0% found this document useful (0 votes)
215 views

Generator Protection

The document discusses various types of electrical protection systems. It describes protection for buses, transformers, motors, and generators. The key purposes of protection systems are to minimize damage from faults, leave unaffected equipment in service, maintain operating limits, and ensure system stability. Protection devices discussed include overcurrent, differential, backup, undervoltage, instantaneous, thermal overload, and ground fault relays. Zones of protection and duplicate schemes are also covered.

Uploaded by

karthik
Copyright
© Attribution Non-Commercial (BY-NC)
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
215 views

Generator Protection

The document discusses various types of electrical protection systems. It describes protection for buses, transformers, motors, and generators. The key purposes of protection systems are to minimize damage from faults, leave unaffected equipment in service, maintain operating limits, and ensure system stability. Protection devices discussed include overcurrent, differential, backup, undervoltage, instantaneous, thermal overload, and ground fault relays. Zones of protection and duplicate schemes are also covered.

Uploaded by

karthik
Copyright
© Attribution Non-Commercial (BY-NC)
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 69

Electrical Protection

Electrical Faults
• Phase to phase
• Phase to ground
• Phase to phase to phase
• Phase to phase to phase to ground
Purpose of Protection System
• Minimize damage
• Leave unaffected equipment in-service
• Maintain equipment operating limits
• Maintain electrical system stability
Requirements of a Protection
System
• Speed
• Reliability
• Security
• Sensitivity
Some terms
• Over-current
• Overload
• Inverse time
Protection Zones
Simple Zone
Double Protection
Circuit Circuit
Breaker Breaker
Bus Zone X Y

CT CT CT CT Bus CT CT CT CT
1 2 3 4 4 3 2 1
"B" Bus Protection

"A" Bus Protection


Bus Zone H2 Bus Zone H3
Bus Zone H1
Bus x Y Bus
H2 Bus H1 H3

Zone
T1 Transformer
Zone T1
SST1

SST1 Bus L1 Bus Zone L1


Protection
Zones
LV Bus
Transformer
SST1

Zone
G1 G1
Breaker Failure
• Minimizes the amount of equipment
removed from service in event of a failure
• Failure Determination
– Not started opening in a certain time
– Not open in a certain time
– Current not broken in a certain time
Duplicate Protection Schemes
CT CT
1 2 Electrical
Electrical bus
System
PT
System
Input

A Protection B Protection
Protection
Logic

Initiate Trip Close Initiate Trip Close Protection


Output

Action Q Breaker X Breaker Y Device Z Electrical


Devices
Bus Protection
Bus Protection
• Over-current
• Differential
• Back-up
• Under voltage
Over-current Relay

CT 2000/5 A

I 1P

I 1S
Differential Protection
I = 1P
I = 2P
I

CT1 2000/5 A X Bus Y


CT2 2000/5 A
H1
I 1P I 2P
I = 1S
I = 2S
I
I 1S I 2S

I 1S I 2S

I = 1S
I = 2S
I
Fault Conditions
Fault

CT1 2000/5 A X Bus Y CT2 2000/5 A


H1
I1P I2P

I1S I2S

I1S I2S
X Bus Y
CT 2000/5 A CT 2000/5 A
H1
I 1P I 2P
I 3P
I 1S I 2S
I 3S
CT 2000/5 A

T1
I3S

I 1S I 2S
Bus Protection Scheme
Bus Differential Backup

X Zone L1
T1
Load
Bus L1
S

Y Zone L2
Load
L2
Back-up relay
Over Current
Backup Relay Differential
Relay

X
T1
Load
Bus L1
S

Y
Load
L2
Bus Under Voltage Protection
Armature shown in the non-energized (trip) position

Normally
Open
Contacts

To Potential
Transformer
Bus Protection
• Over-current
• Differential
• Back-up
• Under voltage
Transformer Protection
Transformer Protection
• Instantaneous
• Differential
• Gas
• Thermal Overload
• Ground
Transformer Characteristics
• High magnetizing inrush currents
• Ratio mismatch with CTs aggravated by
tap-changers
• Phase shifts
• Transformers are affected by over-fluxing
• Affected by over-temperature
Transformer Zone
T1 Zone

T1

CT CT CT CT CT CT CT CT
1 2 3 4 4 3 2 1
"B" Transformer Protection

"A" Transformer Protection


Differential
T1

CT1 CT2

I 1P I 2P

I 1S Restraint Restraint I 2S
Coil Coil

I 1S Operate
I 2S
Coil

I = 1S
I = 2S
I
Gas Relay
Winding Temperature
Ground Fault Protection
T1
CT2
CT1
IN

IF
CT3 Differential
Relay

Transformer
Star Point

Ground Ground
CT Backup

IN
Transformer Protection
• Instantaneous
• Differential
• Gas
• Thermal Overload
• Ground
Motor Protection
Service Factor
• Continuous allowable overload
– Many motors some with a power rating and a
service factor
– A 10 HP motor with a service factor of 1.15
has a maximum continuous output of 11.5 HP
Motor Protection Summary
• Instantaneous Over-current
• Stall
• Thermal Overload
• Phase Unbalance
• Ground
Inverse
Time
Relay
Overload
Ground Fault Protection
Single Phase to Ground
Protection
Stalls
Thermal Overload & Phase
Unbalance
Diagram of the Unit
Rotation as Elements Heat/Co ol
Load Indicating Po inter
Phase Unbalance Contacts
Heater Adjus table Overload Contact
(electrical
connectio ns no t
s ho wn) Overload
Setting
Po inter

Actuating Bimetal

Ambient Co mpensating Bimetal


Shaft

Heat Shield
Motor Protection Summary
• Instantaneous Over-current
• Stall
• Thermal Overload
• Phase Unbalance
• Ground
Generator Protection
Classes of TG trips
• Class A
– Trip generator breaker, field breaker and
turbine
– Electrical trips before the output breakers
• Class B
– Trip generator output but leave it supplying
station service
– Electrical faults in the switchyard
Classes of TG trips
• Class C
– Over excitation high V/Hz
– Only used when generator is isolated from grid
• Class D
– Trip turbine
– Trip Generator after motoring is detected
– Mechanical type turbine trips high condenser pressure
Generator Protection
• Over-current
• Overload
• Differential
• Split phase differential
• Ground
• Rotor ground
• Phase Unbalance
• Low field
• Under frequency
• Out of Step
• Reverse power
Ge ne rator Terminals

R W B

Diffe re ntial
Relay

Prote ction
Zo ne s

Ne utral Co nne c tion


to Gro und

a) He althy Phas e b) Faulted Phas e c ) Ope n Circ uit in


the Phas e
Differential
Generator
Star Point
IP = I1P = I2P
I 1P
G1 To Main
CT1 CT2 Transformer

I 2P

I 1S Restraint Restraint I 2S
Coil Coil

Operate
I 1S Coil
I 2S

Is = I1S = I2S
Ground Fault Protection
T1

G1

GT1

Stator Ground
Relay
IF
Rotor Ground Fault
Other Protections
• Phase Unbalance
• Loss of field
• Under frequency
• Out of Step
Reverse Power

V.T.
Re ve rse
Powe r
Re aly
Generator Protection
• Over-current
• Overload
• Differential
• Split phase differential
• Ground
• Rotor ground
• Phase Unbalance
• Low field
• Under frequency
• Out of Step
• Reverse power
For You To Do

You might also like