Lecture10 Combined Footings
Lecture10 Combined Footings
Lecture #10
Combined Footings
- Rectangular Footings.
- Trapezoidal Footings.
L. Prieto-Portar 2008
A combined footing is usually used to support two columns of unequal loads. In such a
case, the resultant of the applied loads would not coincide with the centroid of the
footing, and the consequent the soil pressure would not be uniform.
The area of the combined footing may be proportioned for a uniform settlement by
making its centroid coincide with the resultant of the column loads supported by the
footing.
There are many instances when the load to be carried by a column and the soil
bearing capacity are such that the standard spread footing design will require an
extension of the column foundation beyond the property line. In such a case, two or
more columns can be supported on a single rectangular foundation. If the net
allowable soil pressure is known, the size of the foundation B x L can be determined.
This photo shows an example of
combined footings used in a heavy
industrial plant, where the machinery
loads place very large loads upon
relatively confined space.
Step #1. The required design area A of a footing can be found from,
Q1 + Q2
A= (1)
qall net
where Q1, Q2 are the loads in columns #1 and #2, and q all (net) is the net allowable soil bearing
capacity.
Step #2. Determine the location of the resultant of the column loads.
Q2 L3
x= (2)
Q1 + Q2
Step #3. For a uniform distribution of soil pressure under the footing, the resultant of the
column loads should pass through the centroid of the foundation. Thus,
L = 2( L2 + x ) (3)
where L = length of the foundation
Step #4. Once the length L is determined from above, the value of L1 can be obtained from,
L1 = L – L2 – L3 (4)
The magnitude of L2 will be known and depends on the location of the property line.
The width B of the foundation then is then found from,
(5)
A
B=
L
L2 Q#1 L3 Q#2 L1
R =Q1 +Q2
X
Section view
L
Plan view
Figure 1
Trapezoidal Combined Footing.
This type of combined footing, shown in Figure 2, is sometimes used as an isolated spread
foundation for a column that is required to carry a large load in a tight space. The size of
the trapezoidal footing that will generate a uniform pressure on the soil can be found
through the following procedure.
Step #1. If the net allowable soil pressure is known, determine the area of the footing,
Q1 + Q2
A=
qall net
From Figure 2, A = [ ( B1 + B2 ) / 2 ] L (6)
Step #2. Determine the location of the resultant for the column loads,
Q2 L3
x=
Q1 + Q2
B1 + 2 B2 L
From the properties of a trapezoid,
x + L2 = [ ]
B1 + B2 3 (7)
With known values of A, L, x, and L2, solve equations (6) and (7) to obtain B1 and B2. Note
that for a trapezoid (L/3) < (x+ L2) < (L/2).
Q#1 Q#2
R=Q#1+Q#2
L2 L3
L1
X
Section view
B1 B2
Plan view
Figure 2
Cantilever or Strap Footings.
The strap is used to transmit the moment caused from an eccentricity to the interior
column footing so that a uniform soil pressure is generated beneath both footings.
Property line
Plan view
Figure 3
Example #1.
Design a rectangular combined footing, given that f’c = 3.5 ksi, fy = 50 ksi, qall = 5 ksf
with a SF = 3, Df = 5 feet, the edge of column #1 is at the property line, and the spacing
between columns is 18 feet center-to-center (c.c.).
Step 1: Determine the ultimate column loads and the soil stress at ultimate loads qult.
B = (P1u + P2u) / (L)(qu) = 932/(22)(7.97) = 5.31 feet Use B = 5 ft-4 in. for construction.
q’ = (qu)(B) = (7.97)(5.31) = 42.3 k/ft.
Step 3: Draw the shear (V) and moment (M) diagrams.
The column loads are treated as concentrated loads acting at the centers of the columns.
The shear and moment diagrams are,
Step 4: Determine the footing thickness T.
Note that the diagonal-tension analysis reflects on a three-sided section for column 1
and a four-sided section for column 2. If column 2 were close to the end of the footing,
a three-sided analysis might be required; however, that’s not the case here. First
determine d via a wide-beam analysis, then check for the diagonal tension. From the
shear diagram, the maximum shear is near column 2. At a distance d from the face of
column 2.
V = 340.8 – 42.3 d
V = column load less upward soil pressure = P1u – (A)(qult) = 410 – A(7.97)
But A = (18 + d/2)(18 + d) = (18 + 17.1)(18 + 34.3) = 1835.7 in2 = 12.75 ft2
At column 2,
As (d - a/2) = Mu / Ø fy (B)
For fy = 50 ksi, f’c = 3.5 ksi, b = 12 in., therefore a = (As fy) / (0.85) f’c b = 1.40 As
Provided that 1/3 of the bars extend the full length of the footing, the bars could be cut
off as dictated by the moment requirements (the moment diagram). However, the
saving is not worth the effort (engineering, fabrication, placing, possible mistakes,
etc.). Thus, typically, all bars will run the full length of the footing.
+As = (1.65)(5.31) = 8.76 in2. Use 9 # 9 bars, As = 9 in2 > 8.76 in2.
This As is larger than that required by positive +M. Place these bars at 7 in. c.c.
leaving approximately 4 in. from each side and 4 inches above the footing invert.
Also, based upon the moment diagram, running 1/3 of +As (three bars) the full length
of the footing satisfies both ACI and the moment requirements. The other six bars
could be cut off at say, half-length and placed on the right half (under column 2) of the
footing.
Step 6: Determine the area of the transverse reinforcing steel, As,
Based on pmin, As in 11.96 ft-section = 19 in2, thus, use 19 # 9 bars at 8 in. c.c.
Step 7. Prepare a drawing showing the design details.
P1 P2
L = 22 ft
B = 5 ft 4 in. 24 in. x 24 in.
18 in. x 18 in.
11 # 10 bars full length
3 ½ in
L = 22 ft
Example #2.
Design a strap-footing for the following conditions, f’c = 3.5 ksi, fy = 60 ksi, and qa = 2.5
ksf for both the footing and the strap, with a FS=4. The edge of column 1 is placed at the
property line, and the center of the columns are 25 feet center-to-center (c.c.).
Column #1 (12 in. x 12 in., with 4 # 7 bars) Column #2 (16 in. x 16 in., with 6 # 8 bars)
DL = 80 kips DL = 120 kips
LL = 60 kips LL = 110 kips
Step 1: Determine the ultimate column loads and the soil stress at ultimate loads qult.
NOTE: While a deeper strap is more efficient than a wider but shallower one (i.e., larger l ),
too narrow a strap may pose some practical or functional concerns (e.g., limited space for
reinforcement, lateral or torsional stiffness). It is recommended that the range for strap widths
b as 2ft b (L’/10) ft, and an effective depth, d, 50 to 100% larger than theoretically needed,
in order to reduce the number of reinforcing bars (thus, accommodating spacing) and to
minimize the effects of an uneven excavation and perhaps eliminate the need for stirrups. L’ =
distance between footings.
Footing #1. For b = 9 feet and vc = 14.4 ksf, therefore (9)(14.44) d = 179.34 – 34.65 d
Solving, d = 1.09 feet = 13 inches.
Use 13 # 8 bars ( As = 10.20 in2). Extend 7 # 8 bars from the strap the full length (7 feet)
and add 3 # 8 bars at approximately 16 in. c.c. on each side of strap bars.
Step 6: Prepare a drawing showing the details of the design.
References.