Distance Protection Part 3
Distance Protection Part 3
(21Z)
ZULKARNAIN BIN ISHAK
TECHNICAL EXPERT
ENGINEERING DEPARTMENT
TNB TRANSMISSION
Directional Decision by
Phase Angle Comparison (2)
direction. S1
Power equation
P =VI Cos (θ) S2
S2
S2
S2
S2
S2
S2
Contents – Part 3
9Distance Teleprotection Scheme
9Under-reach and Over-reach Effect
9Setting Calculation Example
9Voltage Transformer Supervision (VTS) Function
9Switch On To Fault (SOTF) Function
9Power Swing Blocking (PSB) Function
9.0 Distance
Teleprotection Scheme
XPermissive Underreach Scheme
XBlocking Scheme
Permissive Underreach
Scheme
Teleprotection
– Distance with Communication Signal
XBlocking Scheme
Permissive Underreach Scheme
X Applying basic step distance will caused the last 10-20% of line
not covered by Zone 1 (Instantaneous tripping).
Z2G
Z1G
K H
J G
Z1H
F Z2G
Permissive Underreach Scheme
J G
Z1H
F Z2G
Signal
send
Z1
Tx Signal
send
Tx Z1
Z2 Z2T 0 Z2
Z2T 0
Z3T 0 Z3
Z3 Z3T 0 ≥1 Trip Trip ≥1
Signal
receive
0 T & & 0 T Signal
receive
Rx Rx
Permissive Underreach Scheme
A B
z If signal send from C
resets before relay D
operates then aided
C D tripping will not occur
Fault
21 21 z To prevent this a
Rx + Z2 delayed on drop off
(normally 100ms) of the
signal send is used in
the scheme logic
Permissive Underreach Transfer Trip -
Advantages
Z1H Z1J
H K L
G J
F
Z1K
Z2K
X POR utilized the zone with overreach setting (e.g. Zone 2) to issue
permissive signal for instantaneous operation of the distance zone at
remote end station.
X Distance relay at J and K will trip instantaneously for fault at F1.
X Without permissive signal, Zone 2 (Z2K) will operate with delayed time (e.g.
fault at F2). Z2J
H K L
G J
F2 F1
Z2K
Z1 Tx Signal Signal
send
Tx Z1
send
Z2 Z2T 0 Z2
Z2T 0
Z3T 0 Z3
Z3 Z3T 0 ≥1 Trip Trip
≥1
Signal
receive & & Signal
receive
Rx Rx
Permissive Overreach Scheme (CB Echo Logic)
Z3
Z2
Z1
Z1
Z2
Z3
Z2 T2 . . T2 Z2
Z3 T3 T3 Z3
Permissive Overreach Scheme (WI Echo Logic)
Z4
Z2
Z1
Z1
Z2
Z4
Z2 T2 . . T2 Z2
Z3 T3 T3 Z3
POR – Current Reversal
H K
H1
K1
H2
K2
Weak source Strong source
Permissive signal
POR – Current Reversal
H K
H1
K1
H2
K2
Weak source Strong source
Permissive signal
POR – Current Reversal
H K
H1
K1
H2
K2
Weak source Strong source
1. The timer is used to block the permissive trip and signal send
POR- Current Reversal Guard
H K
H1 K1
H2 K2
Weak source Strong source
H K
H1 K1
H2 K2
H K
H1 K1
H2 K2
Weak source Strong source
H K
H1 K1
H2 K2
Weak source Strong source
Z3
Z2
Z1
Send Logic : Z3 + Z2
Z1 Trip Logic : Rx + Z2
Z2
Z3
& &
Rx Rx
Tx Tx
& &
Z1 1 Trip Trip 1 Z1
Z2 T2 . . T2 Z2
Z3 T3 T3 Z3
Blocking Scheme - External Fault
Z3
Z2
Z1
Send Logic : Z3 + Z2
Trip Logic : Rx + Z2
Z1
Z2
Z3
& &
Rx Rx
Tx Tx
& &
Z1 1 Trip Trip 1 Z1
Z2 T2 . . T2 Z2
Z3 T3 T3 Z3
Blocking Scheme - Advantages
X Fast tripping will still be possible at closed end of line for all
fault positions with remote breaker open
The effect of infeed between the relay and the fault location,
including the influence of different Z0/Z1 ratios of the various
sources.
Under / Over Reach Effect
Continued.
The effect of a load transfer between the ends of the protected line.
Especially when the fault resistance is appreciable; it must be
recognized.
ZA ZB
IA IA+IB
IB
Relay Location
IR = IA
IA
Relay experienced under reaching
Infeed Effect
Busbar Infeed between Relay and Fault
A I B
B
Zm0
IA
RELAY F
X Most of the multi circuit lines are double circuits that operates in
parallel.
Z0AB- Z0m
X Mutual coupling reduce distance reach at one end but the same time
proportionally increase at the opposite line end.
A Im B
A Im B A Z0AB- Z0m B
Z0m
Zm0
Z0AB- Z0m
IA
RELAY F
CT
275kV System
VT
8. Setting philosophy
1. Zone 1 = 80% of protected line.
2. Zone 2 =100% of protected line + 50% of shortest adjacent line.
3. Zone 3 = 100% of protected line + 120% of longest adjacent line.
4. Zone 3 Reverse = 20% of Zone 1
9. Protected line will experience additional 50% load current over its
rated current during adverse system conditions with 5% system
voltage drop.
Calculation Example
– Mho Z1 & Z2 and Offset Mho Z3.
1. Calculate the secondary impedance factor.
2. Calculate the Zero Sequence Compensation factor KN for earth fault
element.
3. Calculate the relay Zone reach setting to apply on the relay.
i. Zone 1
ii. Zone 2
iii. Zone 3
iv. Zone 3Reverse
4. Calculate relay characteristic angle for
i. Phase-phase distance element
ii. Phase-earth distance element
5. Plot the relay characteristic using positive sequence impedance
diagram.
6. Calculate minimum load impedance.
Calculation Example
– Mho Z1 & Z2 and Offset Mho Z3.
1. Calculate the secondary impedance factor.
C.T. RATIO
S.I.F. =
V.T. RATIO
600/1
S.I.F. =
275kV/110V
S.I.F. = 0.24
So
Line +ve seq. impedance (secondary), ZL1 = (0.02136 + j 0.07776) ohm/km
= 0.0806∠74.64˚
Line zero seq. impedance, ZL0 = (0.04896 + j 0.20112) ohm/km
= 0.207∠76.32˚(secondary)
2. Calculate the Zero Sequence Compensation factor KN for earth fault
element.
1 Z0 – 1
KN =
3 Z1
KN = 0.523∠2.75˚
Calculation Example
– Mho Z1 & Z2 and Offset Mho Z3.
3. Calculate the relay Zone reach setting to apply on the relay (secondary)
i. Zone 1 = 80% of protected line.
= 0.8 x 50 x 0.0806
= 3.224 Ω
= 0.2 x 3.224
= 0.6448 Ω
Calculation Example
– Mho Z1 & Z2 and Offset Mho Z3.
4. i. Phase-phase distance element
∠Ø-Ø = 74.64˚
∠Ø-E = 77.34˚
Calculation Example
– Mho Z1 & Z2 and Offset Mho Z3.
= 167.59Ω primary
= 40.22Ω secondary
Quadrilateral Distance
Characteristic Setting Example
Calculation Example
– Numerical relay with Quadrilateral Characteristic .
CT
275kV System
VT
8. Setting philosophy
1. Zone 1 = 80% of protected line.
2. Zone 2 =100% of protected line + 50% of shortest adjacent line.
3. Zone 3 = 100% of protected line + 120% of longest adjacent line.
4. Zone 3 Reverse = 20% of Zone 1
600/1
S.I.F. =
275kV/110V
S.I.F. = 0.24
So
Line +ve seq. impedance, ZL1 = (0.02136 + j 0.07776) ohm/km
= 0.0806∠74.64˚ (secondary)
Line zero seq. impedance, ZL0 = (0.04896 + j 0.20112) ohm/km
= 0.207∠76.32˚(secondary)
Earth Impedance Ratio
XE 1 ⎛ X0 ⎞
= ⋅ ⎜⎜ − 1⎟⎟
X L 3 ⎝ X1 ⎠
1 ⎛ 0.20112 ⎞
= ⋅⎜ − 1⎟
3 ⎝ 0.07776 ⎠
= 0.5288Ω
Calculation Example
– Numerical relay with Quadrilateral Characteristic .
X1 = 3.1088 Ω
X3 = 12.287 Ω
X3R = 0.6218
Phase-phase Resistive Reach Setting
Phase-phase Rarc
Phase-earth Rarc
28710 28710
Rarc = 1.4
⋅7 RarcE = 1.4
⋅4
2099 2099
= 4.489Ω = 2.6Ω
≈ 5.0Ω
Phase-phase Resistive Reach Setting
1
RF 2 = R2 Line + ⋅ Rarc
2
1
= 2.0282 + ⋅ 5.0
2
= 4.5282Ω
Phase-phase Resistive Reach Setting
1
RF 3 = R3 Line + ⋅ Rarc
2
1
= 3.3475 + ⋅ 5.0
2
= 5.8475Ω
1
RF 3 R = R3 RLine + ⋅ Rarc
2
1
= 0.1708 + ⋅ 5.0
2
= 2.6708Ω
Phase-earth Resistive Reach Setting
Distance Relay
CT
To relay
Terminal Block
VT MCB
VT
+ +
From VT
Voltage Supervision
X –ve seq. and zero seq. setting must always be set with a safety
margin of 10 to 20%, depending on the system operating conditions.
CT CT
VT VT
21Z 21Z
SOTF
ON
ND- Zone &
R
Requirement on Power Swing Blocking
X (1) A short-circuit, the impedance vector abruptly changes from the load
condition into this fault detection range.
X (2) A power swing, the apparent impedance vector initially enters the outer
characteristic of power swing and only later enters the fault detection range.
X (3) It is also possible that a power swing vector will enter the area of the
power swing range and leave it again without coming into contact with the
fault detection range
X (4) If the vector enters and passes through and leaving on the opposite side
of the power swing characteristic, then the sections of the network seen from
the relay location have lost synchronism
Power Swing Vector
with Quad Distance Characteristic
X PS outer zone
ΔZ
PS inner zone
Zone 3
FD
Zone 2 4
ΔZ 3
Zone 1
2
1
R
Load Impedance
Load Impedance
Area Zone 4
ΔZ Area
ΔZ
Power Swing Vector
with MHO Distance Characteristic
jX PS Outer Zone
PS Inner Zone
Z3
4
Z2
3
Z1
2
1
ΔZ
Load Impedance
R Load Impedance
Area
Area
Power Swing with Fault Condition