This 3 sentence summary provides the key details from the document: The document outlines the work instruction sheet for performing preventative maintenance on transformers, CTs, PTs, and CVTs at a Tata Motors plant in Ahmedabad, with 5 steps including collecting permits, checking safety measures, performing checks and recording readings, checking with the PM checklist, and charging after maintenance is complete while ensuring safety measures are followed. It assigns responsibilities for the different steps to shift leads, operators, and maintenance personnel.

Uploaded by

123adp
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
132 views

Work Instruction Sheet (WIS) : SL No. Action Plan Responsibility

This 3 sentence summary provides the key details from the document: The document outlines the work instruction sheet for performing preventative maintenance on transformers, CTs, PTs, and CVTs at a Tata Motors plant in Ahmedabad, with 5 steps including collecting permits, checking safety measures, performing checks and recording readings, checking with the PM checklist, and charging after maintenance is complete while ensuring safety measures are followed. It assigns responsibilities for the different steps to shift leads, operators, and maintenance personnel.

Uploaded by

123adp
Copyright
© Attribution Non-Commercial (BY-NC)
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 3

Doc. No.

:
PS 11/WIS/PWR/ 01
Work Instruction Sheet Page 1 of 1
TATA MOTORS Rev. No. & date:
LTD. (WIS) 01 & 27.01.2010
Ahmedabad Date (o):
27.01.2010

SL NO. ACTION PLAN RESPONSIBILITY

Prepared by Review & Issue Controlled by Approved by

S.MEHER Mr. D P chatterjee


PARESH MEVADA

PS00-F014-00, 09-09-10
Doc. No.:
PS 11/WIS/PWR/ 01
Work Instruction Sheet Page 1 of 1
TATA MOTORS Rev. No. & date:
LTD. (WIS) 01 & 27.01.2010
Ahmedabad Date (o):
27.01.2010

1. Before starting the P.M. of Transformer / CT / PT /


CVT observe the following sequence when switching SHIFT IN CHARGE
on the plant:
Collection of work permit and lock out form TML
Check visually earthing of HT & LT points.
Ensure using safety PPEs and have tool box talk.
All connected breakers are off and physically isolated.
(Electrical and mechanical interlock)

2. CONDITIONS SHOULD BE MET:


Disconnector can be closed or opened only if the associated OPERATOR
circuit breaker is in “Off” condition.

Earth switch can be closed only if the disconnector is in the


“open” condition. Line Earth switch should be closed only
after ensuring that the said line is fully dead.

Earth switch can be opened only if the disconnector is in the


“open” condition.
Disconnector cannot be closed if the earth switch is already
in “closed” condition.

The fixed contact of the earth switch is generally mounted on


the moving connection arms of the disconnector. If one tries
to close the disconnector when the earth switch is on, it may
damage the earth switch fixed contact and earth switch arm.

3. CHECK AND RECORD FOLLOWING OPREATING


READINGS FROM OPERATOR
( a ) Volts
( b ) Amps

4. Start checking with PM check sheet. PS11-PWR-PM-01

5. Charging after PM:


Check visually earthing has been removed from HT & LT
points. SHIFT IN CHARGE
Removal of all interlocks (Electrical and mechanical interlock)
Return of work permit and lock out to TML.
Charging can be done.

Prepared by Review & Issue Controlled by Approved by

S.MEHER Mr. D P chatterjee


PARESH MEVADA

PS00-F014-00, 09-09-10
Doc. No.:
PS 11/WIS/PWR/ 01
Work Instruction Sheet Page 1 of 1
TATA MOTORS Rev. No. & date:
LTD. (WIS) 01 & 27.01.2010
Ahmedabad Date (o):
27.01.2010

Prepared by Review & Issue Controlled by Approved by

S.MEHER Mr. D P chatterjee


PARESH MEVADA