HVAC Design 1
HVAC Design 1
HVAC Design 1
Part
ETone
Estimate Space Cooling Load
Simplified method for determining the space
cooling load
Cooling load factor
Residential 1cfm/sf
Office 1.2 cfm/sf
School 1.5 cfm/sf
Aud. / theater 2.5 cfm/sf
ventilation load not included
ETone
Estimate Space Cooling Load Example
ETone
Estimate Ventilation Load
Ventilation Requirements
Ventilation factor
Residential 10 cfm/person
Office 20 cfm/person
School 15 cfm/person
Aud. / theater 15 cfm/person
adds to the space cooling load
ETone
Estimate Ventilation Load Example
ETone
Estimate Total Supply Air Example
ETone
Estimate Equipment Sizes Example
1,575 cfm
VAV box sizes
required at each zone for temperature control
total air
See course handout required
•
Table reprinted from Architectureal Graphic Standards
ETone
Estimate Equipment Sizes Example
Air Handler Unit Sizes 6,300 cfm
Supply air to multiple zones required
See course handout
ETone
Estimate Equipment Sizes
Calculating the refrigeration required
Converting air flow quantities to tons of cooling required
Total CFM
6,300 CFM per AHU
ETone
Estimate Ventilation Load
Ventilation Sensible
based on the )t between cooling coil and outside temp
ETone
Estimate Ventilation Load
Ventilation Latent
based on the )w between cooling coil and outside temp
ETone
Estimate Ventilation Load
Ventilation Total Load
Qtotal ventilation
ETone
Estimate Equipment Sizes Example
ETone
Estimate Equipment Sizes Example
ETone
Estimate Equipment Sizes Example
484 tons
Cooling Tower Size of cooling
Based on tons of cooling required
required
•
Table reprinted from Architectureal Graphic Standards
ETone
System Design
Revise basic layout adding equipment sizes
ETone
Review
ETone
HVAC System Design
Simplified Method for Early Design Environmental
Technology 1
Part