7sj Manual
7sj Manual
7sj Manual
SIPROTEC 7SJ600
Numerical Overcurrent, Motor and Overload Protection Relay
Function overview
Feeder protection
• Overcurrent-time protection
• Earth-fault protection
• Overload protection
• Negative-sequence protection
• Cold load pickup
• Auto-reclosure
• Trip circuit supervision
LSP2001-afpen.tif
Motor protection
• Starting time supervision
• Locked rotor
Control functions
• Commands for control of a circuit- 5
Fig. 5/19 SIPROTEC 7SJ600 breaker
numerical overcurrent, motor and overload protection relay • Control via keyboard,
DIGSI 4 or SCADA system
Measuring functions
• Operational measured values I
Description
Monitoring functions
The SIPROTEC 7SJ600 is a numerical • Fault event logging with time stamp
overcurrent relay which, in addition to its (buffered)
primary use in radial distribution networks • 8 oscillographic fault records
and motor protection, can also be em-
• Continuous self-monitoring
ployed as backup for feeder, transformer
and generator differential protection. Communication
The SIPROTEC 7SJ600 provides defi- • Via personal computer and DIGSI 3 or
nite-time and inverse-time overcurrent DIGSI 4 (≥ 4.3)
protection along with overload and nega- • Via RS232 – RS485 converter
tive-sequence protection for a very com- • Via modem
prehensive relay package. In this way, • IEC 60870-5-103 protocol, 2 kV-isolated
equipment such as motors can be pro-
• RS485 interface
tected against asymmetric and excessive
loading. Asymmetric short-circuits with Hardware
currents that can be smaller than the larg- •3 current transformers
est possible load currents or phase inter-
•3 binary inputs
ruptions are reliably detected.
•3 output relays
•1 live status contact
Application
Inverse-time characteristics
In addition, invese-time overcurrent pro-
tection characteristics (IDMTL) can be ac-
LSP2002-afpen.tif
tivated.
Fig. 5/21
Rear view of flush-mounting housing
Fig. 5/23
Inverse-time overcurrent characteristic
Protection functions
Switch-onto-fault protection
If switched onto a fault, instantaneous trip-
ping can be effected. If the internal control
function is used (local or via serial inter-
face), the manual closing function is avail-
able without any additional wiring. If the
control switch is connected to a cir-
cuit-breaker bypassing the internal control
function, manual detection using a binary
input is implemented.
Busbar protection
(Reverse interlocking)
Binary inputs can be used to block any of
the six current stages. Parameters are as-
signed to decide whether the input circuit
is to operate in open-circuit or closed-cir- 5
cuit mode. In this case, reverse interlocking
provides high-speed busbar protection in
radial or ring power systems that are
opened at one point. The reverse interlock-
ing principle is used, for example, in me-
dium-voltage power systems and in
switchgear for power plants, where a
high-voltage system transformer feeds a
busbar section with several medium-volt-
age outgoing feeders. Fig. 5/25 Reverse interlocking
Connection diagrams
Fig. 5/29
Fig. 5/30
Connection of 2 CTs only for isolated or
Sensitive earth-fault protection
resonant-earthed (grounded) power systems
(3 -times increased sensitivity)
Technical data
Technical data
EMC tests for interference immunity; type tests Mechanical stress tests
Standards IEC 60255-6; IEC 60255-22 Vibration, shock and seismic vibration
(product standard) During operation
EN 50082-2 (generic standard),
DIN VDE 0435 Part 303 Standards Acc. to IEC 60255-2-1 and
IEC 60068-2
High-frequency test 2.5 kV (peak), 1 MHz, τ = 15 μs,
IEC 60255-22-1, class III 400 surges/s, duration 2 s Vibration Sinusoidal 10 to 60 Hz: ± 0.035 mm
IEC 60255-21-1, class1 amplitude, 60 to 150 Hz: 0.5 g accel-
Electrostatic discharge 4 kV/6 kV contact discharge, IEC 60068-2-6 eration
IEC 60255-22-2, class III 8 kV air discharge, both polarities, Sweep rate 1 octave/min
and IEC 61000-4-2, class III 150 pF, Ri=330 Ω 20 cycles in 3 orthogonal axes
Irradiation with radio-frequency Shock Half-sine, acceleration 5 g, duration
field IEC 60255-21-2, class 1 11 ms, 3 shocks in each direction of 3
Non-modulated, 10 V/m, 27 to 500 MHz orthogonal axes
IEC 60255-22-3 (report) class III
Amplitude modulated, 10 V/m, 80 to 1000 MHz, Seismic vibration Sinusoidal
IEC 61000-4-3, class III 80 % AM, 1 kHz IEC 60255-21-3, class 1, 1 to 8 Hz: ± 3.5 mm amplitude
Pulse modulated, 10 V/m, 900 MHz, repetition IEC 60068-3-3 (horizontal axis)
IEC 61000-4-3, class III frequency, 200 Hz, duty cycle 50 % 1 to 8 Hz: ± 1.5 mm amplitude
5 (vertical axis)
Fast transient interference/bursts 2 kV, 5/50 ns, 5 kHz, burst length 8 to 35 Hz: 1 g acceleration
IEC 60255-22-4 and 15 ms, repetition rate 300 ms, both (horizontal axis)
IEC 61000-4-4, class III polarities, Ri = 50 Ω, duration 1 min 8 to 35 Hz: 0.5 g acceleration
Conducted disturbances induced by 10 V, 150 kHz to 80 MHz, (vertical axis)
radio-frequency fields, 80 % AM, 1 kHz Sweep rate 1 octave/min
amplitude modulated 1 cycle in 3 orthogonal axes
IEC 601000-4-6, class III During transport
Power frequency magnetic field 30 A/m continuous, 50 Hz Vibration Sinusoidal
IEC 61000-4-8, class IV 300 A/m for 3 s, 50 Hz IEC 60255-21-1, class 2 5 to 8 Hz: ± 7.5 mm amplitude;
IEC 60255-6 0.5 mT; 50 Hz IEC 60068-2-6 8 to 150 Hz: 2 g acceleration
Oscillatory surge withstand 2.5 to 3 kV (peak), 1 MHz to Sweep rate 1 octave/min
capability ANSI/IEEE C37.90.1 1.5 MHz, decaying oscillation, 50 shots 20 cycles in 3 orthogonal axes
(common mode) per s, duration 2 s, Ri = 150 Ω Shock Half-sine, acceleration 15 g ,
to 200 Ω IEC 60255-21-2, class 1 duration 11 ms, 3 shocks in each
Fast transient surge withstand 4 to 5 kV, 10/150 ns, 50 surges IEC 60068-2-27 direction of 3 orthogonal axes
capability ANSI/IEEE C37.90.1 per s, both polarities, duration 2 s, Continuous shock Half-sine, acceleration 10 g
(commom mode) Ri = 80 Ω IEC 60255-21-2, class 1 duration 16 ms, 1000 shocks in each
Radiated electromagnetic interfer- 10 to 20 V/m, 25 to 1000 MHz, IEC 60068-2-29 direction of 3 orthogonal axes
ence, ANSI/IEEE C37.90.2 amplitude and pulse-modulated
High-frequency test 2.5 kV (peak, alternating polarity), Climatic stress tests
Document 17C (SEC) 102 100 kHz, 1 MHz, 10 MHz and
50 MHz, decaying oscillation, Temperatures
Ri = 50 Ω Recommended temperature
EMC tests for interference emission; type tests during operation –5 °C to +55 °C / +23 °F to +131 °F
> 55 °C decreased display contrast
Standard EN 50081-* (generic standard)
Permissible temperature
Conducted interference voltage, aux. 150 kHz to 30 MHz
during operation –20 °C to +70 °C / –4 °F to +158 °F
voltage CISPR 22, EN 55022,
during storage –25 °C to +55 °C / –13 °F to +131 °F
DIN VDE 0878 Part 22,
during transport –25 °C to +70 °C / –13 °F to +158 °F
limit value class B
(Storage and transport with
Interference field strength 30 to 1000 MHz standard works packaging)
CISPR 11, EN 55011, DIN VDE
Humidity
0875 Part 11, limit value class A
Mean value per year ≤ 75 % relative
humidity, on 30 days per year
95 % relative humidity,
condensation not permissible
Technical data
Functions Tolerances
Definite-time overcurrent protection (ANSI 50, 50N) Pickup values 5%
Delay time for 2 ≤ I/Ip ≤ 20 5 % of theoretical value ± 2 %
Setting range/steps and 0.5 ≤ I/IN ≤ 24 current tolerance, at least 30 ms
Overcurrent pickup phase I> I/IN = 0.1 to 25 (steps 0.1), or ∞
earth IE> = 0.05 to 25 (steps 0.01), or ∞ Influencing variables
phase I>> I/IN = 0.1 to 25 (steps 0.1), or ∞ Auxiliary voltage, range: ≤1%
earth IE>> = 0.05 to 25 (steps 0.01), or ∞ 0.8 ≤ Vaux/VauxN ≤ 1.2
phase I>>> I/IN = 0.3 to 12.5 (steps 0.1), or ∞ Temperature, range: ≤ 0.5 %/10 K
-5 °C ≤ Θamb ≤ 40 °C
Delay times T for I>, IE>, I>> 0 s to 60 s (steps 0.01 s) +23 °F ≤ Θamb ≤ 104 °F
and IE>> Frequency, range: ≤ 8 % referred to theoretical time
The set times are pure delay times 0.95 ≤ f/fN ≤ 1.05 value
Pickup times I>, I>>, IE>, IE>> Negative-sequence overcurrent protection (ANSI 46)
At 2 x setting value, without Approx. 35 ms
meas. repetition Setting range/steps
At 2 x setting value, with meas. Approx. 50 ms Tripping stage 8 % to 80 % of IN
repetition I2> in steps of 1 % 8 % to 80 % of IN
Pickup times for I>>> at 2 x I2>> in steps of 1 %
Approx. 20 ms Time delays T(I2>), T(I2>>) 0.00 s to 60.00 s
setting value
in steps of 0.01s 5
Reset times I>, I>>, IE>, IE> Approx. 35 ms Lower function limit At least one phase current ≥ 0.1 x IN
I>>> Approx. 65 ms
Pickup times At fN = 50 Hz 60 Hz
Reset ratios Approx. 0.95 Tripping stage I2>, tripping Approx. 60 ms 75 ms
Overshot time Approx. 25 ms stage I2>>
But with currents I/IN>1.5 Approx. 200 ms 310 ms
Tolerances
(overcurrent case) or
Pickup values I>, I>>, I>>>, 5 % of setting value
negative-sequence current
IE>, IE>>
< (set value +0.1 x IN)
Delay times T 1 % of setting value or 10 ms
Reset times At fN = 50 Hz 60 Hz
Influencing variables
Tripping stage I2>, Approx. 35 ms 42 ms
Auxiliary voltage, range: ≤1%
tripping stage I2>>
0.8 ≤ Vaux /VauxN ≤ 1.2
Temperature, range: ≤ 0.5 %/10 K Reset ratios
0 °C ≤ Θamb ≤ 40 °C Tripping stage I2>, Approx. 0.95 to 0.01 x IN
Frequency, range: ≤ 1.5 % tripping stage I2>>
0.98 ≤ f/fN ≤ 1.02 Tolerances
Frequency, range: ≤ 2.5 % Pickup values I2>, I2>>
0.95 ≤ f/fN ≤ 1.05 with current I/IN ≤ 1.5 ± 1 % of IN ± 5 % of set value
Harmonics with current I/IN > 1.5 ± 5 % of IN ± 5 % of set value
Up to 10 % of 3rd harmonic ≤1% Stage delay times ± 1 % or 10 ms
Up to 10 % of 5th harmonic ≤1%
Influence variables
Inverse-time overcurrent protection (ANSI 51/51N) Auxiliary DC voltage, range: ≤1%
Setting range/steps 0.8 ≤Vaux /VauxN ≤ 1.2
Overcurrent pickup phase Ip I/IN = 0.1 to 4 (steps 0.1) Temperature, range: ≤ 0.5 %/10 K
earth IEp = 0.05 to 4 (steps 0.01) –5 °C ≤ Θamb ≤ +40 °C
+23 °F ≤ Θamb ≤ +104 °F
Time multiplier for Ip, IEp (IEC charac.) 0.05 to 3.2 s
Frequency,
Tp (steps 0.01 s)
range: 0.98 ≤ f/fN ≤ 1.02 ≤ 2 % of IN
(ANSI charac.) 0.5 to 15 s
range: 0.95 ≤ f/fN ≤ 1.05 ≤ 5 % of IN
(steps 0.1 s)
Auto-reclosure (option) (ANSI 79)
Overcurrent pickup phase I>> I/IN = 0.1 to 25 (steps 0.1), or ∞
phase I>>> = 0.3 to 12.5 (steps 0.1), or ∞ Number of possible shots 1 up to 9
earth IE>> = 0.05 to 25 Auto-reclose modes 3-pole
(steps 0.01), or ∞ Dead times for 1st to 3rd shot 0.05 s to 1800 s (steps 0.01 s)
Delay time T for I>>, IE>> 0 s to 60 s (steps 0.01 s) for 4th and any further 0.05 s to 1800 s (steps 0.01 s)
shot
Tripping time characteristics acc. to IEC
Reclaim time after successful AR 0.05 s to 320 s (steps 0.01 s)
Pickup threshold Approx. 1.1 x Ip
Drop-out threshold Approx. 1.03 x Ip Lock-out time after 0.05 s to 320 s (steps 0.01 s)
Drop-out time Approx. 35 ms unsuccessful AR
Tripping time characteristics acc. to ANSI / IEEE Reclaim time after manual close 0.50 s to 320 s (steps 0.01 s)
Pickup threshold Approx. 1.06 x Ip Duration of RECLOSE command 0.01s to 60 s (steps 0.01 s)
Drop-out threshold, Approx. 1.03 x Ip Control
alternatively: disk emulation
Number of devices 1
Evaluation of breaker control None
Technical data
Unit design
For panel surface mounting, terminals on the side B
For panel flush mounting/cubicle mounting E
Languages
English, German, Spanish, French, Russian 0 5
Auto-reclosure (option)
Without 0
With 1
Control
Without A
With B
UL-Listing
Without UL-listing 0
With UL-listing 1
Converter, full-duplex,
fiber-optic cable RS485 with built-in power supply unit
Auxiliary voltage 24 to 250 V DC and 110/230 V AC 7XV5650- 0BA00
LSP2289-afp.eps
Sample order
7SJ600, 1 A, 60 - 125 V, flush mounting, ARC 7SJ6001-4EA00-1DA0
Converter V.24 -RS485, 230 V AC 7XV5700-0AA00
1) Rated current can be selected by
means of jumpers.
Manual, English C53000-G1176-C106-7
2) Transition between the two auxiliary
voltage ranges can be selected by
means of jumpers.
3) Only when position 16 is not “1” (with UL-listing).
4) Possible versions see part 15.
* RS485 bus system up to 115 kbaud
RS485 bus cable and adaptor 7XV5103-oAAoo;
see part 15.
Connection diagram
Fig. 5/32
Connection diagram according to IEC standard
Fig. 17/15
Housing for panel flush mounting/
cubicle mounting, terminals at rear (1/6 x 19")
Fig. 17/16
Housing for surface mounting,
terminals at top and bottom (1/6 x 19")
Fig. 17/17
Housing for panel surface mounting, terminals on
the side (1/6 x 19")