Worksheet: Reinforced Concrete Design Calculation By: Projek: Check: CCY

This document contains calculations for the reinforced concrete floor slab and ring beam of a proposed 1.0 million gallon circular reservoir. For the floor slab, a minimum steel ratio of 0.35% is required with #12 bars spaced at 125mm. Crack width is calculated to be 0.16mm, less than the 0.2mm limit. For the ring beam, tension is calculated to be 0.35kN/m requiring #12 bars spaced at 250mm around the beam. Crack width is again below the limit of 0.2mm. Construction joints are specified at 7.5-15m for the slab and at the center of the reservoir for the ring beam.

Uploaded by

Ainil Sharir
Copyright
© Attribution Non-Commercial (BY-NC)
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
151 views

Worksheet: Reinforced Concrete Design Calculation By: Projek: Check: CCY

This document contains calculations for the reinforced concrete floor slab and ring beam of a proposed 1.0 million gallon circular reservoir. For the floor slab, a minimum steel ratio of 0.35% is required with #12 bars spaced at 125mm. Crack width is calculated to be 0.16mm, less than the 0.2mm limit. For the ring beam, tension is calculated to be 0.35kN/m requiring #12 bars spaced at 250mm around the beam. Crack width is again below the limit of 0.2mm. Construction joints are specified at 7.5-15m for the slab and at the center of the reservoir for the ring beam.

Uploaded by

Ainil Sharir
Copyright
© Attribution Non-Commercial (BY-NC)
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 2

WorkSheet : REINFORCED CONCRETE DESIGN CALCULATION By: IDZ

Projek: PROPOSED CONSTRUCTION AND COMMISIONNING Check: CCY


OF THE 1.0 MILLION GALLONS CIRCULAR REINFORCED
CONCRETE RESERVOIR ANF ANCILLARY WORKS AT BUKIT NASAH
DAERAH HULU PERAK, PERAK DARUL RIDZUAN
File No: PMK/0779/07/RC

FLOOR SLAB CALCULATION

Provide movement joint spacing 7.5m for partial construction joint or 15m for complete construction
joint. Fall in temperature T2 is not considered.

Table A.1 Minimum steel required is ρ = 0 @ 0.35%

Base Thickness d = 300 mm


b = 1000 mm

As = 0.0035 x 500 x 1000/2


= 525 mm2/m

Cl 3.22 (a) Direct tension in immature concrete


App.A Provide Reinforcement T = 12 @ 125

Section Area A = 653 mm2/m

Cracking Checking

Steel ratio ρ = As/bd


= 0

fct/fb = 0.67

Thermal Coef. α = 1.2 x 10-5

Bar size φ = 12 mm

Fall in temp T1 = 25 0C
T2 = 0 0C

Crack width w = Smax α (T1 + T2)/2

= [ (fct/fb)(φ /2ρ)] [ α (T1+T2)/2]

= [(0.67 x 12)/(2 x 0.0037)] (1.2 x 10-5)(25)/2

= 0.16 < 0.2mm

Provide complete constraction joint at the centre of the pool


WorkSheet : REINFORCED CONCRETE DESIGN CALCULATION By: IDZ
Projek: PROPOSED CONSTRUCTION AND COMMISIONNING Check: CCY
OF THE 1.0 MILLION GALLONS CIRCULAR REINFORCED
CONCRETE RESERVOIR ANF ANCILLARY WORKS AT BUKIT NASAH
DAERAH HULU PERAK, PERAK DARUL RIDZUAN
File No: PMK/0779/07/RC
D = 31.06 m
RING BEAM CALCULATION A = (75/1000)2
= 0.006
Tension T0 (1.4
= LL + 1.2 DL) x 0.01
= 0.024 kN

x = 0.024 cos 200

= 0.02 kN

T = xD/2
= 0.35 kN

As = T/fy
= 0.35 /410
= 852.91 mm2/m

Provide Reinforcement Y = 12 @ 250

Section Area As = 854 mm2/m

Cracking Checking

Steel ratio ρ = As/bd


= 0.002

fct/fb = 0.67

Thermal Coef. α = 1.2 x 10-5

Bar size φ = 12 mm

Fall in temp T1 = 25 0C
T2 = 0 0C

Crack width w = Smax α (T1 + T2)/2

= [ (fct/fb)(φ /2ρ)] [ α (T1+T2)/2]

= [(0.67 x 12)/(2 x 0.0037)] (1.2 x 10-5)(25)/2

= 0.16 < 0.2mm

Provide complete constraction joint at the centre of the pool