C.T Dimensioning
C.T Dimensioning
[IEC 60044 – 1]
Definitions :
Current transformer
An instrument transformer in which the secondary current, in normal conditions of use, is substantially
proportional to the primary current and differs in phase from it by an angle which is approximately zero
for an appropriate direction of the connections
K n Is Ip 100
CurrentError%
Ip
where
Kn is the rated transformation ratio;
Ip is the actual primary current;
Is is the actual secondary current when Ip is flowing, under the conditions of
measurement.
Phase displacement
The difference in phase between the primary and secondary current vectors, the direction of the vectors
being so chosen that the angle is zero for a perfect transformer.
The phase displacement is said to be positive when the secondary current vector leads the primary
current vector. It is usually expressed in minutes or centiradians.
NOTE This definition is strictly correct for sinusoidal currents only.
Composite error
Under steady-state conditions, the r.m.s. value of the difference between:
a) the instantaneous values of the primary current; and
b) the instantaneous values of the actual secondary current multiplied by the rated transformation ratio,
the positive signs of the primary and secondary currents corresponding to the convention for terminal
markings
The composite error Ec is generally expressed as a percentage of the r.m.s. values of the primary
current according to the formula:
100 1 T 2
c K ni s i p dt
Ip T 0
where
Kn is the rated transformation ratio;
Ip is the r.m.s. value of the primary current;
ip is the instantaneous value of the primary current;
is is the instantaneous value of the secondary current;
T is the duration of one cycle.
For more details and the use of the composite error , please refer to Annex – A .
Since “The rated equivalent limiting secondary e.m.f.” Eal or The Rated Knee Point Voltage Vk in
according with the IEC 60044-6 standard to specify the CT requirements for different protection
equipment which shall be higher than the required limiting secondary e.m.f EalReq. or the required knee
point voltage Vkreq. Which is to be calculated as per all the Protection Relay Manufacturers
recommendations and compliance with IEC 60044-6 standard .
NOTE The Rated knee point e.m.f. will be the Required knee point e.m.f. which will be in according
with the protection relay manufacturer recommendation .
Class X or PX CTs are mostly used for high impedance circulating current protection which requires
high Equivalent Secondary e.m.f (E) .This can be economically achieved with Class X or PX which is of
Low Leakage Reactance and can have a High magnetizing Current at Vk . Three factors will influence
the emf “E”. It’s the number of secondary turns “N”, the core area “A” and the induction in Wb/m2 “B”.
E Si
B
2 f Aj N2
where:
A = core area in m2
B = ux density in Tesla (T)
f = frequency
N2 = number of secondary turns
The induction is dependent of the core material, which influences the size of the magnetizing current.
For a certain application the secondary turns and the core area are thus selected to give the required
emf output.
CT types:
Generally, there are three different types of CTs from the Construction Point of view :
• High remanence type CT
• Low remanence type CT
• Non remanence type CT
Accuracy Class Current Error at Rated Primary Current Composite Error at Rated
Accuracy Limit
Primary Current
5P ±1% 5%
10P ±3% 10%
The primary difference is that the measuring current transformer(FS) is required to retain a specified
accuracy over the normal range of load currents, whereas the protective current transformer (5P , PX )
must be capable of providing an adequate output over a wide range of fault conditions, from a fraction
of full load to many times full load.
CT – Measuring vs Protection :
Measuring CT Protection CT
Under over current, the CT In case of over current, the
should limit the secondary CT should maintain the
current to avoid thermal secondary current within
overload of the connected the rated limit to enable
equipment proper protection operation
At rated burden (cos = 0.8) At rated burden (cos = 0.8)
and rated security factor, the and rated accuracy limit factor
composite error should be>10% the composite error should be
< 5% or 10%
Current transformers according to ANSI/IEEE are partly specified in different ways. A rated secondary
terminal voltage UANSI is specified for a CT of class C. UANSI is the secondary terminal voltage the CT
will deliver to a standard burden at 20 times rated secondary current without exceeding 10 % ratio
correction. There are a number of standardized UANSI values e.g. UANSI is 400 V for a C400 CT. A
corresponding rated equivalent limiting secondary e.m.f. EalANSI can be estimated as follows:
E alANSI 20 I sn RCT U ANSI 20 I sn RCT 20 I sn Z bANSI
where
ZbANSI : The impedance (i.e. complex quantity) of the standard ANSI burden for the specific
C class ( ).
UANSI : The rated secondary terminal voltage for the specific C class (V).
The C.Ts according to class C must have a calculated rated equivalent limiting secondary e.m.f. EalANSI
that fulfills the following:
(Corrected VA Wdg. Re s )
K OALF RATED ALF
(Connected VA Wdg. Re s )
Also , some clients specify two Main Protections from different manufacturers for each type
of protection on the 400 KV and 132 KV Substations . In our calculated examples , we will
elaborate on the different protection relays which are most commonly used for each circuit
on the 132 KV system (cable feeder , OHL , Transformer & Bus coupler / Section ) which
will cover both ( One Protection or Two Protection schemes ).
The CT saturation is directly affected by the voltage at the CT secondary terminals. This
voltage is developed in a loop containing the conductors and the relay burden. For three-
phase faults, the neutral current is zero, and only the phase conductor and relay phase
Burden (VA)
Bay Control Unit , REF545-ABB 0.1
(Synchro Check Function)
2 × 100m Cable of 4 mm² 1.122
Digital Fault Recorder 0.1
Total 1.322
40000
Re quired ALF 26.6 For 1500/1 A CT ratio
1500
40000
Re quired ALF 40 For 1000/1 A CT ratio
1000
The Operating Accuracy Limit Factor (KOALF )
(Corrected VA Wdg . Re s)
K OALF RATED ALF
(Connected VA Wdg . Re s )
Rated VA
22.5
Corrected VA 18VA , and
1.25 1.25
15
12VA
1.25
18 2
20 120.4 26.6 For CT ratio 1500/1 A
1.322 2
12 1.33
20 100.52 40 For CT ratio 1000/1 A
1.322 1.33
Since , the operating accuracy limiting factor KOALF=120.4/100.52 being higher than the required
accuracy limiting factor 26.6/40 for CT ratios 1500/1000/1 A , the proposed 5P20, 22.5/15VA current
transformer is adequate
The O/C & E/F protection functions are mostly incorporated in the Bay Control Unit ( BCU ) or the Pilot
Wire Differential Protection along with the Breaker Failure function . However , the same
procedure to be followed for the loose relays if used. If the proposed BCU incorporate other protection
functions such as Breaker Failure where as per the manufacturer recommendation that the CTs must
have a rated equivalent secondary e.m.f. Eal that is larger than or equal to the required secondary e.m.f.
Ealreq which must be verified also .
3. Bus Bar Protection :
This is a form of bus bar protection using either unbiased high input impedance relays or biased low
impedance relays. Differential protection uses the principal of Kirchhoff’s first law to sum the current
from the CTs covering the protected zone. The relay detects the summation current and will trip the
associated breakers if it indicates a fault within the zone.
It shall be verified with all circuits connected to the Bus Bar Protection .
1. Bus Bar Protection - Low Impedance :
Protection must have a low burden to enable it to be installed in series with other equipment on
common secondary cores of the current transformers. It has to allow the use of different class and type
of CTs made by different manufacturers. In particular, it will have to be able to accept mixes of plant,
satisfying different standards (e.g. British Standard 3938: Class X, IEC 185: Class 5P20, IEC 44-6
Class TPX, TPY or TPZ).The protection has to be stable for all types of external faults and in particular
under CT saturation conditions. This saturation has to be able to be detected in less than 2 ms. The
differential bus bar protection has to implement also an effective protection against circuit breaker
failures.
Example for Low Impedance with SIEMENS Relay Type 7SS52 C.T Data :
CT ratio: 3000/1A VA: 30
Class: 5P20 RCT 8
Burden ( VA )
BBP relay Type 7SS52 , SIEMENS 0.1
2×100m cable of 4 mm² 1.122
Total 1.222 < 30 VA
RCT Rb
K SSC K SSC
RCT Rb
Where
40000
K SSC 0. 5 6.667(required )
3000
And
RCT Rb
K SSC K SSC (effective)
RCT Rb
8 30
K SSC 20 82.4 6.667
8 1.222
As the effective symmetrical short circuit current factor of proposed CT is above the required
effective symmetrical short circuit current factor .
Further , as per manufacture catalogue Vk for relay type 7SS (measuring ) is calculated as follows
:
100
Vk RCT R I sn
1.3
100
Vk 8 1.222 1 709.4V
1.3
24 8 1 20
492.3V
1.3
Therefore , Rated knee point voltage < Required Vk
Other Example for Low Impedance with ABB Relay Type REB 670
CT Ratio 3000/1A
Class of Accuracy 5P20
CT Resistance RCT > 15
Burden 50 VA
Corrected Burden 40 VA
V V
k available k cal
I sn SR
V 0.5 I t max RCT RL
k cal I pn I R2
I sn SR
V 0.5 I t max RCT RL
k cal I pn I R2
As per the relay manual , since the CT requirement are mentioned for BS Class PX class . Hence
final class 5P CT parameters are CV
The design values according to BS can be approximately transferred in to IEC-60044 std using
the following formula:
All CTs must have the same transformation ratio . To prevent maloperation of the relay during
saturation of the CTs on an external fault, the actual stability voltage Us must be higher than the
voltage (Ustab ) produced by the maximum secondary through fault current , flowing
Us U stab
In addition to this, the knee point voltage must be higher than twice the actual stability voltage:
U Knee 2 Us
Where:
Since
Us U stab is considered as
Us= 225 V
Therefore
U Knee 2 Us
2 225
450V
Criteria is
Proposed Vk Required Vk
1500 450
Hence
CT is : Suitably dimensioned
I pn
IP I sn ( I s. min n Ie )
Where
Fault Setting
The primary operating current of busbar protection is normally set to less than 30% of the
minimum expected fault current. Unless otherwise specified. Further as per specification
requirement, the setting shall be above 125% of nominal full load current of transformer.
DEWA ( Dubai Electricity & Water Authority ) specify the minimum and maximum primary operating
current as follows which will be followed in the calculations :
IP min= 1100 A
IP max= 1400 A
For a desired increased sensitivity of 2000 A primary setting . The relay setting shall be
I sn US
I I n Ie
s set (min) p des I pn U knee
I sn US
I I n Ie
s set (max) p des I pn U knee
The proper value of stabilizing resistor Rstab is required to ensure stability and is calculated by
using the formula
Us
R Rb
stab (max) I
s set
225 0.1
0.41
= 726
1
Vf V 3k Rstab If 4
1.3
1
1500 3 726 13.34 4
1.3
3108 V
Half second rating of stabilizing resistor Phalf =
2
V1
Rstab
2
3108 / 726
13306W
13kW
Hence stabilizing resistor of 0-5000 variable , having a power rating of 350 W and short
time rating of 15kW will be selected
U 2 2 U knee U U knee
max relay SCC max int
= 10037 V
U 1500V
max relay
10037 1500V
Hence Metrosil is required
The type of metrosil required is chosen by its thermal rating as defined by the formula
P 4 / 3.14 If Vk
4 / 3.14 13.34 1500
25477.71 J / S
25.48 kJ / S
Select a metrosil with C=900 , = 0.2
Another example with another Type which is also widely used AREVA - MCAG34 High Impedance
Protection Relay for 11 KV Busbar Protection .
11 kV Busbar Protection Discriminating and check Zone
Vs I F ( A D 2G )T
Where :
IF = Fault Current Corresponding to the rated stability limit (100 percentage of switchgear short circuit
rating as per clause 5.6 of ESI 48-3)
=25kA
=Resistance of Wiring plus current transformer winding
= RCT+RL=10+0.9=10.9
2
RL=0.9 , L=100 m, A=2.5 mm , r= 9 /km
Vs I F ( A G )T (V )
2500
Vs 10.9 85.16V
3200
Vs 85.16V
b) Knee Point Voltage (Vk)
As per ESI 48-3 , the minimum current transformer knee point voltage is :
V 2 Vs 2 95 200V
kn min
V 200V
kn min
100
I fs 0.05 66 0.0018 0.003 3200 553.3 A
90000
Which is approximately 27.6% , of the min , fault current at the 11kV Bus .
However based on the data provided by manufacturer for similar type of CTs it can be
assumed that average current is approximately 1mA, reconsidering the above formula
100
I fs 0.05 66 0.001 0.003 3200 384.4 A
90000
Which is approximately 19.2% , of the min , fault current at the 11kV Bus
For Disc. zone
100
I fs 0.05 24 0.0018 0.003 3200 311.4 A
90000
Which is approximately 15.56 % , of the min , fault current at the 11kV Bus .
However based on the data provided by manufacturer for similar type of CTs it can be
assumed that average current is approximately 1mA, reconsidering the above formula
100
I fs 0.05 24 0.001 0.003 3200 249.95 A
90000
Which is approximately 12.5 % , of the min , fault current at the 11kV
Since the fault setting is between 10% and 30% of the minimum fault current
(as per ESI 48-3 and tender documents) and DEWA’s requirement is fulfilled,
the selected magnetizing current 1.5 mA at Vk/2 is suitable for the system protection.
Therefore, the relay current setting will be provided with range (5%-20%) in seven
equal steps, which is confirmed by above calculation as adequate.
d) Stabilizing Resistor
To assure stability for through faults a stabilizing resistor will be required . The value of series
resistance is calculated as follows :
Vs VA
RS
Ir I r2
Where :
RS Value of the stabilizing resistor
VS Minimum required stability voltage i.e. setting voltage
Ir Relay setting current is negligible
The resistors incorporate in the scheme must be capable of withstanding the associated thermal
conditions
The continuous Power Rating of a resistor is defined as
Pcon 2
I con R
Where
Pcon = Resistor Continuous Power Rating
Icon =Continuous Resistor Current Power Rating
R =Resistance
For Check
2
553.3
Pcon 2000
3200
= 59.8 Watts
For Disc
2
311.4
Pcon 2000
3200
=18.9 Watts
The voltage developed across a resistor for a maximum internal fault condition
is defined as
Vf 2 Vk3 R I fs 1.3
2
830.3
2000
344.7Watts
Where
Vf = rms voltage across resistor
25000
Secondary current is 7.813
3200
Vf
2
2203 2000 7.813 1.3
=
830.3V
V f2
Phalf
R
V f2
R
2
830.3
2000
344.7Watts
As per the manufacturer catalogue, short time rating of stabilizing resistor used in MCAG34 AREVA
relay is : ZB9016783
e) Requirement of Metrosil
The maximum voltage in the absence of CT saturation is :
Vf I F T RCT 2 RL RS RRe lay
25000
10 2 0.9 2000 1 15725 V
3200
Peak to peak voltage developed across the relay is:
VP 2 2 Vk Vf Vk
Where
Vk=200 V
= 5223.8 V
Since the peak voltage developed across the relay is more than 3kV , metrosils are required . Selected
metrosil is three phase 6”,600A/S3/S802,C=450, =0.25
Comparison of High and Low-Impedance Bus bar Protection :
Nowadays high impedance protection is still widely used, because it is considered “cheap and
easy”. But most users only look at the relay price itself, without considering the other disadvantages of
a high impedance schemes:
All CTs must have the same ratio
Class X for all CT cores
Bus sectionalizers with circuit-breaker must be equipped with two CTs
Separate CT cores for busbar protection
Advantages of numerical protection technology(e.g. fault recording, communication, etc.) not
available
Check zone needs separate CT cores
Isolator replica requires switching of CT secondaries , additional check zone obligatory.
3. Pilot Wire Current Differential Protection :
CHARGING CURRENT COMPENSATION
The basic premise for the operation of differential protection schemes in general is that the sum of the
currents entering the protected zone is zero. In the case of a power system transmission line, that may
not be entirely true because of the capacitive charging current of the line. For short overhead
transmission lines, the charging current can be treated as a small unknown error. In that case, the error
due to the line charging current is covered by the percentage restraint characteristic of the current
differential scheme. For long transmission lines and cables, the charging current may be too large to
treat as an unknown error. In that case, it is often necessary to desensitize the current differential
protection to prevent mis-operations due to the line charging current which shall be considered in the
Relay setting :
The sensitive differential set point I-DIFF> is calculated according the charge current of the cable or
set to a minimum value, which results from the CT´s transient behavior. The charge current caused
Prepared by : Mohammad Subhi Abdel -–Halim 22
Senior Substation Design Engineer
PBME – AMMAN Office / JORDAN
PART I - Current Transformers Dimensioning
[IEC 60044 – 1]
by the capacitance of the line/cable is a permanent differential current during normal operation. I-DIFF>
should be set 2,5-3 times of this steady state charge current or as per the relay manufacturer
recommendation . The charge current is calculated as follows:
6
IC 3.63 10 UN f N COP 1
Example : Pilot Wire Current Differential Protection with SIEMENS Relay Type 7SD522 :
CT Ratio: 1500-1000/1A Vk 1950/1300V Ie 50/100mA at Vk
Class : PX RCT 5.5/3.67
To ensure correct operation of the connected relay , CT to remain stable under all through fault
conditions and the rated knee point voltage should be greater than the calculated knee point voltage
Since, effective CT accuracy limiting factor,
I SSC , max
K OALF and K OALF 30
IN
40000 A 40000 A
K OALF 26.67 , 40
1500 A 1000 A
The knee point voltage as per the revised formula given by DEWA :
I
SSC max( Ext . fault )
Vk K td RCT Rb I SN
I PN
Where
Ktd = 3.75 Transient Dimensioning Factor
(Considering 75% remanance in the CT core as suggested by DEWA)
ISSC,max(ext.fault current) =40000A
Hence the calculated knee point voltages for ratios 1500/1000/1 A are satisfied as their values are less
than the rated CT knee point voltages , Vk=1950/1300V > UKN=735/828 V respectively
Hence the proposed CT cores for ratios 1500/1000/1A are acceptable
There are no specific requirements on magnetizing current
CT Requirements for Main-2 Backup distance protection:
The CT requirement to ensure correct operation of the distance protection relay
I
SSC max( close .in. fault )
Vk K td ( a ) RCT RL RR
1.3 I PN
I
SSC zone1.end . fault )
Vk K td ( b) RCT RL RR
1.3 I PN
Where
ISSC,max(close in fault ) Max short circuit current for faults close to the relay
ISSC,max(zone-1 end fault ) Max short circuit current for faults at zone-1 reach
40000
Vk 4 5.5 1.8 0.05
1.3 1500
40000
Vk 4 3.67 1.8 0.05
1.3 1000
= 679.38V< 1300 V
For Zone 1 end fault :
I
SSC zone1.end . fault )
Vk K td ( b) RCT RL RR
1.3 I PN
40000
Vk 5 5.5 1.8 0.05
1.3 1500
40000
Vk 5 3.67 1.8 0.05
1.3 1000
= 849.23V< 1300 V
Hence the calculated knee point voltages for ratios 1500/1000/1A are satisfied as their values
are less than the rated CT knee point voltages
Hence the proposed CT cores for ratios 1500/1000/1A are acceptable
There are no specific requirements on magnetizing currents
Remote End C.T Dimensioning :
For proper protection scheme operation , the Protection Relay at the remote end shall be the same
SIEMENS Type 7SD522 , same all above C.T requirement equations and procedure shall be followed :
C.T Data :
C.T Ratio Vk Class Rct at 75º C RL at 75º C Rb
1500-1000-500/1 1950 – 1300 – 650 V X 4.284 – 2.783 – 1.365 0.75 0.05
RL is calculated as 0.00375 ohm/meter for (A = 6 mm²X100 meter length = 0.00375x100x2 = 0.75
To ensure correct operation of the connected relay , CT to remain stable under all through fault
conditions and the rated knee point voltage should be greater than the calculated knee point voltage
Since, effective CT accuracy limiting factor,
I SSC , max
K OALF and K OALF 30
IN
40000 A 40000 A
K OALF 26.67 , 40
1500 A 1000 A
500 /1 ratio result can be ignored . Since , no 500/1 tap at the remote end and will not be used .
Where
Ktd = 3.75 Transient Dimensioning Factor
(Considering 75% remanance in the CT core as suggested by DEWA)
I
SSC zone1.end . fault )
Vk K td ( b) RCT RL RR
1.3 I PN
Where
ISSC,max(close in fault ) Max short circuit current for faults close to the relay
ISSC,max(zone-1 end fault ) Max short circuit current for faults at zone-1 reach
40000
Vk 4 4.284 0.75 0.05
1.3 1500
40000
Vk 4 2.783 0.75 0.05
1.3 1000
40000
Vk 5 4.284 0.75 0.05
1.3 1500
40000
Vk 5 2.783 0.75 0.05
1.3 1000
Same must be repeated for the 1000 / 1 A ratio considering the Rct for the 1000/1 A ratio :
Vk requirement equations for other types of relays which are also widely used are as
follows :
Same as above if IF = 40000 A is used, it will give better safety . Other wise , the actual Zs and ZL shall
be calculated .
If a separate BCU ( Bay Control & Protection Unit ) is used with Circuit breaker failure protection , the
C.T must fulfill the Manufacturer recommendation , the following example with ABB REC 561 control
and protection unit
As per ABB REC 561 manual with Circuit breaker failure protection in REC 561 , CT core must meet
the following requirement:
With maximum value for Ereq = 159,3V and Eknee = 300V Ereq < Eknee
Thus , CT core is adequate and suitably dimensioned.
2. Bus Bar Protection : same as the cable feeder .
3. Distance Protection : Example with ABB distance Protection Relay Type REL 511
protection
Short Circuit calculation for Zone – 1 three phase & phase to earth fault currents :
With maximum value for Ealreq = 476V and Eknee = 1000V Ealreq < Eknee
Core 2 data for REL 511 are thus satisfactory.
C. 132 KV Feeder with Reactor : For reactor detail , please refer to Annex – C :
A. Line Protection : The same as the above Feeder Protection (OHL or Cable Feeder )
B. Reactor Protection : We will elaborate on the Reactor Differential Protection , Restricted Earth
Fault (REF) and the Stand – by E/F protection which mostly will cover the Transformer Protection .
Since , if separate back up Over – Current and E/F are used , the same previous dimensioning for
the Feeder circuit is applicable :
1. Differential Protection :
A differential relay, of high impedance type should be used as main protection. CT’s should be specified
at both the phase and the neutral side of each phase and a three phase protection should be used as a
three phase protection gives a higher sensitivity for internal faults. The general requirement on the
function values of the high impedance differential protection is that at maximum through fault current for
an external faults the relay wont mal-operate even with one CT fully saturated.
For a reactor the dimensioning criteria will be for the inrush current, since a reactor only will give a
through fault current equal to rated current, at an external earth-fault. The maximum inrush current for a
reactor is approximately two times the rated current. If no specific requirement concerning at what
current the relay should be stable exists, five times the rated current is used when operating voltage is
selected. The function value of the relay should be chosen:
REACTOR DATA:
Rated voltages of windings 132/145kV
Rated Current 43.7/48A
Connection symbol YN
Rating 10/12.1MVAr
Cooling ONAN
10 10 103
= A 437.39 A
3 132
Corresponding secondary current is:
437.4
2.916
150
10.S r 10 10 103
IF A 437.38 A
3 .uk .U n 3 132
Corresponding secondary current is (CT Ratio: 150/1A as per Tender documents):
437.38
2.92
150
40000
266.67 A
150
Vkn 220V
Vs I f RCT 2RL
V I R 2R
s f CT L
If : Maximum secondary external fault current
RCT : Resistance of the current transformer secondary winding
RL : Resistance of a sigle wire from the rely to the CT
A stabilizing resistor RST can be used in series with the relay circuit in order to improve the stability of
the relay under external fault conditions. This resistor will limit the spill current under Is.
Vs = Is × (RST)
Is : Current relay setting
Vs : Stability Voltage setting
Vs If A C T V
Where is:
IF = Max. primary current for which stability is required
= 10 times rated current of protected winding as per clause 5.5.2 (ii) of ESI 48-3
10 10 103
= A 437.39 A
3 132
a.2) Consider an external phase to earth short circuit and assume complete saturation of the neutral
current transformer, then Vs shall be not less than
Vs I B DT V
f
1
Vs 437.39 0.75 1.08 1.08 8.49V
150
a.3)Considering an external phase to phase short circuit and assume complete saturation of a line CT,
then Vs shall be not less than
Vs I AT V
f
1
Vs 437.39 0.75 1.08 5.34V
150
a.4)Considering an external 3 phase short circuit and assume complete saturation of a line CT, then Vs
shall be not less than
Vs I B T V
f
1
Vs 437.39 0.75 1.08 5.34V
150
From above calculations, Itemsa.1, a.2, a.3 and a.4 refer, the stability voltage setting should be
considered as follows:
Hence, Vs 10V For can be considered respectively
f) Knee Point Voltage (Vk)
As per ESI 48-3, the minimum current transformer knee point voltage is:
1
T = Turns ratio=
150
Hence Vk > 450 V and Vs = 10 V
Im = Metrosil current = 1mA
Il & In = Line & Neutral CT Magnetizing current at Vs = < 2.5mA
IOP = [0.03 + 0.0025 + 3*0.005 + 0.001] x 150 = 6.15A
Approximately 14.1 % of the rated current of the protected winding.
Considering Relay setting current = 0.015 A
IOP = [0.01 + 0.01 + 3*0.01 + 0.001] x 150 = 7.65A.
Approximately 17.5 % of the rated current of the protected winding.
Hence, relay current setting will be from 0.002 A to 1.0 A (Adjustable range)
h) Stabilizing Resistor :
As per ESI Standard 48-3 , the required minimum knee-point voltage for CT ratio 150/1 A is VkMin.
2 Vs = 2 x 10 = 20 V. Hence the required stabilizing resistor to assure the minimum required knee-
point voltage is :
The value of series resistance is calculated as follows:
Vs
Rs
Is
The burden of the relay is a small value and it is negligible. Therefore
Rs =Relay Circuit impedance at setting
Is =Selected relay setting current at Vs=10V
P I 2 .R
con con
Where:
Pcon = Resistor continuous power rating
Icon = Continuous resistor current i.e operating current of the relay
R = Resistance
Or
= ( 7.65/150)² x 1000 = 2.6 Watts.
The rms voltage developed across a resistor for a maximum internal fault condition is defined
V 4 V 3 .R.I 1.3
f k fs
Where:
Vf = rms voltage across resistor
Ifs = Maximum secondary fault current which can be calculated from the circuit breaker rating, Ich, if the maximum
internal fault current is not given. The maximum internal fault current is usually the same as the maximum
through fault current.
Ifs = The maximum three phase through fault current
= 10 times rated current of the protected winding
Hence,
Ifs = The max. three phase through fault current.
10 10 103
= A 437.39 A
3 132
Corresponding secondary current is:
437.4
2.916
= 150
Vf 4
4503 333.3 2.92 1.3 709.43
OR
Vf 4
4503 1000 2.92 1.3 933.7
Thus the half second power rating is given by:
P V 2 /R
half f
= 709² / 333.3 = 1510.02 Watts
Or
= 933² / 1000 = 871.8 Watts
Hence selected stabilizing resistor is adequate .
i) Requirement of Metrosil :
The maximum voltage in the absence of CT saturation :
V I T R 2R R R
f F CT L S relay
= 437.4/150 ( 0.75 + 2*1.08 + 333.3+0 ) = 980.4 V
OR = 437.4/150 ( 0.75 + 2*1.08 + 1000 +0 ) = 2924.5 V
The peak to peak voltage developed across relay :
Vp 2 2 V V V
k f k
Where Vk ( Actual Vk of CT )
C. Transformer Feeder :
1. Differential Protection : Example using AREVA MICOM P633:
CT Data for T1L CORE-1:
VA 0.1
= 2
0.1
I nom 12
Ithr = Max. three phase fault current
For 500/1A:
Sr 1 50.103 1
I thr . 1.39 A 1.5 A
3 .uk .U n CT ratio 3 0.315 132 500
For 300/1A:
Sr 1 50.103 1
I thr . 2.31A 2. 5 A
3 .uk .U n CT ratio 3 0.315 132 300
Taking into account the above data, required Vkn is calculated as follows:
Sr 1 50.103 1 3499
If 16. . 16. 7A (for 500/1 A)
3 .U n CT ratio 3 132 500 500
50.103 1 3499
16. 11.66 A (for 300/1 A)
3 132 300 300
Taking into account the above data, required Vkn is calculated as follows:
I 3 FMax 40000
If 80 A (for 500/1 A)
CT ratio 500
40000
133.33 A (for 300/1 A)
300
Taking into account the above data, required Vkn is calculated as follows:
From the above calculation 1 and 2, the required knee point voltage shall be considered as follows:
CT requirements:
Based on the AREVA recommendations for the relay type P63X, the following formulae for the knee
point voltage are applied:
VA 0.1
= 2
0.1
I nom 12
Ithr = Max. three phase through fault current
Sr 1 50.103 1 7637.13
I thr . 2.387 A
3 .uk .U n CT ratio 3 0.315 12 3200 3200
To be on safety side, 2.5 A is considered further in calculation:
Taking into account the above data, required Vkn is calculated as follows:
i) Inrush current
If = 16 times rated current of protected winding
Sr 1 50.103 1 3849.15
If 16. . 16. 12.03 A
3 .U n CT ratio 3 12 3200 3200
Taking into account the above data, required Vkn is calculated as follows:
Vkn 70V
Corrected VA Wdg Res .Isn . Rated ALF
The rated knee point voltage =
1.3
16 15.5 1 20
= =484.62 V
1.3
Therefore, Rated knee point voltage > Required Vk.
Hence the proposed CT core for ratios 3200/1 A is adequate.
The same above note regarding the Low Impedance REF C.T is applicable.
I sn SR
Eal E alreq 30.I nt . RCT RL
I pn I r2
Equation 2:
I sn SR
Eal Ealreq 2.I tf . RCT RL
I pn I r2
Equation 3:
I sn SR
Eal Ealreq If. RCT RL
I pn I r2
Where:
Int = the rated primary current of the power transformer (A)
50.103
= = 218.69 A
3 132
Itf = max. primary fundamental frequency current that passes two main CTs and the power transformer (A)
= 16×218.69=3499.09A
If = max. primary fundamental frequency current that passes two main CTs without passing the power transformer (A)
Equation 1:
I sn SR
Eal E alreq 30.I nt . RCT RL
I pn I r2
1 0.02
Eal Ealreq 30 218.69 0.8 0.75 for CT ratio 500/1 A
500 12
= 20.6 V
1 0.02
Eal Ealreq 30 218.69 0.5 0.75 for CT ratio 300/1 A
300 12
=27.7 V
Equation 2:
I sn SR
Eal Ealreq 2.I tf . RCT RL
I pn I r2
1 0.02
Eal Ealreq 2 3499.09 0.8 0.75 for CT ratio 500/1 A
500 12
= 21.9 V
1 0.02
Eal Ealreq 2 3499.09 0.5 0.75 for CT ratio 300/1 A
300 12
=29.6 V
Equation 3:
I sn SR
Eal Ealreq If. RCT RL
I pn I r2
1 0.02
Eal Ealreq 40000 0.8 0.75 for CT ratio 500/1 A
500 12
= 125.6 V
1 0.02
Eal Ealreq 40000 0.5 0.75 for CT ratio 300/1 A
300 12
=169.3 V
40000
Required limiting factor = 133.33 for CT ratio 300/1 A
300
For CT cables size 4sqmm used in secondary circuits:
CT Description Burden (VA)
11 KV Side :
Proposed current transformer data:
CT ratio: 3200/1A VA: 20
Class: 5P20 Rct: 15.5
As per manufacturer’s recommendation for relay type RET670-ABB, the current transformers for
transformer differential protection must have a rated equivalent secondary e.m.f Eal that is larger the
maximum of the required secondary e.m.f Ealreq below:
Equation 1:
I sn SR
Eal E alreq 30.I nt . RCT RL
I pn I r2
Equation 2:
I sn SR
Eal Ealreq 2.I tf . RCT RL
I pn I r2
Where:
Int = the rated primary current of the power transformer (A)
50.103
= = 2406 A
3 12
Itf = max. primary fundamental frequency current that passes two main CTs and the power transformer (A)
Ipn = the rated primary CT current (A)
Isn = the rated secondary CT current (A)
RCT = the secondary resistance of the CT ( )
RL = the CT secondary loop resistance ( ) =1.8
(For loop resistance, 2×100m cable of 2.5sqmm is considered)
SR = the rated burden=0.02VA
1 0.02
Eal Ealreq 30 2406 15.5 1.8 for CT ration 3200/1 A
3200 12
= 390.6 V
1 0.02
Eal Ealreq 2 2406 15.5 1.8 for CT ration 3200/1 A
3200 12
= 26.04 V
Required knee point voltage, Vk 390.6V
There are no specific requirements on the magnetizing current.
The proposed 5P20, 20VA current transformer is adequate.
D. Bus Coupler:
1. Bus Bar Protection :
A. Low Impedance: Same as the above Line Feeder.
B. High Impedance: Same as the above Line Feeder.
2. O/C & E/F Protection: included in the Bay Control Unit – same as the above Line
Feeder.
3. Breaker Failure Protection: It was not shown as separate protection in the Line
Feeder Protection; it is included as a Function in the Pilot Wire Differential Protection
and the Distance Protection.
Example 1 : Using AREVA MICOM P142 – Breaker Failure Relay:
CT Data for T1L CORE-3:
CT ratio: 3000/1A VA: 30
Class: 5P20 Rct:
I fp
Time-delayed phases overcurrent V k Rct Rl R rp
2
I fn
Time-delayed earth fault overcurrent V k Rct Rl R rn
2
Where
Rl= Connected lead resistance=1.8
40000
Ifp=Max. secondary fault current= 13.33 A
3000
Ifn=Max. secondary fault current=13.33A
Rct=Internal resistance=8
Rrp=Relay burden=0.04 VA
Rrn= Relay burden=0.04 VA
Hence,
Phase overcurrent
13.33
Vk 8 1.8 0.04 65.58V
2
Earth fault overcurrent
13.33
Vk 8 1.8 0.04 65.58V
2
Corrected VA Wdg Res .Isn . Rated ALF
The rated knee point voltage =
1.3
Corrected VA = 30/1.25 = 24 VA
24 8 1 20
= =492.3 V
1.3
Therefore, Rated knee point voltage > Required Vk.
Hence , C.T is adequate and suitably sized.
Example 2: using SIEMENS Type 7SJ64: with the same above C.T Data:
Hence,
40000
Vk 8 1.85 1 101.02V
1.3 3000
Corrected VA Wdg Res .Isn . Rated ALF
The rated knee point voltage =
1.3
Corrected VA = 30/1.25 = 24 VA
24 8 1 20
= =492.3 V
1.3
Therefore, Rated knee point voltage > Required Vk.
Hence, C.T is adequate and suitably sized.
Choice of Measuring CT
• For classes 0.1 – 1, the accuracy is based on a total connected burden between 25% to 100% of the
rated burden
• For classes 0.1, 0.2 and 0.2S with rated burden < 15VA, an extended range of burden can be
specified (from 1VA to 100% of the rated burden)
Dimensioning factor (Kx) :
a factor assigned by the purchaser to indicate the multiple of rated secondary current (Isn) occurring
under power system fault conditions, inclusive of safety factors, up to which the transformer is required
to meet performance requirements".
CT – Magnetizing Curve
Rated knee point e.m.f. (Ek) :
That minimum sinusoidal e.m.f. (r.m.s.) at rated power frequency when applied to the secondary
terminals of the transformer, all other terminals being open-circuited, which when increased by 10 %
causes the r.m.s. exciting current to increase by no more than 50 %
NOTE The actual knee point e.m.f. will be the rated knee point e.m.f.
NOTE The rated knee point e.m.f. is generally determined as follows:
Ek = Kx × (Rct + Rb) × Isn
Where (Kx) is the dimensioning factor .
2 2
Z Ri Rb Xb
The inductive flux density necessary for inducing the voltage Esi can be calculated from
E
B si
2 f A N
i 2
where:
A = core area in m2
B = ux density in Tesla (T)
f = frequency
N2 = number of secondary turns
nf K ssc K td
The secondary core will be designed on the basis of the Kssc (AC- ux) and Ktd (DC ux).Typical value of
Ktd is 10 - 25.
For special measurement of fault current (transient current,) including both a.c. and
d.c. components, IEC 60044-6 defines the accuracy classes TPX, TPY and TPZ.
The cores must be designed according to the transient current:
• TPX cores have no requirements for remanence flux and have no air gaps.
• TPY cores have requirements for remanence flux and are provided with small air gaps.
• TPZ cores have specific requirements for phase displacement and the air gaps will be large.
Typical secondary time constants are for
• TPX core 5 - 20 seconds (no air gaps)
• TPY core 0.5 - 2 seconds (small air gaps)
• TPZ core ~ 60 msec. (phase displacement 180 min.+/- 10%) (large air gaps)Air gaps in the
core give a shorter Ts.
Factors affecting CT saturation
CT ratio : Over Dimensioning of the C.T ratio
Core cross-sectional area
Core design
Connected burden : If the Load Burden is lower than the Rated Burden (<25% ) , the Saturation
value increases
B-H characteristic of core
Amount of remanent flux : In most cases the CTs will have some remanence, which can
increase the saturation rate of the CTs.
Fault current & DC offset : If a CT has been saturated the secondary current will not recover
until the DC-component in the primary fault current has subsided.
System time constant
CT primary may be in earthed position.
CT internal winding may be short circuit and Winding resistance is less than designed value.
Annex – A : Composite error
Under steady-state conditions, the r.m.s. value of the difference between:
a) the instantaneous values of the primary current; and
b) the instantaneous values of the actual secondary current multiplied by the rated transformation ratio,
the positive signs of the primary and secondary currents corresponding to the convention for terminal
markings
The composite error Ec is generally expressed as a percentage of the r.m.s. values of the primary
current according to the formula:
T
100 1 2
K n is i p .dt
Ip T 0
Use of composite error
The numeric value of the composite error will never be less than the vector sum of the current error and
the phase displacement (the latter being expressed in centiradians).
Consequently, the composite error always indicates the highest possible value of current error or phase
displacement.
S n Rct I sn2
n Fs
S Rct I sn2
where
Sn = rated burden in VA
S = actual burden in VA
Isn = rated secondary current in A
Rct = internal resistance at 75ºC in ohm
To ful ll high accuracy classes (e.g. class 0.2, IEC) the magnetizing current in the
core must be kept at a low value. The consequence is a low ux density in the
core. High accuracy and a low number of ampere-turns result in a high saturation factor (FS). To ful ll
high accuracy with low saturation factor the core is usually made of nickel alloyed steel.
NOTE! The accuracy class will not be guaranteed for burdens above rated burden or below 25% of the
rated burden (IEC).
With modern meters and instruments with low consumption the total burden can
be lower than 25% of the rated burden (see Figure 2.1). Due to turns correction and core material the
error may increase at lower burdens. To ful ll accuracy requirements the rated burden of the metering
core shall thus be relatively well matched to the actual burden connected. The minimum error is
typically at 75% of the rated burden. The best way to optimize the core regarding accuracy is
consequently to specify a rated burden of 1.5 times the actual burden.
It is also possible to connect an additional burden, a “dummy burden”, and in this way adapt the
connected burden to the rated burden. However, this method is rather inconvenient.
The shunt reactor is normally connected to the transmission line to avoid excess over voltage
appearance when the load decreases at night and off days. Since the substations in the urban
areas mostly have the transmission lines of small short-circuit capacities, the line voltages fluctuate
largely when the shunt reactor of a large capacity is connected or disconnected.
Shunt reactors carry out different types of tasks:
They compensate the capacitive reactive power of the transmission cables, in particular in
networks with only light loads or no load.
They reduce system-frequency over-voltages when a sudden load drop occurs or there is no
load.
They improve the stability and efficiency of the energy transmission.
Reactors to limit over-voltages are most needed in weak power systems, i.e. when network short-circuit
power is relatively low.
Mostly problems occur on gas-insulated circuit breaker for shunt reactor switching. The frequent
switching of the SF6 CB for shunt reactors degraded gas insulation level. The melted contacts, in turn,
could not clear the current prospectively. Meanwhile, the high rise rate of transient recovery voltage of
inductive current switching caused re-striking phenomenon and incomplete tripping. These two main
characteristics make the SF6 CB used for shunt reactor un-expectantly damaged .
Therefore “ Separate Type Test Report from Accredited Testing Laboratory shall be submitted
for the proposed C.B Type for Shunt Reactor or Shunt Capacitor banks Switching .”
The unavoidable high frequency transient recovery voltage (TRV) existed in circuit breakers due
to inductive switching can be depressed to reasonable and safely level by equipping suitable
arrestor. The maintenance policy for the breakers should be planned based on a fixed period
maintenance schedule or conditional basic maintenance schedule. Finally, the circuit breaker
should be re-flashed after every 500 switching operations to maintain the power system normally
Typically, the voltage variation at the high voltage bus bar after switching of a shunt reactor shall not be
higher than 2 to 3% of rated voltage.
MAIN CALCULATION OF SHUNT REACTORS: All the shunt reactor data and rating will be
given in the contract specifications, this summary is just for information.
For the calculation of the positive sequence reactance and the current requirements of a shunt
reactor, it is necessary to know only the rated three-phase reactive power and the rated system
voltage and frequency, as summarized in the table below.
So, the relation between the ending voltages of the transmission line is given by:
B ZY L
V1 A'.V2 V1 A .V2 V1 1 .V2
XR 2 LR
Application Example
Consider a lossless radial transmission line, frequency 60 Hz, length = 350 km, and parameters z = j
0,32886 /km and bC = j 5,097 µS/km. To estimate the reactive power of shunt reactors to be installed
in the transmission line to provide a maximum operating voltage of 1.05 pu at the open-circuited
terminal (receiving ending), when the line is energized with 1.0 pu in the sending ending.
Solution:
Total impedance and admittance of the non-compensated transmission line
Z j(z. ) j115.1
Y j(bc . ) j1783.95 S
Parameter A:
ZY
A 1 0.8973
2
Operating voltage at the receiving ending of the non- compensated transmission line
1
V2 .V1 1.1144.V1
0.8973
Calculation of the shunt reactor reactance:
ZY L
V1 1 .V2
2 LR
115.1
1.0 0.8973 .1.05
XR
115.1
XR 2090
1.0
0.8973
1.05
Calculation of the three-phase reactive power of the shunt reactor:
U N2 5252
S R3 132 MVAr
XR 2090
Calculation of the three-phase reactive power of the shunt reactor:
S R3
K SH 2. 54%
QC3
A practical circuit is used to simplify the analysis of voltage control (see picture below). The
determination of the shunt reactor to provide a required voltage variation in the bus bar can calculated
through the short-circuit power of system at the bus bar where the reactor will be connected.
V1 V1 V 2
V2 S R3 S CC
S R3 V2
1
S CC
Application Example:
To estimate the reactive power of shunt reactors to be installed in the 34.5kV busbar in order to
reduce the voltage level from 1.02 to 0.99pu, considering a fault current of 25kA (or short circuit
power of 1495MVA).
1.02 0.99
S R3 1485 45MVAr
0.99
Reference Documents :
IEC 60044 – 1 & IEC 60044 – 6 .
ESI Standard 48-3 : Instantaneous High Impedance Differential Protection , December
1977 .
ABB : Instrument Transformers Application Guide .
Siemens : C.T Dimensioning .
AREVA : Tech. News : Shunt Reactors in Power Systems .
Different Contractors Submittals for Different Projects in different countries which were
reviewed by us , commented , revised & re-submitted till approved .