intended for loading. In any case a neutral bushing should be provided either for
overvoltage protection purpose or for direct earthing. In the latter case the insulation level of the
neutral may be made lower than in the phase end of the winding with economical benefit.
The Y-connected winding has also the benefit that tappings for turn ratio regulation can be
provided at the neutral end where also a tap changer can be located. The tap changer will then
operate at a low voltage level to earth, and the voltage difference between the phases is low as
well. A cheaper tap changer can be selected compared to a tap changer located at a higher
voltage level.
When Y-connection is used in one side of the transformer, one other side should preferably be
delta connected, especially when the neutral of the Y-connected winding is intended to be
loaded. The delta connected winding provides ampere-turn balance for the zero sequence
current floating through the neutral and each phase of the Y-winding, which gives a reasonable
zero sequence impedance. Without a D-connected winding the zero sequence current would
create a zero sequence field in the core. If the core has 3 limbs, such a field will find its path
from yoke to yoke through the tank wall and create excessive heating there. If the core has 5-
limbs or is a shell type core, the field will find its path from yoke to yoke through the unwound
side-limbs, and the zero sequence impedance will be extremely high. A consequence is that the
current in case of an earth fault might become so small that the protecting relays do not react.
In a D-connected winding the current through each phase-winding is the line current divided by
√3, while in a Y-connected winding the line current floating through each phase-winding is equal
to the line current. On the other hand the D-connected winding requires √3 times as many turns
as a Y-connected winding for the same voltage.
The D-connected winding is advantageous in large power transformers when the current is high
and the voltage relatively low, like for example in the low voltage winding of generator step up
transformers.
Figure 12-2
The frequently used combination Yd11 means for instance that there is 30 ° displacement
between the voltages of the two sides as illustrated in Figure 12-2.
Physical Additional
Viscosity Low particle content
Appearance Compatibility with other transformer
materials
Density Gassing properties
Pour point Aromatic structure
Surface tension Poly-aromatic structure
Flash point Solubility properties
4,5
4
R0/X1=0
3,5 R0/X1=0,5
R0/X1=1
Earth-fault factor.
3 R0/X1=2
R0/X1=5
2,5 R0/X1=50
1,5
0,5
0
-15 -10 -5 0 5 10 15
X0/X1
Figure 15-1
The duration of the overvoltage corresponds to the duration of the fault and will remain until fault
clearing. In systems without earth-fault clearing the duration may be several hours. This will imply
surge arresters with higher protection level and lower safety margin regarding transient
overvoltages.
In insulation co-ordination knowledge about the earth-fault factor at various places in the network,
in different loading conditions and system configurations is of vital importance. A thorough system
analysis is necessary.
16.3. IP-CLASSIFICATION
16.3.1. General
IP classification describes to what extent electrical equipment, in this regard the transformer
terminals as well as accessories, are protected against touching and external influence such as
dust, pollution, moisture etc.
Reference is made to IEC 60529 for a detailed description on this subject. *Copyright © IEC,
Geneva, Switzerland. www.iec.ch
Explanation of numerals : IP23
The first characteristic numeral (2) describes the protection against solid foreign objects of 12.5
mm diameter and greater.
The second characteristic numeral (3) describes the protection against spraying water.
1.1 1.2
2.1 2.2
Figure 16-1
According to ANSI/IEEE C57.12.70-1978TM, the two terminals at the high-voltage side shall be
marked H1 and H2 and the two terminals at the low-voltage side shall be marked X1 and X2.
X2 X1
Figure 16-2
When Single-Phase transformers are used in a three-phase system, they are connected in Three-
Phase Banks. In figure Figure 16-3 is an example with three Single-Phase transformers connected
∆-Y used in Three-Phase Banks with 30° angular displacements.
A B C
H1 H2 H1 H2 H1 H2
ADDT ADDT ADDT
PLRT PLRT PLRT
X2 X1 X2 X1 X2 X1
a b c
Figure 16-3
For more information about how to use single-phase transformers in three-phase banks see
ANSI/IEEE C57.12.70-1978TM.
Figure 16-4
According to ANSI/IEEE C57.12.70-1978TM, the terminals shall be located and marked from left to
right in following sequence, at the high-voltage H0, H1, H2, H3, and at the low-voltage X0, X1, X2, X3
side both seen from the low-voltage side. (H0 and X0 are the neutral terminals.)
16.6.1. Definitions
*Copyright © IEC, Geneva, Switzerland. www.iec.ch
The International Electrotechnical Vocabulary (IEV) gives the following definition of EMC:
”The ability of an equipment or system to function satisfactorily in its electromagnetic environment
without introducing intolerable electromagnetic disturbances to anything in that environment.” [IEV
161-01-07]
Other relevant definitions are:
Electromagnetic disturbance
Any electromagnetic phenomenon which, by being present in the electromagnetic environment,
can cause electrical equipment to depart from its intended performance [IEV 161-01-05, modified]
Electromagnetic interference (EMI)
Degradation of the performance of equipment, transmission channel or system caused by an
electromagnetic disturbance.
NOTE The terms “electromagnetic disturbance” and “electromagnetic interference” denote respectively
cause and effect, but they are often used indiscriminately. [IEV 161-01-06]
Disturbance level
The amount or magnitude of an electromagnetic disturbance, measured and evaluated in a
specified way [IEV 161-03-01, modified]
Electromagnetic compatibility level
The specified electromagnetic disturbance level used as a reference level in a specified
environment for co-ordination in the setting of emission and immunity limits
NOTE By convention, the compatibility level is chosen so that there is only a small probability that it will be
exceeded by the actual disturbance level. [IEV 161-03-10, modified]
Immunity level
The maximum level of a given electromagnetic disturbance incident on a particular device,
equipment or system for which it remains capable of operating at a required degree of performance
[IEV 161-03-14]
Unit Unit
Quantity
Symbol Name
Length m metre
Mass kg kilogramme
Time s second
Electric current A ampere
Thermodynamic temperature K kelvin
Luminous intensity cd candela
Quantity of substance mole mole
Name Section
Karlsen, Roar 2.1, 2.3, 16.5
[email protected]
Løvlien, Svein Ola 5, 7.1, 7.2, 7.3, 7.4.1, 7.4.2,
[email protected]
Parma, Diego 0, 1.1, 1.2,
[email protected]
16.10. FEEDBACK
Any feedback regarding editorial changes, additional subject proposals etc. can be sent by E-mail
to [email protected].
Any questions regarding the various subjects can be sent by E-mail to the author with a copy to
[email protected].
1)
New edition in process
1)
New edition in process
Re. 5 INSULATION
As conventional (air insulated) installations cannot be impulse tested, the installation requires
minimum clearances between live parts and earth and between live parts of phases in order to
avoid flashover below the impulse withstand level specified for individual tested components of the
installation.
Insulation coordination shall be in accordance with IEC 60071-1.
Table 1 – Minimum clearances in air – Voltage range I ( 1 kV < Um ≤ 245 kV
kV kV kV kV mm mm
20 60 120
3 3,6 10
40 60 120
40 60 120
6 7,2 20
60 90 120
60 90 150
10 12 28 75 120 150
95 160 160
75 120 160
15 17,5 38
95 160 160
95 160
20 24 50 125 220
145 270
145 270
30 36 70
170 320
I 45 52 95 250 480
66 72,5 140 325 630
b
185 450 900
110 123
230 550 1 100
b b
185 450 900
132 145 230 550 1 100
275 650 1 300
b b
230 550 1 100
150 170 275 650 1 300
325 750 1 500
b b
275 650 1 300
b b
325 750 1 500
220 245 360 850 1 700
395 950 1 900
460 1 050 2 100
a The rated lightning impulse is applicable to phase-to-phase and phase-to-earth.
b If values are considered insufficient to prove that the required phase-to-phase withstand voltages are met,
additional phase-to-phase withstand tests are needed.
c For rod-structure.
Re. 7 INSTALLATIONS
Re. 7.1 General requirements
This clause specifies only general requirements for the installations regarding choice of circuit
arrangement, circuit documentation, transport routes, lighting, operational safety and labelling.
Distances, clearances and dimensions specified are the minimum values permitted for safe
operation. They are generally based on the minimum values given in the former national standards
of the IEC members. A user may specify higher values if necessary.
NOTE For minimum clearances (N) of live parts, refer to 5.3 and to tables 1 and 2 and annex A.
National standards and regulations may require the use of higher clearance values.
Where an existing installation is to be extended, the requirements applicable at the time of its
design and erection may be specified as an alternative.
The relevant standards for operation of electrical (power) installations shall additionally be taken
into account. Operating procedures shall be agreed upon between manufacturer and user. Where
applicable, the documentation shall be provided with each installation to allow erection,
commissioning, operation, maintenance and environmental protection.
The extent of the documentation shall be agreed upon between the supplier and the user.
Diagrams, charts and tables, if any, shall be prepared in accordance with IEC 60617 and IEC
61082.
Re. 7.1.6 Operational safety
Operational safety installations shall be designed so that the escape and rescue paths and the
emergency exit can be safely used in the event of a fire, and that protection and environmental
compatibility are ensured.
Where necessary, installations themselves shall be protected against fire hazard, flooding and
contamination. If required, additional measures shall be taken to protect important installations
against the effects of road traffic (salt spray, vehicle accident).
If automatically activated fire extinguishing equipment is installed, the clearance G can be reduced.
Doors shall have a fire resistance of at least 60 min. Doors which open to the outside are adequate
if they are of fire-retardant material and construction. Ventilation openings necessary for the
operation of the transformers are permitted. When designing the openings, the possible escape of
hot gases shall be considered.
a
The wall in this area shall be designed to avoid spread of fire.
NOTE In addition, the water from the fire extinguishing (if any) should be considered
a
Containment: the entire quantity of fluid of the transformer plus rain water
NOTE In addition, the water from fire estinguishing installation (if any) should be considered
a
Containment outdoor: the entire quantity of fluid of the largest transformer plus rain
Containment indoor: the entire quantity of fluid of the largest transformer
NOTE The dotted area denotes the volume of the entire quantity of insulating fluid of the
transformer spilled on the floor
Figure11 – Example for small transformer without gravel layer and catchment tank
Note:
We reserve the right to make technical changes or modify the contents of this document without prior notice.
With regard to purchase orders, the agreed particulars shall prevail.
ABB does not accept any responsibility whatsoever for potential errors and or possible lack of information
in this document.
We reserve the rights in this document and in the subject matter and illustrations contained therein.
Any reproduction – in whole or in parts – is forbidden without ABB’s prior written consent.
Reference is also made to copyright notes contained in the text, e.g. to Copyright © IEC, Geneva,
Switzerland. www.iec.ch.
ABB 2004.