HEAT PUMP THERMOSTAT CROSS REFERENCE/SELECTION GUIDE
70-6627 • 2
HEAT PUMP THERMOSTAT CROSS REFERENCE/SELECTION GUIDE
70-6627 • 3
HEAT PUMP THERMOSTAT CROSS REFERENCE/SELECTION GUIDE
70-6627 • 4
HEAT PUMP THERMOSTAT CROSS REFERENCE/SELECTION GUIDE
Outdoor Reset
Some heat pump thermostats apply outdoor reset to minimize the effect of the interstage differential. It takes more than a
one-degree change in temperature to initiate the second stage of heating. Added to a certain amount of droop under
high loads, there can be a fairly large offset between the setpoint temperature and the room temperature. To correct this
difference, an outdoor thermistor is used.
In warm weather, the outdoor thermistor has a very low resistance, permitting a large amount of current to flow in the
heater. This reduces the call for second stage heating.
In cool weather, the outdoor thermistor has a very high resistance, permitting a small amount of current to flow in the
heater. When this happens, calls for second stage heating are more frequent. This helps reduce the difference between
the setpoint temperature and the room temperature.
Select one of the following T841 or Y594 models if a thermostat with outdoor reset capability is required:
T841A1555
Y594G1161
Y594R1763
If an outdoor thermistor is not provided, use the Honeywell C815A Outdoor Thermistor, ordered separately.
NOTE: All Honeywell electronic heat pump thermostats are droopless controls and do not require the use of outdoor reset.
70-6627 • 5
HEAT PUMP THERMOSTAT CROSS REFERENCE/SELECTION GUIDE
Using the Chronotherm III or Chronotherm IV T8611M on Two-Speed Heat Pump Compressor Equipment
The T8611M is a three-stage heat/two-stage cool thermostat used to control multistage heat pump equipment. However,
there is no difference in controlling multistage equipment and in controlling two-speed multistage equipment. The
differential required between stage 1 and stage 2 in multistage equipment is the same as the differential required
between low-speed and high-speed in two-speed equipment.
Equipment T8611M
Equipment Function Terminals Terminals
Transformer Common C C
Power R R
Fan G G
or
Cooling Changeover O O O/B
or
Heating Changeover B B O/B
W2
Emergency Heating E E
M13229
70-6627 • 6
HEAT PUMP THERMOSTAT CROSS REFERENCE/SELECTION GUIDE
Adaptive Intelligent Recovery™ control assures that the comfort setting is achieved at the programmed time regardless
of weather conditions. Conventional recovery starts recovery at the beginning of the programmed time period and uses
the equipment to achieve the comfort settings as soon as possible.
Unlike the Chronotherm III models, the Adaptive Intelligent Recovery control can be turned off in the Installer Set-up
mode in the Chronotherm IV thermostat. Honeywell does not recommend this because the auxiliary heat comes on
when the program time begins, and runs continuously until the setpoint is reached.
* The O terminal is connected to the coil terminals on the R8222B Switching Relay. When the system switch is in the
COOL position, the O terminal is energized, reversing the logic of the Chronotherm III T8611G and T8611M Y
terminal. Now when the thermostat calls for cooling, the Y terminal activates the first stage of cooling.
70-6627 • 7
HEAT PUMP THERMOSTAT CROSS REFERENCE/SELECTION GUIDE
Equipment T8611M
Equipment Function Terminals Terminals
Power R R
Fan G G
Transformer Common C C
O
R8222B Relay
Heating Changeover B B
M13231
Fig. 2. Installing an R8222B Switching Relay on heat pumps requiring heating mode changeover.
* The B terminal is connected to the coil terminals of the R8222B Switching Relay. When the system switch is in the
HEAT position, the B terminal is energized, reversing the logic of the Chronotherm® III T8611G and T8611M Y
terminal. Now when the thermostat calls for heating, the Y terminal activates the first stage of heating.
Equipment T8611M
Equipment Function Terminals Terminals
Power R R
Fan G G
Transformer Common C C
B
R8222B Relay
Cooling Changeover O O
M13230
Fig. 3. Installing an R8222B Switching Relay on heat pumps requiring cooling mode changeover.
70-6627 • 8
HEAT PUMP THERMOSTAT CROSS REFERENCE/SELECTION GUIDE
To change the fan operation on the TRADELINE and SUPER TRADELINE models, follow the wiring diagram shown
below. Connecting the thermostat and relay to the equipment in this manner disables the fan switch in the emergency
heat mode. During normal operation, the fan switch is enabled and the fan operation is as described in the installation
instructions.
R (Power)
E C (Common)
E (EM. Heat)
G G (Fan)
Fig. 4 Changing fan operation in emergency heat mode for electronic thermostats.
O
M13235
Fig. 5. Relay wiring connections for Carrier equipment (typical 38BQ), and T8511M, T8611M,
PC8900/W8900B1002. Require relay (R8222B1067 typically) for proper operation.
70-6627 • 9
HEAT PUMP THERMOSTAT CROSS REFERENCE/SELECTION GUIDE
Power Red R
Emergency Heat
A L
M13241
Fig. 6. Relay wiring connections for Evcon/Coleman equipment (3200, 3300). Requires R8222B1067
Relay to operate system. Equipment requires normally energized emergency heat.
Power Red R
Emergency Heat A
M13236
Fig. 7. Relay wiring connections for Evcon/Coleman equipment (3200, 3300, 3360, 3400, 6000, and 6500).
Requires R8222B1067 Relay to operate system. Equipment requires normally energized emergency heat.
System Monitor L
or
L X1
M13237
Fig. 8. Relay wiring connections for Lennox equipment (HP9, HP10). Requires R8222B1067 Relay to operate the
system monitor light (emergency heat LED) on TRADELINE replacement thermostats. Tape off if light is not desired.
70-6627 • 10
HEAT PUMP THERMOSTAT CROSS REFERENCE/SELECTION GUIDE
System Monitor L
or or
L X1 F
M13238
Fig. 9. Relay wiring connections for Lennox equipment (HP16, HP19, HP21, HP22 Direct Replacements).
Requires R8222B1067 Relay to operate the system monitor light (emergency heat LED) on
TRADELINE replacement thermostats. Tape off if light is not desired.
System Monitor X1
or
L X1
M13239
Fig. 10. Relay wiring connections for Magic Chef equipment (PE Series). Requires R8222B1067 Relay
if outdoor section has reset shunt relay and malfunction light indicator is desired on thermostat.
or
System Monitor L X
or
L X1
M13240
Fig. 11. Relay wiring connections for Mammoth. Requires R8222B1067 Relay if outdoor
section has reset shunt relay and malfunction light indicator is desired on thermostat.
70-6627 • 11
HEAT PUMP THERMOSTAT CROSS REFERENCE/SELECTION GUIDE
Equipment PC8900
Equipment Function Terminals Terminals
Transformer Common C C
Power R R
Fan G G
O/B
Changeover Valve B
Emergency Heat E E
M13233
Fig. 12. Relay wiring connections for PC8900 in heat pump applications
requiring separate Y1 and W1 terminals with a heating changeover.
Equipment PC8900
Equipment Function Terminals Terminals
Transformer Common C C
Power R R
Fan G G
O/B
Changeover Valve O
Emergency Heat E E
M13234
Fig. 13. Relay wiring connections for PC8900 in heat pump applications
requiring separate Y1 and W1 terminals with a cooling changeover.
70-6627 • 12
HEAT PUMP THERMOSTAT CROSS REFERENCE/SELECTION GUIDE
Understanding Circuits
To understand wiring diagrams, it is important to know what all the symbols mean and how to trace the path of the
circuits from the transformer. Circuit descriptions and terminology are defined as follows:
Auto changeover—refers to the presence of an AUTO position in the system switching (EX: Q674F with OFF-COOL
AUTO-HEAT-EM. HEAT switching). The thermostat automatically changes between heat and cool modes as
indoor temperature changes.
Manual changeover—requires a system switch movement to change mode (EX: Q674L with EM. HT.-HEAT-OFF-
COOL switching).
Cool changeover valve—operates on cooling. The reversing valve or relay is activated either by moving the system
switch to COOL (manual changeover) or by a mercury switch that makes on a temperature rise (auto changeover).
Heat changeover valve—operates on heating. The reversing valve or relay is activated either by moving the system
switch to HEAT (manual changeover) or by a mercury switch that makes on a temperature fall (auto changeover).
System monitor relay—optional equipment on some heat pumps. This system monitor relay detects a malfunction in
the compressor and indicates the malfunction by activating the EMERGENCY HEAT LED on the switching
subbase. The system monitor relay may be wired to the L terminal on some thermostats
Each anticipator is identified and each switch affected is named (EX: H1 anticipator, C1 anticipator).
All T874 Multistage Thermostats use mercury switches. Each schematic indicates switch operation by being drawn
in the open position with an arrow indicating operation with a temperature RISE or FALL.
RELAY/CONTACTOR CONTACTS
TRANSFORMER
(24 VAC SECONDARY)
B
TERMINAL
RELAY OR CONTACTOR COIL
LED
ODT
MERCURY SWITCH OUTDOOR THERMOSTAT
EHR
EMERGENCY HEAT RELAY
FIXED ANTICIPATOR
HIGH RESISTANCE RTD
(TYPICALLY 5 KILOHMS) TIME DELAY RELAY
RD
DEFROST RELAY
CHP
ADJUSTABLE ANTICIPATOR PRESSURE SWITCH
LOW RESISTANCE LACO
(TYPICALLY 0 TO 5 OHMS) LOW AMBIENT CUTOFF
M5848
70-6627 • 13
HEAT PUMP THERMOSTAT CROSS REFERENCE/SELECTION GUIDE
Why is this so important? Because today’s sophisticated control systems require reliable, accurate voltage output for
optimal system performance. It’s especially important for electrical controls (OEM boards in high efficiency furnaces, for
example) or resistive heaters, such as thermostat heat anticipators.
For better performance, some heat pumps require a NEMA standard transformer. Conformance to NEMA standards
assures the voltage output of a transformer will remain within acceptable limits, regardless of load conditions. No
excessively high open-circuit voltage under light load conditions. No low, “brown-out” voltage levels under heavy load
conditions. At 100% load, the transformer secondary must supply between 23 and 25 volts to meet the NEMA standard.
How can you tell that the transformers you buy meet this tough, high standard? Look for the transformer to be marked:
NEMA Type B (20VA), NEMA Type D (40VA), NEMA Type E (48-50 VA). Only transformers conforming to the NEMA
standard can be marked in this way. The following are recommended Honeywell NEMA standard transformers:
AT72D1691, AT72D1683, AT87A1106
27
26
25
24
SECONDARY VOLTAGE
23
22
21
20
19
18
17
16
15
14
70-6627 • 14
HEAT PUMP THERMOSTAT CROSS REFERENCE/SELECTION GUIDE
1
RTD 1 ODT 1
H1 FAN
SWITCH EHR 1 RTD 2
C1
FALL
AUTO
H1/C1 ODT 2
ON
ANTICIPATOR
EHR 2 RTD 3
FAN RELAY
R
W2
H2 ANTICIPATOR AUX. HT.
LED (GREEN) RTD 1
E
H2 RD
EM. HT. RELAY
L
FALL
2 EM. HT. SYSTEM MONITOR
EM. HT. LED (RED)
HEAT B
1 COOL CHANGE-
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND
OVER VALVE
OVERLOAD PROTECTION AS REQUIRED.
M6060A
2 NO AUTO FAN IN EMERGENCY HEAT.
Fig. 16. Internal schematic and typical wiring diagram for T841A1308.
70-6627 • 15
HEAT PUMP TH ERMOSTAT CROSS REFERENCE/SELECTION GUIDE
G
9
FAN RELAY
H1 W
C1
FALL 2 AUX. HEAT
U RELAY
2 AUX. HEAT
C
LED (GREEN)
ANTICIPATOR FAN
SWITCH B
3
H1/C AUTO EM. HEAT
ANTICIPATOR LED (RED)
ON
5
F
COMPRESSOR
8 MONITOR
L1
R (HOT)
11 OUTDOOR
L2
THERMOSTAT
SYSTEM SWITCH
X2 1
3
12
EM. HT.
T
HEAT
FALL H2
10 OFF
OUTDOOR
THERMISTOR
1 COOL O
Fig. 17. Internal schematic and typical wiring diagram for T841A1555.
W3
W3 RELAY
FALL
O
COOL
10 CHANGEOVER
H1
C1 RELAY
EM. HEAT
5 FAN LED (RED)
SWITCH
AUTO
2
H1
ANTICIPATOR ON
G
FAN RELAY
3 L2
1
C1 R
ANTICIPATOR L1
(HOT)
7 9
E
EM. HEAT RELAY
SYSTEM X
8 6 SWITCH
AUX. HEAT
EM. HT. LED (GRN)
12 W2
HEAT AUX. HEAT RELAY
H2
H2 ANTICIPATOR OFF
FALL
11
COOL B
HEAT
CHANGEOVER
RELAY
COMPRESSOR
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS CONTACTOR
AND OVERLOAD PROTECTION AS REQUIRED.
Y
M13249
Fig. 18. Internal schematic and typical wiring diagram for T841A1712 and T841A1738.
70-6627 • 16
HEAT PUMP THERMOSTAT CROSS REFERENCE/SELECTION GUIDE
W1
H1/C1
ANTICIPATOR HEAT RELAY 1
H1 W2
C1
HEAT RELAY 2
FALL
B
R L1
(HOT)
SYSTEM
L2
SWITCH 1
X
HEAT
H2 ANTICIPATOR
OFF
Y1
H2 COOL
FALL COMPRESSOR
CONTACTOR
Fig. 19. Internal schematic and typical wiring diagram for T841B1000.
C815A OUTDOOR
THERMISTOR
FALL T
FAN
H1
SWITCH
FAN RELAY
H1 ANTICIPATOR AUTO
G
ON
CHANGEOVER
VALVE
O
H2 L1
R
(HOT)
FALL L2
X2 1
RESET SYSTEM
HEATER SWITCH OUTDOOR
THERMOSTAT
EM .HT.
RISE
W
AUTO
AUX. HT. AUX. HT.
CHANGEOVER LED (GREEN) RELAY
OFF
B
EM. HT.
LED (RED)
C1
ANTICIPATOR F
Y
RISE
C1 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. M1593
Fig. 20. Internal schematic and typical wiring diagram for Y594G1161.
70-6627 • 17
HEAT PUMP THERMOSTAT CROSS REFERENCE/SELECTION GUIDE
1 O
FALL H1 ANTICIPATOR FAN SWITCH
COOL CHANGEOVER
AUTO VALVE
2 G
ON B RELAY
FAN RELAY
H1 B
4
L1
R (HOT)
6
SYSTEM
L2
H2 SWITCH
ANTICIPATOR E 1
OFF
EM. HT. RELAY
H2 FALL EM. HT. L
W2
C1 ANTICIPATOR
Y
10
COMPRESSOR
11 CONTACTOR
RISE
CO 1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND M8702
12 OVERLOAD PROTECTION AS REQUIRED.
Fig. 21. Internal schematic and typical wiring diagram for Y594G1633.
1 FAN
SWITCH W3 RELAY
CHANGEOVER
W3
(HEAT) AUTO
2 ON G
FALL H1
ANTICIPATOR FAN RELAY
L2 1
3
R L1
FALL 4 (HOT)
W2
H2 EM. HT.
RELAY AUX. HEAT
5
RELAY
H2 ANTICIPATOR E
AUX.
H1 HT. LED
FALL (GREEN)
6 SYSTEM X1
SWITCH
COMPRESSOR
CHECK
CHANGEOVER 8 OFF FAULT
LED (RED)
(COOL)
9 EM. HT. X2
RISE HEAT EM. HT.
LED (RED)
AUTO
10 X
C1 COOL COOL CHANGEOVER
ANTICIPATOR VALVE
O
C1
RISE B
11
HEAT CHANGEOVER
W1 RELAY VALVE
W1
2 COMPRESSOR
CONTACTOR
Y1
Fig. 22. Internal schematic and typical wiring diagram for Y594G1419 and Y594G1476.
70-6627 • 18
HEAT PUMP THERMOSTAT CROSS REFERENCE/SELECTION GUIDE
1 G
FAN RELAY
W
2 AUX. HEATER
AUX. HEAT 2
AUTO U RELAY
LED (GREEN)
H1 ON
C1
B
FALL 3 EM. HEAT COMPRESSOR
FAN MONITOR
LED (RED)
SWITCH
F
1
4 L1
R
(HOT)
L2
H2
FALL 5 SYSTEM
SWITCH
T
EM. HEAT
6
HEAT OUTDOOR
X2 SENSOR
OFF
OUTDOOR
THERMOSTAT
11 COOL
O
COOL
COMPRESSOR
CHANGEOVER
CONTACTOR
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND VALVE
OVERLOAD PROTECTION AS REQUIRED. Y
M8701
2 FIELD REMOVABLE JUMPER.
Fig. 23. Internal schematic and typical wiring diagram for Y594R1763.
L1
2
R (HOT)
H1 AND C1 L2
ANTICIPATOR
FAN
3 SWITCH L 1
COOL E
COMPRESSOR
EM. HEAT CONTACTOR
RELAY
Y
"B" RELAY
B
M8700
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
Fig. 24. Internal schematic and typical wiring diagram for Y594R1797.
70-6627 • 19
HEAT PUMP THERMOSTAT CROSS REFERENCE/SELECTION GUIDE
W3
W3 RELAY
O
COOL CHANGEOVER
VALVE
COMPRESSOR
L
MONITOR
H1 FAN RELAY
FAN
ANTICIPATOR
1 SWITCH G
AUTO
C ANTICIPATOR ON L1
2 R (HOT)
L2
1
H1 3 W2
C
EM. HT. AUX. HT. RELAY
FALL
LED (RED)
SYSTEM
SWITCH
4 AUX. HT. E
LED (GRN)
EM. HT. RELAY
EM. HT.
5
H2 HEAT X
ANTICIPATOR
6 3
H2 OFF
FALL X2 HEAT
COOL CHANGEOVER
VALVE
B
11
W1 RELAY
Fig. 25. Internal schematic and typical wiring diagram for Y594R1425.
70-6627 • 20
HEAT PUMP THERMOSTAT CROSS REFERENCE/SELECTION GUIDE
2
L1
R
(HOT)
POWER HIGH L2
SUPPLY LIMIT 1
C/X
FAN AUX. HT.
SWITCH LED (GREEN)
EM. HT.
ON
LED L
THERMO- SUBBASE (RED)
STAT LOGIC/ AUTO MONITOR AUX. HT.
LOGIC CONTROL RELAY
CIRCUIT CIRCUIT W2
HEAT 2
FAN RELAY
G
EM. HT.
Y
HIGH
LIMIT COMPRESSOR
HEAT 1 X1 CONTACTOR
3
CHECK
LED
(YELLOW)
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD
PROTECTION AS REQUIRED. X2
X2 TO C/X X2 TO C/X X2
70-6627 • 21
HEAT PUMP THERMOSTAT CROSS REFERENCE/SELECTION GUIDE
L1
R (HOT)
4
POWER HIGH L2
SUPPLY LIMIT 1
3
C
FAN AUX. HT.
SWITCH LED (GREEN)
EM. HT.
ON
LED L
THERMO- SUBBASE (RED)
AUTO MONITOR AUX. HT.
STAT LOGIC/ RELAY
LOGIC CONTROL
CIRCUIT CIRCUIT W3
HEAT 3
STAGE 2
RELAY
W2
HEAT 2
EM. HT. RELAY
EM. HT.
COOL CHANGEOVER
C. O. VALVE
HEAT O
OFF
HEAT CHANGEOVER
AUTO C. O. VALVE
B
COOL
STAGE 1 COMPRESSOR
COOL 1
CONTACTOR
Y
HEAT 1
STAGE 2 COMPRESSOR
HIGH CONTACTOR
LIMIT Y2
COOL 2
S1 S1 5
X1
S2 S2
2
CHECK
S3 S3 LED
(YELLOW)
6 200905 REMOTE
SENSOR X2
X1 TO R X1 TO R X1
X2 TO C X2 TO C X2
4 NOMINAL 24 VAC POWER MUST BE PRESENT BETWEEN R AND C TERMINALS FOR THERMOSTAT OPERATIONS.
5 AVAILABLE ONLY ON MODLES WITH SEPARATE SENSOR FOR REMOTE TEMPERATURE SENSING.
6 RECOMMENDED INTERCONNECT CABLE: 18-GAUGE THERMOSTAT CABLE, 200 FT. (61 M) MAXIMUM LENGTH.
ROUTE INTERCONNECT CABLE AWAY FROM SOURCES OF ELECTRICAL NOISE. M2656
70-6627 • 22
HEAT PUMP THERMOSTAT CROSS REFERENCE/SELECTION GUIDE
L1
R
(HOT)
POWER HIGH L2
SUPPLY LIMIT 1
C
EM. HT.
3 LED AUX. HT.
LED (GREEN) MONITOR
FAN (RED)
SWITCH L AUX. HT.
THERMO- SUBBASE RELAY
ON
STAT LOGIC/
W2
LOGIC CONTROL
CIRCUIT CIRCUIT AUTO
HEAT 2 EM. HT. RELAY
E
STAGE 1
HEAT RELAY
W1
EM. HT.
HEAT O
2 COOL
OFF CHANGEOVER VALVE
COOL
B
HEAT CHANGEOVER
VALVE
HIGH Y1
LIMIT
HEAT 1
COMPRESSOR
COOL 1 CONTACTOR
P
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED. DEFROST
CONTROL
2 REMOVE JUMPER FOR SYSTEM WITH ISOLATED STAGE 1 HEATING AND COOLING CONNECTIONS.
L1
R (HOT)
THERMISTOR STAGE 2 RELAY
SENSOR L2
AUXILARY
THERMOSTAT HEAT RELAY 1
LOGIC SYSTEM
SWITCH W2
RELAY
EM. HT.
L
HEAT CHANGEOVER
VALVE HEAT
OFF
B
COOL CHANGEOVER
VALVE COOL
O
STAGE 1 RELAY COMPRESSOR
CONTACTOR
2 COMPRESSOR
CONTACTOR
HEAT
W1
EMERGENCY
HEAT RELAY
FAN SWITCH E
FAN RELAY
ON
G
POWER AUTO
SUPPLY
C
70-6627 • 23
HEAT PUMP THERMOSTAT CROSS REFERENCE/SELECTION GUIDE
L1 1
(HOT) L2
C
POWER COMPRESSOR
SUPPLY CONTACTOR HEAT
W2 W1
W1
AUXILIARY
HEAT RELAY
W2
EMERGENCY
THERMOSTAT HEAT RELAY
LOGIC 3
W2 W1 E
COMPRESSOR
CONTACTOR
E Y1 G O/B
Y1
FAN RELAY
E
G
Y1
G CHANGEOVER
O/B 2
VALVE
O/B
COMPRESSOR
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD CHECK LED (RED) MONITOR
PROTECTION AS REQUIRED.
L TO R
2 O/B IS FIELD CONFIGURABLE TO SELECT ENERGIZED IN HEATING OR
COOLING. (DEFAULT IS ENERGIZED IN HEATING).
OT
3 REMOVE JUMPER, WHEN SUPPLIED, FOR SYSTEMS WITH SEPARATE OUTDOOR
HEATING COMPRESSOR CONTACTOR (W1 SEPARATE FROM Y1). SENSOR C7089B
OT
M13281
70-6627 • 24
HEAT PUMP THERMOSTAT CROSS REFERENCE/SELECTION GUIDE
L1 1
(HOT) L2
C
POWER COMPRESSOR
SUPPLY CONTACTOR HEAT
W2 W1
E W1
AUXILIARY
HEAT RELAY
W2
THERMOSTAT EMERGENCY
4 HEAT RELAY
LOGIC
E
COMPRESSOR
CONTACTOR
Y1
3
CHANGEOVER
VALVE
O/B
Y
O/B
G
G
FAIL LED (RED) FAN RELAY
X1
M13250
70-6627 • 25
HEAT PUMP THERMOSTAT CROSS REFERENCE/SELECTION GUIDE
70-6627 • 26
HEAT PUMP THERMOSTAT CROSS REFERENCE/SELECTION GUIDE
Table 3. T8511G Sequence of Operation for Separate Compressor Terminal (Y and W1) Models.
Fan Selection System Selection Call Energize Display Icons
Auto Off None None None
On Off Fan G
Auto Heat or Auto Stage 2 heating O/B a, W1, W2, G , , and Aux Ht
70-6627 • 27
HEAT PUMP THERMOSTAT CROSS REFERENCE/SELECTION GUIDE
Auto Heat or Auto Stage 2 heating B or O/B a with W2, W1 and G , , and Aux Ht
70-6627 • 28
HEAT PUMP THERMOSTAT CROSS REFERENCE/SELECTION GUIDE
70-6627 • 29
HEAT PUMP THERMOSTAT CROSS REFERENCE/SELECTION GUIDE
70-6627 • 30
HEAT PUMP THERMOSTAT CROSS REFERENCE/SELECTION GUIDE
70-6627 • 31
HEAT PUMP THERMOSTAT CROSS REFERENCE/SELECTION GUIDE
70-6627 • 32
HEAT PUMP THERMOSTAT CROSS REFERENCE/SELECTION GUIDE
Existing
Control Electronic Perfect Climate
Terminal Electromechanical Chronotherm III Replacement Chronotherm IV Comfort Center
Designation Thermostat Thermostat or Upgrade Thermostat Control System
C Hook wire X or to C or to C or to C or to C
previously
on C to X
R Hook wire R or to R or to R or to R or to R
previously
on R to R
M13251
7. Connect only those terminals shown with lines to them on the diagram. Some terminals on the new thermostat may
not be used.
8. Refer to the following two pages for an example of a typical cross reference diagram and the associated footnotes.
70-6627 • 33
HEAT PUMP THERMOSTAT CROSS REFERENCE/SELECTION GUIDE
61 2 2
L 100 0
10 1
20 2
10 6
10 2
K 1M2 017
T8 611M 100
G1 19
1G 00
1G 02
2
1G 00
1R 00
1G 00
00 0/
5
4
47
28
28
14
00
2
L 02
94 14
89 90
61 R1
51 G1
71
61 G2
01 R1
41 R1
42
47
T8 611M
B1
Y5 594G
W PC8
A1
R1
T8 8611
T8 8511
T8 8011
T8 8611
T8 8411
41
94
T8
Y
T
T8
T
T
Y5
Function
Common A X X X C C C C C C C
Power R R R R R R R R R R
or E
Compressor Y Y Y1 Y1 Y Y Y1 Y Y1 Y1 Y1/W1
I I I I I I I
1st Stage – W1 W1 W1 W1 W1 W1 W1 – –
Heat M
F
Auxiliary W2 W2 W2 W2 W2 W2 W2 W2 Y2 Aux.
Heat
P P P P P P P
Fan G G G G G G G G G G
C C C
or or or C
C/O Valve B B B B B B O/B B B O/B B O/B O/B
Heat
C C C
or or or C
C/O Valve O O O O O O O/B O O O/B O O/B O/B
Cool
G H H G H G GH G
System Monitor/ – L L L L L L L L
Sytem Defrost
Em. Heat E E E E E E E E E E
Multiple Heat W3 W3 W3 J J J J J W3 J
Loads B
D D D
D
LED Indication – X2 X1 X2 X1 X2 – – – X1 X2 X1 X2 –
N
Defrost – – – P – – – – – –
F
2nd Stage – – – – – – – – Y2 W2
Compressor
O
2nd Stage – – – – – – – – – Y2
Cool in two
Stage System
M13245
70-6627 • 34
HEAT PUMP THERMOSTAT CROSS REFERENCE/SELECTION GUIDE
X1 TO R X1 TO R X1
X2 TO C/X X2 TO C/X X2
70-6627 • 35
AMANA
Models: RHA1842A, RHA (24-42)A2A, RHA (48-60)A2A, RHA (36, 48, 60)A3A & A4A, RHD (18-24)A2A, RHD (30-60)A2A,
RHE (18-24)A2A, RHE (30-60)A2A, RHA (36, 48, 60)A3B & A4B.
10 1
20 2
10 4
10 6
10 2
G1 19
1G 02
1G 00
1R 0 0
2
1R 00
00 0/
1R 00
47
28
00
14
28
00
5
6
94 14
2
51 G1
89 90
61 G1
61 G2
01 R1
42
47
41 R1
71
B1
Y5 594G
W PC8
R1
T8 8511
T8 8611
T8 8611
T8 8011
A1
T8 8411
Existing
94
41
T
T
T
T
Y5
T
Function Terminals T8
or or
Common C X X1 C X X X C C C C C C
Power R R R R R R R R R R
or D
Compressor Y Y Y Y1 Y1 Y Y Y1 Y Y1 Y1/W1
B B B B B B B B
1st Stg. Heat W1 – W1 W1 W1 W1 W1 W1 W1 –
I
Aux. Heat W2 W2 W2 W2 W2 W2 W2 W2 W2 Aux.
Fan G G G G G G G G G G
or H or H H
C/O Valve O O O O O O O O/B O O O/B O/B
Cool
or H or H H
C/O Valve B B B B B B B O/B B B O/B O/B
Heat
Em. Heat E E E E E E E E E E
A J F F J F J J
System Monitor/ L L L L L L L L
System Defrost
A
Multiple Aux. W3 W3 W3 W3 G G G G G G
Heat Loads
E
LED Indication – – X2 X1 X2 X1 X2 – – – X1 X2 –
A
Defrost P – – – – – – – – –
I
2nd Stage – – – – – – – – – W2
Compressor
2nd Stage – – – – – – – – – Y2
Cool
A Not available on all models. F L terminal is powered continuously when thermostat is in Em. Ht. position.
B Do not remove factory-installed jumper. G If multiple auxiliary heat loads are used, connect to W2 (Aux W8900B)
C Terminal must be connected to the transformer common. terminal.
D If separate Y1 and W1 terminals are required, install R8222D1014. H Configure O/B (select models) in Installer Setup.
See page 12. I When W2 is not used, configure W2 cycle rate to NC.
E Field-installed X2 to X jumper. J LED is energized when terminal is powered.
M13172
TYPICAL THERMOSTATS AND SUBBASES — HONEYWELL MODEL NUMBER (CUSTOMER PART NUMBER)
T841A1241 (D99458003) T8611R1083 (D9807605) T874R1194/Q674L1249
70-6627 • 36
AMERICAN STABILIS
TYPICAL THERMOSTATS AND SUBBASES: HP1, HP1EF, HP10EF, HP15
10 1
20 2
10 2
10 6
1M 10 0
1G 02
G1 19
1G 00
2
1R 00
1R 00
00 0/
47
28
28
61 G 00
14
70 04
00
2
6
5
08
51 G1
89 90
94 14
61 G2
41 R1
01 R1
71
T8 611 1R1
47
42
B1
W PC8
Y5 594G
A1
T8 8511
R1
T8 8411
T8 8611
T8 8011
T8 861
Existing
41
94
T
Y
T
T
T8
Y5
Function Terminals
Common E C X X X C C C C C C
Power R R R R R R R R R R
or
Compressor Y1 Y Y1 Y1 Y1 Y Y Y1 Y Y1 Y1/W1
G G G G G G G
1st Stg. Heat – – W1 W1 W1 W1 W1 W1 W1 –
B
Aux. Heat W2 W2 W2 W2 W2 W2 W2 W2 W2 Aux.
Fan G G G G G G G G G G
A A
or or A
C/O Valve B B B B B B B O/B B B O/B O/B
Heat
A A
or or A
C/O Valve O O O O O O O O/B O O O/B O/B
Cool
D
C C D C D C C
System Monitor/ X L X1 L L L L L L
System Defrost
EM. Heat E E E E E E E E E E
Multiple Aux. – W3 W3 W3 – – – – – –
Heat Loads
H F
LED Indication – – X2 X2 H X1 X2 – – – X1 X2 –
B
2nd Stage – – – – – – – – – W2
Compressor
A Confgure O/B (select models) in Installer Setup. F Optional CHECK LED on T8611G,M. Connect X to X1; jumper X2 to C.
B When W2 is not used, configure W2 cycle rate to NC. See Fig. 26 and 27.
C LED is energized when terminal is powered. G Field-installed W1 to Y1 jumper (provided).
D L terminal is powered continuously when thermostat is in Em. Ht. position. H Field-installed X2 to X jumper (provided).
E Terminal X (C) must be connected to transformer common. M13142
70-6627 • 37
ARMSTRONG/AIR-EASE
G2 02
R1 06
10 1
10 0
10 2
002
028
1 G 02
014
1 G 00
G 1 19
1 R 00
900 00/
47
04
611 20
28
011 10
5
6
2
51 G1
61 R1
9 4 14
41 R1
42
47
71
T8 611G
B1
T8 011R
W8 PC89
Y5 594G
T8 8511
T8 8611
T8 8411
R1
A1
Existing
94
41
T8
T8
T
T
T
Y
Terminals
Y5
Function T8
or
Common E X C X X X C C C C C C
Power R R R R R R R R R R
or J
Compressor Y Y Y Y1 Y1 Y Y Y1 Y Y1 Y1/W1
F F F F F F F F
1st Stg. Heat W1 – W1 W1 W1 W1 W1 W1 W1 –
G
Aux. Heat W2 W2 W2 W2 W2 W2 W2 W2 W2 Aux.
Fan G G G G G G G G G G
A A
or or A
C/O Valve B B B B B B B O/B B B O/B O/B
Heat
A A
or or A
C/O Valve O O O O O O O O/B O O O/B O/B
Cool
B B C C B C B B
System Monitor/ L L X1 L L L L L L
System Defrost
A
EM. Heat E E E E E E E E E E
Multiple Aux. W3 W3 W3 W3 – – – – –
Heat Loads D
H I
LED Indication – – X2 X2 H X1 X2 – – – X1 X2 –
K
Defrost P – – – P – – – – –
G
2nd Stage – – – – – – – – – W2
Compressor
A Configure O/B (select models) in Installer Setup. G When W2 is not used, configure W2 cycle rate to NC.
B LED is energized when terminal is powered. H Field-installed X2 to X jumper (provided).
C L terminal is powered continuously when thermostat is in Em. Ht. position. I Optional CHECK LED on T8611G1004. See Fig. 26.
D Terminal is for multiple second stage loads such as contactors, J If separate Y1 and W1 terminals are required, install R8222D1014. See
sequencers, or relays. page 12.
E Terminal X or C must be connected to transformer common. K Available on T8611R1000 only. M13143
F Do not remove factory-installed jumper.
70-6627 • 38
ARCOAIRE/SNYDER GENERAL/COMFORTMAKER
AYC, AYD, AYF
10 1
10 2
10 0
20 2
10 6
1G 02
1R 00
G1 19
1G 00
1G 00
2
1R 00
47
00 0/
28
28
04
14
00
5
6
2
51 G1
89 90
41 R1
94 14
61 R1
61 G2
01 R1
42
47
71
B1
W PC8
Y5 594G
T8 8511
T8 8411
T8 8611
R1
A1
T8 8611
T8 8011
Existing
94
41
T
T
T
Y
T
T
Y5
Terminals
T8
Function
Common C or
X C X X X C C C C C C
or X1
Power R R R R R R R R R R
or K
Compressor Y Y Y Y1 Y1 Y Y Y1 Y Y1 Y1/W1
E E E E E E E
1st Stg. Heat W1 – W1 W1 W1 W1 W1 W1 W1 –
or B
Aux. Heat W2 W1 W2 W2 W2 W2 W2 W2 W2 W2 Aux.
Fan G G G G G G G G G G
A A
or or A
C/O Valve B B B B B B B O/B B B O/B O/B
Heat
A A
or or A
C/O Valve O O O O O O O O/B O O O/B O/B
Cool
or I I L L I L I I
System Monitor/ L X L X1 L L L L L L
System Defrost
EM. Heat E E E E E E E E E E
Multiple Aux. – W3 W3 W3 H H H H H H
Heat Loads D
G F
LED Indication – – X2 X2 G X1 X2 – – – X1 X2 –
J
Defrost P – – – P – – – – –
B
2nd Stage – – – – – – – – – W2
Compressor
A Configure O/B (select models) in Installer Setup. H If multiple auxiliary heat loads are used, connect to W2 (Aux W8900B)
B When W2 is not used, configure W2 cycle rate to NC. terminal.
C Terminal X (C, X1) must be connected to transformer common. I LED is energized when terminal is powered.
D Terminal is for multiple second stage loads such as contactors, J Available on T8611R1000 only.
sequencers, or relays. K If separate Y1 and W1 Terminals are required, install R8222D1014.
E Do not remove factory-installed jumper. See page 12.
F Optional CHECK LED on T8611G1004. See Fig. 26. L L terminal is powered continuously when thermostat is in Em. Ht. position.
G Field-installed X2 to X jumper (provided). M13144
TYPICAL THERMOSTATS AND SUBBASES — HONEYWELL MODEL NUMBER (CUSTOMER PART NUMBER)
T841A1142 (1506726) T841A1159 (1505726) T874D1603
T874G1592/Q674F1212 T874G1782/Q674J1175 (1506756) T874G1774/Q674J1175 (1505756)
T874R1301/Q674L1181 (1505714) T874R1483/Q674L1538 (1505721) T874R1517/Q674L1538 (1506721)
T874R1525/Q674L1181 T874R1574/Q674L1538 T874R1582/Q674L1538 (A02077)
T874R1723/Q674L1702 (654958B07) T8611R1067 (1506-744) T8611R1075 (1505-744)
T8300A1193/Q6300A
70-6627 • 39
BARD
Models: 24UHPQC, 30UHPQC, 42UHPQC, 48UHPQB, 48UHPQB-B, 48UHPQC-B, 60UHPQC-B
10 2
10 1
20 2
10 6
G1 000
G1 19
1R 00
1G 02
1G 00
1R 00
2
28
47
28
00 0/
14
004
5
00
6
2
94 14
41 R1
51 G1
61 G2
611 R1
01 R1
89 90
42
47
71
B1
Y5 594G
W PC8
T8 8411
R1
T8 8611
A1
T8 8511
T8 8611
T8 8011
Existing
94
41
T
Y
T
T
Y5
Function Terminals T8
Common E C or X X X X C C C C C C
or X1
Power Rh
or R R R R R R R R R R
Rc
Compressor or
Y Y Y Y1 Y1 Y Y Y1 Y Y1 Y1/W1
F F F F F F F
1st Stg. Heat – – W1 W1 W1 W1 W1 W1 W1 –
B
Aux. Heat W2 W2 W2 W2 W2 W2 W2 W2 W2 Aux.
Fan G G G G G G G G G G
A A
or or or A
C/O Valve B W1 B B B B B B O/B B B O/B O/B
Heat
A A
or or A
C/O Valve O O O O O O O O/B O O O/B O/B
Cool
I I J J I J I I
System Monitor/ L L X1 L L L L L L
System Defrost
EM. Heat E E E E E E E E E E
Multiple Aux. W3 W3 W3 W3 C C C C C C
Heat Loads D
H G
LED Indication – – X2 X2 H X1 X2 – – – X1 X2 –
B
2nd Stage – – – – – – – – – W2
Compressor
A Configure O/B (select models) in Installer Setup. E Terminal X (C, X1) must be connected to transformer.
B When W2 is not used, configure W2 cycle rate to NC. F Do not remove factory-installed jumper.
C If multiple auxiliary heat loads are used, connect to W2 (Aux W8900B) G Optional CHECK LED on T8611G1004. See Fig. 26.
terminal. H Field-installed X2 to X jumper (provided).
D Terminal is for multiple second stage heating loads such as contactors, I LED is energized when terminal is powered.
sequencers, or relays. J L terminal is powered continuously when thermostat is in Em. Ht. position.
M13145
70-6627 • 40
B.D.P. (BRYANT-DAY/NIGHT-PAYNE)
10 1
10 6
10 0
20 2
10 2
1G 02
G1 19
1R 00
1G 00
1G 00
1R 00
2
47
B1 /
14
28
28
04
00 00
00
5
6
2
51 G1
94 14
01 R1
61 R1
61 G2
41 R1
42
47
71
89 89
Y5 594G
T 8 8511
R1
T 8 8011
A1
T 8 8611
T 8 8411
T 8 8611
W PC
Existing
41
94
T
T
Y
T
T8
Function
Y5
Terminals
C1
Common F or C X X X C C C C C C
X1
Power R R R R R R R R R R
or
Compressor W1 or Y Y1 Y Y1 Y1 Y Y Y1 Y Y1 Y1/W1
G G G G G G G
B
Aux. Heat W2 W2 W2 W2 W2 W2 W2 W2 W2 Aux.
Fan G G G G G G G G G G
A A A
C/O Valve B B B B B B B or O/B B B or O/B O/B
Heat
A A
or or A
C/O Valve Y1 or O O O O O O O O/B O O O/B O/B
Cool
K M M K M K K
System Monitor/ L or F L L L L L L L
System Defrost
EM. Heat X or E E E E E E E E E E
C
Multiple Aux. W3 W3 W3 W3 J J J J J J
Heat Loads D
E E
Defrost P – – – P – – – – –
L H L
LED Indication X – X2 I X1 X2 X1 X2 – – – X1 X2 –
B
2nd Stage – – – – – – – – – W2
Compressor
A Configure O/B (select models) in Installer Setup. H Optional CHECK LED on T8611G1004. See Fig. 26.
B When W2 is not used, configure W2 cycle rate to NC. I Field-installed X2 to X jumper (provided).
C If provided on original equipment. J If multiple auxiliary heat loads are used, connect to W2 (Aux W8900B)
D Terminal is for multiple second stage heating loads such as contactors, terminal.
sequencers, or relays. K LED is energized when terminal is powered.
E Model 545 typical. P terminal provided on T8611R1000 only. L Optional Check LED activated with completed circuit on X1 and X2 terminals.
F Terminal X (C, X1, C1) must be connected to transformer common. M L terminal is powered continuously when thermostat is in Em. Ht. position.
G Do not remove factory-installed jumper. M13146
TYPICAL THERMOSTATS AND SUBBASES — HONEYWELL MODEL NUMBER (CUSTOMER PART NUMBER)
T872G1166/Q672F1125 T874J1010/Q674J1084 (34427DP124/P272-2471/34427DP126,P272-1879)
T872G1174/Q672F1125 T874J1010/Q674L1371 (34427DP124/P272-2471/34427DP125,P272-1878)
T874G1261/Q674F1253 T874R1004/Q674B1042
T874G1451 (HH641502)/Q674F1212 T874R1335 (HH641501)/Q674L1405
70-6627 • 41
CARRIER
TYPICAL 50YQ, QT; 38QF, QN, QB, NPHPO1, 38YRA
10 1
20 2
10 2
10 0
10 6
G1 19
1G 02
1G 00
1R 00
1G 00
2
1R 00
47
28
00 0/
28
04
14
00
5
6
2
94 14
51 G1
61 G2
89 90
41 R1
61 R1
01 R1
42
47
71
B1
Y5 594G
W PC8
R1
T8 8511
A1
T8 8611
T8 8411
T8 8611
T8 8011
Existing
94
41
T
T
T
T
Y5
Function Terminals T8
Common E C X X X C C C C C C
Power R R R R R R R R R R
or
Compressor Y Y Y Y1 Y1 Y Y Y1 Y Y1 Y1/W1
F F F F F F F
1st Stg. Heat W1 – W1 W1 W1 W1 W1 W1 W1 –
or B
Aux. Heat W1 W2 W2 W2 W2 W2 W2 W2 W2 W2 Aux.
Fan G G G G G G G G G G
A A
or or A
C/O Valve B B B B B B B O/B B B O/B O/B
Heat
A A
or or A
C/O Valve O O O O O O O O/B O O O/B O/B
Cool
C
or I I K K I K I I
System Monitor/ F L L X1 L L L L L L
System Defrost
EM. Heat E E E E E E E E E E
Multiple Aux. – W3 W3 W3 – – – – – –
Heat Loads D
G
LED Indication – – X2 H X2 H X1 X2 – – – X1 X2 –
J
Defrost P – – – P – – – – –
B
2nd Stage – – – – – – – – – W2
Compressor
A Configure O/B (select models) in Installer Setup. G Optional CHECK LED on T8611G1004. See Fig. 26.
B When W2 is not used, configure W2 cycle rate to NC. H Field-installed X2 to X jumper (provided).
C If provided on original equipment. I LED is energized when terminal is powered.
D Terminal is for multiple second stage loads such as contactors, sequencers, J Available on T8611R1000 only.
or relays. K L terminal is powered continuously when thermostat is in Em. Ht. position.
E Terminal X (C) must be connected to transformer common. M13147
F Do not remove factory-installed jumper.
TYPICAL THERMOSTATS AND SUBBASES — HONEYWELL MODEL NUMBER (CUSTOMER PART NUMBER)
T841C1009 (HH07AT180) T874G1121 (HH07AT161) T874R1319/Q674B1281 (42QH400083/42QH400103)
T872G1075/Q672J1054 (HH07AT171/HH93AZ173) T874G1717/Q674J1167 T874R1384/Q674L1439 (HH07AQ170/HH93AZ187)
T872G1075/Q672L1052 (HH07PZ085/HH93AZ075A) T874H1070/Q674B1406 (HH07AT166/HH93AZ200) T874R1384/Q674L1579 (HH07AQ170/HH93AZ198)
T874C1166 (HH07AT160) T874H1070/Q674C1322 (HH07AT166/HH93AZ199) T874V1008/Q674R1003 (HH07AT177/HH93AZ190)
T874D1272 (HH07AT162) T874H1088/Q674B1406 (HH07AT166/HH93AZ200) T8085R1007/Q682L1002 (HH07AT075/HH93AZ159C)
T874G1055/Q674J1035 (HH07AT171/HH93AZ173A) T874H1088/Q674C1322 (HH07AT166/HH93AZ199) T8085R1023/Q682L1028 (HH07AT075C/HH93AZ159C)
T874G1055/Q674J1118 (HH07AT171/HH93AZ188) T874J1002/Q674L1074 (HH07AT175/HH93AZ186) T8141A1147
T874G1055/Q674L1041 (HH07AT171/HH93AZ175A) T874L1000/Q674E1270 (HH07AT176/HH93AZ189) T8611G1046 (HH07AE001)
T874G1055/Q674L1397 (HH07AT171/HH93AZ185A) T874L1018/Q674B1356 (HH07AT178/HH93AZ192) T8611R1208 (HH07AX114)
T874G1055/Q674P1005 (HH07AT171/HH93AZ169) T874L1018/Q674C1264 (HH07AT178/HH93AZ193) T8611R1216 (HH07AX115)
T874G1071/Q674P1005 (HH07AT171/HH93AZ169)
70-6627 • 42
CARRIER
TYPICAL 38BQ C
20 7
F1 5/
1M 01
02
2
08
25
00 0/
00
74 116
2
61 M2
10
89 90
70
02
B1
1M
W PC8
Q6 74D
1M
T8 8611
Existing
51
61
T8
T
Function Terminals
T8
T8
Common A C X1 C C C C
Power R R R R R R
C
1st Stage Cool Y1 Y1 C C C C
C
1st Stage Heat W1 W1 C C C C
B
2nd Stage Heat W2 W2 W2 Y2 Y2 W2
Fan G G G G G G
C CE CE CE
C/O Valve – O O O/B O/B O/B
Cool C
B
Em. Heat E E E E E E
C C C CF
Common 1st Stage – – Y Y1 Y1 Y1/W1
Compressor C
G H G H
System Monitor/ – – L L L L
System Defrost
B D D
LED Indication X X2 X1 X2 – X1 X2 –
A Terminal must be connected to the transformer common. D Optional LED indication activated with completed circuit on X1 and
B For auxiliary heat LED indication, jumper X2 to W2 on Q674. For emergency X2 terminals.
heat LED indication, jumper X2 to E. E Configure O/B (select models) in Installer Setup.
C Relay required (R8222B1067 typically) for T8511M, T8611M, F Configure Y1/W1 terminal in installer setup.
PC8900/W8900B1002 application. See page 9 for wiring diagram. G L terminal is continuously energized in Em. Heat Mode.
H LED is energized when terminal is powered. M13148
TYPICAL THERMOSTATS AND SUBBASES — HONEYWELL MODEL NUMBER (CUSTOMER PART NUMBER)
T874D1074/Q674F1030 (HHO7AT172/HH93AZ174)
T874D1074/Q674F1063 (HH07AT172/HH93AZ181)
70-6627 • 43
CARRIER
USES HONEYWELL Q674L1116 (HH93AZ171) SUBBASE
02 /
20 7
F1 65
2H
E
02
2
08
25
00 0/
1M 01
BL
00
BL
74 D11
AI T
89 90
AI T
10
70
61 2
AV NO
B1
AV NO
T8 611M
LA
W PC8
LA
1M
1M
Q6 874
Existing
51
61
T
T8
T8
Function
T8
Terminals
Common B C X1 C C C C
Power R R R R R R
G G G
Compressor Y Y1 Y Y1 Y1 Y1/W1
E
NOT AVAILABLE
NOT AVAILABLE
2nd Stage Y1 W2 W2 Y2 Y2 W2
Compressor
Fan G G G G G G
D D D
C/O Valve – B B O/B O/B O/B
Heat
D D D
C/O Valve O O O O/B O/B O/B
Cool
F J I J I
System Monitor/ L X2 L L L L
System Defrost
F
EM. Heat E E E E E E
LED Indication – – X1 X2 C – X2 C –
A Jumper Y2 to W2. G Both first stage heat and cool are connected to Y or Y1/W1 terminal.
B Terminal C (X1) must be connected to transformer common. H When subbase system switch is in AUTO position, equipment operates in
C Optional CHECK LED on T8611M7008. Connect L to X1, jumper X2 to C. cool mode only.
D Configure O/B (select models) in Installer Setup. I LED is energized when terminal is powered.
E In this application, auxiliary heat and compressor two are both connected J L terminal is powered continuously when thermostat is in Em. Ht. position.
to terminal Y1.
F For second stage compressor LED indication, jumper X2 to Y2 on Q674.
For emergency heat LED indication, jumper X2 to E. For system monitor M13149
LED indication, connect L to X2.
TYPICAL THERMOSTATS AND SUBBASES — HONEYWELL MODEL NUMBER (CUSTOMER PART NUMBER)
T874D1264/Q674L1116 (HH07AT173/HH93AZ171)
70-6627 • 44
CARRIER
TWO-SPEED COOLING COMPRESSORS
20 7
E
E
E
02
25
1M 01
2
08
00 0/
BL
BL
BL
00
AI T
AI T
AI T
10
89 90
61 2
70
AV NO
AV NO
AV NO
T8 611M
B1
LA
LA
LA
1M
W PC8
1M
Existing
51
61
T8
T8
Function
T8
Terminals
Common A C C C C C
Power R R R R R
NOT AVAILABLE
NOT AVAILABLE
2nd Stg. Y2 Y2 Y2 Y2 Y2
Compressor
2nd Stg. W2 W2 E E W2
Heat Relay
Fan G G G G G
B B B
C/O Valve O O O/B O/B O/B
Cool
B B B
C/O Valve – B O/B O/B O/B
Heat
D C D C
System Monitor/ L L L L L
System Defrost
EM. Heat E E E E E
A Terminal C must be connected to transformer common. D L terminal is powered continuously when thermostat is in Em. Ht. position.
B Configure O/B in Installer Setup. E If 2nd stage heat is auxiliary (electric resistive), connect auxiliary stage
C LED is energized when terminal is powered. to W3. M13150
TYPICAL THERMOSTATS AND SUBBASES — HONEYWELL MODEL NUMBER (CUSTOMER PART NUMBER)
T874S1001/Q674F1501 (HH07AT201/HH93AZ215)
T8611T7000 (HH07AX112)
T8611T7018 (HH07AX113)
70-6627 • 45
CRISPAIRE/MARVAIR
10 2
10 6
10 0
10 1
20 2
1R 00
1R 00
1G 00
1G 02
1G 00
2
28
14
00 0/
47
28
04
00
3
8
41 R1
01 R1
89 90
61 R1
51 G1
61 G2
63
30
79
B1
W PC8
T8 8411
G1
T8 011
T8 8611
T8 8511
A1
R1
T8 8611
Existing
94
41
94
T8
T
T
T
Y5
Function T8
Y5
Terminals
Common A X X X X C C C C C C
Power R R R R R R R R R R
or
Compressor Y Y Y Y Y1 Y Y Y1 Y Y1 Y1/W1
C C C C C
1st Stg. Heat – – – – W1 W1 W1 W1 W1 –
B
Aux. Heat W2 W2 W2 W2 W2 W2 W2 W2 W2 Aux.
D D D D D D
Fan G G G G G G G G G G
E E
or or E
C/O Valve B B B B B B B O/B B B O/B O/B
Heat
E E
or or E
C/O Valve O O O O O O O O/B O O O/B O/B
Cool
F F F G G F G F F
System Monitor/ A L L L L L L L L L
System Defrost
D D D D D D
EM. Heat E E E E E E E E E E
B
2nd Stage – – – – – – – – – W2
Compressor
A Terminal X or C must be connected to transformer common. E Configure O/B (select models) in Installer Setup.
B When W2 is not used, configure W2 cycle rate to NC. F LED is energized when terminal is powered.
C Do not remove factory-installed jumper. G L terminal is powered continuously when thermostat is in Em. Ht. position.
D To eliminate automatic fan in emergency heat mode, connect switching relay M13151
as shown on page 9.
70-6627 • 46
ECONAR
10 2
10 0
20 2
10 6
10 1
1R 00
1G 00
1G 00
G1 19
2
1R 00
1G 02
00 0/
28
28
04
14
47
00
2
89 90
41 R1
61 R1
61 G2
94 14
01 R1
51 G1
71
42
47
B1
W PC8
Y5 594G
T8 8411
T8 8611
A1
T8 8611
R1
T8 8011
T8 8511
Existing
41
94
T
T
T
T
Y
T
T8
Function
Y5
Terminals
Common E X X X X C C C C C C
Power R R R R R R R R R R
or
Compressor Y Y Y Y1 Y1 Y Y Y1 Y Y1 Y1/W1
F F F F F F F
1st Stg. Heat – – W1 W1 W1 W1 W1 W1 W1 –
B
Aux. Heat W2 W2 W2 W2 W2 W2 W2 W2 W2 Aux.
Fan G G G G G G G G G G
A A
or or A
C/O Valve B B B B B B B O/B B B O/B O/B
Heat
A A
or or A
C/O Valve O O O O O O O O/B O O O/B O/B
Cool
C G L L G L G G
System Monitor/ L L L L L L L L
System Defrost
EM. Heat E E E E E E E E E E
Multiple Aux. W3 W3 W3 W3 K K K K K K
Heat Loads D
J I J
H
LED Indication – – X2 X1 X2 X1 X2 – – – X1 X2 –
B
2nd Stage – – – – – – – – – W2
Compressor
70-6627 • 47
ECONAR
20 2
10 2
10 1
10 6
1G 00
E
1R 00
1G 02
2
1R 00
G1 19
00 0/
28
00
28
47
14
00
BL
61 G2
AI T
89 90
41 R1
51 G1
01 R1
94 14
10
42
47
B1
AV NO
W PC8
LA
Y5 594G
T8 8611
1R
T8 8411
T8 8011
T8 8511
R1
Existing
61
94
T
T
T
T
Y
T8
Function
Y5
Terminals
Common A X X X C C C C C C
Power R R R R R R R R R
F
Compressor Y Y Y1 Y1 Y Y1 Y Y1 Y1/W1
B B B B B B B
NOT AVAILABLE
D
Aux. Heat W2 W2 W2 W2 W2 W2 W2 W2 Aux.
Fan G G G G G G G G G
G G
or or G
C/O Valve B B B B B B O/B B B O/B O/B
Heat
H H I I H I H H
System Monitor/ L L X1 L L L L L L
System Defrost
EM. Heat E E E E E E E E E
Multiple Aux. W3 W3 W3 E E E E E E
Heat Loads C
G G
or or G
C/O Valve O O O O O O O/B O O O/B O/B
Cool
LED Indication – X2 X2 – – – – X1 X2 –
D
2nd Stage – – – – – – – – W2
Compressor
A Terminal X (C) must be connected to transformer common. E If multiple auxiliary heat loads are used, connect to W2 (Aux W8900B)
B Remove factory-installed Y1 (Y) to W1 jumper. terminal.
C Terminal is for multiple second stage loads such as contactors, sequencers, F Install R8222D1014 (see page 12) for separate Y1 and W1 terminals.
or relays. G Configure O/B (select models) in Installer Setup.
D When W2 is not used, configure W2 cycle rate to NC. H LED is energized when terminal is powered.
I L terminal is powered continuously when thermostat is in Em. Ht. position.
M13153
70-6627 • 48
ENERSTAT
20 7
10 2
10 1
10 6
1M 01
1R 00
1G 02
G1 19
2
1R 00
08
T8 1G 0
1M 04
00 0/
25
28
47
14
00
61 100
5
6
2
61 M2
89 90
41 R1
51 G1
94 14
01 R1
70
61 10
42
47
71
B1
W PC8
Y5 594G
T8 11R
T8 8411
T8 8511
R1
T8 8011
A1
T8 8611
Existing
94
41
T
Y
T8
T
Function
Y5
T8
Terminals
Common E X X X X C C C C C C
Power R R R R R R R R R R
B
or or
1st Stage HP1 HP Y Y1 Y1 Y1 Y Y Y1 Y Y1 Y/W1
Compressor
G G G G G G
1st Stage – – W1 W1 W1 W1 W1 W1 – –
Heat
I
2nd Stage – W2 W2 W2 W2 W2 W2 W2 W2 Aux.
Aux. Heat
3rd Stage – – – – W3 – – – W3 –
Aux. Heat
Fan G G G G G G G G G G
C J
2nd Stage HP2 Y2 Y2 Y2
Comp.
A A A
C or
C/O Valve B B B B B B B O/B B O/B O/B
Heat
C A A A
or
C/O Valve O O O O O O O O/B O O/B O/B
Cool
System Monitor/ – – L X1 L L L L L L
System Defrost
EM. Heat – E E E E E E E E E
Multiple Aux. – W3 W3 W3 – – – – – –
Heat Loads D
Remote Sensor – – – – – – – – – –
H F
LED Indication – – X2 X2 H X1 X2 – – – X1 X2 –
A Configure O/B (select models) in Installer Setup. F Optional CHECK LED on T8611G,M. See Fig. 26 and 27.
B Both first stage heat and cool are connected to HP terminal. G Do not remove factory-installed jumper.
C If provided on original equipment. H Field-installed X2 to X jumper (provided).
D Terminal is for multiple auxiliary heat loads such as contactors, sequencers, I When W2 is not used, configure W2 cycle rate to NC.
or relays. J T8611M7008 Model. M13173
E Terminal X (C) must be connected to transformer common.
70-6627 • 49
EVCON/COLEMAN
MODELS: 3200, 3300 A
A 102 2
A 101 6
1R 00
1R 00
8
0
4
A 100
41 R1
01 R1
T8 8411
T8 8011
1 R
Existing
61
T
Function Terminals
T8
Common B BLCK C C C
(2)
Power RED R R R
(1)
Aux. Heat
(4) W2 W2 W2 W2
Fan G G G G
C/O Valve B O O O
Cool (5)
C/O Valve – B B B
Heat
A
System Monitor/ E L L L
System Defrost A (3)
A
EM. Heat A
(10) A E E E
LED Indication X – – –
(3)
A R8222B1067 relays required to operate system. Equipment requires normally C Remove factory-installed jumper on Model 3200. Do not remove factory-
energized emergency heat. See page 10 for wiring diagram. installed jumper on Model 3300.
B Terminal must be connected to the transformer common. M13203
70-6627 • 50
EVCON/COLEMAN
MODELS: 3200, 3300, 3360, 3400, 6000, 6500 AD
10 1
20 2
10 0
10 6
10 2
G1 19
1G 02
1G 00
1G 00
2
1R 00
1R 00
00 0/
47
04
28
14
28
00
5
6
2
94 14
89 90
51 G1
61 G2
61 R1
01 R1
41 R1
42
47
71
B1
Y5 594G
W PC8
R1
T8 8611
T8 8511
T8 8611
T8 011
A1
T8 8411
Existing
94
41
T8
Y
T
T
Y5
Function
T8
Terminals
Common E BLCK X X X C C C C C C
(2)
Power RED R R R R R R R R R
(1)
or
Compressor Y Y Y Y1 Y1 Y Y Y1 Y Y1 Y1/W1
(6) G G G G G G G
1st Stage – – W1 W1 W1 W1 W1 W1 W1 –
Heat
I
Aux. Heat W2 W2 W2 W2 W2 W2 W2 W2 W2 Aux.
(4)
Fan G G G G G G G G G G
B B B
or or
C/O Valve – B B B B B B O/B B B O/B O/B
Heat
B B B
or or
C/O Valve V O O O O O O O/B O O O/B O/B
Cool (5)
System Monitor/ – – L – L L L L L L
System Defrost
D
Em. Heat D A E E E E E E E E E
Multiple Aux. – W3 W3 W3 – – – – – –
Heat Loads F
C C
H C
LED Indication X – X2 X1 X2 X1 X2 – – – X1 X2 –
(3)
I
2nd Stage – – – – – – – – – W2
Compressor
2nd Stage Y2 – – Y2 – – – – – Y2
Cool
A See Coleman wholesaler to obtain replacements for these thermostats. If not E Terminal must be connected to the transformer common.
possible, basic functions can be provided as shown. F Terminal is for multiple auxiliary heat loads such as contactors, sequencers,
B Configure O/B (select models) in Installer Setup. or relays.
C Optional LED indication activated with completed circuit on X1 and G Do not remove factory-installed jumper.
X2 terminals. H Field-installed X2 to X (C) jumper.
D R8222B1067 relays required to operate system. Equipment requires normally I When W2 is not used, configure W2 cycle rate to NC.
energized emergency heat. See page 10 for wiring diagram. M13204
TYPICAL THERMOSTATS AND SUBBASES — HONEYWELL MODEL NUMBER (CUSTOMER PART NUMBER)
T8300A1029/Q6300A1029 (3300-382/3300-383)
70-6627 • 51
EVCON/COLEMAN
TYPICAL 3700, 3900, 4400, 6500, 7100, 9200 (3600 SERIES THERMOSTAT) DIRECT REPLACEMENTS
10 2
20 2
10 6
10 1
10 0
1R 00
1G 00
2
1R 00
1G 02
1G 00
00 0/
28
28
14
47
04
00
33
7
8
89 90
41 R1
61 G2
01 R1
51 G1
61 R1
79
30
B1
6
W PC8
T8 8411
G1
T8 8011
R1
T8 8611
A1
T8 8511
T8 8611
Existing
94
94
41
T
T
T
Function
Y5
Y5
T8
Terminals
Common A X X X X C C C C C C
Power R R R R R R R R R R
or
Compressor Y Y Y Y Y1 Y Y Y1 Y Y1 Y1/W1
C C C C C
1st Stage – – – – W1 W1 W1 W1 W1 –
Heat
B
Auxiliary W2 W2 W2 W2 W2 W2 W2 W2 W2 Aux.
Heat
D D D D D D
Fan G G G G G G G G G G
E E E
or or
C/O Valve B B B B B B B O/B B B O/B O/B
Heat
E E E
or or
C/O Valve O O O O O O O O/B O O O/B O/B
Cool
F F F G G F G F F
System Monitor/ L L L L L L L L L L
System Defrost
D D D D D D
Em. Heat E E E E E E E E E E
B
2nd Stage – – – – – – – – – W2
Compressor
A Terminal X (C) must be connected to transformer common. E Configure O/B (select models) in Installer Setup.
B When W2 is not used, configure W2 cycle rate to NC. F LED is energized when terminal is powered.
C Do not remove factory-installed jumper. G L terminal is powered continuously when thermostat is in Em. Ht. position.
D To eliminate automatic fan in emergency heat mode, connect switching M13157
relay as shown on page 9.
TYPICAL THERMOSTATS AND SUBBASES — HONEYWELL MODEL NUMBER (CUSTOMER PART NUMBER)
T874G1501 (3600-375)/Q674F1378
T874G1576 (3600-373)/Q674F1402
T874R1368 (3600-368)/Q674L1421
70-6627 • 52
EVCON/COLEMAN
TYPICAL 3700, 3900, 4400, 6500, 7100, 9200 (3600 SERIES THERMOSTAT) ALTERNATIVE REPLACEMENTS
20 2
10 2
10 1
10 6
10 0
1G 00
1R 00
1G 02
G1 19
2
1R 00
28
1G 00
00 0/
28
47
14
04
00
5
6
2
61 G2
89 90
41 R1
51 G1
94 14
01 R1
61 R1
42
47
71
B1
W PC8
Y5 594G
T8 8611
T8 8411
T8 8511
R1
T8 8011
A1
T8 8611
Existing
94
41
T
T
T
Y
T
Function
Y5
T8
Terminals
or
Common D C/X X X X X C C C C C C
Power R R R R R R R R R R
or
Compressor Y Y Y Y1 Y1 Y Y Y1 Y Y1 Y1/W1
E E E E E E E
1st Stage W1 – W1 W1 W1 W1 W1 W1 W1 –
Heat
L
Aux. Heat W2 W2 W2 W2 W2 W2 W2 W2 W2 Aux.
Fan G G G G G G G G G G
K
Defrost B B B B B B B B B B
A A A
K or or
C/O Valve O O O O O O O O/B O O O/B O/B
Cool
B B I I B I B B
System Monitor/ L L X1 L L L L L L
System Defrost
EM. Heat E E E E E E E E E E
Multiple Aux. – W3 W3 W3 H H H H H H
Heat Loads C
G
LED Indication – – X2 X2 G X1 X2 F – – – X1 X2 –
J
EM. Heat P – – – P – – – – –
L
2nd Stage – – – – – – – – – W2
Compressor
TYPICAL THERMOSTATS AND SUBBASES — HONEYWELL MODEL NUMBER (CUSTOMER PART NUMBER)
T8611R1059 (3600A-381)
70-6627 • 53
FEDDERS
10 2
20 2
10 6
10 1
G1 19
1R 00
E
1G 00
2
1R 00
00
1G 02
00 0/
28
28
14
47
00
BL
6
94 14
89 90
41 R1
AI T
61 G2
01 R1
10
51 G1
42
47
B1
AV NO
Y5 594G
W PC8
LA
1R
R1
T8 8411
T8 8011
T8 8611
T8 8511
Existing
61
94
T
Y
T
T8
Y5
T
Function Terminals
A A A A A A
Common A C X X C C C C C C
or
Power Rc Rh R R R R R R R R R
or D
Compressor Y1 Y Y Y1 Y1 Y Y1 Y Y1 Y1/W1
B B B B B B B
1st Stage W1 W1 W1 W1 W1 W1 W1 W1 –
Heat
G
NOT AVAILABLE
Auxiliary W2 W2 W2 W2 W2 W2 W2 W2 Aux.
Heat
Fan G G G G G G G G G
F F F
or or
C/O Valve – B B B B B O/B B B O/B O/B
Heat
F F F
or or
C/O Valve – O O O O O O/B O O O/B O/B
Cool
or H H I I H I H H
System Monitor/ L Z L X1 L L L L L L
System Defrost
Em. Heat K E E E E E E E E
Multiple Aux. – W3 W3 – – – – – –
Heat Loads C
E
LED Indication – X2 E X2 – – – – X1 X2 –
G
2nd Stage – – – – – – – – W2
Compressor
TYPICAL THERMOSTATS AND SUBBASES — HONEYWELL MODEL NUMBER (CUSTOMER PART NUMBER)
T872C/Q672L1102 T874D1462/Q674E1205 (THTX-220-AOHB; 88-58-00550-001)
T874C/Q674L1090 T874R1269/Q674L1066 (THTX-120-HEHB; 88-58-00540-001)
T874D1249 T874R1343/Q674L1413 (THTX-120-HEHC; 88-58-00560-001)
70-6627 • 54
FLORIDA HEAT PUMP
TYPICAL “LT” UNITS
20 2
10 0
10 6
10 1
10 2
1G 00
G1 19
1G 00
2
1R 00
1G 02
1R 00
00 0/
28
04
14
47
28
00
5
6
2
89 90
61 G2
94 14
61 R1
01 R1
51 G1
41 R1
42
47
71
B1
W PC8
Y5 594G
T8 8611
T8 8611
R1
T8 8011
A1
T8 8411
T8 8511
Existing
94
41
T
Y
T
T
T
Function
Y5
T8
Terminals
Common E C X X X C C C C C C
Power R R R R R R R R R R
or
Compressor Y Y Y Y1 Y1 Y Y Y1 Y Y1 Y1/W1
F F F F F F F
1st Stage – – W1 W1 W1 W1 W1 W1 W1 –
Heat
J
Aux. Heat W W2 W2 W2 W2 W2 W2 W2 W2 Aux.
Fan G G G G G G G G G G
A A A
or or
C/O Valve – B B B B B B O/B B B O/B O/B
Heat
A A A
or or or
C/O Valve W O O O O O O O O/B O O O/B O/B
Cool
B B I I B I B B
System Monitor/ X L X1 L L L L L L
System Defrost
D D D D D D D D
D
EM. Heat – E E E E E E E E E
Multiple Aux. – W3 W3 W3 – – – – – –
Heat Loads C
H
LED Indication – – X2 X2 H X1 X2 G – – – X1 X2 –
J
2nd Stage – – – – – – – – – W2
Compressor
A Configure O/B (select models) in Installer Setup. F Do not remove factory-installed jumper.
B LED is energized when terminal is powered. G Optional CHECK LED on T8611G1004. See Fig. 26.
C Terminal is for multiple second stage heating loads such as contactors, H Field-installed X2 to X jumper (provided).
sequencers, or relays. I L terminal is powered continuously when thermostat is in Em. Ht. position.
D E-W2 jumper required unless emergency heat function is wired separately. J When W2 is not used, configure W2 cycle rate to NC.
E Terminal X (C) must be connected to transformer common. M13175
70-6627 • 55
FRIEDRICH
20 2
10 0
10 6
10 1
10 2
2
1G 00
G1 19
1G 00
00 0/
1R 00
1G 02
1R 00
28
04
14
47
00
28
5
89 90
2
61 G2
94 14
61 R1
01 R1
51 G1
41 R1
42
47
71
B1
W PC8
Y5 594G
T8 8611
T8 8611
R1
T8 8011
A1
T8 8411
T8 8511
Existing
94
41
T
Y
T
T
T
Function
Y5
Terminals T8
Common E X X X X C C C C C C
Power R R R R R R R R R R
or
Compressor Y Y Y Y1 Y1 Y Y Y1 Y Y1 Y1/W1
F F F F F F F
1st Stage – – W1 W1 W1 W1 W1 W1 W1 –
Heat
J
Aux. Heat W2 W2 W2 W2 W2 W2 W2 W2 W2 Aux.
Fan G G G G G G G G G G
A A A
or or
C/O Valve B B B B B B B O/B B B O/B O/B
Heat
A A A
or or
C/O Valve O O O O O O O O/B O O O/B O/B
Cool
B B I I B I B B
System Monitor/ L L X1 L L L L L L
System Defrost
EM. Heat E E E E E E E E E E
Multiple Aux. W3 W3 W3 W3 D D D D D D
Heat Loads C
H
LED Indication – – X2 X2 H X1 X2 G – – – X1 X2 –
J
2nd Stage – – – – – – – – – W2
Compressor
A Configure O/B (select models) in Installer Setup. E Terminal X (C) must be connected to transformer common.
B LED is energized when terminal is powered. F Do not remove factory-installed jumper.
C Terminal is for multiple second stage heating loads such as contactors, G Optional CHECK LED on T8611G1004. See Fig. 26.
sequencers, or relays. H Field-installed X2 to X jumper (provided).
D If multiple auxiliary heat loads are used, connect to W2 (Aux W8900) I L terminal is powered continuously when thermostat is in Em. Ht. position.
terminal. J When W2 is not used, configure W2 cycle rate to NC. M13179
TYPICAL THERMOSTATS AND SUBBASES — HONEYWELL MODEL NUMBER (CUSTOMER PART NUMBER)
T841A1324 (AT12124)
70-6627 • 56
GENERAL ELECTRIC
10 1
20 2
10 6
10 0
10 2
1G 02
1G 00
2
1R 00
1G 00
1R 00
00 0/
47
04
28
14
28
00
3
61
5
89 90
51 G1
61 G2
01 R1
61 R1
41 R1
76
55
B1
1
W PC8
R1
G1
T8 8511
T8 8611
T8 8011
A1
T8 611
T8 8411
Existing
94
94
41
T8
T
T
T
Y5
Function
Y5
T8
Terminals
or
Common A C B B B B C C C C C C
Power R R R R R R R R R R
or
Compressor Y Y Y Y1 Y1 Y Y Y1 Y Y1 Y1/W1
C C C C C
1st Stage – – – – W1 W1 W1 W1 W1 –
Heat
or I
Aux. Heat W1 W W W W W2 W2 W2 W2 W2 Aux.
Fan G G G G G G G G G G
E E E
or or
C/O Valve – – – – B B B O/B B B O/B O/B
Heat
E E E
or or
C/O Valve O O O O O O O O/B O O O/B O/B
Cool
G G G H H G H G G
System Monitor/ F F F F L L L L L L
System Defrost
EM. Heat B – – – – – – – – –
Outdoor T T T T B B B B B B
Sensor
or
Outdoor W2 X2 X2 X2 X2 E E E E E E
Thermostat
F
LED Indication – – – – X1 X2 D – – – X1 X2 –
I
2nd Stage – – – – – – – – – W2
Compressor
A Terminal X (C) must be connected to transformer common. F Optional LED indication activated with completed circuit on X1 and
B Tape off. Electric thermostat replaces outdoor reset with improved zero droop X2 terminals.
performance. G LED is energized when terminal is powered.
C Do not remove factory-installed jumper. H L terminal is powered continuously when thermostat is in Em. Ht. position.
D Optional CHECK LED on T8611G1004. See Fig. 26. I When W2 is not used, configure W2 cycle rate to NC.
E Configure O/B (select models) in Installer Setup. M13180
70-6627 • 57
GENERAL ELECTRIC
10 1
20 2
10 6
10 0
10 2
1G 02
1G 00
G1 19
2
1R 00
1G 00
1R 00
00 0/
04
47
28
14
28
00
5
6
2
89 90
51 G1
61 G2
94 14
01 R1
61 R1
41 R1
42
47
71
B1
W PC8
Y5 594G
T8 8511
R1
T8 8611
T8 8011
A1
T8 611
T8 8411
Existing
94
41
T8
T
T
Y
T
Function
Y5
Terminals T8
or
Common B C B X X X C C C C C C
Power R R R R R R R R R R
or
Compressor Y Y Y1 Y1 Y1 Y Y Y1 Y Y1 Y1/W1
E E E E E E E
1st Stage – – W1 W1 W1 W1 W1 W1 W1 –
Heat
or J
Aux. Heat W1 W W2 W2 W2 W2 W2 W2 W2 W2 Aux.
Fan G G G G G G G G G G
I I I
or or
C/O Valve – B B B B B B O/B B B O/B O/B
Heat
I I I
or or
C/O Valve O O O O O O O O/B O O O/B O/B
Cool
or K K L L K L K K
System Monitor/ F L L X1 L L L L L L
System Defrost
EM. Heat – – – – – – – – – –
Outdoor T A A A C C C C C C
Sensor
or
Outdoor E X2 E E E E E E E E E
Thermostat
Defrost Control – – – – P – – – – –
Multiple Aux. W2 W3 W3 W3 H H H H H H
Heat Loads D
LED Indication – – X2 G X2 G X1 X2 F – – – X1 X2 –
J
2nd Stage – – – – – – – – – W2
Compressor
A Tape off. Outdoor reset not provided with TRADELINE® replacement F Optional CHECK LED on T8611G1004. See Fig. 26.
thermostats. G Field-installed X2 to X jumper (provided).
B Terminal X (C) must be connected to transformer common. H If multiple auxiliary heat loads are used, connect to W2 (Aux W8900B)
C Tape off. Electronic thermostat replaces outdoor reset with improved zero droop terminal.
performance. I Configure O/B (select models) in Installer Setup.
D Terminal is for multiple auxiliary heat loads such as contactors, sequencers, J When W2 is not used, configure W2 cycle rate to NC.
or relays. K LED is energized when terminal is powered.
E Do not remove factory-installed jumper. L L terminal is powered continuously when thermostat is in Em. Ht. position.
M13181
70-6627 • 58
GEO SYSTEM
20 2
10 1
10 0
10 6
10 2
1G 00
G1 19
1G 02
1G 00
2
1R 00
1R 00
28
00 0/
04
47
14
28
00
5
6
2
61 G2
94 14
89 90
51 G1
61 R1
01 R1
41 R1
42
47
71
B1
Y5 594G
W PC8
T8 8611
R1
T8 8611
T8 8511
T8 8011
A1
T8 8411
Existing
94
41
T
Y
T
T
Y5
Function
T8
Terminals
Common D X X X X C C C C C C
Power R R R R R R R R R R
or
Compressor Y Y Y Y1 Y1 Y Y Y1 Y Y1 Y1/W1
E E E E E E E
1st Stage – – W1 W1 W1 W1 W1 W1 W1 –
Heat
K
Aux. Heat W2 W2 W2 W2 W2 W2 W2 W2 W2 Aux.
Fan G G G G G G G G G G
A A A
or or
C/O Valve B B B B B B B O/B B B O/B O/B
Heat
A A A
or or
C/O Valve O O O O O O O O/B O O O/B O/B
Cool
J J I I J I J J
System Monitor/ L L X1 L L L L L L
System Defrost
EM. Heat E E E E E E E E E E
Multiple Aux. W3 W3 W3 W3 H H H H H H
Heat Loads C
G
LED Indication – – X2 X2 G X1 X2 F – – – X1 X2 –
K
2nd Stage – – – – – – – – – W2
Compressor
70-6627 • 59
HEAT CONTROLLER/COMFORT AIR
10 1
20 2
10 0
10 6
10 2
1G 02
1G 00
2
1G 00
G1 19
1R 00
00 0/
47
1R 00
28
04
14
28
00
5
2
51 G1
61 G2
89 90
61 R1
94 14
01 R1
41 R1
42
71
47
B1
W PC8
Y5 594G
T8 8511
T8 8611
R1
T8 8611
T8 8011
A1
T8 8411
Existing
94
41
T
T
T
Y
T
Y5
Function Terminals T8
Common E C X X X C C C C C C
Power R R R R R R R R R R
B or
Compressor W1 Y Y Y1 Y1 Y Y Y1 Y Y1 Y1/W1
F F F F F F F
1st Stage – – W1 W1 W1 W1 W1 W1 W1 –
Heat
G
Aux. Heat W2 W2 W2 W2 W2 W2 W2 W2 W2 Aux.
Fan G G G G G G G G G G
A A A
or or
C/O Valve – B B B B B B O/B B B O/B O/B
Heat
A A A
or or
C/O Valve Y1 O O O O O O O/B O O O/B O/B
Cool
I J J I J I I
System X L L L L L L L
Monitor
D
EM. Heat E E E E E E E E E E
Multiple Aux. – W3 W3 W3 – – – – – –
Heat Loads C
H H H
LED Indication – – X2 X1 X2 X1 X2 – – – X1 X2 –
G
2nd Stage – – – – – – – – – W2
Compressor
2nd Stage – – – – – – – – – Y2
Cool
A Configure O/B (select models) in Installer Setup. F Do not remove factory-installed jumper.
B Both first stage heat and cool are connected to Y terminal. G When W2 is not used, configure W2 cycle rate to NC.
C Terminal is for multiple second stage loads such as contactors, sequencers, H Optional LED indication activated with completed circuit on X1 and
or relays. X2 terminals.
D If provided on original equipment. I LED is energized when terminal is powered.
E Terminal X (C) must be connected to transformer common. J L terminal is powered continuously when thermostat is in Em. Ht. position.
M13217
70-6627 • 60
HEATWAVE/SOUTHWEST MFG.
10 1
20 2
10 6
10 0
10 2
1G 02
1G 00
G1 19
2
1R 00
1G 00
1R 00
47
00 0/
28
04
14
28
00
5
6
2
51 G1
61 G2
89 90
94 14
01 R1
61 R1
41 R1
42
47
71
B1
W PC8
Y5 594G
T8 8511
R1
T8 8611
T8 8011
A1
T8 611
T8 8411
Existing
94
41
T8
T
Y
T
T
Y5
Function
T8
Terminals
Common D X X X X C C C C C C
Power R R R R R R R R R R
B or
Compressor Y Y Y Y1 Y1 Y Y Y1 Y Y1 Y1/W1
E E E E E E E
1st Stage – – W1 W1 W1 W1 W1 W1 W1 –
Heat
G
Aux. Heat W2 W2 W2 W2 W2 W2 W2 W2 W2 Aux.
Fan G G G G G G G G G G
A A A
or or
C/O Valve – B B B B B B O/B B B O/B O/B
Heat
A A A
or or
C/O Valve O O O O O O O O/B O O O/B O/B
Cool
System – – L – L L L L L L
Monitor
EM. Heat E E E E E E E E E E
Multiple Aux. – W3 W3 W3 – – – – – –
Heat Loads C
F F F
LED Indication X2 X1 X2 X1 X2 – – – X1 X2 –
Defrost B – – – – – – – – –
G
2nd Stage – – – – – – – – – W2
Compressor
2nd Stage – – – – – – – – – Y2
Cool
A Configure O/B (select models) in Installer Setup. E Do not remove factory-installed jumper.
B Both first stage heat and cool are connected to Y terminal. F Optional LED indication activated with completed circuit on X1 and
C Terminal is for multiple second stage loads such as contactors, sequencers, X2 terminals.
or relays. G When W2 is not used, configure W2 cycle rate to NC.
D Terminal X (C) must be connected to transformer common. M13218
70-6627 • 61
HONEYWELL
UNIVERSAL
10 1
20 2
10 0
10 6
10 2
G1 19
1G 02
1G 00
1G 00
2
1R 00
1R 00
00 0/
47
28
04
14
28
00
6
5
2
94 14
51 G1
89 90
61 G2
61 R1
01 R1
41 R1
47
42
71
B1
Y5 594G
W PC8
R1
T8 8511
T8 8611
T8 8611
T8 8011
A1
T8 8411
Existing
94
41
T
T
T
T
T
Y5
Function Terminals T8
Common D X X X X C C C C C C
Power B R R R R R R R R R R
or or
Compressor Y1 Y Y Y Y1 Y1 Y Y Y1 Y Y1 Y1/W1
F F F F F F F F
1st Stage W1 – W1 W1 W1 W1 W1 W1 W1 –
Heat
or L
Aux. Heat W W2 W2 W2 W2 W2 W2 W2 W2 W2 Aux.
Fan G G G G G G G G G G
A A A
or or
C/O Valve B B B B B B B O/B B B O/B O/B
Heat I
A A A
or or
C/O Valve O O O O O O O O/B O O O/B O/B
Cool I
or or J K K J K J J
System L1 X1 L L L L L L L L
Monitor
EM. Heat E E E E E E E E E E
Multiple Aux. W3 W3 W3 W3 E
– E E E E E
Heat Loads C
H
H
LED Indication X2 – X2 X1 X2 X1 X2 G – – – X1 X2 –
L
2nd Stage – – – – – – – – – W2
Compressor
2nd Stage – – – – – – – – – Y2
Cool
A Configure O/B (select models) in Installer Setup. G Optional CHECK LED. See Fig. 26.
B For best performance, use a NEMA standard transformer. H Optional LED indication activated with completed circuit on X1 and
C Terminal is for multiple second stage heating loads such as contactors, X2 terminals.
sequencers, or relays. I Thermostat will have connection to either O or B terminal, not both.
D Terminal X (C) must be connected to transformer common. J LED is energized when terminal is powered.
E If multiple auxiliary heat loads are used, connect to W2 (Aux W8900B) K L terminal is powered continuously when thermostat is in Em. Ht. position.
terminal. L When W2 is not used, configure W2 cycle rate to NC.
F Do not remove factory-installed jumper. M13186
70-6627 • 62
HONEYWELL
SEPARATE FIRST STAGE HEAT AND COOL TERMINALS
20 2
10 1
10 6
10 2
E
1G 00
G1 19
1G 02
2
1R 00
00
1R 00
28
00 0/
47
14
28
BL
00
6
5
AI T
61 G2
94 14
89 90
51 G1
01 R1
10
41 R1
47
42
AV NO
B1
LA
Y5 594G
W PC8
1R
T8 8611
R1
T8 8511
T8 8011
T8 8411
Existing
61
94
T
Y
T
T8
T
Y5
Function Terminals
Common A X X X C C C C C C
Power R R R R R R R R R
D
1st Stage Y1 Y1 Y1 Y1 Y Y1 Y Y1 Y1/W1
Cool
G G G G G G G
1st Stage W1 W1 W1 W1 W1 W1 W1 W1
Heat
NOT AVAILABLE
C
2nd Stage W2 W2 W2 W2 W2 W2 W2 W2 Aux.
Heat
Fan G G G G G G G G G
E E E
B or or
C/O Valve B B B B B B O/B B B O/B O/B
Heat
E E E
B or or
C/O Valve O O O O O O O/B O O O/B O/B
Cool
or B
System X2 L X1 L L L L L L
Monitor
or
EM. Heat Z E E E E E E E E E
Defrost – – – P – – – – –
B
2nd Stage Y2 – – – – – – – Y2
Cool
Multiple Aux. – W3 W3 – – – – – –
Heat Loads F
LED Indication – X2 X1 X2 – – – – X1 X2 –
C
2nd Stage – – – – – – – – W2
Compressor
2nd Stage – – – – – – – – Y2
Cool
A Terminal X (C) must be connected to transformer common. F Terminal is for multiple second stage heat loads such as contactors,
B If provided on original equipment. sequencers, or relays.
C When W2 is not used, configure W2 cycle rate to NC. G Remove factory-installed jumper for independent first stage heat and cool
D If separate Y1 and W1 terminals are required, install R8222D1014; see page 12. operation.
E Select O/B (select models) in Installer Setup. M13187
70-6627 • 63
HONEYWELL
RETAIL HEAT PUMP THERMOSTATS
10 1
20 2
10 0
10 6
10 2
1G 02
1G 00
1G 00
G1 19
2
1R 00
1R 00
00 0/
47
28
04
14
28
00
6
2
51 G1
89 90
61 G2
61 R1
94 14
01 R1
41 R1
47
71
42
B1
W PC8
Y5 594G
T8 8511
T8 8611
T8 8611
T8 8011
A1
R1
T8 8411
Existing
41
94
T
T
T
Y
T
Function T8
Y5
Terminals
Common D X X X X C C C C C C
Power B R R R R R R R R R R
or C
Compressor Y1 Y Y Y1 Y1 Y Y Y1 Y Y1 Y1/W1
F F F F F F F F
1st Stage W1 – W1 W1 W1 W1 W1 W1 W1 –
Heat
E
Aux. Heat W2 W2 W2 W2 W2 W2 W2 W2 W2 Aux.
Fan G G G G G G G G G G
A A A
or or
C/O Valve B B B B B B B O/B B B O/B O/B
Heat
A A A
or or
C/O Valve O O O O O O O O/B O O O/B O/B
Cool
G H H G H G G
System L L L L L L L L
Monitor
EM. Heat E E E E E E E E E E
LED Indication – – X2 X1 X2 X1 X2 – – – X1 X2 –
E
2nd Stage – – – – – – – – – W2
Compressor
2nd Stage – – – – – – – – – Y2
Cool
A Configure O/B (select models) in Installer Setup. E When W2 is not used, configure W2 cycle rate to NC.
B For best performance, use a NEMA standard transformer. F Do not remove factory-installed jumper.
C If separate Y1 and W1 terminals are required, install R8222D1014; see G LED is energized when terminal is powered.
page 12. H L terminal is powered continuously when thermostat is in Em. Ht. position.
D Terminal X (C) must be connected to transformer common. M13188
70-6627 • 64
HONEYWELL
MODELS USING OUTDOOR RESET
20 2
10 1
10 6
10 2
10 4
1G 00
1G 02
2
1R 00
1R 00
1R 00
00 0/
28
47
14
28
00
00
3
61
5
61 G2
89 90
51 G1
01 R1
41 R1
61 G1
76
55
B1
1
W PC8
R1
T8 8611
G1
T8 8011
T8 8511
A1
T8 8411
T8 8611
Existing
94
94
41
T
T
T
T
Y5
T
Function
Y5
T8
Terminals
Common AB B B B B C C C C C C
Power R R R R R R R R R R
or
Compressor Y Y Y Y Y1 Y Y Y1 Y Y1 Y1/W1
D D D D D
1st Stage – – – – W1 W1 W1 W1 W1 –
Heat
F
Aux. Heat W W W W W2 W2 W2 W2 W2 Aux.
Fan G G G G G G G G G G
Outdoor T T T T E E E E E E
Thermistor
Outdoor X2 X2 X2 X2 E E E E E E
Thermostat
C C C
or or
Cooling O O O O O O O O/B O O O/B O/B
Changeover
G G G H H G H G G
System F F F F L L L L L L
Monitor
F
2nd Stage – – – – – – – – – W2
Compressor
2nd Stage – – – – – – – – – Y2
Cool
A For best performance, use a NEMA standard transformer. E No connection. Tape off.
B Terminal B (C) must be connected to transformer common. F When W2 is not used, configure W2 cycle rate to NC.
C Configure O/B (select models) in Installer Setup. G LED is energized when terminal is powered.
D Leave factory-installed jumper in place. H L terminal is powered continuously when thermostat is in Em. Ht. position.
M13189
70-6627 • 65
HONEYWELL
HEATING CHANGEOVER
10 1
20 2
10 0
10 6
10 2
1G 02
1G 00
1G 00
G1 19
2
1R 00
1R 00
47
00 0/
28
04
14
28
00
5
6
2
51 G1
61 G2
89 90
61 R1
94 14
01 R1
41 R1
42
47
71
B1
W PC8
Y5 594G
R1
T8 8511
T8 8611
T8 8611
T8 8011
A1
T8 8411
Existing
94
41
T
T
T
Y
T
Y5
Function Terminals T8
Common E X X X X C C C C C C
Power R R R R R R R R R R
or or or
Compressor Y1 Y C Y Y Y1 Y1 Y Y Y1 Y Y1 Y1/W1
D D D D D D D
1st Stage – – W1 W1 W1 W1 W1 W1 W1 –
Heat
B
Aux. Heat W2 W2 W2 W2 W2 W2 W2 W2 W2 Aux.
Fan G G G G G G G G G G
1 1 1
or or
C/O Valve W1 B B B B B B O/B B B O/B O/B
Heat
1 1 1
or or
C/O Valve – O O O O O O O/B O O O/B O/B
Cool
J K K J K J J
System L L L L L L L L
Monitor
or
Em. Heat E K E E E E E E E E E
Multiple Aux.
Heat Loads C W3 W3 W3 W3 F F F F F F
I
H I G
LED Indication – – X2 X1 X2 X1 X2 – – – X1 X2 –
B
2nd Stage – – – – – – – – – W2
Compressor
2nd Stage – – – – – – – – – Y2
Cool
A Configure O/B (select models) in Installer Setup. G Optional CHECK LED on T8611G1004. See Fig. 26.
B When W2 is not used, configure W2 cycle rate to NC. H Field-installed X2 to X jumper (provided).
C Terminal is for multiple second stage heating loads such as contactors, I Optional LED indication activated with completed circuit on X1 and
sequencers, or relays. X2 terminals.
D Leave factory-installed jumper in place. J LED is energized when terminal is powered.
E Terminal X (C) must be connected to transformer common. K L terminal is powered continuously when thermostat is in Em. Ht. position.
F If multiple auxiliary heat loads are used, connect to W2 (Aux W8900B) M13190
terminal.
70-6627 • 66
HONEYWELL
UNIVERSAL THERMOSTATS
10 6
20 2
2
1R 00
04
1G 00
00 0/
10
58
02
00
14
28
00
89 90
01 R1
10
61 G2
10
11
10
10
B1
W PC8
1G
0A
1R
0A
1R
T8 8011
T8 8611
61
30
61
30
61
T
T8
T
Q6
T8
Function
Q6
T8
Common B X X C B C C C C
Power R R R R R R R R
Compressor Y Y Y1 Y1 Y Y Y1 Y1/W1
A A A A A
1st Stage – W1 W1 W1 – W1 W1 –
Heat
F
Auxiliary W2 W2 W2 W2 W2 W2 W2 Aux.
Heat
Fan G G G G G G G G
or C C
C/O Valve B B B H B B B O/B O/B
Heat
or C C
C/O Valve O O O O O O O O/B O/B
Cool
H H H H G G
System Monitor/ L L L L L L L L
Sytem Defrost
Em. Heat E E E E E E E E
Multiple – – E E E E E E
Heat Loads
D D
LED Indication – – – – X1 X2 – X1 X2 –
Defrost P – P – – – – –
F
2nd Stage – – – – – – – W2
Compressor
2nd Stage – – – – – – – Y2
Cool I
A Remove factory-installed jumper for independent first stage heat and cool E If multiple auxiliary heat loads are used, connect to W2 (Aux W8900B)
operation. terminal.
B Terminal must be connected to the transformer common. F When W2 is not used, configure W2 cycle rate to NC.
C Configure O/B (select models) in Installer Setup. G LED is energized when terminal is powered.
D Optional LED indication activated with completed circuit on X1 and H L terminal is powered continuously when thermostat is in Em. Ht. position.
X2 terminals. I If Y2 is used, T8611M may be used as replacement.
M13244
70-6627 • 67
INTERCITY PRODUCTS/HEIL QUAKER/WHIRLPOOL/TEMPSTAR
20 2
10 2
10 1
10 6
G1 19
1G 00
1R 00
E
1G 02
2
1R 00
00
28
00 0/
28
47
14
00
6
BL
94 14
61 G2
89 90
41 R1
AI T
51 G1
01 R1
10
47
42
B1
AV NO
Y5 594G
W PC8
LA
1R
T8 8611
R1
T8 8411
T8 8511
T8 8011
Existing
61
94
T
T
T
T8
Y5
Function Terminals
Common A X X X C C C C C C
Power R R R R R R R R R
F
Compressor Y Y Y1 Y1 Y Y1 Y Y1 Y1/W1
B B B B B B B
1st Stage W1 W1 W1 W1 W1 W1 W1 W1
Heat
NOT AVAILABLE
G
Auxiliary W2 W2 W2 W2 W2 W2 W2 W2 Aux.
Heat
Fan G G G G G G G G G
D D D
or or
C/O Valve B B B B B B O/B B B O/B O/B
Heat
D D D
or or
C/O Valve O O O O O O O/B O O O/B O/B
Cool
H I I H I H H
System Monitor/ L L L L L L L L
System Defrost
Em. Heat E E E E E E E E E
Multiple Aux. W3 W3 W3 E E E E E E
Heat Loads C
LED Indication – X2 X1 X2 – – – – X1 X2 –
Defrost P – – P – – – – –
G
2nd Stage – – – – – – – – W2
Compressor
A Terminal X (C) must be connected to transformer common. F If separate Y1 and W1 terminals are required, install R8222D1014. See
B Remove factory-installed Y1 (Y) to W1 jumper. page 12.
C Terminal is for multiple auxiliary heat loads such as contactors, sequencers or G When W2 is not used, configure W2 cycle rate to NC.
relays. H LED is energized when terminal is powered.
D Configure O/B (select models) in Installer Setup. I L terminal is powered continuously when thermostat is in Em. Ht. position.
E If multiple auxiliary heat loads are used, connect to W2 (W8900B) terminal. M13159
TYPICAL THERMOSTATS AND SUBBASES — HONEYWELL MODEL NUMBER (CUSTOMER PART NUMBER)
T8611R1190 (HQ1149375HW)
T874R1947/Q674L1819 (HQ1149406HW/HQ1149407HW)
70-6627 • 68
INTERCITY PRODUCTS/HEIL QUAKER/WHIRLPOOL/TEMPSTAR
20 2
10 1
10 0
10 6
10 2
1G 00
1G 02
1G 00
G1 19
2
1R 00
1R 00
28
00 0/
04
47
14
28
00
6
2
61 G2
89 90
51 G1
61 R1
94 14
01 R1
41 R1
47
71
42
B1
W PC8
Y5 594G
T8 8611
T8 8611
T8 8511
T8 8011
A1
R1
T8 8411
Existing
41
94
T
T
T
Y
T
Function
T8
Y5
Terminals
or
Common E C B X X X C C C C C C
Power R R R R R R R R R R
B or
Compressor Y Y Y Y1 Y1 Y Y Y1 Y Y1 Y1/W1
F F F F F F F
1st Stage – – W1 W1 W1 W1 W1 W1 W1 –
Heat
or H
Aux. Heat W2 W W2 W2 W2 W2 W2 W2 W2 W2 Aux.
Fan G G G G G G G G G G
A A A
or or
C/O Valve B B B B B B B O/B B B O/B O/B
Heat
A A A
or or
C/O Valve O O O O O O O O/B O O O/B O/B
Cool
or I D D I D I I
System X L L L L L L L L
Monitor
or
EM. Heat X E E E E E E E E E E
Multiple Aux. W3 W3 W3 W3 – – – – – –
Heat Loads C
G G G
LED Indication X1 X2 – X2 X1 X2 X1 X2 – – – X1 X2 –
Defrost P – – – P – – – – –
H
2nd Stage – – – – – – – – – W2
Compressor
2nd Stage – – – – – – – – – Y2
Cool
A Configure O/B (select models) in Installer Setup. F Do not remove factory-installed jumper.
B Both first stage heat and cool are connected to Y terminal. G Optional LED indication activated with completed circuit on X1 and
C Terminal is for multiple second stage loads such as contactors, sequencers, X2 terminals.
or relays. H When W2 is not used, configure W2 cycle rate to NC.
D L terminal is powered continuously when thermostat is in Em. Ht. position. I LED is energized when terminal is powered.
E Terminal X (C) must be connected to transformer common. M13185
TYPICAL THERMOSTATS AND SUBBASES — HONEYWELL MODEL NUMBER (CUSTOMER PART NUMBER)
T841A1134 (HQ1147021HW) T874R1673/Q674L1132 (HAXB004TW01/711598) T8141A1048
T841A1175 (HQ1147004HW) T874R1749/Q674F1329 (TAXB004TW01/712005) T8141A1055
T841A1589 (HQ1149480HW) T874R1749/Q674L1132 (TAXB004TW01/711598) T8141A1139
T872R1172/Q672L1193 T874R1731/Q674L1132 (HQ1147909HW/711598) T8300A1136/Q6300A1119
T874G1246/Q674F1212 T8141A1022 (HQ713669HW)
T874R1137/Q674L1132 (HQ711597HW/711598) T8141A1030 T8611G1020 (HQ713669HW)
70-6627 • 69
INTERTHERM/MILLER/NORDYNE
20 2
10 1
10 6
10 2
1G 00
1G 00
1G 02
2
1R 00
1R 00
00 0/
28
47
04
14
28
00
7
61 10
8
61 G2
89 90
51 G1
01 R1
41 R1
79
63
30
10
B1
T8 611R
W PC8
T8 8611
R1
G1
T8 8011
T8 8511
A1
T8 8411
Existing
94
94
41
T8
T
T
T
T
Y5
Function
Y5
Terminals T8
Common D X X X X C C C C C C
Power R R R R R R R R R R
or
Compressor Y Y Y Y Y1 Y Y Y1 Y Y1 Y1/W1
E E E E E
1st Stage – – – – W1 W1 W1 W1 W1 –
Heat
B
Aux. Heat W2 W2 W2 W2 W2 W2 W2 W2 W2 Aux.
H H H H H H H
Fan G G G G G G G G G G
1 1 1
or or
C/O Valve W1 B B B B B B O/B B B O/B O/B
Heat
1 1 1
or or
C/O Valve – O O O O O O O/B O O O/B O/B
Cool
C C C G G C G C C
System Z L L L L L L L L L
Monitor
Em. Heat K E E E E E E E E E
F
LED Indication – – – – X1 X2 – – – X1 X2 –
B
2nd Stage – – – – – – – – – W2
Compressor
2nd Stage – – – – – – – – – Y2
Cool
A Configure O/B (select models) in Installer Setup. F Optional LED indication activated with completed circuit on X1 and
B When W2 is not used, configure W2 cycle rate to NC. X2 terminals.
C LED is energized when terminal is powered. G L terminal is powered continuously when thermostat is in Em. Ht. position.
D Terminal X (C) must be connected to transformer common. H To eliminate auto fan in emergency heat mode, add switching relay as
E Do not remove factory-installed jumper. shown on page 9.
M13191
70-6627 • 70
INTERTHERM/MILLER/NORDYNE
20 2
10 1
10 0
10 6
10 2
1G 00
G1 19
1G 02
1G 00
2
1R 00
1R 00
28
00 0/
04
47
14
28
00
6
5
2
61 G2
89 90
94 14
51 G1
61 R1
01 R1
41 R1
47
42
71
B1
W PC8
Y5 594G
T8 8611
T8 8611
T8 8511
R1
T8 8011
A1
T8 8411
Existing
94
41
T
Y
T
T
Function
Y5
T8
Terminals
or
Common C X C X X X C C C C C C
Power R R R R R R R R R R
or
Compressor Y Y Y Y1 Y1 Y Y Y1 Y Y1 Y1/W1
E E E E E E E
1st Stage – – W1 W1 W1 W1 W1 W1 W1 –
Heat
B
Aux. Heat W2 W2 W2 W2 W2 W2 W2 W2 W2 Aux.
I I I I I I I
Fan G G G G G G G G G G
1 1 1
or or
C/O Valve B B B B B B B O/B B B O/B O/B
Heat
1 1 1
or or
C/O Valve O O O O O O O O/B O O O/B O/B
Cool
J
K J K J K K
System L L L L L L L L
Monitor
Em. Heat E E E E E E E E E E
Multiple Aux.
Heat Loads D W3 W3 W3 W3 H H H H H H
I
or G I F
LED Indication X2 X1 – X2 X1 X2 X1 X2 – – – X1 X2 –
B
2nd Stage – – – – – – – – – W2
Compressor
2nd Stage – – – – – – – – – Y2
Cool
70-6627 • 71
INTERTHERM/MILLER/NORDYNE
20 2
10 2
10 4
10 1
10 6
1G 00
1R 00
1R 00
2
1G 02
1R 00
00 0/
28
28
00
47
14
00
61
3
5
61 G2
89 90
41 R1
61 G1
51 G1
01 R1
76
55
B1
1
W PC8
T8 8411
G1
T8 8611
T8 8011
R1
T8 8611
A1
T8 8511
Existing
94
94
41
T
T
T
T
Function
Y5
Y5
Terminals T8
B
Common A X B B B C C C C C C
Power R R R R R R R R R R
or
Compressor Y Y Y Y1 Y1 Y Y Y1 Y Y1 Y1/W1
D D D D D
1st Stage – – – – W1 W1 W1 W1 W1 –
Heat
G
Auxiliary W2 W W W W2 W2 W2 W2 W2 Aux.
Heat
F F F F F F F F F
Fan G G G G G G G G G G
Outdoor T T T T E E E E E E
Thermistor
Em. Heat F K X2 X2 X2 E E E E E E
C C C
or or
C/O Valve W1 O O O O O O O/B O O O/B O/B
Cool
H H H I I H I H H
System Monitor/ Z F F F L L L L L L
System Defrost
A For best performance, use a NEMA rated transformer. F To eliminate auto fan in EM. Heat mode, see page 9.
B Terminal B (C, X) must be connected to transformer common. G Use Aux terminal for Auxiliary heat and configure W2 cycle rate to NC.
C Configure O/B (select models) in Installer Setup. H LED is energized when terminal is powered.
D Leave factory-installed jumper W1-Y1 (Y) in place. I L terminal is powered continuously when thermostat is in Em. Ht. position.
E Tape off. Electronic thermostat replaces outdoor reset with improved zero M13160
droop performance.
70-6627 • 72
JANITROL/TAPPAN
10 2
10 1
20 2
10 0
10 6
G1 19
1R 00
1G 02
1G 00
2
1G 00
1R 00
00 0/
28
47
28
04
14
00
6
2
94 14
89 90
41 R1
51 G1
61 G2
61 R1
01 R1
47
71
42
B1
Y5 594G
W PC8
A1
R1
T8 8411
T8 8511
T8 8611
T8 8611
T8 8011
Existing
41
94
T
T
T
T
T8
Y5
Function Terminals
Common D C X X X C C C C C C
Power R R R R R R R R R R
B or
Compressor Y Y Y Y1 Y1 Y Y Y1 Y Y1 Y1/W1
E E E E E E E
1st Stage – – W1 W1 W1 W1 W1 W1 W1 –
Heat
or I
Auxiliary OTC W2 W2 W2 W2 W2 W2 W2 W2 W2 Aux.
Heat
Fan G G G G G G G G G G
G A A A
or or or
C/O Valve B W1 B B B B B O/B B B O/B O/B
Heat
A A A
G or or
C/O Valve O O O O O O O O/B O O O/B O/B
Cool
System – – L – L L L L L L
Monitor
EM. Heat E E E E E E E E E E
Multiple Aux. – W3 W3 W3 H H H H H H
Heat Loads C
F F F
LED Indication – – X2 X1 X2 X1 X2 – – – X1 X2 –
I
2nd Stage – – – – – – – – – W2
Compressor
2nd Stage – – – – – – – – – Y2
Cool
A Configure O/B (select models) in Installer Setup. F Optional LED indication activated with completed circuit on X1 and
B Both First stage heat and cool are connected to Y terminal. X2 terminals.
C Terminal is for multiple auxiliary heat loads such as contactors, sequencers, G Thermostat will have connection to either O or B terminal, not both.
or relays. H If multiple auxiliary heat loads are used connect to W2 (Aux W8900B)
D Terminal must be connected to the transformer common. terminal.
E Do not remove factory-installed jumper. I When W2 is not used, configure W2 cycle rate to NC.
M13223
TYPICAL THERMOSTATS AND SUBBASES — HONEYWELL MODEL NUMBER (CUSTOMER PART NUMBER)
T872G1109/Q672F1117 (080-13708-52/080-13708-53)
T874G1147/Q674F1139
70-6627 • 73
KEEPRITE
20 2
10 1
10 0
10 6
10 2
1G 00
1G 02
G1 19
1G 00
2
1R 00
1R 00
28
00 0/
04
47
14
28
00
6
5
2
61 G2
89 90
51 G1
94 14
61 R1
01 R1
41 R1
47
42
71
B1
W PC8
Y5 594G
T8 8611
T8 8611
T8 8511
T8 8011
R1
A1
T8 8411
Existing
94
41
T
T
T
Y
T
T
Function
Y5
Terminals T8
Common D B X X X C C C C C C
Power R R R R R R R R R R
or
Compressor Y Y Y Y1 Y1 Y Y Y1 Y Y1 Y1/W1
E E E E E E E
1st Stage – – W1 W1 W1 W1 W1 W1 W1 –
Heat
B
Aux. Heat W W2 W2 W2 W2 W2 W2 W2 W2 Aux.
Fan G G G G G G G G G G
1 1 1
or or
C/O Valve – B B B B B B O/B B B O/B O/B
Heat
1 1 1
or or
C/O Valve O O O O O O O O/B O O O/B O/B
Cool
System – – L – L L L L L L
Monitor
Em. Heat X E E E E E E E E E
Multiple Aux.
Heat Loads C – W3 W3 W3 – – – – – –
LED Indication – – X2 X1 X2 X1 X2 – – – X1 X2 –
B
2nd Stage – – – – – – – – – W2
Compressor
2nd Stage – – – – – – – – – Y2
Cool
A Configure O/B (select models) in Installer Setup. D Terminal X (C,B) must be connected to transformer common.
B When W2 is not used, configure W2 cycle rate to NC. E Leave factory-installed jumper in place.
C Terminal is for multiple auxiliary heat loads such as contactors, sequencers, M13193
or relays.
70-6627 • 74
LENNOX
TYPICAL HP6 (ALTERNATE)
20 2
10 2
10 0
10 1
10 6
1G 00
G1 19
1R 00
1G 00
2
1G 02
1R 00
00 0/
28
28
04
47
14
00
6
5
61 G2
89 90
94 14
41 R1
61 R1
51 G1
01 R1
47
42
B1
W PC8
Y5 594G
T8 8411
T8 8611
T8 8611
R1
T8 8011
T8 8511
94
T
Y
T
T
Function
Y5
Existing Terminals
or or or
Common D X2 – – – X X C C C C C C
I I
Power V R V/VR V/VR R R R R R R R R
B H
or
Compressor M W1 M1 M Y1 Y1 Y1 Y Y Y1 Y Y1 Y1/W1
J J J J J J J
1st Stage – – R – W1 W1 W1 W1 W1 W1 W1 –
Heat
K
Auxiliary Y W2 Y Y W2 W2 W2 W2 W2 W2 W2 Aux.
Heat
Fan F G F G G G G G G G G G
A A A
or or
C/O Valve – – – – B B B B B O/B B B O/B O/B
Heat
A A A
or or
C/O Valve R Y1 – R O O O O O O/B O O O/B O/B
Cool
F G G F G F F
System Monitor/ – – – – L – L L L L L L
System Defrost
E E E E E E E E
Em. Heat E – – – E E E E E E E E
Multiple Aux. – – – – – W3 – – – – – –
Heat Loads C
LED Indicator – – – – – X1 X2 X1 X2 – – – X1 X2 –
K
2nd Stage – – – – – – – – – – – W2
Compressor
A Configure O/B (select models) in Installer Setup. G L terminal is powered continuously when thermostat is in Em. Ht. position.
B Both first stage heat and cool are connected to M terminal. H If separate Y1 and W1 terminals are required, install R8222D1014; see
C Terminal is for multiple auxiliary heat loads such as contactors, sequencers or page 12.
relays. I If separate transformers are used, replace with one 75 VA transformer as
D Terminal X (C) must be connected to transformer common. shown on page 78.
E Field-installed E to W2 (Aux) jumper required. J When replacing models with one compressor terminal (M), jumper Y1 to W1.
F LED is energized when terminal is powered. K When W2 is not used, configure W2 cycle rate to NC.
M13161
70-6627 • 75
LENNOX
HP6
10 2
10 0
20 2
10 6
10 1
1R 00
1G 00
1G 00
2
1R 00
28
1G 02
B1 18
00 0/
04
28
14
47
00
41 R1
0
LE
89 90
61 R1
61 G2
01 R1
51 G1
74 10
00
07
B1
AIL T
W PC8
AB
T8 8411
AV NO
Q6 874C
T8 8611
T8 011
T8 8611
B1
T8 8511
Existing
41
T8
T
T
T
T
T
Function
T8
Terminals
or or
Common A – – – X – C C C C C C
or D or D
Power R V VR V VR V R R R R R R R R
E C
Compressor Y1 M1 M Y1 Y1 Y1 Y Y1 Y Y1 Y1/W1
E E E E E E E
1st Stage W1 R – W1 W1 W1 W1 W1 W1 W1 –
Heat
NOT AVAILABLE
G
Auxiliary W2 Y Y W2 W2 W2 W2 W2 W2 W2 Aux.
Heat
Fan G F F G G G G G G G G
B B B
C/O Valve or or
– – R O O O O O O/B O O O/B O/B
Cool
SystemMonitor/ X1 – – – – L L L L L L
System Defrost
F F F F F F
Em. Heat – – – – – E E E E E E
G
2nd Stage – – – – – – – – – – W2
Compressor
A Terminal X (C) must be connected to transformer common. D If separate transformers are used, replace with one 75 VA transformer as
B Configure O/B (select models) in Installer Setup. shown on page 78.
C If separate Y1 and W1 terminals are required, install R8222D1014; see E When replacing models with one compressor terminal, jumper Y1 to W1.
page 12. F Field-installed E to W2 (Aux) jumper required.
G When W2 is not used, configure W2 cycle rate to NC. M13162
70-6627 • 76
LENNOX
HP9, HP10
IMPORTANT: Replace separate indoor/outdoor transformers with single 75 VA transformer. See diagram on page 78.
10 1
20 2
10 2
10 6
10 0
1G 02
1G 00
1R 00
G1 19
2
1R 00
1G 00
00 0/
47
28
28
14
04
00
6
2
51 G1
89 90
61 G2
41 R1
94 14
01 R1
61 R1
47
71
42
B1
W PC8
Y5 594G
T8 8411
T8 8511
T8 8611
T8 8011
A1
R1
T8 8611
Existing
41
94
T
T
Y
T
Function
T8
Y5
Terminals
Common X X X X C C C C C C
Indoor D
Common X3 – – – – – – – – –
Outside
Power VR R R R R R R R R R
Indoor
I
Power V – – – – – – – – –
Outside
or
Compressor M Y Y Y1 Y1 Y Y Y1 Y Y1 Y1/W1
E E E E E E E
1st Stage – – W1 W1 W1 W1 W1 W1 W1 –
Heat
or
Auxiliary W1 Y W2 W2 W2 W2 W2 W2 W2 W2 Aux.
Heat
Fan F G G G G G G G G G
A A A
or or
C/O Valve – B B B B B B O/B B B O/B O/B
Heat
A A A
or or
C/O Valve R O O O O O O O/B O O O/B O/B
Cool
C J K K J K J J
System Monitor/ L L L L L L L L
System Defrost
Em. Heat E E E E E E E E E E
B
Thermistor A – – – – – – – – –
Multiple Aux. – W3 W3 W3 – – – – – –
Heat Loads
G F
LED Indication – – X2 X1 X2 X1 X2 – – – X1 X2 –
70-6627 • 77
IMPORTANT: DISCONNECT POWER SUPPLY BEFORE BEGINNING WIRING.
YELLOW
F G
INDOOR BLOWER
RELAY
M Y
DEFROST
COMPRESSOR CONTROL (Y1 + W1)
CONTACTOR RELAY
DEFROST
RELAY
R O
REVERSING
VALVE
E E
EMERGENCY
HEAT RELAY
3 X X
Y W2
HEAT RELAY
NO. 1 DEFROST
RELAY
L L (X1)
SERVICE
LIGHT
THERMOSTAT
1 X2
THERMISTOR
A
X
OUTDOOR
TAPE
THERMOSTAT VR R
OFF
70-6627 • 78
LENNOX
HP11
IMPORTANT: Replace separate indoor/outdoor transformers with single 75 VA transformer. See diagram on page 78.
20 7
F1 5/
1M 01
02
2
08
25
00 0/
00
74 116
2
61 M2
10
89 90
70
02
B1
1M
W PC8
Q6 74D
1M
T8 8611
Existing A
51
61
T8
T
Function Terminals
T8
T8
Common D X X1 C C C C
G
Power Indoor VR R R R R R
Common Outside X – – – – –
G
Common Outside V G G G G G
E
Compressor Stage 1 M Y1 Y Y1 Y1 Y1/W1
Compressor Stage 2 M2 Y2 Y2 Y2 Y2 Y2
W2 – – W2
C C C C
Auxiliary Heat Y W2 W3 W3 W3 Aux.
Fan F G G G G G
H H H
C/O Valve R O O O/B O/B O/B
Cool
H H H
C/O Valve – B B O/B O/B O/B
Heat
B J I J I
System Monitor/ L X2 L L L L
System Defrost
Em. Heat E E E E E E
Thermistor A – – – – –
F F
LED Indication – – X1 X2 – X1 X2 –
A IMPORTANT: When subbase system is in AUTO position, equipment will F Optional LED indication activated with completed circuit on X1 and
operate in COOL mode only (Q674F1022). X2 terminals.
B For emergency heat indication, jumper E and X2. For auxiliary heat G Replace separate indoor and outdoor transformers with one 75 VA
indication, jumper W2 and X2. For any X2 functions, X1 must be connected to transformer. See page 78 for wiring diagram.
transformer common. H Configure O/B (select models) in Installer Setup.
C For proper operation of auxiliary heat connect Y to W3 or AUX terminal. I LED is energized when terminal is powered.
D Terminal must be connected to the transformer common. J L terminal is powered continuously when thermostat is in Em. Ht. position.
E W1 to Y1 jumper required. M13156
70-6627 • 79
LENNOX
HP16, HP19, HP21, HP22 (DIRECT REPLACEMENTS)
10 2
20 2
10 6
10 1
10 0
1R 00
1G 00
2
1R 00
1G 02
00 0/
28
28
1G 00
14
47
00
04
1
3
5
89 90
41 R1
61 G2
01 R1
51 G1
16
76
61 R1
55
B1
W PC8
T8 8411
G1
T8 8611
T8 8011
R1
A1
T8 8511
T8 8611
Existing
94
94
41
T
T
T
Function
Y5
Y5
T
T8
Terminals
Common A X B B B C C C C C C
F
Power V VR R R R R R R R R R
or
Compressor M Y Y Y Y1 Y Y Y1 Y Y1 Y1/W1
C C C C C
1st Stage – – – – W1 W1 W1 W1 W1 –
Heat
Auxiliary Y W W W W2 W2 W2 W2 W2 Aux.
Heat
Fan F G G G G G G G G G
H H H
or or
C/O Valve – – – – B B B O/B B B O/B O/B
Heat
H H H
or or
C/O Valve R O O O O O O O/B O O O/B O/B
Cool
E
G J J J E J E J J
System Monitor/ L F F F L L L L L L
Sytem Defrost
G
Outdoor Stat/ E X2 X2 X2 E E E E E E
Em. Heat
Outdoor A T T T B B B B B B
Sensor
D D
LED Indication – – – – X1 X2 – – – X1 X2 –
A Terminal B (C or X) must be connected to transformer common. F If separate transformers are used, replace with one 75 Va transformer as
B Tape off. Thermostat replaces outdoor reset with improved zero droop shown on page 78.
performance. G R8222B1067 Relay required to operate system monitor light (emergency
C Do not remove factory-installed jumper. heat LED) on TRADELINE replacement thermostats. See page 11. Tape
D Optional LED indication activated with completed circuit on X1 and X2 off if LED indication is not desired.
terminals. H Configure O/B (select models) in Installer Setup.
E L terminal is powered continuously when thermostat is in Em. Ht. position. I When W2 is not used, configure W2 cycle rate to NC.
J LED is energized when terminal is powered. M13164
TYPICAL THERMOSTATS AND SUBBASES — HONEYWELL MODEL NUMBER (CUSTOMER PART NUMBER)
T874C1448/Q674L1355 (24F5101/31F3201) T874C1448/Q674L1165 (24F5101/24F5901)
T874R1178/Q674L1355 (24F5601/31F3201) T874R1178/Q674L1165 (24F5601/24F5901)
70-6627 • 80
LENNOX
HP16, HP18, HP19, HP20, HP21, HP22
10 2
10 6
10 1
20 2
10 0
1R 00
G1 19
2
1R 00
1G 02
00 0/
1G 00
28
1G 00
14
47
28
00
04
2
6
5
89 90
41 R1
94 14
01 R1
51 G1
61 G2
71
47
61 R1
42
B1
W PC8
Y5 594G
T8 8411
A1
T8 011
R1
T8 8511
T8 8611
T8 8611
Existing
41
94
T8
T
Y
T
T8
Function
T
T
Y5
Terminals
or or or
Common G X X2 C X X X X C C C C C C
I
or or
Power V VR R R R R R R R R R R
or or
Compressor M Y Y Y Y1 Y1 Y Y Y1 Y Y1 Y1/W1
H H H H H H H
1st Stage – – W1 W1 W1 W1 W1 W1 W1 –
Heat
or or J
Auxiliary Y W W2 W2 W2 W2 W2 W2 W2 W2 W2 Aux.
Heat
or
Fan F G G G G G G G G G G
A A A
or or or
C/O Valve – B B B B B B B O/B B B O/B O/B
Heat
A A A
or or or
C/O Valve R O O O O O O O O/B O O O/B O/B
Cool
CF L M M L M L L
System Monitor/ L L L L L L L L
System Defrost
F
EM. Heat E E E E E E E E E E
Multiple Aux. W3 W3 W3 W3 K K K K K K
Heat Loads E
Thermistor D
A – – – – – – – – –
B B
or B
LED Indication X1 X2 – X2 X1 X2 X1 X2 – – – X1 X2 –
A Configure O/B (select models) in Installer Setup. G Terminal X (X2 or C) must be connected to transformer common.
B Optional LED indication activated with completed circuit on X1 and H Do not remove factory-installed jumper.
X2 terminals. I If separate transformers are used, replace with one 75 VA transformer as
C Not on HP18 or HP20. shown on page 78.
D Tape off. Not used. J When W2 is not used, configure W2 cycle rate to NC.
E Terminal is for multiple second stage loads such as contactors, sequencers, K If multiple auxiliary heat loads are used, connect to W2 (Aux W8900B)
or relays. terminal.
F R8222B1067 Relay required to operate system monitor light (emergency L LED is energized when terminal is powered.
heat LED) on TRADELINE replacement thermostats, see page 10. Tape off M L terminal is powered continuously in Emergency Heat Position.
if LED indication is not desired. M13165
TYPICAL THERMOSTATS AND SUBBASES — HONEYWELL MODEL NUMBER (CUSTOMER PART NUMBER)
T874C1448/Q674L1355(24F5101/31F3201) T874C1448/Q674L1165(24F5101/24F5901)
T874G1014/Q674F1113(24F5801/24F6201) T874G1154/Q674F1105
T874R1178/Q674L1355(24F5601/31F3201) T874R1178/Q674L1165(24F5601/24F5901)
T8141A1089 T8611G1053 (27H3001)
70-6627 • 81
LUXAIRE (MONCRIEF/FRASER JOHNSTON)
10 2
10 6
10 1
20 2
10 0
1R 00
G1 19
2
1R 00
1G 02
00 0/
1G 00
28
1G 00
14
47
28
04
00
6
2
89 90
41 R1
94 14
01 R1
51 G1
61 G2
61 R1
47
71
42
B1
W PC8
Y5 594G
T8 8411
T8 8011
A1
R1
T8 8511
T8 8611
T8 8611
Existing
41
94
T
Y
T
Function
T
T
T8
Y5
Terminals
or
Common D B X X X X C C C C C C
Power R R R R R R R R R R
B or
Compressor Y Y Y Y1 Y1 Y Y Y1 Y Y1 Y1/W1
E E E E E E E
1st Stage – – W1 W1 W1 W1 W1 W1 W1 –
Heat
or J
Auxiliary W W2 W2 W2 W2 W2 W2 W2 W2 W2 Aux.
Heat
Fan G G G G G G G G G G
A A A
or or
C/O Valve – B B B B B B O/B B B O/B O/B
Heat
A A A
or or
C/O Valve O O O O O O O O/B O O O/B O/B
Cool
System Monitor/ – – L – L L L L L L
System Defrost
or
EM. Heat X E E E E E E E E E E
Multiple Aux. – W3 W3 W3 G G G G G G
Heat Loads C
I H I
LED Indication – – X2 F X1 X2 X1 X2 – – – X1 X2 –
J
2nd Stage – – – – – – – – – W2
Compressor
A Configure O/B (select models) in Installer Setup. G If multiple auxiliary heat loads are used, connect to W2 (Aux W8900B)
B Both first stage heat and cool are connected to Y terminal. terminal.
C Terminal is for multiple second stage loads such as contactors, sequencers, H Optional CHECK LED. Connect X1 to switching device; jumper X2 to C.
or relays. I Optional LED indication activated with completed circuit on X1 and
D Terminal X (C or B) must be connected to transformer common. X2 terminals.
E Do not remove factory-installed jumper. J When W2 is not used, configure W2 cycle rate to NC.
F Field-installed X2 to X jumper (provided). M13166
70-6627 • 82
MAGIC CHEF
“PB” SERIES EQUIPMENT
10 1
20 2
10 6
10 2
E
A 1034 /
2
G1 19
00
00 0/
1G 02
8
1G 00
1R 00
1R 00
47
BL
28
00
14
28
74 101
6
AI T
89 90
94 14
10
51 G1
61 G2
01 R1
41 R1
47
AV NO
B1
LA
W PC8
Y5 594G
1R
Q6 74C
T8 8511
T8 8011
T8 8411
T8 8611
B
Existing
61
T8
T8
Function
T
T
T
Terminals
Common B C X C C C C C C
Power R Rc R R R R R R R
F
1st Stage Y1 Y1 Y1 Y1 Y Y1 Y Y1 Y1/W1
Cool
C C C C C C C
1st Stage W1 W1 W1 W1 W1 W1 W1 W1 –
NOT AVAILABLE
Heat
2nd Stage W2 W2 W2 W2 W2 W2 W2 W2 W2
Heat
Fan G G G G G G G G G
or or
C/O Valve – B B B B B O/B B B O/B O/B
Heat
or or
C/O Valve O O O O O O O/B O O O/B O/B
Cool
E 4 4 E 4 E E
System Monitor/ X1 X1 L L L L L L
System Defrost
EM. Heat E – E E E E E E E
2nd Stage – Y2 – – – – – – Y2
Cool
Power Heat – Rh – – – – – – –
A IMPORTANT: No provision for emergency heat, system monitor (compressor D L terminal is powered continuously when thermostat is in Em. Ht. position.
fault), or auxiliary heat LEDs. E LED is energized when terminal is powered.
B Terminal C (X) must be connected to transformer common. F If separate Y1 and W1 terminals required, install R8222D1014; see
C Remove Y1 (Y) to W1 (W) jumper. page 12.
M13167
70-6627 • 83
MAGIC CHEF
“PE” SERIES EQUIPMENT
10 1
10 2
10 0
10 6
20 2
1G 02
1R 00
G1 19
2
1G 00
1R 00
47
00 0/
28
04
1G 00
14
00
28
5
6
2
51 G1
89 90
41 R1
94 14
61 R1
01 R1
42
47
71
61 G2
B1
W PC8
Y5 594G
T8 8511
T8 8411
R1
T8 8611
T8 8011
A1
T8 8611
Existing
94
41
T
T
T
T
Y
Y5
Function Terminals T8
T
Common F C X X X C C C C C C
Power R R R R R R R R R R
B or
Compressor Y Y Y Y1 Y1 Y Y Y1 Y Y1 Y1/W1
G G G G G G G
1st Stage – – W1 W1 W1 W1 W1 W1 W1 –
Heat
L
Aux. Heat W W2 W2 W2 W2 W2 W2 W2 W2 Aux.
Fan G G G G G G G G G G
A A A
or or
C/O Valve – B B B B B B O/B B B O/B O/B
Heat
A A A
or or
C/O Valve O O O O O O O O/B O O O/B O/B
Cool
E N N M N M M
System Monitor/ X1 L L L L L L L
System Defrost
4
EM. Heat E E E E E E E E E E
Multiple Aux. – W3 W3 W3 J J J J J J
Heat Loads C
K K
LED Indication I H
– – X2 X1 X2 X1 X2 – – – X1 X2 –
2nd Stage L
Compressor – – – – – – – – – W2
A Configure O/B (select models) in Installer Setup. H Optional CHECK LED on T8611G1004. Connect X1 to X1 on control
B Both first stage heat and cool are connected to Y terminal. terminal; jumper X2 to R.
C Terminal is for multiple second stage loads such as contactors, sequencers, I Field-installed X2 to X jumper (provided).
or relays. J If multiple auxiliary heat loads are used, connect to W2 (Aux W8900B)
D If provided on original equipment. terminal.
E Relay (typically R8222B1067) required if outdoor section has reset shunt K Optional LED indication activated with completed circuit on X1 and
relay and malfunction light indication is desired on thermostat. See page 11. X2 terminals.
F Terminal C (X) must be connected to transformer common. L When W2 is not used, configure W2 cycle rate to NC.
G Do not remove factory-installed jumper. M LED is energized when terminal is powered.
N L terminal is powered continuously in Emergency Heat Position.
M13168
70-6627 • 84
MAMMOTH
10 1
20 2
10 2
10 0
10 6
1G 02
G1 19
1G 00
1R 00
2
1G 00
1R 00
47
00 0/
28
28
04
14
00
6
5
2
51 G1
94 14
89 90
61 G2
41 R1
61 R1
01 R1
47
42
71
B1
Y5 594G
W PC8
T8 8511
T8 8411
T8 8611
R1
T8 8611
T8 8011
A1
Existing
94
41
T
T
Y
T
T
T
Function
Y5
T8
Terminals
or
Common F C X X X X C C C C C C
or
Power R R1 R R R R R R R R R
Power Reset R2 – – – – – – – – –
or B or
1st Stage Y1 Y Y Y Y1 Y1 Y Y Y1 Y Y1 Y1/W1
Comp.
G G G G G G G
2nd Stage Y2 – – – – – – – – – Y2
Comp.
1st Stage – – W1 W1 W1 W1 W1 W1 W1 –
Heat
D J
Aux. Heat W2 W2 W2 W2 W2 W2 W2 W2 W2 Aux.
Fan G G G G G G G G G G
A A A
or or
C/O Valve B B B B B B B O/B B B O/B O/B
Heat
A A A
or or
C/O Valve O O O O O O O O/B O O O/B O/B
Cool
D E
or L M M L M L L
System Monitor/ X L L L L L L L L
System Defrost
E
EM. Heat – E E E E E E E E E
Multiple Aux. – W3 W3 W3 – – – – – –
Heat Loads C
K
I K H
LED Indication – – X2 X1 X2 X1 X2 – – – X1 X2 –
Filter F – – – – – – – – –
2nd Stage J
Compressor – – – – – – – – – W2
A Configure O/B (select models) in Installer Setup. G Do not remove factory-installed jumper.
B Both first stage heat and cool are connected to Y terminal. H Optional CHECK LED on T8611G1004. See Fig. 26.
C Terminal is for multiple auxiliary heat loads such as contactors, sequencers, I Field-installed X2 to X jumper (provided).
or relays. J When W2 is not used, configure W2 cycle rate to NC.
D If provided on original equipment. K Optional LED indication activated with completed circuit on X1 and
E Relay (typically R8222B1067) required if outdoor section has reset shunt X2 terminals.
relay and malfunction light indication is desired on thermostat. See page 11. L LED is energized when terminal is powered.
F Terminal X (C) must be connected to transformer common. M L terminal is powered continuously in Emergency Heat Position. M13169
70-6627 • 85
MAMMOTH
USED WITH A STANDARD HEAT PUMP THERMOSTAT
10 1
10 6
10 2
20 2
10 0
G1 19
2
1G 02
1R 00
1R 00
1G 00
00 0/
1G 00
47
14
28
28
04
00
6
5
2
94 14
89 90
51 G1
01 R1
41 R1
61 G2
47
42
61 R1
71
B1
Y5 594G
W PC8
R1
T8 8011
A1
T8 8511
T8 8411
T8 8611
T8 8611
Existing
94
41
T
T
T
T
Function
Y5
T
Terminals T8
Common D C X X X C C C C C C
Power R R R R R R R R R R
H or
Compressor Y Y Y Y1 Y1 Y Y Y1 Y Y1 Y1/W1
E E E E E E E
1st Stage – – W1 W1 W1 W1 W1 W1 W1 –
Heat
C J
Aux. Heat W2 W2 W2 W2 W2 W2 W2 W2 W2 Aux.
Fan G G G G G G G G G G
1 1 1
or or
C/O Valve B B B B B B B O/B B B O/B O/B
Heat
1 1 1
or or
C/O Valve O O O O O O O O/B O O O/B O/B
Cool
L M M L M L L
System Monitor/ L L L L L L L L
System Defrost
Em. Heat – E E E E E E E E E
Multiple Aux.
Heat Loads B – W3 W3 W3 I I I I I I
K
G K F
LED Indication – – X2 X1 X2 X1 X2 – – – X1 X2 –
J
2nd Stage – – – – – – – – – W2
Compressor
2nd Stage – – – – – – – – – Y2
Cool
A Configure O/B (select models) in Installer Setup. H Both first stage heat and cool are connected to Y terminal.
B Terminal is for multiple auxiliary heat loads such as contactors, sequencers, I If multiple auxiliary heat loads are used, connect to W2 (Aux W8900B)
or relays. terminal.
C If provided on original equipment. J When W2 is not used, configure W2 cycle rate to NC.
D Terminal must be connected to the transformer common. K Optional LED indication activated with completed circuit on X1 and
E Do not remove factory-installed jumper. X2 terminals.
F Optional CHECK LED on T8611G1004. Connect L to X1; jumper X2 to C. L LED is energized when terminal is powered.
G Field-installed X2 to X jumper. M L terminal is powered continuously when thermostat is in Em. Ht. position.
M13194
TYPICAL THERMOSTATS AND SUBBASES — HONEYWELL MODEL NUMBER (CUSTOMER PART NUMBER)
T834C2135 (71116901) T841B1042 (71117001)
70-6627 • 86
MAMMOTH
USED WITH A NIGHT SETBACK THERMOSTAT
10 1
10 6
20 2
10 2
10 0
G1 19
1G 02
2
1R 00
1G 00
1R 00
00 0/
1G 00
47
14
28
28
04
00
6
5
2
89 90
94 14
51 G1
01 R1
61 G2
41 R1
61 R1
47
42
71
B1
W PC8
Y5 594G
R1
T8 8011
T8 8511
A1
T8 8411
T8 8611
T8 8611
Existing
94
41
T
T
T
T
T
Function
Y5
T8
Terminals
J
Common F C X X X C C C C C C
D
Power R1 R R R R R R R R R
Night Setback R2 – – – – – – – – –
Power
or
Compressor Y Y Y Y1 Y1 Y Y Y1 Y Y1 Y1/W1
G G G G G G G
1st Stage – – W1 W1 W1 W1 W1 W1 W1 –
Heat
B
Aux. Heat – W2 W2 W2 W2 W2 W2 W2 W2 Aux.
Fan G G G G G G G G G G
1 1 1
or or
C/O Valve B B B B B B B O/B B B O/B O/B
Heat
1 1 1
or or
C/O Valve O O O O O O O O/B O O O/B O/B
Cool
L M M L M L L
System Monitor/ X L L L L L L L
System Defrost
Em. Heat – E E E E E E E E E
Multiple Aux.
Heat Loads C – W3 W3 W3 K K K K K K
E
I E H
LED Indication – – X2 X1 X2 X1 X2 – – – X1 X2 –
B
2nd Stage – – – – – – – – – W2
Compressor
2nd Stage – – – – – – – – – Y2
Cool
A Configure O/B (select models) in Installer Setup. G Do not remove factory-installed jumper.
B When W2 is not used, configure W2 cycle rate to NC. H Optional CHECK LED on T8611G1004. See Fig. 26.
C Terminal is for multiple auxiliary heat loads such as contactors, sequencers, I Field-installed X2 to X (C) jumper.
or relays. J C terminal is located on terminal strip, not on subbase.
D Disconnect external timimg device from circuit before wiring replacement K If multiple auxiliary heat loads are used, connect to W2 (Aux W8900B)
thermostat. terminal.
E Optional LED indication activated with completed circuit on X1 and L LED is energized when terminal is powered.
X2 terminals. M L terminal is powered continuously when thermostat is in Em. Ht. position.
F Terminal must be connected to the transformer common. M13195
TYPICAL THERMOSTATS AND SUBBASES — HONEYWELL MODEL NUMBER (CUSTOMER PART NUMBER)
T874G1378/Q674C1124 T874G1659/Q674C1330 (71115201) T874H1096/Q674C1330 (71115201)
70-6627 • 87
MARTIN INDUSTRIES
10 1
20 2
10 6
10 2
10 0
1G 02
1G 00
G1 19
2
1R 00
1R 00
00 0/
1G 00
47
28
14
28
04
00
5
6
2
89 90
51 G1
61 G2
94 14
01 R1
41 R1
42
61 R1
47
71
B1
W PC8
Y5 594G
R1
T8 8511
T8 8611
T8 8011
A1
T8 8411
T8 8611
Existing
94
41
T
T
Y
T
Y5
T
Function Terminals T8
Common E X X X X C C C C C C
Power R R R R R R R R R R
B or
Compressor Y Y Y Y1 Y1 Y Y Y1 Y Y1 Y1/W1
F F F F F F F
1st Stage – – W1 W1 W1 W1 W1 W1 W1 –
Heat
G
Aux. Heat W2 W2 W2 W2 W2 W2 W2 W2 W2 Aux.
Fan G G G G G G G G G G
1 1 1
or or
C/O Valve B B B B B B B O/B B B O/B O/B
Heat
1 1 1
or or
C/O Valve O O O O O O O O/B O O O/B O/B
Cool
I J J I J I I
System Monitor/ L L L L L L L L
System Defrost
Em. Heat E E E E E E E E E E
Multiple Aux. W3 W3 W3 W3 H H H H H H
Heat Loads C
D D D
LED Indication – – X2 X1 X2 X1 X2 – – – X1 X2 –
G
2nd Stage – – – – – – – – – W2
Compressor
2nd Stage – – – – – – – – – Y2
Cool
A Configure O/B (select models) in Installer Setup. F Do not remove factory-installed jumper.
B Both first stage heat and cool are connected to Y terminal. G When W2 is not used, configure W2 cycle rate to NC.
C Terminal is for multiple auxiliary heat loads such as contactors, sequencers, H If multiple auxiliary heat loads are used, connect to W2 (Aux W8900B)
or relays. terminal.
D LED indication with completed circuit on X1 and X2 terminals. I LED is energized when terminal is powered.
E Terminal must be connected to the transformer common. J L terminal is powered continuously when thermostat is in Em. Ht. position.
M13196
TYPICAL THERMOSTATS AND SUBBASES — HONEYWELL MODEL NUMBER (CUSTOMER PART NUMBER)
T841A1183 T841A1522 T841A1548 (24015808)
70-6627 • 88
PHILLIPS ENERGY
10 1
20 2
10 6
10 2
1G 00
G1 19
1G 02
1G 00
2
1R 00
1R 00
00 0/
47
28
04
14
28
00
5
61 10
2
94 14
89 90
51 G1
61 G2
42
01 R1
41 R1
47
71
10
B1
T8 611R
Y5 594G
W PC8
R1
T8 8511
T8 8611
T8 8011
A1
T8 8411
Existing
94
41
T8
Y
T
Y5
T
T
T
Function
T8
Terminals
Common D C X X X C C C C C C
Power R R R R R R R R R R
H or
Compressor Y1 Y Y Y1 Y1 Y Y Y1 Y Y1 Y1/W1
F F F F F F F F
1st Stage W1 – W1 W1 W1 W1 W1 W1 W1 –
Heat
B
Aux. Heat W2 W2 W2 W2 W2 W2 W2 W2 W2 Aux.
Fan G G G G G G G G G G
1 1 1
or or
C/O Valve B B B B B B B O/B B B O/B O/B
Heat
1 1 1
or or
C/O Valve O O O O O O O O/B O O O/B O/B
Cool
H I I H I H H
System Monitor/ L L L L L L L L
System Defrost
Em. Heat E E E E E E E E E E
Multiple Aux.
Heat Loads C – W3 W3 W3 E E E E E E
G J J J
LED Indication X2 – X2 X1 X2 X1 X2 – – – X1 X2 –
B
2nd Stage – – – – – – – – – W2
Compressor
2nd Stage – – – – – – – – – Y2
Cool
A Configure O/B (select models) in Installer Setup. F Do not remove factory-installed jumper.
B When W2 is not used, configure W2 cycle rate to NC. G Field-installed X2 to X jumper.
C Terminal is for multiple auxiliary heat loads such as contactors, sequencers, H LED is energized when terminal is powered.
or relays. I L terminal is powered continuously when thermostat is in Em. Ht. position.
D Terminal must be connected to the transformer common. J Optional LED indication activated with completed circuit on X1 and
E If multiple auxiliary heat loads are used, connect to W2 (Aux W8900B) X2 terminals. M13197
terminal.
70-6627 • 89
RHEEM/RUUD
COOLING CHANGEOVER (PRE 11/85) (PCA, PNA, PNB TYPICAL)
10 1
20 2
10 6
10 2
1G 00
1G 02
1G 00
G1 19
2
1R 00
1R 00
00 0/
47
28
04
14
28
00
5
61 10
2
89 90
51 G1
61 G2
94 14
01 R1
41 R1
42
47
71
10
B1
T8 611R
W PC8
Y5 594G
R1
T8 8511
T8 8611
T8 8011
A1
T8 8411
Existing
94
41
T8
T
Y
T
T
Y5
Function Terminals T8
Common D X X X X C C C C C C
Power R R R R R R R R R R
or or
Compressor Y1 Y Y Y Y1 Y1 Y Y Y1 Y Y1 Y1/W1
F F F F F F F
1st Stage W1 – W1 W1 W1 W1 W1 W1 W1 –
Heat
C 2
Aux. Heat W2 W2 W2 W2 W2 W2 W2 W2 W2 Aux.
Fan G G G G G G G G G G
1 1 1
or or
C/O Valve B B B B B B B O/B B B O/B O/B
Heat
1 1 1
or or
C/O Valve O O O O O O O O/B O O O/B O/B
Cool
I J J I J I I
System L L L L L L L L
Monitor
Em. Heat E E E E E E E E E E
Multiple Aux.
Heat Loads C W3 W3 W3 W3 E E E E E E
H G G G
LED Indication – – X2 X1 X2 X1 X2 – – – X1 X2 –
2
2nd Stage – – – – – – – – – W2
Compressor
2nd Stage – – – – – – – – – Y2
Cool
A Configure O/B (select models) in Installer Setup. F Do not remove factory-installed jumper.
B When W2 is not used, configure W2 cycle rate to NC. G Optional LED indication with completed circuit on X1 and X2 terminals.
C Terminal is for multiple auxiliary heat loads such as contactors, sequencers, H Field-installed X2 to X (C) jumper.
or relays. I LED is energized when terminal is powered.
D Terminal must be connected to the transformer common. J L terminal is powered continuously when thermostat is in Em. Ht. position.
E If multiple auxiliary heat loads are used, connect to W2 (Aux W8900B) M13198
terminal.
70-6627 • 90
RHEEM/RUUD
PCB, PFA, PGB, PGA HEATING CHANGEOVER (AFTER 11/85) RPCB, RPFA
10 1
20 2
10 0
10 6
10 2
G1 19
1G 02
1G 00
1G 00
2
1R 00
1R 00
00 0/
47
04
28
14
28
00
6
5
8
94 14
89 90
51 G1
61 G2
61 R1
01 R1
41 R1
47
42
30
B1
Y5 594G
W PC8
R1
T8 8611
T8 8511
T8 8611
T8 8011
A1
T8 8411
Existing
94
41
T
T
T
Y5
Function
T8
Terminals
Common D X X X X C C C C C C
Power R R R R R R R R R R
or
Compressor Y Y Y1 Y1 Y1 Y Y Y1 Y Y1 Y1/W1
E E E E E E E
1st Stage – – W1 W1 W1 W1 W1 W1 W1 –
Heat
B
Aux. Heat W2 W2 W2 W2 W2 W2 W2 W2 W2 Aux.
J J
Fan G G G G G G G G G G
A A A
or or
C/O Valve B B B B B B B O/B B B O/B O/B
Heat
A A A
or or
C/O Valve O O O – O O O O/B O O O/B O/B
Cool
I I I J J I J I I
System L L L X1 L L L L L L
Monitor
Em. Heat E E E E E E E E E E
Multiple Aux. – H W3 W3 H H H H H H
Heat Loads C
LED Indication G G F
– – X2 X2 X1 X2 – – – X1 X2 –
B
2nd Stage – – – – – – – – – W2
Compressor
2nd Stage – – – – – – – – – Y2
Cool
A Configure O/B (select models) in Installer Setup. F Optional Check LED on T8611G1004. See Fig. 26.
B When W2 is not used, configure W2 cycle rate to NC. G Field-installed X2 to X (C) jumper.
C Terminal is for multiple auxiliary heat loads such as contactors, sequencers, H If multiple auxiliary heat loads are used, connect to W2 (Aux W8900B)
or relays. terminal.
D Terminal must be connected to the transformer common. I LED is energized when terminal is powered.
E Do not remove factory-installed jumper. J L terminal is powered continuously when thermostat is in Em. Ht. position.
M13206
70-6627 • 91
SECO
TA2000, TA2040, TA2010 TA2050
10 1
20 2
10 6
10 2
1G 00
1G 02
1G 00
G1 19
2
1R 00
1R 00
00 0/
47
28
04
14
28
00
5
61 10
2
89 90
51 G1
61 G2
94 14
01 R1
41 R1
42
47
71
10
B1
T8 611R
W PC8
Y5 594G
R1
T8 8511
T8 8611
T8 8011
A1
T8 8411
Existing
94
41
T8
T
T
Y
T
Y5
Function
T8
Terminals
Common D X X X X C C C C C C
Power R R R R R R R R R R
or
Compressor Y Y Y Y1 Y1 Y Y Y1 Y Y1 Y1/W1
F F F F F F F
1st Stage – – W1 W1 W1 W1 W1 W1 W1 –
Heat
B
Aux. Heat W2 W W W W2 W2 W2 W2 W2 Aux.
Fan G G G G G G G G G G
A A A
or or
C/O Valve B B B B B B B O/B B B O/B O/B
Heat
A A A
or or
C/O Valve O O O O O O O O/B O O O/B O/B
Cool
J I K K I K I I
System Monitor/ L L L L L L L L
System Defrost
J F F F
Em. Heat E E E E E E E E E E
Multiple Aux. W3 W3 W3 W3 E E E E E E
Heat Lads C
G G G
LED Indication – – X2 H X1 X2 X1 X2 – – – X1 X2 –
B
2nd Stage – – – – – – – – – W2
Compressor
2nd Stage – – – – – – – – – Y2
Cool
A Configure O/B (select models) in Installer Setup. F Do not remove factory-installed jumper.
B When W2 is not used, configure W2 cycle rate to NC. G Optional LED indication with completed circuit on X1 and X2 terminals.
C Terminal is for multiple auxiliary heat loads such as contactors, sequencers, H Field-installed X2 to X (C) jumper.
or relays. I LED is energized when terminal is powered.
D Terminal must be connected to the transformer common. J E and L terminals are not available on TA2010 or TA2050.
E If multiple auxiliary heat loads are used, connect to W2 (Aux W8900B) K L terminal is powered continuously when thermostat is in Em. Ht. position.
terminal. M13171
70-6627 • 92
SECO
TA2060
10 1
20 2
10 6
10 2
1G 00
1G 02
1G 00
2
1R 00
1R 00
00 0/
47
28
04
14
28
00
61
3
61 10
5
89 90
51 G1
61 G2
01 R1
41 R1
76
55
10
B1
1
T8 611R
W PC8
G1
T8 8511
T8 8611
T8 8011
R1
A1
T8 8411
Existing
94
94
41
T8
T
T
T
Function
Y5
Y5
T8
Terminals
Common A X B B B C C C C C C
Power R R R R R R R R R R
or
Compressor Y Y Y Y Y1 Y Y Y1 Y Y1 Y1/W1
C C C C C
1st Stage – – – – W1 W1 W1 W1 W1 –
Heat
G
Aux. Heat W2 W W W W2 W2 W2 W2 W2 Aux.
Fan G G G G G G G G G G
E E E
or or
C/O Valve – – – – B B B O/B B B O/B O/B
Heat
E E E
or or
C/O Valve O O O O O O O O/B O O O/B O/B
Cool
H H H I I H I H H
System Monitor/ L F F F L L L L L L
System Defrost
F F F
Outdoor W3 T T T B B B B B B
Thermistor/
Sensor
Em. Heat E X2 X2 X2 E E E E E E
D 4
LED Indication – – – – X1 X2 – – – X1 X2 –
G
2nd Stage – – – – – – – – – W2
Compressor
2nd Stage – – – – – – – – – Y2
Cool
A Terminal must be connected to the transformer common. E Configure O/B (select models) in Installer Setup.
B Tape off. Thermostat replaces outdoor reset with improved zero droop F Replace existing thermistor with Honeywell C815A1005.
performance. G When W2 is not used, configure W2 cycle rate to NC.
C Do not remove factory-installed jumper. H LED is energized when terminal is powered.
D Optional LED indication with completed circuit on X1 and X2 terminals. I L terminal is powered continuously when thermostat is in Em. Ht. position.
M13199
70-6627 • 93
SUN MANUFACTURING
10 1
20 2
10 6
10 2
1G 00
G1 19
1G 02
1G 00
2
1R 00
1R 00
00 0/
47
28
04
14
28
00
5
61 10
2
94 14
89 90
51 G1
61 G2
01 R1
42
41 R1
47
71
10
B1
T8 611R
Y5 594G
W PC8
R1
T8 8511
T8 8611
T8 8011
A1
T8 8411
Existing
94
41
T8
Y
T
T
Y5
T
Function Terminals T8
Common C X X X X C C C C C C
Power R R R R R R R R R R
or
Compressor Y Y Y Y1 Y1 Y Y Y1 Y Y1 Y1/W1
E E E E E E E
1st Stage – – W1 W1 W1 W1 W1 W1 W1 –
Heat
B
Aux. Heat W1 W2 W2 W2 W2 W2 W2 W2 W2 Aux.
Fan G G G G G G G G G G
A A A
or or
C/O Valve B B B B B B B O/B B B O/B O/B
Heat
A A A
or or
C/O Valve O O O O O O O O/B O O O/B O/B
Cool
I I J J I J I I
System Monitor/ L L X1 L L L L L L
System Defrost
Em. Heat E E E E E E E E E E
F F F
Multiple Aux. W3 W3 W3 W3 H H H H H H
Heat Loads D
F
LED Indication – – X2 G X2 G X1 X2 – – – X1 X2 –
B
2nd Stage – – – – – – – – – W2
Compressor
2nd Stage – – – – – – – – – Y2
Cool
A Configure O/B (select models) in Installer Setup. F Optional LED indication with completed circuit on X1 and X2 terminals.
B When W2 is not used, configure W2 cycle rate to NC. G Field-installed X2 to X (C) jumper.
C Terminal must be connected to the transformer common. H If multiple auxiliary heat loads are used, connect to W2 (Aux W8900B)
D Terminal is for multiple auxiliary heat loads such as contactors, sequencers, terminal.
or relays. I LED is energized when terminal is powered.
E Do not remove factory-installed jumper. J L terminal is powered continuously when thermostat is in Em. Ht. position.
M13200
TYPICAL THERMOSTATS AND SUBBASES — HONEYWELL MODEL NUMBER (CUSTOMER PART NUMBER)
T841A1399 (HPL1404)
70-6627 • 94
SQUARE D/SUN DIAL
10 1
20 2
10 6
10 2
10 /
1G 00
1G 02
G1 19
1G 00
2
1R 00
1R 00
00 0/
47
28
04
14
28
00
5
6
2
89 90
61 10
51 G1
94 14
61 G2
01 R1
41 R1
42
47
71
B1
W PC8
T8 611R
Y5 594G
R1
T8 8511
T8 8611
T8 8011
A1
T8 8411
Existing
94
41
T8
T
Y
T
T
T
Y5
Function
T8
Terminals
or
Common D C X X X X C C C C C C
Power R R R R R R R R R R
or
Compressor Y Y Y Y1 Y1 Y Y Y1 Y Y1 Y1/W1
F F F F F F F
1st Stage – – W1 W1 W1 W1 W1 W1 W1 –
Heat
B
Aux. Heat W2 W2 W2 W2 W2 W2 W2 W2 W2 Aux.
Fan G G G G G G G G G G
A A A
or or
C/O Valve B B B B B B B O/B B B O/B O/B
Heat
A A A
or or
C/O Valve O O O O O O O O/B O O O/B O/B
Cool
8 G G 8 G 8 8
System Monitor/ L L L L L L L L
System Defrost
or
Em. Heat K E E E E E E E E E E
Multiple Aux. W3 W3 W3 W3 E E E E E E
Heat Loads C
LED Indication – – X2 X1 X2 X1 X2 – – – X1 X2 –
B
2nd Stage – – – – – – – – – W2
Compressor
2nd Stage – – – – – – – – – Y2
Cool
A Configure O/B (select models) in Installer Setup. E If multiple auxiliary heat loads are used, connect to W2 (Aux W8900B)
B When W2 is not used, configure W2 cycle rate to NC. terminal.
C Terminal is for multiple auxiliary heat loads such as contactors, sequencers, F Do not remove factory-installed jumper.
or relays. G L terminal is powered continuously when thermostat is in Em. Ht. position.
D Terminal must be connected to the transformer common. 8 LED is energized when terminal is powered. M13201
TYPICAL THERMOSTATS AND SUBBASES — HONEYWELL MODEL NUMBER (CUSTOMER PART NUMBER)
T841A1357
T841A1365 (121000012)
70-6627 • 95
SQUARE D/SUN DIAL
10 1
20 2
10 6
10 2
E
F1 8/
1G 02
1G 00
2
1R 00
00
1R 00
00 0/
47
28
14
28
BL
BL
00
74 101
2
AI T
89 90
51 G1
AI T
61 G2
01 R1
10
41 R1
02
AV NO
B1
AV NO
LA
LA
W PC8
1R
Q6 74C
T8 8511
T8 8611
T8 8011
T8 8411
Existing
61
T8
T
T
T8
T
Function Terminals
or or
Common B X X1 C X1 C C C C C C
Power R R R R R R R R
or or C
Compressor Y Y1 Y1 Y1 Y Y Y1 Y Y1 Y1/W1
A A A A A A
1st Stage W1 W1 W1 W1 W1 W1 W1 –
Heat
NOT AVAILABLE
E
NOT AVAILABLE
Fan G G G G G G G G
or or
C/O Valve B B B B B O/B B B O/B O/B
Heat
or or
C/O Valve O O O O O O/B O O O/B O/B
Cool
F G G F G F F
System Monitor/ L X2 L L L L L L
System Defrost
or
Em. Heat K E E E E E E E E
D
LED Indication X2 X2 X1 X2 –
E
2nd Stage – – – – – – – W2
Compressor
2nd Stage Y2 Y2 Y2
Cool
A Remove factory-installed Y1 (Y) to W1 jumper. E When W2 is not used, configure W2 cycle rate to NC.
B Terminal must be connected to the transformer common. F LED is energized when terminal is powered.
C If separate Y1 and W1 terminals are required, install R8222D1014; see page 12. G L terminal is powered continuously when thermostat is in Em. Ht. position.
D Optional LED indication activated with completed circuit on X1 and
M13202
X2 terminals.
TYPICAL THERMOSTATS AND SUBBASES — HONEYWELL MODEL NUMBER (CUSTOMER PART NUMBER)
T872C1525/Q672F1182 (HCD-2/HCB-1)
T874C1224/Q674F1071 (63600-002-09/63600-002-11)
70-6627 • 96
TRANE/AMERICAN STANDARD
DIRECT TRADE REPLACEMENTS
10 2
10 1
20 2
10 0
10 6
1R 00
1G 02
1G 00
1G 00
2
1R 00
00 0/
28
47
04
28
14
00
61
3
5
89 90
41 R1
51 G1
61 G2
61 R1
01 R1
76
55
B1
1
W PC8
T8 8411
G1
T8 8611
T8 8511
T8 8611
T8 8011
R1
A1
Existing
94
94
41
T
T
T
T
Function
Y5
Y5
T8
Terminals
Common A B B B B C C C C C C
Power R R R R R R R R R R
or
Compressor Y Y Y Y Y1 Y Y Y1 Y Y1 Y1/W1
C C C C C
1st Stage – – – – W1 W1 W1 W1 W1 –
Heat
F
Aux. Heat W or W1 W W W W2 W2 W2 W2 W2 Aux.
Fan G G G G G G G G G G
E E E
or or
C/O Valve – – – – B B B O/B B B O/B O/B
Heat
E E E
or or
C/O Valve O O O O O O O O/B O O O/B O/B
Cool
G G G H H G H G G
System Monitor/ F F F F L L L L L L
System Defrost
or
Outdoor T A T T T B B B B B B
Sensor C
Outdoor Stat X2 X2 X2 X2 E E E E E E
D D
LED Indication – – – – X1 X2 – – – X1 X2 –
F
2nd Stage – – – – – – – – – W2
Compressor
2nd Stage – – – – – – – – – Y2
Cool
A Terminal must be connected to the transformer common. E Configure O/B (select models) in Installer Setup.
B Tape off. Thermostat replaces outdoor reset with improved zero droop F When W2 is not used, configure W2 cycle rate to NC.
performance. G LED is energized when terminal is powered.
C Do not remove factory-installed jumper. H L terminal is powered continuously when thermostat is in Em. Ht. position.
D Optional LED indication with completed circuit on X1 and X2 terminals. M13225
TYPICAL THERMOSTATS AND SUBBASES — HONEYWELL MODEL NUMBER (CUSTOMER PART NUMBER)
T841A1407 (ASYSTAT652) T874R1939 (ASYSTAT-651A)/Q674L1801 (THT1225)
T841A1530 (ASYSTAT652A) T8141A1014
T872G1059/Q672J1039 T8141A1071
T872R1057/Q672L1037 T8300A1128/Q6300A1101 (BAY28X194/BAY28X195)
T874G1204/Q674J1043 T8611G1038 (THT-0603)
T874G1675/Q674J1142 (ASYSTAT650/WY28X0250) T8611G1111 (TAYSTAT501)
T874R1053/Q674L1140 T8611R1091
T874R1426/Q674L1496 (BAYSTAT339/WY28X0112) T8611R1109 (THT-0602)
T874R1657/Q674L1611 (ASYSTAT651/WY28X235) T8611R1117 (ASYSTAT700)
70-6627 • 97
TRANE/AMERICAN STANDARD
10 2
10 1
20 2
10 0
10 6
1R 00
1G 02
1G 00
1G 00
2
1R 00
00 0/
28
47
04
28
14
00
1
3
5
89 90
41 R1
51 G1
61 G2
61 R1
01 R1
16
76
55
B1
W PC8
T8 8411
G1
T8 8611
T8 8511
T8 8611
T8 8011
R1
A1
Existing
94
94
41
T
T
T
T
Function
Y5
Y5
Terminals T8
Common A C B B B C C C C C C
Power R R R R R R R R R R
or or
Compressor Y Y1 Y Y Y Y1 Y Y Y1 Y Y1 Y1/W1
C C C C C
1st Stage W1 – – – W1 W1 W1 W1 W1 –
Heat
F
Aux. Heat W2 W W W W2 W2 W2 W2 W2 Aux.
Fan G G G G G G G G G G
E E E
or or
C/O Valve B – – – B B B O/B B B O/B O/B
Heat
E E E
or or
C/O Valve O O O O O O O O/B O O O/B O/B
Cool
G G G H H G H G G
System Monitor/ L F F F L L L L L L
System Defrost
Outdoor Stat E X2 X2 X2 E E E E E E
B
or D
LED Indication X1 X2 – – – X1 X2 – – – X1 X2 –
F
2nd Stage – – – – – – – – – W2
Compressor
2nd Stage – – – – – – – – – Y2
Cool
A Terminal must be connected to the transformer common. E Configure O/B (select models) in Installer Setup.
B Optional LED indication activated with completed circuit on X1 and F When W2 is not used, configure W2 cycle rate to NC.
X2 terminals. G LED is energized when terminal is powered.
C Do not remove factory-installed jumper. H L terminal is powered continuously when thermostat is in Em. Ht. position.
D Optional LED on T8611G1004. See Fig. 26. M13226
70-6627 • 98
TRANE/AMERICAN STANDARD
10 2
10 1
20 2
10 0
10 6
1R 00
1G 02
1G 00
1G 00
G1 19
2
1R 00
00 0/
28
47
04
28
14
00
5
6
2
89 90
41 R1
51 G1
61 G2
61 R1
94 14
01 R1
42
47
71
B1
W PC8
Y5 594G
R1
T8 8411
T8 8611
T8 8511
T8 8611
T8 8011
A1
Existing
94
41
T
T
T
T
Y
Y5
Function
T8
Terminals
Common B B X X X C C C C C C
Power R R R R R R R R R R
or
Compressor Y Y Y Y1 Y1 Y Y Y1 Y Y1 Y1/W1
E E E E E E E
1st Stage – – W1 W1 W1 W1 W1 W1 W1 –
Heat
L
Aux. Heat W or X1 W2 W2 W2 W2 W2 W2 W2 W2 Aux.
Fan G G G G G G G G G G
D D D
or or
C/O Valve – B B B B B B O/B B B O/B O/B
Heat
D D D
or or
C/O Valve O O O O O O O O/B O O O/B O/B
Cool
H H I I H I H H
System Monitor/ F L X1 L L L L L L
System Defrost
or
Outdoor T H A A A C C C C C C
Sensor
Outdoor Stat X2 E E E E E E E E E
Multiple Aux. – W3 W3 W3 J J J J J J
Heat Loads K
LED Indication – – X2 G X2 G X1 X2 F – – – X1 X2 –
L
2nd Stage – – – – – – – – – W2
Compressor
2nd Stage – – – – – – – – – Y2
Cool
A Tape off. Outdoor reset not provided with Tradeline replacement thermostat. H LED is energized when terminal is powered.
B Terminal must be connected to the transformer common. I L terminal is powered continuously when thermostat is in Em. Ht. position.
C Tape off. Thermostat replaces outdoor reset with improved zero droop J If multiple auxiliary heat loads are used, connect to W2 (Aux W8900B)
performance. terminal.
4 Configure O/B (select models) in Installer Setup. K Terminal is for multiple auxiliary heat loads such as contactors, sequencers,
E Do not remove factory-installed jumper. or relays.
F Optional Check LED on T8611G1004. See Fig. 26. L When W2 is not used, configure W2 cycle rate to NC.
G Field-installed X2 to X (C) jumper. M13227
70-6627 • 99
TRANE/AMERICAN STANDARD
10 2
10 1
20 2
10 0
10 6
1R 00
1G 02
1G 00
1G 00
G1 19
2
1R 00
00 0/
28
47
04
28
14
00
5
6
2
89 90
41 R1
51 G1
61 G2
61 R1
94 14
01 R1
42
47
71
B1
W PC8
Y5 594G
R1
T8 8411
T8 8611
T8 8511
T8 8611
T8 8011
A1
Existing
94
41
T
T
T
T
Y
Y5
Function Terminals T8
Common B C X X X C C C C C C
Power R R R R R R R R R R
or or
Compressor Y Y1 Y Y Y1 Y1 Y Y Y1 Y Y1 Y1/W1
E E E E E E E
1st Stage W1 – W1 W1 W1 W1 W1 W1 W1 –
Heat
A
Aux. Heat W2 W2 W2 W2 W2 W2 W2 W2 W2 Aux.
Fan G G G G G G G G G G
K K K
or or
C/O Valve B B B B B B B O/B B B O/B O/B
Heat
K K K
or or
C/O Valve O O O O O O O O/B O O O/B O/B
Cool
H I I H I H H
System Monitor/ L L L L L L L L
System Defrost
Outdoor Stat E E E E E E E E E E
Multiple Aux. – W3 W3 W3 J J J J J J
Heat Loads D
C
or
LED Indication X1 X2 – X2 G X1 X2 C X1 X2 F – – – X1 X2 –
A
2nd Stage – – – – – – – – – W2
Compressor
2nd Stage – – – – – – – – – Y2
Cool
A When W2 is not used, configure W2 cycle rate to NC. F Optional Check LED on T8611G1004. See Fig. 26.
B Terminal must be connected to the transformer common. G Field-installed X2 to X (C) jumper.
C Optional LED indication activated with completed circuit on X1 and H LED is energized when terminal is powered.
X2 terminals. I L terminal is powered continuously when thermostat is in Em. Ht. position.
D Terminal is for multiple auxiliary heat loads such as contactors, sequencers, J If multiple auxiliary heat loads are used, connect to W2 (Aux W8900B)
or relays. terminal.
E Do not remove factory-installed jumper. K Configure O/B (select models) in Installer Setup.
M13228
TYPICAL THERMOSTATS AND SUBBASES — HONEYWELL MODEL NUMBER (CUSTOMER PART NUMBER)
T841A1407 (ASYSTAT652) T874R1053/Q674L1140 T8611G1038 (THT-0603)
T841A1530 (ASYSTAT652A) T874R1426/Q674L1496 (BAYSTAT339/WY28X0112) T8611G111 (TAYSTAT501)
T872G1059/Q672J1039 T874R1657/Q674L1611 (ASYSTAT651/WY28X235) T8611R1091
T872R1057/Q672L1037 T874R1939 (ASYSTAT-651A)/Q674L1801 (THT1225) T8611R1109 (THT-0602)
T874G1204/Q674J1043 T8141A1014 T8611R1117 (ASYSTAT700)
T874G1675/Q674J1142 T8141A1071
(ASYSTAT650/WY28X0250) T8300A1128/Q6300A1101 (BAY28X194/BAY28X195)
70-6627 • 100
WEATHERKING
10 1
20 2
10 6
10 2
1G 02
1G 00
2
1R 00
00
1R 00
00 0/
47
28
14
28
00
7
33
8
89 90
51 G1
61 G2
01 R1
10
41 R1
79
30
B1
6
W PC8
1R
R1
G1
T8 8511
T8 8611
T8 8011
A1
T8 8411
Existing
61
94
94
41
T
T
T8
T
Y5
Function
Y5
T8
Terminals
Common A X X X X C C C C C C
Power R R R R R R R R R R
Compressor Y Y Y Y Y1 Y Y1 Y Y1 Y1/W1
C C C C C
1st Stage – – – – W1 W1 W1 W1 W1 –
Heat
E
Aux. Heat W2 W2 W2 W2 W2 W2 W2 W2 W2 Aux.
D 4 4 4 4 4
Fan G G G G G G G G G G
B B B
or or
C/O Valve B B B B B B B O/B B B O/B O/B
Heat
B B B
or or
C/O Valve O O O O O O O O/B O O O/B O/B
Cool
F F F G G F G F F
System Monitor/ L L L L L L L L L L
System Defrost
Em. Heat E E E E E E E E E E
LED Indication X – X2 X2 X1 X2 – – – X1 X2 –
E
2nd Stage – – – – – – – – – W2
Compressor
2nd Stage – – – Y2 – – – – – Y2
Cool
A Terminal must be connected to the transformer common. E When W2 is not used, configure W2 cycle rate to NC.
B Configure O/B (select models) in Installer Setup. F LED is energized when terminal is powered.
C Do not remove factory-installed jumper. G L terminal is powered continuously when thermostat is in Em. Ht. position.
D To eliminate automatic fan in emergency heat mode, connect switching relay M13205
as shown on page 9.
TYPICAL THERMOSTATS AND SUBBASES — HONEYWELL MODEL NUMBER (CUSTOMER PART NUMBER)
T841A1456 (41-20796-65)
T874R1830/Q674L1504 (41-20769-64)
70-6627 • 101
WEATHERKING
TYPICAL WPH SERIES
10 1
20 2
10 0
10 6
10 2
1G 02
1G 00
1G 00
G1 19
2
1R 00
1R 00
00 0/
47
04
28
14
28
00
5
6
2
89 90
51 G1
61 G2
61 R1
94 14
01 R1
41 R1
42
47
71
B1
W PC8
Y5 594G
R1
T8 8611
T8 8511
T8 8611
T8 8011
A1
T8 8411
Existing
94
41
T
T
Y
T
Y5
Function Terminals T8
or or
Common 6 X C1 C X X X C C C C C C
Power R R R R R R R R R R
or or
Compressor Y W1 Y Y Y1 Y1 Y Y Y1 Y Y1 Y1/W1
G G G G G G G
1st Stage – – W1 W1 W1 W1 W1 W1 W1 –
Heat
or B
Aux. Heat W2 E W2 W2 W2 W2 W2 W2 W2 W2 Aux.
J J
Fan G G G G G G G G G G
A A A
or or
C/O Valve B B B B B B B O/B B B O/B O/B
Heat
A A A
or or or
C/O Valve O Y1 O O O O O O O/B O O O/B O/B
Cool
or D D E E D E D D
System Monitor/ L X L X1 L L L L L L
System Defrost
Em. Heat E E E E E E E E E E
Multiple Aux. W3 W3 W3 W3 J J J J J J
Heat Loads C
I
LED Indication – K X2 X2 I X1 X2 H – – – X1 X2 –
B
2nd Stage – – – – – – – – – W2
Compressor
2nd Stage – – – – – – – – – Y2
Cool
A Configure O/B (select models) in Installer Setup. G Do not remove factory-installed jumper.
B When W2 is not used, configure W2 cycle rate to NC. H Optional Check LED on T8611G1004. See Fig. 26.
C Terminal is for multiple auxiliary heat loads such as contactors, sequencers, I Field-installed X2 to X (C) jumper.
or relays. J If multiple auxiliary heat loads are used, connect to W2 (Aux W8900B)
D LED is energized when terminal is powered. terminal.
E L terminal is powered continuously when thermostat is in Em. Ht. position.
F Terminal must be connected to the transformer common. M13209
TYPICAL THERMOSTATS AND SUBBASES — HONEYWELL MODEL NUMBER OR CUSTOMER PART NUMBER
T841A1373 T8141A1105 GE 3AAT80
70-6627 • 102
WESCO/ADDISON
Models: WPH022, 028, 032, 036, 044, 054, 064. WRH022, 028, 032, 036, 044, 054, 064. WSH028, 032, 036, 042. DWPG024, 030, 036, 042,
048, 054, 060, 066. HWPG012, 017, 020, 024, 030, 036, 042, 048, 054, 060, 066. VWPG017, 020, 024, 030, 036, 042, 048, 054, 060, 066.
10 2
10 1
20 2
10 6
10 0
1R 00
1G 02
G1 19
1G 00
2
1R 00
1G 00
00 0/
28
47
28
14
04
00
5
6
2
89 90
41 R1
51 G1
94 14
61 G2
01 R1
42
61 R1
47
71
B1
W PC8
Y5 594G
R1
T8 8411
T8 8511
T8 8611
T8 8011
A1
T8 8611
Existing
94
41
T
Y
T
T
Y5
T
Function Terminals
T8
or
Common E C1 C X X X C C C C C C
Power R R R R R R R R R R
or or
Compressor W1 Y Y Y Y1 Y1 Y Y Y1 Y Y1 Y1/W1
F F F F F F F
1st Stage – – W1 W1 W1 W1 W1 W1 W1 –
Heat
or or B
Auxiliary W1 W2 W2 W2 W2 W2 W2 W2 W2 W2 W2 Aux.
Heat
Fan G G G G G G G G G G
A A A
or or
C/O Valve – B B B B B B O/B B B O/B O/B
Heat
A A A
or or or
C/O Valve Y1 O O O O O O O O/B O O O/B O/B
Cool
D G G D G D D
System Monitor/ X L L L L L L L
System Defrost
EM. Heat E E E E E E E E E E
Multiple Aux. – W3 W3 W3 – – – – – –
Heat Loads C
LED Indication – – X2 X1 X2 X1 X2 – – – X1 X2 –
B
2nd Stage – – – – – – – – – W2
Compressor
2nd Stage – – – – – – – – – Y2
Cool
A Configure O/B (select models) in Installer Setup. D LED is energized when terminal is powered.
B When W2 is not used, configure W2 cycle rate to NC. E Terminal must be connected to the transformer common.
C Terminal is for multiple auxiliary heat loads such as contactors, sequencers, F Do not remove factory-installed jumper.
or relays. G L terminal is powered continuously in Em. Ht. position.
M13222
TYPICAL THERMOSTATS AND SUBBASES — HONEYWELL MODEL NUMBER (CUSTOMER PART NUMBER)
T872G1265/Q672F1265 T874G1287/Q6741253
T872G1281/Q672F1265 T874G1543/Q674F1345 (403-197)
T872R1016/Q672B1103 T874R1012/Q674B1109
T874C1315
70-6627 • 103
WESTINGHOUSE
TYPICAL HSO
10 1
20 2
10 0
10 6
10 2
G1 19
1G 02
1G 00
1G 00
2
1R 00
1R 00
00 0/
47
04
28
14
28
00
5
6
2
94 14
89 90
51 G1
61 G2
61 R1
01 R1
42
41 R1
47
71
B1
Y5 594G
W PC8
R1
T8 8611
T8 8511
T8 8611
T8 8011
A1
T8 8411
Existing
94
41
T
T
Y5
T
Function Terminals T8
Common E X X X X C C C C C C
Power R R R R R R R R R R
or
Compressor Y Y Y Y1 Y1 Y Y Y1 Y Y1 Y1/W1
F F F F F F F
1st Stage – – W1 W1 W1 W1 W1 W1 W1 –
Heat
B
Aux. Heat W W2 W2 W2 W2 W2 W2 W2 W2 Aux.
Fan G G G G G G G G G G
A A A
or or
C/O Valve B B B B B B B O/B B B O/B O/B
Heat
A A A
or or
C/O Valve O O O O O O O O/B O O O/B O/B
Cool
or D D J J D J D D
System Monitor/ L L1 L X1 L L L L L L
System Defrost
Em. Heat E E E E E E E E E E
Multiple Aux. W3 – W3 W3 I I I I I I
Heat Loads C
H
LED Indication – – X2 X2 H X1 X2 G – – – X1 X2 –
B
2nd Stage – – – – – – – – – W2
Compressor
2nd Stage – – – – – – – – – Y2
Cool
A Configure O/B (select models) in Installer Setup. F Do not remove factory-installed jumper.
B When W2 is not used, configure W2 cycle rate to NC. G Optional Check LED on T8611G1004. See Fig. 26.
C Terminal is for multiple auxiliary heat loads such as contactors, sequencers, H Field-installed X2 to X (C) jumper.
or relays. I If multiple auxiliary heat loads are used, connect to W2 (Aux W8900B)
D LED is energized when terminal is powered. terminal.
E Terminal must be connected to the transformer common. J L terminal is powered continuously when thermostat is in Em. Ht. position.
M13210
70-6627 • 104
WESTINGHOUSE
TYPICAL HB, HI RELI, HLO
10 1
20 2
10 6
10 2
E
G1 19
1G 02
1G 00
2
1R 00
1R 00
00 0/
47
00
28
14
28
BL
00
5
6
AI T
94 14
89 90
51 G1
61 G2
01 R1
42
41 R1
47
10
AV NO
B1
LA
Y5 594G
W PC8
R1
T8 8511
1R
T8 8611
T8 8011
T8 8411
Existing
94
61
Y
T
T
Y5
T
Function
T8
Terminals
Common 2 X X X C C C C C C
Power R R R R R R R R R
1st Stage W1 W1 W1 W1 W1 W1 W1 W1
Heat
G
2nd Stage W2 W2 W2 W2 W2 W2 W2 W2 Aux.
Heat
NOT AVAILABLE
Fan G G G G G G G G G
A A A A A A A
F
1st Stage Y Y Y1 Y1 Y Y1 Y Y1 Y1/W1
Cool
2nd Stage – – – – – – – – Y2
Cool
or or
C/O Valve – B B B B B O/B B B O/B O/B
Heat
or or
C/O Valve – O O O O O O/B O O O/B O/B
Cool
System Monitor/ – L X1 L L L L L L
System Defrost
Em. Heat E E E E E E E E E
Multiple Aux. – W3 W3 D D D D D D
Heat Loads C
LED Indication – X2 E X2 E – – – – X1 X2 –
G
2nd Stage – – – – – – – – W2
Compressor
70-6627 • 105
WESTINGHOUSE
TYPICAL HE SERIES
10 1
20 2
10 0
10 6
10 2
1G 02
1G 00
1G 00
G1 19
2
1R 00
1R 00
00 0/
47
04
28
14
28
00
5
6
2
89 90
51 G1
61 G2
61 R1
94 14
01 R1
41 R1
42
47
71
B1
W PC8
Y5 594G
R1
T8 8611
T8 8511
T8 8611
T8 8011
A1
T8 8411
Existing
94
41
T
T
Y
T
Y5
Function Terminals T8
Common E 2 X X X C C C C C C
Power V R R R R R R R R R
or
Compressor C Y Y Y1 Y1 Y Y Y1 Y Y1 Y1/W1
F F F F F F F
1st Stage – – W1 W1 W1 W1 W1 W1 W1 –
Heat
H
Aux. Heat H2 W2 W2 W2 W2 W2 W2 W2 W2 Aux.
Fan F G G G G G G G G G
A A A
or or
C/O Valve Z B B B B B B O/B B B O/B O/B
Heat
A A A
or or
C/O Valve – O O O O O O O/B O O O/B O/B
Cool
System Monitor/ – – L – L L L L L L
System Defrost
D D D D D D D D D
Em. Heat – E E E E E E E E E
Multiple Aux. – W3 W3 W3 G G G G G G
Heat Loads C
LED Indication – – X2 X1 X2 X1 X2 – – – X1 X2 –
H
2nd Stage – – – – – – – – – W2
Compressor
2nd Stage – – – – – – – – – Y2
Cool
A Configure O/B (select models) in Installer Setup. E Terminal must be connected to the transformer common.
B Use common from secondary side of system trransformer. F Do not remove factory-installed jumper.
C Terminal is for multiple auxiliary heat loads such as contactors, sequencers, G If multiple auxiliary heat loads are used, connect to W2 (Aux W8900B)
or relays. terminal.
D Field-installed E to W2 (Aux W8900B) jumper required. H When W2 is not used, configure W2 cycle rate to NC. M13212
70-6627 • 106
WESTINGHOUSE
TYPICAL 2-SPEED PUMP
20 7
1M 01
02
2
25
08
F 5
00 0/
00
74 116
61 M2
A 1022
10
89 90
70
B1
1M
W PC8
1M
T8 8611
Q6 84D
Existing
51
61
T
T
Function Terminals
T8
T8
Common D X X1 C C C C
Power R R R R R R
Compressor Stage 2 Y2 Y2 Y2 Y2 Y2 Y2
F F F
2nd Stage Heat – W2 W2 – – W2
Fan G G G G G G
G G G
C/O Valve O O O O/B O/B O/B
Cool
G G G
C/O Valve B C B O/B O/B O/B
Heat
H I H I H
System Monitor/ L X2 L L L L
System Defrost
Em. Heat W E E E E E
E E
LED Indication – – X1 X2 – X1 X2 –
A When subbase system switch is in AUTO position, equipment will E Optional LED indication activated with completed circuit on X1 and
operate in COOL mode only. X2 terminals.
B IMPORTANT: Do not use T874D/Q674F1022 if B terminal is used on F Y2 to W2 jumper required.
original equipment. G Configure O/B (Select Models) in Installer Setup.
C Y1 to W1 jumper required. H LED is energized when terminal is powered.
D Terminal must be connected to the transformer common. I L terminal is powered continuously when thermostat is in Em. Ht. position.
M13242
70-6627 • 107
WHITE RODGERS
TYPICAL 1F92-1, 1F92-6, 1F92-7, 1F58-910 THERMOSTAT, S28 SUBBASES
20 7
61 10 0
1M 04
1M 01
02
T8 611G 100
2
G1 19
00 0/
08
25
00
5
2
89 90
61 M2
10
94 14
42
70
71
47
T8 611R
B1
W PC8
1M
Y5 594G
R1
A1
T8 8611
Existing
51
94
41
T8
Y
T
T8
Y5
Function
T8
Terminals
or
Common E X1 C X X X C C C C
Power R R R R R R R R
or or
Compressor Y Y1 Y Y Y1 Y Y1 Y1 Y1 Y1/W1
B B B
1st Stage W1 – W1 W1 W1 – – –
Heat
K
Aux. Heat W2 W2 W2 W2 W2 F F W2
C K
3rd Stage W3 W3 W3 W3 Aux.
Aux. Heat
Fan G G G G G G G G
C
2nd Stage Y2 Y2 Y2 Y2 Y2
Cool
C A A A
C/O Valve B B B B B O/B O/B O/B
Heat
A A A
C/O Valve O O O O O O/B O/B O/B
Cool
C H I H I H
System Monitor/ L – L – L L L L
System Defrost
C
Em. Heat E E E E E E E E
Multiple Aux. – W3 W3 W3 – – – –
Heat Lads D
G J J J
LED Indication – – X2 X1 X2 X1 X2 – X1 X2 –
70-6627 • 108
WILLIAMSON
COOLING CHANGEOVER
10 1
20 2
10 6
10 2
1G 00
G1 19
1G 02
1G 00
2
1R 00
1R 00
00 0/
47
28
04
14
28
00
6
5
61 10
2
94 14
89 90
51 G1
61 G2
01 R1
41 R1
47
42
71
10
B1
T8 611R
Y5 594G
W PC8
R1
T8 8511
T8 8611
T8 8011
A1
T8 8411
Existing
94
41
T8
Y
T
T
T
Y5
Function
T8
Terminals
Common F X X X X C C C C C C
Power R R R R R R R R R R
or
Compressor Y Y Y Y1 Y1 Y Y Y1 Y Y1 Y1/W1
G G G G G G G
1st Stage – – W1 W1 W1 W1 W1 W1 W1 –
Heat
B
Aux. Heat W2 W2 W2 W2 W2 W2 W2 W2 W2 Aux.
Fan G G G G G G G G G G
1 1 1
or or
C/O Valve – B B B B B B O/B B B O/B O/B
Heat
1 1 1
or or
C/O Valve O O O O O O O O/B O O O/B O/B
Cool
J K K J K J J
System Monitor/ L L L L L L L L
System Defrost
Em. Heat E E E E E E E E E E
Multiple Aux.
Heat Loads C W3 W3 W3 W3 E E E E E E
I D H D
LED Indication A – X2 X1 X2 X1 X2 – – – X1 X2 –
B
2nd Stage – – – – – – – – – W2
Compressor
2nd Stage – – – – – – – – – Y2
Cool
A Configure O/B (select models) in Installer Setup. F Terminal must be connected to the transformer common.
B When W2 is not used, configure W2 cycle rate to NC. G Do not remove factory-installed jumper.
C Terminal is for multiple auxiliary heat loads such as contactors, sequencers, H Optional Check LED on T8611G1004. See Fig. 26.
or relays. I Field-installed X2 to X (C) jumper.
D Optional LED indication activated with completed circuit on X1 and J LED is energized when terminal is powered.
X2 terminals. K L terminal is powered continuously when thermostat is in Em. Ht. position.
E If multiple auxiliary heat loads are used, connect to W2 (Aux W8900B) M13213
terminal.
70-6627 • 109
WILLIAMSON
HEATING CHANGEOVER
10 1
20 2
10 6
10 2
1G 00
G1 19
1G 02
1G 00
2
1R 00
1R 00
00 0/
47
28
04
14
28
00
6
5
61 10
2
94 14
89 90
51 G1
61 G2
01 R1
41 R1
47
42
71
10
B1
T8 611R
Y5 594G
W PC8
R1
T8 8511
T8 8611
T8 8011
A1
T8 8411
Existing
94
41
T8
Y
T
T
T
Function
Y5
Terminals T8
Common E X X X X C C C C C C
Power R R R R R R R R R R
or
Compressor Y1 Y Y1 Y Y1 Y1 Y Y Y1 Y Y1 Y1/W1
F F F F F F F
1st Stage – – W1 W1 W1 W1 W1 W1 W1 –
Heat
J
Aux. Heat W2 W2 W2 W2 W2 W2 W2 W2 W2 Aux.
Fan G G G G G G G G G G
I I I
or or
C/O Valve W1 B B B B B B O/B B B O/B O/B
Heat
I I I
or or
C/O Valve – O O O O O O O/B O O O/B O/B
Cool
A A B B A B A A
System Monitor/ L L X1 L L L L L L
System Defrost
Em. Heat E E E E E E E E E E
Multiple Aux.
Heat Loads C W3 W3 W3 W3 D D D D D D
H
LED Indication – – X2 X2 H X1 X2 G – – – X1 X2 –
J
2nd Stage – – – – – – – – – W2
Compressor
2nd Stage – – – – – – – – – Y2
Cool
A LED is energized when terminal is powered. E Terminal must be connected to the transformer common.
B L terminal is powered continuously when thermostat is in Em. Ht. position. F Do not remove factory-installed jumper.
C Terminal is for multiple auxiliary heat loads such as contactors, sequencers, G Optional LED indication with completed circuit on X1 and X2 terminals.
or relays. H Field-installed X2 to X (C) jumper.
D If multiple auxiliary heat loads are used, connect to W2 (Aux W8900B) I Configure O/B (select models) in Installer Setup.
terminal. J When W2 is not used, configure W2 cycle rate to NC. M13214
70-6627 • 110
YORK/BORG WARNER
B2CH, B2PS, E1CS, E1EB, E1HB, E2CH, STELLAR 2000 (DIRECT REPLACEMENTS)
10 2
10 1
20 2
10 6
G1 19
1R 00
1G 02
1G 00
2
1R 00
00
00 0/
28
47
28
14
5
00
94 14
2
42
89 90
41 R1
51 G1
61 G2
47
01 R1
10
71
B1
Y5 594G
R1
W PC8
1R
T8 8411
T8 8511
T8 8611
T8 8011
A1
94
Existing
61
41
Y
Y5
T
T
T8
Function
T8
Terminals
Common B B X X X C C C C C C
Power R R R R R R R R R R
or
Compressor Y Y1 Y Y Y1 Y1 Y Y1 Y Y1 Y1/W1
D D D D D D D
1st Stage W1 – W1 W1 W1 W1 W1 W1 W1 –
Heat
or E
Aux. Heat W W2 W2 W2 W2 W2 W2 W2 W2 W2 Aux.
Fan G G G G G G G G G G
C C C
A or or
C/O Valve H B B B B B B O/B B B O/B O/B
Heat
C C C
or or
C/O Valve O O O O O O O O/B O O O/B O/B
Cool
System Monitor/ X – L – L L L L L L
System Defrost
or
Em. Heat E X E E E E E E E E E
Mutiple E
Heat Loads – W3 W3 W3 – – – – – W2
LED
Indication – – X2 X1 X2 – – – – – –
TYPICAL THERMOSTATS AND SUBBASES — HONEYWELL MODEL NUMBER (CUSTOMER PART NUMBER)
T841A1274 (2TH11703324) T874G1428/Q674J1027 (6TH11702424)
T872G1299/Q672L1177 T874R1046/Q674L1017 (2TH11702224)
T872R1032/Q672L1011 T874R1046/Q674L1272 (2TH11702224)
T874G1170/Q674J1027 (2TH11702424) T8141A1006
T874G1196/Q674J1027 T8300A1037/Q6300A1044 (2ET11700124A)
T874G1345 (2TH11702624) T8611R1018 (025-27655)
T874G1402/Q674L1363 (2TH11702824)
70-6627 • 111
YORK/BORG WARNER
DIRECT REPLACEMENTS (OUTDOOR THERMISTOR MODELS) B2CH, B2PS, E1CS, E1EB, E1HB, E2CH
10 2
10 1
20 2
10 6
1R 00
1G 02
1G 00
2
1R 00
00
00 0/
28
47
28
14
00
1
3
5
89 90
41 R1
51 G1
61 G2
01 R1
10
16
76
55
B1
W PC8
1R
T8 8411
G1
T8 8511
T8 8611
T8 8011
R1
A1
Existing
61
94
94
41
T
T
T8
Function
Y5
Y5
Terminals T8
Common C B B B B C C C C C C
Power R R R R R R R R R R
Compressor Y Y Y Y Y1 Y Y1 Y Y1 Y1/W1
E E E E E
1st Stage – – – – W1 W1 W1 W1 W1 –
Heat
F
Aux. Heat W W W W W2 W2 W2 W2 W2 Aux.
Fan G G G G G G G G G G
D D D
A or or
C/O Valve H – – – B B B O/B B B O/B O/B
Heat
D D D
or or
C/O Valve O O O O O O O O/B O O O/B O/B
Cool
A
System Monitor/ F F F F L L L L L L
System Defrost
Em. Heat X X2 X2 X2 E E E E E E
Outdoor T T T T B B B B B B
Thermistor
A F and H terminals are not available on all models. D Configure O/B (select models) in Installer Setup.
B Tape off. Thermostat replaces outdoor reset models with improved zero droop E Do not remove factory-installed jumper.
performance. F Configure W2 cycle rate to NC. M13216
C Terminal must be connected to the transformer common.
TYPICAL THERMOSTATS AND SUBBASES — HONEYWELL MODEL NUMBER (CUSTOMER PART NUMBER)
T872G1042/Q672J1021 T874R1145/Q674L1272 T874R1169/Q674L1330
T874R1251/Q674L1272 (2TH11702324) T874R1327/Q674L1272 (6TH11702224)
70-6627 • 112
YORK/BORG WARNER
B2CH, B2PS, EICS, EIEB, EIHB, E2CH (ALTERNATE REPLACEMENTS)
10 2
10 1
20 2
10 6
10 0
G1 19
1R 00
1G 02
1G 00
2
1R 00
00 0/
28
47
28
1G 00
14
00
04
5
6
7
89 90
94 14
41 R1
51 G1
61 G2
01 R1
42
47
61 R1
21
B1
W PC8
Y5 594G
R1
T8 8411
T8 8511
T8 8611
T8 8011
A1
T8 8611
Existing
94
41
T
Y
T
T
Y5
Function
T
T8
Terminals
Common H B X X X C C C C C C
Power R R R R R R R R R R
or or
Compressor Y Y1 Y Y Y1 Y1 Y Y Y1 Y Y1 Y1/W1
I I I I I I I I
1st Stage W1 – W1 W1 W1 W1 W1 W1 W1 –
Heat
or B
Auxiliary W W2 W2 W2 W2 W2 W2 W2 W2 W2 Aux.
Heat
Fan G G G G G G G G G G
A A A
L or or
C/O Valve H B B B B B B O/B B B O/B O/B
Heat
A A A
or or
C/O Valve O O O O O O O O/B O O O/B O/B
Cool
D D E E D E D D
System Monitor/ X L X1 L L L L L L
System Defrost
or G G G G G G G G G
EM. Heat E X E E E E E E E E E
Multiple Aux. – W3 W3 W3 – – – – – –
Heat Loads C
F K K
LED Indication T X – X2 X2 X1 X2 J – – – X1 X2 –
B
2nd Stage – – – – – – – – – W2
Compressor
2nd Stage – – – – – – – – – Y2
Cool
A Configure O/B (select models) in Installer Setup. H Terminal must be connected to the transformer common.
B When W2 is not used, configure W2 cycle rate to NC. I Do not remove factory-installed jumper.
C Terminal is for multiple auxiliary heat loads such as contactors, sequencers, J Optional Check LED on T8611G1004. See Fig. 26.
or relays. K Field-installed X2 to X (C) jumper.
D LED is energized when terminal is powered. L H terminal is not available on all models.
E L terminal is powered continuously in Em. Ht. position. M Using these thermostats with a W8045 Demand Defrost Control may cause
F Tape off. Not used. customer complaints. If replacing a thermostat used on a W8045, see
G Field-installed E to W2 jumper for improved performance in emergency heat. York/Borg Warner Direct Replacements. M13224
TYPICAL THERMOSTATS AND SUBBASES — HONEYWELL MODEL NUMBER (CUSTOMER PART NUMBER)
T841A1274 (2TH11703324) T874G1345 (2TH11702624)1 T8141A1006
T872G1299/Q672L1177 1 T874G1402/Q674L1363 (2TH11702824) T8300A1037/Q6300A1044 (2ET11700124A)
T872R1032/Q672L1011 1 T874G1428/Q674J1027 (6TH11702424)1 T8300A1144/Q6300A1044 (6ET11700124A)
T874G1170/Q674J1027 (2TH11702424) T874R1046/Q674L1017 (2TH11702224)1 T8611R1018 (025-27655)
T874G1196/Q674J1027 T874R1046/Q674L1272 (2TH11702224)1
70-6627 • 113
YORK/BORG WARNER
10 2
10 1
20 2
10 0
10 6
G1 19
1R 00
1G 02
1G 00
1G 00
2
1R 00
00 0/
28
47
04
28
14
00
5
6
2
94 14
89 90
41 R1
51 G1
61 G2
61 R1
42
01 R1
47
71
B1
Y5 594G
W PC8
R1
T8 8411
T8 8611
T8 8511
T8 8611
T8 8011
A1
Existing
94
41
T
T
T
Y5
T
Function Terminals T8
Common E X X X X C C C C C C
Power R R R R R R R R R R
or
Compressor Y Y Y Y1 Y1 Y Y Y1 Y Y1 Y1/W1
G G G G G G G
1st Stage – W1 W1 W1 W1 W1 W1 W1 –
Heat
B
Aux. Heat W2 W2 W2 W2 W2 W2 W2 W2 W2 Aux.
Fan G G G G G G G G G G
A A A
or or
C/O Valve – B B B B B B O/B B B O/B O/B
Heat
A A A
or or
C/O Valve O O O O O O O O/B O O O/B O/B
Cool
D J J K K J K J J
System Monitor/ L L X1 L L L L L L
System Defrost
D
Em. Heat E E E E E E E E E E
D
Multiple Aux. W3 W3 W3 W3 F F F F F F
Heat Loads C
LED Indication – – X2 I X2 I X1 X2 H – – – X1 X2 –
B
2nd Stage – – – – – – – – – W2
Compressor
– – – – – – – – – Y2
2nd Stage
Cool
A Configure O/B (select models) in Installer Setup. F If multiple auxiliary heat loads are used, connect to W2 (Aux W8900B)
B When W2 is not used, configure W2 cycle rate to NC. terminal.
C Terminal is for multiple auxiliary heat loads such as contactors, sequencers, G Do not remove factory-installed jumper.
or relays. H Optional Check LED on T8611G1004. See Fig. 26.
D If provided on original equipment. I Field-installed X2 to X (C) jumper.
E Terminal must be connected to the transformer common. J LED is energized when terminal is powered.
K L terminal is powered continuously when thermostat is in Em. Ht. position.
M13219
TYPICAL THERMOSTATS AND SUBBASES — HONEYWELL MODEL NUMBER (CUSTOMER PART NUMBER)
T874G1410/Q674F1311(6TH11703024)
70-6627 • 114
YORK/BORG WARNER
TYPICAL EBHP SERIES
10 2
10 1
20 2
10 6
E
G1 19
1R 00
1G 02
1G 00
2
1R 00
00
00 0/
28
47
28
14
BL
00
6
5
AI T
94 14
89 90
41 R1
51 G1
61 G2
01 R1
10
47
42
AV NO
B1
LA
Y5 594G
W PC8
1R
R1
T8 8411
T8 8511
T8 8611
T8 8011
Existing
61
94
T
T
T8
Y5
Function Terminals
or
Common B B X2 X X C C C C C C
Power R R R R R R R R R
1st Stage W1 W1 W1 W1 W1 W1 W1 W1 –
Heat A A A A A A A
F
NOT AVAILABLE
Fan G G G G G G G G G
E
1st Stage Y1 Y Y1 Y1 Y Y1 Y Y1 Y1/W1
Cool
or or
C/O Valve – B B B B B O/B B B O/B O/B
Heat
or or
C/O Valve – O O O O O O/B O O O/B O/B
Cool
System Monitor/ – L – L L L L L L
System Defrost
Em. Heat E E E E E E E E E
Multiple Aux. – W3 W3 – – – – – –
Heat Loads C
LED Indication – X2 D X1 X2 – – – – X1 X2 –
70-6627 • 115
ZONE AIRE
VHP SERIES
10 2
10 1
20 2
10 0
10 6
G1 19
1R 00
1G 02
1G 00
1G 00
2
1R 00
00 0/
28
47
04
28
14
00
6
5
2
94 14
89 90
41 R1
51 G1
61 G2
61 R1
01 R1
47
42
71
B1
Y5 594G
W PC8
R1
T8 8411
T8 8611
T8 8511
T8 8611
T8 8011
A1
Existing
94
41
T
T
T
T
Y5
Function Terminals T8
or
Common 4 X1 X X X X C C C C C C
Power R R R R R R R R R R
or
Compressor Y Y Y Y1 Y1 Y Y Y1 Y Y1 Y1/W1
G G G G G G G
1st Stage – – W1 W1 W1 W1 W1 W1 W1 –
Heat
I
Aux. Heat W2 W2 W2 W2 W2 W2 W2 W2 W2 Aux.
Fan G G G G G G G G G G
A A A
or or or
C/O Valve B W1 B B B B B B O/B B B O/B O/B
Heat
A A A
or or
C/O Valve – O O O O O O O/B O O O/B O/B
Cool
J K K J K J J
System Monitor/ L L L L L L L L
System Defrost
Em. Heat E E E E E E E E E E
Multiple Aux. W3 W3 W3 W3 E E E E E E
Heat Loads C
B H B
LED Indication X2 – X2 F X1 X2 X1 X2 – – – X1 X2 –
I
2nd Stage – – – – – – – – – W2
Compressor
2nd Stage – – – – – – – – – Y2
Cool
70-6627 • 116
HEAT PUMP THERMOSTAT CROSS REFERENCE/SELECTION GUIDE
Index
Subject/Manufacturer Page Number
Amana ..................................................................................................................................................................... 36
Addison ................................................................................................................................................................... 103
Air-Ease .................................................................................................................................................................. 38
American Stabilis .................................................................................................................................................... 37
American Standard ................................................................................................................................................. 97-100
Application Tips ....................................................................................................................................................... 33
Arcoaire ................................................................................................................................................................... 39
Armstrong ............................................................................................................................................................... 38
Bard ........................................................................................................................................................................ 40
Borg Warner ............................................................................................................................................................ 111-115
Bryant-Day/Night-Payne ......................................................................................................................................... 41
Carrier ..................................................................................................................................................................... 42-45
Coleman .................................................................................................................................................................. 50-53
Comfort Air .............................................................................................................................................................. 60
Comfortmaker ......................................................................................................................................................... 39
Crispaire .................................................................................................................................................................. 46
Econar ..................................................................................................................................................................... 47-48
Enerstat ................................................................................................................................................................... 49
Evcon ...................................................................................................................................................................... 50-53
Fedders ................................................................................................................................................................... 54
Florida Heat Pump .................................................................................................................................................. 55
Fraser Johnston ...................................................................................................................................................... 82
Friedrich .................................................................................................................................................................. 56
General Electric ...................................................................................................................................................... 57-58
Geo System ............................................................................................................................................................ 59
Heat Controller ........................................................................................................................................................ 60
Heatwave ................................................................................................................................................................ 61
Heil Quaker ............................................................................................................................................................. 68-69
Hookup Diagrams ................................................................................................................................................... 15-25
Honeywell ............................................................................................................................................................... 62-67
InterCity Products ................................................................................................................................................... 68-69
Intertherm ................................................................................................................................................................ 70-72
Janitrol .................................................................................................................................................................... 73
Keeprite ................................................................................................................................................................... 74
Lennox .................................................................................................................................................................... 75-81
Luxaire .................................................................................................................................................................... 82
Index ....................................................................................................................................................................... 117-119
70-6627 • 117
HEAT PUMP THERMOSTAT CROSS REFERENCE/SELECTION GUIDE
70-6627 • 118
HEAT PUMP THERMOSTAT CROSS REFERENCE/SELECTION GUIDE
Wiring Diagrams
Fig. 16 Internal schematic and typical wiring diagram for T841A1308. ............................................... 15
Fig. 17 Internal schematic and typical wiring diagram for T841A1555. ............................................... 16
Fig. 18 Internal schematic and typical wiring diagram for T841A1712 and T841A1738. .................... 16
Fig. 19 Internal schematic and typical wiring diagram for T841B1000. ............................................... 17
Fig. 20 Internal schematic and typical wiring diagram for Y594G1161. .............................................. 17
Fig. 21 Internal schematic and typical wiring diagram for Y594G1633. .............................................. 18
Fig. 22 Internal schematic and typical wiring diagram for Y594G1419 and Y594G1476. ................... 18
Fig. 23 Internal schematic and typical wiring diagram for Y594G1763. .............................................. 19
Fig. 24 Internal schematic and typical wiring diagram for Y594R1797. ............................................... 19
Fig. 25 Internal schematic and typical wiring diagram for Y594R1425. ............................................... 20
Fig. 26 Internal schematic and typical wiring diagram for T8611G1004 and T8611G1103. ................ 21
Fig. 27 Typical wiring diagram for T8611M7008. ................................................................................ 22
Fig. 28 Typical wiring diagram for T8611R1000. ................................................................................. 23
Fig. 29 Typical wiring diagram for T8011R and T8411R. .................................................................... 23
Fig. 30 Typical wiring diagram for T8511G. ......................................................................................... 24
Fig. 31 Typical wiring diagram for T8611G2002 and T8611G2028. .................................................... 25
70-6627 • 119
70-6627 • 120
Home and Building Control Home and Building Control